AX-RHT-x3-x

RH & T Transmitter – Duct, Room and Outside-Air

Product overview
The Axio AX-RHT-3-x range of RH & T
Transmitters provide accurate Relative
Humidity and Temperature
measurements, with selectable current or
voltage analogue outputs. The units are
extremely reliable, have excellent
stability and a quick response time. The
standard accuracy range is 3%.

Features
● 3% accuracy ● 0-5/10Vdc and 4-20mA selectable output
● 24Vac/dc powered ● Optional thermistor output for temperature

Product specifications
RH accuracy +/- 3% typical
Temperature accuracy +/- 0.3°C typical
Sensor type Capacitive
Sensor protection PTFE filter
Long term stability +/-1% RH at 50% RH in 5 years
Repeatability +/- 0.5% RH
Hysteresis +/-1% of span max
Response time 15 seconds @ 25°C, but dependant on airflow
Supply voltage 24Vac/dc (+/-15%) (24Vdc only for Room unit with 4-20mA output selected)
Output (voltage) 0 – 10Vdc or 0 – 5Vdc at 10mA maximum load
Output (current) 4-20mA at 500Ohms maximum load
Output range - Relative Humidity 0 to 95%
Output range - Temperature Room -10°C to +40°C, Duct 0°C to +70°C, Outside Air -20°C to +50°C
Terminals Rising clamp for 0.5-2.5mm2 cable
Ambient temperature range -10°C to 50°C, 0-95% RH
Dimensions, weight & protection Room: 85 x 85 x 24mm, 75g, IP20
Duct: 115 x 80 x 52mm housing - 230(L) x 12mm ∅ maximum probe, 115g, IP65
(housing only)
Outside air: 115 x 80 x 52mm, 140g, IP65 (housing only)
Country of origin United Kingdom

Issue 1.0 (08/08/11) Annicom Ltd Page 1 of 3


Unit 21, Highview, Bordon,Hampshire. GU35 0AX.
Tel: +44(0)1420 487788 Fax: +44(0)1420 487799
Email: [email protected]
www.annicom.com

© Copyright Annicom 2011. All rights reserved.


AX-RHT-x3-x
RH & T Transmitter – Duct, Room and Outside-Air

Order codes
AX-RHT-S3 Room RH & T Sensor - 2 x analogue outputs, 3%
AX-RHT-S3-T Room RH & T Sensor - 2 x analogue outputs, 3% , + 10K3A1 sensor Order online at:
AX-RHT-D3 Duct RH & T Sensor - 2 x analogue outputs, 3% www.annicom.com
AX-RHT-D3-T Duct RH & T Sensor - 2 x analogue outputs, 3%, + 10K3A1 sensor Email orders and enquiries to:
AX-RHT-O3 Outside Air RH & T Sensor - 2 x analogue outputs, 3% [email protected]
AX-RHT-03-T Outside Air RH & T Sensor - 2 x analogue outputs, + 10K3A1 sensor

Description
The AX-RHT-x3-x is a Relative Humidity and Temperature transmitter. The output range is selectable with jumpers for
both the Humidity and Temperature analogue outputs.

Installation
The AX-RHT-x3-x should be installed by a suitably qualified technician in conjunction with any guidelines for the
equipment it is to be connected to. Field wiring should be installed to satisfy the requirements set out by the
manufacturer of the equipment that the module is being connected to.
Antistatic precautions must be observed when handling these transmitters. The PCB contains circuitry that can be
damaged by static discharge. Transmitters should only be fitted to a system after airflow calibration has been carried
out and preferably following full fan running of at least several days, in order that the main contaminants have been
removed from the stagnant system. The transmitter board should not be mounted where temperatures will exceed the
ambient temperature range specified.

Connection
The transmitters should be connected to the controller using 0.5 to 2.5mm2 cable. The units require a minimum of five
wires (power, 0V Supply, RH output, Temperature output and 0V Signal) for all operations. The use of shielded cable is
optional but recommended for the highest noise immunity. Do not route signal wires in the same conduit with power
cables as signal degradation may occur. The controller Analogue Input (AI) must be selected to match the transmitter
output before power is applied. The AI type must be a high impedance voltage input for use with 0-10Vdc transmitters,
or a current input with between 250 and 500 ohm impedance. See the connection diagram for more details.

Remove power to the transmitter before changing between voltage and current output signal types. Ensure the wiring
is correct for the selected output signal type. Use caution when changing jumper positions as not to damage the circuit
board, any components or the sensing elements. The unit comes factory set for current output. To change the output
signal to voltage, carefully remove the 2-position shorting jumper and replace it in the ‘VOLTAGE’ position. Place the
3-position shorting jumper in the correct position for the required span.

Issue 1.0 (08/08/11) Annicom Ltd Page 2 of 3


Unit 21, Highview, Bordon,Hampshire. GU35 0AX.
Tel: +44(0)1420 487788 Fax: +44(0)1420 487799
Email: [email protected]
www.annicom.com

© Copyright Annicom 2011. All rights reserved.


AX-RHT-x3-x
RH & T Transmitter – Duct, Room and Outside-Air

DUCT & OUTSIDE-AIR ROOM Tx CONNECTIONS


Tx CONNECTIONS
OUTPUT RANGE SELECT
(0-5,0-10,4-20)
RH TEMP.

TEMP.

OUTPUT TYPE I V
SELECT(I,V)

RH I V

RH TEMP. RH TEMP.
OUTPUT TYPE OUTPUT RANGE
SELECT (I,V) SELECT
(4-20,0-10,0-5)
TEMPERATURE
REL.HUMIDITY
0V SIGNAL

THERMISTOR
THERMISTOR
0V SUPPLY
24V SUPPLY

OPTION -IF FITTED

1. For the Duct unit, select a location in the duct where dust & contaminants are at a minimum (i.e. after filters
etc.) and which will give a representative sample of the prevailing air condition. Drill a 13mm (up to 15mm)
diameter hole in the return air duct. Insert probe through the hole and secure the enclosure to the duct with
suitable sheet metal screws on 92mm centres. Orientation of the enclosure and probe will have no effect on the
operation of the device.
2. For the Outside-Air unit, orient the housing such that the cable gland is pointing downwards. Fit the housing
to the mounting surface using suitable screws on 92mm centres.
3. Ensure that the supply voltage is within the specified tolerances.
4. Allow 3 minutes before checking functionality, and allow a further 30 minutes before carrying out pre-
commissioning checks.
5. Chemical vapours at high concentration in combination with long exposure times will offset the sensor
reading. This includes transportation before installation.

Every effort has been taken in the production of this datasheet to ensure accuracy. Axio do not accept responsibility for
any damage, expense, injury, loss or consequential loss resulting from any errors or omissions. Axio has a policy of
continuous improvement and reserves the right to change this specification without notice.