JU Project - VC0-Report
JU Project - VC0-Report
Author
Project: JU test Project
Variant: JU simulation variant
PVsyst V7.3.1
VC0, Simulation date:
09/19/24 14:26
with v7.3.1
Project summary
Geographical Site Situation Project settings
Dakshin Krok Latitude 23.88 °N Albedo 0.20
Bangladesh Longitude 90.27 °E
Altitude 23 m
Time zone UTC+6
Meteo data
Dakshin Krok
Meteonorm 8.1 (1991-2012), Sat=100% - Synthetic
System summary
Grid-Connected System Trackers single array
System information
PV Array Inverters
Nb. of modules 70 units Nb. of units 1 unit
Pnom total 30.8 kWp Pnom total 30.0 kWac
Pnom ratio 1.027
User's needs
Unlimited load (grid)
Results summary
Produced Energy 34716 kWh/year Specific production 1127 kWh/kWp/year Perf. Ratio PR 66.83 %
Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Near shading definition - Iso-shadings diagram 5
Main results 6
Loss diagram 7
Predef. graphs 8
Single-line diagram 9
PVsyst V7.3.1
VC0, Simulation date:
09/19/24 14:26
with v7.3.1
General parameters
Grid-Connected System Trackers single array
PV Field Orientation
Orientation Tracking algorithm Trackers configuration
Tracking plane, horizontal N-S axis Astronomic calculation Nb. of trackers 4 units
Axis azimuth 90.2 ° Single array
Sizes
Tracker Spacing 5.00 m
Collector width 2.12 m
Ground Cov. Ratio (GCR) 42.5 %
Phi min / max. -/+ 90.0 °
Shading limit angles
Phi limits for BT -/+ 64.7 °
Models used
Transposition Perez
Diffuse Perez, Meteonorm
Circumsolar separate
PV Array Characteristics
PV module Inverter
Manufacturer Generic Manufacturer Generic
Model Mono 440 Wp Twin 144 half-cells Model 30 kWac inverter
(Original PVsyst database) (Original PVsyst database)
Unit Nom. Power 440 Wp Unit Nom. Power 30.0 kWac
Number of PV modules 70 units Number of inverters 1 unit
Nominal (STC) 30.8 kWp Total power 30.0 kWac
Modules 5 Strings x 14 In series Operating voltage 450-700 V
At operating cond. (50°C) Pnom ratio (DC:AC) 1.03
Pmpp 27.97 kWp
U mpp 525 V
I mpp 53 A
Array losses
Thermal Loss factor DC wiring losses Module Quality Loss
Module temperature according to irradiance Global array res. 165 mΩ Loss Fraction -0.4 %
Uc (const) 20.0 W/m²K Loss Fraction 1.5 % at STC
Uv (wind) 0.0 W/m²K/m/s
PVsyst V7.3.1
VC0, Simulation date:
09/19/24 14:26
with v7.3.1
Array losses
IAM loss factor
Incidence effect (IAM): Fresnel, AR coating, n(glass)=1.526, n(AR)=1.290
PVsyst V7.3.1
VC0, Simulation date:
09/19/24 14:26
with v7.3.1
Iso-shadings diagram
Orientation #1
PVsyst V7.3.1
VC0, Simulation date:
09/19/24 14:26
with v7.3.1
Main results
System Production
Produced Energy 34716 kWh/year Specific production 1127 kWh/kWp/year
Performance Ratio PR 66.83 %
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
PVsyst V7.3.1
VC0, Simulation date:
09/19/24 14:26
with v7.3.1
Loss diagram
1536 kWh/m² Global horizontal irradiation
+9.8% Global incident in coll. plane
-16.09% Near Shadings: irradiance loss
PVsyst V7.3.1
VC0, Simulation date:
09/19/24 14:26
with v7.3.1
Predef. graphs
Daily Input/Output diagram