46-123 Series 3 Liquid Level Switches
46-123 Series 3 Liquid Level Switches
D E S C R I P T I O N
F E A T U R E S
• Special materials of construction available upon ASME B31.3 construction for use in refineries and
request petrochemical plants.
• Available with special coatings including Epoxy,
• Gas/oil separators • Receivers
Carbo Zinc® 11 Primer and Carboline Top Coat,
Dimetcote® and Amercoat® • Knockout drums • Flare pots
• Crude/salt water separators • Accumulators
• Optional high or low temperature insulation available
O P T I O N S
Many options are available for Series 3 level switches. Should you require an option not listed,
consult the factory for further information.
EXAMINATIONS/TESTS
MATERIALS OF
CONSTRUCTION Magnetrol is equipped to provide a full range of special
quality control testing, including:
Chambers and internal components on some models
• Dye penetration • Radiography
available in other metal alloys.
• Charpy • Magnetic particle
• 304 SS • 316 SS
• Extended hydrostatic • Ultrasonic
• Hastelloy® C • Monel
• Hardness testing
• Carpenter 20® • Duplex Stainless Steel
CHROME-MOLY
WELDING
CONSTRUCTION
Stress relieving of chamber welds is available for
The model B35 is available with a P22/F22 chrome-
flanged cage models and the model B35-7.
moly chamber and 321 SS float for high pressure
applications at high temperatures.
ACTUATING LEVELS
2
S T A N D A R D A S M E S T A N D A R D A S M E
B31.1 CONSTRUCTION B31.3 CONSTRUCTION
Pressure vessels are designed within code specified Pressure vessels are designed within code specified
stress limits. Design calculations, design prints and stress limits. Design calculations, design prints and
weld qualifications are available for audit. All chamber weld qualifications are available for audit. All chamber
branch and circumferential weld joints are designed to branch and circumferential weld joints are designed to
achieve FULL penetration. achieve FULL penetration.
WELDING WELDING
All welding is performed by qualified welders and per All welding is performed by qualified welders and per
procedures required by the ASME Boiler Pressure procedures required by the ASME Boiler Pressure
Vessel Code Sec. IX. Welds are visually inspected for Vessel Code Sec. IX. Welds are visually inspected for
FULL penetration. All other nondestructive examination FULL penetration; and 5% radiographic inspection of
is performed per ASME B31.1. weld is performed per ASME B31.3.
MATERIALS OF MATERIALS OF
CONSTRUCTION CONSTRUCTION
All pressure-retaining materials are procured with All pressure-retaining materials are procured with
Certificates of Conformance to assure compliance of Certificates of Conformance to assure compliance of
components with required standards. Chrome-Moly components with required standards.
models are post-weld heat-treated.
HYDROSTATIC TEST
HYDROSTATIC TEST
All chambers are hydrostatically tested at 1.5 times the
All chambers are hydrostatically tested at 1.5 times the design pressure.
design pressure.
S T A N D A R D N A C E C O N S T R U C T I O N
WELDING MATERIALS OF
All welding is performed by qualified welders and per CONSTRUCTION
procedures required by the ASME Boiler Pressure Only NACE listed materials are used for pressure retain-
Vessel Code Sec. IX. Carbon steel pressure boundary ing parts. Certificates of Conformance assure compliance
parts are post weld stress relieved. All welds and heat of components to required material standards.
affected zones are hardness tested to ensure compli-
ance with NACE maximum hardness requirements.
HYDROSTATIC TEST
3
T E C H N O L O G Y
retracts the magnet, deactuating the switch. Rising Level Falling Level
A G E N C Y A P P R O V A L S
AGENCY MODEL APPROVED APPROVAL CLASSES
FM All with an electric switch mechanism and a housing Class I, Div 1, Groups C & D
listed as TYPE 4X/7/9 Class II, Div 1, Groups E, F & G
All with an electric switch mechanism and a housing Class I, Div 1, Groups B, C & D
listed as TYPE 4X/7/9 Class I, Div 1, Group B Class II, Div 1, Groups E, F & G
CSA All with a Series HS, F, 8 or 9 electric switch Class I, Div 2, Groups A, B, C & D
mechanism and a housing listed as CSA TYPE 4X
All with an electric switch mechanism and a housing Class I, Div 1, Groups C & D
listed as TYPE 4X/7/9 Class II, Div 1, Groups E, F & G
All with an electric switch mechanism and a housing Class I, Div 1, Groups B, C & D
listed as TYPE 4X/7/9 Class I, Div 1, Group B Class II, Div 1, Groups E, F & G
ATEX / IEC Ex ➁ All with an electric switch mechanism and an ATEX II 2 G EEx d IIC T6
ATEX housing ➀ 94/9/EC
IEC Ex Ex d IIC T6
IP 66
CE All models Installation Category II
Pollution Degree 2
4
S P E C I F I C A T I O N S
S W I T C H M E C H A N I S M S A N D E N C L O S U R E S
SERIES B, C, D & R DRY CONTACT SWITCHES SERIES F, HS, 8 & 9 HERMETICALLY SEALED SWITCHES
• Designs for AC and DC current applications • Ideal for use in salt and other corrosive atmospheres
• Process temperatures to +1000 °F (+538 °C) • HS is a positively pressurized capsule for entire
mechanism and contacts
• Process temperatures to +1000 °F (+538 °C)
5
A S M E B 3 1 . 1 A C T U A T I N G L E V E L S
For float operated units, levels are dependent upon the NOTE: Actuation levels for saturate steam service ratings are
shown for single switch units with 1" process connections only.
specific gravity of the process media. Consult factory for units with two and three set point and 11⁄2" or 2"
process connections.
SATURATED STEAM SERVICE RATINGS (See model selection charts for maximum ratings)
ASME B31.1 SEALED CAGE MODELS WITH 1" PROCESS CONNECTIONS
INCHES MILLIMETERS
Sealed Actuation Levels Sealed Actuation Levels
Cage Pressure Temperature Specific Cage Pressure Temperature Specific
(psig) (° F) Gravity HL LL (bar) (° C) Gravity HL LL
Models Models
B35 812 520 0.76 3.33 3.91 B35 56 271 0.76 85 99
C35 379 443 0.83 4.05 4.57 C35 26 227 0.83 103 116
G35 546 476 0.80 4.33 4.77 G35 38 247 0.80 110 121
V35 1044 550 0.74 3.19 3.81 V35 72 288 0.74 81 97
Z35 1113 558 0.73 3.39 3.97 Z35 77 292 0.73 86 101
Levels ± 0.25" (6 mm) Levels ± 0.25" (6 mm)
A S M E B 3 1 . 3 D I S P L A C E R M O D E L S
A S M E B 3 1 . 3 D I S P L A C E R M O D E L S
(Displacer Models cont. from page 6)
DISPLACER MODELS WITH 1" PROCESS CONNECTIONS – MILLIMETERS
Liquid Specific Gravity
Model Process 0.40 0.50 0.60 0.70 0.80 0.90 1.00
Code Temp. ° C HL LL HL LL HL LL HL LL HL LL HL LL HL LL
38 33 121 55 127 69 131 80 134 87 136 93 138 98 140
B34 93 31 119 54 126 69 130 79 133 87 136 93 137 98 139
149 30 117 53 124 68 129 78 132 86 135 92 137 98 138
38 116 214 146 227 167 235 181 241 191 246 200 249 207 252
93 106 205 140 219 160 229 176 235 187 241 195 245 203 248
C34 149 97 194 132 210 154 221 170 229 183 235 191 240 198 243
205 n/a n/a 122 200 146 213 164 222 176 229 186 235 194 238
260 n/a n/a 113 189 138 203 157 214 170 222 181 229 189 233
Levels ± 0.25" (6 mm)
7
D I M E N S I O N A L S P E C I F I C A T I O N S
I N C H E S ( m m )
M
ASME B31.1 & B31.3 SEALED CAGE MODELS
L
All housings rotatable 360°.
Allow 8 inches (203 mm) overhead clearance
for cover removal. NEMA 1: 8.50 (216)
TYPE 4X/7/9: 10.12 (257)
Group B: 10.12 (257)
K K
Conduit Connections K Plugged
Electrical Switches
TYPE 4X/7/9: 1" NPT
Group B: 1" NPT
Pneumatic Switches
NEMA 1: 1
⁄4" NPT
HL
(Ref) C
Outline LL
L M
Dimensions
TYPE4X/7/9
4.29 5.93 A
TYPE4X/7/9
(108) (151)
Group B
5.00 4.62
NEMA 1
(127) (117)
M
L
M
L
K K
Plugged
K K
Plugged
HL
(Ref) J LL
HL
LL
(Ref) F
G
H E
Flanged Flanged
Side/Side Upper Side/Bottom
8
D I M E N S I O N A L S P E C I F I C A T I O N S
SEALED CAGE MODELS — ASME B31.1 150# & 300# ANSI PRESSURE RATINGS
ASME B31.3 ALL PRESSURE RATINGS
9
D I M E N S I O N A L S P E C I F I C A T I O N S
I N C H E S ( mm )
M
ASME B31.1 & B31.3 SEALED CAGE MODELS
L
All housings rotatable 360°.
Allow 8 inches (203 mm) overhead clearance
for cover removal. NEMA 1: 8.50 (216)
TYPE 4X/7/9: 10.12 (257)
Group B: 10.12 (257)
K K
Conduit Connections K Plugged
Electrical Switches
TYPE 4X/7/9: 1" NPT
Group B: 1" NPT
Pneumatic Switches
NEMA 1: 1
⁄4" NPT
HL
(Ref) C
Outline LL
L M
Dimensions
TYPE4X/7/9
4.29 5.93 A
TYPE4X/7/9
(108) (151)
Group B
5.00 4.62
NEMA 1
(127) (117)
M
L
M
L
K K
Plugged
K K
Plugged
HL
(Ref) J LL
HL
LL
(Ref) F
G
H E
Flanged Flanged
Side/Side Upper Side/Bottom
10
D I M E N S I O N A L S P E C I F I C A T I O N S
ASME B31.1 SEALED CAGE MODELS — 600# & 900# ANSI PRESSURE RATINGS
CHAMBERS WITH 1- INCH CONNECTIONS — 600 & 900 LB. ANSI CLASS
INCHES MILLIMETERS
1" NPT
1" NPT Threaded & 1" Flanged 1" Flanged 1" Flanged 1" Flanged
Thread &
Socket Weld Upper Side/Bottom Side/Side Upper Side/Bottom Side/Side
Model Socket Weld
Code D F G J D F G J
A B C E H A B C E H
14" 16" 14" 16" 14" 16" 14" 16" 14" 16" 14" 16" 14" 16" 14" 16"
B35 8.92 4.15 15.12 14.00 — 9.00 20.20 — 14.00 — 9.00 20.20 — 227 105 384 356 — 229 513 — 356 — 229 513 —
C35 8.92 4.15 15.12 14.00 — 9.00 20.20 — 14.00 — 9.00 20.20 — 227 105 384 356 — 229 513 — 356 — 229 513 —
G35 9.80 4.69 16.17 — 16.00 10.00 — 22.36 — 16.00 10.00 — 22.36 249 119 410 — 406 254 — 568 — 406 254 — 568
V35 8.92 4.15 15.12 14.00 — 9.00 20.20 — 14.00 — 9.00 20.20 — 227 105 384 356 — 229 513 — 356 — 229 513 —
Z35 9.80 4.69 16.17 — 16.00 10.00 — 22.36 — 16.00 10.00 — 22.36 249 119 410 — 406 254 — 568 — 406 254 — 568
CHAMBERS WITH 112⁄ - INCH CONNECTIONS — 600 & 900 LB. ANSI CLASS
INCHES MILLIMETERS
11⁄2" NPT
11⁄2" NPT Threaded 11⁄2" Flanged 11⁄2" Flanged 11⁄2" Flanged 11⁄2" Flanged
Thread &
& Socket Weld Upper Side/Bottom Side/Side Upper Side/Bottom Side/Side
Model Socket Weld
Code D F G J D F G J
A B C E H A B C E H
14" 16" 14" 16" 14" 16" 14" 16" 14" 16" 14" 16" 14" 16" 14" 16"
B35 8.92 4.22 15.12 14.00 — 9.00 20.20 — 14.00 — 9.00 20.20 — 227 107 384 356 — 229 513 — 356 — 229 513 —
C35 8.92 4.22 15.12 14.00 — 9.00 20.20 — 14.00 — 9.00 20.20 — 227 107 384 356 — 229 513 — 356 — 229 513 —
G35 9.80 4.75 16.17 — 16.00 10.00 — 22.36 — 16.00 10.00 — 22.36 249 121 410 — 406 254 — 568 — 406 254 — 568
V35 8.92 4.22 15.12 14.00 — 9.00 20.20 — 14.00 — 9.00 20.20 — 227 107 384 356 — 229 513 — 356 — 229 513 —
Z35 9.80 4.75 16.17 — 16.00 10.00 — 22.36 — 16.00 10.00 — 22.36 249 121 410 — 406 254 — 568 — 406 254 — 568
CHAMBERS WITH 2 - INCH CONNECTIONS — 600 & 900 LB. ANSI CLASS
INCHES MILLIMETERS
2" NPT
2" NPT Threaded & 2" Flanged 2" Flanged 2" Flanged 2" Flanged
Thread &
Socket Weld Upper Side/Bottom Side/Side Upper Side/Bottom Side/Side
Model Socket Weld
Code D F G J D F G J
A B C E H A B C E H
14" 16" 14" 16" 14" 16" 14" 16" 14" 16" 14" 16" 14" 16" 14" 16"
B35 8.92 4.34 15.12 14.00 — 9.00 20.20 — 14.00 — 9.00 20.20 — 227 110 384 356 — 229 513 — 356 — 229 513 —
C35 8.92 4.34 15.12 14.00 — 9.00 20.20 — 14.00 — 9.00 20.20 — 227 110 384 356 — 229 513 — 356 — 229 513 —
G35 9.80 4.88 16.17 — 16.00 10.00 — 22.36 — 16.00 10.00 — 22.36 249 124 410 — 406 254 — 568 — 406 254 — 568
V35 8.92 4.34 15.12 14.00 — 10.00 20.20 — 14.00 — 10.00 20.20 — 227 110 384 356 — 254 513 — 356 — 254 513 —
Z35 9.80 4.88 16.17 — 16.00 10.00 — 22.36 — 16.00 10.00 — 22.36 249 124 410 — 406 254 — 568 — 406 254 — 568
11
D I M E N S I O N A L S P E C I F I C A T I O N S
I N C H E S ( m m )
M
L
ASME B31.1 & B31.3 FLANGED CAGE MODELS
All housings rotatable 360°.
NEMA 1: 8.50 (216)
Allow 8 inches (203 mm) overhead clearance TYPE 4X/7/9: 10.12 (257)
Group B: 10.12 (257)
for cover removal. K K
Plugged
Conduit Connections K
Electrical Switches
TYPE 4X/7/9: 1" NPT
Group B: 1" NPT HL
LL
Pneumatic Switches (Ref) C
NEMA 1: 1
⁄4" NPT
A
Outline
L M
Dimensions
TYPE4X/7/9
3.87 5.93
TYPE4X/7/9 B
(98) (151)
Group B
5.00 4.62
NEMA 1
(127) (117)
Threaded and Socket Weld
Upper Side/Bottom
M M
L L M
L
K K K K Plugged
Plugged K
K
Plugged
K
HL HL
LL LL HL
(Ref) J
(Ref) F LL
(Ref) J
G
G D
12
D I M E N S I O N A L S P E C I F I C A T I O N S
FLANGED CAGE MODELS — ASME B31.1 150# & 300# ANSI PRESSURE RATINGS
ASME B31.3 ALL PRESSURE RATINGS
CHAMBERS WITH 1- INCH CONNECTIONS
INCHES MILLIMETERS
Head 1" NPT Threaded 1" Flanged 1" Flanged 1" NPT Thread 1" Flanged 1" Flanged
Model Flg. & Socket Weld Upper Side/Bottom Side/Side & Socket Weld Upper Side/Bottom Side/Side
Code rating D F G J D F G J
(lbs.) A B C E H A B C E H
Std. 14" Std. 14" Std. 14" Std. 14" Std. 14" Std. 14" Std. 14" Std. 14"
300 15.63 3.13 22.59 18.33 21.68 5.45 25.29 28.64 18.97 14.00 5.45 25.93 28.64 397 80 574 466 551 138 642 727 482 356 138 659 727
C34
600 15.63 3.13 22.97 18.33 21.68 5.45 25.66 29.00 18.97 14.00 5.45 26.30 29.00 397 80 583 466 551 138 351 737 482 356 138 668 737
150 9.12 3.63 16.64 12.06 14.00 6.13 19.58 21.51 12.71 14.00 6.13 20.23 21.51 232 92 423 306 356 156 497 546 323 356 156 514 546
B3F 300 9.12 3.63 17.32 12.06 14.00 6.13 20.26 22.19 12.71 14.00 6.13 20.91 22.19 232 92 440 306 356 156 515 564 323 356 156 531 564
600 9.12 3.63 18.45 12.06 14.00 6.13 21.39 23.32 12.71 14.00 6.13 22.04 23.32 232 92 469 306 356 156 543 592 323 356 156 560 592
150 10.12 4.69 18.30 13.06 14.00 7.19 21.25 22.19 13.71 14.00 7.19 21.89 22.19 257 119 465 332 356 183 540 564 348 356 183 556 564
G3F 300 10.12 4.69 19.12 13.06 14.00 7.19 22.06 23.00 13.71 14.00 7.19 22.71 23.00 257 119 486 332 356 183 560 584 348 356 183 577 584
600 10.12 4.69 20.56 13.06 14.00 7.19 23.50 24.44 13.71 14.00 7.19 24.15 24.43 257 119 522 332 356 183 597 621 348 356 183 613 621
600 10.11 4.68 20.19 13.06 14.00 7.19 23.14 24.08 13.71 14.00 7.19 23.79 24.08 257 119 513 332 356 183 588 612 348 356 183 604 612
Z3F
900 10.11 4.68 21.13 13.06 14.00 7.19 23.14 25.37 13.71 14.00 7.19 23.79 24.08 257 119 537 332 356 183 588 612 348 356 183 604 612
D F G J D F G J
A B C E H A B C E H
Std. 16" Std. 16" Std. 16" Std. 16" Std. 16" Std. 16" Std. 16" Std. 16"
150 11.62 5.69 20.38 14.56 16.00 8.19 23.33 24.77 15.21 16.00 8.19 23.98 24.77 295 145 518 370 406 208 593 629 386 406 208 609 629
K3F 300 11.62 5.69 21.25 14.56 16.00 8.19 24.20 25.64 15.21 16.00 8.19 24.85 25.64 295 145 540 370 406 208 615 651 386 406 208 631 651
600 11.62 5.69 22.93 14.56 16.00 8.19 25.88 27.32 15.21 16.00 8.19 26.53 27.32 295 145 582 370 406 208 657 694 386 406 208 674 694
*See page 15 for ASME B31.1 600# dimensional information.
CHAMBERS WITH 112⁄ - INCH CONNECTIONS
INCHES MILLIMETERS
Head 11⁄2" NPT Threaded 11⁄2" Flanged 11⁄2" Flanged 11⁄2" NPT Thread 11⁄2" Flanged 11⁄2" Flanged
Model Flg. & Socket Weld Upper Side/Bottom Side/Side & Socket Weld Upper Side/Bottom Side/Side
Code rating D F G J D F G J
(lbs.) A B C
Std. 14"
E
Std. 14" Std. 14"
H
Std. 14"
A B C
Std. 14"
E
Std. 14" Std. 14"
H
Std. 14"
300 15.63 3.19 22.59 18.33 21.68 6.19 25.29 28.64 18.97 14.00 6.19 25.93 28.64 397 81 574 466 551 157 642 727 482 356 157 659 727
C34
600 15.63 3.19 22.97 18.33 21.68 6.19 25.66 29.00 18.97 14.00 6.19 26.30 29.00 397 81 583 466 551 157 351 737 482 356 157 668 737
150 9.12 3.69 16.64 13.06 14.00 7.13 20.58 21.51 13.71 14.00 7.13 21.23 21.51 232 94 423 332 356 181 523 546 348 356 181 539 546
B3F 300 9.12 3.69 17.32 13.06 14.00 7.13 21.26 22.19 13.71 14.00 7.13 21.91 22.19 232 94 440 332 356 181 540 564 348 356 181 556 564
600 9.12 3.69 18.45 13.06 14.00 7.13 22.39 23.32 13.71 14.00 7.13 23.04 23.32 232 94 469 332 356 181 568 592 348 356 181 585 592
150 10.12 4.75 18.30 14.06 14.00 8.19 22.25 22.19 14.71 14.00 8.19 22.89 22.19 257 121 465 357 356 208 564 563 374 356 208 581 564
G3F 300 10.12 4.75 19.12 14.06 14.00 8.19 23.06 23.00 14.71 14.00 8.19 23.71 23.00 257 121 486 357 356 208 586 584 374 356 208 602 584
600 10.12 4.75 20.56 14.06 14.00 8.19 24.50 24.44 14.71 14.00 8.19 25.15 24.44 257 121 522 357 356 208 622 621 374 356 208 639 621
600 10.11 4.75 20.19 14.06 14.00 8.18 24.14 24.08 14.71 14.00 8.18 24.79 24.08 257 121 513 357 356 208 613 612 374 356 208 630 612
Z3F
900 10.11 4.75 21.13 14.06 14.00 8.18 24.14 24.08 14.71 14.00 8.18 24.79 24.08 257 121 537 357 356 208 613 612 374 356 208 630 612
D F G J D F G J
A B C E H A B C E H
Std. 16" Std. 16" Std. 16" Std. 16" Std. 16" Std. 16" Std. 16" Std. 16"
150 11.62 5.75 20.38 15.56 16.00 9.19 24.33 24.77 16.21 16.00 9.19 24.98 24.77 295 146 518 395 406 233 618 629 412 406 233 634 629
K3F 300 11.62 5.75 21.25 15.56 16.00 9.19 25.50 25.64 16.21 16.00 9.19 25.85 25.64 295 146 540 395 406 233 648 651 412 406 233 657 651
600 11.62 5.75 22.93 15.56 16.00 9.19 26.88 27.32 16.21 16.00 9.19 27.53 27.32 295 146 582 395 406 233 683 694 412 406 233 699 694
*See page 15 for ASME B31.1 600# dimensional information.
CHAMBERS WITH 2 - INCH CONNECTIONS
INCHES MILLIMETERS
Head 2" NPT Threaded 2" Flanged 2" Flanged 2" NPT Thread 2" Flanged 2" Flanged
Model Flg. & Socket Weld Upper Side/Bottom Side/Side & Socket Weld Upper Side/Bottom Side/Side
Code rating D F G J D F G J
(lbs.) A B C
Std. 14"
E
Std. 14" Std. 14"
H
Std. 14"
A B C
Std. 14"
E
Std. 14" Std. 14"
H
Std. 14"
300 15.63 3.31 22.59 18.33 21.68 6.25 25.29 28.64 18.97 14.00 6.25 25.93 28.64 397 84 574 466 551 159 642 727 482 356 159 659 727
C34
600 15.63 3.31 22.97 18.33 21.68 6.25 25.66 29.00 18.97 14.00 6.25 26.30 29.00 397 84 583 466 551 159 351 737 482 356 159 668 737
150 9.12 3.81 16.64 13.06 14.00 7.13 20.58 21.51 13.71 14.00 7.13 21.23 21.51 232 97 423 332 356 181 523 546 348 356 181 539 546
B3F 300 9.12 3.81 17.32 13.06 14.00 7.13 21.26 22.19 13.71 14.00 7.13 21.91 22.19 232 97 440 332 356 181 540 564 348 356 181 556 564
600 9.12 3.81 18.45 13.06 14.00 7.13 22.39 23.32 13.71 14.00 7.13 23.04 23.32 232 97 469 332 356 181 569 592 348 356 181 585 592
150 10.12 4.88 18.30 14.06 14.00 8.19 22.25 22.19 14.71 14.00 8.19 22.89 22.19 257 124 465 357 356 208 565 564 374 356 208 581 564
G3F 300 10.12 4.88 19.12 14.06 14.00 8.19 23.06 23.00 14.71 14.00 8.19 23.71 23.00 257 124 486 357 356 208 586 584 374 356 208 602 584
600 10.12 4.88 20.56 14.06 14.00 8.19 24.50 24.44 14.71 14.00 8.19 25.15 24.44 257 124 522 357 356 208 622 621 374 356 208 639 621
600 10.11 4.87 20.19 14.06 14.00 8.18 24.14 24.08 14.71 14.00 8.18 24.79 24.08 257 124 513 357 356 208 613 612 374 356 208 630 612
Z3F
900 10.11 4.87 21.13 14.06 14.00 8.18 24.14 24.08 14.71 14.00 8.18 24.79 24.08 257 124 537 357 356 208 613 612 374 356 208 630 612
D F G J D F G J
A B C E H A B C E H
Std. 16" Std. 16" Std. 16" Std. 16" Std. 16" Std. 16" Std. 16" Std. 16"
150 11.62 5.88 20.38 15.56 16.00 9.19 24.33 24.77 16.21 16.00 9.19 24.98 24.77 295 149 518 395 406 233 618 629 412 406 233 634 629
K3F 300 11.62 5.88 21.25 15.56 16.00 9.19 25.50 25.64 16.21 16.00 9.19 25.85 25.64 295 149 540 395 406 233 648 651 412 406 233 657 651
600 11.62 5.88 22.93 15.56 16.00 9.19 26.88 27.32 16.21 16.00 9.19 27.53 27.32 295 149 582 395 406 233 683 694 412 406 233 699 694
*See page 15 for ASME B31.1 600# dimensional information.
13
D I M E N S I O N A L S P E C I F I C A T I O N S
I N C H E S ( m m )
M
ASME B31.1 & B31.3 FLANGED CAGE MODELS L
Conduit Connections K
Electrical Switches
TYPE 4X/7/9: 1" NPT
Group B: 1" NPT
Pneumatic Switches
NEMA 1: 1
⁄4" NPT HL
LL
(Ref) C
Outline A
L M
Dimensions
TYPE4X/7/9
3.87 5.93
TYPE4X/7/9
(98) (151)
Group B
5.00 4.62
NEMA 1
(127) (117) B
M
L
M
L
K K
Plugged
K K
K
Plugged
HL
LL
HL
(Ref) J LL
(Ref) F
G
H E
Flanged Flanged
Side/Side Upper Side/Bottom
14
D I M E N S I O N A L S P E C I F I C A T I O N S
FLANGED CAGE MODELS — ASME B31.1 600# & 900# ANSI PRESSURE RATING
15
A S M E B 3 1 . 1 M O D E L N U M B E R S
S E A L E D C A G E M O D E L S Models available for quick shipment, usually within one
week after factory receipt of a complete purchase order,
MODEL NUMBER CODE through the Expedite Ship Plan (ESP)
MATERIALS OF CONSTRUCTION
P Carbon steel chamber, 316L stainless steel float, 400 series stainless steel sleeve, ASME B31.1 Construction
7 P22/F22 Chrome-Moly chamber, 347 SS float, 400 series SS sleeve, ASME B31.1 Construction, model B35 only
16
ELECTRIC SWITCH MECHANISM AND ENCLOSURE
Models B35, C35 & G35 Models V35 & Z35
Process ➄ ≈
Switch Temperature Set TYPE 4X/7/9 Aluminum Enclosure
Range Contacts
Description Points Class I, Div 1 Class I, Div 1 ATEX ATEX
Class I, Div 1 Class I, Div 1
°F (°C) Ex II 2 G EEx Ex II 2 G EEx
Groups C&D Group B Groups C&D Group B
d IIC T6 d IIC T6
1 BKA BKJ BCC BKB BKK BC9
SPDT 2 BLA BLJ BDC BLB BLK BD9
Series B -40 to +250
3 BMA BMJ BEC BMB BMK BE9
Snap Switch (-40 to +121)
1 BNA BNJ BFC BNB BNK BF9
DPDT
2 BOA BOJ BGC BOB BOK BG9
1 CKA CKJ CCC CKB CKK CC9
SPDT 2 CLA CLJ CDC CLB CLK CD9
Series C -40 to +450
3 CMA CMJ CEC CMB CMK CE9
Snap Switch (-40 to +232)
1 CNA CNJ CFC CNB CNK CF9
DPDT
2 COA COJ CGC COB COK CG9
1 DKB DKK DC9 DKB DKK DC9
SPDT 2 DLB DLK DD9 DLB DLK DD9
Series D DC Current -40 to +250
3 DMB DMK DE9 DMB DMK DE9
Snap Switch (-40 to +121)
1 DNB DNK DF9 DNB DNK DF9
DPDT
2 DOB DOK DG9 DOB DOK DG9
1 FKA FKJ FCC FKB FKK FC9
Series F SPDT
-50 to +750 2 FLA FLJ FDC FLB FLK FD9
Hermetically Sealed
(-46 to +399) 1 FNA FNJ FFC FNB FNK FF9
Snap Switch DPDT
2 FOA FOJ FGC FOB FOK FG9
Series HS 1 HMJ HMK HMJ HMK
-50 to +400 SPDT
Hermetically Sealed 2 HMN HMP HMN HMP
(-46 to +204) N/A N/A
∆
5-amp Snap Switch 1 HMS HMT HMS HMT
with Wiring Leads DPDT
2 HMY HMZ HMY HMZ
Series HS SPDT 1 HM3 HM4 HA9 HM3 HM4 HA9
-50 to +400
Hermetically Sealed
(-46 to +204)
∆
5-amp Snap Switch
with Terminal Block DPDT 1 HM7 HM8 HB9 HM7 HM8 HB9
1 RKB RKK RC9 RKB RKK RC9
Series R SPDT
-40 to +750 2 RLB RLK RD9 RLB RLK RD9
High Temperature
(-40 to +399) 1 RNB RNK RF9 RNB RNK RF9
Snap Switch DPDT
2 ROB ROK RG9 ROB ROK RG9
1 8KA 8KJ 8CC 8KB 8KK 8C9
Series 8 SPDT 2 8LA 8LJ 8DC 8LB 8LK 8D9
-50 to +750
Hermetically Sealed 3 8MA 8MJ 8EC 8MB 8MK 8E9
(-46 to +399)
Snap Switch 1 8NA 8NJ 8FC 8NB 8NK 8F9
DPDT
2 8OA 8OJ 8GC 8OB 8OK 8G9
1 9KA 9KJ 9CC 9KB 9KK 9C9
Series 9 SPDT 2 9LA 9LJ 9DC 9LB 9LK 9D9
High Temperature -50 to +750
3 9MA 9MJ 9EC 9MB 9MK 9E9
Hermetically Sealed (-46 to +399)
Snap Switch 1 9NA 9NJ 9FC 9NB 9NK 9F9
DPDT
2 9OA 9OJ 9GC 9OB 9OK 9G9
Process ➄ ≈ CS/Aluminum Cast Iron CS/Aluminum Cast Iron
Switch Temp. Range Contacts Set
Description Points Class I, Div 1 Class I, Div 1 Class I, Div 1 Class I, Div 1
°F (°C) NEMA 4X NEMA 4X
Groups C&D Group B Groups C&D Group B
1 R1M RKM RKW
Series R -40 to +1000 SPDT
2 R3M RLM RLW
High Temperature (-40 to +538) N/A N/A
Snap Switch ➇ DPDT
1 RDM RNM RNW
2 REM ROM ROW
1 9AD 9KD 9KV 9AM 9KM 9KW
Series 9 SPDT 2 9BD 9LD 9LV 9BM 9LM 9LW
-50 to +1000
High Temperature
(-46 to +538) 3 9CD 9MD 9MV 9CM 9MM 9MW
➇
Hermetically Sealed
Snap Switch 1 9DD 9ND 9NV 9DM 9NM 9NW
DPDT
2 9ED 9OD 9OV 9EM 9OM 9OW
17
A S M E B 3 1 . 1 M O D E L N U M B E R S
F L A N G E D C A G E M O D E L S Models available for quick shipment, usually within one
week after factory receipt of a complete purchase
MODEL NUMBER CODE order, through the Expedite Ship Plan (ESP)
Minimum Pressure Rating
Model Head S.G.
Code Flange Gravity ➁ psig @ ° F bar @ ° C
➀ ANSI Class
1 100 550 750 800 38 288 399 427
150# 0.78 285 155 95 80 19.6 10.7 6.5 5.5
B3F 300# 0.66 740 588 505 410 51.0 39.6 34.8 28.3
600# 0.66 1000 875 805 795 68.9 60.3 55.5 54.8
150# 0.41 285 155 95 80 19.6 10.7 6.5 5.5
G3F 300# 0.55 740 588 505 410 51.0 45.0 41.4 28.3
600# 0.70 1000 875 805 795 68.9 60.3 55.5 54.8
K3F ➂ 600# 0.60 1480 1170 1015 825 102.0 80.7 70.0 56.9
Z3F ➂
600# 1480 1170 1015 825 102.0 80.7 70.0 56.9
0.67
900# 2044 1913 1554 1291 140.9 131.9 107.1 89.0
MATERIALS OF CONSTRUCTION
P Carbon steel chamber, 316L stainless steel float, 400 stainless steel sleeve, ASME B31.1 Construction
18
ELECTRIC SWITCH MECHANISM AND ENCLOSURE
All models except B3F, G3F, K3F & Z3F Models B3F, G3F, K3F & Z3F
Process ≈ ∆ with 600# or 900# ANSI ratings with 600# or 900# ANSI ratings
Switch Temperature Set TYPE 4X/7/9 Aluminum Enclosure
Range Contacts
Description Points ATEX ATEX
°F (°C) Class I, Div 1 Class I, Div 1 Class I, Div 1 Class I, Div 1
Ex II 2 G EEx Ex II 2 G EEx
Groups C&D Group B Groups C&D Group B
d IIC T6 d IIC T6
1 BKA BKJ BCC BKB BKK BC9
SPDT 2 BLA BLJ BDC BLB BLK BD9
Series B -40 to +250
3 BMA BMJ BEC BMB BMK BE9
Snap Switch (-40 to +121)
1 BNA BNJ BFC BNB BNK BF9
DPDT
2 BOA BOJ BGC BOB BOK BG9
1 CKA CKJ CCC CKB CKK CC9
SPDT 2 CLA CLJ CDC CLB CLK CD9
Series C -40 to +450
3 CMA CMJ CEC CMB CMK CE9
Snap Switch (-40 to +232)
1 CNA CNJ CFC CNB CNK CF9
DPDT
2 COA COJ CGC COB COK CG9
1 DKB DKK DC9 DKB DKK DC9
SPDT 2 DLB DLK DD9 DLB DLK DD9
Series D DC Current -40 to +250
3 DMB DMK DE9 DMB DMK DE9
Snap Switch (-40 to +121)
1 DNB DNK DF9 DNB DNK DF9
DPDT
2 DOB DOK DG9 DOB DOK DG9
1 FKA FKJ FCC FKB FKK FC9
Series F SPDT
-50 to +750 2 FLA FLJ FDC FLB FLK FD9
Hermetically Sealed
(-46 to +399) 1 FNA FNJ FFC FNB FNK FF9
Snap Switch DPDT
2 FOA FOJ FGC FOB FOK FG9
Series HS ➇ SPDT
1 HMJ HMK HMJ HMK
Hermetically Sealed -50 to +400 2 HMN HMP HMN HMP
N/A N/A
5-amp Snap Switch (-46 to +204) 1 HMS HMT HMS HMT
with Wiring Leads DPDT
2 HMY HMZ HMY HMZ
Series HS ➇ SPDT 1 HM3 HM4 HA9 HM3 HM4 HA9
Hermetically Sealed -50 to +400
5-amp Snap Switch (-46 to +204)
with Terminal Block DPDT 1 HM7 HM8 HB9 HM7 HM8 HB9
1 RKB RKK RC9 RKB RKK RC9
Series R SPDT
-40 to +750 2 RLB RLK RD9 RLB RLK RD9
High Temperature
(-40 to +399) 1 RNB RNK RF9 RNB RNK RF9
Snap Switch DPDT
2 ROB ROK RG9 ROB ROK RG9
1 8KA 8KJ 8CC 8KB 8KK 8C9
Series 8 SPDT 2 8LA 8LJ 8DC 8LB 8LK 8D9
-50 to +750
Hermetically Sealed 3 8MA 8MJ 8EC 8MB 8MK 8E9
(-46 to +399)
Snap Switch 1 8NA 8NJ 8FC 8NB 8NK 8F9
DPDT
2 8OA 8OJ 8GC 8OB 8OK 8G9
1 9KA 9KJ 9CC 9KB 9KK 9C9
Series 9 SPDT 2 9LA 9LJ 9DC 9LB 9LK 9D9
High Temperature -50 to +750
3 9MA 9MJ 9EC 9MB 9MK 9E9
Hermetically Sealed (-46 to +399)
Snap Switch 1 9NA 9NJ 9FC 9NB 9NK 9F9
DPDT
2 9OA 9OJ 9GC 9OB 9OK 9G9
Process ≈ ∆ CS/Aluminum Cast Iron CS/Aluminum Cast Iron
Switch Temp. Range Contacts Set
Description Points Class I, Div 1 Class I, Div 1 Class I, Div 1 Class I, Div 1
°F (°C) NEMA 4X NEMA 4X
Groups C&D Group B Groups C&D Group B
1 R1M RKM RKW
Series R -40 to +1000 SPDT
2 R3M RLM RLW
High Temperature (-40 to +538) N/A N/A
Snap Switch ➈ DPDT
1 RDM RNM RNW
2 REM ROM ROW
1 9AD 9KD 9KV 9AM 9KM 9KW
Series 9 SPDT 2 9BD 9LD 9LV 9BM 9LM 9LW
-50 to +1000
High Temperature
(-46 to +538) 3 9CD 9MD 9MV 9CM 9MM 9MW
➈
Hermetically Sealed
Snap Switch 1 9DD 9ND 9NV 9DM 9NM 9NW
DPDT
2 9ED 9OD 9OV 9EM 9OM 9OW
19
A S M E B 3 1 . 3 M O D E L N U M B E R S
S E A L E D C A G E M O D E L S Models available for quick shipment, usually within one
week after factory receipt of a complete purchase
MODEL NUMBER CODE order, through the Expedite Ship Plan (ESP)
Min. S.G. for Models Pressure Rating
Model with Material of
Code Construction Code ➁ psig @ °F bar @ °C
➀
1 2 100 550 750 800 900 1000 38 288 399 427 482 538
FLOAT MODELS
B35 0.69 0.72 1000 875 805 795 428 181 68.9 60.3 55.5 54.8 29.5 12.5
C35 0.57 0.59 500 438 403 398 390 181 34.5 30.2 27.8 27.4 26.9 12.5
G35 0.54 0.56 750 656 604 596 393 167 51.7 45.2 41.6 41.1 27.1 11.5
K35 ➂ 0.40 0.40 600 525 483 477 353 150 41.4 36.2 33.3 32.9 24.3 10.3
L35 0.41 0.43 300 263 242 239 234 167 20.7 18.1 16.7 16.4 16.1 11.5
V35 ➃ 0.71 0.81 2250 1913 1720 1411 730 n/a 155.1 131.9 118.6 97.3 50.3 n/a
Z35 ➃ 0.66 0.71 2250 1913 1662 1363 705 n/a 155.1 131.9 114.6 94.0 48.6 n/a
DISPLACER MODEL 100 200 300 38 93 149
B34 ➂≈➄
n/a n/a
0.40 0.40 1300 1225 1145 89.6 84.4 78.9
MATERIALS OF CONSTRUCTION
1 Carbon steel chamber, 316L stainless steel float, 400 stainless steel sleeve, ASME B31.3 construction
2 Carbon steel chamber, 316L stainless steel float, 316 stainless steel sleeve, ASME B31.3 construction
20
ELECTRIC SWITCH MECHANISM AND ENCLOSURE
Models B35, C35, K35 & L35 Models B34, V35, Z35 & all models
Process ➇ with Material of Construction Code 1 with Material of Construction Code 2
Switch Temperature Set TYPE 4X/7/9 Aluminum Enclosure
Range Contacts
Description Points ATEX ATEX
°F (°C) Class I, Div 1 Class I, Div 1 Class I, Div 1 Class I, Div 1
Ex II 2 G EEx Ex II 2 G EEx
Groups C&D Group B Groups C&D Group B
d IIC T6 d IIC T6
1 BKA BKJ BCC BKB BKK BC9
SPDT 2 BLA BLJ BDC BLB BLK BD9
Series B -40 to +250
3 BMA BMJ BEC BMB BMK BE9
Snap Switch (-40 to +121)
1 BNA BNJ BFC BNB BNK BF9
DPDT
2 BOA BOJ BGC BOB BOK BG9
1 CKA CKJ CCC CKB CKK CC9
SPDT 2 CLA CLJ CDC CLB CLK CD9
Series C -40 to +450
3 CMA CMJ CEC CMB CMK CE9
Snap Switch (-40 to +232)
1 CNA CNJ CFC CNB CNK CF9
DPDT
2 COA COJ CGC COB COK CG9
1 DKB DKK DC9 DKB DKK DC9
SPDT 2 DLB DLK DD9 DLB DLK DD9
Series D DC Current -40 to +250
3 DMB DMK DE9 DMB DMK DE9
Snap Switch (-40 to +121)
1 DNB DNK DF9 DNB DNK DF9
DPDT
2 DOB DOK DG9 DOB DOK DG9
1 FKA FKJ FCC FKB FKK FC9
Series F SPDT
-50 to +750 2 FLA FLJ FDC FLB FLK FD9
Hermetically Sealed
(-46 to +399) 1 FNA FNJ FFC FNB FNK FF9
Snap Switch DPDT
2 FOA FOJ FGC FOB FOK FG9
Series HS ➈ SPDT
1 HMJ HMK HMJ HMK
-50 to +550
Hermetically Sealed 2 HMN HMP HMN HMP
(-46 to +288) N/A N/A
➉
5-amp Snap Switch 1 HMS HMT HMS HMT
with Wiring Leads DPDT
2 HMY HMZ HMY HMZ
Series HS ➈ SPDT 1 HM3 HM4 HA9 HM3 HM4 HA9
-50 to +550
Hermetically Sealed
(-46 to +288)
➉
5-amp Snap Switch
with Terminal Block DPDT 1 HM7 HM8 HB9 HM7 HM8 HB9
1 RKB RKK RC9 RKB RKK RC9
Series R SPDT
-40 to +750 2 RLB RLK RD9 RLB RLK RD9
High Temperature
(-40 to +399) 1 RNB RNK RF9 RNB RNK RF9
Snap Switch DPDT
2 ROB ROK RG9 ROB ROK RG9
1 8KA 8KJ 8CC 8KB 8KK 8C9
Series 8 SPDT 2 8LA 8LJ 8DC 8LB 8LK 8D9
-50 to +750
Hermetically Sealed 3 8MA 8MJ 8EC 8MB 8MK 8E9
(-46 to +399)
Snap Switch 1 8NA 8NJ 8FC 8NB 8NK 8F9
DPDT
2 8OA 8OJ 8GC 8OB 8OK 8G9
1 9KA 9KJ 9CC 9KB 9KK 9C9
Series 9 SPDT 2 9LA 9LJ 9DC 9LB 9LK 9D9
High Temperature -50 to +750
3 9MA 9MJ 9EC 9MB 9MK 9E9
Hermetically Sealed (-46 to +399)
Snap Switch 1 9NA 9NJ 9FC 9NB 9NK 9F9
DPDT
2 9OA 9OJ 9GC 9OB 9OK 9G9
Process ➇ CS/Aluminum Cast Iron CS/Aluminum Cast Iron
Switch Temp. Range Contacts Set
Description Points Class I, Div 1 Class I, Div 1 Class I, Div 1 Class I, Div 1
°F (°C) NEMA 4X NEMA 4X
Groups C&D Group B Groups C&D Group B
-40 to +1000 1 R1M RKM RKW
Series R SPDT
(-40 to +538) 2 R3M RLM RLW
High Temperature N/A N/A
11 1 RDM RNM RNW
Snap Switch DPDT
2 REM ROM ROW
1 9AD 9KD 9KV 9AM 9KM 9KW
Series 9 SPDT 2 9BD 9LD 9LV 9BM 9LM 9LW
-50 to +1000
High Temperature
(-46 to +538) 3 9CD 9MD 9MV 9CM 9MM 9MW
Hermetically Sealed
Snap Switch
11 1 9DD 9ND 9NV 9DM 9NM 9NW
DPDT
2 9ED 9OD 9OV 9EM 9OM 9OW
21
A S M E B 3 1 . 3 a n d N A C E M O D E L N U M B E R S
F L A N G E D C A G E M O D E L S Models available for quick shipment, usually within one week after factory
receipt of a complete purchase order, through the Expedite Ship Plan (ESP)
MODEL NUMBER CODE
Head Min. S.G. for Models ➁ Pressure Rating
Model with Material of
Flange
Code
➀ ANSI Construction Code psig @ °F bar @ °C
Class 1 2 or N 100 550 750 800 900 1000 38 288 399 427 482 538
FLOAT MODELS
150# 0.78 0.83 285 155 95 80 50 20 19.6 10.7 6.5 5.5 3.4 1.4
B3F 300# 0.66 0.68 740 588 505 410 230 85 51.0 39.6 34.8 28.3 15.9 5.9
600# ➂➃ 0.66 0.71 1000 875 805 795 460 170 68.9 60.3 55.5 54.8 31.7 11.7
150# 0.41 0.43 285 155 95 80 50 20 19.6 10.7 6.5 5.5 3.4 1.4
G3F 300# 0.55 0.56 740 588 505 410 230 85 51.0 45.0 41.1 28.3 15.9 5.9
600# ➂➃ 0.70 0.76 1000 875 805 795 460 170 68.9 60.3 55.5 54.8 31.7 11.7
150# 0.33 0.33 285 155 95 80 50 20 19.6 10.7 6.5 5.5 3.4 1.4
K3F ➄ 300# 0.40 0.40 600 525 483 410 230 85 41.4 36.2 33.3 28.3 15.9 5.9
600# ➂➃≈ 0.60 0.62 1480 1170 1015 825 460 n/a 102.0 80.7 70.0 56.9 31.7 n/a
600# ➂➃≈ 0.67 0.74 1480 1170 1015 825 460 n/a 102.0 80.7 70.0 56.9 31.7 n/a
900# ➂➃≈
Z3F
0.67 0.73 2220 1758 1520 1235 690 n/a 153.1 121.2 104.8 85.2 47.8 n/a
DISPLACER MODELS 100 300 500 100 300 500
300# 740 655 600 51.0 45.2 41.1
C34 ∆➇ 600# ➃
n/a n/a
n/a 1480 1310 1200 102.0 90.7 82.7
Minimum SG 0.40 0.40 0.44 0.40 0.40 0.44
MATERIALS OF CONSTRUCTION
1 Carbon steel chamber, 316L stainless steel float, 400 stainless steel sleeve, ASME B31.3 Construction
2 Carbon steel chamber, 316L stainless steel float, 316 stainless steel sleeve, ASME B31.3 Construction
4 316 stainless steel chamber, 316L stainless steel float, 316 stainless steel sleeve, ASME B31.3 Construction
M 316 stainless steel chamber, 316L stainless steel float, 316 stainless steel sleeve, NACE and ASME B31.3 Construction
N Carbon steel chamber, 316L stainless steel float, 316 stainless steel sleeve, NACE and ASME B31.3 Construction
NACE construction: float cage is thermally stress relieved after welding, then hardness tested to assure compliance. Complies with NACE MR0175 & MR0103 latest revisions.
TANK CONNECTION TYPE AND SIZE
Connection Size ➇
Type C/C 1" 11⁄2" 2"
ANSI Head Flange Rating (lbs.)
150 300 600 900 150 300 600 900 150 300 600 900
Threaded s/b Std. B20 B60 B80 B40 C20 C60 C80 C40 D20 D60 D80 D40
Socket Weld s/b Std. B30 B70 B90 B50 C30 C70 C90 C50 D30 D70 D90 D50
Flanged Std. N30 N40 N50 N60 P30 P40 P50 P60 Q30 Q40 Q50 Q60
Upper Side/ 14" ➄ N34 N44 N54 N64 P34 P44 P54 P64 Q34 Q44 Q54 Q64
Bottom 16" ➈ N36 N46 N56 N66 P36 P46 P56 P66 Q36 Q46 Q56 Q66
Std. S30 S40 S50 S60 T30 T40 T50 T60 V30 V40 V50 V60
14" ➄
Flanged
S34 S44 S54 S64 T34 T44 T54 T64 V34 V44 V54 V64
16" ➈
Side/Side
S36 S46 S56 S66 T36 T46 T56 T66 V36 V46 V56 V66
≈ Construction Code N is not applicable to this unit due to 17–7 ph stainless steel float material.
∆ Consult factory for Model C34 up to +750 °F (+399 °C).
➇ Codes for 150 lb. flanges are not applicable to the C34 displacer model.
➈ Codes for a 16" center-to-center dimension are applicable to the K3F model only.
22
ELECTRIC SWITCH MECHANISM AND ENCLOSURE
All models C34 and all models All models C34 and all models with
with Material of Construction Code 1 Material of Construction Codes 2 & N
Process ➉ except B3F, G3F, K3F & Z3F and B3F, G3F, K3F & Z3F
Switch Temperature Set with 600# or 900# ANSI ratings with 600# or 900# ANSI ratings
Range Contacts
Description Points TYPE 4X/7/9 Aluminum Enclosure
°F (°C) ATEX ATEX
Class I, Div 1 Class I, Div 1 Class I, Div 1 Class I, Div 1
Ex II 2 G EEx Ex II 2 G EEx
Groups C&D Group B Groups C&D Group B
d IIC T6 d IIC T6
1 BKA BKJ BCC BKB BKK BC9
SPDT 2 BLA BLJ BDC BLB BLK BD9
Series B -40 to +250
3 BMA BMJ BEC BMB BMK BE9
Snap Switch (-40 to +121)
1 BNA BNJ BFC BNB BNK BF9
DPDT
2 BOA BOJ BGC BOB BOK BG9
1 CKA CKJ CCC CKB CKK CC9
SPDT 2 CLA CLJ CDC CLB CLK CD9
Series C -40 to +450
3 CMA CMJ CEC CMB CMK CE9
Snap Switch (-40 to +232)
1 CNA CNJ CFC CNB CNK CF9
DPDT
2 COA COJ CGC COB COK CG9
1 DKB DKK DC9 DKB DKK DC9
SPDT 2 DLB DLK DD9 DLB DLK DD9
Series D DC Current -40 to +250
3 DMB DMK DE9 DMB DMK DE9
Snap Switch (-40 to +121)
1 DNB DNK DF9 DNB DNK DF9
DPDT
2 DOB DOK DG9 DOB DOK DG9
1 FKA FKJ FCC FKB FKK FC9
Series F SPDT
-50 to +750 2 FLA FLJ FDC FLB FLK FD9
Hermetically Sealed
(-46 to +399) 1 FNA FNJ FFC FNB FNK FF9
Snap Switch DPDT
2 FOA FOJ FGC FOB FOK FG9
Series HS 1 HMJ HMK HMJ HMK
-50 to +550 SPDT
Hermetically Sealed 2 HMN HMP HMN HMP
(-46 to +288) N/A N/A
5-amp Snap Switch 1 HMS HMT HMS HMT
with Wiring Leads
11
DPDT
2 HMY HMZ HMY HMZ
Series HS SPDT 1 HM3 HM4 HA9 HM3 HM4 HA9
Hermetically Sealed -50 to +550
5-amp Snap Switch (-46 to +288)
with Terminal Block
11
DPDT 1 HM7 HM8 HB9 HM7 HM8 HB9
1 RKB RKK RC9 RKB RKK RC9
Series R SPDT
-40 to +750 2 RLB RLK RD9 RLB RLK RD9
High Temperature
(-40 to +399) 1 RNB RNK RF9 RNB RNK RF9
Snap Switch DPDT
2 ROB ROK RG9 ROB ROK RG9
1 8KA 8KJ 8CC 8KB 8KK 8C9
Series 8 SPDT 2 8LA 8LJ 8DC 8LB 8LK 8D9
-50 to +750
Hermetically Sealed 3 8MA 8MJ 8EC 8MB 8MK 8E9
(-46 to +399)
Snap Switch 1 8NA 8NJ 8FC 8NB 8NK 8F9
DPDT
2 8OA 8OJ 8GC 8OB 8OK 8G9
1 9KA 9KJ 9CC 9KB 9KK 9C9
Series 9 SPDT 2 9LA 9LJ 9DC 9LB 9LK 9D9
High Temperature -50 to +750
3 9MA 9MJ 9EC 9MB 9MK 9E9
Hermetically Sealed (-46 to +399)
Snap Switch 1 9NA 9NJ 9FC 9NB 9NK 9F9
DPDT
2 9OA 9OJ 9GC 9OB 9OK 9G9
Process ➉ CS/Aluminum Cast Iron CS/Aluminum Cast Iron
Switch Temp. Range Contacts Set
Description Points Class I, Div 1 Class I, Div 1 Class I, Div 1 Class I, Div 1
°F (°C) NEMA 4X NEMA 4X
Groups C&D Group B Groups C&D Group B
1 R1M RKM RKW
Series R -40 to +1000 SPDT
2 R3M RLM RLW
High Temperature (-40 to +538) N/A N/A
Snap Switch ➉
12
DPDT
1 RDM RNM RNW
2 REM ROM ROW
1 9AD 9KD 9KV 9AM 9KM 9KW
Series 9 SPDT 2 9BD 9LD 9LV 9BM 9LM 9LW
-50 to +1000
High Temperature
(-46 to +538) 3 9CD 9MD 9MV 9CM 9MM 9MW
➉
Hermetically Sealed 12
Snap Switch 1 9DD 9ND 9NV 9DM 9NM 9NW
DPDT
2 9ED 9OD 9OV 9EM 9OM 9OW
(+450 °C).
23
Q U A L I T Y
The quality assurance system in place at The Magnetrol quality assurance system is reg-
Magnetrol guarantees the highest level of quality istered to ISO 9001 affirming its commitment to
throughout the company. Magnetrol is commit- known international quality standards provid-
ted to providing full customer satisfaction both ing the strongest assurance of product/service
in quality products and quality service. quality available.
E S P
Several Series 3 level switches are available for ESP service may not apply to orders of ten units
Expedite quick shipment, usually within one week after or more. Contact your local representative for
Ship
factory receipt of a complete purchase order, lead times on larger volume orders, as well as
through the Expedite Ship Plan (ESP). other products and options.
W A R R A N T Y
All Magnetrol mechanical level and flow con- repair or replace the control at no cost to the
trols are warranted free of defects in materials purchaser (or owner) other than transportation.
or workmanship for three full years from the Magnetrol shall not be liable for misapplication,
date of original factory shipment. labor claims, direct or consequential damage or
If returned within the warranty period; and, expense arising from the installation or use of
upon factory inspection of the control, the equipment. There are no other warranties
cause of the claim is determined to be covered expressed or implied, except special written
under the warranty; then, Magnetrol will warranties covering some Magnetrol products.
magnetrol.com
BULLETIN: 46-123.24
Copyright © 2022 AMETEK Magnetrol USA, LLC
EFFECTIVE: August 2021
Performance specifications are effective with date of issue and are subject to change without notice.
SUPERSEDES: August 2017