Prevention is the key to eliminating the conditions that may contribute to the cause of any fire or
loss of life. Apart from arson, major causes of school fires include improper handling and storage
of flammable liquids, overloaded electrical outlets, and excessive cumulative combustible
materials.
The Office of Public Education Facilities Modernization (OPEFM), Safety, Regulatory and
Environmental Compliance Section, in collaboration with the DC Fire Marshal’s Office, has
developed the following compilation to assist school administrators and personnel responsible
for the daily maintenance of physical facilities in schools. It includes building features,
maintenance, and operational requirements from the International Fire Code (IFC) and applicable
National Fire Protection Association (NFPA) standards.
• Principals and teachers must inspect all exit facilities daily in order to make sure that all
stairways, doors, and other exits are in proper condition. Exit discharge areas and outside
steps must be kept clear of snow, ice, or debris accumulations that could impede egresses.
• Exit doors must be easily opened from the side of egresses. Only one locking or latching
device is permitted on any exit door. Locking devices that require the use of a key, tool,
or special knowledge to open from the egress side of the door are strictly prohibited.
1
This Protocol contains information developed and implemented by District of Columbia Public Schools and can be
used as a guideline for other District LEAs. Each LEA should review and edit the contents to conform to their
procedures and contacts.
• Exit doors must never be chained, locked, slide-bolted or barred against an egress when a
building is occupied. (A building is considered to be occupied when 10 or more adults or
one student is present in a facility.)
• Means of egress must be marked with illuminated signs except where locations of exits
are otherwise obvious.
• Storage of any type is prohibited in a stairway. Clothing and personal effects must not be
stored in hallways unless the building is protected by an automatic sprinkler system, the
hallway is protected by a smoke detection system, or storage is in metal lockers.
Combustible or flammable materials must not be placed, stored, or kept in any portion of
an exit.
• Any fire door (e.g., stairwell door) that is designated to normally be kept closed
(equipped with a self-closing mechanism) must not be blocked open. These doors may be
equipped with a magnetic hold-open device if it releases the door automatically upon
activation of smoke detectors, which are supervised by the building’s fire alarm system.
• Mirrors must not be placed in or adjacent to an exit in a way that would confuse the
direction of egress. Draperies and similar hangings must not obscure an exit.
• Vending machines, display boards, signs, coat racks, and any other movable equipment
that obstructs the path of egress travel is prohibited. Exit access corridors shall be not less
than six feet clear width.
• Any penetrations through fire separation walls, ceilings, or floors must be sealed with an
appropriate sealing compound or device. Ordinary caulking or duct seal are not
acceptable for this purpose.
• Student-prepared artwork and teaching materials may be attached directly to the walls
and must not exceed 20 percent of wall areas.
• Draperies, curtains, and similar furnishings and decorations must be flame resistant and
certified as passing the flame resistance testing of NFPA 701 and must not exceed 10
percent of wall and ceiling area.
• Display of live or fresh-cut trees, even during the holiday season, is prohibited in all
educational buildings. Noncombustible artificial trees may be displayed in locations that
will not interfere with egress.
General housekeeping
• Only items associated with operations of the boiler room and/or mechanical rooms should
be stored in these areas. No combustible materials are to be stored in these areas.
• Storage areas and supply rooms must be kept neat and orderly. Empty cartons, old
decorations, and other items should not be allowed to accumulate. Storage of these
materials must be separated from heat sources. Note: Pallets are not required for storage
of combustible materials/boxes or for keeping them “off of the floor.”
• Maintain storage height to 24 inches or more below the ceiling in nonsprinklered
buildings, or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas
of the building.
• All materials subject to slow oxidation (e.g., paint rags, wax rags, oil mops, etc.) should
be stored in approved, closed metal containers until they can be either laundered or
disposed of properly.
• Volatile and flammable liquids (duplicating fluids, paints, paint thinners, oils, wax,
gasoline, etc.) must be stored in approved containers. Use of these materials is prohibited
in areas where there are open flames, electrical sparks, and running motors. Bulk storage
of such materials must be in specified flammable-liquid storage rooms only. In the
absence of such a special room, they must be stored in outside areas such as tractor
storage rooms.
• Refer to the Classroom HAZMAT Storage Checklist to be utilized in schools that is
available for download at the ESA website: http://esa.dc.gov
Fire extinguishers
• All portable fire extinguishers must be checked monthly for obvious damage, broken
seals, and to ensure that the gauge is in the operable range or, if not equipped with a
gauge, for the proper weight. School-based personnel are responsible for monthly
inspection of fire extinguishers.
• Pressurized water extinguishers (or any other extinguisher that carries a 2-A rating) in
hallways must be placed so that the travel distance to reach extinguisher is no more than
75 feet (distance between extinguishers cannot exceed 150 feet). All laboratories, shops,
mechanical and boiler rooms, and other areas containing special hazards must have an
extinguisher(s) rated for use with A, B, and C-type hazards. Portable fire extinguishers
must be installed in all kitchens and must be compatible with the automatic suppression
system agent used in the hood suppression system.
• A thorough inspection by trained personnel, following maintenance procedures in NFPA
10, the Standard for Portable Fire Extinguishers, is required annually.
Location of classrooms
Emergency lights
• All emergency lighting systems must be tested for proper operation for a minimum of 30
seconds every month. School-based personnel are responsible for the monthly inspection
of emergency lights.
• On an annual basis, a test must be conducted for 1 1/2–hour duration. Equipment must
function properly during the test.
• Written records of all tests must be maintained for review by the Fire Marshal.
Areas of assembly (auditoriums, gymnasiums, multipurpose rooms)
• All assembly rooms must post a sign displaying the maximum capacity as determined by
the Department of Regulatory Affairs.
• When utilizing areas of assembly during school hours or for any other purpose, the
maximum capacity may not be exceeded.
• When arranging folding seats or chairs for programs, exit aisles must be maintained.
Aisles must not be less than 36 inches wide where serving seats on one side only, and not
less than 42 inches wide where serving seats on both sides. The space between parallel
rows of seats must not constitute an aisle. Not more than six seats shall intervene between
any seat and an aisle (12 seats per parallel row). All aisle spaces must remain
unobstructed.
• Do not block electrical panels. Maintain at least 3 feet of clear space in front of the width
of all electrical panels.
• Cords and plugs on electrical equipment as well as extension cords must be visually
inspected before each use. This required inspection should include an examination for
external damage and defects (such as missing or deformed prongs, loose parts, or
damaged outer jacket or insulation) as well as evidence of possible internal damage (such
as a pinched or crushed outer jacket).
• Never overload an electrical outlet. Never interconnect or daisy-chain power strips. Use
surge protectors only with electronic computer equipment and equipment that requires
such protection.
• Use only UL-approved grounded, three-prong plug heavy duty extension cords.
Extension cords should never be used in lieu of permanent wiring and can only be used
for portable equipment.
• Keep wiring away from doorways and windows. Never run wiring or extension cords
under carpeting, above ceilings, or through walls.
Fire drills
• At least two fire drills must be conducted during the first two weeks of the school year,
and one a month thereafter.. When weather is severe during the winter months, at least
six drills must be held at the beginning of the school year, and four drills after the winter
months to complete the required drills.
• Evaluate the effectiveness and operation of the fire alarm system (You may refer to the
Fire Alarm Evaluations in the Prevention Protocols, Section 6, of the School Emergency
Response Plan and Management Guide for additional information.)
• Announce the first fire drill of the school year in advance so that instructions can be
given and procedures established. Procedures, not time, should be most important for the
first drill.
• At least one fire drill in the fall and one in the spring should be conducted for adult
education programs.
• At least one fire drill during the first week of any summer school program, or any special
programmed activity (e.g. summer recreation program) must be conducted.
• Fire drills should be conducted under a variety of conditions: different times of school
day, during lunch periods, during class changes, during assemblies, etc., to avoid
distinction between drills and actual fires.
• Drills should be conducted with a primary exit route blocked to test use of secondary exit
routes.
• For DCPS or any schools with fire alarm monitoring, each time a fire drill is
conducted, security/monitor must be contacted to alert personnel monitoring all school
fire alarm systems that a building evacuation drill is being conducted (not an actual
emergency situation). Once the drill has been completed, a follow-up call should be
placed to security/monitor to verify that the building’s alarm signal was received by
monitoring personnel.
• A record of each fire drill must be maintained at each school and office for review by the
fire marshal. These reports must include the following:
o Time and date the drill was conducted;
o Weather conditions at the time of evacuation;
o Number of occupants evacuated;
o Total time of evacuation; and
o Other information relevant to the drill.
• DC Public Schools specific requirements:
o Number of mobility impaired persons present during drill;
o Number of mobility impaired persons assisted out of the building;
o Areas of refuge or staging areas used for the mobility impaired; and
o Fire alarm system operational.
• Utilize the School Emergency Procedures Guide (flipchart) following the Evacuation
procedures for buildings during all fire drills. Refer to your school’s Emergency
Response Plan for specific information.
• Note any fire alarm deficiencies discovered during the drill and call for emergency
repairs.
• Fire alarms in schools do not notify Emergency Responders. This must be done with a
call to 911 either directly or through an alarm monitoring service.
Fire watch
• If the fire alarm system is inoperable, the authority having jurisdiction (AHJ) requires
that a fire watch be implemented until service is restored.
• Fire watch forms are available on the ESA website.
Fire emergency
• If a fire is discovered, the fire alarm must immediately be activated and the building
evacuated without delay. After evacuation has been initiated, personnel trained in fire
extinguisher operation may attempt to suppress the fire if, in their judgment, this can be
accomplished without risk of injury. Evacuation should never be delayed to attempt fire
suppression.
• Once the building has been evacuated, no one must be allowed to reenter the school until
fire fighting units have arrived and they completely search the building. All students and
personnel must remain at the evacuation staging area until the fire incident commander
declares the building safe to enter.
• If school personnel suspect a fire, or determine that an actual fire exists, they must
immediately activate the fire alarm evacuation signal and call the fire department at 911.
All fires, regardless of magnitude, must be reported to the fire department. This is strictly
enforced by the fire marshal.
• Refer to your school’s Emergency Response Plan for specific information.
Fire inspections
• During inspections by the FEMS Fire Inspector, the principal/designee must accompany
the fire official during the entire facility assessment. Other officials having a role during
the inspection process include building maintenance staff, facility manager, safety
officer, etc.
• At the conclusion of the inspection, obtain a copy of the field report prepared by the Fire
Inspector and retain this for school records
This collection does not cover all aspects of the Fire Code; for situations that are not fully
addressed, or if further clarification is required, please contact the OPEFM Safety, Regulatory
and Environmental Compliance Section at (202)576–8962 or the DC Fire Marshal’s Office at
(202) 727-1600.