Amvic ICF Installation Manual
Amvic ICF Installation Manual
Preface ............................................................................................................................................................................
Technical Support...........................................................................................................................................................
Amvic Website................................................................................................................................................................
Acknowledgment............................................................................................................................................................
Disclaimer.......................................................................................................................................................................
Copyright.........................................................................................................................................................................
Part 1 - Introduction..................................................................................................................................................... 8
Preface
Amvic ICF are the best insulated concrete forms available on the market today. Competitive pricing, extensive
product distribution and excellent technical support are combined to provide our clients with a simplified approach
to a superior finished product at an installation cost less than any other comparable systems.
If any of your questions or concerns are not completely addressed in this manual, please attend one of Amvic’s
training seminars (check your local area for schedule) or feel free to contact us and our staff will be happy to answer
your questions. At Amvic, we pride ourselves in offering our customers an exceptional level of customer service.
Technical Support
Please contact us for any inquiries pertaining to information included in this manual or if you require other technical
assistance.
Phone: 1 (877) 470-9991 (toll free)
Email: [email protected]
Amvic Website
The Amvic website is updated regularly with the most updated information including, product data sheets,
construction details and installation manuals. This technical and installation manual is posted on the website, see
www.amvicsystem.com
Acknowledgment
Amvic would like to thank all those who participated in the original compilation of this manual. Special thanks to:
• Bill Juhl
• Bob Barker
• John and Kathy Krzic
• Rory and Tonia Ahern
• Joe Wallace
• Lindsey McLeod
• Steve Rentz
• Norman Williams
• Gary Brown
Disclaimer
This document is provided for informational purposes only. The information contained in this document represents
the current view of Amvic Corporation on the issues discussed as of the date of publication. These opinions as
expressed, should not be interpreted to be a commitment on the part of Amvic Corporation and cannot guarantee
the accuracy of any information presented after the date of publication. The user assumes the entire risk as to the
accuracy and use of this document.
This manual is intended to supplement rather than replace the basic construction knowledge of the construction
professional. All structures built with the Amvic Building System must be designed and erected in accordance with all
applicable building codes and/or guidance of a licensed professional engineer. In all cases, applicable building code
regulations take precedence over this manual.
INFORMATION CONTAINED IN THIS DOCUMENT IS PROVIDED “AS IS” WITHOUT ANY WARRANTY OF ANY KIND,
EITHER EXPRESSED OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY,
FITNESS FOR A PARTICULAR PURPOSE AND FREEDOM OF INFRINGEMENT.
Copyright
This document may not be copied or reproduced in any form without the written consent of Amvic Corporation
Copyright© 2019 Amvic Corporation
PART 1 INTRODUCTION
Figure 1 – Amvic ICF products Figure 2 – Typical Amvic reversible ICF straight block
The webs used in Amvic ICF greatly reduce the need for rebar tie downs while placing rebar most effectively to
ensure superior structural strength. The webs are manufactured using more raw material than competing products
allowing for superior finishing capabilities and 198lbs (90kg) pull out strength for drywall screws. Webs are spaced 6”
(152mm) on center for the Amvic R22 block or 8” (203mm) on center for the Amvic R30 resulting in greater rigidity,
which keeps the wall straight and plumb during stacking and pouring of the concrete.
8
PART 1 INTRODUCTION
Amvic webs connect the EPS panels and terminate with a 1-1/2” (38mm) flange which is embedded 1/2” (13mm)
beneath the outside surface of the panels. The flange has a height of 15” (381mm) in all blocks except the 10”
(254mm) and 12” (305mm) block which has a flange height of 22” (559mm). When the blocks are stacked, the
flanges form a continuous horizontal and vertical grid which is used to attach interior finishes like gypsum board
(drywall) and exterior finishes like stucco, wood siding and brick veneer ties.
6" 1"
34
1"
34
WEB
1"
22
6"
1"
22
3" 6" 6" 6" 6" 6" 6" 6" 3"
48"
Figure 3 – Typical Amvic straight ICF blocks (R30 6” block at the top and R22 6”, bottom)
9
PART 1 INTRODUCTION
Amvic ICF blocks use the FormLock™ interlocking system developed by Amvic, which has considerably deeper
grooves than competing products. The interlock exists on all long edges allowing the blocks to be fully reversible.
They also secure the courses together, preventing any movement or leakage during the concrete pour. This unique
feature allows Amvic ICF to be stacked quickly, easily and little need for glue or ties. Amvic’s user friendly, easy to
install system increases job site efficiency and worker productivity which saves time and money.
1"
12 8"
15" 16"
1"
12 6"
Figure 4 – Side view of Amvic ICF straight block showing web flanges
10
PART 1 INTRODUCTION
INTEGRATED REBAR
PLACEMENT AND
HOLDING SLOTS IN
WEBS
6" 1"
34 8" 1"
34
4" 1"
22 6" 1"
22 8" 1"
22
INTEGRATED REBAR
PLACEMENT AND
HOLDING SLOTS IN
WEBS
10" 1"
22 12" 1"
22
11
PART 1 INTRODUCTION
8"
FORM LOCKä
INTERLOCKING INTEGRATED
SYSTEM DRAINAGE CHANNELS
6"
Figure 6 – Interior view of ICF panel showing integrated drainage (R30 at the top, R22 bottom)
Amvic ICF R22 is available in a variety of sizes allowing for concrete cores of 4” (102mm), 6” (152mm), 8” (203mm),
10” (254mm) and 12” (305mm). Straight, 90° corner, 45° corner, taper top, brick ledge, T-block and radius blocks are
available in most core sizes. For Amvic ICF R30 straight, 90° corner, 45° corner, taper top and brick ledge blocks (only
in 6” (152mm)) are available in 6” (152mm) and 8” (203mm) core sizes.
12
PART 1 INTRODUCTION
R6"
6"
6" 1"
R34
6" 1"
R34
Figure 7 – Typical Amvic ICF corners. Short R22 corner (above), long R22 corner (middle) and R30 corner (bottom)
Amvic is the best ICF system available on the market today. Competitive pricing, extensive product distribution and
professional technical support are combined to provide customers with a superior product with an installation cost
less than comparable systems.
13
PART 2 PRODUCTS AND AVAILABILITY
All Amvic ICF blocks and accessories are packaged in bundles to achieve maximum space utilization during shipping,
refer to table below for details. Make sure to contact your local Amvic territory manager or distributor to discuss
stock availability of blocks, tools and accessories.
Number
Bundle Size Bundle Weight Blocks per
Amvic Code Item Description Bundles per
(L x W x H) in inches (Gross) In lbs Bundle
53ft Trailer
BLO0406 R22 4” Straight 55 x 48.5 x 49 125.5 18 814
BLO0407 R22 4” 90° Short Corner 52.5 x 43 x 49 90.00 24 1280
BLO0408 R22 4” 45° Short Corner 50 x 50 x 49 98.00 24 1179
BLO0606 R22 6” Straight 55 x 48.5 x 49 110.0 15 678
BLO0614L R22 6” 90° Long Corner 49 x 35 x 49 60.00 6 405
BLO0608 R22 6” 45° Short Corner 51.5 x 28.5 x 49 55.50 12 770
BLO0610 R22 6” Brick Ledge 49.5 x 48.5 x 49 76.75 9 455
BLO0611 R22 6” Double Taper Top 55 x 48.5 x 49 107.5 15 678
BLOT06S R22 6” Short T-Block
45 x 31 x 49 46.00 6 389
BLOT06L R22 6” Long T-Block
BLO0636 R30 6” Straight 50 x 48 x 49 87.00 12 590
BLO0637 R30 6” 90° Long Corner 44 x 40 x 49 58.00 6 400
BLO0638 R30 6” 45° Long Corner 53 x 35 x 49 55.50 6 374
BLO0639 R30 6” Brick Ledge 55 x 48 x 49 90.00 9 426
BLO0640 R30 6” Double Taper Top 50 x 48 x 49 84.00 12 590
BLO0806 R22 8” Straight 53.25 x 48 x 49 89.00 12 570
BLO0814L R22 8” 90° Long Corner 49 x 38 x 49.5 68.25 6 385
BLO0808 R22 8” 45° Short Corner 60 x 31 x 49 57.50 12 796
BLO0811 R22 8” Brick Ledge 54.5 x 48.5 x 49 78.75 9 407
BLO0812 R22 8” Double Taper Top 53 x 48.5 x 49 84.00 12 570
BLOT08S R22 8” Short T-Block
49 x 33 x 49 78.75 6 442
BLOT08L R22 8” Long T-Block
BLO0836 R30 8” Straight 60 x 49 x 49 88.00 12 519
BLO0837 R30 8” 90° Long Corner 46 x 46 x 49 60.00 6 351
BLO0838 R30 8” 45° Long Corner 53 x 35 x 49 55.50 6 354
BLO0839 R30 8” Double Taper Top 60 x 49 x 49 80.00 12 519
BLO0101 R22 10” Straight 45 x 48.5 x 48.5 56.00 6 319
BLO0102 R22 10” 90° Short Corner 43.5 x 34 x 49 43.00 4 313
BLO1201 R22 12” Straight 51 x 48.5 x 48.5 76.00 6 295
BLO1202 R22 12” 90° Short Corner 39 x 38 x 49 44.00 4 301
14
PART 3 ACCESSORIES AND TOOLS
Note: Keep spare a concrete pencil vibrator head and shaft on hand.
15
PART 4 10 STEP ICF CONSTRUCTION GUIDE
Step 1
Plan the outline of the blocks and the location of
door and window openings on a conventional footing
or a slab that is level, straight and square. Rebar
should extend upward at least 24” (610mm) from the
footing into the cavity of the block or as per structural
requirement.
Step 2
Place the first corner blocks at each corner, then lay
the straight blocks toward the center of each wall
segment. On the first course, use zip ties on the webs
to connect the blocks and pull them snugly together.
Following this, install horizontal rebar by placing it in
the clips at the top of the internal webs within the
block cavity. The clips hold the rebar securely and
eliminate the need for wire tying. (Repeat this process
for each course of block).
16
PART 4 10 STEP ICF CONSTRUCTION GUIDE
Step 3
Install the second course of blocks by reversing the
corner blocks, so that the second course of block is
offset from the first, in a running bond pattern. At this
point check for level across all of the blocks. If the
courses are not level, use shims or trim the block as
required.
Step 4
Install window and door frames (bucks) at each
location where an opening is required; cut and fit the
ICF blocks around them. Bucks are used to hold back
the concrete and stay in place permanently providing
a nailing surface for the installation of windows and
doors. Pressure-treated lumber or vinyl bucks may be
used.
17
PART 4 10 STEP ICF CONSTRUCTION GUIDE
Step 5
Install additional courses of block by continuing to
overlap the courses so that all joints are locked both
above and below by overlapping blocks.
Step 6
Install alignment bracing along the entire interior
(recommended) of the wall perimeter. This ensures
that the walls are straight and plumb and allow
alignment adjustment before and during the pour.
The bracing also serves the dual purpose of providing
a secure and safe framework to support scaffolding
planks once five courses have been stacked.
Figure 7 – Install alignment and bracing system around the interior of the
perimeter wall
18
PART 4 10 STEP ICF CONSTRUCTION GUIDE
Step 7
Stack the block to the full wall height for single story
construction, or to just above floor height for multi
story construction. Cut the vertical rebar to length
and begin installing it from the opening at the top of
the wall, through the spaces between the horizontal
rebar.
Step 8
Pour the concrete into the stacked walls using a
boom pump. Do this in layers approximately 3-4’
(0.9-1.2m) at a time, circling the structure until the
top of the wall is reached. Use a mechanical pencil
vibrator (stinger) to vibrate the concrete and remove
all air pockets within the wall. Up to one story can be
poured each day using this method.
19
PART 4 10 STEP ICF CONSTRUCTION GUIDE
Step 9
Screed off the concrete until it is even with the block
top and then “wet set” anchor bolts into the concrete
top. These bolts will be used later to install the top
plate (mud sill) for the installation of rafters or trusses.
Step 10
Remove bracing after the concrete has cured, then
proceed with further stages of construction.
Figure 11 - Once the concrete had time to cure, remove bracing if not
needed for following stages of construction
20
PART 5 FOOTINGS, SLABS AND COURSING
An Amvic ICF wall can be started from either a footing or a slab depending on the design and structural
requirements. There are benefits and drawbacks to both methods ultimately depending on the specific site
conditions.
OPTIONAL
METAL
TRACK
OPTIONAL
METAL
TRACK
21
PART 5 FOOTINGS, SLABS AND COURSING
Level Foundation
After pouring the footings and/or slab on grade, the
top finished surface should be level to within 1/4”
(6.35mm). This is commonly a local building code
requirement. A proper level footing will make installing
the first two courses of block significantly easier.
Level can be checked using a laser, transit or water level.
If the top surface is not within 1/4” (6.35mm) all the
way around, the ICF blocks will need to be adjusted at a
later time during installation. It is good practice to mark
the variance of each corner of the footing or slab.
Note: If the installation of the first story of Amvic ICF
will take a few days to complete, it is recommended to
protect the chalk line to avoid it being washed away by
rain or wind gusts.
22
PART 5 FOOTINGS, SLABS AND COURSING
23
PART 5 FOOTINGS, SLABS AND COURSING
ROUGH OPENING
ROUGH OPENING
ROUGH OPENING
ROUGH OPENING
ICF ICF ICF ICF
CUT CUT CUT CUT
LINE LINES LINE LINE
Figure 6 – Rough opening size depends on the type of bucking system used
Dowel Placement
When pouring footings or concrete slab, place reinforcing dowels as per engineer and/or local building code
requirements. For most walls, the dimension of the wall does not perfectly divide into an even number of blocks. In
order to keep the webs vertically aligned it is best to use a standing seam, see Part 9.12. Dowel placement should be
started at the corners and worked towards the center/cut joint. If the dowel comes up directly at a web location, the
bar can be bent in a slight S-curve to allow it to clear the web. See Part 5.1 for specific dowel placement and spacing
for all Amvic ICF block sizes
24
PART 5.1 COURSING AND DOWEL PLACEMENT
Table 1 ‐ Vertical coursing chart for Amvic R22 & R30 4" (102mm), 6" (152mm) & 8" (203mm) blocks
Table 1 ‐ Vertical coursing chart for Amvic R22 & R30 4" (102mm), 6" (152mm) & 8" (203mm) blocks
Plus 2" (51mm) Plus 3" (51mm) Plus 4" (51mm)
No. of Total Height Plus 2" (51mm) Plus 3" (51mm) Plus 4" (51mm)
No. of Total Height Height Adjuscter Height Adjuscter Height Adjuscter
Courses Height Adjuscter Height Adjuscter Height Adjuscter
Courses (in) (ft) (mm) (in) (ft) (mm) (in) (ft) (mm) (in) (ft) (mm)
(in) (ft) (mm) (in) (ft) (mm) (in) (ft) (mm) (in) (ft) (mm)
1 16 1' 4" 406 18 1' 6" 457 19 1' 7" 483 20 1' 8" 508
1 16 1' 4" 406 18 1' 6" 457 19 1' 7" 483 20 1' 8" 508
2 32 2' 8" 813 34 2' 10" 864 35 2' 11" 889 36 3' 0" 914
2 32 2' 8" 813 34 2' 10" 864 35 2' 11" 889 36 3' 0" 914
3 48 4' 0" 1219 50 4' 2" 1270 51 4' 3" 1295 52 4' 4" 1321
3 48 4' 0" 1219 50 4' 2" 1270 51 4' 3" 1295 52 4' 4" 1321
4 64 5' 4" 1626 66 5' 6" 1676 67 5' 7" 1702 68 5' 8" 1727
4 64 5' 4" 1626 66 5' 6" 1676 67 5' 7" 1702 68 5' 8" 1727
5 80 6' 8" 2032 82 6' 10" 2083 83 6' 11" 2108 84 7' 0" 2134
5 80 6' 8" 2032 82 6' 10" 2083 83 6' 11" 2108 84 7' 0" 2134
6 96 8' 0" 2438 98 8' 2" 2489 99 8' 3" 2515 100 8' 4" 2540
6 96 8' 0" 2438 98 8' 2" 2489 99 8' 3" 2515 100 8' 4" 2540
7 112 9' 4" 2845 114 9' 6" 2896 115 9' 7" 2921 116 9' 8" 2946
7 112 9' 4" 2845 114 9' 6" 2896 115 9' 7" 2921 116 9' 8" 2946
8 128 10' 8" 3251 130 10' 10" 3302 131 10' 11" 3327 132 11' 0" 3353
8 128 10' 8" 3251 130 10' 10" 3302 131 10' 11" 3327 132 11' 0" 3353
9 144 12' 0" 3658 146 12' 2" 3708 147 12' 3" 3734 148 12' 4" 3759
9 144 12' 0" 3658 146 12' 2" 3708 147 12' 3" 3734 148 12' 4" 3759
10 160 13' 4" 4064 162 13' 6" 4115 163 13' 7" 4140 164 13' 8" 4166
10 160 13' 4" 4064 162 13' 6" 4115 163 13' 7" 4140 164 13' 8" 4166
11 176 14' 8" 4470 178 14' 10" 4521 179 14' 11" 4547 180 15' 0" 4572
11 176 14' 8" 4470 178 14' 10" 4521 179 14' 11" 4547 180 15' 0" 4572
12 192 16' 0" 4877 194 16' 2" 4928 195 16' 3" 4953 196 16' 4" 4978
12 192 16' 0" 4877 194 16' 2" 4928 195 16' 3" 4953 196 16' 4" 4978
13 208 17' 4" 5283 210 17' 6" 5334 211 17' 7" 5359 212 17' 8" 5385
13 208 17' 4" 5283 210 17' 6" 5334 211 17' 7" 5359 212 17' 8" 5385
14 224 18' 8" 5690 226 18' 10" 5740 227 18' 11" 5766 228 19' 0" 5791
14 224 18' 8" 5690 226 18' 10" 5740 227 18' 11" 5766 228 19' 0" 5791
15 240 20' 0" 6096 242 20' 2" 6147 243 20' 3" 6172 244 20' 4" 6198
15 240 20' 0" 6096 242 20' 2" 6147 243 20' 3" 6172 244 20' 4" 6198
16 256 21' 4" 6502 258 21' 6" 6553 259 21' 7" 6579 260 21' 8" 6604
16 256 21' 4" 6502 258 21' 6" 6553 259 21' 7" 6579 260 21' 8" 6604
17 272 22' 8" 6909 274 22' 10" 6960 275 22' 11" 6985 276 23' 0" 7010
17 272 22' 8" 6909 274 22' 10" 6960 275 22' 11" 6985 276 23' 0" 7010
18 288 24' 0" 7315 290 24' 2" 7366 291 24' 3" 7391 292 24' 4" 7417
18 288 24' 0" 7315 290 24' 2" 7366 291 24' 3" 7391 292 24' 4" 7417
19 304 25' 4" 7722 306 25' 6" 7772 307 25' 7" 7798 308 25' 8" 7823
19 304 25' 4" 7722 306 25' 6" 7772 307 25' 7" 7798 308 25' 8" 7823
20 320 26' 8" 8128 322 26' 10" 8179 323 26' 11" 8204 324 27' 0" 8230
20 320 26' 8" 8128 322 26' 10" 8179 323 26' 11" 8204 324 27' 0" 8230
Table 2 ‐ Vertical coursing chart for Amvic R22 10" (254mm) and 12" (305mm) blocks
Table 2 ‐ Vertical coursing chart for Amvic R22 10" (254mm) and 12" (305mm) blocks
Plus 2" (51mm) Plus 3" (51mm) Plus 4" (51mm)
No. of Total Height Plus 2" (51mm) Plus 3" (51mm) Plus 4" (51mm)
No. of Total Height Height Adjuscter Height Adjuscter Height Adjuscter
Courses Height Adjuscter Height Adjuscter Height Adjuscter
Courses (in) (ft) (mm) (in) (ft) (mm) (in) (ft) (mm) (in) (ft) (mm)
(in) (ft) (mm) (in) (ft) (mm) (in) (ft) (mm) (in) (ft) (mm)
1 24 2' 0" 610 26 2' 2" 660 27 2' 3" 686 28 2' 4" 711
1 24 2' 0" 610 26 2' 2" 660 27 2' 3" 686 28 2' 4" 711
2 48 4' 0" 1219 50 4' 2" 1270 51 4' 3" 1295 52 4' 4" 1321
2 48 4' 0" 1219 50 4' 2" 1270 51 4' 3" 1295 52 4' 4" 1321
3 72 6' 0" 1829 74 6' 2" 1880 75 6' 3" 1905 76 6' 4" 1930
3 72 6' 0" 1829 74 6' 2" 1880 75 6' 3" 1905 76 6' 4" 1930
4 96 8' 0" 2438 98 8' 2" 2489 99 8' 3" 2515 100 8' 4" 2540
4 96 8' 0" 2438 98 8' 2" 2489 99 8' 3" 2515 100 8' 4" 2540
5 120 10' 0" 3048 122 10' 2" 3099 123 10' 3" 3124 124 10' 4" 3150
5 120 10' 0" 3048 122 10' 2" 3099 123 10' 3" 3124 124 10' 4" 3150
6 144 12' 0" 3658 146 12' 2" 3708 147 12' 3" 3734 148 12' 4" 3759
6 144 12' 0" 3658 146 12' 2" 3708 147 12' 3" 3734 148 12' 4" 3759
7 168 14' 0" 4267 170 14' 2" 4318 171 14' 3" 4343 172 14' 4" 4369
7 168 14' 0" 4267 170 14' 2" 4318 171 14' 3" 4343 172 14' 4" 4369
8 192 16' 0" 4877 194 16' 2" 4928 195 16' 3" 4953 196 16' 4" 4978
8 192 16' 0" 4877 194 16' 2" 4928 195 16' 3" 4953 196 16' 4" 4978
9 216 18' 0" 5486 218 18' 2" 5537 219 18' 3" 5563 220 18' 4" 5588
9 216 18' 0" 5486 218 18' 2" 5537 219 18' 3" 5563 220 18' 4" 5588
10 240 20' 0" 6096 242 20' 2" 6147 243 20' 3" 6172 244 20' 4" 6198
10 240 20' 0" 6096 242 20' 2" 6147 243 20' 3" 6172 244 20' 4" 6198
11 264 22' 0" 6706 266 22' 2" 6756 267 22' 3" 6782 268 22' 4" 6807
11 264 22' 0" 6706 266 22' 2" 6756 267 22' 3" 6782 268 22' 4" 6807
12 288 24' 0" 7315 290 24' 2" 7366 291 24' 3" 7391 292 24' 4" 7417
12 288 24' 0" 7315 290 24' 2" 7366 291 24' 3" 7391 292 24' 4" 7417
13 312 26' 0" 7925 314 26' 2" 7976 315 26' 3" 8001 316 26' 4" 8026
13 312 26' 0" 7925 314 26' 2" 7976 315 26' 3" 8001 316 26' 4" 8026
14 336 28' 0" 8534 338 28' 2" 8585 339 28' 3" 8611 340 28' 4" 8636
14 336 28' 0" 8534 338 28' 2" 8585 339 28' 3" 8611 340 28' 4" 8636
15 360 30' 0" 9144 362 30' 2" 9195 363 30' 3" 9220 364 30' 4" 9246
15 360 30' 0" 9144 362 30' 2" 9195 363 30' 3" 9220 364 30' 4" 9246
16 384 32' 0" 9754 386 32' 2" 9804 387 32' 3" 9830 388 32' 4" 9855
16 384 32' 0" 9754 386 32' 2" 9804 387 32' 3" 9830 388 32' 4" 9855
17 408 34' 0" 10363 410 34' 2" 10414 411 34' 3" 10439 412 34' 4" 10465
17 408 34' 0" 10363 410 34' 2" 10414 411 34' 3" 10439 412 34' 4" 10465
18 432 36' 0" 10973 434 36' 2" 11024 435 36' 3" 11049 436 36' 4" 11074
18 432 36' 0" 10973 434 36' 2" 11024 435 36' 3" 11049 436 36' 4" 11074
19 456 38' 0" 11582 458 38' 2" 11633 459 38' 3" 11659 460 38' 4" 11684
19 456 38' 0" 11582 458 38' 2" 11633 459 38' 3" 11659 460 38' 4" 11684
20 480 40' 0" 12192 482 40' 2" 12243 483 40' 3" 12268 484 40' 4" 12294
20 480 40' 0" 12192 482 40' 2" 12243 483 40' 3" 12268 484 40' 4" 12294
25
PART 5.1 COURSING AND DOWEL PLACEMENT
Table 3 ‐ Horizontal coursing chart for Amvic R22 4" (102mm) short 90° corner blocks
Inside ‐ Outside Outside ‐ Outside Inside ‐ Inside Inside ‐ Outside Outside ‐ Outside Inside ‐ Inside
[ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)]
1' 4" (406)(1) 2' 1" (635)(1) 0' 7" (178) (1) 13' 4" (4064)(1) 14' 1" (4293)(1) 12' 7" (3835)(1)
1' 10" (559)(2) 2' 7" (787)(2) 1' 1" (330) (2) 13' 10" (4216)(2) 14' 7" (4445)(2) 13' 1" (3988)(2)
2' 4" (711) 3' 1" (940) 1' 7" (483) 14' 4" (4369) 15' 1" (4597) 13' 7" (4140)
2' 10" (864) 3' 7" (1092) 2' 1" (635) 14' 10" (4521) 15' 7" (4750) 14' 1" (4293)
3' 4" (1016) 4' 1" (1245) 2' 7" (787) 15' 4" (4674) 16' 1" (4902) 14' 7" (4445)
3' 10" (1168) 4' 7" (1397) 3' 1" (940) 15' 10" (4826) 16' 7" (5055) 15' 1" (4597)
4' 4" (1321) 5' 1" (1549) 3' 7" (1092) 16' 4" (4978) 17' 1" (5207) 15' 7" (4750)
4' 10" (1473) 5' 7" (1702) 4' 1" (1245) 16' 10" (5131) 17' 7" (5359) 16' 1" (4902)
5' 4" (1626) 6' 1" (1854) 4' 7" (1397) 17' 4" (5283) 18' 1" (5512) 16' 7" (5055)
5' 10" (1778) 6' 7" (2007) 5' 1" (1549) 17' 10" (5436) 18' 7" (5664) 17' 1" (5207)
6' 4" (1930) 7' 1" (2159) 5' 7" (1702) 18' 4" (5588) 19' 1" (5817) 17' 7" (5359)
6' 10" (2083) 7' 7" (2311) 6' 1" (1854) 18' 10" (5740) 19' 7" (5969) 18' 1" (5512)
7' 4" (2235) 8' 1" (2464) 6' 7" (2007) 19' 4" (5893) 20' 1" (6121) 18' 7" (5664)
7' 10" (2388) 8' 7" (2616) 7' 1" (2159) 19' 10" (6045) 20' 7" (6274) 19' 1" (5817)
8' 4" (2540) 9' 1" (2769) 7' 7" (2311) 20' 4" (6198) 21' 1" (6426) 19' 7" (5969)
8' 10" (2692) 9' 7" (2921) 8' 1" (2464) 20' 10" (6350) 21' 7" (6579) 20' 1" (6121)
9' 4" (2845) 10' 1" (3073) 8' 7" (2616) 21' 4" (6502) 22' 1" (6731) 20' 7" (6274)
9' 10" (2997) 10' 7" (3226) 9' 1" (2769) 21' 10" (6655) 22' 7" (6883) 21' 1" (6426)
10' 4" (3150) 11' 1" (3378) 9' 7" (2921) 22' 4" (6807) 23' 1" (7036) 21' 7" (6579)
10' 10" (3302) 11' 7" (3531) 10' 1" (3073) 22' 10" (6960) 23' 7" (7188) 22' 1" (6731)
11' 4" (3454) 12' 1" (3683) 10' 7" (3226) 23' 4" (7112) 24' 1" (7341) 22' 7" (6883)
11' 10" (3607) 12' 7" (3835) 11' 1" (3378) 23' 10" (7264) 24' 7" (7493) 23' 1" (7036)
12' 4" (3759) 13' 1" (3988) 11' 7" (3531) 24' 4" (7417) 25' 1" (7645) 23' 7" (7188)
12' 10" (3912) 13' 7" (4140) 12' 1" (3683) 24' 10" (7569) 25' 7" (7798) 24' 1" (7341)
(1) Minimum dimension required for a short corner with a stack joint
(2) Minimum dimension required for a short corner with a running bond pattern
(3) Bold dimensions indicate the use of full size Amvic blocks with no cutting required
INSIDE - INSIDE
1"
182
5" 5" 6"
INCREMENTS 1" 1"
22 22
INSIDE - OUTSIDE
OF 6"
1"
182
26
PART 5.1 COURSING AND DOWEL PLACEMENT
Table 4 ‐ Horizontal coursing chart for Amvic R22 4" (102mm) 45° corner blocks
21" 1"
C
22
R
INSIDE - INSIDE
EM
9" 6"
EN
4" 4"
TS
1"
O
15" 1" 22
F
54
6"
15" 4"
1"
174
RECOMMENDED
C C DOWEL
PLACEMENT
1"
54 1741"
OUTSIDE - OUTSIDE
27
PART 5.1 COURSING AND DOWEL PLACEMENT
Table 6 ‐ Horizontal coursing chart for Amvic R22 6" (152mm) long 90° corner blocks
Inside ‐ Outside Outside ‐ Outside Inside ‐ Inside Inside ‐ Outside Outside ‐ Outside Inside ‐ Inside
[ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)]
(1) (1) (1) (1) (1) (1)
2' 1" (635) 3' 0" (914) 1' 2" (356) 14' 1" (4293) 15' 0" (4572) 13' 2" (4013)
(2) (2) (2) (2) (2) (2)
2' 7" (787) 3' 6" (1067) 1' 8" (508) 14' 7" (4445) 15' 6" (4724) 13' 8" (4166)
3' 1" (940) 4' 0" (1219) 2' 2" (660) 15' 1" (4597) 16' 0" (4877) 14' 2" (4318)
3' 7" (1092) 4' 6" (1372) 2' 8" (813) 15' 7" (4750) 16' 6" (5029) 14' 8" (4470)
4' 1" (1245) 5' 0" (1524) 3' 2" (965) 16' 1" (4902) 17' 0" (5182) 15' 2" (4623)
4' 7" (1397) 5' 6" (1676) 3' 8" (1118) 16' 7" (5055) 17' 6" (5334) 15' 8" (4775)
5' 1" (1549) 6' 0" (1829) 4' 2" (1270) 17' 1" (5207) 18' 0" (5486) 16' 2" (4928)
5' 7" (1702) 6' 6" (1981) 4' 8" (1422) 17' 7" (5359) 18' 6" (5639) 16' 8" (5080)
6' 1" (1854) 7' 0" (2134) 5' 2" (1575) 18' 1" (5512) 19' 0" (5791) 17' 2" (5232)
6' 7" (2007) 7' 6" (2286) 5' 8" (1727) 18' 7" (5664) 19' 6" (5944) 17' 8" (5385)
7' 1" (2159) 8' 0" (2438) 6' 2" (1880) 19' 1" (5817) 20' 0" (6096) 18' 2" (5537)
7' 7" (2311) 8' 6" (2591) 6' 8" (2032) 19' 7" (5969) 20' 6" (6248) 18' 8" (5690)
8' 1" (2464) 9' 0" (2743) 7' 2" (2184) 20' 1" (6121) 21' 0" (6401) 19' 2" (5842)
8' 7" (2616) 9' 6" (2896) 7' 8" (2337) 20' 7" (6274) 21' 6" (6553) 19' 8" (5994)
9' 1" (2769) 10' 0" (3048) 8' 2" (2489) 21' 1" (6426) 22' 0" (6706) 20' 2" (6147)
9' 7" (2921) 10' 6" (3200) 8' 8" (2642) 21' 7" (6579) 22' 6" (6858) 20' 8" (6299)
10' 1" (3073) 11' 0" (3353) 9' 2" (2794) 22' 1" (6731) 23' 0" (7010) 21' 2" (6452)
10' 7" (3226) 11' 6" (3505) 9' 8" (2946) 22' 7" (6883) 23' 6" (7163) 21' 8" (6604)
11' 1" (3378) 12' 0" (3658) 10' 2" (3099) 23' 1" (7036) 24' 0" (7315) 22' 2" (6756)
11' 7" (3531) 12' 6" (3810) 10' 8" (3251) 23' 7" (7188) 24' 6" (7468) 22' 8" (6909)
12' 1" (3683) 13' 0" (3962) 11' 2" (3404) 24' 1" (7341) 25' 0" (7620) 23' 2" (7061)
12' 7" (3835) 13' 6" (4115) 11' 8" (3556) 24' 7" (7493) 25' 6" (7772) 23' 8" (7214)
13' 1" (3988) 14' 0" (4267) 12' 2" (3708) 25' 1" (7645) 26' 0" (7925) 24' 2" (7366)
13' 7" (4140) 14' 6" (4420) 12' 8" (3861) 25' 7" (7798) 26' 6" (8077) 24' 8" (7518)
(1) Minimum dimension required for a short corner with a stack joint
(2) Minimum dimension required for a short corner with a running bond pattern
(3) Bold dimensions indicate the use of full size Amvic blocks with no cutting required
18"
1"
52 INCREMENTS OF 6"
1"
52 6"
18"
1"
22 1"
22
INSIDE - OUTSIDE
37"
48"
INSIDE - INSIDE RECOMMENDED 13"
DOWEL
PLACEMENT 6"
28
PART 5.1 COURSING AND DOWEL PLACEMENT
Table 7 ‐ Horizontal coursing chart for Amvic R22 6" (152mm) 45° corner blocks
1"
214 1"
22
IN
1"
94
C
INSIDE - INSIDE
R
6"
EM
6"
EN
1"
42 1"
TS
1" 1" 22
11"
O
42 154 416
F
6"
11"
1616
1"
154
RECOMMENDED
C DOWEL
C
PLACEMENT
11"
416 11"
1616
OUTSIDE - OUTSIDE
29
PART 5.1 COURSING AND DOWEL PLACEMENT
Table 8 ‐ Horizontal coursing chart for Amvic R30 6" (152mm) long 90° corner blocks
Inside ‐ Outside Outside ‐ Outside Inside ‐ Inside Inside ‐ Outside Outside ‐ Outside Inside ‐ Inside
[ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)]
2' 1‐1/2" (648) (1) 3' 2" (965) (1) 1' 1" (330) (1) 18' 1‐1/2" (5525)(1) 19' 2" (5842) (1) 17' 1" (5207) (1)
2' 9‐1/2" (851) (2) 3' 10" (1168) (2) 1' 9" (533) (2) 18' 9‐1/2" (5728)(2) 19' 10" (6045) (2) 17' 9" (5410) (2)
3' 5‐1/2" (1054) 4' 6" (1372) 2' 5" (737) 19' 5‐1/2" (5931) 20' 6" (6248) 18' 5" (5613)
4' 1‐1/2" (1257) 5' 2" (1575) 3' 1" (940) 20' 1‐1/2" (6134) 21' 2" (6452) 19' 1" (5817)
4' 9‐1/2" (1461) 5' 10" (1778) 3' 9" (1143) 20' 9‐1/2" (6337) 21' 10" (6655) 19' 9" (6020)
5' 5‐1/2" (1664) 6' 6" (1981) 4' 5" (1346) 21' 5‐1/2" (6541) 22' 6" (6858) 20' 5" (6223)
6' 1‐1/2" (1867) 7' 2" (2184) 5' 1" (1549) 22' 1‐1/2" (6744) 23' 2" (7061) 21' 1" (6426)
6' 9‐1/2" (2070) 7' 10" (2388) 5' 9" (1753) 22' 9‐1/2" (6947) 23' 10" (7264) 21' 9" (6629)
7' 5‐1/2" (2273) 8' 6" (2591) 6' 5" (1956) 23' 5‐1/2" (7150) 24' 6" (7468) 22' 5" (6833)
8' 1‐1/2" (2477) 9' 2" (2794) 7' 1" (2159) 24' 1‐1/2" (7353) 25' 2" (7671) 23' 1" (7036)
8' 9‐1/2" (2680) 9' 10" (2997) 7' 9" (2362) 24' 9‐1/2" (7557) 25' 10" (7874) 23' 9" (7239)
9' 5‐1/2" (2883) 10' 6" (3200) 8' 5" (2565) 25' 5‐1/2" (7760) 26' 6" (8077) 24' 5" (7442)
10' 1‐1/2" (3086) 11' 2" (3404) 9' 1" (2769) 26' 1‐1/2" (7963) 27' 2" (8280) 25' 1" (7645)
10' 9‐1/2" (3289) 11' 10" (3607) 9' 9" (2972) 26' 9‐1/2" (8166) 27' 10" (8484) 25' 9" (7849)
11' 5‐1/2" (3493) 12' 6" (3810) 10' 5" (3175) 27' 5‐1/2" (8369) 28' 6" (8687) 26' 5" (8052)
12' 1‐1/2" (3696) 13' 2" (4013) 11' 1" (3378) 28' 1‐1/2" (8573) 29' 2" (8890) 27' 1" (8255)
12' 9‐1/2" (3899) 13' 10" (4216) 11' 9" (3581) 28' 9‐1/2" (8776) 29' 10" (9093) 27' 9" (8458)
13' 5‐1/2" (4102) 14' 6" (4420) 12' 5" (3785) 29' 5‐1/2" (8979) 30' 6" (9296) 28' 5" (8661)
14' 1‐1/2" (4305) 15' 2" (4623) 13' 1" (3988) 30' 1‐1/2" (9182) 31' 2" (9500) 29' 1" (8865)
14' 9‐1/2" (4509) 15' 10" (4826) 13' 9" (4191) 30' 9‐1/2" (9385) 31' 10" (9703) 29' 9" (9068)
15' 5‐1/2" (4712) 16' 6" (5029) 14' 5" (4394) 31' 5‐1/2" (9589) 32' 6" (9906) 30' 5" (9271)
16' 1‐1/2" (4915) 17' 2" (5232) 15' 1" (4597) 32' 1‐1/2" (9792) 33' 2" (10109) 31' 1" (9474)
16' 9‐1/2" (5118) 17' 10" (5436) 15' 9" (4801) 32' 9‐1/2" (9995) 33' 10" (10312) 31' 9" (9677)
17' 5‐1/2" (5321) 18' 6" (5639) 16' 5" (5004) 33' 5‐1/2" (10198) 34' 6" (10516) 32' 5" (9881)
(1) Minimum dimension required for a short corner with a stack joint
(2) Minimum dimension required for a short corner with a running bond pattern
(3) Bold dimensions indicate the use of full size Amvic blocks with no cutting required
19"
1"
64 INCREMENTS OF 8"
1"
64
19" 6"
1"
34 1"
34
INSIDE - OUTSIDE
1"
302
RECOMMENDED 43" 1"
INSIDE - INSIDE DOWEL 142
PLACEMENT
8"
30
PART 5.1 COURSING AND DOWEL PLACEMENT
Table 9 ‐ Horizontal coursing chart for Amvic R30 6" (152mm) 45° corner blocks
36" 1"
34
20" 1"
IN
8" 34
C
R
EM
13" 20"
EN
6" 1416
1"
TS
13" 20" 54
O
3016 1"
F
54
8"
RECOMMENDED
DOWEL PLACEMENT
INSIDE - INSIDE
C C
13"
1416 OUTSIDE - OUTSIDE 3013
16"
31
PART 5.1 COURSING AND DOWEL PLACEMENT
Table 11 ‐ Horizontal coursing chart for Amvic R22 8" (203mm) long 90° corner blocks
Inside ‐ Outside Outside ‐ Outside Inside ‐ Inside Inside ‐ Outside Outside ‐ Outside Inside ‐ Inside
[ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)]
1' 11" (584) (1) 3' 0" (914) (1) 0' 10" (254) (1) 13' 11" (4242)(1) 15' 0" (4572) (1) 12' 10" (3912) (1)
2' 5" (737) (2) 3' 6" (1067) (2) 1' 4" (406) (2) 14' 5" (4394)(2) 15' 6" (4724) (2) 13' 4" (4064) (2)
2' 11" (889) 4' 0" (1219) 1' 10" (559) 14' 11" (4547) 16' 0" (4877) 13' 10" (4216)
3' 5" (1041) 4' 6" (1372) 2' 4" (711) 15' 5" (4699) 16' 6" (5029) 14' 4" (4369)
3' 11" (1194) 5' 0" (1524) 2' 10" (864) 15' 11" (4851) 17' 0" (5182) 14' 10" (4521)
4' 5" (1346) 5' 6" (1676) 3' 4" (1016) 16' 5" (5004) 17' 6" (5334) 15' 4" (4674)
4' 11" (1499) 6' 0" (1829) 3' 10" (1168) 16' 11" (5156) 18' 0" (5486) 15' 10" (4826)
5' 5" (1651) 6' 6" (1981) 4' 4" (1321) 17' 5" (5309) 18' 6" (5639) 16' 4" (4978)
5' 11" (1803) 7' 0" (2134) 4' 10" (1473) 17' 11" (5461) 19' 0" (5791) 16' 10" (5131)
6' 5" (1956) 7' 6" (2286) 5' 4" (1626) 18' 5" (5613) 19' 6" (5944) 17' 4" (5283)
6' 11" (2108) 8' 0" (2438) 5' 10" (1778) 18' 11" (5766) 20' 0" (6096) 17' 10" (5436)
7' 5" (2261) 8' 6" (2591) 6' 4" (1930) 19' 5" (5918) 20' 6" (6248) 18' 4" (5588)
7' 11" (2413) 9' 0" (2743) 6' 10" (2083) 19' 11" (6071) 21' 0" (6401) 18' 10" (5740)
8' 5" (2565) 9' 6" (2896) 7' 4" (2235) 20' 5" (6223) 21' 6" (6553) 19' 4" (5893)
8' 11" (2718) 10' 0" (3048) 7' 10" (2388) 20' 11" (6375) 22' 0" (6706) 19' 10" (6045)
9' 5" (2870) 10' 6" (3200) 8' 4" (2540) 21' 5" (6528) 22' 6" (6858) 20' 4" (6198)
9' 11" (3023) 11' 0" (3353) 8' 10" (2692) 21' 11" (6680) 23' 0" (7010) 20' 10" (6350)
10' 5" (3175) 11' 6" (3505) 9' 4" (2845) 22' 5" (6833) 23' 6" (7163) 21' 4" (6502)
10' 11" (3327) 12' 0" (3658) 9' 10" (2997) 22' 11" (6985) 24' 0" (7315) 21' 10" (6655)
11' 5" (3480) 12' 6" (3810) 10' 4" (3150) 23' 5" (7137) 24' 6" (7468) 22' 4" (6807)
11' 11" (3632) 13' 0" (3962) 10' 10" (3302) 23' 11" (7290) 25' 0" (7620) 22' 10" (6960)
12' 5" (3785) 13' 6" (4115) 11' 4" (3454) 24' 5" (7442) 25' 6" (7772) 23' 4" (7112)
12' 11" (3937) 14' 0" (4267) 11' 10" (3607) 24' 11" (7595) 26' 0" (7925) 23' 10" (7264)
13' 5" (4089) 14' 6" (4420) 12' 4" (3759) 25' 5" (7747) 26' 6" (8077) 24' 4" (7417)
(1) Minimum dimension required for a short corner with a stack joint
(2) Minimum dimension required for a short corner with a running bond pattern
(3) Bold dimensions indicate the use of full size Amvic blocks with no cutting required
18"
1"
62 INCREMENTS OF 6"
1"
62
18" 8"
1"
22 1"
22
INSIDE - OUTSIDE
RECOMMENDED 35"
DOWEL 48"
INSIDE - INSIDE PLACEMENT 11"
6"
32
PART 5.1 COURSING AND DOWEL PLACEMENT
Table 12 ‐ Horizontal coursing chart for Amvic R22 8" (203mm) short 45° corner blocks
1' 8‐5/8" (524)(2) 2' 2" (660) (2) 1' 3‐1/4" (387) (2)
22" 1"
22
IN
C INSIDE - INSIDE
R 10" 6"
EM
EN 8"
TS 16" 1"
22
O
F
6" 16" 5" 45
8" 5"
168
5"
RECOMMENDED
DOWEL
C C PLACEMENT
45
8" 1658"
OUTSIDE - OUTSIDE
33
PART 5.1 COURSING AND DOWEL PLACEMENT
Table 13 ‐ Horizontal coursing chart for Amvic R30 8" (203mm) long 90° corner blocks
Inside ‐ Outside Outside ‐ Outside Inside ‐ Inside Inside ‐ Outside Outside ‐ Outside Inside ‐ Inside
[ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)]
2' 3‐1/2" (699)(1) 3' 6" (1067) (1) 1' 1" (330) (1) 18' 3‐1/2" (5575) (1) 19' 6" (5944) (1) 17' 1" (5207) (1)
2' 11‐1/2" (902)(2) 4' 2" (1270) (2) 1' 9" (533) (2) 18' 11‐1/2" (5779) (2) 20' 2" (6147) (2) 17' 9" (5410) (2)
3' 7‐1/2" (1105) 4' 10" (1473) 2' 5" (737) 19' 7‐1/2" (5982) 20' 10" (6350) 18' 5" (5613)
4' 3‐1/2" (1308) 5' 6" (1676) 3' 1" (940) 20' 3‐1/2" (6185) 21' 6" (6553) 19' 1" (5817)
4' 11‐1/2" (1511) 6' 2" (1880) 3' 9" (1143) 20' 11‐1/2" (6388) 22' 2" (6756) 19' 9" (6020)
5' 7‐1/2" (1715) 6' 10" (2083) 4' 5" (1346) 21' 7‐1/2" (6591) 22' 10" (6960) 20' 5" (6223)
6' 3‐1/2" (1918) 7' 6" (2286) 5' 1" (1549) 22' 3‐1/2" (6795) 23' 6" (7163) 21' 1" (6426)
6' 11‐1/2" (2121) 8' 2" (2489) 5' 9" (1753) 22' 11‐1/2" (6998) 24' 2" (7366) 21' 9" (6629)
7' 7‐1/2" (2324) 8' 10" (2692) 6' 5" (1956) 23' 7‐1/2" (7201) 24' 10" (7569) 22' 5" (6833)
8' 3‐1/2" (2527) 9' 6" (2896) 7' 1" (2159) 24' 3‐1/2" (7404) 25' 6" (7772) 23' 1" (7036)
8' 11‐1/2" (2731) 10' 2" (3099) 7' 9" (2362) 24' 11‐1/2" (7607) 26' 2" (7976) 23' 9" (7239)
9' 7‐1/2" (2934) 10' 10" (3302) 8' 5" (2565) 25' 7‐1/2" (7811) 26' 10" (8179) 24' 5" (7442)
10' 3‐1/2" (3137) 11' 6" (3505) 9' 1" (2769) 26' 3‐1/2" (8014) 27' 6" (8382) 25' 1" (7645)
10' 11‐1/2" (3340) 12' 2" (3708) 9' 9" (2972) 26' 11‐1/2" (8217) 28' 2" (8585) 25' 9" (7849)
11' 7‐1/2" (3543) 12' 10" (3912) 10' 5" (3175) 27' 7‐1/2" (8420) 28' 10" (8788) 26' 5" (8052)
12' 3‐1/2" (3747) 13' 6" (4115) 11' 1" (3378) 28' 3‐1/2" (8623) 29' 6" (8992) 27' 1" (8255)
12' 11‐1/2" (3950) 14' 2" (4318) 11' 9" (3581) 28' 11‐1/2" (8827) 30' 2" (9195) 27' 9" (8458)
13' 7‐1/2" (4153) 14' 10" (4521) 12' 5" (3785) 29' 7‐1/2" (9030) 30' 10" (9398) 28' 5" (8661)
14' 3‐1/2" (4356) 15' 6" (4724) 13' 1" (3988) 30' 3‐1/2" (9233) 31' 6" (9601) 29' 1" (8865)
14' 11‐1/2" (4559) 16' 2" (4928) 13' 9" (4191) 30' 11‐1/2" (9436) 32' 2" (9804) 29' 9" (9068)
15' 7‐1/2" (4763) 16' 10" (5131) 14' 5" (4394) 31' 7‐1/2" (9639) 32' 10" (10008) 30' 5" (9271)
16' 3‐1/2" (4966) 17' 6" (5334) 15' 1" (4597) 32' 3‐1/2" (9843) 33' 6" (10211) 31' 1" (9474)
16' 11‐1/2" (5169) 18' 2" (5537) 15' 9" (4801) 32' 11‐1/2" (10046) 34' 2" (10414) 31' 9" (9677)
17' 7‐1/2" (5372) 18' 10" (5740) 16' 5" (5004) 33' 7‐1/2" (10249) 34' 10" (10617) 32' 5" (9881)
(1) Minimum dimension required for a short corner with a stack joint
(2) Minimum dimension required for a short corner with a running bond pattern
(3) Bold dimensions indicate the use of full size Amvic blocks with no cutting required
21"
8"
1"
34 1"
34
INSIDE - OUTSIDE
1"
302
INSIDE - INSIDE 45" 1"
142
RECOMMENDED
DOWEL 8"
PLACEMENT
OUTSIDE - OUTSIDE 29"
34
PART 5.1 COURSING AND DOWEL PLACEMENT
Table 14 ‐ Horizontal coursing chart for Amvic R30 8" (203mm) 45° corner blocks
36" 1"
34
20" 1"
8" 34
IN
C
R
EM
14" 20"
EN
8"
1"
TS
30" 20" 52
O
F
1"
8"
52
RECOMMENDED
DOWEL PLACEMENT
INSIDE - INSIDE
C C
35
PART 5.1 COURSING AND DOWEL PLACEMENT
Table 15 ‐ Horizontal coursing chart for Amvic R22 10" (254mm) short 90° corner blocks
Inside ‐ Outside Outside ‐ Outside Inside ‐ Inside Inside ‐ Outside Outside ‐ Outside Inside ‐ Inside
[ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)]
1' 10" (559)(1) 3' 1" (940)(1) 0' 7" (178)(1) 13' 10" (4216)(1) 15' 1" (4597) (1) 12' 7" (3835)(1)
2' 4" (711)(2) 3' 7" (1092)(2) 1' 1" (330)(2) 14' 4" (4369)(2) 15' 7" (4750) (2) 13' 1" (3988)(2)
2' 10" (864) 4' 1" (1245) 1' 7" (483) 14' 10" (4521) 16' 1" (4902) 13' 7" (4140)
3' 4" (1016) 4' 7" (1397) 2' 1" (635) 15' 4" (4674) 16' 7" (5055) 14' 1" (4293)
3' 10" (1168) 5' 1" (1549) 2' 7" (787) 15' 10" (4826) 17' 1" (5207) 14' 7" (4445)
4' 4" (1321) 5' 7" (1702) 3' 1" (940) 16' 4" (4978) 17' 7" (5359) 15' 1" (4597)
4' 10" (1473) 6' 1" (1854) 3' 7" (1092) 16' 10" (5131) 18' 1" (5512) 15' 7" (4750)
5' 4" (1626) 6' 7" (2007) 4' 1" (1245) 17' 4" (5283) 18' 7" (5664) 16' 1" (4902)
5' 10" (1778) 7' 1" (2159) 4' 7" (1397) 17' 10" (5436) 19' 1" (5817) 16' 7" (5055)
6' 4" (1930) 7' 7" (2311) 5' 1" (1549) 18' 4" (5588) 19' 7" (5969) 17' 1" (5207)
6' 10" (2083) 8' 1" (2464) 5' 7" (1702) 18' 10" (5740) 20' 1" (6121) 17' 7" (5359)
7' 4" (2235) 8' 7" (2616) 6' 1" (1854) 19' 4" (5893) 20' 7" (6274) 18' 1" (5512)
7' 10" (2388) 9' 1" (2769) 6' 7" (2007) 19' 10" (6045) 21' 1" (6426) 18' 7" (5664)
8' 4" (2540) 9' 7" (2921) 7' 1" (2159) 20' 4" (6198) 21' 7" (6579) 19' 1" (5817)
8' 10" (2692) 10' 1" (3073) 7' 7" (2311) 20' 10" (6350) 22' 1" (6731) 19' 7" (5969)
9' 4" (2845) 10' 7" (3226) 8' 1" (2464) 21' 4" (6502) 22' 7" (6883) 20' 1" (6121)
9' 10" (2997) 11' 1" (3378) 8' 7" (2616) 21' 10" (6655) 23' 1" (7036) 20' 7" (6274)
10' 4" (3150) 11' 7" (3531) 9' 1" (2769) 22' 4" (6807) 23' 7" (7188) 21' 1" (6426)
10' 10" (3302) 12' 1" (3683) 9' 7" (2921) 22' 10" (6960) 24' 1" (7341) 21' 7" (6579)
11' 4" (3454) 12' 7" (3835) 10' 1" (3073) 23' 4" (7112) 24' 7" (7493) 22' 1" (6731)
11' 10" (3607) 13' 1" (3988) 10' 7" (3226) 23' 10" (7264) 25' 1" (7645) 22' 7" (6883)
12' 4" (3759) 13' 7" (4140) 11' 1" (3378) 24' 4" (7417) 25' 7" (7798) 23' 1" (7036)
12' 10" (3912) 14' 1" (4293) 11' 7" (3531) 24' 10" (7569) 26' 1" (7950) 23' 7" (7188)
13' 4" (4064) 14' 7" (4445) 12' 1" (3683) 25' 4" (7722) 26' 7" (8103) 24' 1" (7341)
(1) Minimum dimension required for a short corner with a stack joint
(2) Minimum dimension required for a short corner with a running bond pattern
(3) Bold dimensions indicate the use of full size Amvic blocks with no cutting required
1"
32 1"
272
RECOMMENDED 1"
422
DOWEL
PLACEMENT
10"
36
PART 5.1 COURSING AND DOWEL PLACEMENT
Table 16 ‐ Horizontal coursing chart for Amvic R22 12" (305mm) short 90° corner blocks
Inside ‐ Outside Outside ‐ Outside Inside ‐ Inside Inside ‐ Outside Outside ‐ Outside Inside ‐ Inside
[ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)] [ft ‐ in (mm)]
2' 0" (610)(1) 3' 5" (1041)(1) 0' 7" (178)(1) 14' 0" (4267)(1) 15' 5" (4699)(1) 12' 7" (3835)(1)
2' 6" (762)(2) 3' 11" (1194)(2) 1' 1" (330)(2) 14' 6" (4420)(2) 15' 11" (4851)(2) 13' 1" (3988)(2)
3' 0" (914) 4' 5" (1346) 1' 7" (483) 15' 0" (4572) 16' 5" (5004) 13' 7" (4140)
3' 6" (1067) 4' 11" (1499) 2' 1" (635) 15' 6" (4724) 16' 11" (5156) 14' 1" (4293)
4' 0" (1219) 5' 5" (1651) 2' 7" (787) 16' 0" (4877) 17' 5" (5309) 14' 7" (4445)
4' 6" (1372) 5' 11" (1803) 3' 1" (940) 16' 6" (5029) 17' 11" (5461) 15' 1" (4597)
5' 0" (1524) 6' 5" (1956) 3' 7" (1092) 17' 0" (5182) 18' 5" (5613) 15' 7" (4750)
5' 6" (1676) 6' 11" (2108) 4' 1" (1245) 17' 6" (5334) 18' 11" (5766) 16' 1" (4902)
6' 0" (1829) 7' 5" (2261) 4' 7" (1397) 18' 0" (5486) 19' 5" (5918) 16' 7" (5055)
6' 6" (1981) 7' 11" (2413) 5' 1" (1549) 18' 6" (5639) 19' 11" (6071) 17' 1" (5207)
7' 0" (2134) 8' 5" (2565) 5' 7" (1702) 19' 0" (5791) 20' 5" (6223) 17' 7" (5359)
7' 6" (2286) 8' 11" (2718) 6' 1" (1854) 19' 6" (5944) 20' 11" (6375) 18' 1" (5512)
8' 0" (2438) 9' 5" (2870) 6' 7" (2007) 20' 0" (6096) 21' 5" (6528) 18' 7" (5664)
8' 6" (2591) 9' 11" (3023) 7' 1" (2159) 20' 6" (6248) 21' 11" (6680) 19' 1" (5817)
9' 0" (2743) 10' 5" (3175) 7' 7" (2311) 21' 0" (6401) 22' 5" (6833) 19' 7" (5969)
9' 6" (2896) 10' 11" (3327) 8' 1" (2464) 21' 6" (6553) 22' 11" (6985) 20' 1" (6121)
10' 0" (3048) 11' 5" (3480) 8' 7" (2616) 22' 0" (6706) 23' 5" (7137) 20' 7" (6274)
10' 6" (3200) 11' 11" (3632) 9' 1" (2769) 22' 6" (6858) 23' 11" (7290) 21' 1" (6426)
11' 0" (3353) 12' 5" (3785) 9' 7" (2921) 23' 0" (7010) 24' 5" (7442) 21' 7" (6579)
11' 6" (3505) 12' 11" (3937) 10' 1" (3073) 23' 6" (7163) 24' 11" (7595) 22' 1" (6731)
12' 0" (3658) 13' 5" (4089) 10' 7" (3226) 24' 0" (7315) 25' 5" (7747) 22' 7" (6883)
12' 6" (3810) 13' 11" (4242) 11' 1" (3378) 24' 6" (7468) 25' 11" (7899) 23' 1" (7036)
13' 0" (3962) 14' 5" (4394) 11' 7" (3531) 25' 0" (7620) 26' 5" (8052) 23' 7" (7188)
13' 6" (4115) 14' 11" (4547) 12' 1" (3683) 25' 6" (7772) 26' 11" (8204) 24' 1" (7341)
(1) Minimum dimension required for a short corner with a stack joint
(2) Minimum dimension required for a short corner with a running bond pattern
(3) Bold dimensions indicate the use of full size Amvic blocks with no cutting required
1"
142 6"
1"
22 1"
22
1"
322
INSIDE - OUTSIDE
12"
37
PART 6 WALL REINFORCEMENT
Building any structure using Amvic ICF requires the installer to have a good knowledge about the fundamentals of
steel reinforcement. This part of the manual will discuss the basics of reinforcing steel requirements for Amvic ICF
walls. Plan the outline of the block and the location of door and window openings on a conventional footing or a slab
that is level, straight and square. Rebar should extend upward at least 24” (610mm) from the footing into the cavity
of the block or as per engineering requirement.
Plan Requirements
For any given project, the following information should be indicated on the drawings.;
1. Separate cross sections of all walls using Amvic ICF. Each cross section should show the type of Amvic ICF
block used (i.e. core size) clearly marked and readily visible to the building official and installer.
2. Each cross section should show the wall heights involved for every floor.
3. Vertical and horizontal reinforcing bar sizes, spacing and grade of steel should be clearly marked for every
story in each wall cross section or in a separate note on other sheets.
4. The placement of reinforcing steel bars especially the vertical ones should be clearly marked (i.e. off center
or towards interior/exterior or centered in the wall).
5. The designer should specify the lap splice type and lengths for every section of the wall where splicing is
anticipated (covered in later part of this section).
Horizontal Reinforcement
Amvic’s polypropylene ICF webs are specifically designed to accommodate and secure the horizontal reinforcing bars
in place practically eliminating the need to tie them. Typically, the first course of horizontal reinforcement is placed
in the notches closer to the EPS panel (i.e. on the tension side of the wall for below grade). The second course of
horizontal reinforcement should be placed in the notch towards the center of the concrete wall. The third course
will be placed in the same position as the first course. The fourth course will be placed in the same position as the
second. This staggered pattern of horizontal reinforcement is necessary to allow for the vertical reinforcement to be
placed from the top and weave in between the horizontal steel bars.
38
PART 6 WALL REINFORCEMENT
Vertical Reinforcement
Vertical reinforcement is placed after the Amvic ICF wall has been stacked and completely erected. In case of a
multi-story wall, the vertical reinforcement is placed after the erection of each individual storey. As mentioned
above, vertical reinforcement bars are slid into place from the top and weaved into the horizontal reinforcement and
secured into the proper place according to the project requirements.
8" 8"
ALTERNATING
HORIZONTAL
STEEL
REINFORCING
16" BARS
VERTICAL
VERTICAL STEEL
STEEL
REINFORCING
REINFORCING
BARS OFFSET
BARS
TOWARDS
CENTERED IN
INTERIOR
WALL
Figure 1 – Typical reinforcing steel placement below (left) and above (right) grade
39
PART 6 WALL REINFORCEMENT
Splicing Reinforcement
Steel reinforcement typically comes in 20 feet (6 meters) lengths. In such cases where steel reinforcement is required
to exceed this length then a splice is required. The main purpose of the splice is to transform the stresses whether
tensile or compression from one steel reinforcing bar or a group of bundled bars to another in a manner to satisfy
the governing local building codes and/or requirements of the structural design.
d
Min. 40d
Min. 40d
d
CONCRETE CONCRETE
Figure 2 – Contact lap splices (left) and non-contact lap splices (right)
40
PART 6 WALL REINFORCEMENT
Option 1
Extend the vertical reinforcement steel bars beyond the top level of the lower story. The length of the extension
should be equal to the required splice length specified by the structural engineer or a minimum length of 40d (where
d = diameter of smaller steel bar being spliced).
EXTEND VERTICAL
STEEL
TYPICAL WOOD
REINFORCING
SUBFLOOR, JOISTS
BARS INTO
WITH HANGERS,
SECOND POUR
LEDGER BOARD
AND LEDGER
BEGINNING Min. 40d CONNECTORS TO
OF SECOND ICF WALL
POUR
END OF
FIRST POUR
HORIZONTAL
VERTICAL REINFORCING
REINFORCING STEEL AS
STEEL AS REQUIRED
REQUIRED
41
PART 6 WALL REINFORCEMENT
Option 2
In some situations, it might be more beneficial to use a dowel as a splice due to ease of installation or site conditions.
Cut the vertical reinforcement steel bars for the lower story so that they are flush with the top of that wall. Shortly
after pouring the concrete, wet set additional vertical reinforcing bars also known as dowels into the concrete. These
bars should extend into the freshly poured wall a length equal to the splice length specified by the design engineer
or a minimum length of 40d (where d = diameter of smaller steel bar being spliced). The wet set vertical splice
reinforcing steel bars should ALSO protrude into the upper wall by the same splice length specified by the design
engineer or 40d as a minimum.
HORIZONTAL
REINFORCING
WET SET DOWELS
STEEL AS
IN FRESH
REQUIRED
CONCRETE AFTER
FIRST POUR TYPICAL WOOD
SUBFLOOR, JOISTS
WITH HANGERS,
BEGINNING Min. 40d LEDGER BOARD
OF SECOND AND LEDGER
POUR CONNECTORS TO
ICF WALL
END OF
FIRST Min. 40d
POUR
42
PART 6 WALL REINFORCEMENT
Canada
Amvic’s Canadian Design Guide (Part 6.1) and ICF CCMC Code Requirements
report 13043-R contain reinforcing steel tables for below
A. Design of reinforced concrete shall be in accordance
grade and up to two stories of above grade applications
with CSA A23.3.
in residential projects. The report also contains some
lintel tables for wall openings both in metric and B. Reinforcing steel placement shall conform to CSA
A23.1, CSA A23.4 and/or the local building code
imperial units.
having jurisdiction.
There are applicability limits mentioned in the report C. Reinforcing steel bars shall conform to clause 7 of
which must be adhered to. If the particular project at CSA A23.1 AND CSA G30.18.
hand falls outside of these limits, then a local licensed/
D. Minimum Steel Yield Strength shall not be less than
registered engineer should be retained.
300 MPa (40 ksi).
United States
NAHB (National Association of Home Builders) in Code Requirements
association with PCA (Portland Cement Association)
have prepared the “Prescriptive Method for Insulating A. Design of reinforced concrete and placement of
Concrete Forms in Residential Construction” specifically reinforcing steel bars shall be in accordance to ACI
for the ICF industry. 318 or ACI 332 and/or the local building code having
jurisdiction..
The book contains reinforcing steel schedules for below
grade and up to 2 stories above grade applications.
The book also contains a lot of lintel tables for wall B. Reinforcing steel bars shall conform to one of the
openings in different applications. As expected, there following specifications;
are limitations to using the book which must be adhered
a. ASTM A615 – Specifications for Deformed and
in order to use it.
Plain Billet-Steel Bars
For applications that fall outside the scope of the
“Prescriptive Method” a local licensed/registered b. ASTM A706 – Specifications for Low-Alloy Steel
engineer should be retained. Deformed and Plain Bars
PCA (Portland Cement Association) has prepared
c. ASTM A996 – Specifications for Rail-Steel and
another tool targeted at engineers to assist them
Axle Steel Deformed Bars
in the design of ICF walls namely “Structural Design
of Insulating Concrete Form Walls in Residential
Construction”. This publication explains in more detail
the engineering principles involved in design load C. Minimum yield strength of reinforcing steel shall
be Grade 40 (300 MPa) except for seismic design
bearing and non-load bearing ICF walls even for walls
categories D1 & D2 the minimum yield strength of
outside the scope of “The Prescriptive Method”. reinforcing steel shall be Grade 60 (400 MPa).
43
PART 6 WALL REINFORCEMENT
44
PART 7 WALL OPENINGS
Window and door bucks are an integral part of the ICF construction process. Some contractors build their own bucks
using two-by lumber, while others prefer using a vinyl buck. Experienced ICF installers use a variety of methods
for forming and installing bucks. This section explains the main principles and most common methods of buck
construction and installation. This section should only be used as a guideline.
Note: It is advisable to follow window manufacturers guidelines for rough opening sizes to ensure proper dimensions are
achieved with taking into consideration the buck configuration. It is important to verify with the window manufacturer
that the specified rough opening is the size of the buck and not the size of the actual window.
Note: Most windows in ICF construction should be placed on the solid area of the opening and not directly on top of the
of the EPS panels. This will provide proper support and eliminate potential issues of sagging and movement over time.
45
PART 7 WALL OPENINGS
Figure 2 – Typical full width wood buck made of pressure treated Figure 3 – Regular wood lumber with waterproofing membrane
lumber
Figure 4 – Typical full width window buck bottom construction Figure 5 – Opening at bottom of full width window buck for pouring
concrete
46
PART 7 WALL OPENINGS
47
PART 8 ICF INSTALLATION PROCESS
This part covers the installation process in detail for a typical Amvic ICF project.
Figure 1 – Placing Amvic ICF within the perimeter of the wall layout
Figure 2 – Moving ICF bundles by hand Figure 3 – Using forklift to move bundles
48
PART 8 ICF INSTALLATION PROCESS
Figure 4 – Using pre-cut & bent reinforcing steel will increase efficiency
Section 8.2 - Course Planning: Determining Wall Heights and Number of Courses per Floor
Prior to laying block, determine the exact wall height required for the project. Amvic ICF is manufactured to 16”
(406mm) high with the only exception being the 10” (254mm) and 12” (305mm) blocks which are 24” high (610
mm). If the floor heights are not divisible by 16” (406mm) or 24” (610mm), the two most common practices are the
following:
1) Rip-cut the first or last course of block horizontally. Cutting the first course is recommended since the cut
edge will be glued to the footing/slab and will not affect the interlocking of subsequent courses. If using this
method, make sure to preserve the polypropylene webs which connect the two EPS panels.
a. A table saw is recommended for rip cuts since cutting the webs by hand can be tedious and time
consuming.
2) Use an Amvic ICF height adjuster. These are available in 2”, 3” and 4” heights (51mm, 76mm and 102mm)
and can be placed below the first course or above the last course. Placing the height adjuster above the top
course is recommended.
Figure 5 – Amvic ICF height adjuster Figure 6 – Using a circular saw to horizontally rip cut ICF
For single story structures the walls will be poured in one day from the footing/slab to the top plate. For multi-storey
structures, blocks will typically be stacked and poured one floor at a time. Once a floor is complete, the floor joists
and subfloor will be installed before the next story is stacked and poured.
49
PART 8 ICF INSTALLATION PROCESS
50
PART 8 ICF INSTALLATION PROCESS
Figure 10 – Cutting the final block for a wall section Figure 11 – Fitting the cut block in place
6) Connect blocks in the first two courses together using zip ties (plastic ties). One zip tie per end joint is
generally sufficient. Place zip ties towards either edge (next to the EPS inside face). Tightening the zip ties
at the center will flex the webs and may lead to foam fracturing at that location creating a source of failure
during the concrete pour.
51
PART 8 ICF INSTALLATION PROCESS
Figure 12 – Using zip ties to tie the first course of blocks together
7) Install the horizontal reinforcing steel as per engineering or local building code requirements (See Canadian
and US Design Guides).
52
PART 8 ICF INSTALLATION PROCESS
1) Stacking with the corner blocks first. Every corner block has a short leg and a long leg. Make sure that the
corner block is reversed at the corners on the second course by flipping them upside down so that the long
leg interlocks with the short leg of the first course. This will create a running bond pattern between the two
courses.
2) Stack the straight forms, working towards the center of the wall.
3) Place the cut block on this course at the same location as the first course. This will ensure the offset joint
remains roughly in the same place.
a. It is very important to keep the offset joint at roughly the same location for each wall section
as you stack the courses. This will ensure that there is a straight “stud” for interior and exterior
attachments.
4) Press down firmly on the blocks to ensure a secure connection with the course below.
5) Install horizontal rebar as per engineering or local building code requirements.
Figure 15 – Reversing 45° corner blocks for bay window Figure 16 – Placing the offset joint in approximately same place as
first course
53
PART 8 ICF INSTALLATION PROCESS
Figure 18 – Shimming the first course with foam cuttings Figure 19 – Trimming the first course of block with a hand saw
54
PART 8 ICF INSTALLATION PROCESS
Figure 20 – Using foam adhesive to secure the first course of block to the foundation/slab
If the form interlock on the bottom of the first course was not cut prior to the installation, it is recommended to have a
continuous bead of foam adhesive to secure the first course to the footings/slab and to prevent the cement paste in the
concrete from leaking away. Securing the first course of block to the foundation is an ideal task to do just before a break.
55
PART 8 ICF INSTALLATION PROCESS
56
PART 8 ICF INSTALLATION PROCESS
Figure 25 – Installing reinforcing steel bars for wall opening header or lintel
57
PART 8 ICF INSTALLATION PROCESS
58
PART 8 ICF INSTALLATION PROCESS
59
PART 8 ICF INSTALLATION PROCESS
Most bracing systems include a scaffold platform upon which scaffolding planks are placed for workers to work from
along with provision for installing a handrail. Scaffold planks and handrails are typically not included with the bracing
system and are provided separately.
Bracing is usually attached either with a “hat bracket” that wraps the strongback or through slotted screw holes in
the brace. It is recommended to use Amvic’s 2” (51mm) ICF screws to secure the strongback to the ICF webs. For
a strongback with slotted screw holes, install the screws near the top of the slot. Over tightening the screw may
result in the block settling or compressing which can misalign a wall, however, this is unlikely with Amvic ICF which
compresses very little. If the first course of ICF blocks is firmly attached to the footing/slab using glue, start the
bracing installation from the second course. Attach the strongback at every course and twice for the top course.
Figure 31 – A hat bracket wrapped around a vertical strong-back and screwed to webs
on both sides
60
PART 8 ICF INSTALLATION PROCESS
61
PART 8 ICF INSTALLATION PROCESS
62
PART 8 ICF INSTALLATION PROCESS
3) At each buck, in at least the four corners on each side, install a cleat that screws to the buck and overlaps the
foam to hold the buck flush with the form on both the inside and outside. The cleat can be anything, e.g. a
concrete stake, piece of OSB or plywood, etc.
4) If already not done so, install both horizontal and vertical braces in all doors and windows bucks. There
should be a cross brace at least every 2’ (610mm). Lintels over 8’ (2.4m) may require additional shoring.
63
PART 8 ICF INSTALLATION PROCESS
• Where an offset joint exists. An offset joint is where the interlocking system between the block courses does
not line up. This most likely happens when there has been a cut in the last block in a wall section so that
it fits the required wall dimension. The “running bond” pattern on an offset joint is less than 12” (305mm)
which is the recommended overlap of the interlock.
• Where the edge of the block joins a window or door buck if using wooden bucks.
64
PART 8 ICF INSTALLATION PROCESS
65
PART 8 ICF INSTALLATION PROCESS
66
PART 8 ICF INSTALLATION PROCESS
67
PART 8 ICF INSTALLATION PROCESS
Figure 43 – Cutting openings in EPS between webs Figure 44 – Making the end cuttings flare out
4) Place the OSB & anchor bolts into the holes and attach with four screws, one in each corner. Drywall screws
work well.
Figure 45 – Installing the OSB with anchor bolts onto the EPS openings
and securing with drywall screws
5) Allow at least 3 days after the pour before tensioning the anchor bolts.
68
PART 8 ICF INSTALLATION PROCESS
6) Install the ledger by leveling it precisely below the anchor bolts. Using a reference block, do a drop-down
takeoff and drill holes slightly larger than the anchor bolts. Place the ledger. Install the required anchor bolt
washers and nuts.
7) Use standard joist hangers to attach floor joists to the ledger board.
69
PART 8 ICF INSTALLATION PROCESS
Figure 50 – Inserting the ICFVL long legs through the EPS and into the concrete
3) Fix it in place either with a foam adhesive or a single screw through the small hole in the center of the ICFVL
plate into a web (the ICFVL base plate would need to be centered with the web).
4) After the concrete has been poured and has cured for 3-4 days place the ledger in the proper place, level it
and temporarily brace it.
70
PART 8 ICF INSTALLATION PROCESS
Figure 53 – Attaching floor joists to the ledger board with the Simpson-Tie™ (ICFVL-W with dimensional lumber shown)
Additional technical and engineering information on the ICFVL system can be found at www.strongtie.com
71
PART 8 ICF INSTALLATION PROCESS
Section 8.13 – Beam Pocket and Floor Joist Directly Bearing on ICF Wall
Steel beams and solid wood floor joists may be required to bear on the ICF walls according to structural design. A
beam pocket made inside the wall can be created as per the following steps.
1) Establish the beam dimensions and the elevation at which it will be installed. Use a laser level to mark the
elevations on the inside of the EPS panel.
2) On one side of the wall where the beam will bear, cut out an opening from the inside and outside EPS
panels. Make sure that the cut-out pieces are aligned in elevation and are larger than the actual beam size by
about 1/2” (13 mm) all around. This will facilitate placing the beam in place.
3) On the opposite wall where the other end of the beam will be bearing, cut out a piece from the inside EPS
panel only. The opening should again be aligned with the opposite wall and larger than the actual beam size
by 1/2” (13 mm) all around.
4) Block the void between the two openings in one wall completely from inside out using waste EPS or wood.
The opening in the other wall should also be blocked deep enough into the wall cavity to provide the
required bearing length as depicted on the plans.
5) After the concrete is poured and has gained enough strength, break off the blocking EPS or wood to reveal
the beam pocket or voids created in the wall.
6) Maneuver the beam in place and secure. Seal the area between the beam and void pocket as required.
Figure 54 – Cut beam opening through both EPS panels Figure 55 – Block opening voids with scrap foam or wood
72
PART 8 ICF INSTALLATION PROCESS
Figure 56 – Opening should be blocked deep enough to provide Figure 57 – Once the concrete is cured sufficiently, void fill is
required bearing removed, and beam is installed
73
PART 9 SPECIAL ICF INSTALLATION
This part explains some of the more advanced installation techniques and special floor systems that can be used with
Amvic ICF. The most common special installations are included below, however if the project has any site specific
situation that are not covered by this manual, please contact us for assistance.
Section 9.1.1 – Short corners using 90° corner blocks with a stack joint
A short corner can be constructed using at least two (2) 90° corner blocks. Refer to Part 5 for coursing and minimum
corner dimensions using this method. Recommended steps are given below;
• Install the first course so that the short legs on both blocks are adjoining each other as illustrated in Figure 1
below.
• Install second and consecutive courses of corner blocks in the same manner without alternating forms. This
will create a stack joint.
• Ensure stack joint is adequately braced on both sides of forms and at every course.
• Failure to brace a stack joint adequately may lead to a blowout during the concrete pour. Make sure to use
additional bracing if necessary.
BRACE
WIRE TIE
BRACE
74
PART 9 SPECIAL ICF INSTALLATION
Section 9.1.2 – Short corners using 90° corner blocks with a running bond pattern
This method also involves at least two (2) 90° corner blocks. Refer to Part 5 for coursing and minimum corner
dimensions using this method. The recommended steps are given below;
• Install the first course so that the long leg of one corner block and the short leg from the second block are
adjoining each other as illustrated in Figure 2 below.
• Install second and consecutive courses by alternating the forms to create a running bond pattern. Refer to
Figure 3 below.
RUNNING
BOND IS
FORMED AS
BLOCK
COURSES
ARE STACKED
AND
ALTERNATED
FIRST CONSECUTIVE
COURSE COURSE
Figure 2 – Plan view of two short corners made using 90° forms to create a running bond pattern
Figure 3 – Short corner made of 90° forms with a running bond pattern
75
PART 9 SPECIAL ICF INSTALLATION
Figure 4 – Cutting foam from the end of the straight block on one EPS panel
4. Set the forms in place and glue the cut off pieces to fill the ends of the forms thereby creating a 90°
corner.
Figure 5 – Setting the two cut forms into position Figure 6 – Using cut off pieces to close the open ends and create a
corner
5. Construct two 90° wood forms made of 2x10” (38x235mm) lumber and place them on each of the formed
EPS corners.
76
PART 9 SPECIAL ICF INSTALLATION
Figure 8 – Inserting the threaded rod through the drilled holes Figure 9 – Threaded rod inserted through both wood forms
7. Continue to cut and stack the blocks to the desired wall height. Place the threaded bolts approximately
16” (406mm) on center vertically. When the concrete has been poured and has set for a few hours,
remove the wooden forms and cut the threaded rod so that it is flush with the concrete surface. Use
foam adhesive to fill the holes in the EPS panels.
77
PART 9 SPECIAL ICF INSTALLATION
Amvic manufacturing facilities provide pre-cut radius forms which ensure that
courses fit together easily, and installation goes smoothly with minimal labor
costs. Pre-cut radius forms are tongue and groove cut on the inside EPS panel
and slit cut on the outside EPS panel. Radius forms can also be constructed by
the contractor on site using straight Amvic ICF.
For contractors who opt to cut the ICF on site, refer to Figures 13, 14 and
tables below for information on radius dimensions and cutting blocks.
Figure 12 – Several courses of radius blocks installed Figure 11 – Bending and securing the radius
form into place
78
PART 9 SPECIAL ICF INSTALLATION
W
INSIDE RADIUS
TONGUE & GROOVE EPS PANEL
CUTS 6" (152mm) O.C.
(CUT WIDTH "W" VARIES
WITH WALL RADIUS)
Figure 13 – Radius wall tongue & groove and slit cut details
OUTSIDE RADIUS
EPS PANEL
INSIDE RADIUS
EPS PANEL
Figure 14 – Radius wall bent to shape
79
PART 9 SPECIAL ICF INSTALLATION
80
PART 9 SPECIAL ICF INSTALLATION
Plumber strap
Figure 16 – Typical T-wall connection diagram showing Amvic’s molded R22 6” (152mm) blocks
81
PART 9 SPECIAL ICF INSTALLATION
Plumber strap
82
PART 9 SPECIAL ICF INSTALLATION
BRICK VENEER
AMVIC ICF
BRICK LEDGE
FORM
Figure 19 – Brick ledge form used for supporting exterior masonry veneer
83
PART 9 SPECIAL ICF INSTALLATION
Alternatively, the brick ledge block forms can be used with the ledge support on the interior side of the building to
provide support for flooring systems such as wood joists, steel joists etc.
Figure 20 – Brick ledge form used for supporting interior floor system
MAIN
REINFORCING
STEEL CONTINUOUS
STIRRUPS TYPICAL
AS HORIZONTAL
REQUIRED STIRRUP
HANGERS
(#4/10M)
Figure 21 – Cross section of 8” (203mm) brick ledge form with Amvic Brick Ledge Reinforcer or conventional stirrups
84
PART 9 SPECIAL ICF INSTALLATION
Figure 22 – Amvic brick ledge form installed as a single course Figure 23 – Completed brick ledge installation for exterior brick
veneer support
Figure 24 – Laying standard brick veneer on the brick ledge support Figure 25 – Standard brick ties screwed into the Amvic webs
85
PART 9 SPECIAL ICF INSTALLATION
Figure 27 – Place the Reinforcer into the form. No additional tying or securement is
needed.
86
PART 9 SPECIAL ICF INSTALLATION
Figure 29 – Install the Brick Ledge Extension by securing it to the ICF webs with Amvic’s
assembled fasteners
Figure 30 – Once the foam extension is attached, place reinforcing into the cavity
87
PART 9 SPECIAL ICF INSTALLATION
Figure 33 – Cut the brick ledge extension to size and secure it to the corner block using
the fastening kit
88
PART 9 SPECIAL ICF INSTALLATION
Figure 35 – Maneuvering a precast hollow core slab for placement on Figure 36 – A precast slab panel placed on an ICF wall
an ICF wall
89
PART 9 SPECIAL ICF INSTALLATION
BEARING AS PER
SPECIFICATIONS
HAMBRO COMPOSITE
FLOOR SYSTEM
SECOND
POUR
FIRST
POUR
VERTICAL AND
HORIZONTAL
REINFORCEMENT
AS REQUIRED
Figure 37 – Typical Amvic ICF wall with Hambro® composite floor system
90
PART 9 SPECIAL ICF INSTALLATION
SECOND
POUR
FIRST
POUR OWSJ
4" (102mm)
BEARING PLATE
WITH ANCHOR
BOLT
VERTICAL AND
HORIZONTAL
REINFORCEMENT CONTINUOUS STEEL ANGLE
AS REQUIRED
Figure 38 – Typical Amvic ICF wall open web steel joist (OWSJ) installation
91
PART 9 SPECIAL ICF INSTALLATION
92
PART 9 SPECIAL ICF INSTALLATION
93
PART 9 SPECIAL ICF INSTALLATION
In most cases, as the blocks are being stacked from the opposing corners, there will be a section which requires one
of the blocks to be cut. In this situation, there is a need to create a stack or offset joint. At this location, the cut block
will have one factory edge and one cut edge. If the blocks in the following courses are stacked in a way where the
vertical seam is aligned from course to course, this will create a stack join.
Mini ICF: A cut form that has 3” [(76mm) for R22 and 4” (102mm) for R30] of foam from both sides of a web. This
form can be placed anywhere in the wall and webs will align properly with the interlock and the webs allowing
running bond to be maintained.
Mark the standing seam at the first course of forms and each course thereafter with a sad face (or any visual que)
using a marker. This serves as a visual reminder to reinforce the area. Strap a wailer and spray foam adhesive across
the standing seam on “both” sides of the wall prior to placing concrete, as no interlock is functioning at this location.
Notes:
• Have only one standing seam per
wall section.
• Window or door openings are
a good place situate a standing
seam as it will eliminate some
of the extra work required in
(wailing) the standing seam.
• If possible, avoid standing seams
in corners.
• Always assemble “one wall
section at a time”, by laying down
the two opposing corner forms
and work towards the center of
each wall.
94
PART 9 SPECIAL ICF INSTALLATION
Figure 45 - Place the bottom of the hook under the top portion of the lower block’s web
Figure 46 - Bring the top portion of the hook up and over the top of the two webs and snap it in place (pull the lip up to unhook it)
95
PART 9 SPECIAL ICF INSTALLATION
Figure 47 - 4” (102mm) double side factory fabricated height adjuster (available for both R22 and R30)
Figure 48 - Site fabricated height adjusters can be manually cut using a hand saw or a table saw
Figure 49 - Site fabricated height adjusters with the web intact provide additional strength
96
PART 9 SPECIAL ICF INSTALLATION
Figure 50 – Use hand saw or hot knife (not shown) to cut blocks Figure 53 – For taller walls (>4’ (1.2m)), exterior bracing is needed
to size
97
PART 9 SPECIAL ICF INSTALLATION
a. b. c.
Figure 54 – Typical taper top block (a), typical straight block (b), straight block after interlock removal (c)
d. e. f.
Figure 54 – Half block height cut-out (d), 60° cut-out (e), 45 ° cut-out (f)
98
PART 10 CONCRETE PLACEMENT
This section of the manual covers the basic fundamentals of concrete. New Amvic ICF installers should review
this information before proceeding to the following section which deals with concrete placement techniques
recommended for Amvic ICF.
99
PART 10 CONCRETE PLACEMENT
100
PART 10 CONCRETE PLACEMENT
101
PART 10 CONCRETE PLACEMENT
Mineral admixtures affect the nature of the hardened concrete through hydraulic or pozzolanic activity. Pozzolans are
cementitious materials and include natural pozzolans (such as the volcanic ash used in Roman concrete), fly ash and
silica fume.
102
PART 10 CONCRETE PLACEMENT
103
PART 10 CONCRETE PLACEMENT
104
PART 10 CONCRETE PLACEMENT
105
PART 10 CONCRETE PLACEMENT
Amvic ICF blocks have an ultimate forming capacity of 864 lbs/ft2 (41.4 kPa) as tested according to section 6.4.4
of the Canadian CCMC technical guide for modular expanded polystyrene concrete forms. Table below shows the
design lateral pressure for newly placed concrete that should be used for the wall formworks. The pressures are
based on the recommendations and formulas given by ACI 347-04.
Amvic’s recommended pour rate is between 3-4 ft/hr (915-1200 mm/hr). However, it is evident from the table above
that concrete pour rates of up to 5 ft/hr (1.5 m/hr) are possible in warm temperatures (70°F (21°C)).
106
PART 10 CONCRETE PLACEMENT
Placement Method Type of work best suited for Adantages Special Notes
Concrete Boom Pump Used to convey concrete Different boom reaches For maximum efficiency,
directly from discharge point available. Delivers concrete in schedule concrete trucks
like concrete truck mixer into continuous stream. Pump can appropriately to provide
Amvic ICF wall. move concrete vertically and continuous supply of concrete
horizontally. Pump mounted to the pump with minimal
on truck has high mobility idle times. Employ 3” (76mm),
and very versatile to many 2.5” (64mm) or 2” (51mm)
pouring situations reducers and flexible hose at
end of pipeline to reduce rate
of concrete pour.
Crane & Bucket Used mainly for conveying Provides clean discharge Make sure bucket has a
concrete above ground level and there are many bucket handle to control the rate of
directly from discharge point capacities available. Cranes concrete discharge. Select
into Amvic ICF wall. may be used to convey other fitting at bottom of bucket to
materials such reinforcing suit placement in ICF walls
steel
Chutes on Truck Mixers For conveying concrete to Very economic and easy to Slopes should range between
a lower level, usually below maneuver. No power required 1:2 and 1:3. Chute should
ground level directly from since gravity does most of be adequately supported in
discharge point into Amvic ICF work. all positions. End discharge
wall. arrangements required to
prevent segregation.
Belt Conveyors For conveying concrete Belt conveyors have End discharge arrangements
horizontally or to a higher or adjustable reach, traveling needed to prevent
lower level. May be used to diverter and variable speed segregation. In extreme
discharge concrete directly for forward and reverse. weather conditions, long
into Amvic ICF wall but Can place large volumes of reaches of belt may need
usually positioned between concrete for limited access cover to protect concrete
main discharge and second situations
discharge point.
Table 5 – Most common method for concrete placement used with Amvic ICF
107
PART 10 CONCRETE PLACEMENT
108
PART 10 CONCRETE PLACEMENT
109
PART 10 CONCRETE PLACEMENT
Section 10.9.2 - Pouring Concrete around Windows/ Doors & Straight Sections
1. Typically, contractors will start by bringing the boom hose down and filling the bottom of the window bucks
first. Each window bottom should be consolidated using a concrete vibrator and then screeded off.
a. Depending on the slump, it is advisable to nail or screw an OSB cap over the opening(s) in the
bottom of the window buck, to prevent the concrete from bulging up or overflowing when you pour
down the sides from above in the next passes.
2. Window and door bucks should not be fully filled on one side at one time. Fill both sides of the opening
using a back-and-forth rhythm and avoid spilling concrete into the window and door headers (also known as
lintels) in doing so.
a. With a 2-3” (51 -76 mm) reducer on the pump hose, it is frequently possible to hold back the flow of
concrete briefly by placing one’s rubber gloved hand over the end of the nozzle and quickly swinging
the hose to the other side of the window or door.
3. Pour concrete normally into straight sections up to the required lift height.
4. As the walls are filled to a lintel, ensure a continuous pour along its entire length without creating any cold
joints. Proper and adequate concrete consolidation in lintels is of paramount concern.
5. Stop short of pouring concrete into a second corner by approximately 2-3’ (0.6-0.9m). Follow the
recommendations given above for concrete placement in corner blocks.
110
PART 10 CONCRETE PLACEMENT
111
PART 10 CONCRETE PLACEMENT
Specification 4 and 6” (102 and 152mm) ICF 8, 10 & 12” (203, 254 and 305mm) ICF
Maximum vibrator head diameter 1” (25mm) 1.25” (32mm)
Frequency (vibrations per minute) 10,000 vpm 9,000 vpm
Minimum Radius of Action 4” (102mm) 6” (152mm)
Insertion on center spacing 6” (152mm) 9” (229mm)
Centrifugal Force 220 lbs (100 Kg) 500 lbs (227 Kg)
Compaction rate 2-4 yds /hr
3
2-5 yds3/hr
(1.5-3 m3/hr) (1.5-3.8 m3/hr)
Table 6 – Recommended immersion type concrete vibrator specifications for use with Amvic ICF
112
PART 10 CONCRETE PLACEMENT
Figure 14 – Vibrator head placement Figure 15 – Radius of action of concrete Figure 16 – Insert vibrator head at 1.5 times radius of
vibrator action
• Allow vibrator to penetrate 6” (152mm) into the previous layer to ensure proper bond and eliminate cold
joints.
• Pour concrete into the walls in lifts of 3-4’ (0.9-1.2m) high per hour. For proper consolidation, each of the lifts
should be poured in layers of the same thickness as the vibrator head length minus depth of penetration into
previous layer, typically 6” (152mm).
• Stop vibration when the surface becomes shiny and there are no more breaking air bubbles.
• Ensure the vibrator flexible shaft has enough length to match the wall height being poured.
• Make sure there are enough workers for placing and consolidating concrete during the pour. A two-man
crew should be handling the concrete vibrator and follow immediately after the person working the pump
hose as each layer is poured.
Practices to Avoid;
• Do not use vibrator to move concrete laterally. This causes segregation.
• The vibrator head should not touch the sides of the ICF forms. It should only be in contact with concrete.
• Do not immerse the vibrator head down the same path more than once.
• Do not run the vibrator in air for more than 15 seconds. This will cause overheating.
• Avoid sticking the vibrator head into the top of a concrete heap. To flatten a concrete heap, insert the head
around the perimeter. Do this carefully to avoid segregation.
113
PART 10 CONCRETE PLACEMENT
Section 10.13.1 - After the Pour: Recheck Wall Straightness and Adjust
After pouring is complete, immediately check the corners again for plumb and the wall for straightness. You have a
short window in which the bracing system can push and move the wall. If realignment is required adjust the bracing
to do so. It is good to have 3 to 4 spare braces ready in the event you need to quickly install an additional adjustable
brace to push the wall in an area that you didn’t expect.
Before all pours, brief everyone on the crew on procedures to handle a blowout. If a blowout occurs, the ground man
should:
1. Waive off the pump and vibrator
2. If the foam has only bulged and not separated from the webs, install a piece of form support at the same
location. You can use an extra bracing for that purpose.
3. If foam has broken out, remove it and clean out concrete, reinsert the broken piece of foam so that it is flush
with the wall
4. Install one or more pieces of OSB with multiple screws into intact webs or bucks on either side of the failure
location
5. Go back to work as normal, a very minor event if you are prepared
114
PART 11 BELOW GRADE PROTECTION
As with any below grade structure, it requires protection from moisture ingress and in some areas also needing
protection from termites as well. ICF construction is used throughout North America in various climates and soil
conditions and can easily be adapted to meet the local needs of a given area. It is always a good practice to enlist an
experienced designer and builder to make sure the correct system is used with ICF for below grade protection which
will be both long-lasting and cost effective.
115
PART 11 BELOW GRADE PROTECTION
Section 11.1.5 – Damp Proofing & Waterproofing Applications for Amvic ICF
There are three types of membranes that can be applied to Amvic ICF including liquid applied membranes, peel &
stick membranes and dimpled membranes. Each of the above-mentioned types have advantages and disadvantages
and the choice to choose one of the other is left up to the designer/client. However, factors to consider before
making a choice are:
• Local availability – Check with your local Amvic distributor to inquire about the availability of applicable
products to Amvic ICF in your area.
• Product Technical Information – Ensure that your product of choice has the proper technical information
with regards to specifications, installation instructions and meets the local building code requirements.
• Manufacturer’s warranty – The product manufacturer should have a product warranty against production
deficiencies. Some manufacturers offer up to 30 years of warranty on their products.
• Installer’s Warranty – The contractor installing the product should offer an installation warranty to guarantee
that product is installed properly and will perform up to the requirements for a given period of time.
• Installer’s reference – It is recommended to ask your installer about his experience using the specific product
of choice.
• Price – Higher performance products will almost always cost more than less performance ones. Carefully
weigh the benefits against the costs before deciding on which product to use.
Regardless of which type and brand of application to be used, always follow the manufacturer’s installation
procedures for ICF application.
116
PART 11 BELOW GRADE PROTECTION
Compatible liquid applied waterproofing membrane products for Amvic ICF include:
• Henry Company, BLUE SEAL™ ICF and Concrete Construction - www.ca.henry.com
• Henry Company, Aqua-Bloc 720-33 - www.ca.henry.com
• Henry Company, Aqua-Bloc 720-38 - www.ca.henry.com
• Carlisle, CCW BARRICOAT - www.carlisleccw.com
• EPRO, e.spray - www.eproinc.com
• Advanced Coatings, Rub-R-Wall - www.advancedcoatings.on.ca
117
PART 11 BELOW GRADE PROTECTION
118
PART 11 BELOW GRADE PROTECTION
119
PART 11 BELOW GRADE PROTECTION
Figure 6 – Most common species of termites found in North America Figure 7 – Termite risk map of Canada (excluding territories) and US
120
PART 11 BELOW GRADE PROTECTION
Section 11.2.3 - International Residential Code 2003, Termite Control and EPS Protection [R320.1]
Subterranean termite control.
In areas favorable to termite damage as per table R301.2(1) methods of protection shall be any of the following:
• Chemical soil treatment
• Pressure treated wood in accordance with AWPA standards
• Naturally termite resistant wood
• Physical barriers such as metal or plastic termite shields
• Any combination of above
[R320.4] Foam Plastic Protection.
In areas where the probability of termite infestation is ‘very heavy’ as per figure R301.2(6), EPS foam shall not be
installed on the exterior face or under interior or
exterior foundation walls or slab foundations located
below grade. There should be a minimum clearance of
at least 6” (152mm) between foam plastics installed
above grade and exposed earth.
Exceptions in the code:
• Building structural members of walls,
floors, ceilings and roofs are entirely of
noncombustible materials or pressure treated
wood.
• In addition to requirements of R320.1 an
approved method of protecting the foam
plastic and structure from subterranean
termite damage is provided.
• On the interior side of basement walls.
Figure 8 – Illustration R301.2(6) as per IRC 2003 showing probability of
termite infestation
121
PART 11 BELOW GRADE PROTECTION
Section 11.2.4 – National Building Code of Canada 2005, Termite Control and EPS Protection
[NBC 2005 – 9.12.1.1 (2)]
In localities where termite infestation is known to be a problem, all stumps, roots and other wood debris shall be
removed from the soil to a depth of not less than 300mm in unexcavated areas under a building.
[NBC 2005 – 9.3.2.9 (1)]
In localities where termites are known to occur,
a) clearance between structural wood elements and finished ground level directly below them shall be not less
than 450mm all sides of the supporting elements shall be visible to permit inspection, or
b) structural wood elements, supported by elements in contact with the ground or exposed over bare soil, shall
be pressure treated with a chemical that is toxic to termites.
122
PART 11 BELOW GRADE PROTECTION
Figure 9 – Metal termite shield using copper metal on top of Figure 10 – Detail of metal shield at inside corner
foundation wall
Particle Sized Barrier
A physical barrier consisting of particle-sized rocks, such as crushed basalt, silica sand, natural sand, granite, glass
shards, limestone, quartz and coral sand, can be used to prevent termite entry. There are three basic requirements
that must exist for a particle sized barrier to be effective:
1. Granules size must be small enough so that when compacted together, the space between them is too small
for the termites to squeeze through.
2. Granules must be big and heavy enough so that the termites can’t pick them up and move them using their
mandibles.
3. Granules must be too hard for the termites to chew.
The current studies conducted by entomologists reveal that particle sizes between 1.4-2.8mm (0.055-0.11”) are
impenetrable to subterranean termites. Particle-sized barriers are used under slabs, around foundations, and around
plumbing to create a physical barrier against termites.
An example of a successful particle sized barrier is the Basaltic Termite Barrier (BTB) made of crushed and/or sieved
basalt which was invented in Hawaii and is currently being used extensively throughout the US for new commercial
and residential construction.
123
PART 11 BELOW GRADE PROTECTION
Termimesh
Termimesh is a marine grade 316 stainless steel wire mesh which protects the foundation walls and slab on grade
of a structure from termite penetration. The aperture grille of the mesh is too small for the termites to penetrate
and too hard for them to chew. Termimesh will not kill or eliminate termites. It will physically prevent termites from
penetrating a building structure.
Termimesh can be installed during construction on the exterior of foundation walls, under the slab on grade,
and around service pipes penetrating the structure. For the system to be effective, proper installation is critical.
Termimesh can only be installed by licensed professionals who have been trained by the company to specifically
install Termimesh.
Compliance of Termimesh with building code requirements for termite protection is covered by the ICC-ES Evaluation
Report ESR-1860: https://icc-es.org/report-listing/esr-1860/
For more information on this product and its availability please refer to following website: http://www.
termistopusa.com/
124
PART 11 BELOW GRADE PROTECTION
Termite baits are used for controlling termite infestations rather than being a barrier to prevent termites from
penetrating a structure. There are several commercial termite bait systems available on the market including:
• Sentricon® Termite Colony Elimination System
www.sentricon.com
• BASF Trelona® Advance Termite Bait System
www.basf.com
• Ensystex EXTERRA Termite Baiting System
www.ensystex.com
• FMC FirstLine® Termite Defense System
125
PART 11 BELOW GRADE PROTECTION
126
PART 12 UTILITIES AND SERVICES INSTALLATION
Electrical Wiring
Wiring is installed in Amvic ICF walls after the concrete is poured by cutting channels in the EPS panels in which the
Romex wires are embedded. The most efficient way of cutting the channels is by using a chainsaw (hot knife can be
used as well albeit slower) with a depth stop installed. It is recommended to cut 2” (51mm) deep to reduce the risk
of nail/screws hitting the wiring during or after gypsum board installation. To maintain the continuity of the thermal
envelope, it is recommended to backfill the channels with spray foam.
127
PART 12 UTILITIES AND SERVICES INSTALLATION
The Romex wires stay embedded in the EPS panels by friction. If the channels were not fully covered with spray
foam, use spray foam adhesive to spot glue the wires to the EPS roughly every 24” (610mm) in a similar manner as
staples are used with wiring and conventional framing. Use protective nail plates over the wiring in places where it
could be hit by drywall screws.
If horizontal wiring is still needed, it is recommended to create the horizontal channels in the seam between two
horizontal courses. Since the ICF webs are only 15” (381mm) while the blocks are 16” (410mm) in height, when they
are stacked, there is a 1” (25mm) between the webs allowing for easy cutting. If an electrical fixture must be at a
given location, cutting through the webs is also acceptable but can take a little more effort if cut with something
other than a chainsaw.
128
PART 12 UTILITIES AND SERVICES INSTALLATION
DO NOT drill additional holes than what is provided in plastic electric boxes. This will void the UL/ULC rating.
129
PART 12 UTILITIES AND SERVICES INSTALLATION
If brackets for fixtures are required, concrete screws can be used to secure the brackets to the concrete.
Larger diameter plumbing pipes e.g. 3” (76 mm) or larger vents can be installed by furring out the ICF wall to
accommodate them or chases made of wood or metal in which the pipes are hidden and easily accessed for
maintenance.
It is not recommended to place plumbing pipes in the concrete cavity of ICF walls because it creates a weak spot. If
it is essential to run the pipes in the concrete cavity for architectural aesthetics, a local licensed/registered engineer
should design and/or approve such a detail.
130
PART 13 EXTERIOR AND INTERIOR FINISHES
Cabinetry
The webs in the ICF blocks serve is the nailing/fastening members in a similar way as studs. Unlike studs, the webs do
not form a continuous vertical solid surface and there could be situation where fastening screw might miss the webs.
There are several ways which this can be circumvented.
The first method involved some planning before the concrete is placed. Roughly where the upper cabinets would be
installed, two horizontal strips would need to be removed from the foam panel and replaced with two-by lumber.
The lumber would include some anchoring to the concrete (similar fashion to a door/window jamb) and once the
concrete is cured, it provides for an excellent anchoring point.
The second method can be used once the concrete is already cured and requires some sheathing boards such as OSB
or plywood. The sheathing board is installed roughly in the area where the upper cabinets will be and fastened to the
ICF webs. The sheathing board is fastened with screws roughly every 16” (410mm) and provides a solid surface to
mount the cabinets.
Shelving
Depending on the type of shelving and what is to be stored on them, they can be installed in a similar fashion to the
kitchen cabinets. Since only a strip of sheathing is required for shelf installation, it is beneficial to choose the same
thickness sheathing as the gypsum board which will allow it to be sanded and painted to uniform. For smaller areas
such as closets it might be easier to install OSB sheathing on the entire height of a wall or two and then cover it
with gypsum board. This will provide easy mounting at any height and location while maintain a smooth and clean
finished surface.
131
PART 13 EXTERIOR AND INTERIOR FINISHES
Blinds/Curtains
For curtain rods or blind installation above windows a similar methodology can be used as for the shelving. A strip of
plywood of similar thickness as the gypsum board can be installed above the window overshooting by however much
might be needed. This piece is fastened to the ICF webs and will provide a sturdy mounting surface. It can be sanded
and finished to look indistinguishable from the gypsum once painted. Alternatively, drywall anchors can be used to
mount the curtain rods or blinds.
132
PART 13 EXTERIOR AND INTERIOR FINISHES
133
PART 13 EXTERIOR AND INTERIOR FINISHES
The EPS foam that makes up the Amvic ICF panels is a suitable substrate for applying EIFS cladding directly without
the need for an additional foam board. This foamless EIFS configuration can sometimes be called DEFS (Direct
Applied Exterior Finish System in the case of DuROCK) and is essentially a proprietary acrylic stucco system.
For ICF applications, stucco-based systems can be applied in various ways. One of the easier ways is to install the
base coat with reinforcing mesh (can be metal or fiber) and then the finish coat. Although not necessarily needed, a
liquid applied weather resistive barrier might be required or even a step further, a fully drained system (EIFS). In such
cases consult the manufacturer.
• When applying EIFS cladding, always follow the manufacturer installation instructions and inspection
guidelines for proper installation.
• Check manufacturer details for sealing window and doors to ensure moisture seepage control.
• Check local building code having jurisdiction and ensure compliance with any requirements regarding EIFS
applications.
Figure 4 – Brick veneer construction with Amvic ICF Figure 5 – Stone with ICF retaining wall
134
PART 13 EXTERIOR AND INTERIOR FINISHES
Figure 6 – ICF house with siding and stucco finishes on the exterior
135
INSTALLATION MANUAL ICF
Amvic ICF is a high quality, innovative construction system designed for both residential and
commercial applications. Competitive pricing, extensive product distribution and excellent
technical support are combined to provide our clients with a simplified approach to a
superior finished product. If any questions or concerns are not completely addressed in this
manual, please contact us and our staff will be happy to answer any question. At Amvic, we
pride ourselves in offering our customers an exceptional level of customer service.
Disclaimer
Information contained in this document is provided as a guideline only, without any warranty
of any kind, either expressed or implied, including, but not limited to, the implied warranties
of merchantability, fitness for a particular purpose, and freedom of infringement.
This document is provided for informational purposes only. The information contained in this
document represents the current views of Amvic Corporation on the issues discussed as of
the date of this publication. These opinions, as expressed, should not be interpreted to be
a commitment on the part of Amvic Corporation The user assumes the entire risk as to the
accuracy and the use of this document.
This manual provides a basic guide for the installation of Amvic ICF and is intended to
supplement, rather than replace, the basic construction knowledge of a construction
professional. All installations of Amvic ICF must be in accordance with all applicable building
codes and/or under the guidance of a licensed professional engineer. In all cases, applicable
building code regulations take precedence over this manual.
Technical Support
Please contact us for any inquiries pertaining to information included in this manual, or if you
require any other technical assistance.
Email [email protected]
The Amvic website is updated regularly with the most current news, including testing
reports, technical bulletins and evaluation reports. This document is available both in print
and as a downloadable file from www.amvicsystem.com
PRO0111
www.amvicsystem.com
BUILD TO A HIGHER STANDARD