Column Load (G+2)
Column Load (G+2)
Input Data
No of Stories 3 Unit
Height of Floor 3 m
Beam Size (Primary); Width (b) 230 mm
Depth (D) 450 mm
Beam Size (Secondary); Width (b) 230 mm
Depth (D) 300 mm
Column Size; Width (B) 300 mm
Depth (D) 300 mm
Wall Thickness (External) 230 mm
Wall Thickness (Internal) 230 mm
Soil Bearing Capacity 150 kN/m²
Height of Neck Column
(Footing top to Ground Level) 2 m
Load on Beams
(Primary + Secondary)
Self weight of P.Beam 2.5875 kN/m
Factored Self weight of P.Beam 3.88125 kN/m
Self weight of S.Beam 1.725 kN/m
Factored Self weight of S.Beam 2.5875 kN/m
Wall Loads
Height of External Walls 2.55 m
Height of Inernal Walls 2.55 m
Height of Parapet Walls 1m
Density of Brick Masonry
20 kN/m³
Self weight of E.wall 11.73 kN/m
Factored self weight of E.wall 17.595 kN/m
Self weight of I.wall 11.73 kN/m
Factored Self weight of I.wall 17.595 kN/m
Self weight of Parapet wall 4.6 kN/m
Factored Self weight of Parapet wall 6.9 kN/m
HOD FOR CALCULATION OF COLUMN LOADS IN G+2 BU
m to footing
o Secondary Beam)
38.8125 kN
38.8125 kN
26.1 kN
1544.32 kN
Interior
10%
1698.7534 kN
f Footing
1698.7534 kN
1132.5023 kN
1245.7525 kN
150 kN/m²
8.3050165 m²
2.8818426 m
3m
3m
9 m²
125.83358 kN/m²
g Size is OK
APPROXIMATE METHOD FOR CALCU
Input Data
No of Stories 3 Unit
Height of Floor 3 m
Beam Size (Primary); Width (b) 230 mm
Depth (D) 450 mm
Beam Size (Secondary); Width (b) 230 mm
Depth (D) 300 mm
Column Size; Width (B) 300 mm
Depth (D) 300 mm
Wall Thickness (External) 230 mm
Wall Thickness (Internal) 230 mm
Soil Bearing Capacity 150 kN/m²
Height of Neck Column
(Footing top to Ground Level) 2 m
Load on Beams
(Primary + Secondary)
Self weight of P.Beam 2.5875 kN/m
Factored Self weight of P.Beam 3.88125 kN/m
Self weight of S.Beam 1.725 kN/m
Factored Self weight of S.Beam 2.5875 kN/m
Wall Loads
Height of External Walls 2.55 m
Height of Inernal Walls 2.55 m
Height of Parapet Walls 1m
Density of Brick Masonry
20 kN/m³
Self weight of E.wall 11.73 kN/m
Factored self weight of E.wall 17.595 kN/m
Self weight of I.wall 11.73 kN/m
Factored Self weight of I.wall 17.595 kN/m
Self weight of Parapet wall 4.6 kN/m
Factored Self weight of Parapet wall 6.9 kN/m
HOD FOR CALCULATION OF COLUMN LOADS IN G+2 BU
m to footing
o Secondary Beam)
15.525 kN
15.525 kN
26.1 kN
478.59 kN
Corner
30%
622.167 kN
f Footing
622.167 kN
414.778 kN
456.2558 kN
150 kN/m²
3.0417053 m²
1.7440485 m
1.7 m
1.7 m
2.89 m²
143.5218 kN/m²
g Size is OK
APPROXIMATE METHOD FOR CALC
Input Data
No of Stories 3 Unit
Height of Floor 3 m
Beam Size (Primary); Width (b) 230 mm
Depth (D) 450 mm
Beam Size (Secondary); Width (b) 230 mm
Depth (D) 300 mm
Column Size; Width (B) 300 mm
Depth (D) 300 mm
Wall Thickness (External) 230 mm
Wall Thickness (Internal) 230 mm
Soil Bearing Capacity 150 kN/m²
Height of Neck Column
(Footing top to Ground Level) 2 m
Load on Beams
(Primary + Secondary)
Self weight of P.Beam 2.5875 kN/m
Factored Self weight of P.Beam 3.88125 kN/m
Self weight of S.Beam 1.725 kN/m
Factored Self weight of S.Beam 2.5875 kN/m
Wall Loads
Height of External Walls 2.55 m
Height of Inernal Walls 2.55 m
Height of Parapet Walls 1m
Density of Brick Masonry
20 kN/m³
Self weight of E.wall 11.73 kN/m
Factored self weight of E.wall 17.595 kN/m
Self weight of I.wall 11.73 kN/m
Factored Self weight of I.wall 17.595 kN/m
Self weight of Parapet wall 4.6 kN/m
Factored Self weight of Parapet wall 6.9 kN/m
HOD FOR CALCULATION OF COLUMN LOADS IN G+2 B
am to footing
no Secondary Beam)
27.16875 kN
27.16875 kN
26.1 kN
1113.26 kN
Side Column
15%
1280.251875 kN
of Footing
1280.251875 kN
853.50125 kN
938.851375 kN
150 kN/m²
6.259009167 m²
2.501801184 m
2.6 m
2.6 m
6.76 m²
126.2575814 kN/m²
g Size is OK