APPROXIMATE METHOD FOR CALCU

Input Data
No of Stories 3 Unit
Height of Floor 3 m
Beam Size (Primary); Width (b) 230 mm
Depth (D) 450 mm
Beam Size (Secondary); Width (b) 230 mm
Depth (D) 300 mm
Column Size; Width (B) 300 mm
Depth (D) 300 mm
Wall Thickness (External) 230 mm
Wall Thickness (Internal) 230 mm
Soil Bearing Capacity 150 kN/m²
Height of Neck Column
(Footing top to Ground Level) 2 m

Plinth Height above G.L 600 mm


RCC Density 25 kN/m³
Slab Thickness (Roof) 125 mm
Slab Thickness (Floor) 125 mm
Live Load on Roof 1.5 kN/m²
Live Load on Floor 3 kN/m²
Floor Finishing 1 kN/m²
Waterproofing Load 0.8 kN/m²
Thickness of Parapet wall 230 mm

Load on Roof Slab


Thickness of slab 0.125 m
Self Weight 3.125 kN/m²
Live Load 1.5 kN/m²
Floor Finish 1 kN/m²

Waterproofing 0.8 kN/m²


Total Load 6.425 kN/m²
Factored Load 9.6375 kN/m²

Load on Floor Slab


Thickness of slab
0.125 m
Self Weight 3.125 kN/m²
Live Load 3 kN/m²
Floor Finish
1 kN/m²
Total Load 7.125 kN/m²
Factored Load 10.6875 kN/m²

Load on Beams
(Primary + Secondary)
Self weight of P.Beam 2.5875 kN/m
Factored Self weight of P.Beam 3.88125 kN/m
Self weight of S.Beam 1.725 kN/m
Factored Self weight of S.Beam 2.5875 kN/m

Wall Loads
Height of External Walls 2.55 m
Height of Inernal Walls 2.55 m
Height of Parapet Walls 1m
Density of Brick Masonry
20 kN/m³
Self weight of E.wall 11.73 kN/m
Factored self weight of E.wall 17.595 kN/m
Self weight of I.wall 11.73 kN/m
Factored Self weight of I.wall 17.595 kN/m
Self weight of Parapet wall 4.6 kN/m
Factored Self weight of Parapet wall 6.9 kN/m
HOD FOR CALCULATION OF COLUMN LOADS IN G+2 BU

Plinth Beam to footing


Column Load Calculation (No walls and no Secondary Bea
Column No 6 Beam Load (P)
Length of Slab Surrounded 6m Total Load
Width of Slab Surrounded 4m
Total Self-weight of Column
Area of Slab 24 m² (Col Area x Ht of Col x 25)
Length of P.Beam 10 m
Length of S.Beam 3m
Wall Length under P.Beam 10 m Total Load on Column
Wall Length under S.Beam 3m
Parapet Wall Length 0m Note:- For interior columns, we should consid
side columns – 11% to 15% and for corner co
for bending due to fixity.

Load on Column Type of Column


Roof to 2nd Floor Increment in Load
Roof Load 231.3 KN Total Axial Load on Column
Beam Load (P) 38.8125 kN
Beam Load (S) 3.88125 kN Size of Footing
Wall Load (P) 175.95 KN Total Axial Load on Column
Wall Load (S) 26.3925 kN Column Working Load
Parapet wall Load 0 kN Design Load of Footing
Total Load 476.34 kN Soil Bearing Capacity
Footing Area Required
2nd Floor to 1st Floor Side of square footing required
Floor Load 256.5 KN Size provided; L
Beam Load (P) 38.8125 kN B
Beam Load (S) 3.88125 kN Area of Footing Provided
Wall Load (P) 175.95 KN Net Soil Pressure
Wall Load (S) 26.3925 kN
Parapet wall Load 0 kN Footing Size is OK
Total Load 501.536 kN

1st Floor to Plinth


Floor Load 256.5 kN
Beam Load (P) 38.8125 kN
Beam Load (S) 3.88125 kN
Wall Load (P) 175.95 kN
Wall Load (S) 26.3925 kN
Total Load 501.536 kN
S IN G+2 BUILDING

m to footing
o Secondary Beam)
38.8125 kN
38.8125 kN
26.1 kN

1544.32 kN

ns, we should consider an increment of 0 to 10%, For


% and for corner columns – 16% to 33% as allowance

Interior
10%
1698.7534 kN

f Footing
1698.7534 kN
1132.5023 kN
1245.7525 kN
150 kN/m²
8.3050165 m²
2.8818426 m
3m
3m
9 m²
125.83358 kN/m²

g Size is OK
APPROXIMATE METHOD FOR CALCU
Input Data
No of Stories 3 Unit
Height of Floor 3 m
Beam Size (Primary); Width (b) 230 mm
Depth (D) 450 mm
Beam Size (Secondary); Width (b) 230 mm
Depth (D) 300 mm
Column Size; Width (B) 300 mm
Depth (D) 300 mm
Wall Thickness (External) 230 mm
Wall Thickness (Internal) 230 mm
Soil Bearing Capacity 150 kN/m²
Height of Neck Column
(Footing top to Ground Level) 2 m

Plinth Height above G.L 600 mm


RCC Density 25 kN/m³
Slab Thickness (Roof) 125 mm
Slab Thickness (Floor) 125 mm
Live Load on Roof 1.5 kN/m²
Live Load on Floor 3 kN/m²
Floor Finishing 1 kN/m²
Waterproofing Load 0.8 kN/m²
Thickness of Parapet wall 230 mm

Load on Roof Slab


Thickness of slab 0.125 m
Self Weight 3.125 kN/m²
Live Load 1.5 kN/m²
Floor Finish 1 kN/m²

Waterproofing 0.8 kN/m²


Total Load 6.425 kN/m²
Factored Load 9.6375 kN/m²

Load on Floor Slab


Thickness of slab
0.125 m
Self Weight 3.125 kN/m²
Live Load 3 kN/m²
Floor Finish
1 kN/m²
Total Load 7.125 kN/m²
Factored Load 10.6875 kN/m²

Load on Beams
(Primary + Secondary)
Self weight of P.Beam 2.5875 kN/m
Factored Self weight of P.Beam 3.88125 kN/m
Self weight of S.Beam 1.725 kN/m
Factored Self weight of S.Beam 2.5875 kN/m

Wall Loads
Height of External Walls 2.55 m
Height of Inernal Walls 2.55 m
Height of Parapet Walls 1m
Density of Brick Masonry
20 kN/m³
Self weight of E.wall 11.73 kN/m
Factored self weight of E.wall 17.595 kN/m
Self weight of I.wall 11.73 kN/m
Factored Self weight of I.wall 17.595 kN/m
Self weight of Parapet wall 4.6 kN/m
Factored Self weight of Parapet wall 6.9 kN/m
HOD FOR CALCULATION OF COLUMN LOADS IN G+2 BU

Plinth Beam to footing


Column Load Calculation (No walls and no Secondary Bea
Column No 1 Beam Load (P)
Length of Slab Surrounded 2m Total Load
Width of Slab Surrounded 2m
Total Self-weight of Column
Area of Slab 4 m² (Col Area x Ht of Col x 25)
Length of P.Beam 4m
Length of S.Beam 0m
Wall Length under P.Beam 4m Total Load on Column
Wall Length under S.Beam 0m
Parapet Wall Length 4m Note:- For interior columns, we should consid
side columns – 11% to 15% and for corner co
for bending due to fixity.

Load on Column Type of Column


Roof to 2nd Floor Increment in Load
Roof Load 38.55 KN Total Axial Load on Column
Beam Load (P) 15.525 kN
Beam Load (S) 0 kN Size of Footing
Wall Load (P) 70.38 KN Total Axial Load on Column
Wall Load (S) 0 kN Column Working Load
Parapet wall Load 27.6 kN Design Load of Footing
Total Load 152.05 kN Soil Bearing Capacity
Footing Area Required
2nd Floor to 1st Floor Side of square footing required
Floor Load 42.75 KN Size provided; L
Beam Load (P) 15.525 kN B
Beam Load (S) 0 kN Area of Footing Provided
Wall Load (P) 70.38 KN Net Soil Pressure
Wall Load (S) 0 kN
Parapet wall Load 27.6 kN Footing Size is OK
Total Load 156.255 kN

1st Floor to Plinth


Floor Load 42.75 kN
Beam Load (P) 15.525 kN
Beam Load (S) 0 kN
Wall Load (P) 70.38 kN
Wall Load (S) 0 kN
Total Load 128.655 kN
S IN G+2 BUILDING

m to footing
o Secondary Beam)
15.525 kN
15.525 kN
26.1 kN

478.59 kN

ns, we should consider an increment of 0 to 10%, For


% and for corner columns – 16% to 33% as allowance

Corner
30%
622.167 kN

f Footing
622.167 kN
414.778 kN
456.2558 kN
150 kN/m²
3.0417053 m²
1.7440485 m
1.7 m
1.7 m
2.89 m²
143.5218 kN/m²

g Size is OK
APPROXIMATE METHOD FOR CALC
Input Data
No of Stories 3 Unit
Height of Floor 3 m
Beam Size (Primary); Width (b) 230 mm
Depth (D) 450 mm
Beam Size (Secondary); Width (b) 230 mm
Depth (D) 300 mm
Column Size; Width (B) 300 mm
Depth (D) 300 mm
Wall Thickness (External) 230 mm
Wall Thickness (Internal) 230 mm
Soil Bearing Capacity 150 kN/m²
Height of Neck Column
(Footing top to Ground Level) 2 m

Plinth Height above G.L 600 mm


RCC Density 25 kN/m³
Slab Thickness (Roof) 125 mm
Slab Thickness (Floor) 125 mm
Live Load on Roof 1.5 kN/m²
Live Load on Floor 3 kN/m²
Floor Finishing 1 kN/m²
Waterproofing Load 0.8 kN/m²
Thickness of Parapet wall 230 mm

Load on Roof Slab


Thickness of slab 0.125 m
Self Weight 3.125 kN/m²
Live Load 1.5 kN/m²
Floor Finish 1 kN/m²

Waterproofing 0.8 kN/m²


Total Load 6.425 kN/m²
Factored Load 9.6375 kN/m²

Load on Floor Slab


Thickness of slab
0.125 m
Self Weight 3.125 kN/m²
Live Load 3 kN/m²
Floor Finish
1 kN/m²
Total Load 7.125 kN/m²
Factored Load 10.6875 kN/m²

Load on Beams
(Primary + Secondary)
Self weight of P.Beam 2.5875 kN/m
Factored Self weight of P.Beam 3.88125 kN/m
Self weight of S.Beam 1.725 kN/m
Factored Self weight of S.Beam 2.5875 kN/m

Wall Loads
Height of External Walls 2.55 m
Height of Inernal Walls 2.55 m
Height of Parapet Walls 1m
Density of Brick Masonry
20 kN/m³
Self weight of E.wall 11.73 kN/m
Factored self weight of E.wall 17.595 kN/m
Self weight of I.wall 11.73 kN/m
Factored Self weight of I.wall 17.595 kN/m
Self weight of Parapet wall 4.6 kN/m
Factored Self weight of Parapet wall 6.9 kN/m
HOD FOR CALCULATION OF COLUMN LOADS IN G+2 B

Plinth Beam to footing


Column Load Calculation (No walls and no Secondary Be
Column No 11 Beam Load (P)
Length of Slab Surrounded 4m Total Load
Width of Slab Surrounded 3m
Total Self-weight of Column
Area of Slab 12 m² (Col Area x Ht of Col x 25)
Length of P.Beam 7m
Length of S.Beam 6m
Wall Length under P.Beam 7m Total Load on Column
Wall Length under S.Beam 6m
Parapet Wall Length 4m Note:- For interior columns, we should consid
side columns – 11% to 15% and for corner co
bending due to fixity.

Load on Column Type of Column


Roof to 2nd Floor Increment in Load
Roof Load 115.65 KN Total Axial Load on Column
Beam Load (P) 27.1687 kN
Beam Load (S) 7.7625 kN Size of Footing
Wall Load (P) 123.165 KN Total Axial Load on Column
Wall Load (S) 52.785 kN Column Working Load
Parapet wall Load 27.6 kN Design Load of Footing
Total Load 354.13 kN Soil Bearing Capacity
Footing Area Required

2nd Floor to 1st Floor Side of square footing required


Floor Load 128.25 KN Size provided; L
Beam Load (P) 27.1687 kN B
Beam Load (S) 7.7625 kN Area of Footing Provided
Wall Load (P) 123.165 KN Net Soil Pressure
Wall Load (S) 52.785 kN
Parapet wall Load 27.6 kN Footing Size is OK
Total Load 366.731 kN

1st Floor to Plinth


Floor Load 128.25 kN
Beam Load (P) 27.1687 kN
Beam Load (S) 7.7625 kN
Wall Load (P) 123.165 kN
Wall Load (S) 52.785 kN
Total Load 339.131 kN
S IN G+2 BUILDING

am to footing
no Secondary Beam)
27.16875 kN
27.16875 kN
26.1 kN

1113.26 kN

ns, we should consider an increment of 0 to 10%, For


% and for corner columns – 16% to 33% as allowance for

Side Column
15%
1280.251875 kN

of Footing
1280.251875 kN
853.50125 kN
938.851375 kN
150 kN/m²

6.259009167 m²
2.501801184 m
2.6 m
2.6 m
6.76 m²
126.2575814 kN/m²

g Size is OK