SDM120C

SMART MINI POWER


DIN Rail Smart Energy Meter for Single Electrical Systems

USER MANUAL
2014 V1.0

Downloaded from www.Manualslib.com manuals search engine


Important Safety Information is contained in the Maintenance section. Familiarize yourself with
this information before attempting installation or other procedures.

Symbols used in this document:

Risk of Danger: These instructions contain important safety information:


Read them before starting installation or servicing of the equipment

Caution: Risk of Electric Shock

Downloaded from www.Manualslib.com manuals search engine


1 Introduction
This document provides operating, maintenance and installation instructions.The unit measures
and displays the characteristics of single phase two wires(1p2w)supply, including voltage(V),
current(A),power(W),frequency(Hz),power factor(PF),active energy(kWh).The non-displayed
parameters of imported and exported energy can be read via RS485 communication with
corresponding register.
The meter is self-power supplied when it’s connected with single phase two wires system,does
not need to input a auxiliary power supply.It’s directed connected,does not need to connect with
external current transformer(CT).Built-in interfaces provides pulse and RS485 Modbus RTU
outputs.

1.1 Unit Characteristics


The Unit can measure and display:
 Voltage
 Current
 Power
 Frequency
 Power factor
 Active energy
Two pulse output indicates real-time energy measurement. An RS485 output allows remote
monitoring from another display or a computer.

1.2 RS485 Serial – Modbus RTU


This uses an RS485 serial port with Modbus RTU protocol to provide a means of remotely
monitoring and controlling the Unit

1.3 Pulse output


This provides two pulse outputs,Pulse 1 is settable and can be setted into four different energy
output modes:
Mode 1 0.001kWh/imp(default)
Mode 2 0.01kWh/imp
Mode 3 0.1kWh/imp
Mode 4 1kWh/imp

Also,pulse 1 can be setted into three types pulse out modes.


Mode 1:Measures imported energy.Total energy=imported energy(default)
Mode 2:Measures imported energy and exported energy.
Total energy=imported energy+exported energy
Mode 3:Measures imported energy and exported energy.
Total energy=imported energy-exported energy
Pulse 2 is fixed as 1000imp/kwh and cannot be setted.

-1-

Downloaded from www.Manualslib.com manuals search engine


2.Specifications
2.1 Performance criteria
Operating humidity ≤ 85%
Storage humidity ≤ 95%
Operating temperature -25 ° C - +55 ° C
(3K6)
Storage temperature -30°C - +70°C
International standard IEC 62053-21
Accuracy class 0.5 or 1.0
Protection against penetration of dust and water IP51
Insulating encased meter of protective class II

2.2 Meter specifications


Nominal voltage(Un) 230V AC 110V AC
Operational voltage 0.7-1.3Un
Insulation capabilities:
- AC voltage withstand 4KV for 1 minute
- Impulse voltage withstand 6kV-1.2µS waveform
Basic current(Ib) 5A
Maximum rated current(Imax) 45A
Operational current range 0.4% Ib-Imax
Over current withstand 20Imax for 0.01s
Operational frequency range 50-60Hz ±2%
Internal power consumption ≤ 2W / 10VA
Test output flash rate (RED LED) 1000imp/kWh
Pulse output rate 1000imp/kWh
Consumption indicator (RED LED) Flashing at load running
Data communication port RS485 Modbus RTU
Data save >20 years when power off

2.3 RS485 communication specifications


Bus type RS485
protocol MODBUS RTU with 16 bit CRC
baud rate 1200,2400(default), 4800,9600
Address range 1-247 user settable
Bus Loading 32 meters per bus
Rage 1000M
Parity EVEN (default)/ODD/NONE
Stop bit 1
Data bits 8

-2-

Downloaded from www.Manualslib.com manuals search engine


2.4 Accuracy
Voltage 0·5% of range maximum
Current 0·5% of nominal
Frequency 0·2% of mid-frequency
Power factor 1% of unity (0.01)
Active power (W) ±1% of range maximum
Reactive power (VAr) ±2% of range maximum
Apparent power (VA) ±1% of range maximum
Active energy (Wh) Class 1 IEC 62053-21

2.5 Environment
Operating temperature -25°C to +55°C*
Storage temperature -40°C to +70°C*
Relative humidity 0 to 90%, non-condensing
Altitude Up to 2000m
Warm up time 1 minute
Vibration 10Hz to 50Hz, IEC 60068-2-6, 2g
Shock 30g in 3 planes
*Maximum operating and storage temperatures are in the context of typical daily and seasonal
variation.

3. Start Up Screens
The first screen lights up all display segments
and can be used as a display check

The second screen indicates the firmware


version number

The interface performs a HELLO to welcome

After a short delay, the screen will display active energy measurements.

4.Measurements and display


The buttons operate as follows:

-3-

Downloaded from www.Manualslib.com manuals search engine


Press the button once effectively to scroll the display interface

Long press the button last for 3 secs to enter the set-up model

Each successive pressing of the button selects a new range:


Total kWh
The default display form is X.XX,when it achieve
9.99,the display form will turn to XX.XX,
then XXX.XX and XXXX.XX
Voltage

Current

Power

Frequency

Power factor

Meter number(meter ID)


Default 001

Baud rate
Default 2400bps

-4-

Downloaded from www.Manualslib.com manuals search engine


5. Setting Up

To enter set-up mode, pressing the button for 3 seconds, until the lcd display the -SET-

5.1 Set-up Entry Methods


After successfully enter the SET model,then the set-up can be realized via RS485 communication
with the correct Modbus Protocol.
The electrical interface is 2-wire RS485,via 2 screw terminal.Connection should be made using
twisted pair screened cable(Typically 22 gauge Belden 8761 or equivalent).A total maximum
length of 3900 feet(1200 meters) is allowed for the RS485 network.A maximum of 32 electrical
nodes can be connected,including the controller.The address of SDM120C smart meter can be set
to any value between 1 and 247.Broadcast mode(address 0)is not supported.
All data values in the SDM120C smart meter are transferred as 32 bit IEEE754 floating print
numbers,therefore each SDM120C smart meter value is transferred using two Modbus Protocol
registers.All register read requests and data write requests must specify and even number of
registers.Attempts to read/write and odd number of registers prompt the SDM120C smart meter
to return a Modbus Protocol exception message.
The Modbus Protocol establishes the format for the master's query by placing into it the device
address,a function code defining the requested action,any data to be sent,and an error checking
field.The slave's response message is also constructed using Modbus Protocol.

Modbus Protocol function code 04/03 is used to read data.


For example:
to request 01 04 00 00 00 02 CRC to read the voltage
to request 01 04 00 12 00 02 CRC to read apparent power

For example:
to request 01 10 00 14 00 02 04 40 00 00 00 CRC to set meter address as 02
(Hex 40 00 00 00 equals float 2)
to request 01 10 00 1C 00 02 04 40 00 00 00 CRC to set baud rate as 9600
(Hex 40 00 00 00 equals float 2)

5.2 The detailed register map information of SDM120C are as follows:


Part 1
*Parameters to be read by function code 04:
Address Input Register Parameter Modbus Protocol Start
(Register) Address Hex
Parameter Units Format Hi byte Lo byte
30001 Voltage Volts Float 00 00

-5-

Downloaded from www.Manualslib.com manuals search engine


30017 Current Amps Float 00 06
30013 Active power Watts Float 00 0C
30019 Apparent power VA Float 00 12
30025 Reactive power VAr Float 00 18
30031 Power factor None Float 00 1E
30071 Frequency Hz Float 00 46
30073 Import active energy kWh Float 00 48
30075 Export active energy kWh Float 00 4A
30343 Total active energy kWh Float 01 56

Part 2
*It needs to long press the button on meter last for 3 seconds to enter the set-up interface
firstly,then the set-up can be realized via RS485 communication.After the set-up is finished,long
press last for 3 seconds to exit the set-up interface
*Parameters to be setted by function code 10,and to be read by function code 03:
Address Input Register Parameter Modbus Description
(Register) Protocol Start
Address Hex
Parameters Format Hi Lo
byte byte
40021 Meter ID Float 00 14 Ranges from 1 to 247,
and requires a restart to become
effective.Default ID is 1.
It can also be modified via the
display set-up menus.
40029 Baud rate Float 00 1C 0:2400bps(default)
1:4800bps
2:9600bps
5:1200bps
Requires a restart to become
effective.
463745 Time of display BCD F9 00 0-30s
in turns Default 0:does not display in
turns
463761 Pulse 1 output Hex F9 10 0000:0.001kWh/imp(default)
0001:0.01kWh/imp
0002:0.1kWh/imp
0003:1kWh/imp
463777 Measurem-ent Hex F9 20 0001:mode 1(default)
mode 0002:mode 2
0003:mode 3
463793 Pulse 1 output Hex F9 30 0000:Import+export energy,
mode both LEDs of import and export
energy light on(default)

-6-

Downloaded from www.Manualslib.com manuals search engine


0001:Import energy,only the LED
of import energy lights on
0002:Export energy,only the LED
of export energy lights on

6 Dimensions

7. Installation

35
mm

DIN Rail

8.Wiring diagram

-7-

Downloaded from www.Manualslib.com manuals search engine


-8-

Downloaded from www.Manualslib.com manuals search engine