Bahamas Building Code 3rd Edition - Print - Parte3 - 1
Bahamas Building Code 3rd Edition - Print - Parte3 - 1
*Weights of masonry include mortar but not plaster. For plaster, add 5 lbf/ff for
each face plastered. Values given represent averages. In some cases there is a
considerable range of weight for the same construction.
TABLE20-A4
MINIMUM DESIGN LOADS FOR MATERIALS
Bituminous products 81
Asphaltum 135
Graphite
Paraffin
Petroleum, crude 55
Petroleum, refined 50
Petroleum, benzine 46
Petroleum, gasoline 42
Pitch 69
Tar 75
Brass 526
Bronze 552
Cast-stone masonry (cement, stone, sand) 144
Ceramic Tile 150
Charcoal 12
Concrete
Plain 144
Vermiculite and perlite aggregate, nonload-bearing 25-50
20-1
Other light aggregate, load bearing 70-105
Reinforced 150
Copper 556
Cork, compressed 14.4
Earth (not submerged)
Soil 100
Sand and gravel 110
Sand and gravel, and clay 120
Earth (submerged)
Soil 70
Sand and gravel 60
Sand and gravel, and clay 65
Gravel, dry 104
Gypsum, loose 70
Gypsum, wallboard 50
Ice 57.2
Iron
Cast 450
Wrought 480
Lead 710
Lime
Hydrated, loose 32
Hydrated, compacted 45
Masonry, ashlar
Granite 165
Limestone, oolitic 135
Marble 173
Sandstone 144
Masonry, brick
Hard (low absorption) 130
Medium (medium absorption) 115
Masonry, rubble mortar
Limestone. Oolitic 138
Marble 156
Mortar, hardened
Cement 130
Lime 110
Particleboard 45
Plywood 36
Sand, clean and dry 90
Steel, cold drawn 489
Stone
Limestone, marble, quartz 95
Tin 459
Water
20-2
Fresh 62.4
Sea 64
20-3
Wood, seasoned
Cypress, southern 34
Fir, Douglas, coast region 34
Hem fir 28
Pine, southern yellow 37
Redwood 28
Spruce, red, white and Sitka 29
Zinc, rolled, sheet 449
20-4
NOTES
20-5
CHAPTER21
EXCAVATIONS, FOOTINGS AND FOUNDATIONS
2101 EXCAVATIONS
2102 BEARING CAPACITY OF SOILS
2103 SOIL BEARING FOUNDATIONS
2104 PILE FOUNDATIONS
2105 FOUNDATION WALLS AND GRADE BEAMS
2106 RETAINING WALLS
2107 SEAWALLS, BULKHEADS AND DOCKS
2108 MATERIALS
2101 EXCAVATIONS
2101.1 GENERAL:
(a) Excavations or fills for any buildings or structure and excavations
or fills accessory thereto shall be so constructed or protected that
they do not endanger life and property.
21-2
the excavation exists. Permanent excavations shall have retaining walls
of steel, masonry, concrete or similar approved material of sufficient
strength to retain the embankment together with any surcharged loads.
(b) The classification of the soil under all portions of every building
shall be based upon the examination of adequate test borings or
excavations made at the site when required by the BCO. When
ever, in the opinion of the BCO, the adequacy and class of a soil
cannot be determined by the test borings or excavations, he may
require a special soil investigation by an engineer recognised by
the Minister before approving the use of the footings.
21-3
All stumps and roots shall be removed from the soil to a depth of at least
12 inches below the surface of the ground in areas to be occupied by
build ings.
Where swampy conditions exist, the BCD may require the use of a Regis
tered Engineer.
21-4
(c) The minimum continuous footings specified in this section shall
be reinforced as follows:
4--# 5 El rs .6"Wid
(e) Concrete footings and pads shall not receive superimposed loads
until 12 hours or more after the concrete is placed.
21-5
(g) Excavations for continuous footings shall be cut true to line and
grade and the sides of footings shall be formed, except where soil
conditions are such that the sides of the excavation stand firm
and square. Excavations shall be made to firm clear bearing soil
or rock.
(h) Continuous footings shall be placed level and any changes in the
grade of such footings shall be made with a vertical tie of the
same cross section and design as the footings, or the smaller of
the footings, so joined.
(c) Concrete floor slabs placed directly on the supporting soil shall be
reinforced with not less than 0.029 square inches area of reinforc
ing per linear foot of slab in each direction (corresponds to 6" x 6"
10 ga./10 ga. steel wire. 10 ga. = 3.43 mm diameter).
21-6
2104 PILE FOUNDATIONS
2104.1 GENERAL:
(a) The use of types of piles not specifically mentioned in this Chap
ter, and the use of piles under conditions not specifically covered
herein, shall be permitted, subject to the approval of the BCO,
upon submission of acceptable test data, calculations, or other
informa tion relating to the properties and load-carrying capacity
of such piles.
(c) All piles standing unbraced in air, water, or material not capable
of lateral support, shall conform with the applicable column
formula as specified in this Code. Such piles driven into firm
ground may be considered fixed and laterally supported at five
feet (d) below the ground surface and in soft material at ten feet
(10) below the ground surface unless otherwise prescribed by the
BCO after an acceptable foundation investigation has been made.
(d) Piles used for the support of any building or structure shall be
driven to a resistance and penetration in accordance with the
plans and/ or specifications and as set forth herein.
(e) Jetting shall not be used except where and as specifically permit
ted by the BCD. When used, jetting shall be carried out in such a
manner that the carrying capacity of existing piles and structures
shall not be impaired. After withdrawal of the jet, piles shall be
driven down until the required resistance is obtained, in no case
shall this be less than 12",
(f) The minimum centre to centre spacing of piles shall be not less
than twice the average diameter of round piles or 1-3/ 4 times the
diagonal dimension of rectangular piles but in no case less than
30 inches.
(g) Reinforced concrete caps shall be provided for all pile clusters
and such caps shall extend laterally not less than 6 inches beyond
the extreme pile surface and vertically not less than 4 inches
below the pile butt. Pile caps may be omitted when piles are used
to support grade beams, provided that the spacing of paragraph (f)
above is complied with and provided that the portions of the
grade beams acting in place of the pile cap shall be computed by a
recognised method of analysis to properly carry the loads.
21-7
(h) Piles shall be driven using an approved cushion block consisting
of material so arranged as to provide transmission of hammer en
ergy equivalent to one-piece hardwood with the grain parallel to
the axis of the pile and enclosed in a metal housing to prevent its
lateral deformation between the hammer ram and the top of the
pile.
(i) Diesel hammers may be used for driving piles if provided with one
of the following means of determining the energy of the hammer's
blow.
21-8
(m) Piles may be driven with drop or gravity hammers provided
the hammer shall weigh not less than 3,000 pounds and the fall of
the hammer shall not exceed 6 feet.
(n) Piles shall be driven with a variation of not more than 1 / 4 inch
per foot from the vertical, or from the batter line indicated, with a
maxi mum variation of the head of the pile from the position
shown on the plans of not more than three inches.
(q) The maximum load permitted on any pile shall not exceed 50 tons
unless substantiated by load test performed at the site as set forth
inSub-section2104.2 (c) of this Chapter. The BCO may require tests
on any pile where its performance is questionable.
(r) Piles shall be designed and driven to develop not less than 10 tons
safe bearing capacity.
(t) Piles shall not be driven closer than two feet nor jetted closer than
ten feet to an existing building or structure unless approved by the
recognized engineer.
21-9
2104.2 ALLOWABLE PILE LOADS:
(a) GENERAL: The allowable axial and lateral loads on piles shall
be determined by an approved driving formula, by load tests, or
by a foundation investigation by a recognized engineer. A
foundation investigation shall be made if required by the BCO.
21-11
ment is removed, and the final rebound shall be recorded 24
hours after the entire test load has been removed. The maximum
allow able pile load shall be 1 / 2 that which causes a net
settlement after deducting the rebound of not more than 1 / 100 of
an inch per ton of total test load or shall be 1 / 2 that which
causes a gross settle ment of one inch, whichever is less. Elastic
shortening of the pile shall not be included in the gross
settlement.
(b) Untreated wood piles in all cases shall be cut off not higher than
mean low water and shall be capped with concrete.
(d) Piles of southern pine, Norway pine, Douglas fir or red oak when
pressure treated by an empty cell process, with coal tar creosote
to a net final retention of not less than 12 pounds of creosote per
cu bic foot of wood, may be used as follows:Where the upper
portion of the pile is exposed and accessible for inspection, the
cut-off may be above ground level or water level; where the upper
portion of the pile will not be readily accessible for inspection, the
cut-off shall be below the ground level but may be above the
ground-water level provided the tops are encased in masonry
footings so that no part of the pile will be exposed to the air. The
tops of the cut-off piles shall be treated with three coats of hot
creosote.
(e) The treatment of other species of wood for piles to extend above
permanent ground-water level, and the use of other preservative
materials or methods, may be used subject to written approval of
the BCO.
(f) Wood piles shall be driven with a protective driving cap or ring
21-12
when necessary to prevent brooming or splitting of the butt.
When
21-13
brooming or splitting occurs, such piles shall be cut back to solid
wood before the final resistance to penetrations is measured.
(h) In the absence of load tests, the total load on any wood pile shall
not exceed these values:
Tip Diameter Butt Diameter Maximum Load
(Tons)
6" 10" 15
8" 12" 20
10" 14" 25
(e) Piling shall have their date of manufacture and the lifting points
clearly marked on the pile.
(f) In the absence of load tests, the maximum allowable load per pile
shall not exceed the values set forth in the following table:
Size (Inches) Maximum Load (Tons)
10 X 10 17
12 X 12 25
21-14
14x 14 35
21-15
2104.5 PRECAST PRESTRESSED CONCRETE PILES (PRETENSIONED):
(a) Precast prestressed concrete piles shall develop a compressive
strength of not less than 4000 pounds per square inch before driv
ing based on standard 6 x 12 inch test cylinder. The piles shall de
velop an ultimate compressive strength at 28 days after pouring of
not less than 5000 pounds per square inch based on standard 6 x
12 inch test cylinder.
(h) The allowable stress in the prestressing steel shall not exceed the
values specified in the Chapter on Reinforced Concrete. (Chapter
22).
(i) Maximum allowable loads per pile, in the absence of load tests,
shall not exceed the values set forth in the table on Precast Rein
forced Concrete Piles, Section 2104.4 of this Chapter.
21-16
2104.6 CONCRETE FILLED STEEL PIPE PILES:
(a) Concrete filled steel pipe piles driven open ended shall have a nomi
nal outside diameter of not less than 10 inches and a nominal wall
thickness of not less than 0.25 inch except that pipes having a
nomi nal outside diameter 14 inches or over shall have a nominal
wall thickness of not less than 0.375 inch. Concrete filled steel
tubular piles driven with ends closed may be of smaller sizes and
wall thickness but no tapered pile shall have a diameter of less
than 8 inches at the top nor 6 inches at the foot, and nosuch pile
of uniform section shall have a diameter of less than 8 inches.
(b) A forged, cast steel or flat plated end of approved design shall be
used on concrete-filled steel pipe piles driven with a closed end.
(b) Sections of such pile of H form shall have flange projections not
exceeding 14X the thickness of web or flange and total flange
width not less than 85% of the depth of the section.
(c) No section shall have a nominal thickness of metal less than 3/8".
21-17
(d) For end-bearing piles, the allowable stress may be determined on
the basis of an allowable stress of 25% of the yield value of the
steel.
(f) The allowable load, when used as friction piles, shall be deter
mined by load tests at the Site.
(a) Single piles tested shall be loaded to at least twice the desired de
sign load and should pile groups be tested, the test load shall be
not less than 1-1/2 times the total desired load for the group.
(b) The apparatus for applying known vertical loads to the top of the
pile shall maintain constant load under increasing settlement, and
shall apply the loads in such a way that no lateral forces or im
pact will occur. Hydraulic jacks when used, shall be equipped
with a calibrated pressure gage. Uplift piles used to provide the
jacking resistance shall be a sufficient distance from the test pile
so as not to influence its behaviour under test.
(c) The test load shall be applied in increments of not more than 25%
of the design load until the total test load has been applied.
The total load shall be maintained until settlement does not exceed
0.01 in 24 hrs. Settlement readings shall be taken at regular inter
11
(f) After the maximum load has remained on the pile for 24 hrs and
final settlement readings have been taken, the pile shall be un
loaded in 50% decrements of design load. Re-bound readings
21-18
shall
21-19
be taken at regular intervals during the unloading period, and fi
nal reading taken approximately 12 hrs after the entire load has
been removed.
(g) The maximum allowable pile load shall be 1/2 of that load which
causes a net settlement of not more than 0.005" per ton of test
load, a gross settlement of 1", whichever is less, or a
disproportionate increase in settlement.
(1) The thickness of the foundation wall shall be not less than
8 inches.
(2) Where wood joist construction is used for the ground floor,
the thickness of the exterior foundation walls shall be not
less than 8 inches plus 4 inches for the bearing of joists.
21-20
(3) Foundations of unit masonry supporting joists shall be
capped with 4 inches of concrete.
(b) For wood frame buildings not exceeding one-storey in height, iso
lated piers may be substituted for interior foundation walls where
such piers do not exceed 24 inches in height, are a minimum of
12 inches by 12 inches in cross-sectional dimension, and are
located at corners and points of concentration, but not more than
six feet apart. Where such piers rest on rock they shell be keyed 6
inches into the rock.
(b) Grade beams shall be the thickness of the wall they support
but never less than 8 inches nor less than set forth for foundation
walls herein.
(a) Walls built to retain or support the lateral pressure of earth or water or
other superimposed loads shall be designed and constructed of approved
masonry, reinforced concrete, steel sheet piling or other approved
materi als within allowable stresses conforming to this code.
(b) Retaining walls shall be designed to resist the pressure of the retained
material including both dead and live load surcharges to which they may
be subjected, and to insure stability against overturning, sliding, exces
sive foundation pressure and water uplift.
(c) Unless drainage is provided, the hydrostatic head of water pressure shall
be assumed equal to the height of the wall.
21-21
(d) All masonry retaining walls other than reinforced concrete walls shall be
protected with an approved coping.
All dredging, waterfront filing and excavation, and waterfront construction such as
docks, piers, wharves, badges, groins, jetties, moles, break-waters, seawalls, revetments, and
cause ways, shall be planned and designed by an engineer recognized by the Minister.
2108 MATERIALS
The quality and design of materials used structurally in excavations, footings, founda
tions, retaining walls, seawalls, bulkheads and docks, shall conform to the requirements
specified in the Chapters forming the Engineering and Construction Requirements of this
Code. (Chapters 20-27).
21-22
NOTES
21-23
CHAPTER22
REINFORCED CONCRETE
2201 GENERAL
2202 STANDARDS
2203 DEFINITIONS
2204 MATERIALS AND TESTS
2205 WORKING STRESSES AND QUALITY OF CONCRETE
2206 MIXING AND PLACING
2207 FORMS AND DETAILS OF CONSTRUCTION
2208 PRECAST CONCRETE FLOOR AND ROOF UNITS
2209 PRESTRESSED CONCRETE
2210 PNEUMATICALLY PLACED CONCRETE
2201 GENERAL
2202 STANDARDS
The standards listed in Appendix A are hereby adapted as a part of this Code and supple
ment, but do not supersede, the specific requirements as set forth herein.
2203 DEFINITIONS
The following words and terms shall for the purpose of this Code, have the meanings set
forth in this section:
AGGREGATE, inert material which is mixed with Portland cement and water to
produce concrete.
22-1
COLUMN, an upright compression member the length of which exceeds three times
its least lateral dimension.
GROUT, a large amount of cement paste to which has been added a small amount
of fine aggregate to produce a mixture of fluid consistency. When the amount of
fine aggregate is increased so that the mixture loses its fluidity and behaves as a
cohesive plastic, the mixture is termed MORTAR.
PRECAST CONCRETE, a plain or reinforced concrete element cast in other than its
final position in the structure.
22-2
2204 MATERIALS AND TESTS
2204.2 TESTS:
(a) The BCO may order or make a test of any material entering into
concrete or reinforced concrete to determine its suitability for the
purpose; may order or make a reasonable number of tests of the
concrete from time to time to determine whether the materials and
methods in use are such as to produce concrete of the necessary
quality; and may order or make a test under load of any portion of
a completed structure, when conditions have been such as to leave
doubt as to the adequacy of the structure to serve the purpose for
which it is intended.
(d) Where earlier tests than 28 days are used the relationship between
the early tests and the 28 day strength of the concrete shall be es
tablished by tests for the materials and the proportions used.
22-3
2205.2 CONCRETE QUALITY:
(a) For the design of reinforced concrete structures, the specified
compressive strength used for determining the allowable stresses
shall be based on the 28-day compressive strength of the concrete
or the specified minimum compressive strength at the earlier age
at which the concrete may be expected to receive its full load. All
plans, submitted for approval or used on the job, shall clearly
show the assumed strength of concrete at a specified age for
which all parts of the structure were designed.
(c) The BCO may in particular cases accept concrete mixed in the
pro portion of one cubic foot or one 94 lb. sack of Portland
cement, two cubic feet of sand and 3 cubic feet of coarse
aggregate when ma chine mixed with sufficient water to make a
plastic mix with no free water, provided the use of concrete so
proportioned and mixed is limited to minor building components.
22-4
MAXIMUM PERMISSIBLE WATER-CEMENT RATIOS
FOR CONCRETE (METHOD NO. 1)"·1
(Without Preliminary Tests)
1. The minimum cement content shall be not less than five bags per cubic
yard (a bag weighing not less than 94 pounds) unless the mix is
designed specifically for the project.
(c) For job mixed concrete, the mixer shall be rotated at a speed rec
ommended by the manufacturer and mixing shall be continued
for at least 1-1/ 2 minutes after all materials are in the drum. For
batches larger than one cubic yard, mixing time shall be
increased 15 seconds for each additional cubic yard or fraction
thereof.
(b) The concrete shall exhibit a slump of approximately 2-1/ 2" prior
to the addition of the superplasticizing agent and approximately
8" after: Such concrete shall not exhibit excess bleeding or segrega
tion, abnormal retardation and air entrapment shall also be
absent.
2206.4 CONVEYING:
(a) Concrete shall be conveyed from the mixer to the place of final
deposit by methods which will prevent separation or loss of the
materials.
22-6
(b) Equipment for chuting, pumping and pneumatically conveying
concrete shall be of such size and design as to insure a practically
continuous flow of concrete at the delivery end without separa
tion of the materials.
2206.5 DEPOSITING:
(a) Concrete shall be deposited as nearly as practicable in its final po
sition to avoid segregation due to rehandling or flowing. The con
creting shall be carried on at such a rate that the concrete is at all
times plastic and flows readily into the spaces between the bars.
No concrete that has been contaminated by foreign materials shall
be deposited in the structure.
2206.6 CURING: In all concrete structures, concrete made with normal Portland
cement shall be maintained in a moist condition for at least the first
seven days after placing and high-early-strength concrete shall be so
maintained for at least the first three days. Other curing periods or
methods of curing may be used if the specified strengths are obtained.
2206.7 BONDING:
(a) Before new concrete is deposited on or against concrete which
has set, the forms shall be retightened, the surface of the set
concrete shall be cleaned of all foreign matter and laitance, and
wetted. The cleaned and wetted surfaces of the hardened concrete
shall first be slushed with a coating of neat cement against which
the new con crete shall be placed before the mortar has attained
22-7
its initial set.
22-8
(b) Where bonding of fresh to hardened concrete is necessary, constrnc
tion joints and joints between footings and walls or columns and
beams or floors they support, and joints in unexposed walls shall
be accomplished by reinforcement, dowels, adhesives,
mechanical connectors, or other approved methods. Hardened
concrete at joints shall be dampened, but not saturated,
immediately prior to the placement of fresh concrete.
22-9
2207.2 (a) REMOVAL OF FORMS: The removal of forms shall be carried out
in such a manner as to insure the complete safety of the structure.
Vertical forms may be removed in 24 hours, provided that the
con crete has hardened sufficiently so that it is not injured. 14
days; except that where tests indicate that the concrete has
attained Bot tom forms and shoring for slabs, beams and girders
shall not be removed in less than sufficient strength to safely
support itself and any imposed loads in less time, adjustments in
the above waiting periods may be made by the BCO in
conformance with the results obtained.
22-10
(b) The concrete protective covering for reinforcement at surfaces not
exposed directly to the ground or weather shall be not less than 3 /
4 inch for slabs and walls; and not less than 1-1/ 2 inches for
beams, girders and columns. In concrete ribbed or joist floors in
which the clear distance between ribs or joists is not more than
thirty inches, the protection of reinforcement shall be at least 3 / 4
inch. Cover is to main bars.
(b) A delay of at least one day must occur in columns or walls before
concreting beams, girders, or slabs supported thereon. Beams,
gird ers, brackets, column capitals, and haunches shall be
considered as part of the floor system and shall be placed
monolithically there with.
2208.1 GENERAL:
(a) Precast concrete units shall comply with the minimum requirements
set forth in this Chapter, and the Standards set forth in the Appen
dices.
(c) Only the material cast monolithically with the units at the time of
manufacture shall be used in computing stresses unless adequate
and approved mechanical shear transfer is provided.
(e) The BCO shall have free access to the plant of any producer at all
hours of normal operation, and failure to permit such access shall
be cause for revocation of approval.
(f) Failure of any product to satisfy in every respect the quality pre
scribed, or failure to conform with plans and specifications, shall
be cause for rejection of the products.
2208.3 WORKMANSHIP:
(a) The mix, the gradation of the aggregate and the workability shall
be such as to insure complete filling of the form and continuous
intimate bond between the concrete and all steel.
(b) The use of precast structural units not complying with the Stand
ards listed in the Appendices, or having visible cracks, honey comb,
exposed reinforcing except at ends or, with a compressive section
dimension more than one-eighth inch less than specified
dimension shall not be permitted.
22-12
2208.4 IDENTIFICATION AND MARKING: All joists, beams, girders, and
other units shall show some mark plainly indicating the top of the unit
and its location and orientation in the structure. Identification marks
shall be re produced from the placing plans. This mark or symbol shall
also indicate the manufacturer, the date of the manufacture and the
length, size and type of reinforcing.
2208.8 CONNECTIONS: All joints and connections will perform their function
at all stages of loading without overstress and with proper safety factors
against failure due to overload. Loading conditions to be considered in
the design of joints and connections are service loads, including wind
forces, volume changes due to shrinkage, creep, and temperature change,
erection loads, and loading encountered in stripping forms, shoring and
removal of shores, storage, and transportation of members.
22-13
2209 PRESTRESSED CONCRETE
2209.1 GENERAL:
(a) The term "prestressed concrete" refers to pretensioned concrete in
which the reinforcing is tensioned before hardening of the con
crete; or to post-tensioned concrete in which the reinforcing is
tensioned after hardening of the concrete; or combinations of both
pre-tensioning and post-tensioning. The internal stresses intro
duced are of such magnitude and distribution to counteract the
stresses resulting from service loads.
(e) The BCO shall have free access to the plant of any producer at all
hours of normal operation, and failure to permit such access shall
be cause for revocation of approval.
(b) Calcium chloride shall not be used in concrete for prestressed mem
bers.
22-15
2210 PNEUMATICALLY PLACED CONCRETE
2210.2 MATERIALS:
(a) Portland cement shall comply with the Standard Specifications
for Portland Cement, as set forth in Appendix A.
(c) All reinforcement shall be clean and free of loose rust or other
coat ings harmful to bond. Only round bars or wire mesh shall be
used.
2210.3 PROPORTIONS:
(a) Unless otherwise specified, all pneumatically placed concrete
shall be mixed in the proportions of one part of cement to four
and one half parts of sand based on loose, dry volume.
(b) (1) The Building Control Officer may require that core tests shall
be made to determine the strength of the material placed.
(2) Not less than two test cylinders shall be made of each
day's operation.
(6) One cylinder shall be tested at seven days and shall develop
a compressive strength of not less than 2400 p.s.i. and one
22-16
cylinder shall be tested at 28 days and shall develop the speci
fied strength but not less than 3000 p.s.i. based on 1:4-1/2
mix.
2210.6 FORMS: Forms shall be true to line and level, shall be substantially
braced to avoid excessive vibration and shall be adequately supported to
avoid deflection. Forms for columns shall, where practicable, be on two
sides only. Forms for beams shall be a soffit and one side or may be a
soffit only with vertical backing of fine wire mesh near the centre.
Forms shall be clean and thoroughly wetted before application of mortar.
(b) All concrete and masonry surfaces shall be cleaned of dust and
loose particles by compressed air and water and shall be
thoroughly wetted and surface damp before application of mortar.
(c) Steel surfaces shall be cleaned free of substances that will prevent
bond and shall be sand blasted where necessary.
(c) The nozzle shall be held at right angles to the surface and at a dis
tance of two and one-half to three and one-half feet.
22-17
(d) When enclosing reinforcing steel, the nozzle shall be held to
direct the material behind the bars. Each side of individual bars
shall be shot separately.
(g) In shooting walls and columns, application shall begin at the bot
tom and the first coat shall completely embed the reinforcement
to the form.
(i) In shooting slabs, the nozzle shall be held at a slight angle to the
work so that rebound is blown on to the finished portion where it
shall be removed. The limit of material in one layer shall be the
appearance of excess moisture on the surface.
22-18
CHAPTER23
STEEL AND IRON
2301 GENERAL
2302 MATERIALS
2303 DESIGN LOADS
2304 MINIMUM THICKNESS OF STRUCTURAL STEEL
2305 CONNECTIONS AND WELDING
2306 TUBULAR COLUMNS
2307 PROTECTION OF METAL
2308 OPEN WEB STEEL JOISTS
2309 LIGHT-GAGE STEEL CONSTRUCTION
2301 GENERAL
2301.1 DESIGN: Steel and iron members and structures shall be designed by
methods admitting of rational analysis according to established princi
ples of mechanics, and in accordance with the Standards adopted by this
Code and set forth in Appendix A.
2301.2 SCOPE: The design, fabrication and erection of steel and iron for build
ings and other structures shall be as set forth in this Chapter and as set
forth in Appendix A.
2302 MATERIALS
2302.1 STEEL: Steel shall conform to the physical requirements set forth in the
Standards, adopted as a part of this Code.
2302.3 RIBBED BOLTS: Ribbed bolts shall be made from a carbon manganese
steel with a minimum tensile strength of 70,000 psi.
23-1
Where light gauge (gage) steel structural members are furnished to a speci
fied minimum yield point greater than 33,000 pounds per square inch,
the grade and the specification designation shall be indicated by paint
ing, decal, tagging or other suitable means on each lift or bundle of
fabri cated elements. In the case of members having a yield point in
excess of 33,000 pounds per square inch obtained through additional
treatment, the resulting minimum yield point shall be indicated in
addition to the specification designation.
2302.5 USED AND DAMAGED MATERIAL: All steel shall be straight and
true, and any section damaged so as to be out of shape shall not be used.
Steel previously used or fabricated for use or fabricated in error shall not
be used except with the approval of the BCO. Filled holes or welds shall
not be concealed. Straightened or retempered fire-burned steel shall not
be used except with the approval of the BCO.
2302.6 TESTS: The BCO may require tests and/ or mill records to determine the
quality of materials.
2303.1 Design shall be based on the dead, live, wind and other loads set forth in
the Chapter on Live and Dead Loads (Chapter 20) and the additional
stress considerations set forth in this Chapter.
2303.2 Designs of arches and rigid frames shall include provisions for
resistance of lateral thrust at the support by means of tie rods,
abutments, founda tions, or other adequate measures. When the
superstructure is designed separately from the foundation, the
magnitude of the vertical and hori zontal reactions shall be made
available to the foundation designer and shall be shown on the plans.
23-2
(a) 5 /16-inch for columns; lintels; girders; beams exterior trusses and exte
rior bracing members;
(b) 3 / 16-inch for purling, girts, trusses and bracing members sheltered
from exposure to rain or located more than 100 yards from the High
Water Mark.
2305.2 WELDING:
(a) Welding in the shop or field shall be done only by persons who
have been tested and certified for the welds to be performed.
(b) Surfaces to be welded shall be free from loose scale, slag, rust, paint,
grease or other foreign matter.
(e) Nothing in this Code shall prohibit arc or gas cutting in steel con
struction; provided that arc or gas cutting shall not be done on a
member while it is under substantial stress.
(f) Cut edges shall be smooth and regular in contour, and when used
in the preparation of base metal parts for welding, special care
shall be taken to assure a surface suitable for welding.
23-3
2306 TUBULAR COLUMNS
2306.1 (a) Tubular columns and other primary compression members, shall
have a minimum least dimension of 2-1/ 2 inches and a minimum
wall thickness of 3 / 16 of an inch.
(b) Secondary post and struts, not subject to bending, and whose de
sign load does not exceed 2000 pounds may be exempted the
mini mum dimension set out in (a) above.
2306.2 Tubular members when filled with concrete shall have one-quarter inch
diameter pressure relief holes drilled through the shell, within 6 inches
of the top and bottom of the exposed length of the member, and one
hole at mid height.
2306.3 Concrete fill in tubular members shall not be assumed to carry any of the
load except for compression members having a least dimension of 8
inches or greater and having a one-inch inspection hole in the plate at
each end.
2307.1 All field rivets, bolts, welds and abrasions to the shop coat shall be spot
painted or treated with the material used for the shop coat, or an equiva
lent comparable to the shop coat, after removal of all objectionable
mate rials.
(b) fresh or salt water spray (this includes all such members located
within 100 yards of the High Water Mark): or
23-4
(c) any other corrosive agent,
2307.5 Where structural members are exposed to industrial fumes, fresh and/ or
salt water, salt water spray, and other corrosive agents, such members
shall be effectively protected with a corrosion-resistive metallic or other
equivalent approved coating.
2307.7 Floor or roof construction which extends into an exterior wall shall be
adequately waterproofed and protected from the weather to prevent cor
rosion.
2308.1 STANDARDS: Open web steel joists shall comply with the Standards
set forth in Appendix A.
2308.2 (a) DESIGN: Open web steel joist systems shall be designed to ac
commodate the loads and forces set forth in the Chapter 20.
(b) Where the net uplift force is equal to or greater than the gravity
load of construction, all web and bottom chord members shall
com ply with slenderness ratio requirements for top chord and for
com pression members other than top chord as provided for in the
stand ards set forth in Appendix A.
(c) The top chord for superimposed dead and live loads shall be con
sidered to be stayed laterally if:
2308.4 BRIDGING:
(a) Lateral bracing shall be provided at intervals suitable for intended
use and not greater than given in the following table:
Cliar pan
• l of sp
40 to 4 £ t hr il:'Q'IW5- at apprmd.t't'ii .ti.!l 1 /6
poin of $f!<'J.i'I.
23-6
(c) The ends of joists shall have a minimum bearing, on reinforced
concrete and steel supports as specified in the Standards set forth
in Appendix A.
2308.6 SHOP STANDARDS: The BCO may require that shop drawings,
prepared by a recognized engineer, showing stress diagrams, sizes of
members and sizes of welds, be submitted for approval before erection
of open-web steel joists and that the designer make inspection of the
joists in place and certify that the fabrication and placing conforms to
the design.
2308.7 MATERIALS:
(a) Joists shall be manufactured of hot rolled or cold-formed sections
having a minimum thickness of 1 / 8 inch for shapes, flats and
formed sections, and 3/ 8 inch for round sections.
(b) Light gauge steel for the treads. risers, stringers and landings of
stairways shall have a minimum thickness of .1046 inches.
(c) (1) Light-gauge steel studs for bearing walls shall have a mini-
mum thickness of .0478 inches and, except where
23-7
specifically
23-8
designed as columns, shall be spaced not more than 24
inches on centres. Provisions shall be made to resist
horizontal wind forces by diagonal members, diaphragm
panels or other com parable means.
(d) Light-gauge steel joists, rafters, purlins, and girts shall have a
mini mum thickness of .0598 inches, minimum bearing of 4
inches on concrete, minimum bearing of 2-1/2 inches on steel and
each end shall be positively anchored to resist the loads set forth
in the Chap ter on Live and Dead Loads.
(b) (i) Decks and wall panels, where properly supported by and
attached to the building frame, may be considered to act as
a diaphragm in resisting lateral forces, where designed as
such by an engineer recognised by the Minister.
(c) Where large openings occur, the perimeter of the opening shall be
framed with adequate supports for the panels. Openings 12 inches
and smaller shall be reinforced as required so that the allowable
stresses in the adjoining materials are not exceeded.
23-9
(d) Positive attachment shall be provided as set forth in Paragraph
2309.3 (a). Maximum spacing of fastenings along each
supporting member is to be based on gravity, uplift, stress
reversal, and dia phragm requirements, but not to exceed 8 inches
nominal on cen tres at ends of sheets and 12 inches nominal on
centres at interme diate bearings. At perimeters, parallel to
direction of span, edges of sheets are to be so supported as to
provide for a maximum spac ing of fastenings of 12 inches on
centres. An adequate sidelock or other connection shall be made
to provide for the distribution of imposed loads. Where
continuous interlocking or lightweight con crete fill is not
provided, side edges shall be fastened together at intervals not
exceeding 12 inches where diaphragm action is re quired or 18
inches otherwise. Roof and floor panels having a con crete or
lightweight concrete fill mechanically connected to the structure
may utilize the properly designed fill in diaphragm ac tion, where
designed as such by an engineer recognized by the Minister.
(g) The bending stress of metal siding and roof panels shall be de
signed utilizing a safety factor of not less than 2.5.
(h) Minimum roof decking uplift loads shall comply with UL 580 Class
90.
(i) Metal building siding and roof decking shall be designed without
an allowable increase in stresses of 1/3 due to wind load.
(b) Attachment shall be as set forth in Paragraph 2309.4 (d) but not
less than 12 inches on centres each way; except that attachment
23-10
may be by 8d nails, penetrating not less than three-fourths inch
into wood sheathing or by No. 6 screws.
23-11
CHAPTER24
WOOD
2401 DESIGN
2402 STANDARDS
2403 DEFINITIONS
2404 QUALITY AND SIZES
2405 ALLOWABLE UNIT STRESSES AND LOAD TABLES
2406 CONSTRUCTION DETAILS
2407 HEAVY TIMBER CONSTRUCTION
2408 PROTECTION OF WOOD
2409 FIRE-RETARDANT TREATED WOOD
2410 MINISTRY OF WORKS LOW COST HOUSING PLANS
2401 DESIGN
Wood members used for structural purposes shall be designed by methods admitting of
rational analysis according to established principles of mechanics, and in accordance
with the Standards adopted by this Code and set forth in Appendix A.
2402 STANDARDS
The Standards listed in Appendix A are hereby adopted as a part of this Code and
supple ment, but do not supersede, the specific requirements as set forth herein.
2403 DEFINITIONS
The following words and terms shall for the purpose of this Code, have the meanings set
forth in this section:
GLUED BUILT-UP MEMBERS, structural members, the sections of which are com
posed of built-up sawn lumber alone, plywood alone, or plywood in combination
with sawn or glued-laminated lumber; all parts bonded together with adhesives.
24-1
GRADE-STRESS (Lumber), a lumber grade defined in such terms that a definite
working stress may be assigned to it as set forth in the Standards in Appendix A.
NOMINAL SIZE (Lumber), the commercial size designation of width, and depth,
in standard sawn lumber and glued-laminated lumber grades; somewhat larger
than the standard net size of dressed lumber, in accordance with the Standards in
Appendix A.
2404.1 QUALITY:
(a) All lumber used for joists, rafters, stringers and/or beams shall be
of a grade not less than 1200 psi extreme fiber stress in bending
and tension parallel to the grain.
(c) The species and grade of all wood used for load-bearing purposes,
the design of which is based on stresses in excess of 1200 p.s.i. lum
ber, shall be shown on the plans submitted with applications for
building permits.
2404.2 SIZES:
(a) Wood members shall be of sufficient size to carry the dead and
required live loads without exceeding the allowable deflections or
working stresses specified in this Code.
24-2
(b) Sizes of wood members referred to by this Code are nominal
sizes. Nominal sizes may be shown on the plans. The minimum
accept able net sizes conforming to nominal sizes shall be within
2% of the minimum net sizes contained in the Standard specified
in Ap pendix A at 19% moisture content. Computations to
determine the required sizes of members shall be based on the net
sizes contained in the standard.
(c) Fire rated wood shingles and/ or shakes shall be clearly identified
by bundle or certificate in accordance with the Standards in Ap
pendix A.
(d) All structural-use panels shall be identified for end use grade and
exposure durability classificationby the trade mark of an
approved testing and grading agency in accordance with the
Standards in Appendix A.
24-3
2405 ALLOWABLE UNIT STRESSES AND LOAD TABLES
2405.1 GENERAL:
(a) Wood joists and rafters may be of the sizes set forth in the follow
ing table without additional professional design or shall be de
signed based on the allowable unit stresses set forth in the Stand
ards in Appendix A. Where the design is based on allowable
work ing stresses higher than the lowest stress-grade for the
species, the design shall be supported by computations submitted
by an engi neer recognised by the Minister.
TABLE24-A
ALLOWABLE SPANS - FLOOR JOISTS, ROOF AND
CEILING JOISTS
(Based on 1200 psi fibre stress and L/360 deflection)
12
13'-3"
23'-0"
14'-5"
24'-10"
15'-11"
27'-0"
-
18'-0"-
-23'-2"
16 19'-10" 21'-6" 23'-8" 26'-0" -
24 16'-3" 17'-6" 19'-3" 21'-9" --
4x6 12 13'-2' 14'-2.,, 15'-8" 15'-8" 22'-2"
16 11'-6" 12'-5" 13'-9" 14'-3" 20'-0"
4x8
24
12
9'-5'"
17'-4"
10'-1"
18'-9"
1'-2"
20'-7"
12'-5"
20'7"
-
16'-4"
24-4
Loadings given in the table in pounds per
square foot correspond to these combinations
of design or working loadings:
67 psf: Floor joists with plaster below-SO psf live load and 17 psf dead
load.
57 psf: Floor joists with plaster below---40 psf live load and 17 psf dead
load, or roof rafters with a slope greater than 2-1 / 2 to 12 - 30 psf live
load and 27 psf dead load.
47 psf: Floor joists without plaster below---40 psf live load and 7 psf
dead load, or roof joists with plaster below-30 psf live load and 17 psf
dead load.
37 psf: Ceiling joists over living rooms and usable attic space-25 psf live
load and 12 psf dead load, or Roof joists without plaster under-30 psf
live load and 7 psf dead load.
22 psf: Ceiling joists without usable attic space-10 psf live load, and
12 psf dead load.
(a) The deflection of wood members shall not exceed that set forth in
the Chapter on Live and Dead Loads.
(b) The span of roof rafters shall be measured horizontally from bearing
to bearing, and the horizontal distance from plate to ridge or other
support shall be the span.
24-5
(e) All plywood used structurally shall bear the identification of the
manufacturer as to type and grade, species of veneer used and
con formance with the appropriate commercial standard.
2405.3 GLUED-LAMINATED:
(a) Glued-laminated members shall comply with the Standards set
forth in Appendix A. Where deemed necessary by the Buildings
Control Officer, the use of trussed rafters or the equivalent may
be requested.
(c) The BCO may limit or otherwise regulate the use of glued lami
nated members.
(b) Where Prefabricated wood roof trusses are used the roof
framing plans which constitute part of the permit documents
shall be provided and shall be signed by the truss manuf ac
turer's Engineers who shall be an Engineer recognised by the
Minister. Such roof framing plans shall be reviewed and
approved by the Architect or Engineer of Record.
(e) The allowable deflection under live load for trusses shall
not exceed span/360 for plastered ceilings span/240 for
unplastered.
(g) Flat roof trusses shall be designed for not less than the
loads set forth in Subparagraph 2405.4(1)(d)above,except
that the dead load on the top chord may be taken as 10 psf
in lieu of 15 psf, and the total load reduced to 50 psf. No
stress in crease for wind, live, or dead loading shall be
permitted for flat trusses.
(h) Gable end trusses shall be designed for a minimum live load
of 30 psf and a minimum dead load of 15 psf on the top chord.
The minimum load of 10 psf on the bottom chord may be
omitted where continuous support is provided.
24-7
(2) MATERIAL SPECIFICATIONS:
(a) Trusses shall be fabricated of Southern Yellow Pine, Doug
las Fir, Hem-Fir or Fir-Larch, applying the stress ratings
listed in the Standards set forth in forth in Appendix A.
(e) All lumber shall be 2" x4" nominal or larger, and no 2"
nomi nal member shall be less in size than 11/2 ".
(f) The moisture content of all lumber used in wood truss fabri
cation shall not exceed 19%.
(h) All connector plates shall bear the name, logo or other
mark ings which clearly identify the manufacturer. Semi-
annu ally, Plate manufacturers shall certify compliance with
the provisions of Section 202 of the TPI Design
Specification for Metal Plate Connected Wood Trusses; with
respect to the grade of steel, thickness or gauge of material,
and galvaniz ing to ASTM G-60 as a minimum. This
certification require ment may be satisfied by submitting
certified mill reports or independent laboratory reports to
the Buildings Control Of ficer.
24-8
(3) FABRICATION:
(a) Manufacturers and fabricators of prefabricated wood truss
assemblies shall obtain valid approval in accordance with
Section 317 of this Code.
(b) Each truss shall bear the fabricators stamp on a web mem
ber and 75% shall be placed so as to be clearly visible after
erection.
(b) All wood columns and posts shall have the bottom protected from
deterioration.
2406.2 STUDS:
(a) SIZE: Studs shall be not less than 2"X 4" and, where supporting
24-9
more than one floor and a roof, shall be not less than 2"x 6" or
3"x 4".
(c) SPACING: Studs shall be spaced not more than 16 inches on cen tres
when supporting floors. Vertical studs not more than 10 feet in
length may be spaced 24 inches on centres when supporting
roof and ceiling loads only.
(f) BASE PLATES: Stud walls resting on masonry shall have base
plates or sills of wood treated with an approved preservative.
(h) SPLICING: Bearing studs shall be spliced only at points where lat
eral support is provided.
24-10
(i) NOTCHING: No notching or cutting whatsoever shall be permit
ted in studs which carry loads in excess of 75 percent of their ca
pacity.
2406.3 FIRESTOPS: Firestopping shall be provided to cut off all concealed draft
spaces both vertical and horizontal. Firestops shall form effective fire
bar riers between storeys and between a storey and roof space. Firestops
shall be provided in specific locations, as follows:
(c) BEARING: Joists and rafters shall bear on wood plates and shall
not be directly in contact with masomy; except that joists and
raft ers, when more than 6 feet above grade and bearing on
concrete beams cast in masonry walls which extend above the
wood joists and rafters, may bear on such concrete beams
provided the ends shall be fire-cut and anchored as specified in
Paragraph (d) below.
Joists and rafters shall have not less than 4 inches of bearing, ex
cept as follows:
(1) Ceiling joists may butt into the web of a steel beam and be
neatly fitted to bear on not less than 3 inch wide bottom flange
of such beam.
24-13
secured to the concrete with anchor bolts or metal straps as
set forth below except as noted in (iii).
(d) ANCHORAGE:
(1) Joists fire-cut into a masonry wall shall be anchored to the
concrete beam on which they bear. Such anchors shall be
spaced not more than 4 feet apart and shall be placed at op
posite ends across the building on the same run of joists.
(2) All joists shall be nailed to the bearing plates, to each other
where they lap, and to the studs where such studs are adja
cent; and ceiling joists shall be nailed to roof rafters, if
practi cable.
(3) Every roof rafter and/ or roof joist shall be anchored to the
beam or studs on which they bear, and roof rafters
opposing at a ridge shall be anchored across the ridge.
The projection of anchor bolts above the top of the tie beam
shall be such that the wall plates referred to in sub-section
(c) (2) of this section are securely bolted down without
reduction in thickness of the plate.
(2) METAL STRAPS: Where 1"x 1 / 8" metal straps are used
to secure rafters or joists to a wall plate, or to a metal
saddle, care shall be taken with their placement, bent over
or mis aligned straps shall not be considered acceptable.
(g) FLOOR JOISTS: Floor joists under all walls parallel to any joists
shall be doubled. Such doubled joists may be separated not more
24-15
than 6 inches by solid blocking spaced at 4-foot intervals.
(i) ROOF JOISTS: Roof joists may cantilever over exterior walls as lim
ited by the allowable stress, but the length of such cantilever shall
not exceed the length of that portion of such joist inside the build
ing.
(2) Collar ties shall be provided at each pair of rafters, unless other
means of resisting the thrust of the rafters is required and
provided and/ or the ridge is designed as a supporting
pbeam. Such collar ties shall be placed horizontally at or
below the upper-third point of the rafters, and shall be not
less than l"x 6" rough or 2"x 4" nominal size. Effectively
nailed ceiling joists may serve as collar ties.
(b) Joists of a suspended ceiling shall be not less than 2"x 4"
members, and wood hangers shall provide nailing and be not less
than the equivalent of 1"x 4" members.
24-16
2406.6 SHEATHING:
(1) FLOOR SHEATHING:
(a) Floor sheathing, where a part of a required fire-resistive
as sembly, shall comply with Chapter 32 of this Code.
than 16 o/c nor less than 3/4 thick when joists shall
11 11
at intermediate supports.
24-17
TABLE 24-B
ALLOWABLE SPANS FOR SUB-FLOOR [1]
Pane] Maxim:Urm
ldlentific tfon"nd.ex[2] Plywoo.d pan :
[l]
36/M
42/20 20" [ ]
/21
(f) Flooring shall be nailed with Bd common nails not less than
2 each board at each support.
(h) Flooring shall not extend closer than 1/2" from masonry
walls.
24-18
face grain
24-19
perpendicular to supports. Maximum thickness and
maximum joist spacing shall comply with table 24-C below:
TABLE24-C
12 16 24 32 42 48
lz4/0 112 24 24 90 65 30 - - - 0
4/16
8124
112
314,7/8
24
48
24
36
13510040 - - - 16
24
210155100 65 50 35
[3] All panels support 85 psf floor live load plus 10 psf dead
load at rated maximum span.
24-21
(2) ROOF SHEATHING:
(1) Wood roof sheathing shall be boards, plywood or structural
use panels, except as may be otherwise approved by the
Buildings Control Officer.
TABLE24-D
ALLOWABLE SPANS FOR PLYWOOD ROOF SHEATHING [1]
24-22
recommended by the panel manufacturer. Nailing shall be
in accordance with sub-sections (c) (i) and (c) (ii) above.
Pan els may be used for the spacing of supports with live
loads not to exceed those given in the table in subsection
2406.6 (a) (10).
TABLE24-E
WALL SHEATHING
24/0,32/16 1/2 24 24
24-23
(d) EXTERIOR WALL CLADDING:
(i) The panel thickness shall be not less than 3/8 inch ex
cept for 303 speciality siding panels and Texture 1-11
panels and the supporting studs shall be spaced not
more than 16 inches on centres.
(3) Where face plies are vertical, bridging pieces spaced not far
ther apart than three feet eight inches vertically shall be pro
vided for support of plywood for first storey installation and
not farther apart than two feet four inches for second storey
installations.
2406.7 FURRING: Where the interior of masonry walls are furred, such furring
shall be treated and firestopped as herein required and shall be securely
fastened to the masonry with not less than one cut nail in alternate
courses of block.
2406.8 CONNECTORS:
(a) The allowable loads on all types of connectors shall be as set
forth in the Standards listed in Appendix A.
(b) G-ring shank nails should be used for all roof sheathing.
(c) Nails, bolts and other metal connectors which are used in loca
tions exposed to the weather shall be galvanised or otherwise cor
rosion resistant.
24-24
TABLE 24-F
(b) NUMBER OF NAILS REQUIRED FOR CONNECTING
WOOD MEMBERS:
Co:nne tion Con:u on
N;ari1s,
Joist to Sii.M or Gi:rder, toe :mt.it 6d 2
Br-idgi.m: g to Joist., 1toe ail 2eacil nd
Sd
1"x 6"' · t11b loor to Joist•, ac:
ail 8d 2
0 @r 1" 6" sub-' or to each 3 1 or each iz.
jr0i tr Fi;lce N H 8d inc ;ease
2"' ·ub filo u· to joist or ·ir,dc-r,
blind and fac :n il 16d 2
so·ll ph1t _. 1- t or ·1tiloc:king
·are nail 16dl 6" o aeiJre
fop OE' : ._1- . • t o $hl.d, ,end
1a.a1 d 16d
8dor J
24-25
1
J. 1 or ea(:!h i.w
jru:: :as.
JO 'on c-entr-E
J2• ,on c ntr at top and bot't·om ari.d stagger
.d, 2 a:t ends and at e.acih spli.
2 each b a.ring
24-26
(e) Except for plywood and other laminated members manufactured
under technical control and rigid inspection, gluing shall not be
considered an acceptable connector in lieu of the connectors
herein specified.
(f) Safe loads and design practice for types of connectors not men
tioned or fully covered herein shall be determined by the BCO
be fore approval.
(b) Wood joists may be used to support concrete and cement base tile
or terrazzo floor surfaces for bathrooms of less than 100 square
feet in area, having slabs not more than two and one-half inches
in thickness.
2407.1 GENERAL: Heavy timber construction is that type in which fire resist
ance is attained by placing limitations on the minimum size, thickness,
or composition of all load-carrying wood members; by avoiding
concealed spaces under floors or roofs; by using approved fastenings,
construction details, and adhesives; and by providing the required
degree of fire-re sistance in exterior and interior walls.
24-27
Columns shall be continuous or directly superimposed, one above
the other with no girders or bolsters between columns,
through out all storeys by means of reinforced concrete or metal
caps with brackets, or shall be connected by properly designed steel
or iron caps, with pintles and base plates, or by timber splice plates
affixed to the column by means of metal connectors housed
within the contact faces, or other approved methods.
(b) FLOORFRAMING:
(1) Beams, girders and joists may be sawn or glued-
laminated and shall be not less than 6 inch, nominal, in
width and 8 inch, nominal, in depth.
(c) ROOF FRAMING: Beams, girders and joists may be sawn or glued
laminated and shall be not less than 6 inch, nominal, in least di
mension. Framed members or glued laminated arches which
spring from the floor line and do not support floor loads shall
have mem bers of not less than 6 inch, nominal, in width and 6
inch, nominal, in depth for the lower half of the height and not
less than 6 inch, nominal, in any dimension for the upper half of
the height. Framed members or glued laminated arches which
spring from the top of walls or wall abutments. framed timber
trusses, and other roof fram ing which does not support floor loads,
shall have members not less than 4 inch nominal in width and 6
inch nominal in depth.
24-29
face of the wall. Roof anchors shall be provided as set forth in
this Chapter but not less than required to resist the uplift loads as
set forth in the Chapter on Live and Dead Loads (Chapter 20 ).
(b) All wood in contact with, or less than 18 inches from the ground
shall be treated in an approved method with an approved
preserva tive or shall be of a durable species as approved by the
BCO.
24-30
be treated in an approved method with an approved preservative
or
24-31
shall be of durable species as approved by the BCO, except that
the ends of joists not less than 8 feet above grade when in contact
with concrete or masonry, may be treated by dipping the ends in
an approved preservative for a period of not less than 5 minutes.
2408.2 VENTILATION: Attic space between ceiling joists and roof rafters shall
be effectively ventilated. Openings shall be located to provide effective
cross ventilation, and such openings shall be covered with a corrosion
resistant mesh with openings not greater than one-sixteenth inch.
(b) Where wood-floor joists are used, there shall be not less than 18
inches distance between the bottom of such floor joists and the
grade beneath.
2409.3 Fire-retardant treated wood shall have no greater fuel contributed than
30 nor smoke developed greater than 65 as tested in accordance with ASTM
Standard E84 (Standard Test Method for Fire Hazard Classification of
Building Materials.)
24-32
2409.4 Fire retardant treated wood, where permitted and which may be exposed
to the weather, shall maintain required fire-retardant classification when
tested in accordance with the rain and weathering tests for durability of
fire-retardant treated wood of the Standard Test Methods for Fire-Resist
ance of Roof Covering materials; UL 790.
24-33
NOTES
24-34
CHAPTER25
ALUMINIUM
2501 GENERAL
2502 ALLOWABLE UNIT STRESSES
2503 DESIGN
2504 CONSTRUCTION DETAILS
2505 FABRICATION AND ERECTION DETAILS
2506 DISSIMILAR MATERIALS
2501 GENERAL
2502.1 The design, fabrication and assembly of aluminium members for build
ing and other structures shall conform to the Standard set forth in Sub
section 2501.2 herein and as otherwise set forth herein.
(b) The BCO may require that any structure using aluminium
primary or secondary members be designed by an engineer
recognised by the Minister.
25-1
(c) Working stresses are given below for the three most commonly
used structural aluminium alloys: 6061-T6, 6063-T6, and 6063-
T5 (ASTM designations). Other aluminium alloys may be used
with allowable types of stress conforming to the types of stress
given below, in proportion to the yield strength, ultimate strength
and other properties of the aluminium alloy used.
2502.2 The use of aluminium alloys, other than those listed in the standard
shall provide performance not less than those required by the Standards
con tained in Appendix 'A'.
(a) Working stresses shall not exceed the stresses given below.
25-2
*Ratio of edge distance to rivet or bolt diameter of two or greater. For
smaller ratios, multiply this working stress by the ratio:
edge distance
twice the rivet or bolt diameter
A]uminium Alfoy by
A . .
25-3
*** Working stresses apply to all material welded with 5356 or 5556
filler alloy and to material 3 / 5 inches or less in thickness welded with
4043 filler alloy. For thicker material welded with 4043 filler alloy,
reduce these working stresses by multiplying them by 0.8.
edge distance
twice the rivet or bolt diameter
(d) If less than 15 percent of the area of a given cross section lies
within 1 inch of a weld, the effect of the weld may be neglected
and the working stresses for non-welded structural members may
be used. If the area of a cross section that lies within 1 inch of a
weld is between 15 percent and 100 percent of the total area of the
cross section, the working stress shall be calculated in accordance
with the provisions of Section 2502.2 (a) of this code.
Sl11ea Olill
Del riptiolil. o!f Rivet Eff • U
01' &olt Sheaa!li' Ai!!', a
. IT53-Ti 1 ·v ts,· 8,500
6061-T4.3rivets1 dri'v,e-n
tem_pe:rawres.o-f fr.om 990,..to
at
10509 9))0.0
1-T6 ri,. , cold dri,nm 11,.000
606il.-Th ·pirns 11)100
2.024-T4 bolt l6,.000 26,000
25-4
(f) WORKING STRESSES IN SHEAR FOR FILLET WELDS SHALL
NOT EXCEED THE FOLLOWING ALLOWABLE SHEAR
STRESS
* IN LBS. PER SQUARE INCH.
.ooo, 7,000
*** These values are controlled by the shear strength of the parent mate
rial; all other values are controlled by the strength of the fillet metal.
2502.2 Aluminium members shall be limited by the deflections set forth in the
relevant Subsections of Chapter 20 of this Code.
25-5
2502.5 The working stress in compression elements of columns and beams of
such proportions that local buckling controls the design shall be reduced
in accordance with the provisions of Section 2501.2 of this code.
2502.6 The working stress in shear in webs of beams shall vary with the ratio of
web height to thickness in accordance with the provisions of Section 2501.2
of this code.
2503 DESIGN
2503.1 The Buildings Control Officer may require that any structure using alu
minium primary or secondary members be designed by an Engineer
recog nised by the Minister.
2503.2 Increases in allowable unit stresses as set forth for wind loads in Chap
ter 20 of this Code shall be applicable to aluminium structural members
except that allowable unit stresses thus increased shall not exceed 75%
of the minimum yield strength.
2503.3 In addition to flexural and shearing stresses, the critical factors of buck
ling, fatigue, stress raisers such as notches or holes or shape re-entrant
corners, deflection and connections shall be considered and provided for
by proper design.
(b) Aluminium sheets used for roof decking or siding shall be not less
than 0.019 in thickness.
11
25-6
(d) Fasteners shall have a head, and/or be provided with washers not
less than 1/2" in diameter.
(e) Fasteners located at end laps shall be placed not more than 2" nor
less than 1"from the end of overlapping sheets.
2505.2 BOLTS: Bolts and other fasteners used with aluminium shall be alu
minium, stainless steel, aluminized, hot-dip galvanized or electro-gal
vanized steel.
2505.3 RIVETS: Rivets shall be driven hot or cold, as called for on the plans,
and shall fill the holes completely. Rivet heads shall be concentric with
rivet holes and shall be in proper contact with the surface of the metal.
Defec tive rivets shall be removed by drilling.
25-7
2505.4 WELDING: Welding shall be accomplished by means of an arc of resist
ance welding process. No welding process that requires the use of a
weld ing flux shall be used.
2505.7 FIELD JOINTS: Field joints shall not be finally made up until that part
of the structure which will be stiffened thereby has been properly
aligned.
2505.8 WALL PANELS: Aluminium sheets used in wall panels shall have a thick
ness of not less than .032 inch.
2506.1 Where aluminium surfaces come in contact with metals other than stain
less steel, zinc, white bronze of small area or other metals compatible
with aluminium, aluminium surfaces shall be kept from direct contact
with such parts by one of these methods:
2506.3 Aluminium surf aces in contact with lime mortar, concrete or other
ma sonry materials shall be protected with alkali-resistant coatings,
such as heavy-bodied bituminous paint or water-white methacrylate
25-8
lacquer.
25-9
2506.4 Aluminium in contact with wood or other absorptive materials which
may become repeatedly wet shall be painted with two coats of aluminium
metal-and-masonry paint or a coat of heavy-bodied bituminous paint,
or the wood or other absorptive material shall be painted with two coats
of aluminium house paint and joints shall be sealed with a good quality
caulking compound.
2506.5 Where aluminium is in contact with treated wood, such wood shall be
treated with pentachlorophenol,5 percent minimum concentration or
creo sote or zinc naphthanate, following the protective measures outlined
in Subsection 2506.4.
25-10
NOTES
25-11
CHAPTER26
REINFORCED GYPSUM CONCRETE
2601 DESIGN
2602 STANDARDS
2603 STRESSES
2604 TESTS
2605 CONSTRUCTION DETAILS
2601 DESIGN
26-1
2602 STANDARDS
The Standards listed in Appendix A are hereby adopted to supplement, but not super
sede, the specific requirements set forth herein.
2603 STRESSES
Allowable unit working stresses and ultimate compressive stresses for Reinforced Gyp
sum Concrete shall be as follows:
UNIT WORK,I G -R SS S
1
Qas,sA
Type of. Stress. P,otnds per I .Pound' per
S • uare s - !!la ' btch
• ru:h
Comp sion-flexu al 220
Compr -. sio:111.-B arin.g 125 1 5
Bond and She - 100 20
: odulus of Elas.tkity 10 600,000
200,000
2604 TESTS
The BCO may require a reasonable number of tests of gypsum-concrete units or the mate
rials of gypsum-concrete construction to determine their quality.
26-2
sectional area of not less than 0.026 square inches per foot of
width
26-3
or No. 12 gauge wire spaced four inches on centres as principal
reinforcing nor less than 0.0075 square inches per foot of width or
No. 14 gauge wire spaced eight inches on centres as temperature
reinforcing, and shall be lapped not less than 16 inches at the
ends. Sides of fabric shall be butted or spaced not more than four
inches.
(e) Where sub-purlins are not used, resistance to uplift loads given in
the Chapter on Live and Dead Loads (Chapter 20) shall be other
wise provided by suitable design equivalent to the sub-purlin.
(h) Suspended ceilings shall not be hung from the gypsum. Such ceil
ings may be hung from the sub-purling where the sub-purling are
so designed.
26-4
(b) Except as otherwise provided in Section 2605.2 (c) of this
Chapter, precast gypsum-concrete units shall have not less than
the follow ing thicknesses:
(1) Solid units shall be not less than two inches thick; if a span
over three feet shall be not less than three inches thick.
(2) Hollow units shall be not less than three inches thick, nor
the shell in compression less than three-fourths inch thick;
in a long span (over three feet), the units shall be not less
than five inches thick nor the shell in compression less than
one and three-eighths inches thick.
(3) Recessed units shall be not less than five inches thick nor
the panel less than one and three-eighths inches thick.
26-5
CHAPTER27
MASONRY
2701 DESIGN
2702 STANDARDS
2703 DEFINITIONS
2704 QUALITY, TESTS AND APPROVALS
2705 ALLOWABLE UNIT STRESSES IN MASONRY
2706 CONSTRUCTION
2701 DESIGN
2702 STANDARDS
2702.1 The Standards listed in Appendix A are hereby adopted as a part of this
Code and supplement, but do not supersede the specific requirements as
set forth herein.
2703 DEFINITIONS
The following words and terms shall for the purpose of this Code, have the meanings set
forth in this Section:
27-1
DIMENSIONS: Dimensions given are nominal; actual dimensions of unit
masonry may not be decreased by more than one half inch (1/ 2").
MASONRY UNIT, any brick, stone, or block conforming to the requirements speci
fied in this Code.
2704.1 GENERAL:
(a) QUALITY: The quality of materials assembled into masonry and
the method and manner of their assembly shall conform to the re
quirements of this Chapter.
(b) OTHER MATERIALS: A material of masonry, other than set
forth herein, which is noncombustible and otherwise sufficiently
em bodies the characteristics and satisfies the requirements of one
of the materials herein may be approved by the BCO subject to
such tests as he may prescribe.
(c) TESTS: The BCO may require materials to be subjected to tests
to determine their quality whenever there is reason to believe the
materials used do not meet the requirements of this Code, and
may require any tests to be repeated if there is any reason to
believe that a material is no longer up to the standards on which
the approval was based. The cost of such tests shall be borne by
the person or persons proposing to use or continue the use of such
material or product. Concrete block strength shall not be less than
400 pounds per square inch.
27-2
(d) APPROVALS:
(1) Only such masonry units as bear the approval of the BCD
and are manufactured or fabricated by plants approved by
the BCD shall be considered acceptable for the
construction of buildings or other structures. Such approval
shall be for a period not exceeding 12 months.
(2) The provisions for tests for approval of masonry units shall
not be construed as a substitute for any tests otherwise re
quired under this Chapter.
2704.2 BRICK:
(a) GENERAL: Brick shall include masonry units usually about two
and one-fourth inches thick, three and three-fourths inches wide,
and eight inches long, and not less than 75 percent solid.
(c) QUALITY:
(1) Burned clay or shale brick shall conform to the Standards
given in the Appendix A.
2704.4 CAST STONE: Cast stone shall be made of Portland cement, aggregates
and water with or without admixtures. Cast stone for load-bearing ma
somy or where exposed to the weather shall have an average
compressive strength, at 28 days, of at least 3000 pounds per square inch
and shall have not more than seven percent water absorption by weight.
(2) Concrete blocks used for fire-resistive walls rated two hours
or more or used for load-bearing or exterior walls shall have
a minimum face-shell thickness of one and one-fourth inches,
a minimum web thickness of one inch, and shall have a net
cross-sectional area not less than 50 percent of the gross
sec tion.
(3) Concrete blocks for other purposes shall have wall and web
thicknesses of not less than three-fourths inch.
(c) QUALITY:
(1) Structural clay load-bearing wall tile shall conform to the
Standards given in Appendix A.
27-4
(c) QUALITY: Gypsum partition tile or block shall conform to the
Standards given in Appendix A.
2704.8 PLAIN CONCRETE: Plain concrete is concrete cast in place and not
rein forced, or reinforced only for shrinkage or change of temperature.
Plain concrete shall be mixed, placed and cured as specified for concrete
in the Chapter on Reinforced Concrete (Chapter 22)., The minimum
strength of regular concrete shall be not less than 2000 psi in 28 days as
determined by 6"x 12" cylinders.
The minimum strength of light weight aggregate shall be not less than
500 psi in 28 days as determined by 6"x 12" cylinders.
2704.10 MORTAR:
(a) GENERAL: Except as otherwise set forth herein, all mortars and
the materials therein shall conform to the "Mortar of Masonry
Units," ASTM C 270.
(b) AGGREGATES:
(1) The gradation of aggregate for masonry mortar shall be
such that the fineness modulus is between 1.20 and 2.35
when de termined in accordance with "Aggregate for
Masonry Mor tar" ASTM C144 - 62T.
(c) MORTAR:
(1) Mortar used to bond unit masonry shall be of Type M, S, N,
or O and shall comply with either the specifications set
forth hereinafter or the Specifications of the Standards set
forth in Paragraph 2704.10 (a).
J\\IORl> SJ:RENGTIJSP
Type
M 2500
1800
N : 0
W".JO
27-5
(2) The type of mortar based on consideration of the location
of the unit masonry construction shall be as follows:
U- orLo!i'.: llin'll
(3) All solid unit masonry shall be laid in full beds with full
end joints. All hollow unit masonry shall be laid with full
mortar coverage of the face shells in both horizontal and
vertical joints.
MORTARP .OPORTl'O
(Parts by Volwne)
Miriiii'ium
•• y,;l.Mt d. Damp•
nJ,1 ndJ lmir o- Le
C1:mi!.-I.
Um tty Aggl,ep'.
s 2000 ] N lk-s.s>!lwli
N .so 1 l-V · _oo
L l,Miui:m:r;1 5{I l 'l:rorot\"
"b j 1 !han31im;es
0
27-6
2705 ALLOWABLE UNIT STRESSES IN MASONRY
2705.1 COMPRESSION:
(a) Allowable working compressive stresses in masonry walls shall
not exceed the limits in pounds per square inch of gross area
given in the following table:
2705.2 SHEAR: The shear in unit masonry shall not exceed one-tenth the allow
able compressive stress.
2706.1 GENERAL:
(a) Masonry walls of hollow or solid units or plain concrete shall be
constructed as specified in this Section.
(c) Reinforced concrete required in this Section shall comply with the
27-7
Chapter on Reinforced Concrete (Chapter 22).
27-8
(d) Reinforced unit masonry shall comply with Sub-section 2706.1
herein.
(e) Second-hand masonry units shall not be used unless they conform
to the requirements of this Code, are sound, and have been thor
oughly cleaned and are approved for use by the BCO.
27-9
Load bearing walls shall be analyzed and designed for
strength where floor loadings are 60 psf or more, or
where floors are of unusually long span.
(3) Corner tie columns shall be not less than 12 inches in width
on both sides of the corner, and not less in thickness than
the wall nor less than a nominal 8 inches. The unbraced
height shall be taken at the point of positive lateral support
in the direction of consideration or the column may be
designed to resist applicable lateral loads based on rational
analysis.
27-11
(5) Corner tie columns shall be reinforced with not less than
five No. 5 vertical rods, nor less than 0.0125 of the gross
cross sectional area (whichever is greater), tied with No. 2
(1/ 4") closed hoops spaced not more than 12" apart,
staggered so that each longitudinal rod shall have lateral
support provided by the corner of a tie. Vertical reinforcing
shall have starter bars provided in the footing and splices
shall be lapped 24 bar diameters. Starter bars are not
required if the column steel is embedded in the footing
without splices at the bottom of the steel. For No. 5 bars, a
standard lap distance of 15" shall be used. If high strength
steels are used to provide a struc turally designed column,
laps shall conform to the stand ards given in the Chapter on
Reinforced Concrete (Chapter 22).
(6) The concrete tie columns set forth herein are a minimum to
limit masonry panel areas and provide an integrated frame
work for masonry. The spacing of concrete columns for
skel eton frame construction, designed as specified in the
Chap ter on Reinforced Concrete, may exceed the spacing
herein set forth provided the masonry panels have an area
of less than 240 square feet and provided the structural
system is designed to transmit horizontal wind loads to the
columns.
27-13