Generic PLL-Based Grid-Forming Control
Generic PLL-Based Grid-Forming Control
Letters
Generic PLL-Based Grid-Forming Control
Lennart Harnefors , Fellow, IEEE, Mario Schweizer , Member, IEEE, Jarno Kukkola ,
Mikko Routimo , Member, IEEE, Marko Hinkkanen , Senior Member, IEEE,
and Xiongfei Wang , Senior Member, IEEE
Abstract—In grid-forming control, the swing equation of a syn- applied [4]. During normal operation, the PLL can be disengaged
chronous machine is emulated by a power controller. Thereby, and the PC solely be relied upon.
frequency droop, power-oscillation damping, and/or virtual inertia Unfortunately, as a consequence, during current limitation,
can be obtained. In this letter, it is shown that a phase-locked
loop—which is normally grid following—can be designed so as an ON/OFF chattering behavior of the PLL may occur. One way
to, in turn, emulate a generic power controller, thus, becoming of preventing this would be somehow to make the PLL fulfill
grid-forming. Property 2, allowing the PC to be eliminated, thus, simplifying
Index Terms—Grid-connected converters, grid-forming control, the structure of the SC. Steps in that direction have been taken. A
phase-locked loops, voltage-source converters. PLL in [5] is shown to have structural similarities to the swing
equation, and can reproduce certain characteristics thereof if
tuned properly [6], [7].
I. INTRODUCTION The contribution of this letter—in relation to prior art, where
RID-FORMING control of a voltage-source converter has certain special cases are considered—is the design of a PLL-
G two fundamental properties.
r Property 1: The back electromotive force of a synchronous
based grid-forming control (PLL-GFC) scheme that emulates a
generic PC.1 See Section III. The emulation is not exact, but the
machine is emulated, giving a stiff converter voltage. accuracy is sufficient as seen from the fairly slow time scale of
r Property 2: The swing equation of a synchronous ma- grid-frequency variations. Thus, Property 2 is fulfilled. Design
chine is emulated, giving an active-power response to for PSC correspondence, fulfilling also Property 1, is considered
grid-frequency variations. in Section IV. (The design in Section IV summarizes the key
Schemes based on vector current control are normally grid- results of [1], but PC emulation by the PLL is not considered
following. Yet, in [1], it is shown that Property 1 can be fulfilled in [1].) Experimental evaluation with performance comparison
by a vector-current-control scheme, designed for correspon- of PLL-GFC and PSC is made in Section V.
dence to power-synchronization control (PSC).
Property 2 is, in conventional PSC, fulfilled by a power II. PRELIMINARIES
controller (PC) [2]. In [1], a hybrid synchronization controller
Boldface letters denote the complex space vectors. The super-
(SC) is proposed, where the PC is combined with a phase-locked
script s denotes a vector referred to the stationary αβ reference
loop (PLL). A similar scheme is suggested in [3]. In PSC, the
frame. The corresponding vector referred to the synchronous
PLL is needed for synchronization at startup [2] as well as to
dq reference frame, which has angle θ as reference, is denoted
prevent loss of synchronism when converter-current limitation is
without a superscript. Italic letters denote the scalar variables and
real transfer functions. The reference for a controlled variable is
Manuscript received June 2, 2021; revised July 12, 2021; accepted August
11, 2021. Date of publication August 19, 2021; date of current version October denoted by appending the sub- or superscript ref. The Laplace
15, 2021. This work was supported in part by ABB. (Corresponding author: variable s is to be considered as the operator s = d/dt, where
Lennart Harnefors.) appropriate.
Lennart Harnefors is with the ABB AB, Corporate Research, 722 26 Västerås,
Sweden (e-mail: [email protected]). Fig. 1 illustrates the main circuit and the controller block
Mario Schweizer is with the ABB Switzerland Ltd., Corporate Research, 5405 diagram. The former consists of an inductor, with inductance
Baden-Dättwil, Switzerland (e-mail: [email protected]). L and inner resistance R, between the converter and point-of-
Jarno Kukkola and Marko Hinkkanen are with the Department of Electrical
Engineering and Automation, Aalto University, 02150 Espoo, Finland (e-mail: common-coupling (PCC) buses. The respective voltage vectors
[email protected]; [email protected]). are vs and Es , whereas the output current is is . The active output
Mikko Routimo is with the ABB Oy Drives, 00380 Helsinki, Finland (e-mail:
[email protected]).
Xiongfei Wang is with the Department of Energy Technology, Aalborg
University, 9100 Aalborg, Denmark (e-mail: [email protected]). 1 Important special cases of the generic PC are pure proportional, giving
Color versions of one or more figures in this article are available at frequency droop; proportional–integral, giving power-oscillation damping and
https://doi.org/10.1109/TPEL.2021.3106045. virtual inertia; and lead–lag, giving frequency droop, power-oscillation damping,
Digital Object Identifier 10.1109/TPEL.2021.3106045 and virtual inertia [8].
0885-8993 © 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See https://www.ieee.org/publications/rights/index.html for more information.
Authorized licensed use limited to: Seoul National University. Downloaded on June 30,2024 at 08:12:31 UTC from IEEE Xplore. Restrictions apply.
1202 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 37, NO. 2, FEBRUARY 2022
Fig. 1. Circuit and controller block diagram. Fig. 3. Generalized AVC with current-reference selection and SAT.
Authorized licensed use limited to: Seoul National University. Downloaded on June 30,2024 at 08:12:31 UTC from IEEE Xplore. Restrictions apply.
IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 37, NO. 2, FEBRUARY 2022 1203
TABLE II
EXPERIMENTAL SETUP DATA
TABLE I
CONTROLLER SELECTIONS
Authorized licensed use limited to: Seoul National University. Downloaded on June 30,2024 at 08:12:31 UTC from IEEE Xplore. Restrictions apply.
1204 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 37, NO. 2, FEBRUARY 2022
VI. CONCLUSION
Previous findings concerning the similarity between a PLL
and the swing equation of a synchronous machine were general-
ized. The scheme PLL-GFC results, where the PLL is designed
to emulate a generic PC, fulfilling Property 2. Design for PSC
correspondence was considered, fulfilling also Property 1.
Experimental comparison of PLL-GFC and PSC showed
near-identical performance. The most notable difference is that,
in PLL-GFC, transients in P are reflected by transients in Eq
(and vice versa). This is caused by the coupling from Eq to iref
d ,
with gain Ba , introduced to fulfill Property 2. The transients in
Eq diminish as Ba is increased.
REFERENCES
[1] L. Harnefors, J. Kukkola, M. Routimo, M. Hinkkanen, and X.
Wang, “A universal controller for grid-connected voltage-source con-
verters,” IEEE J. Emer. Sel. Top. Power Electron., early access,
doi: 10.1109/JESTPE.2020.3039407.
[2] L. Zhang, L. Harnefors, and H.-P. Nee, “Power-synchronization control
Fig. 6. Islanded operation with load-resistance step.
of grid-connected voltage-source converters,” IEEE Trans. Power Syst.,
vol. 25, no. 2, pp. 809–920, May 2010.
[3] L. Huang, H. Xin, Z. Wang, L. Zhang, K. Wu, and J. Hu, “Transient stability
PSC and PLL-GFC deviate transiently. This is because the PLL analysis and control design of droop-controlled voltage source converters
emulation of the PC is not exact. Yet, the active-power responses considering current limitation,” IEEE Trans. Smart Grid, vol. 10, no. 1,
pp. 578–591, Jan. 2019.
are virtually identical, showing that the quasi-stationary design [4] L. Harnefors, “Method and control system for controlling a voltage source
principle in Section III is relevant. converter using power-synchronisation control,” Patent EP 3 534 522 B1.
The experimental setup unfortunately does not facilitate mul- [5] X. Wang, M. G. Taul, H. Wu, Y. Liao, F. Blaabjerg, and L. Harnefors,
“Grid-synchronization stability of converter-based resources-an overview,”
tiple converters. To show that PLL-GFC has the capability of IEEE Open J. Ind. Appl., vol. 1, pp. 115–134, 2020.
islanded operation with multiple converters, the experimental [6] H. Alatrash, A. Mensah, E. Mark, G. Haddad, and J. Enslin, “Generator
setup is replicated in Simulink, but with two converters (I and emulation controls for photovoltaic inverters,” IEEE Trans. Smart Grid,
vol. 3, no. 2, pp. 996–1011, Jun. 2012.
II) connected in parallel at the PCC. The converters and their [7] M. Zhang, X. Yuan, and J. Hu, “Inertia and primary frequency provisions
controls are identical, but to introduce an asymmetry, they have of PLL-synchronized VSC HVDC when attached to islanded ac system,”
slightly different filter inductances: LI = 1.1 L and LII = 0.9 L. IEEE Trans. Power Syst., vol. 33, no. 4, pp. 4179–4188, Jul. 2018.
[8] W. Zhang et al., “Comparison of different power loop controllers for
As can be observed in Fig. 7, the converters share the load power synchronous power controlled grid-interactive converters,” in Proc. IEEE
equally. In fact, the curves (for voltage, Eq only) replicate the Energy Conv. Congr. Expos., Montreal, 2015, pp. 3780–3787.
Authorized licensed use limited to: Seoul National University. Downloaded on June 30,2024 at 08:12:31 UTC from IEEE Xplore. Restrictions apply.