Structural Analysis and Design Report - Merto - L6
Structural Analysis and Design Report - Merto - L6
ANALYSIS
PROPOSED TWO-STOREY RESIDENTIAL BUILDING
PROJECT NAME
CECILE C. MERTO
PROJECT OWNER
STRUCTURAL ANALYSIS
AND DESIGN REPORT
PROPOSED TWO-STOREY
RESIDENTIAL BUILDING
(BLK2 LOT 6)
Location: Forever Homes Subdivision, Block 2, Lot 6, Brgy. Lumbia, Cagayan de Oro City
Owner: Cecile C. Merto
Prepared by:
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
STRUCTURAL ANALYSIS PROPOSED TWO-
TWO-STOREY
& DESIGN REPORT RESIDENTIAL BUILDING (BLK2 LOT 6)
I. PROJECT DETAILS
Concrete – reinforced concrete design shall be in accordance with NSCP 2015. The specified minimum
compressive strength of the concrete by cylinder test at 28days age shall be as follows:
Foundation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 20.7MPa (3000PSI)
Beams - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 20.7MPa (3000PSI)
Columns - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 20.7MPa (3000PSI)
Suspended Slab - - - - - - - - - - - - - - - - - - - - - - - - - - - 20.7MPa (3000PSI)
Slab on Grade - - - - - - - - - - - - - - - - - - - - - - - - - - - - 20.7MPa (3000PSI)
Lean Concrete - - - - - - - - - - - - - - - - - - - - - - - - - - - - -10.0MPa (1450PSI)
Structural Steel – All structural steel such as wide flange, angles, channels, pipes and plates shall conform to
ASTM A36 or equivalent with minimum yield strength of 248MPa.
Anchor Bolt – Anchor Bolt shall conform to ASTM 325 or equivalent. Anchor bolt shall be designed for maximum
tensile stress of 140MPa on the tensile stress area of the bolt.
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
STRUCTURAL ANALYSIS PROPOSED TWO-
TWO-STOREY
& DESIGN REPORT RESIDENTIAL BUILDING (BLK2 LOT 6)
Dead Loads (DL) – consist of the weight of all materials of construction incorporated into the building or other
structure, including but not limited to walls, floors, roofs, ceilings, stairways, finishes, cladding and other similarly
incorporated architectural and structural items, and fixed service equipment, including the weight of cranes.
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
STRUCTURAL ANALYSIS PROPOSED TWO-
TWO-STOREY
& DESIGN REPORT RESIDENTIAL BUILDING (BLK2 LOT 6)
Live Loads (LL) – shall be the maximum loads expected by the intended use or occupancy but in no case shall
be less than the loads required by this section.
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
STRUCTURAL ANALYSIS PROPOSED TWO-
TWO-STOREY
& DESIGN REPORT RESIDENTIAL BUILDING (BLK2 LOT 6)
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
STRUCTURAL ANALYSIS PROPOSED TWO-
TWO-STOREY
& DESIGN REPORT RESIDENTIAL BUILDING (BLK2 LOT 6)
Roof Live Loads (LL) – shall be designed for the unit live loads, Lr, set forth in Table 205-3. The live loads shall
be assumed to act vertically upon the projected area on a horizontal plane.
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
STRUCTURAL ANALYSIS PROPOSED TWO-
TWO-STOREY
& DESIGN REPORT RESIDENTIAL BUILDING (BLK2 LOT 6)
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
STRUCTURAL ANALYSIS PROPOSED TWO-
TWO-STOREY
& DESIGN REPORT RESIDENTIAL BUILDING (BLK2 LOT 6)
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
STRUCTURAL ANALYSIS PROPOSED TWO-
TWO-STOREY
& DESIGN REPORT RESIDENTIAL BUILDING (BLK2 LOT 6)
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
STRUCTURAL ANALYSIS PROPOSED TWO-
TWO-STOREY
& DESIGN REPORT RESIDENTIAL BUILDING (BLK2 LOT 6)
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
STRUCTURAL ANALYSIS PROPOSED TWO-
TWO-STOREY
& DESIGN REPORT RESIDENTIAL BUILDING (BLK2 LOT 6)
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
STRUCTURAL ANALYSIS PROPOSED TWO-
TWO-STOREY
& DESIGN REPORT RESIDENTIAL BUILDING (BLK2 LOT 6)
V. LOAD COMBINATIONS
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
STRUCTURAL ANALYSIS PROPOSED TWO-
TWO-STOREY
& DESIGN REPORT RESIDENTIAL BUILDING (BLK2 LOT 6)
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
STRUCTURAL ANALYSIS PROPOSED TWO-
TWO-STOREY
& DESIGN REPORT RESIDENTIAL BUILDING (BLK2 LOT 6)
VI. GEOMETRY
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
STRUCTURAL ANALYSIS PROPOSED TWO-
TWO-STOREY
& DESIGN REPORT RESIDENTIAL BUILDING (BLK2 LOT 6)
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
STRUCTURAL ANALYSIS PROPOSED TWO-
TWO-STOREY
& DESIGN REPORT RESIDENTIAL BUILDING (BLK2 LOT 6)
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
STRUCTURAL ANALYSIS PROPOSED TWO-
TWO-STOREY
& DESIGN REPORT RESIDENTIAL BUILDING (BLK2 LOT 6)
LIVE LOADS
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
STRUCTURAL ANALYSIS PROPOSED TWO-
TWO-STOREY
& DESIGN REPORT RESIDENTIAL BUILDING (BLK2 LOT 6)
Source: http://faultfinder.phivolcs.dost.gov.ph/
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
STRUCTURAL ANALYSIS PROPOSED TWO-
TWO-STOREY
& DESIGN REPORT RESIDENTIAL BUILDING (BLK2 LOT 6)
EARTHQUAKE LOAD +X DIRECTION
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
STRUCTURAL ANALYSIS PROPOSED TWO-
TWO-STOREY
& DESIGN REPORT RESIDENTIAL BUILDING (BLK2 LOT 6)
VIII. ANALYSIS
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
STRUCTURAL ANALYSIS PROPOSED TWO-
TWO-STOREY
& DESIGN REPORT RESIDENTIAL BUILDING (BLK2 LOT 6)
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
STRUCTURAL ANALYSIS PROPOSED TWO-
TWO-STOREY
& DESIGN REPORT RESIDENTIAL BUILDING (BLK2 LOT 6)
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
STRUCTURAL ANALYSIS PROPOSED TWO-
TWO-STOREY
& DESIGN REPORT RESIDENTIAL BUILDING (BLK2 LOT 6)
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
STRUCTURAL ANALYSIS PROPOSED TWO-
TWO-STOREY
& DESIGN REPORT RESIDENTIAL BUILDING (BLK2 LOT 6)
IX. DESIGN
DESIGN OF SLAB
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
Engineering Report PROPOSED TWO-STOREY
Structural Calculation RESIDENTIAL BUILDING (BLK 2 LOT 6)
SUPPORT CONDITIONS
CASE 1 CASE 2 CASE 3 CASE 4 CASE 5 CASE 6 CASE 7 CASE 8 CASE 9
MOMENT COEFFICIENTS
-CaDL = 0.081 Negative moment coefficient along the shorter dimension due to dead load
-CaLL = 0.081 Negative moment coefficient along the shorter dimension due to live load
-CbDL = 0.010 Negative moment coefficient along the longer dimension due to dead load
-CbLL = 0.010 Negative moment coefficient along the longer dimension due to live load
+CaDL = 0.034 Positive moment coefficient along the shorter dimension due to dead load
+CaLL = 0.058 Positive moment coefficient along the shorter dimension due to live load
+CbDL = 0.004 Positive moment coefficient along the longer dimension due to dead load
+CbLL = 0.007 Positive moment coefficient along the longer dimension due to live load
LOCATION EQUATIONS MOMENT MTOTAL rreqd rused Spacing Sfinal Ductility Rebar spacing, mm
2
Negative -C aDL W uDL L a 2.89
0.10 0.00005 0.0001 12060 375 PASS 10 mm diameter @ 350 mm
Moment, M a -C aLL W uLL L a 2 1.42
2
Negative -C bDL W uDL L b 0.99
2 0.10 0.000049 0.0001 12060 375 PASS 10 mm diameter @ 350 mm
Moment, M b -C bLL W uLL L b 0.49
2
Positive +C aDL W uDL L a 1.21
2.23 0.001100 0.0015 537 375 PASS 10 mm diameter @ 350 mm
Moment, M a +C aLL W uLL L a 2 1.02
2
Positive +C bDL W uDL L b 0.40
0.74 0.000362 0.0005 1632 375 PASS 10 mm diameter @ 350 mm
Moment, M b +C bLL W uLL L b 2 0.34
350 mm 350 mm
350 mm
350 mm 350 mm
350 mm
STRUCTURAL ANALYSIS PROPOSED TWO-
TWO-STOREY
& DESIGN REPORT RESIDENTIAL BUILDING (BLK2 LOT 6)
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
Engineering Report Structural Calculation PROPOSED TWO-STOREY
RESIDENTIAL BUILDING (BLK2 LOT6)
Beam Design
Beam Mark Label RCB1
Design Parameters
F'c = 20 MPa
Fy = 414 MPa
Fy (secondary) = 227 MPa
Rebar Diameter (Main) = 16 mm
Rebar Diameter (Stirrups) = 10 mm
Concrete Density = 24 kN/m3
Wu 21.982 kN/m
Max. Moment 43.964 kN-m
Beam Design
Beam Mark Label RCB2
Design Parameters
F'c = 20 MPa
Fy = 414 MPa
Fy (secondary) = 227 MPa
Rebar Diameter (Main) = 16 mm
Rebar Diameter (Stirrups) = 10 mm
Concrete Density = 24 kN/m3
Wu 21.982 kN/m
Max. Moment 16.493 kN-m
Beam Design
Beam Mark Label RB
Design Parameters
F'c = 20 MPa
Fy = 414 MPa
Fy (secondary) = 227 MPa
Rebar Diameter (Main) = 12 mm
Rebar Diameter (Stirrups) = 10 mm
Concrete Density = 24 kN/m3
Wu 6.33 kN/m
Max. Moment 12.66 kN-m
DESIGN OF COLUMNS
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
Column Design
Engineering Report Structural Calculation PROPOSED TWO-STOREY
BUILDING (BLK2 LOT6)
Column Name C1 Loads Combos Parallel to X-Direction
Design Paramters
fy = 414 Mpa Checking for Min Flexural Strengths
f'c = 20.7 Mpa Mc = 259.913247 kN-m
main bar Ø = 16 mm Mb = 97.4 kN-m
stirrups bar Ø = 10 mm Ratio = 2.66851383 Pass
Concrete Cover = 40 mm
Es = 200000 Mpa Checking for Shear at Joints
Col Height = 3 m
Applied Pu = 125.00 kN MpbR = 85.4 kN-m
Applied Muz = 5.20 kN-m MpbL = 12 kN-m
Applied Mux = 14.00 kN-m
ex = 0.04160
Col-x = 200 mm bw = 200 center
Col-z = 200 mm AstFy = 117.055742 kN
Effective Depth - x 142 mm AsbFy = 117.055742 kN
Area = 40000 mm2 Vpb of Col = 17.3275498 kN
Vj = 216.783935 kN
Assumed Steel Ratio = 1% ØVn = 309.381318 Vn1 =
As = 480 Ratio = 0.70070144 Pass
n= 2.387324146
Use nx= 2
Use nz= 2
Actual As = 402.1238597
Ab = 201.0619298
εsteel = 0.00207
εconc at balance = 0.003
β= 0.85 NSCP Table 422.2.2.4.3
cb = 84.02366864
f = εE use f T = fAs
d c εsteel = As (mm2) e (mm) M (kN-m)
(Mpa) (Mpa) (kN)
F1 142.00 -57.98 0.00207 414.00 -414.00 402.12 -166.48 42.00 6.99
F2 58.00 26.02 0.00093 185.83 168.24 402.12 67.65 42.00 2.84
F3 0.00 84.02 0.00300 600.00 396.41 0.00 0.00 100.00 0.00
F4 0.00 84.02 0.00300 600.00 396.41 0.00 0.00 100.00 0.00
F5 0.00 84.02 0.00300 600.00 396.41 0.00 0.00 100.00 0.00
Cc 251.33 64.29 16.16
Pb = Axial Load Capacity 152.50 kN
Mb = Column Moment Capacity 25.99132469
INTERACTION DIAGRAM
1200
ex = 0.042
1000
Pnz = 348.2713 kN
800 Pnx = 168.8449 kN
Po = 539.1144 kN
600
ULTIMATE AXIAL CAPACITY
400
Allowable Loadings
200 Pu= 144.1125 kN
M z= 12.28 kN-m
Mx= 16.59 kN-m
0
-5 0 5 10 15 20 25 30
D/C Ratio= 0.87 < 1 Pass
-200
-400
-600
A= 2991.15
B = -67719.66859
C = 13993910.32
ccorrected = 58.00950261
acorrected = 49.30807722
fscorrected = 0.098286798
Mo = 19.77028796 kN-m
2
Ash = 314.1592654 mm
Ag = 40000 mm2
Ach = 14400 mm2
fyt = 275 Mpa
2
Ash = 314.1592654 mm
Ag = 40000 mm2
Ach = 14400 mm2
fyt = 275 Mpa
DESIGN OF FOOTINGS
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
STRUCTURAL ANALYSIS PROPOSED TWO-STOREY
DESIGN REPORT RESIDENTIAL BUILDING (BLK2 LOT6)
Footing Name F1
Column Type Isolated
Design Parameters
Pu = 75 KN
f'c = 20 Mpa
fy = 414 Mpa
Embedment = 2000 mm
qall (Soil Bearing Capacity)= 125 Kpa
Trial "t" = 150 mm
Increment "t" = 1 mm
Minimum "L" = 1200 mm Concentric Footing
bar Ø= 12 mm
Col-x = 200 mm
Col-z = 200 mm
REQUIRED DIMENSIONS
Ps = 53.5714286 KN
Footing Areareq = 0.42857143 mm
B= 1200 mm
Used d = 69 mm
bo = 1076 mm
β= 1
as = 40
2
Punching Area = 1367639 mm
VuPunching = 71.2266391 KN
ff'c1/2bod/3 = 83.0073155 KN Safe
Critical Area for Moment
FLEXURAL REINFORCEMENT REQUIREMENTS
d= 69 mm
Mu = 7.81 kN-m steel ratio, r = 0.0039
Rn = 1.51928866 required As = 318.80
rrqrd = 0.00385 number of bars = 2.82
rmin = 0.0034 say = 6.00 pcs - 12 mmf
f Both Ways
USE t = 150 mm
STRUCTURAL ANALYSIS PROPOSED TWO-
TWO-STOREY
& DESIGN REPORT RESIDENTIAL BUILDING (BLK2 LOT 6)
DESIGN OF PURLINS
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
Design of Purlins
Design Paramters
Fbx = Fby 148.80 Mpa Wind Load: P = qh[GCp - GCpi]
# of sagrod = 1 w/ sagrod at midspan Exposure: B
# of purlin = 8 Height: 5.00 m
Live Load = 0.600 kPa Basic Wind Speed: 250 km/hr
Spacing, S = 0.600 m, tributary width Windward, Pres Coef, GCp: 0.49
Span, L = 2.000 m Leeward, Pres Coef, GCp: -0.90
Roof Angle, q = 20.0000 degrees Positive Int. Pressure Coef., GCpi: 0.18
Ceiling = 0.200 kPa Negative Int. Pressure Coef., GCpi: -0.18
Roof = 0.100 kPa Topographic Factor, Kzt: 1.00
Utilities = 0.100 kPa Kz = 0.590
Total Dead Load = 0.40000 kPa
DIAMETER OF SAGROD
T = # of purlin x tangential reaction
= 2.135 kN
Diameter = 4.3 say 10 mm sagrods
DESIGN OF RAFTER
DYNAMIC GROUP EXPERT BUILDERS – Architectural, Engineering Activities and Technical Consultancy
STRUCTURAL ANALYSIS PROPOSED TWO-STOREY
DESIGN REPORT RESIDENTIAL BUILDING (BLK 2 LOT 6)
DESIGN OF RAFTER
2 2
Subst: F A = [ 1- (L/r) /2C ] Fy/Fs
FA = 84.32 MPa > fA
Recommendation:
use 2-50mmx150mmx1.2mmt C-Purlins for Rafter
The maximum permissible area stated by the AISC is 85% of the gross area of the section.
A MAX = 0.85 A (gross area)
2
A MAX = 690.97 mm
Since A MAX > A G , therefore; design section is safe for Tensile Stress!
Recommendation:
use 2-50mmx150mmx1.2mmt C-Purlins for Rafter
STRUCTURAL ANALYSIS PROPOSED TWO-STOREY
DESIGN REPORT RESIDENTIAL BUILDING (BLK 2 LOT 6)
DESIGN OF STEEL GIRT
2 2
Subst: F A = [ 1- (L/r) /2C ] Fy/Fs
FA = 151.0120 MPa > fA
Therefore; design section is safe for Axial Stress!
Recommendation:
use 2- 50mmx50mmx6mmt Angle Bar for Diagonal & Vertical Members.
The maximum permissible area stated by the AISC is 85% of the gross area of the section.
A MAX = 0.85 A (gross area)
2
A MAX = 483.65 mm
Since A MAX > A G , therefore; design section is safe for Tensile Stress!
Recommendation:
use 2- 50mmx50mmx6mmt Angle Bar for Vertical Members.
VERTICAL & DIAGONAL MEMBER
3
2 - 2" x 2" x 16 " THICK ANGLE BAR TOP CHORD
3
2 - 2" x 2" x 16 " THICK ANGLE BAR
BOTTOM CHORD
3
2 - 2" x 2" x 16 " THICK ANGLE BAR