EOOW Orals Electrical Knowledge
EOOW Orals Electrical Knowledge
uk
www.officerofthewatch.co.uk
MCA EOOW Orals
Examination
Revision: Electrical
Knowledge
www.officerofthewatch.co.uk
1: What is Reverse Power Protection for?
Generators intended to operate in Parallel must have a Reverse Power Protection Trip. A
Reverse Power Relay monitors the direction of power flowing between the Generator and
the Switchboard.
If a Prime Mover Failure occurred the Generator would act as a Motor. The Reverse
Power Relay detects this fault and acts to trip the Generator Circuit Breaker.
Where a slow moving high inertia load is involved the starting time must be considered
because of the heating effect of the starting current and in this case a Star/Delta Starter
would be used.
The Star/Delta Starter first connects the Starter Windings in Star and when running
changes over to Delta. The Star connection results in about 58% Line Voltage being
applied to each Phase with therefore a reduction in Starting Current. The Starting Torque
is also reduced to about 1/3 of its direct on-line valve.
Most A C Motors on Ships are of the Induction or Squirrel Cage Motor types, the
principle of operation for which is as follows: The Starter is made up of three separately
phased Windings, to which a 3-phase supply is connected. The Rotor has a series of
Copper Conductors along its Axis, which are joined by rings at the ends to form a Cage.
When the motor is started, the Rotating Magnetic Field induces an E M F in the Cage and
thus a Current Flow. The Current carrying Conductor in a Magnetic Field produces the
Motor effect, which turns the Rotor. The Motor Speed builds up to a value just less than
the Speed of Rotation of the Magnetic Field. The Motor Speed depends upon the E M F
induced in the Rotor and this depends upon the difference in Speed between the
Conductors and the Magnetic Field.
A number of different Fixed Speeds are possible by changing the number of Poles
(Conductors).
Hydrogen.
www.officerofthewatch.co.uk
6: What is meant by Preference Tripping?
Single Phasing can be caused when one of the three back up fuses blows or if one of the
contactor contacts is in open circuit.
Insulation Resistance must be kept above at least 1MW, the higher the Insulation
Resistance the better. Companies have their own Regulations, but most Companies only
allow readings above 5MOhms.
9: What are the two Main Types of Battery commonly used on board Ships?
Over Current
Under Voltage
Reverse Power.
Ex'p' = Pressurisation.
This is where Equipment is Pressurised to prevent any gases entering Equipment.
www.officerofthewatch.co.uk
13: What are the Advantages and Disadvantages of Alkaline Batteries?
The Advantages of Alkaline Batteries are that they retain charge on open circuit and even
if discharged, it can be left for long periods without adverse effect.
The Disadvantages are that they require a greater number of cells to produce a particular
Voltage. They are also more expensive than Lead Acid Batteries.
This is an enclosure that will withstand an Internal Explosion of Flammable Gas within
itself and dissipate heat from that explosion before reaching outside atmosphere, which
could ignite the gas in surrounding atmosphere, i.e. a Ship's Battery Locker could be
classed as Ex'd'.
16: What is done to ensure the Emergency Generator is Always Available and
Will Start?
The System should be checked regularly and operated weekly to ensure it's availability if
required. Fuel tanks should be kept full, ample cooling water in radiator cooling system
and starting equipment should be functional, i.e. batteries should be fully charged or air
receivers full
Load Sharing is the equal balance of loads between Generators irrespective of Load
Changes.
www.officerofthewatch.co.uk
19: What is the Function of a Fuse?
The function of a Fuse is to give Short-circuit Protection and also Overload Protection
and operates in milliseconds.
20: How would you go about finding an Earth Fault in the System?
Finding an Earth Fault would be by the process of elimination i.e. circuit breakers would
be opened and closed until earth fault disappeared, taking care which breakers were being
opened and closed as they maybe supply essential loads at the time. It would be good
practice to start with places such as the Galley and Laundry where faults are common.
The Emergency Generator is located remotely from the Engine Room, usually on the
Accommodation Deck or at Weather Deck Level or above.
The purpose of the Over Current Protection is to Trip the Generator in Overload
situations. The Trip is usually set at 150% Operating Capacity and has a time delay of
usually 20 seconds. This allows for short periods of Overload Currents. It also protects
against a Short Circuit in the Generator.
An Under Voltage Trip is fitted to all Generator Breakers. Its main function is to Trip the
Breaker when severe Voltage Dip (around 50%) occurs. The Under Voltage Trip on a
Generator Circuit Breaker also prevents it being closed when the Generator Voltage is
very low or absent.
The Circuit Breaker is an Isolating Switch that also acts as a Fuse. It has two designed
ratings; one of normal safe working current, and the other against overload, which may
also have a time delay.
www.officerofthewatch.co.uk
25: When working on Batteries, what precautions should be taken?
Ensure the space is well ventilated, do not smoke or use naked lights and also wear
protective clothing such as apron, gloves and face shield.
The Speed of both Machines must be the Same i.e. the Frequency and the Voltages must
be the Same and in Phase.
First raise the alarm then isolate or switch off the current.
If this is not possible, pull or push the victim away from the source, taking care not to
make electrical contact with the victim or the electrical source, i.e. use something non-
conductive.
Once the victim has been removed from the electrical source, if the breathing is feeble or
ceased, artificial respiration should be started at once. Delay in starting artificial
respiration can prove fatal.
Note: If artificial respiration is started at once, 70% of the victims recover. If there is 3
(three) minutes delay, only 20% of victims recover.
They are used for supplying essential power to: Radio Equipment, Telephone Exchange,
Fire Detection, General Alarm Circuits, etc. These Systems are often supplied from two
sets of batteries worked on a regular charge/discharge cycle.
They are also used as Emergency Supplies, i.e. for Emergency Generator Start-up and
Emergency Lighting. Being used in this case in a "stand-by" role to give power when
Main Supplies fail.
www.officerofthewatch.co.uk
30: Give reasons why Protection Equipment is essential in an Electrical
Distribution System.
To disconnect and isolate faulty equipment in order to maintain the power supply
to the remaining healthy circuits in the system.
To prevent damage to equipment from the thermal and magnetic forces that occur
during short circuit and overload faults.
To protect personnel from electric shock.
This is the ability of a Protection System to disconnect only Faulty Circuits and to
maintain the Electrical Supplies to Healthy ones.
Discrimination is achieved by co-ordinating the Current Ratings and the Time Settings of
the Fuses and Over-current Relays used between the Generator and the Load.
The Devices nearest the Load having the lowest Current Rating and shortest Operating
Time; those nearest the Generator having the highest Current Rating and longest
Operating Time.
i.e. a Motor Fault on a Centrifugal Pump would not cause the Generator Breaker to Trip.
www.officerofthewatch.co.uk
32: Draw and explain how Earth Lamps works.
A direct earth on one pole will short circuit it's lamp, causing the other two to shine
brightly.
Single Phasing is where one of the 3-phase's supplying the Motor becomes disconnected.
The Motor will continue to run if this happens and can result in Motor Burnout. The
effect of Single Phasing is to increase the Current in the two remaining Lines and cause
the Motor to become very noisy due to uneven Torque produced.
First the Standby Generator set would start up and automatically put itself on the Board.
If this did not happen, the Ship would "Black Out" and after a time delay, usually 30
seconds, the Emergency Generator would start up and supply the Emergency
Switchboard, which supplies essential equipment.
www.officerofthewatch.co.uk
35: Describe how Synchronising Lamps are used to Parallel a Generator.
This is normally used as a back-up or alternative way to the Synchroscope, the Lamps are
connected between the Incoming Generator and the Bus-bars. The "Sequence Method" is
the preferred one as it displays a rotation of Lamp Brightness, which indicates, whether
the incoming machine is running fast (clockwise) or slow (anti clockwise). As with the
Synchroscope, the Lamp Sequence must appear to rotate slowly clockwise. Correct
synchronisation occurs when the top or "Key" lamp is dark and the two bottom lamps are
equally bright.
The Electrical Power Supply must be from two widely separate supplies i.e. one from the
Main Switchboard and the other from the Emergency Board.
Electrical leads and fuses are to allow 100% overload, giving only short circuit
protection.
If failure does occur on one system, the stand-by system will cut in within 45 seconds.
The Steering Motors will have sequential starting.
38: Why do you require Earth Lamps on 220V Distribution Board when you
have them on the Main Switchboard?
You require Earth Lamps on the 220V Distribution Board as well as the Main Board, due
to the air gap in step down transformer, i.e. 440V Earth Lamps can not detect Earth on
220V systems due to the gap.
www.officerofthewatch.co.uk
39: Explain how the Emergency Generator starts up in the Event of Total Power
Failure.
40: How would you go about finding an Earth Fault in the System?
Finding an Earth Fault would be by the process of elimination i.e. circuit breakers would
be opened and closed until earth fault disappeared, taking care which breakers were being
opened and closed as they maybe supply essential loads at the time. It would be good
practice to start with places such as the Galley and Laundry where faults are common.
www.officerofthewatch.co.uk