User Manual

UPS EPSILON
On-line Double Conversion 1K/2K/3K

Uninterruptible Power Supply System

www.qbex.com
Table of Contents
1. Important Safety Warning……………………………………………… 4
1-1. Transportation.......................................................................................... 4
1-2. Preparation.............................................................................................. 4
1-3. Installation................................................................................................ 4
1-4. Operation................................................................................................. 5
1-5. Maintenance, service and faults.............................................................. 5

2. Installation and setup………………………………………………...... 6


2-1. Rear panel view....................................................................................... 6
2-2. Setup the UPS......................................................................................... 9

3. Operations…………………………………………………………....... 8
3-1. Button operation...................................................................................... 12
3-2. LCD Panel............................................................................................... 13
3-3. Audible Alarm........................................................................................... 14
3-4. LCD display wordings index.................................................................... 15
3-5. UPS Setting............................................................................................. 15
3-6. Operating Mode Description.................................................................... 19
3-7. Faults Reference Code............................................................................ 20
3-8. Warning indicator..................................................................................... 20

4. Troubleshooting………………………………………………………... 21

5. Storage and Maintenance……………………………………………… 22

6. Specifications………………………………………………………….. 23
1. Important Safety Warning 1-4. Operation

Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and Do not disconnect the mains cable on the UPS system or the building wiring outlet

UPS
read carefully the following instructions before installing the unit. Do not operate this unit before reading through (shockproof socket outlet) during operations since this would cancel the protective earthing of the
all safety information and operating instructions carefully. UPS system and of all connected loads.

The UPS system features its own, internal current source (batteries). The UPS output sockets
or output terminals block may be electrically live even if the UPS system is not connected to the
1-1. Transportation building wiring outlet.

Please transport the UPS system only in the original package to protect against shock and impact. In order to fully disconnect the UPS system, first press the OFF/Enter button to disconnect the
mains.

1-2. Preparation Prevent no fluids or other foreign objects from inside of the UPS system.

Condensation may occur if the UPS system is moved directly from cold to warm environment. The UPS
system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to
1-5. Maintenance, service and faults
acclimate the environment.
The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified
Do not install the UPS system near water or in moist environments.
maintenance personnel.
Do not install the UPS system where it would be exposed to direct sunlight or near heater.
Caution - risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet),
components inside the UPS system are still connected to the battery and electrically live and dangerous.
Do not block ventilation holes in the UPS housing.
Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no
current is present and no hazardous voltage exists in the terminals of high capability capacitor such as
1-3. Installation BUS-capacitors.

Do not connect appliances or devices which would overload the UPS system (e.g. laser printers) to the UPS Only persons are adequately familiar with batteries and with the required precautionary measures may
output sockets. replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.

Place cables in such a way that no one can step on or trip over them. Caution - risk of electric shock. The battery circuit is not isolated from the input voltage. Hazardous voltages
may occur between the battery terminals and the ground. Before touching, please verify that no voltage is
Do not connect domestic appliances such as hair dryers to UPS output sockets. present!

The UPS can be operated by any individuals with no previous experience. Batteries may cause electric shock and have a high short-circuit current. Please take the precautionary
measures specified below and any other measures necessary when working with batteries:
Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to Remove wristwatches, rings and other metal objects
the UPS system. use only tools with insulated grips and handles.

Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your computer) to connect the When changing batteries, install the same number and same type of batteries.
UPS system to the building wiring outlet (shockproof outlet).
Do not attempt to dispose of batteries by burning them. This could cause battery explosion.
Please use only VDE-tested, CE-marked power cables to connect the loads to the UPS system.
Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may be toxic.
When installing the equipment, it should ensure that the sum of the leakage current of the UPS and the con
nected devices does not exceed 3.5mA. Please replace the fuse only with the same type and amperage in order to avoid fire hazards.

Do not dismantle the UPS system.

4 EPSILON 1K /2K/3K On line UPS EPSILON 1K /2K/3K On line UPS 5


2. Installation and setup

UPS
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please
keep the original package in a safe place for future use.
2K(L) TOWER

NOTE: There are two different types of online UPS: standard and long-run models. Please refer to the following
model table.

Model Type Model Type


1K 1KL
2K Standard 2KL Long-run
3K 3KL

IEC Tipo NEMA Tipo

2-1. Rear panel view


1K (L) TOWER 3K(L) TOWER

IEC Tipo NEMA Tipo IEC Tipo NEMA Tipo

6 EPSILON 1K /2K/3K On line UPS EPSILON 1K /2K/3K On line UPS 7


1K(L) RACK
1 Programmable outlets: connect to non-critical loads.

UPS
2 Output receptacles: connect to mission-critical loads.
3 AC input
4 Input circuit breaker
5 Network/Fax/Modem surge protection
6 Emergency power off function connector (EPO)
7 USB communication port
IEC Tipo NEMA Tipo
8 RS-232 communication port
9 SNMP intelligent slot
10 External battery connection (only available for L model)
11 Output terminal
2K(L) RACK 12 Output circuit breaker
13 Input terminal

2-2. Setup the UPS


Step 1: UPS input connection
IEC Tipo NEMA Tipo Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords.

For 208/220/230/240VAC models: The power cord is supplied in the UPS package.
For 110/115/120/127VAC models: The power cord is attached to the UPS. The input plug is a NEMA
5-15P for 1K, 1KL, 1.5K and 1.5KL models, NEMA 5-20P for 2K and 2KL models.

Note: For Low voltage models: Check if the site wiring fault indicator lights up in LCD panel. It will be illuminated
3K(L) RACK when the UPS is plugged into an improperly wired utility power outlet (Refer to Troubleshooting section).

Step 2: UPS output connection


For socket-type outputs, there two kinds of outputs: programmable outlets and general outlets. Please
connect non-critical devices to the programmable outlets and critical devices to the general outlets.
During power failure, you may extend the backup time to critical devices by setting shorter backup time
for non-critical devices.

For terminal-type input or outputs, please follow below steps for the wiring configuration:
IEC Tipo NEMA Tipo a) Remove the small cover of the terminal block
b) Suggest using AWG14 or 2.1mm2 power cords. Suggest using WG12-10 or 3.3mm2-5.3mm2 power
cords for NEMA type.
c) Upon completion of the wiring configuration, please check whether the wires are securely affixed.
d) Put the small cover back to the rear panel.

8 EPSILON 1K /2K/3K On line UPS EPSILON 1K /2K/3K On line UPS 9


Step 3: Communication connection Step 6: Turn on the UPS
Communication port:
Press the ON/Mute button on the front panel for two seconds to power on the UPS.

UPS
Note: The battery charges fully during the first five hours of normal operation. Do not expect full battery
USB port RS-232 port Intelligent slot
run capability during this initial charge period.

Step 7: Install software


For optimal computer system protection, install UPS monitoring software to fully configure UPS
shutdown. You may insert provided CD into CD-ROM to install the monitoring software. If not, please
To allow for unattended UPS shutdown/start-up and status monitoring, connect the communication cable one end follow steps below to download and install monitoring software from the internet:
to the USB/RS-232 port and the other to the communication port of your PC. With the monitoring software installed,
you can schedule UPS shutdown/start-up and monitor UPS status through PC.
1. Go to the website http://www.power-software-download.com
The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card. When installing either SNMP or 2. Click ViewPower software icon and then choose your required OS to download the software.
AS400 card in the UPS, it will provide advanced communication and monitoring options. 3. Follow the on-screen instructions to install the software.
PS. USB port and RS-232 port can’t work at the same time. 4. When your computer restarts, the monitoring software will appear as an orange plug icon
located in the system tray, near the clock.

Step 4: Network connection


Network/Fax/Phone surge port Step 8: External battery connection (for long-run models only)
Follow the right chart to make external battery connection.

Connect a single modem/phone/fax line into surge-protected “IN” outlet on the back panel of the UPS unit. Connect
from “OUT” outlet to the equipment with another modem/fax/phone line cable.

Step 5: Disable and enable EPO function


Keep the pin 1 and pin 2 closed for UPS normal operation. To activate EPO function, cut the wire between pin 1
and pin 2.

It’s in closed status for UPS


normal operation.

10 EPSILON 1K /2K/3K On line UPS EPSILON 1K /2K/3K On line UPS 11


3. Operations 3-2. LCD Panel

UPS
3-1. Button operation

Button Function
Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to turn
ON/Mute Button on the UPS.
Mute the alarm: When the UPS is on battery mode, press and hold this button
for at least 5 seconds to disable or enable the alarm system. But it’s not applied
to the situations when warnings or errors occur.
Up key: Press this button to display previous selection in UPS setting mode.
Switch to UPS self-test mode: Press and hold ON/Mute button for 5 seconds Display Function
to enter UPS self-testing while in AC mode, ECO mode, or converter mode. Backup time information

Indicates the backup time in pie chart.


Turn off the UPS: Press and hold this button at least 2 seconds to turn off the
OFF/Enter UPS in battery mode. UPS will be in standby mode under power normal or Indicates the backup time in numbers.
Button H: hours, M: minute, S: second
transfer to Bypass mode if the Bypass enable setting by pressing this button.
Confirm selection key: Press this button to confirm selection in UPS setting Fault information
mode.
Indicates that the warning and fault occurs.

Indicates the warning and fault codes, and the codes are listed in
Switch LCD message: Press this button to change the LCD message for input details in 3-5 section.
voltage, input frequency, battery voltage, output voltage and output frequency. Mute operation
Select Button It will return back to default display when pausing for 10 seconds.
Setting mode: Press and hold this button for 5 seconds to enter UPS setting Indicates that the UPS alarm is disabled.
mode when UPS is in standby mode or bypass mode. Output & Battery voltage information
Down key: Press this button to display next selection in UPS setting mode.
Indicates the output voltage, frequency or battery voltage.
Vac: output voltage, Vdc: battery voltage, Hz: frequency

Switch to bypass mode: When the main power is normal, press ON/Mute and Load information
ON/Mute Select buttons simultaneously for 5 seconds. Then UPS will enter to bypass Indicates the load level by 0-25%, 26-50%, 51-75%, and 76-100%.
+ Select Button mode. This action will be ineffective when the input voltage is out of acceptable
range.
OVER LOAD Indicates overload.

SHORT Indicates the load or the UPS output is short circuit.

Programmable outlets information


P1 Indicates that programmable management outlets are working.

12 EPSILON 1K /2K/3K On line UPS EPSILON 1K /2K/3K On line UPS 13


3-4. LCD display wordings index

UPS
Display Function
Mode operation information Abbreviation Display content Meaning
ENA Enable
Indicates the UPS connects to the mains.
DIS Disable
Indicates the battery is working. ESC Escape

Indicates the bypass circuit is working. HLS High loss


LLS Low loss
Indicates the ECO mode is enabled.
ECO BAT Battery
Indicates the Inverter circuit is working. CF Converter
EP EPO
Indicates the output is working.
FA Fan
Battery information
TP Temperature
Indicates the Battery level by 0-25%, 26-50%, 51-75%, CH Charger
and 76-100%.

BATT. FAULT Indicates the battery is fault.


LOW BATT. Indicates low battery level and low battery voltage.
Input & Battery voltage information 3-5. UPS Setting

Indicates the input voltage or frequency or battery voltage.


Vac: Input voltage, Vdc: battery voltage, Hz: input frequency
Parameter 1

There are three parameters to set up the UPS.

Parameter 1: It’s for program alternatives. There are 9


3-3. Audible Alarm programs to set up. Refer to below table.
Parameter 2: and parameter 3 are the setting options
or values for each program.
Battery Mode Sounding every 4 seconds

Low Battery Sounding every second

Overload Sounding twice every second Parameter 2 Parameter 3


Fault Continuously sounding

Bypass Mode Sounding every 10 seconds

14 EPSILON 1K /2K/3K On line UPS EPSILON 1K /2K/3K On line UPS 15


01: Output voltage setting 05: ECO voltage range setting
Interface Setting Interface Setting

UPS
Parameter 3: Output voltage Parameter 2 & 3: Set the acceptable high voltage point and low
For 208/220/230/240 VAC models, you may choose the fo- voltage point for ECO mode by pressing Down key or Up key.
llowing output voltage:
HLS: High loss voltage in ECO mode in parameter 2.
208: presents output voltage is 208Vac
For 208/220/230/240 VAC models, the setting range in
220: presents output voltage is 220Vac
parameter 3 is from +7V to +24V of the nominal voltage.
230: presents output voltage is 230Vac
240: presents output voltage is 240Vac For 110/115/120/127 VAC models, the setting range in
For 110/150/120/127 VAC models, you may choose the following parameter 3 is from +3V to +12V of the nominal voltage.
output voltage:
110: presents output voltage is 110Vac LLS: Low loss voltage in ECO mode in parameter 2.
115: presents output voltage is 115Vac For 208/220/230/240 VAC models, the setting range in
120: presents output voltage is 120Vac parameter 3 is from -7V to -24V of the nominal voltage.
127: presents output voltage is 127Vac For 110/115/120/127 VAC models, the setting voltage in
parameter 3 is from -3V to -12V of the nominal voltage.

02: Frequency Converter enable/disable


Interface Setting 06: Bypass enable/disable when UPS is off
Interface Setting
Parameter 2 & 3: Enable or disable converter mode. You may
choose the following two options: Parameter 3: Enable or disable Bypass function. You may
CF ENA: converter mode enable choose the following two options:
CF DIS: converter mode disable
ENA: Bypass enable
DIS: Bypass disable

03: Output frequency setting


07: Bypass voltage range setting
Interface Setting
Parameter 2 & 3: Output frequency setting. Interface Setting
You may set the initial frequency on battery mode:
BAT 50: presents output frequency is 50Hz Parameter 2 & 3: Set the acceptable high voltage point and
BAT 60: presents output frequency is 60Hz acceptable low voltage point for Bypass mode by pressing the
If converter mode is enabled, you may choose the following Down key or Up key.
output frequency: HLS: Bypass high voltage point
CF 50: presents output frequency is 50Hz For 208/220/230/240 VAC models:
CF 60: presents output frequency is 60Hz 230-264: setting the high voltage point in parameter 3 from
230Vac to 264Vac.
For 110/115/120/127 VAC models:
04: ECO enable/disable 120-132: setting the high voltage point in parameter 3 from
Interface Setting 120Vac to 132Vac
LLS: Bypass low voltage point
Parameter 3: Enable or disable ECO function. You may For 208/220/230/240 VAC models:
choose the following two options: 170-220: setting the low voltage point in parameter 3 from
ENA: ECO mode enable 170Vac to 220Vac
DIS: ECO mode disable For 110/115/120/127 VAC models:
85-115: setting the low voltage point in parameter 3 from
85Vac to 115Vac.

16 EPSILON 1K /2K/3K On line UPS EPSILON 1K /2K/3K On line UPS 17


3-6. Operating Mode Description

Operating mode Description LCD display

UPS
08: Programmable outlets enable/disable

Interface Setting When the input voltage is within


Online mode
acceptable range, UPS will provide pure
and stable AC power to output. The UPS
Parameter 3: Enable or disable programmable outlets. will also charge the battery at online
ENA: Programmable outlets enable mode.
DIS: Programmable outlets disable

Energy saving mode:


ECO mode When the input voltage is within voltage
regulation range, UPS will bypass voltage
09: Programmable outlets setting to output for energy saving.

Interface Setting

Parameter 3:
Set up backup time limits for programmable outlets. When input frequency is within 40 Hz to
0-999: setting the backup time limits in minutes from 0-999 for 70 Hz, the UPS can be set at a constant
programmable outlets which connect to non-critical devices on Frequency output frequency, 50 Hz or 60 Hz. The
battery mode. Converter UPS will still charge battery under this
mode mode.

When the input voltage is beyond the


acceptable range or power failure and
Battery mode
alarm is sounding every 4 second, UPS
will backup power from battery.

When input voltage is within acceptable


Bypass mode range but UPS is overload, UPS will enter
bypass mode or bypass mode can be set
by front panel. Alarm is sounding every 10
second.

UPS is powered off and no output supply


Standby mode power, but still can charge batteries.

18 EPSILON 1K /2K/3K On line UPS EPSILON 1K /2K/3K On line UPS 19


3-7. Faults Reference Code 4. Troubleshooting
If the UPS system does not operate correctly, please solve the problem by using the table below.

UPS
Fault event Fault code Icon Fault event Fault code Icon
Bus start fail 01 x Inverter voltage Low 13 x Symptom Possible cause Remedy
Bus over 02 x Inverter output short 14 SHORT
No indication and alarm even The AC input power is not Check if input power cord
Bus under 03 x Battery voltage too high 27 BATT. FAULT though the mains is normal. connected well. firmly connected to the mains.

Bus unbalance 04 x Battery voltage too low 28 BATT. FAULT The AC input is connected to Plug AC input power cord to
the UPS output. AC input correctly.
Inverter soft start fail 11 x Over temperature 41 x
The icon and the EPO function is activated. Set the circuit in closed
Inverter voltage high 12 x Over load 43 OVER LOAD
EP
warning code flashing position to disable EPO
on LCD display and alarm is function.
sounding every second.

The icon and Line and neutral conductors of UPS Rotate mains power socket by
3-8. Warning indicator flashing on LCD display and input are reversed. 180° and then connect to UPS
alarm is sounding every system.
second.
Warning Icon (flashing) Alarm The external or internal battery is Check if all batteries are
The icon and
flashing on LCD display and incorrectly connected. connected well.
Low Battery LOW BATT. Sounding every second alarm is sounding every
second.
Overload OVER LOAD Sounding twice every second
Fault code is shown as 27 Battery voltage is too high or the Contact your dealer.
and the icon BATT. FAULT is lighting charger is fault.
Battery is not connected Sounding every second
on LCD display and alarm is
continuously sounding.

Over Charge Sounding every second Fault code is shown as 28 Battery voltage is too low or the Contact your dealer.
and the icon BATT. FAULT is lighting charger is fault.
on LCD display and alarm is
continuously sounding.

UPS is overload Remove excess loads from UPS


The icon and OVER LOAD is output.
Site wiring fault Sounding every second flashing on LCD display and UPS is overloaded. Devices connected to Remove excess loads from UPS
alarm is sounding twice every the UPS are fed directly by the electrical output.
second.

EP
network via the Bypass.
EPO enable Sounding every second After repetitive overloads, the UPS is Remove excess loads from UPS

Fan Failure FA Sounding every second


locked in the Bypass mode. Connected
devices are fed directly by the mains.
output first. Then shut down the
UPS and restart it.

Over temperature Sounding every second Fault code is shown as 43 and The UPS shut down automatically Remove excess loads from UPS
because of overload at the UPS output. output and restart it.
Charger failure CH Sounding every second
The icon OVER LOAD is lighting
on LCD display and alarm is
continuously sounding.
Out of bypass voltage range Sounding every second
Fault code is shown as 14 and The UPS shut down automatically Check output wiring and if
the icon SHORT is lighting because short circuit occurs on the connected devices are in short
on LCD display and alarm is UPS output. circuit status.
continuously sounding.

20 EPSILON 1K /2K/3K On line UPS EPSILON 1K /2K/3K On line UPS 21


Symptom Possible cause Remedy 6. Specifications
Fault code is shown as 1, 2, A UPS internal fault has occurred. There Contact your dealer CAPACITY 1000 VA / 800 W 1500 VA / 1200 W 2000 VA / 1600 W 3000 VA / 2400 W
3, 4, 11, 12, 13 and 41 on are two possible results: INPUT
LCD display and alarm is 1. The load is still supplied, but directly Low Line Transfer 160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5 % or 80 VAC / 70 VAC / 60 VAC / 50 VAC ± 5 %
continuously sounding. from AC power via bypass. Voltage ( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
2. The load is no longer supplied by Range Low Line Comeback 175 VAC ± 5 % or 85 VAC ± 5 %
power.
High Line Transfer 300 VAC ± 5 % or 150 VAC ± 5 %
High Line Comeback 290 VAC ± 5 % or 145 VAC ± 5 %
Battery backup time is shorter Batteries are not fully charged Charge the batteries for at least
Frequency Range 40Hz ~ 70 Hz
than nominal value 5 hours and then check
capacity. If the problem still Phase Single phase with ground
persists, consult your dealer. Power Factor ≥ 0.99 @ 220-230 VAC (input voltage)
OUTPUT
Batteries defect Contact your dealer to replace Output voltage 208/220/230/240VAC or 110/115/120/127 VAC
the battery. AC Voltage Regulation ± 3% (Batt. Mode)
Frequency Range 47 ~ 53 Hz or 57 ~ 63 Hz
The icon and the Fan is locked or not working Check fans and notify dealer. (Synchronized Range)
FA
warning code flashing
on LCD display and alarm is
Frequency Range (Batt. Mode) 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
sounding every second. 100%~110%: audible warning
Overload 110%-130%: UPS shuts down in 30 seconds at battery mode or transfers
to bypass mode when the utility is normal.
>130%: UPS shuts down immediately at battery mode or transfer to
bypass mode when the utility is normal.
3:1
5. Storage and Maintenance
Current Crest Ratio
Harmonic Distortion ≥ 3 % THD (Linear Load) ≥ 4 % THD (Linear Load)
≥ 6 % THD (Non-linear Load) ≥ 7 % THD (Non-linear Load)
5-1. Operation Transfer AC Mode to Batt. Mode Zero
Time Inverter to Bypass 4 ms (Typical)
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient Waveform (Batt. Mode) Pure Sinewave
temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer. EFFICIENCY
AC Mode ~ 85% ~ 88%
Battery Mode ~ 83%
BATTERY
Be sure to deliver the spent battery to a recycling facility Standard Battery Type 12 V / 7 AH 12 V / 9 AH 12 V / 7 AH 12 V / 9 AH
or ship it to your dealer in the replacement battery packing Model Numbers 3 3 6 6
Recharge Time 4 hours recover to 90% capacity (Typical)
material.
Charging Current 1.0 A(max.)
Charging Voltage 41.0 VDC ± 1% 82.1 VDC ±1%
Long-run Battery Type & Numbers Depending on the capacity of external batteries
Charging Current
Storage Model
Charging Voltage
4.0 A or 8.0 A(max.)
41.0 VDC ± 1% 82.1 VDC ±1%
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry location. During storage,
PHYSICAL
recharge the battery in accordance with the following table:
Tower Dimension, D X W X H 397 X 145 X 220 (mm) 421 X 190 X 318 (mm)
Case Net Weight (kgs) 13 7 14 7 26 13 28 13
Rack Dimension, D X W X H 420x438x88[2U] (mm) 580x438x133[3U] (mm)
Storage Temperature Recharge Frequency Charging Duration Case Net Weight (kgs) 16 10 17 10 29 17 31 17
-25°C - 40°C Every 3 months 1-2 hours ENVIRONMENT
Operation Humidity 20-90 % RH @ 0- 40°C (non-condensing)
40°C - 45°C Every 2 months 1-2 hours Noise Level Less than 45dBA @ 1 Meter
MANAGEMENT
Smart RS-232 or USB Supports Windows® 2000/2003/XP/Vista/2008/7, Linux, Unix and MAC
Optional SNMP Power management from SNMP manager and web browser
* Derate capacity to 60% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 208VAC.

22 EPSILON 1K /2K/3K On line UPS EPSILON 1K /2K/3K On line UPS 23


Tabla de Contenido
1. Aviso Importante de Seguridad..................................................................... 26
1-1. Transporte...................................................................................................... 26
1-2. Preparación.................................................................................................... 26
1-3. Instalación...................................................................................................... 26
1-4. Operación....................................................................................................... 27
1-5. Mantenimiento, servicio y fallas...................................................................... 27

2. Instalación y ajuste....................................................................................... 28
2-1. Vista trasera del panel.................................................................................... 28
2-2. Ajuste del UPS................................................................................................ 31

3. Operación...................................................................................................... 34
3-1. Botones de operación..................................................................................... 34
3-2. LCD Panel...................................................................................................... 35
3-3. Alarma Audible................................................................................................ 36
3-4. Índice en la pantalla LCD............................................................................... 37
3-5. Ajustes del UPS.............................................................................................. 41
3-6. Descripción del modo de Operación.............................................................. 42
3-7. Referencia de código de fallas....................................................................... 42
3-8. Indicador de Advertencia................................................................................ 42

4. Solución de problemas.................................................................................. 43

5. Almacenamiento y Mantenimiento................................................................ 44

6. Especificaciones............................................................................................ 45
1. Aviso Importante de Seguridad 1-4. Operación

Por favor cumpla estrictamente con todas las advertencias e instrucciones de operación de este manual. Guarde No desconecte el cable principal en el sistema UPS o los cables de salida del edificio durante la

UPS
este manual apropiadamente y lea cuidadosamente las siguientes instrucciones antes de instalar la unidad. No operación, ello anularía la protección de tierra del UPS y de todas las cargas conectadas.
opere esta unidad antes de leer cuidadosamente através de toda la información de seguridad e instrucciones de
operación. El sistema UPS cuenta con su propia fuente de corriente interna (baterías). Las tomas de salida
del UPS o bloque de salida de los terminales puede ser eléctricamente activo, incluso si el
sistema UPS no está conectado a la toma de cableado del edificio.

1-1. Transporte Para desconectar completamente el sistema de UPS, presione primero el OFF / Enter para
desconectar la red eléctrica.
Por favor transporte el sistema UPS solo en el empaque original para proteger de choques e impactos.
Prevenga entrada de fluidos u objetos extraños dentro del sistema UPS.

1-2. Preparación 1-5. Mantenimiento, servicio y fallas

Puede ocurrir condensación si el sistema UPS es movido directamente desde un ambiente frío a caliente. El El sistema UPS opera con voltajes peligrosos. Reparaciones solo pueden llevarse acabo por personal de
sistema UPS debe estar absolutamente seco antes de ser instalado. Por favor, espere al menos dos horas mantenimiento calificado.
para que el sistema de UPS para aclimatarse al medio ambiente.
Precaución – Riesgo de descarga eléctrica. Incluso después de que la unidad esté desconectada de la red
No instale el sistema UPS cerca a agua o ambientes húmedos. eléctrica (enchufe del cableado del edificio), componentes internos del sistema UPS aún está conectado a la
batería y eléctricamente activo y peligroso.
No instale el sistema UPS donde pueda estar expuesto a la luz directa del sol o cerca de calor.
Antes de realizar cualquier tipo de servicio y / o mantenimiento, desconecte las baterías y compruebe que no
No bloquee los orificios de ventilación del UPS. hay corriente presente y no existe tensión peligrosa en los terminales del condensador de alta capacidad
como BUS-condensadores.

Sólo las personas que estén debidamente familiarizados con baterías y con las medidas necesarias de
1-3. Instalación precaución puede reemplazar las baterías y supervisar las operaciones. Las personas no autorizadas deben
mantenerse alejados de las baterías.
No conecte aplicaciones o dispositivos los cuales puedan sobrecargar el sistema UPS (e.g. impresora láser)
a la salida del UPS. Precaución – Riesgo de descarga eléctrica. El circuito de la batería no está aislado de la tensión de entrada.
Tensión peligrosa puede ocurrir entre los terminales de la batería y el suelo. Antes de tocar, por favor
Ubique los cables de una forma adecuada que nadie pueda pisar o tropezar con ellos. verifique que no haya tensión!

No conecte aplicaciones domesticas como secador de pelo a las tomas de salida del UPS. Baterías podría causar descargas eléctricas y tienen una alta corriente de corto circuito. Por favor, tome las
medidas cautelares indicadas a continuación y las demás medidas necesarias cuando se trabaja con las
El UPS puede ser operado por cualquier individuo sin previa experiencia. baterías:
Retírese relojes de pulsera, anillos y otros objetos.
Conecte el sistema UPS sólo a una salida puesta a tierra que debe ser fácilmente accesible y cerca del Utilizar sólo herramientas con mangos y manija aisladas.
sistema de UPS.
Cuando cargue las baterías, instale el mismo número y tipo de baterías.
Por favor, use sólo cable de red certificado (por ejemplo, el cable de red de su ordenador) para conectar el
sistema UPS a la toma de corriente de un edificio. No intente desechar las baterías por la quema de ellos. Esto podría provocar una explosión de la batería.

Por favor use solo cable certificado para conectar las cargas al sistema UPS. No abrir o destruir las baterías. Escape de electrolitos puede causar lesiones en la piel y los ojos.
Puede ser tóxico.
Cuando instale el equipo, asegúrese que la suma de corrientes de fuga del UPS no excedan 3.5mA. Por favor reemplace el fusible solo con el mismo tipo y amperaje a fin de evitar riesgos de incendio.
No desmonte el sistema UPS.

26 EPSILON 1K /2K/3K On line UPS EPSILON 1K /2K/3K On line UPS 27


2. Instalación y ajuste

UPS
NOTE: Antes de instalar, por favor inspeccione la unidad. Asegúrese que no hay nada dañado dentro del
empaque. Por favor mantenga el empaque original en un lugar seguro para futuros usos.
2K (L) TORRE

NOTA: Hay dos tipos diferentes de UPS online: Modelo estándar y larga duración. Por favor refiérase a la
siguiente tabla.

Modelo Tipo Modelo Tipo


1K 1KL
2K Estándar 2KL Larga
3K 3KL duración

Tipo IEC Tipo NEMA

2-1. Vista trasera del panel


1K (L) TORRE 3K (L) TORRE

Tipo IEC Tipo NEMA Tipo IEC Tipo NEMA

28 EPSILON 1K /2K/3K On line UPS EPSILON 1K /2K/3K On line UPS 29


1K(L) RACK 1 Salidas Programables: Conexión para cargas no críticas.
2 Receptáculos de salida: Conexión para cargas de misión crítica.
3 Entrada AC

UPS
4 Interruptor de circuito de entrada
5 Proteccion de picos para terminal de Red/Fax/Modem
6 Conector de function apagado de emergencia (EPO)
7 Puerto de comunicación USB
8 RS-232 puerto de comunicaciones inteligentes ranura SNMP
Tipo IEC Tipo NEMA
9 Conexión Batería Externa (Solo habilitada para modelo L)
10 Terminal de Salida
11 Interruptor de circuito de salida
12 Terminal de entrada
2K(L) RACK

2-2. Ajustes del UPS


Paso 1: Conexión de entrada del UPS
Conecte el UPS conector de tres hilos, dos polos y receptáculo conectado a tierra. Evite el uso de cables de
extensión

Para modelos 208/220/230/240VAC: El cable de alimentación esta incluido en el empaque del UPS.
Tipo IEC Tipo NEMA Para modelos 110/115/120/127VAC: El cable de alimentación esta conectado al UPS. El conector de
entrada es un NEMA 5-15P para modelos 1K y 1KL, NEMA 5-20P para modelos 2K y 2KL.

Nota: Para modelos de bajo voltaje: Revise si el indicador de falla en cableado del sitio esta indicando falla en
el panel frontal. Este se iluminara cuando el UPS esta conectado no apropiadamente (Refiérase a la sección de
Guía de Fallas).
3K(L) RACK

Paso 2: Conexión de salida del UPS


Para las salidas tipo socket, hay dos clases de salidas: salidas programables y salidas generales. Por
favor conecte dispositivos no críticos a las salidas programables y dispositivos críticas a las salidas
generales. Durante una falla de alimentación de entrada, usted puede extender el tiempo de respaldo a
dispositivos críticos, acortando el tiempo de respaldo para dispositivos no críticos.

Para terminal tipo entrada o salida, por favor siga los pasos siguientes para configuración del cableado:
a) Remueva la pequeña tapa del bloque de terminales
Tipo IEC Tipo NEMA b) Sugerido usar cable AWG14 o 2.1mm2 para el cable de alimentación. Sugerido usar cable WG12-10
o 3.3mm2-5.3mm2 para el cable de alimentación tipo NEMA.
c) Una vez completada la configuración del cableado, por favor compruebe que los cables están firme
mente fijados.
d) Ponga la pequeña tapa en el panel trasero.

30 EPSILON 1K /2K/3K On line UPS EPSILON 1K /2K/3K On line UPS 31


Paso 3: Conexión de comunicación Paso 6: Encienda el UPS
Puerto de Comunicación:
Presione el botón de ON/Mute ubicado en el panel frontal por dos segundos para encender el UPS.

UPS
Puerto USB Puerto RS-232 Ranura Inteligente
Nota: Las baterías quedaran cargadas totalmente durante las primeras cinco horas de
operación normal. No espere respaldo de la capacidad total de la batería durante el periodo
de carga inicial.

Paso 7: Instale software


Para permitir la vigilancia del apagado y arranque del UPS y monitoreo del estatus, conecte un el cable de
comunicación al Puerto USB/RS-232 y otro al Puerto de comunicación de su PC. Con el software de monitoreo Para optima protección del sistema de su computador, instale software de monitoreo del UPS, para
instalado, usted puede programar el horario de encendido / apagado y monitoreo del UPS através de su PC. total configuración de apagado. Instale el CD proveído dentro de la unidad de CD-ROM para instalar el
software de monitoreo. Si no, por favor siga los pasos siguientes para descargar e instalar el software
El UPS esta equipado con una ranura perfecta inteligente para ambas tarjetas SNMP o AS400. Cuando instale la de monitoreo desde el internet:
tarjeta SNMP o AS400 en el UPS, provee avanzadas opciones de comunicación y monitoreo.
PS. El Puerto USB y RS-232 no pueden trabajar al mismo tiempo.
1. Ir a la página Web http://www.power-software-download.com
2. Presione el icono de ViewPower software y escoja su OS requerido para descargar el software.
Paso 4: Conexión de RED. 3. Siga las instrucciones del software en la pantalla.
4. Cuando restaure su computador, el software de monitoreo aparecerá con un icono de conector
Red/Fax/Puerto de protección de picos naranja localizado en la barra del sistema cerca del reloj.

PASO 8: Conector Externo de Baterías


(Solo para los modelos de larga duración)
Conecte la línea de un modem sencillo/teléfono/fax en el protector de picos de entrada “IN” ubicado en el panel
trasero del UPS. Conecte a la salida “OUT” el equipo con otro cable de línea para modem sencillo/teléfono/fax.

Paso 5: Habilitar y deshabilitar la función de EPO


Mantenga el pin 1 y el pin 2 cerrado para operación normal del UPS. Para activar la función de EPO, abra el
cable entre pin 1 y pin 2.

Esta en estado cerrado,


durante el funcionamiento
normal del UPS

32 EPSILON 1K /2K/3K On line UPS EPSILON 1K /2K/3K On line UPS 33


3. Operaciones 3-2. LCD Panel

UPS
3-1. Botón de operación

Botón Función
Encienda el UPS: Presione el botón de ON/Mute por lo menos 2 segundos
ON/Mute Botón para que encienda el UPS.
Alarma de Silencio (Mute): Cuando el UPS está en modo batería, presione
este botón y espere por lo menos 5 segundos para deshabilitar o habilitar el
sistema de alarma. Esto no se aplica a situaciones de advertencia o cuando
ocurre un error.
Tecla de subir (Up key): Presione este botón par ver la pantalla anterior en el Mostrar Función
modo de ajustes del UPS. Información de tiempo de respaldo
Cambiar el UPS a modo de auto-prueba: Presione el botón ON/Mute y
espere por 5 segundos para iniciar el autodiagnóstico mientras el UPS esta en Indicador de tiempo de respaldo en el grafico circular.
modo AC, modo ECO, o modo Inversor.
Indicador de tiempo de respaldo en números.
Apague el UPS: Presione este botón y espere por lo menos 2 segundos para H: horas, M: minutos, S: segundos
apagar el UPS en modo de batería. El UPS debe estar en modo de espera Información de Falla
OFF/Enter con la energía normal o transferir a modo de Bypass en caso de estar
Botón habilitado. Indica advertencia y ocurrió una falla.
Confirmar tecla de selección: Presione este botón para confirmar lo
Indica advertencia y código de falla, el detalle de los códigos esta
seleccionado en modo ajustes del UPS.
listado en la sección 3-5.
Operación de Silencio
Cambiar mensaje en LCD: Presione este botón para cambiar el mensaje de
la pantalla para voltaje de entrada, frecuencia de entrada, voltaje de batería, Indica que la alarma del UPS está deshabilitada.
salida de voltaje y salida de frecuencia. Este regresara por defecto al display
Select Botón inicial cuando pasen 10 segundos. Información de Voltaje de Salida y Batería
Modo Ajustes: Presione este botón y espere 5 segundos para entrar al modo Indica el voltaje de salida, frecuencia o voltaje de batería.
de ajustes del UPS cuando el UPS esta en modo de stanbye o bypass. Vac: Voltaje de salida, Vdc: Voltaje de batería, Hz: frecuencia
Tecla de bajar (Down key): Presione este botón para seleccionar la siguiente
Información de Carga
pantalla en el modo de ajustes del UPS.
Indica el nivel de carga de 0-25%, 26-50%, 51-75%, y 76-100%.
ON/Mute Cambiar a modo de bypass: Cuando el suministro de energía es normal,
+ Select Botón presione ON/Mute y seleccione los botones simultáneamente por 5
segundos. Luego el UPS entrara en modo de bypass. Esta acción no será OVER LOAD Indica sobrecarga.
eficiente cuando los rangos de entrada de voltaje no son aceptables.
SHORT Indica la carga o el circuito de salida del UPS está en corto circuito.

Información de salidas Programables


P1 Indica que la administración de salidas programables está trabajando.

34 EPSILON 1K /2K/3K On line UPS EPSILON 1K /2K/3K On line UPS 35


3-4. Indice Pantalla LCD

UPS
Mostrar Función
Información del Modo de operación Abreviación Contenido de la pantalla Significado
ENA Habilitado
Indica que el UPS está conectado a la red eléctrica.
DIS Deshabilitado
Indica que la batería está trabajando. ESC Escape

Indica que el circuito de bypass está trabajando HLS Alta perdida


LLS Baja perdida
Indica que el modo ECO está habilitado.
ECO BAT Batería
Indica que el circuito inversor está trabajando. CF Conversor
EP EPO
Indica la salida está trabajando.
FA Ventilador
Información de batería
TP Temperatura
Indica el nivel de batería de 0-25%, 26-50%, 51-75%, y CH Cargador
76-100%.

BATT. FAULT Indica que la batería está en falla.


LOW BATT. Indica bajo nivel de batería y bajo voltaje de batería.
Información de voltaje de entrada & batería 3-5. Ajustes del UPS
Indica el voltaje de entrada o frecuencia o voltaje de batería.
Vac: Voltaje de entrada, Vdc: Voltaje de batería, Hz: Frecuencia
de entrada Parámetro 1

Existen 3 parámetros para configurar el UPS.

Parámetro 1: Es para programas alternativos.


3-3. Alarma Audible Existen 9 programas para ajuste del UPS. Refiérase
a la siguiente tabla.

Modo Batería Pita cada 4 Segundo Parámetro 2 y parámetro 3: Son las opciones de
ajuste o valores para cada programa.
Baja Batería Pita cada Segundo

Sobrecarga Pita dos veces cada Segundo Parámetro 2 Parámetro 3


Falla Pita Continuamente

Modo Bypass Pita cada 10 Segundos

36 EPSILON 1K /2K/3K On line UPS EPSILON 1K /2K/3K On line UPS 37


01: Ajustes de salida de voltaje 05: ECO Ajuste de rango de voltaje
Interfaz Ajuste Interfaz Ajuste

UPS
Parámetro 3: Voltaje de salida
Parámetro 2 & 3: Ajuste el punto del nivel de voltaje alto y bajo
Para modelos 208/220/230/240 VAC, usted debe escoger las
aceptable para el modo ECO presionando la tecla de bajar (Down)
siguientes salidas de voltaje:
o subir (Up).
208: Voltaje de salida presente es 208Vac
HLS: Alto perdida de voltaje en el modo ECO en el parámetro 2.
220: Voltaje de salida presente es 220Vac
Para los modelos 208/220/230/240 VAC, el ajuste del rango en el
230: Voltaje de salida presente es 230Vac
parámetro 3 es desde +7V a +24V de voltaje nominal.
240: Voltaje de salida presente es 240Vac
Para modelos 110/115/120/127 VAC, el ajuste del rango en el
Para modelos 110/150/120/127 VAC, usted puede elegir las
parámetro 3 es desde +3V a +12V del voltaje nominal.
siguientes salidas de voltaje:
LLS: Perdida de bajo voltaje en modo ECO en el parámetro 2.
110: Voltaje de salida presente es 110Vac
Para modelos 208/220/230/240 VAC, el ajuste del rango en el
115: Voltaje de salida presente es 115Vac
parámetro 3 es desde -7V a -24V del voltaje nominal.
120: Voltaje de salida presente es 120Vac
Para modelos 110/115/120/127 VAC, el ajuste del voltaje en
127: Voltaje de salida presente es 127Vac
parámetro 3 es de -3V a -12V del voltaje nominal.

02: Convertidor de Frecuencia habilitado/deshabilitado


Interfaz Ajuste 06: Bypass Habilitado/deshabilitado cuando el UPS esta apagado
Interfaz Ajuste
Parámetro 2 & 3: Habilitado o deshabilita modo conversor.
Puede elegir dos opciones: Parámetro 3: Habilitar o deshabilitar la función de Bypass.
CF ENA: modo conversor habilitado Usted puede elegir las siguientes dos opciones:
CF DIS: modo conversor deshabilitado
ENA: Bypass Habilitado
DIS: Bypass Deshabilitado

03: Ajustes de Frecuencia de salida


07: Bypass ajuste del rango de voltaje
Interfaz Ajuste
Parámetro 2 & 3: Ajuste de frecuencia de salida. Interfaz Ajuste
Usted puede ajustar la frecuencia inicial en modo batería:
BAT 50: Salida de frecuencia presente es 50Hz Parámetro 2 & 3: Ajuste el punto de alto voltaje y bajo voltaje
BAT 60: Salida de frecuencia presente es 60Hz aceptable para modo de Bypass presionando la tecla bajar
Si el modo conversor es habilitado, usted puede elegir la (Down) o Subir (Up).
siguiente frecuencia: HLS: Punto de alto voltaje
CF 50: Salida de frecuencia presente es 50Hz Para modelos 208/220/230/240 VAC:
CF 60: Salida de frecuencia presente es 60Hz 230-264: ajuste el punto de alto voltaje en el parámetro 3 de
230Vac a 264Vac.
Para modelos 110/115/120/127 VAC:
04: ECO Habilitado/Deshabilitado 120-132: ajuste el punto de alto voltaje en el parámetro 3 de
Interfaz Ajuste 120Vac a 132Vac
LLS: Punto de bajo voltaje
Parámetro 3: Para habilitar o deshabilitar la función ECO. Para modelos 208/220/230/240 VAC:
Usted puede elegir las siguiente opciones: 170-220: ajuste el punto de bajo voltaje en parámetro 3 de
170Vac a 220Vac
ENA: ECO Modo Habilitado Para modelos 110/115/120/127 VAC:
DIS : ECO Modo Deshabilitado
85-115: ajuste el punto de bajo voltaje en parámetro 3 de 85Vac
a 115Vac.

38 EPSILON 1K /2K/3K On line UPS EPSILON 1K /2K/3K On line UPS 39


3-6. Operating Mode Description

Modo Operación Descripcion Pantalla LCD

UPS
08: Salidas Programables habilitadas /deshabilitadas

Interface Ajuste Cuando la entrada de voltaje está dentro


Modo Online del rango aceptable, UPS provee energía
AC pura y estable. El UPS también
Parámetro 3: Salidas programables habilitado o deshabilitado. cargará la batería en el modo online.
ENA: Salidas programables habilitado
DIS: Salidas programables deshabilitar

Modo de ahorro de energía:


Cuando la entrada de voltaje esta
dentro del voltaje regulado, UPS pasara a
Modo ECO
bypass proporcionando voltaje a la salida
09: : Ajuste de salidas programables para ahorro de energía.

Interface Ajuste

Parámetro 3: Ajuste los límites del tiempo de respaldo par alas Cuando la entrada de frecuencia esta
salidas programables. dentro 40 Hz a 70 Hz, el UPS puede ser
0-999: Ajuste el límite del tiempo de respaldo en minutos de Modo de ajustado a una constante frecuencia de
0-999 para las salidas programables a la cual conecta los conversor de salida, 50 Hz o 60 Hz. El UPS continuara
dispositivos de carga no critica en modo bacteria. Frecuencia cargando la batería de este modo.

Cuando la entrada de voltaje Cuando el


voltaje de entrada está fuera del rango
Modo Batería aceptable o falta de energía eléctrica y la
alarma está sonando cada 4 segundo 4,
UPS soportara con el respaldo de energía
en batería.

Cuando la entrada está dentro del rango


aceptable pero esta en sobrecarga, el
Modo Bypass UPS entrara en modo de Bypass o puede
ser ajustado manualmente desde el
panel. La Alarma sonara cada 10
segundos.

UPS está apagada y no hay energía de


salida, pero aún continua cargando las
Modo Standby baterías.

40 EPSILON 1K /2K/3K On line UPS EPSILON 1K /2K/3K On line UPS 41


3-7. Referencia de código de fallas 4. Solución de Problemas
Si el sistema no opera correctamente, por favor resuelva el problema usando la tabla siguiente

UPS
Evento de error Código de falla Icono Evento de falla Código falla Icono
Bus comienza a fallar 01 x Bajo Voltaje en Inversor 13 X Sintomas Posible causa Solución
Bus por encima 02 x Salida en corto Inversor 14 SHORT
No hay indicación y alarma La entrada AC no está bien Revise el cable de entrada si está
Bus por debajo 03 x Voltaje de batería alto 27 BATT. FAULT a pesar de que la red es conectada. bien conectado a la red eléctrica.
normal.
Bus desbalanceado 04 x Voltaje de batería bajo 28 BATT. FAULT La entrada AC está conectada Conecte el cable de entrada AC
ala salida del UPS. a la entrada AC correctamente.
Inversor en falla 11 x Sobre temperature 41 X
Inversor con voltaje alto 12 x Sobre carga 43 OVER LOAD
El icono y EP el La función de EPO está activada. Ajuste el circuito en la posición
código de advertencia parpa- de cerrado para deshabilitar la
dea en la pantalla y la alarma función de EPO.
suena cada segundo.

El icono y parpadea Los conductores de línea y neutro de la Rotar la toma de corriente de


3-8. Indicador de Advertencia en la pantalla y la alarma entrada del UPS están invertidos. alimentación a 180 ° y luego
suena cada segundo. conectarse al sistema de UPS.

Advertencia Icon (Parpadeando) Alarma La batería externa o interna está Revise si todas las baterías
El icono y
parpadean en la pantalla y la incorrectamente conectada. están bien conectadas.
Batería baja LOW BATT. Pitando cada Segundo alarma suena cada segundo.

Sobrecarga OVER LOAD Pitando dos veces cada segundo


Código de falla 27 y el icono Voltaje del cargador es también alto o Contacte su distribuidor.
está
BATT. FAULT iluminando en el cargador está fallando.
Batería desconectada Pitando cada Segundo
la pantalla y el sonido de la
alarma es continuo.

Sobrecarga Pitando cada segundo Código de falla 28 y el icono Voltaje del cargador es también bajo o Contacte su distribuidor.
BATT. FAULT está iluminando en el cargador está fallando.
la pantalla y el sonido de la
alarma es continuo.

UPS està sobrecargada Remueva el exceso de carga a


El icono y OVER LOAD la salida del UPS.
Sitio con falla de cableado Pitando cada segundo está iluminando en la pantalla UPS està sobrecargada. Dispositivos co- Remueva el exceso de carga de
y la alarma suena dos veces nectados al UPS están siendo directamente la salida del UPS.
cada segundo.

EP
alimentados por la red eléctrica vía bypass.
EPO Habilitado Pitando cada segundo Después de repetitivas sobrecargas, el Remueva el exceso de carga

Ventilador Fallo FA Pitando cada segundo


UPS se bloquea, en el modo de Bypass.
Conecte los dispositivos para que sean
alimentados directamente.
desde la salida del UPS. Luego
apague el UPS y restáurelo.

Sobre temperature Pitando cada segundo


Código de falla 43 y el icono El UPS se apaga automáticamente Remueva el exceso de carga de la
Falla de carga CH Pitando cada segundo OVER LOAD está iluminando en
la pantalla y la alarma suena
porque la salida del UPS está
sobrecargada.
salida del UPS y restáurelo.

continuamente.
Fuera del Rango de voltaje Pitando cada segundo
en bypass Código de falla 14 y icono El UPS se paga automáticamente Revise los cables de salida y el
SHORT esta iluminando en porque ocurrió un corto circuito a la estado de los dispositivos
la pantalla y la alarma esta salida del UPS. conectados que no estén en corto.
pitando continuamente.

42 EPSILON 1K /2K/3K On line UPS EPSILON 1K /2K/3K On line UPS 43


Sintomas Posible causa Solución 6. Especificaciones
Código de falla mostrado Una falla interna ha ocurrido en el UPS. Contacte su distribuidor CAPACIDAD* 1000 VA / 800 W 1500 VA / 1200 W 2000 VA / 1600 W 3000 VA / 2400 W
como 1, 2, 3, 4, 11, 12, 13 Aquí hay dos posibles razones: ENTRADA
y 41 en la pantalla y alarma 1. La carga está aún funcionando,
pitando constantemente. pero directamente desde la red AC vía Transferencia Linea Baja 160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5 % or 80 VAC / 70 VAC / 60 VAC / 50 VAC ± 5 %
Rango ( basado en porcentaje de Carga 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
bypass.
Voltaje Regreso de Linea Baja 175 VAC ± 5 % or 85 VAC ± 5 %
Transferencia Linea alta 300 VAC ± 5 % or 150 VAC ± 5 %
El tiempo de batería es más Baterías no están cargadas totalmente Cargar las baterías por lo Regreso de Linea alta 290 VAC ± 5 % or 145 VAC ± 5 %
corto que el valor nominal. menos 5 horas y luego revise Rango de frecuencia 40Hz ~ 70 Hz
la capacidad. Si el problema Fase Fase monofásica con tierra
aun persiste, consulte su Factor de potencia ≥ 0.99 @ 220-230 VAC (input voltage)
distribuidor. SALIDA
Voltaje de salida 208/220/230/240VAC or 110/115/120/127 VAC
Defecto de Baterías Contacte su distribuidor para
Regulación de voltaje AC ± 3% (Modo Batería)
reemplace las baterías.
Rango de Frecuencia 47 ~ 53 Hz or 57 ~ 63 Hz
El icono y el código Ventilador está bloqueado o no trabaja. Revise los ventiladores y (Rango sincronizado)
de advertencia FA
parpadeando en la pantalla
notifique su distribuidor! Rango de Frecuencia (Modo Batería) 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
1100%~110%: advertencia audible
y la alarma pitando cada Sobre carga 110%-130%: UPS se apagara en 30 segundos en modo batería o
segundo. transfiere a modo de bypass cuando el voltaje de red eléctrica es normal.
>130%: UPS se apagará automáticamente en modo batería o transfiere a
modo de bypass cuando la red eléctrica es normal.
3:1
5. Almacenamiento y Mantenimiento
Corriente de cresta
Distorsión Armónica ≥ 3 % THD (Carga lineal) ≥ 4 % THD (Carga lineal)
≥ 6 % THD (Carga no lineal) ≥ 7 % THD (Carga no lineal)
5-1. Operación Tiempo
transferencia
Modo AC A Batería Zero
Inversor a Bypass 4 ms (Típico)
El UPS no contiene partes reparables por el usuario. Si la vida útil de las baterías (3~5 años a 25°C a temperatura Waveform (Batt. Mode) Onda seno pura
ambiente) ha sido excedida, las baterías deben ser reemplazadas. En este caso, por favor contacte a su EFICIENCIA
distribuidor. Modo AC ~ 85% ~ 88%
Modo Batería ~ 83%
BATERIA
Tipo Batería 12 V / 7 AH 12 V / 9 AH 12 V / 7 AH 12 V / 9 AH
No olvide enviar la batería a un centro de reciclaje o a Modelo
Estandar Número 3 3 6 6
su distribuidor en el material de embalaje de la batería. Tiempo de recarga 4 horas recuperado al 90% capacidad (Típica)
Corriente de carga 1.0 A(max.)
Voltaje de carga 41.0 VDC ± 1% 82.1 VDC ±1%
Modelo Tipo de Batería & Número Dependiendo de la capacidad de las baterías externas
Corriente de carga
Almacenar de larga
duración Voltaje de carga
4.0 A or 8.0 A(max.)
41.0 VDC ± 1% 82.1 VDC ±1%
Antes de almacenar, cargue el UPS 5 horas. Almacene el UPS cubierto en posición vertical en lugar fresco y
FISICAS
seco. Durante el almacenamiento, recargue la batería de acuerdo a la siguiente tabla:
Tipo Dimension, D X W X H 397 X 145 X 220 (mm) 421 X 190 X 318 (mm)
Torre Peso Neto (kgs) 13 7 14 7 26 13 28 13
Tipo Dimension, D X W X H 420x438x88[2U] (mm) 580x438x133[3U] (mm)
Temperatura almacenaje Frecuencia de recarga Duración de la carga- Rack Peso Neto (kgs) 16 10 17 10 29 17 31 17
25°C - 40°C Cada 3 meses 1-2 horas AMBIENTE
Operación Humedad 20-90 % RH @ 0- 40°C (non-condensing)
40°C - 45°C Cada 2 meses 1-2 horas Nivel de Ruido Menos que 45dBA a 1 Metro
SOFTWARE
Puerto Inteligente RS-232 o USB Soporta Windows® 2000/2003/XP/Vista/2008/7, Linux, Unix and MAC
Opcional SNMP Administración de energía desde SNMP y navegador Web
* Derateado capacidad a 60% en modo conversor de frecuencia y a 80% cuando el voltaje de salida es ajustado a 208VAC.

44 EPSILON 1K /2K/3K On line UPS EPSILON 1K /2K/3K On line UPS 45


Manual Usuario

UPS EPSILON
On-line Doble Conversión 1K/2K/3K

Sistema de Alimentación Ininterrumpido

www.qbex.com