Qbex Ups
Qbex Ups
UPS EPSILON
On-line Double Conversion 1K/2K/3K
www.qbex.com
Table of Contents
1. Important Safety Warning……………………………………………… 4
1-1. Transportation.......................................................................................... 4
1-2. Preparation.............................................................................................. 4
1-3. Installation................................................................................................ 4
1-4. Operation................................................................................................. 5
1-5. Maintenance, service and faults.............................................................. 5
3. Operations…………………………………………………………....... 8
3-1. Button operation...................................................................................... 12
3-2. LCD Panel............................................................................................... 13
3-3. Audible Alarm........................................................................................... 14
3-4. LCD display wordings index.................................................................... 15
3-5. UPS Setting............................................................................................. 15
3-6. Operating Mode Description.................................................................... 19
3-7. Faults Reference Code............................................................................ 20
3-8. Warning indicator..................................................................................... 20
4. Troubleshooting………………………………………………………... 21
6. Specifications………………………………………………………….. 23
1. Important Safety Warning 1-4. Operation
Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and Do not disconnect the mains cable on the UPS system or the building wiring outlet
UPS
read carefully the following instructions before installing the unit. Do not operate this unit before reading through (shockproof socket outlet) during operations since this would cancel the protective earthing of the
all safety information and operating instructions carefully. UPS system and of all connected loads.
The UPS system features its own, internal current source (batteries). The UPS output sockets
or output terminals block may be electrically live even if the UPS system is not connected to the
1-1. Transportation building wiring outlet.
Please transport the UPS system only in the original package to protect against shock and impact. In order to fully disconnect the UPS system, first press the OFF/Enter button to disconnect the
mains.
1-2. Preparation Prevent no fluids or other foreign objects from inside of the UPS system.
Condensation may occur if the UPS system is moved directly from cold to warm environment. The UPS
system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to
1-5. Maintenance, service and faults
acclimate the environment.
The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified
Do not install the UPS system near water or in moist environments.
maintenance personnel.
Do not install the UPS system where it would be exposed to direct sunlight or near heater.
Caution - risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet),
components inside the UPS system are still connected to the battery and electrically live and dangerous.
Do not block ventilation holes in the UPS housing.
Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no
current is present and no hazardous voltage exists in the terminals of high capability capacitor such as
1-3. Installation BUS-capacitors.
Do not connect appliances or devices which would overload the UPS system (e.g. laser printers) to the UPS Only persons are adequately familiar with batteries and with the required precautionary measures may
output sockets. replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
Place cables in such a way that no one can step on or trip over them. Caution - risk of electric shock. The battery circuit is not isolated from the input voltage. Hazardous voltages
may occur between the battery terminals and the ground. Before touching, please verify that no voltage is
Do not connect domestic appliances such as hair dryers to UPS output sockets. present!
The UPS can be operated by any individuals with no previous experience. Batteries may cause electric shock and have a high short-circuit current. Please take the precautionary
measures specified below and any other measures necessary when working with batteries:
Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to Remove wristwatches, rings and other metal objects
the UPS system. use only tools with insulated grips and handles.
Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your computer) to connect the When changing batteries, install the same number and same type of batteries.
UPS system to the building wiring outlet (shockproof outlet).
Do not attempt to dispose of batteries by burning them. This could cause battery explosion.
Please use only VDE-tested, CE-marked power cables to connect the loads to the UPS system.
Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may be toxic.
When installing the equipment, it should ensure that the sum of the leakage current of the UPS and the con
nected devices does not exceed 3.5mA. Please replace the fuse only with the same type and amperage in order to avoid fire hazards.
UPS
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please
keep the original package in a safe place for future use.
2K(L) TOWER
NOTE: There are two different types of online UPS: standard and long-run models. Please refer to the following
model table.
UPS
2 Output receptacles: connect to mission-critical loads.
3 AC input
4 Input circuit breaker
5 Network/Fax/Modem surge protection
6 Emergency power off function connector (EPO)
7 USB communication port
IEC Tipo NEMA Tipo
8 RS-232 communication port
9 SNMP intelligent slot
10 External battery connection (only available for L model)
11 Output terminal
2K(L) RACK 12 Output circuit breaker
13 Input terminal
For 208/220/230/240VAC models: The power cord is supplied in the UPS package.
For 110/115/120/127VAC models: The power cord is attached to the UPS. The input plug is a NEMA
5-15P for 1K, 1KL, 1.5K and 1.5KL models, NEMA 5-20P for 2K and 2KL models.
Note: For Low voltage models: Check if the site wiring fault indicator lights up in LCD panel. It will be illuminated
3K(L) RACK when the UPS is plugged into an improperly wired utility power outlet (Refer to Troubleshooting section).
For terminal-type input or outputs, please follow below steps for the wiring configuration:
IEC Tipo NEMA Tipo a) Remove the small cover of the terminal block
b) Suggest using AWG14 or 2.1mm2 power cords. Suggest using WG12-10 or 3.3mm2-5.3mm2 power
cords for NEMA type.
c) Upon completion of the wiring configuration, please check whether the wires are securely affixed.
d) Put the small cover back to the rear panel.
UPS
Note: The battery charges fully during the first five hours of normal operation. Do not expect full battery
USB port RS-232 port Intelligent slot
run capability during this initial charge period.
Connect a single modem/phone/fax line into surge-protected “IN” outlet on the back panel of the UPS unit. Connect
from “OUT” outlet to the equipment with another modem/fax/phone line cable.
UPS
3-1. Button operation
Button Function
Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to turn
ON/Mute Button on the UPS.
Mute the alarm: When the UPS is on battery mode, press and hold this button
for at least 5 seconds to disable or enable the alarm system. But it’s not applied
to the situations when warnings or errors occur.
Up key: Press this button to display previous selection in UPS setting mode.
Switch to UPS self-test mode: Press and hold ON/Mute button for 5 seconds Display Function
to enter UPS self-testing while in AC mode, ECO mode, or converter mode. Backup time information
Indicates the warning and fault codes, and the codes are listed in
Switch LCD message: Press this button to change the LCD message for input details in 3-5 section.
voltage, input frequency, battery voltage, output voltage and output frequency. Mute operation
Select Button It will return back to default display when pausing for 10 seconds.
Setting mode: Press and hold this button for 5 seconds to enter UPS setting Indicates that the UPS alarm is disabled.
mode when UPS is in standby mode or bypass mode. Output & Battery voltage information
Down key: Press this button to display next selection in UPS setting mode.
Indicates the output voltage, frequency or battery voltage.
Vac: output voltage, Vdc: battery voltage, Hz: frequency
Switch to bypass mode: When the main power is normal, press ON/Mute and Load information
ON/Mute Select buttons simultaneously for 5 seconds. Then UPS will enter to bypass Indicates the load level by 0-25%, 26-50%, 51-75%, and 76-100%.
+ Select Button mode. This action will be ineffective when the input voltage is out of acceptable
range.
OVER LOAD Indicates overload.
UPS
Display Function
Mode operation information Abbreviation Display content Meaning
ENA Enable
Indicates the UPS connects to the mains.
DIS Disable
Indicates the battery is working. ESC Escape
UPS
Parameter 3: Output voltage Parameter 2 & 3: Set the acceptable high voltage point and low
For 208/220/230/240 VAC models, you may choose the fo- voltage point for ECO mode by pressing Down key or Up key.
llowing output voltage:
HLS: High loss voltage in ECO mode in parameter 2.
208: presents output voltage is 208Vac
For 208/220/230/240 VAC models, the setting range in
220: presents output voltage is 220Vac
parameter 3 is from +7V to +24V of the nominal voltage.
230: presents output voltage is 230Vac
240: presents output voltage is 240Vac For 110/115/120/127 VAC models, the setting range in
For 110/150/120/127 VAC models, you may choose the following parameter 3 is from +3V to +12V of the nominal voltage.
output voltage:
110: presents output voltage is 110Vac LLS: Low loss voltage in ECO mode in parameter 2.
115: presents output voltage is 115Vac For 208/220/230/240 VAC models, the setting range in
120: presents output voltage is 120Vac parameter 3 is from -7V to -24V of the nominal voltage.
127: presents output voltage is 127Vac For 110/115/120/127 VAC models, the setting voltage in
parameter 3 is from -3V to -12V of the nominal voltage.
UPS
08: Programmable outlets enable/disable
Interface Setting
Parameter 3:
Set up backup time limits for programmable outlets. When input frequency is within 40 Hz to
0-999: setting the backup time limits in minutes from 0-999 for 70 Hz, the UPS can be set at a constant
programmable outlets which connect to non-critical devices on Frequency output frequency, 50 Hz or 60 Hz. The
battery mode. Converter UPS will still charge battery under this
mode mode.
UPS
Fault event Fault code Icon Fault event Fault code Icon
Bus start fail 01 x Inverter voltage Low 13 x Symptom Possible cause Remedy
Bus over 02 x Inverter output short 14 SHORT
No indication and alarm even The AC input power is not Check if input power cord
Bus under 03 x Battery voltage too high 27 BATT. FAULT though the mains is normal. connected well. firmly connected to the mains.
Bus unbalance 04 x Battery voltage too low 28 BATT. FAULT The AC input is connected to Plug AC input power cord to
the UPS output. AC input correctly.
Inverter soft start fail 11 x Over temperature 41 x
The icon and the EPO function is activated. Set the circuit in closed
Inverter voltage high 12 x Over load 43 OVER LOAD
EP
warning code flashing position to disable EPO
on LCD display and alarm is function.
sounding every second.
The icon and Line and neutral conductors of UPS Rotate mains power socket by
3-8. Warning indicator flashing on LCD display and input are reversed. 180° and then connect to UPS
alarm is sounding every system.
second.
Warning Icon (flashing) Alarm The external or internal battery is Check if all batteries are
The icon and
flashing on LCD display and incorrectly connected. connected well.
Low Battery LOW BATT. Sounding every second alarm is sounding every
second.
Overload OVER LOAD Sounding twice every second
Fault code is shown as 27 Battery voltage is too high or the Contact your dealer.
and the icon BATT. FAULT is lighting charger is fault.
Battery is not connected Sounding every second
on LCD display and alarm is
continuously sounding.
Over Charge Sounding every second Fault code is shown as 28 Battery voltage is too low or the Contact your dealer.
and the icon BATT. FAULT is lighting charger is fault.
on LCD display and alarm is
continuously sounding.
EP
network via the Bypass.
EPO enable Sounding every second After repetitive overloads, the UPS is Remove excess loads from UPS
Over temperature Sounding every second Fault code is shown as 43 and The UPS shut down automatically Remove excess loads from UPS
because of overload at the UPS output. output and restart it.
Charger failure CH Sounding every second
The icon OVER LOAD is lighting
on LCD display and alarm is
continuously sounding.
Out of bypass voltage range Sounding every second
Fault code is shown as 14 and The UPS shut down automatically Check output wiring and if
the icon SHORT is lighting because short circuit occurs on the connected devices are in short
on LCD display and alarm is UPS output. circuit status.
continuously sounding.
2. Instalación y ajuste....................................................................................... 28
2-1. Vista trasera del panel.................................................................................... 28
2-2. Ajuste del UPS................................................................................................ 31
3. Operación...................................................................................................... 34
3-1. Botones de operación..................................................................................... 34
3-2. LCD Panel...................................................................................................... 35
3-3. Alarma Audible................................................................................................ 36
3-4. Índice en la pantalla LCD............................................................................... 37
3-5. Ajustes del UPS.............................................................................................. 41
3-6. Descripción del modo de Operación.............................................................. 42
3-7. Referencia de código de fallas....................................................................... 42
3-8. Indicador de Advertencia................................................................................ 42
4. Solución de problemas.................................................................................. 43
5. Almacenamiento y Mantenimiento................................................................ 44
6. Especificaciones............................................................................................ 45
1. Aviso Importante de Seguridad 1-4. Operación
Por favor cumpla estrictamente con todas las advertencias e instrucciones de operación de este manual. Guarde No desconecte el cable principal en el sistema UPS o los cables de salida del edificio durante la
UPS
este manual apropiadamente y lea cuidadosamente las siguientes instrucciones antes de instalar la unidad. No operación, ello anularía la protección de tierra del UPS y de todas las cargas conectadas.
opere esta unidad antes de leer cuidadosamente através de toda la información de seguridad e instrucciones de
operación. El sistema UPS cuenta con su propia fuente de corriente interna (baterías). Las tomas de salida
del UPS o bloque de salida de los terminales puede ser eléctricamente activo, incluso si el
sistema UPS no está conectado a la toma de cableado del edificio.
1-1. Transporte Para desconectar completamente el sistema de UPS, presione primero el OFF / Enter para
desconectar la red eléctrica.
Por favor transporte el sistema UPS solo en el empaque original para proteger de choques e impactos.
Prevenga entrada de fluidos u objetos extraños dentro del sistema UPS.
Puede ocurrir condensación si el sistema UPS es movido directamente desde un ambiente frío a caliente. El El sistema UPS opera con voltajes peligrosos. Reparaciones solo pueden llevarse acabo por personal de
sistema UPS debe estar absolutamente seco antes de ser instalado. Por favor, espere al menos dos horas mantenimiento calificado.
para que el sistema de UPS para aclimatarse al medio ambiente.
Precaución – Riesgo de descarga eléctrica. Incluso después de que la unidad esté desconectada de la red
No instale el sistema UPS cerca a agua o ambientes húmedos. eléctrica (enchufe del cableado del edificio), componentes internos del sistema UPS aún está conectado a la
batería y eléctricamente activo y peligroso.
No instale el sistema UPS donde pueda estar expuesto a la luz directa del sol o cerca de calor.
Antes de realizar cualquier tipo de servicio y / o mantenimiento, desconecte las baterías y compruebe que no
No bloquee los orificios de ventilación del UPS. hay corriente presente y no existe tensión peligrosa en los terminales del condensador de alta capacidad
como BUS-condensadores.
Sólo las personas que estén debidamente familiarizados con baterías y con las medidas necesarias de
1-3. Instalación precaución puede reemplazar las baterías y supervisar las operaciones. Las personas no autorizadas deben
mantenerse alejados de las baterías.
No conecte aplicaciones o dispositivos los cuales puedan sobrecargar el sistema UPS (e.g. impresora láser)
a la salida del UPS. Precaución – Riesgo de descarga eléctrica. El circuito de la batería no está aislado de la tensión de entrada.
Tensión peligrosa puede ocurrir entre los terminales de la batería y el suelo. Antes de tocar, por favor
Ubique los cables de una forma adecuada que nadie pueda pisar o tropezar con ellos. verifique que no haya tensión!
No conecte aplicaciones domesticas como secador de pelo a las tomas de salida del UPS. Baterías podría causar descargas eléctricas y tienen una alta corriente de corto circuito. Por favor, tome las
medidas cautelares indicadas a continuación y las demás medidas necesarias cuando se trabaja con las
El UPS puede ser operado por cualquier individuo sin previa experiencia. baterías:
Retírese relojes de pulsera, anillos y otros objetos.
Conecte el sistema UPS sólo a una salida puesta a tierra que debe ser fácilmente accesible y cerca del Utilizar sólo herramientas con mangos y manija aisladas.
sistema de UPS.
Cuando cargue las baterías, instale el mismo número y tipo de baterías.
Por favor, use sólo cable de red certificado (por ejemplo, el cable de red de su ordenador) para conectar el
sistema UPS a la toma de corriente de un edificio. No intente desechar las baterías por la quema de ellos. Esto podría provocar una explosión de la batería.
Por favor use solo cable certificado para conectar las cargas al sistema UPS. No abrir o destruir las baterías. Escape de electrolitos puede causar lesiones en la piel y los ojos.
Puede ser tóxico.
Cuando instale el equipo, asegúrese que la suma de corrientes de fuga del UPS no excedan 3.5mA. Por favor reemplace el fusible solo con el mismo tipo y amperaje a fin de evitar riesgos de incendio.
No desmonte el sistema UPS.
UPS
NOTE: Antes de instalar, por favor inspeccione la unidad. Asegúrese que no hay nada dañado dentro del
empaque. Por favor mantenga el empaque original en un lugar seguro para futuros usos.
2K (L) TORRE
NOTA: Hay dos tipos diferentes de UPS online: Modelo estándar y larga duración. Por favor refiérase a la
siguiente tabla.
UPS
4 Interruptor de circuito de entrada
5 Proteccion de picos para terminal de Red/Fax/Modem
6 Conector de function apagado de emergencia (EPO)
7 Puerto de comunicación USB
8 RS-232 puerto de comunicaciones inteligentes ranura SNMP
Tipo IEC Tipo NEMA
9 Conexión Batería Externa (Solo habilitada para modelo L)
10 Terminal de Salida
11 Interruptor de circuito de salida
12 Terminal de entrada
2K(L) RACK
Para modelos 208/220/230/240VAC: El cable de alimentación esta incluido en el empaque del UPS.
Tipo IEC Tipo NEMA Para modelos 110/115/120/127VAC: El cable de alimentación esta conectado al UPS. El conector de
entrada es un NEMA 5-15P para modelos 1K y 1KL, NEMA 5-20P para modelos 2K y 2KL.
Nota: Para modelos de bajo voltaje: Revise si el indicador de falla en cableado del sitio esta indicando falla en
el panel frontal. Este se iluminara cuando el UPS esta conectado no apropiadamente (Refiérase a la sección de
Guía de Fallas).
3K(L) RACK
Para terminal tipo entrada o salida, por favor siga los pasos siguientes para configuración del cableado:
a) Remueva la pequeña tapa del bloque de terminales
Tipo IEC Tipo NEMA b) Sugerido usar cable AWG14 o 2.1mm2 para el cable de alimentación. Sugerido usar cable WG12-10
o 3.3mm2-5.3mm2 para el cable de alimentación tipo NEMA.
c) Una vez completada la configuración del cableado, por favor compruebe que los cables están firme
mente fijados.
d) Ponga la pequeña tapa en el panel trasero.
UPS
Puerto USB Puerto RS-232 Ranura Inteligente
Nota: Las baterías quedaran cargadas totalmente durante las primeras cinco horas de
operación normal. No espere respaldo de la capacidad total de la batería durante el periodo
de carga inicial.
UPS
3-1. Botón de operación
Botón Función
Encienda el UPS: Presione el botón de ON/Mute por lo menos 2 segundos
ON/Mute Botón para que encienda el UPS.
Alarma de Silencio (Mute): Cuando el UPS está en modo batería, presione
este botón y espere por lo menos 5 segundos para deshabilitar o habilitar el
sistema de alarma. Esto no se aplica a situaciones de advertencia o cuando
ocurre un error.
Tecla de subir (Up key): Presione este botón par ver la pantalla anterior en el Mostrar Función
modo de ajustes del UPS. Información de tiempo de respaldo
Cambiar el UPS a modo de auto-prueba: Presione el botón ON/Mute y
espere por 5 segundos para iniciar el autodiagnóstico mientras el UPS esta en Indicador de tiempo de respaldo en el grafico circular.
modo AC, modo ECO, o modo Inversor.
Indicador de tiempo de respaldo en números.
Apague el UPS: Presione este botón y espere por lo menos 2 segundos para H: horas, M: minutos, S: segundos
apagar el UPS en modo de batería. El UPS debe estar en modo de espera Información de Falla
OFF/Enter con la energía normal o transferir a modo de Bypass en caso de estar
Botón habilitado. Indica advertencia y ocurrió una falla.
Confirmar tecla de selección: Presione este botón para confirmar lo
Indica advertencia y código de falla, el detalle de los códigos esta
seleccionado en modo ajustes del UPS.
listado en la sección 3-5.
Operación de Silencio
Cambiar mensaje en LCD: Presione este botón para cambiar el mensaje de
la pantalla para voltaje de entrada, frecuencia de entrada, voltaje de batería, Indica que la alarma del UPS está deshabilitada.
salida de voltaje y salida de frecuencia. Este regresara por defecto al display
Select Botón inicial cuando pasen 10 segundos. Información de Voltaje de Salida y Batería
Modo Ajustes: Presione este botón y espere 5 segundos para entrar al modo Indica el voltaje de salida, frecuencia o voltaje de batería.
de ajustes del UPS cuando el UPS esta en modo de stanbye o bypass. Vac: Voltaje de salida, Vdc: Voltaje de batería, Hz: frecuencia
Tecla de bajar (Down key): Presione este botón para seleccionar la siguiente
Información de Carga
pantalla en el modo de ajustes del UPS.
Indica el nivel de carga de 0-25%, 26-50%, 51-75%, y 76-100%.
ON/Mute Cambiar a modo de bypass: Cuando el suministro de energía es normal,
+ Select Botón presione ON/Mute y seleccione los botones simultáneamente por 5
segundos. Luego el UPS entrara en modo de bypass. Esta acción no será OVER LOAD Indica sobrecarga.
eficiente cuando los rangos de entrada de voltaje no son aceptables.
SHORT Indica la carga o el circuito de salida del UPS está en corto circuito.
UPS
Mostrar Función
Información del Modo de operación Abreviación Contenido de la pantalla Significado
ENA Habilitado
Indica que el UPS está conectado a la red eléctrica.
DIS Deshabilitado
Indica que la batería está trabajando. ESC Escape
Modo Batería Pita cada 4 Segundo Parámetro 2 y parámetro 3: Son las opciones de
ajuste o valores para cada programa.
Baja Batería Pita cada Segundo
UPS
Parámetro 3: Voltaje de salida
Parámetro 2 & 3: Ajuste el punto del nivel de voltaje alto y bajo
Para modelos 208/220/230/240 VAC, usted debe escoger las
aceptable para el modo ECO presionando la tecla de bajar (Down)
siguientes salidas de voltaje:
o subir (Up).
208: Voltaje de salida presente es 208Vac
HLS: Alto perdida de voltaje en el modo ECO en el parámetro 2.
220: Voltaje de salida presente es 220Vac
Para los modelos 208/220/230/240 VAC, el ajuste del rango en el
230: Voltaje de salida presente es 230Vac
parámetro 3 es desde +7V a +24V de voltaje nominal.
240: Voltaje de salida presente es 240Vac
Para modelos 110/115/120/127 VAC, el ajuste del rango en el
Para modelos 110/150/120/127 VAC, usted puede elegir las
parámetro 3 es desde +3V a +12V del voltaje nominal.
siguientes salidas de voltaje:
LLS: Perdida de bajo voltaje en modo ECO en el parámetro 2.
110: Voltaje de salida presente es 110Vac
Para modelos 208/220/230/240 VAC, el ajuste del rango en el
115: Voltaje de salida presente es 115Vac
parámetro 3 es desde -7V a -24V del voltaje nominal.
120: Voltaje de salida presente es 120Vac
Para modelos 110/115/120/127 VAC, el ajuste del voltaje en
127: Voltaje de salida presente es 127Vac
parámetro 3 es de -3V a -12V del voltaje nominal.
UPS
08: Salidas Programables habilitadas /deshabilitadas
Interface Ajuste
Parámetro 3: Ajuste los límites del tiempo de respaldo par alas Cuando la entrada de frecuencia esta
salidas programables. dentro 40 Hz a 70 Hz, el UPS puede ser
0-999: Ajuste el límite del tiempo de respaldo en minutos de Modo de ajustado a una constante frecuencia de
0-999 para las salidas programables a la cual conecta los conversor de salida, 50 Hz o 60 Hz. El UPS continuara
dispositivos de carga no critica en modo bacteria. Frecuencia cargando la batería de este modo.
UPS
Evento de error Código de falla Icono Evento de falla Código falla Icono
Bus comienza a fallar 01 x Bajo Voltaje en Inversor 13 X Sintomas Posible causa Solución
Bus por encima 02 x Salida en corto Inversor 14 SHORT
No hay indicación y alarma La entrada AC no está bien Revise el cable de entrada si está
Bus por debajo 03 x Voltaje de batería alto 27 BATT. FAULT a pesar de que la red es conectada. bien conectado a la red eléctrica.
normal.
Bus desbalanceado 04 x Voltaje de batería bajo 28 BATT. FAULT La entrada AC está conectada Conecte el cable de entrada AC
ala salida del UPS. a la entrada AC correctamente.
Inversor en falla 11 x Sobre temperature 41 X
Inversor con voltaje alto 12 x Sobre carga 43 OVER LOAD
El icono y EP el La función de EPO está activada. Ajuste el circuito en la posición
código de advertencia parpa- de cerrado para deshabilitar la
dea en la pantalla y la alarma función de EPO.
suena cada segundo.
Advertencia Icon (Parpadeando) Alarma La batería externa o interna está Revise si todas las baterías
El icono y
parpadean en la pantalla y la incorrectamente conectada. están bien conectadas.
Batería baja LOW BATT. Pitando cada Segundo alarma suena cada segundo.
Sobrecarga Pitando cada segundo Código de falla 28 y el icono Voltaje del cargador es también bajo o Contacte su distribuidor.
BATT. FAULT está iluminando en el cargador está fallando.
la pantalla y el sonido de la
alarma es continuo.
EP
alimentados por la red eléctrica vía bypass.
EPO Habilitado Pitando cada segundo Después de repetitivas sobrecargas, el Remueva el exceso de carga
continuamente.
Fuera del Rango de voltaje Pitando cada segundo
en bypass Código de falla 14 y icono El UPS se paga automáticamente Revise los cables de salida y el
SHORT esta iluminando en porque ocurrió un corto circuito a la estado de los dispositivos
la pantalla y la alarma esta salida del UPS. conectados que no estén en corto.
pitando continuamente.
UPS EPSILON
On-line Doble Conversión 1K/2K/3K
www.qbex.com