Maintenance
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing
of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or
serious injury. When working on the equipment, observe all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be
performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE
and ELECTROCUTION hazards.To avoid these hazards, you MUST follow requirements for field
wiring installation and grounding as described in NEC and your local/state electrical codes.
Failure to follow code could result in death or serious injury.
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical
hazards.
• Before installing/servicing this unit, technicians MUST put on all PPE required for the work
being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard
hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to
appropriate Material Safety Data Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA
guidelines for proper PPE.
• When working with or around hazardous chemicals, ALWAYS refer to the appropriate MSDS/
SDS and OSHA/GHS (Global Harmonized System of Classification and Labeling of
Chemicals) guidelines for information on allowable personal exposure levels, proper
respiratory protection and handling instructions.
• If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE
in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash
protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING,
DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC
FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED
FOR INTENDED VOLTAGE.
Failure to follow instructions could result in death or serious injury.
Copyright
This document and the information in it are the property ofTrane, and may not be used or
reproduced in whole or in part without written permission.Trane reserves the right to revise this
publication at any time, and to make changes to its content without obligation to notify any person
of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
BAS-SVX45E-EN:
• Revisions made to “Setting the BACnet Device ID” section.
• Appendix added: ConfiguringTracer UC600 for BACnet/IP
• Terminology change: WCI now called Air-Fi™ Wireless.
• Revisions made to “Configuring theTracer UC600 with theTracerTU ServiceTool” section.
• PICS appendix removed; Reference the literature in the Other Resources section.
BAS-SVX45D-EN:
• UL864 certified (smoke control systems)
• Wireless support (WCI)
BAS-SVX45C-EN:
• Creating and viewing Schedules
• Viewing custom graphics
BAS-SVX45E-EN 3
Table of Contents
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Smoke Control Support (UUKL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Air-Fi™ Wireless Communications Interface (WCI) Support . . . . . . . . . . . . . . 7
Expansion Module Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Location of LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Hardware Terminations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Agency Listings and Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Additional Ordering Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Required Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Dimensions and Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Mounting and Removing the Tracer UC600 Controller . . . . . . . . . . . . . . . . . 13
DIN Unit Width . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Setting Addresses using Rotary Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Setting the BACnet Device ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
BACnet MS/TP Device ID Assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Device ID Assignment for BACnet/IP Devices . . . . . . . . . . . . . . . . . . . . . . 17
Device ID Assignment for Wireless Devices . . . . . . . . . . . . . . . . . . . . . . . 17
Rotary Dial Address Settings for Non-Trane Systems . . . . . . . . . . . . . . . 17
4 BAS-SVX45E-EN
BACnet MS/TP Link Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
BACnet/IP Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
BAS-SVX45E-EN 5
Deleting Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Deleting Exceptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Deleting a Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Custom Graphics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Graphics Best Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Declaration of CE Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
6 BAS-SVX45E-EN
Overview
TheTracer® UC600 controller, (PN# BMUC600AAA0100011 made in the U.S.A.), is a multi-purpose,
programmable, wireless-compatible device. It is designed to control the following types of
equipment:
• Air-handling units (AHUs)
• Rooftop units
• Chillers
• Central heating and cooling plants
• Cooling towers
• Generic input/output (I/O) control
BAS-SVX45E-EN 7
Overview
Specifications
Tracer UC600 conforms to the specifications shown inTable 1.
Table 1. Specifications
Storage
Operating
Mounting weight of controller: Mounting surface must support 1.3 lb. (0.6 kg)
Location of LEDs
Light emitting diodes (LEDs) indicate the operation and communication status of the controller.
To interpret theTracer UC600 LEDs and safely operate theTracer UC600, see “LED Descriptions and
Activities,” p. 38.
For detailed information about wiring communication links, refer toTracer SC Unit Controller
Wiring Guide (BAS-SVN03) listed in the section, “Other Resources,” p. 75.
.
UC600
LINK MBUS IMC
BO1 BO2 BO3 B O4
Binary output status Communication status TX
ADDRESS
901 901 901
Ethernet LEDs
2 3
2 3
2 3
7 8
7 8
7 8
x100 x10 x1
8 BAS-SVX45E-EN
Overview
Hardware Terminations
Tracer UC600 supports the following hardware terminations:
• Temperature sensors (resistive and thermistor)
• Linear inputs 0–20 mA, such as humidity sensors
• Linear inputs 0–10 VDC, such as indoor air-quality sensors
• Linear outputs 0-20 mA, such as variable frequency drives
• Linear outputs 0–10 VDC, such as accuators for dampers and valves
• Pulse outputs, such as electric heat or humidifier control
• Binary outputs, such as fan start/stop.
• One 3-wire pressure transducer input
Universal Input/Analog
Configure using any combination of analog or binary inputs/analog outputs
Output
Binary output 4 Relay (form A) wet 24 VAC, 0.5A maximum Ranges are given per contact.
Point total 19
BAS-SVX45E-EN 9
Overview
Required Tools
A 1/8 in. (3 mm) flat-bladed screwdriver is required to perform functions such as setting rotary
addressing switches, tightening or loosening screw terminals, and removing or repositioning the
controller on DIN rail.
10 BAS-SVX45E-EN
Overview
P1
UC600
LINK MBUS IMC
BO1 BO2 BO3 BO4 TX
RX
LINK
SERVICE
ACT
SERVICE TOOL
ADDRESS
901 901 901
2 3
2 3
2 3
7 8
7 8
7 8
x100 x10 x1
4.00 in.
(101.6 mm)
BAS-SVX45E-EN 11
Overview
12 BAS-SVX45E-EN
Installation
This section describes how to installTracer UC600 onto a DIN rail and set rotary switches.
NOTICE:
Avoid Equipment Damage!
Do not use excessive force to install the controller on the DIN rail. Excessive force could
result in damage to the enclosure.
BAS-SVX45E-EN 13
Installation
14 BAS-SVX45E-EN
Installation
P1
UC600
LINK MBUS IMC
BO1 BO2 BO 3 BO4 TX
RX
LINK
SERVICE
ACT
SERVICE TOOL
ADDRESS
90 1 90 1 90 1
ADDRESS
901 901 901
2 3
2 3
2 3
7 8
7 8
7 8
2 3
2 3
2 3
7 8
7 8
7 8
x100 x10 x1
4 56 4 56 4 56
x100 x10 x1
AO1 AO2 AO3 AO4 AO5 AO6
UI9 UI10 UI11 UI12 UI13 UI14
direction.
BAS-SVX45E-EN 15
Installation
16 BAS-SVX45E-EN
Installation
BAS-SVX45E-EN 17
Tracer UC600 Pre-power Checks
To avoid equipment damage, a pre-power check for inputs and outputs is recommended before
applying power to theTracer UC600.
Before applying power, check for the following:
• All thermistors; check for 10K by using a digital multimeter (DMM).
• Thumbwheels; range between 189 and 890
• Binary outputs; check for any dead shorts.
• Analog outputs; verify that AC voltage is not present and that the load does not have 24 VAC
or 120 VAC.
This section provides illustrations and methods of how to check theTracer UC600 points before
connection has been made and power applied.The step numbers in each illustration correspond
to the information in each table. (Refer to Table 2, p. 9 for a list of device connections.)
Note: The illustrations in the section, “Commissioning/Troubleshooting in a Powered State,” p. 66
show the location of the UC600.
Resistive Inputs
18 BAS-SVX45E-EN
Tracer UC600 Pre-power Checks
Voltage Inputs
Current Inputs
BAS-SVX45E-EN 19
Tracer UC600 Pre-power Checks
Binary Inputs
20 BAS-SVX45E-EN
Power Budget Check in an Un-powered State
This section provides information about power budget consumption for the UC600 in an
un-powered state.
BAS-SVX45E-EN 21
Power Budget Check in an Un-powered State
22 BAS-SVX45E-EN
Wiring and Powering the Tracer UC600
This section describes how to wire and safely power the UC600.
Important: If problems occur after powering refer to the troubleshooting section,
“Commissioning/Troubleshooting in a Powered State,” p. 66.
Tip: Before powering the UC600, read sections, “Tracer UC600 Pre-power Checks,” p. 18 and
“Power Budget Check in an Un-powered State,” p. 21.
CAUTION
Personal Injury and Equipment Damage!
After installation, verify that the 24 VAC transformer is grounded through the controller. Failure
to do so could result in personal injury and/or damage to equipment. Measure the voltage
between chassis ground and any ground terminal on the controller. Expected result: VAC 4.0 V.
Refer to the section, “Wiring AC Power to Tracer UC600,” p. 25.
Notice:
Equipment Damage!
Complete input/output wiring before applying power to the UC600 controller. Failure to
complete this task may cause damage to the controller or power transformer due to inadvertent
connections to power circuits. The designed units accept only copper conductors. Other types
may cause equipment damage. Do not share 24 VAC between controllers. Sharing 24 VAC power
may cause controller damage (refer to the section, “Transformer Requirements,” p. 24).
BAS-SVX45E-EN 23
Wiring and Powering the Tracer UC600
Transformer Requirements
• AC transformer requirements: UL listed, Class 2 power transformer, 24 VAC ±15%, device max
load 26 VA.The transformer must be sized to provide adequate power to the UC600 controller
(26 VA) and any external device outputs.
• DC power can be used for 4-20 mA devices and up to two expansion modules (XM30, XM32)
and one WCI.
• Include in the total power budget any devices that are powered from the 24 VAC terminal.
• CE-compliant installations:The transformer must be CE marked and SELV compliant per IEC
standards.
A separate transformer is recommended for each controller.The line input to the transformer must
be equipped with a circuit breaker sized to manage the maximum transformer line current.
If a single transformer is shared by multiple UC600 controllers:
• The transformer must have sufficient capacity.
• Polarity must be maintained for every UC600 controller powered by the transformer
Important: If polarity is inadvertently reversed between controllers that are powered by the
same transformer, a difference of 24 VAC will occur between the grounds of each
controller.The following symptoms could result:
–Partial or full loss of communication on the entire BACnet MS/TP link.
–Improper function of UC600 controller outputs.
–Damage to the transformer or a blown transformer fuse.
24 BAS-SVX45E-EN
Wiring and Powering the Tracer UC600
24 VAC
transformer
P1
UC600
LINK MBUS IMC
BO1 BO2 BO3 B O4 TX
RX
LINK
SERVICE
ACT
SERVICE TOOL
ADDRESS
9 0 1 9 0 1 9 0 1
23
23
23
78
78
78
4 5 6 4 5 6 4 5 6
x100 x10 x1
BAS-SVX45E-EN 25
Wiring and Powering the Tracer UC600
Solid Green LED has been pressed and remains on until powered down.
26 BAS-SVX45E-EN
Wiring and Powering the Tracer UC600
BACnet/IP Wiring
Tracer UC600 versions 5.0 or higher firmware supports BACnet/IP over an Ethernet network.The
controller requires a Cat5 Ethernet cable and an RJ-45 plug connector. See “Appendix A:
ConfiguringTracer UC600 for BACnet/IP,” p. 76 for more information.
+ IM +
IMC + IM
VDC VDC VDC
LINK IMC LINK IMC BI LINK IMC
+
AI AI AI AI AI
P1 P1 P P
+
BACnet BACnet
terminator terminator
Zone sensor
BAS-SVX45E-EN 27
Wiring Inputs and Outputs
Wiring and configuration for UC600 inputs and outputs is described in this section. Refer to Table 2,
p. 9 for a complete list of device connections and descriptions of each type.
Important: If there are problems after powering, refer to the troubleshooting section,
“Commissioning/Troubleshooting in a Powered State,” p. 66.
• Input/Output Requirements
All input/output wiring for theTracer UC600 must meet the following requirements:
• All wiring must be in accordance with the National Electrical Code and local codes.
• Do NOT run input/output wires in the same wire bundle with AC-power wires.
• Use only 18–22 AWG (1.02 mm to 0.65 mm diameter), stranded, tinned-copper, shielded,
twisted-pair wire.
• Binary output wiring must not exceed 1,000 ft. (300 m).
• Binary input and 0–20 mA input wiring must not exceed 1,000 ft. (300 m).
• Analog and 24VDC output wiring distances are dependent on the specifications of the receiving
unit. Use shielding for analog and 24 VDC outputs.
• Thermistor input and 0–10 VDC input or output wiring must not exceed 300 ft. (100 m).
28 BAS-SVX45E-EN
Wiring Inputs and Outputs
P1
UC600
LINK MBUS IMC
BO1 BO2 BO3 BO4 TX
RX
LINK
SERVICE
ACT
SERVICE TOOL
ADDRESS
901 901 901
2 3
2 3
2 3
7 8
7 8
7 8
x100 x10 x1
(0.5 A maximum)
BAS-SVX45E-EN 29
Wiring Inputs and Outputs
Binary
Switch
Common Shield
IMC
UC600
ADDRESS
901 901 901
2 3
2 3
2 3
7 8
7 8
7 8
x100 x10 x1
Binary
Switch
AO1 AO2 AO3 AO4 AO5 AO6
UI9 UI10 UI11 UI12 UI13 UI14
Signal
30 BAS-SVX45E-EN
Wiring Inputs and Outputs
P1
UC600
LINK MBUS IMC
BO1 BO2 BO3 BO4 TX
RX
LINK
SERVICE
ACT
SERVICE TOOL
ADDRESS
901 901 901
2 3
2 3
2 3
7 8
7 8
7 8
x100 x10 x1
Common
BAS-SVX45E-EN 31
Wiring Inputs and Outputs
0-20 mA out
24 VDC
ADDRESS
0-20 mA out
90 1 90 1 90 1
2 3
2 3
2 3
7 8
7 8
7 8
4 56 4 56 4 56
3-wire
x100 x10 x1
Common
AO1 AO2 AO3 AO4 AO5 AO6
UI9 UI10 UI11 UI12 UI13 UI14
24 VDC
2-wire
0-20 mA out
32 BAS-SVX45E-EN
Wiring Inputs and Outputs
Common
Common
P1
UC600
LINK MBUS IMC
B O1 B O2 BO3 B O4 TX
RX
LINK
SERVICE
ACT
SERVICE TOOL
ADDRESS
90 1 90 1 90 1
2 3
2 3
2 3
7 8
7 8
7 8
4 56 4 56 4 56
x100 x10 x1
BAS-SVX45E-EN 33
Wiring Inputs and Outputs
P1
UC600
LINK MBUS IMC
B O1 BO2 BO3 BO4 TX
RX
LINK
SERVICE
ACT
SERVICE TOOL
ADDRESS
90 1 90 1 90 1
2 3
2 3
2 3
7 8
7 8
7 8
4 56 4 56 4 56
x100 x10 x1
34 BAS-SVX45E-EN
Wiring Inputs and Outputs
P1
UC600
LINK MBUS IMC
BO1 BO2 BO3 BO4 TX
RX
LINK
0-20 mA ACT
SERVICE
SERVICE TOOL
ADDRESS
24 VDC
90 1 90 1 90 1
2 3
2 3
2 3
7 8
7 8
7 8
4 56 4 56 4 56
x100 x10 x1
Signal
AO1 AO2 AO3 AO4 AO5 AO6
UI9 UI10 UI11 UI12 UI13 UI14
Common BO1
RELAYS 0.5 A MAX
Common
BAS-SVX45E-EN 35
Wiring Inputs and Outputs
Notice:
Controlling coil-based loads: Inrush current (the initial surge of a current into a load before it attains
normal operating condition) can be three times greater, or more, than the operating current.
Important: Use pilot relays for dry contact outputs for load currents greater than 0.5 amperes
and use powered outputs for load currents less than 0.5 amperes.
1. Connect the shield to a common terminal at the terminal board and tape it back at the powered
output device.
2. Connect the signal wire to an available output terminal.
3. Use theTracerTU service tool to configure the binary output for binary operation.
P1
UC600
LINK MBUS IMC
BO1 BO2 BO 3 BO4 TX
RX
LINK
SERVICE
ACT
SERVICE TOOL
ADDRESS
9
01 0
9 1 9
01
2 3
2 3
2 3
7 8
7 8
7 8
x100 x10 x1
Powered
Signal Pilot relay
output
(24 VAC coil)
Signal
Common
Common
Tape back shield
36 BAS-SVX45E-EN
Connecting Pressure Transducer Inputs
Tracer UC600 is equipped with one 3-pin, 5 VDC pressure transducer input connection (P1)
designed for Kavlico pressure transducers.Transducers measure duct static pressure in theTracer
UC600 equipment (VAV AHUs) that is detected from the connected sensor (mounted near the
Tracer UC600).
Important: To ensure accurate data transmission, use Kavlico pressure transducers. Contact
Trane for more details on pressure transducers.
To connect to the pressure transducer input, press the pressure transducer cable onto the pressure
input (P1). Refer to the illustration below.
IMC 24 24 24 +24 +24 +24 IMC
VAC VAC VAC VDC VDC VDC
XFMR OUT MBUS OUT OUT LINK IMC
P1
UC600
LINK MBUS IMC
BO1 BO2 BO3 BO4 TX
RX
Pressure Input P1 LINK
SERVICE
ACT
SERVICE TOOL
ADDRESS
901 901 901
2 3
2 3
2 3
7 8
7 8
7 8
x100 x10 x1
BAS-SVX45E-EN 37
Tracer UC600 Operation
LED Descriptions and Activities
The following table provides a description of LED activity, indicators, and troubleshooting tips.
Refer to Figure 1, p. 8, for locations of the LEDs.
Note: Points that are in an alarm state when the notification type is configured as “alarm” will
cause the power LED to flash red. If the notification type of a point is configured as “event,”
the power LED will not flash when the point is in an alarm state. Modbus is not supported
at this time.
38 BAS-SVX45E-EN
Tracer UC600 Operation
Troubleshooting
The section provides troubleshooting solutions for problems that sometimes occur with theTracer
UC600.
Communication Problems
Problem:Tracer UC600 is not communicating withTracer SC, but can communicate withTracerTU
using a direct USB connection.
Possible cause:The “Soft Set Device ID” check box was unchecked after theTracer UC600 was
installed onto theTracer SC.
Possible solution: Reinstall theTracer UC600 device onto theTracer SC.
1. Verify that theTracer UC600 device ID is set to the rotary address, which is found inTracerTU/
controller/controller settings/protocol.
2. Log on toTracer SC and navigate to the Devices page; select theTracer UC600 device from the
list, then select replace from the actions button.
Alternative cause:The baud rate changed in the controller settings.
Solution: InTracerTU, open the Controller Settings page. Set the baud rate to match the baud rate
on theTracer SC MS/TP link.
Alternate Cause:The rotary switch is not set properly or another device on the same MS/TP link
is set to the same rotary address.
Solution: Verify that the rotary address is correct. If not, change the address and cycle power. If the
device was previously installed in theTracer SC, the device may need to be "replaced" from the
Tracer SC Devices page.
Alternate Solution: If the device is set to the proper rotary address, then another device(s) could
be using the same rotary address on the MS/TP link.
1. Power down the UC600 and discover the link withTracer SC to see if a duplicate device is
present.
2. Change address of duplicate device, then reapply power theTracer UC600.
If previously installed, the device may need to be replaced in theTracer SC.
Output Points
Problem: Output points are not being controlled by theTracer UC600.
Possible cause:The output point was not configured properly inTracerTU.
Solution: Verify the hardware configuration inTracerTU and change as needed.
Problem:The value of an analog point reads correctly inTracerTU but does not read correctly in
theTracer SC.
Solution:Verify that the dimensionality was set properly on the point configuration page ofTU. Log
on toTracer SC and navigate to the Devices page; select theTracer UC600 device from the list, then
select replace from the actions button.
Alternate solution: Verify that the equipment template is pointing to the proper output point in the
Tracer UC600.
Problem:The output point is out of service.
Solution: Place point in service from eitherTracerTU orTracer SC.
BAS-SVX45E-EN 39
Tracer UC600 Operation
Connection Problems
Problem:Tracer UC600 is not responding, communicating, or is unable to connect withTracer SC
or theTracerTU service tool. (For more information about theTracerTU service tool, see
“ConfiguringTracer UC600 withTracerTU,” p. 41.)
Possible cause: Defective application code in the controller.
Possible solution: Reload the application firmware.
1. Power down the controller (make sure to disconnect the USB cable).
2. Continuously hold down the service button pin while applying power. Press the service button
until the power LED illuminates green. Connect withTracerTU and reload the application
firmware.
Note: During the above process, the service LED will be green and the communication status LEDs
will be inactive.
40 BAS-SVX45E-EN
Configuring Tracer UC600 with Tracer TU
TheTracerTU service tool is comprised of tools that allow users to edit objects, configure
equipment, customizeTGP2 programs, and create and edit custom graphics.These functions are
performed using the Device NavigationTree and theTU Utility tab. For more detailed information
about any of these functions and theTU service tool, refer to “Other Resources,” p. 75.
See “Setting UpTracer UC600 BACnet CommunicationWithTracerTU,” p. 78, for details associated
with the BACnet/IP protocol.
Important: TheTracer UC600 is not intended to be disassembled for maintenance.
This section describes:
• Starting a session ofTU and establishing a direct USB connection.
• Establishing a connection using Ethernet or LAN.
• Checking andTransferring Application Code.
• Configuring theTracer UC600.
• Creating and editing points for theTracer UC600.
• Monitoring and viewing the status of theTracer UC600.
• Backing up files and replacing corrupt files (Backup and Replace).
2. If theTracer UC600 appears, select Install the software automatically (Recommended) and then
click Next.
If theTracer UC600 does not appear, repeat theTracerTU installation.
BAS-SVX45E-EN 41
Configuring Tracer UC600 with Tracer TU
42 BAS-SVX45E-EN
Configuring Tracer UC600 with Tracer TU
4. Enter a facility name, IP address, and a description. (Select the IP check box if port forwarding
will be used.)
5. Click Save.The facility is now saved and can be selected from the Facility down-down list.
6. From the Facility drop-down list, select the new entry (Figure 20).
BAS-SVX45E-EN 43
Configuring Tracer UC600 with Tracer TU
Open the Found New Hardware Wizard and verify that Tracer UC600 is displayed after
“This wizard helps you to install software for”.
Respond as follows:
Found New Hardware (Popup message)
If this text is displayed, then select, Install the software automatically
(Recommended). If this text does not appear, run the Tracer TU installation file, Tracer TU
Setup.exe.
Open the File Transfer Utility in the Tracer TU service tool to transfer the Tracer UC600
No application code present
application firmware. (Refer to “Upgrading Firmware,” p. 45.)
44 BAS-SVX45E-EN
Configuring Tracer UC600 with Tracer TU
Upgrading Firmware
Firmware upgrades require the use ofTracerTU (version 8.0 or higher).
To upgrade Tracer UC600 firmware:
1. ConnectTracerTU toTracer UC600 using a USB connection (direct connect).
It is not recommended that the firmware be updated using single-link access or connecting
through theTracer SC.
2. Click the file transfer utility icon ( ) located on the upper left portion ofTracerTU, which
opens the FileTransfer wizard.
3. Select theTracer UC600 from the Selected devices box. Click Next.
The Choose files to Transfer to each Device or Device Group dialog box appears.
4. Click Browse, which opens the Selected files dialog box.
5. Browse to theTracerTU/Firmware/UC600 directory which is often found in My Documents.
6. Select the firmware file that has the .mod file extension. Version 2.0 firmware and higher uses
the .mod extension.
Important: Selecting a lower version of firmware will clear all configuration in the controller.
BAS-SVX45E-EN 45
Configuring Tracer UC600 with Tracer TU
46 BAS-SVX45E-EN
Configuring Tracer UC600 with Tracer TU
BAS-SVX45E-EN 47
Configuring Tracer UC600 with Tracer TU
6. Click Save to File to save the new point configuration or click Send to Device to send the new
point configuration to the controller.
To edit, copy, or delete a point:
1. Click the Status Utility tab on the right side of theTracerTU window.The corresponding
horizontal member tabs appear across the top of the viewing area.
2. Select the menu option for the type of point to edit. Select the check box on the left side of the
row of the point you want to edit.
3. Select the Edit option from the Action drop-down menu and then click Go.
4. The Point Properties dialog box appears.
5. Edit the individual settings you want to change and then click OK.
6. Click Save to File to save the new point configuration or click Send to Device to send the new
point configuration to the controller.
48 BAS-SVX45E-EN
Configuring Tracer UC600 with Tracer TU
Values
Value objects will not accept a written value from applications on the controller, such asTGP2 or
schedules. A remote application, such asTracerTU orTracer SC, allows you to write to a value
object when out-of-service.
Note: This will require the use of the priority table.
BAS-SVX45E-EN 49
Configuring Tracer UC600 with Tracer TU
Select an XM
module from the
Device node
50 BAS-SVX45E-EN
Configuring Tracer UC600 with Tracer TU
Select
“analog
value” from
Select this
the reference
check box
dialog box.
Select “mode” in
the reference
dialog box.
Multistates
for */**
mode
BAS-SVX45E-EN 51
Configuring Tracer UC600 with Tracer TU
52 BAS-SVX45E-EN
Configuring Tracer UC600 with Tracer TU
BAS-SVX45E-EN 53
Configuring Tracer UC600 with Tracer TU
Backup
When you commission a system, it is strongly recommended that you create a backup file of the
initial configuration settings. If necessary, the backup file can be restored at a later date.
The backup procedure storesTGP2 files, all object configuration, setup files, and BACnet
identification files. In addition, the data log configuration is stored in the backup file (data
excluded).
To back up files from the controller:
1. Click the Backup Wizard icon in the upper left corner of theTU window.The Welcome to the
Backup Wizard opens.
2. Click Next.The Choose From Available Devices dialog box appears.
3. Select the controller from which you will be backing up files.
4. Click Browse to navigate to the directory where the backup file will be saved. Select a location.
click Save, and then click Next.
5. Click Start. A dialog box containing a progress meter appears. When the backup process is
complete, a confirmation message appears.
6. Click Finish.
54 BAS-SVX45E-EN
Configuring Tracer UC600 with Tracer TU
Name and
Description fields
BAS-SVX45E-EN 55
Configuring Tracer UC600 with Tracer TU
7. Use the arrow controls to select up to 10 members by transferring points from the All Points
box to the Selected Points box (Figure 32).
The first member added will filter the remaining list of available members to display only
members with the same point type and units.
8. Click Send to Device to save the schedule. If working offline, click Save to File, which will save
the schedule to the configuration file.
56 BAS-SVX45E-EN
Configuring Tracer UC600 with Tracer TU
BAS-SVX45E-EN 57
Configuring Tracer UC600 with Tracer TU
Adding Events
1. From the Actions drop-down list, select Add Event then click Go to display the Events dialog
box (Figure 34).
Events for a particular day can be viewed by selecting the day of the week at the top of the Add
Events dialog box (Figure 35).
2. Follow the steps in the dialog box to add events to one or more days at a time. (Events are
defined as time-value pairs.)
a. Select the day or days that share the event.
b. Set the start time and value.
c. Click Add Events to add the events to the schedule for the days selected.
Note: Verify that the events are current for each day by selecting the day of the week at the top
of the Add Events dialog box.
Day being
viewed
Select days to
which new events
will be applied
58 BAS-SVX45E-EN
Configuring Tracer UC600 with Tracer TU
3. Repeat the above steps to add up to 10 events for each day of the week. Click OK to return to
the Schedules page.
To modify events on a particular day:
Select a day in the EventTable from the Add Event dialog box. Use the arrow buttons to change
the value.The new value is automatically saved.
To delete an event:
Select a day in the EventTable from the Add Event dialog box. Click the Delete button, which
removes the event from the schedule for that particular day.
BAS-SVX45E-EN 59
Configuring Tracer UC600 with Tracer TU
To add exceptions:
1. Open the schedule to which you want to add exceptions.
2. From the Actions drop-down list Select Add Exceptions. Click Go to display the Add Exceptions
dialog box (Figure 36). (Or access from the Exception list page).
3. Select Does Not Recur for a one-time exception and then select the specific date in the Occurs
on Date fly-out calendar on the right. Otherwise, select Monthly or Yearly recurrence options
and specify the appropriate recurrence pattern on the right.
Note: Exceptions that occur on the same date each year, such as Christmas Day and NewYear’s
Day, are examples of exceptions that should be set as recurring.
4. Enter the StartTime and Value. A second event can be added by selecting the corresponding
check box.
5. Click Add Event(s).
The event(s) appear in the Exceptions list at the bottom of the dialog box.
6. Repeat steps 4 and 5 to add more events for an exception. Up to 10 events can be added.
7. Click OK when you have finished adding all exceptions and events.
Note: It is best practice to add an event at midnight to ensure that the exception is in control of
the events for the entire day.
Figure 37, p. 61 shows a typical schedule (resultant) with events and exceptions applied. Exceptions
that do not recur are identified by a downward pointing arrow icon. Exceptions that do recur
are identified by an circular arrow icon.
60 BAS-SVX45E-EN
Configuring Tracer UC600 with Tracer TU
Click on day in the resultant to view all exceptions applied to the day from the highest priority to
the lowest, with normal events at the bottom.
Weekly View
BAS-SVX45E-EN 61
Configuring Tracer UC600 with Tracer TU
Modifying Exceptions
1. Open the schedule containing the exception you want to modify.
2. Select an exception from those listed in the Exceptions group box.
3. From Actions drop-down list, select Modify Selected Exception, then click Go.
Deleting Events
1. Open the schedule from which you want to delete events.
2. From the Actions drop-down list in the Events group box, select Modify Events and then click
Go.
3. Click the tab of the first day of the week to which the event belongs.
4. Click the Delete button in the row of the event you want to delete (Figure 38).
62 BAS-SVX45E-EN
Configuring Tracer UC600 with Tracer TU
Deleting Exceptions
1. Open the schedule containing the exception you want to delete.
2. Select an exception from those listed in the Exceptions group box.
3. From the Actions drop-down list, select Delete Selected Exception and then click Go.
Deleting a Schedule
1. Select Utilities > Equipment > Scheduling to display the Schedules screen.
2. Expand the Schedule box containing the schedule you want to delete.
3. From theActions drop-down list in the Scheduled Events group box, select Delete Schedule and
then click Go (Figure 40).
The schedule is deleted.You can then create a new schedule with a new set of members.
Custom Graphics
Graphics can be viewed inTracerTU by accessing theTD7 operator display user interface.
To access, navigate to the Unit Summary screen. Click the Operator Display User Interface button
located on the bottom left portion of the page. It is not necessary to be connected to aTracerTD7
Display to view the interface.
Note: In order to view theTD7 operator display user interface, you must be connected to the
UC600 using a USB cable.
BAS-SVX45E-EN 63
Configuring Tracer UC600 with Tracer TU
Custom graphics are created and loaded usingTracer Graphics Editor (TGE). See theTGE online
help for more information. Standard graphics are available in the most recent Pre-Packaged
Solutions (PPS) library at https://home.ingerrand.com/our%20businesses/ClimateSolutions/Sales/
prepackaged/Pages/Home.aspx.
Graphics allow you to:
• Perform overrides
• Assign a graphic as your home page
• Link to the Alarms page
• Link to a schedule
• Link to the All Points Report and Custom Reports
• Link to another graphic
64 BAS-SVX45E-EN
Configuring Tracer UC600 with Tracer TU
BAS-SVX45E-EN 65
Commissioning/Troubleshooting in a Powered State
This section provides instructions for testing theTracer UC600 points after making connection and
applying power (indicated in each figure by the terminal connector and theTracer U600 label).The
step numbers or method numbers in each figure correspond to the information in each table. (Refer
to Table 2, p. 9 for a list of device connections.)
The following equipment is required in order to test inputs and outputs:
• Digital multimeter (DMM)
• Small flat-bladed screwdriver
66 BAS-SVX45E-EN
Commissioning/Troubleshooting in a Powered State
Resistive Inputs
Measured Voltage Across a Thermistor Input Measured Voltage Across a Thermistor Input
4 4
Voltage Measured Across Input–Vdc
3.5 3.5
3 3
2.5 2.5
2 2
1.5 1.5
1 1
0.5 0.5
0 0
0 50 100 150 200 -40 -20 0 20 40 60 80 100
Charts show
measurements 2
across thermistor
input (Fahrenheit
1.5
and Celsius) and
resistive input.
1
0.5
0
0 2 4 6 8 10 12 14 16 18 20
BAS-SVX45E-EN 67
Commissioning/Troubleshooting in a Powered State
Voltage Inputs
68 BAS-SVX45E-EN
Commissioning/Troubleshooting in a Powered State
3.5
2.5
1.5
0.5
0
0 2 4 6 8 10 12 14 16 18 20
BAS-SVX45E-EN 69
Commissioning/Troubleshooting in a Powered State
24 Vac Measurement
P1
UC600
LINK MBUS IMC
BO1 BO2 BO3 BO4 TX
RX
LINK
SERVICE
ACT
SERVICE TOOL
ADDRESS
901 901 901
2 3
2 3
2 3
7 8
7 8
7 8
x100 x10 x1
70 BAS-SVX45E-EN
Commissioning/Troubleshooting in a Powered State
BAS-SVX45E-EN 71
Commissioning/Troubleshooting in a Powered State
Open-collector based binary sensors use a bipolar junction transistor (BJT).This is a three-
terminal device in which emitter-to-collector current is controlled by base current as the
switching device in place of a relay.The term, open-collector, refers to the collector connection
on the transistor itself. Open-collector circuits are used for their low fatigue rate and quick
response relative to relay-based outputs.
The circuit within the pulse meter is completed when adding a pull-up resistance and reference
voltage. On the UC600, both universal input (UI) and analog output (AO) circuits add the
necessary resistance and voltage without external parts.
Note: The reference voltage must always be DC.
The voltage across the pulse meter terminals will bounce between Vsat (saturation voltage) of
the transistor in the pulse meter and theVref (reference voltage) provided by the UI or AO circuits
of the UC600. Most bipolar transistors have a Vsat of less than 0.2 Vdc.
The DMM sampling rate may be too slow to measure pulse meter output transitions.
Note: Check the specifications of the DMM. It may be necessary to use an oscilloscope to
measure the transition voltages.
72 BAS-SVX45E-EN
Commissioning/Troubleshooting in a Powered State
BAS-SVX45E-EN 73
Commissioning/Troubleshooting in a Powered State
Ground Measurements
74 BAS-SVX45E-EN
Other Resources
For more detailed information, refer to the following documentation:
• Tracer SC System Controller Installation and Setup (BAS-SVX31)
• BACnet Best Practices andTroubleshooting Guide (BAS-SVX51)
• Tracer Graphical Programming 2 (TGP2) Editor Online Help
• Tracer Graphical Programming (TGP2) Application Guide (BAS-APG008)
• TracerTU Online Help
• TracerTU ServiceTool Getting Started Guide (TTU-SVN01)
• Tracer UC600 Installation Instructions (X39641178-01)
• Tracer XM30 Expansion Module Installation Instructions (X39641148-01)
• Tracer XM32 Expansion Module Installation Instructions (X39641174-01)
• Tracer Expansion Module Installation, Operation, and Maintenance (BAS-SVX046)
• Tracer UC600 Protocol Implementation Conformance Statement (PICS), (BAS-PRG010)
BAS-SVX45E-EN 75
Appendix A: Configuring Tracer UC600 for BACnet/IP
Tracer UC600 controllers with firmware versions 5.0 or higher now support the BACnet/IP protocol.
This appendix providesTracer UC600 configuration information to enable communication using
the BACnet/IP protocol.
76 BAS-SVX45E-EN
Appendix A: Configuring Tracer UC600 for BACnet/IP
BAS-SVX45E-EN 77
Appendix A: Configuring Tracer UC600 for BACnet/IP
78 BAS-SVX45E-EN
Appendix A: Configuring Tracer UC600 for BACnet/IP
Configuring IP Information
1. Navigate to Utilities > Status > Controller Settings.The Controller Settings utility opens.
2. Click Protocol to display a list of protocols thatTracer UC600 uses to communicate with other
controllers.
3. Configure theTracer UC600 with either a specified static IP address or, if necessary, configure
it to automatically acquire its IP address from the network's Dynamic Host Configuration
Protocol (DHCP) server. A hostname can be assigned to the device if a dynamic address is being
used (See Figure 45, p. 80).
4. In the Security frame, select whether to enable HTTP communications (port 80) for remote
communication. (See “Security,” p. 81 for more information).
Note: At this time theTracerTD7 display option is not available when connecting with the
BACnet/IP protocol.This option will be available in a futureTracer UC600 firmware
upgrade.
5. Click Send to Device.
6. Proceed to the “Configuring BACnet Information,” p. 80.
BAS-SVX45E-EN 79
Appendix A: Configuring Tracer UC600 for BACnet/IP
80 BAS-SVX45E-EN
Appendix A: Configuring Tracer UC600 for BACnet/IP
Setting Up a BDT
The BACnet protocol requires the use of IP broadcast messages. IP routers do not pass broadcast
messages from one subnet to another. BACnet BBMD functionality is used to forward broadcast
messages across IP routers to BACnet devices on the remote subnet. BBMDs are not required if all
BACnet/IP devices reside on the same subnet.
A broadcast distribution table (BDT) is part of the BBMD functionality. A BDT contains the list of IP
addresses that identify each BBMD in the BACnet network. All BBMDs should have exactly the
same entries in their BDT and must include their own IP address.
Important: Only one BBMD per IP subnet is allowed.
To set up a BDT for Tracer UC600:
1. Start a session ofTracerTU.
2. Navigate to Utilities > Status > Controller Settings.The Controller Settings utility opens.
3. Click Protocol to display a list of protocols that the UC600 uses to communicate with other
controllers. Select the Controller is a BACnet Broadcast Management Device (BBMD) check
box. (See Figure 47.)
Security
Tracer UC600 network security can be enhanced by limiting user access over the IP network,
restricting access to HTTPS only, and disabling the user interface through a Web browser.The
customer’s IT staff should be consulted when setting up enhanced security.
BAS-SVX45E-EN 81
Appendix A: Configuring Tracer UC600 for BACnet/IP
82 BAS-SVX45E-EN
Declaration of CE Conformity
Manufacturer name: Trane
EN55022:2006 (CISPR
(by Council Directive 2004/108/EEC) 22:2005+A1:2005) Radiated Class B Limit (30 MHz—1000 MHz, 1 GHz—2 GHz)
Emissions
EN55022:2006 (CISPR
22:2005+A1:2005) Radiated 150 kHz—30 MHz
Emissions
EN61000-4-2: 1995+A1:
(by Council Directive 89/336/EEC) 1998+A2:2001 Electrostatic 8 kV air, 4 kV contact
Discharge (ESD)
I/O port, 1 kV
EN61000-4-4: 2004 Fast Transients
AC inputs and output ports, 2 kV
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.