1 2 3 4 5 6 7 8 9 10 11 12

TN PN
90
DOMINANT WIND
A B C D E F G
36000
22.96118 6000 6000 6000 6000 6000 6000
PLANT 0 180
A NORTH A
PN. 361.000 PN. 309.500
TRUE PE. 798.500 MATCHLINE TO DWG. NO. MS-DD-4200-ELE-DWG-0503 PE. 798.500
NORTH SECONDARY
WIND
270 EARTHING WIRE AIR TERMINAL
REF
EQUIPMENT TAG EQUIPMENT DESCRIPTION SIZE (SQMM)
NO.
PER CONNECTION
0 T1 4200-XFR-1101 33/6.9kV MAIN TRANSFORMER PE:95 THIS DRAWING
E07T*2
T2 4200-XFR-2101 6.6/0.42kV TRANSFORMER PE:185 185
T3 4200-XFR-2102 6.6/0.42kV TRANSFORMER PE:185
0
FIREWALL TEST BOX KEY PLAN
T4 4200-XFR-2103 6.6/0.42kV TRANSFORMER PE:185 35 35
APPROX.
300mm

EARTH BAR E08C


T5 4200-XFR-2104 6.6/0.42kV TRANSFORMER PE:185 NOTES:
EARTH BAR PE:95 0 TO LIGHTNING ROD
EARTH BAR NEUTRAL EARTHING RESISTOR FGL
B T6 4200-NER-1101 NER:1C-185 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE MENTIONED. B
EARTH BAR FOR 4200-XFR-1101 3.6/6(7.2)kV E09A ALL LEVELS AND COORDINATES ARE IN METERS.
E14A

APPROX.
SECTION "A" ELEVATION FOR MANYAR SMELTER PROJECT ARE BASED ON “PLANT

300mm
APPROX.

APPROX.
EARTH BAR
500mm

500mm
ELEVATION AS FOLLOWS”:
SCALE: NTS
PTFI DATUM = EL +0.000
E01A E01A E01A E01A MEAN SEA LEVEL = EL +1.420
G.L. G.L. P1 = EL +3.500
E08F*4 E08F*4 E08F*4 E08F*4
EARTHING EARTHING H.P. = EL +4.450
WIRE WIRE 4200-EP-002 4200-EP-003 L.P.= EL +4.000
E07T E07T 4200-EP-004 4200-EP-005 E08A T1
CONCRETE TO MAIN CONCRETE TO MAIN 185 185 185 2. THE EARTHING WIRES SHALL BE STRANDED COPPER WITH GREEN AND
STRUCTURE EARTH LOOP STRUCTURE EARTH LOOP YELLOW STRIPE PVC INSULATION FOR ABOVE GRADE USE AND
35 35
E09A STRANDED BARE COPPER WIRE FOR UNDERGROUND USE. ALL
DETAIL "A" DETAIL "B" E08C E14A UNDERGROUND WIRES SHALL BE BARE STRANDED COPPER FOR THE
GROUND GRID.
35 185
SCALE: NTS SCALE: NTS 185 185 185 185
A
0501
N
E08A 3. THE CONNECTION BETWEEN MAIN EARTHING LOOP AND BRANCH
EARTHING WIRE SHALL BE BY EXOTHERMIC WELDING FOR
MATCHLINE TO DWG. NO. MS-DD-4200-ELE-DWG-0503
C C
E08F UNDERGROUND AND C-TYPE COMPRESSION CONNECTOR FOR ABOVE

MATCHLINE TO DWG. NO. MS-DD-4200-ELE-DWG-0508


T2 GRADE CONNECTIONS.
T3 E08F T4 E08F T5 E08F E08F 1C-185 3.6/6(7.2)kV 4. EARTHING AND BONDING OF CABLE GLAND PLATE, LADDER CABLE TRAY
E08F E08F E08F E08F AND PERFORATED CABLE TRAY SHALL BE REFERRED TO TYPICAL
EARTHING WIRE
REF 185 DRAWING LISTED IN INSTALLATION DETAIL FOR EARTHING WIRING -
EQUIPMENT TAG EQUIPMENT DESCRIPTION SIZE (SQMM) E03A*2
NO. INDEX, DOC. NO. MS-DD-3000-ELE-STA-0004.
PER CONNECTION E08A*3 E08A*2
N N N N E08C*4
E1 4200-SWG-2101 6.6kV MEDIUM VOLTAGE SWITCHGEAR PE:95 4200-PE-009
0 E08F E08F E08F E08F E08D*4 5. EARTHING WIRE SHALL BE INSTALLED DIRECTLY IN THE GROUND AT
SEE DETAIL "A"
E2 4200-MCC-5101 400V MCC PANEL PE:185 E08F*2 E01A MINIMUM DEPTH OF 450MM BELOW GRADE WHERE UNPROTECTED. THE
E14A*2 T6 95 E08F*4 MINIMUM DEPTH MAY BE REDUCED TO 300MM WHERE PROTECTED BY
E3 4200-MCC-5102 400V MCC PANEL PE:185 E14A
16 E08F CONCRETE SLAB.
E4 4200-MCC-5103 400V MCC PANEL PE:185 16 16 16 16
PIPE SLEEVE E14A PIPE SLEEVE E14A PIPE SLEEVE E14A PIPE SLEEVE E14A 4200-EP-006 E07P
E5 4200-MCC-5104 400V MCC PANEL PE:185 E08D 70 E01A
E07P E08D E08D E08D E08D 6. FOR SUBSTATION LIGHTNING PROTECTION REFER TO E-HOUSE
E6 4215-ELP-0001A-MCC WET ESP 1 FIRST STAGE PANEL PE:95 E08F*3 LIGHTNING PROTECTION AND EARTHING DRAWING (4200-SUB-0001), DWG
E01A 4200-PE-007 16
E7 4215-ELP-0001B-MCC WET ESP 2 FIRST STAGE PANEL PE:95 185 4200-PE-008 185 NO. MS-DD-SIE07-ELE-DWG-0019.
D E08F*3 SEE DETAIL "B" E08D E08D E08D PIPE SLEEVE D
E8 4215-ELP-0001C-MCC WET ESP 3 FIRST STAGE PANEL PE:95 SEE DETAIL "B" 185
E9 4215-ELP-0002A-MCC WET ESP 4 FIRST STAGE PANEL PE:95 1 PE PE PE E07P 7. EARTH BAR HEIGHT SHALL BE APPROXIMATELY 500MM FROM GROUND
LEVEL.
4200-EP-001 E08D 35 E08D 35 35 E30 E08D E08D 35 35 E08D 4200-EP-007
E10 4215-ELP-0002B-MCC WET ESP 5 FIRST STAGE PANEL PE:95 16 E08C
0 E08C 35 E08C E4 E08C*2 16 E08C*2 35
E11 4200-UPS-5001 AC UPS PE:95 16 8. THE RESISTANCE TO EARTH SHALL NOT EXCEED 25 OHMS FOR
E12 4200-BAT-6001 BATTERY FOR AC UPS PE:35 E03A*3 16 16 E08A
E03A*3
185 185 EXHAUST INDIVIDUAL ROD.
E08D E08C*2 PLENUM
4500

E13 4200-BCH-5001 DC BATTERY CHARGER PE:95 E08D E08A


E07P E08D*8 E08F E08F
E08C*2 9. THE RESISTANCE TO EARTH OF THE TOTAL SYSTEM LOOP WITH ALL
E14 4200-BAT-6002 BATTERY FOR DC BATTERY CHARGER PE:35
E08C E08F*7
E08D*5
AREA EARTH RODS CONNECTED AND EQUIPMENT EARTHING DISCONNECTED
E15 4200-BAT-B-IRP-001 INTERPOSING RELAY PANEL PE:35 185 E14A
E08F*8 SHALL BE LESS THAN 5 OHMS.
E16 4200-PLD-5001 INDOOR LIGHTING PANEL PE:95 16 EARTHING BAR E1 EARTHING BAR
E08F*2 E3 E08F*2 E14A
4200-PE-006 35 (BY VENDOR SCOPE) (BY VENDOR SCOPE)
E17 4200-PLD-5031 INDOOR RECEPTACLE PANEL PE:95 E08D 10. EXPOSED EARTHING WIRE FROM GROUND LEVEL TO 2M ABOVE ARE
E18 4200-PHD-5001 HVAC POWER DISTRIBUTION PANEL (NORMAL) PE:95 2 SEE DETAIL "A" PE
E08D MECHANICALLY PROTECTED BY CONDUIT. ALL EARTHING WIRE FROM
35 EARTHING BAR E08F*2 E2 UNDERGROUND SHALL BE PROTECTED WITH PVC CONDUIT STUB UP.
E19 4200-PHD-5002 HVAC POWER DISTRIBUTION PANEL (EMERGENCY) PE:95
0 185 E03A*2 (BY VENDOR SCOPE) 16 E08F*2
E20 4215-VSD-0001 VSD PANEL FOR 4215-FAN-0001-VS EMERGENCY FAN PE:95 E08A*3
E08C 11. EARTH ROD/PIT SHOULD BE DRIVEN BELOW THE GROUND AWAY FROM
E21 4221-VSD-0002A VSD PANEL FOR 4221-PUM-0002A-VS IAT ACID PUMP PE:95 E08C*2 E6 E7 E8 E9 E10 E25 E26
E E08F*5 E08A*3 THE PILE CAP OR NON-PILED AREA TO AVOID OBSTRUCTION / E
E22 4221-VSD-0002B VSD PANEL FOR 4221-PUM-0002B -VS IAT ACID PUMP PE:95 E08F*6
E14A INTERFERENCE.
E23 4221-VSD-0001-2 VSD PANEL FOR 4221-PUM-0001-VS DT ACID PUMP PE:95 E20
16500

6000

35
E24 4221-VSD-0008 VSD PANEL FOR 4221-PUM-0008-VS FAT ACID PUMP PE:95 E07T 12. FOR EARTHING CABLE ROUTING ON CABLE LADDER TRAYS, REFER TO
16 E08D CABLE LADDER TRAY LAYOUT DRAWINGS AND SECTION LIST.
E25 4215-ELP-0003 WET ESP HEATING FIRST STAGE PANEL PE:95 4200-PE-002 E08A E08A E08A E08A*2 E5 E14A
E26 4215-ELP-0004 WET ESP HEATING SECOND STAGE PANEL PE:95 SEE DETAIL "A"
E03A*2 E16 E17 E28 D3 E08C
E08A E29 E15
E27 4200-HLC-0001 HVAC LOCAL CONTROLLER PE:35 E08A*4 E27 E08A*3
0 E08C*6 E18 E19
E28 4200-PLD-5161 INDOOR SMALL POWER PANEL FOR 4200-SUB-0001 PE:95 E21 E22 E23 E24
E08D*2 E08A*2 PE DETAIL NO. AS INDICATED:
E29 4200-PLD-5162 OUTDOOR SMALL POWER PANEL FOR 4200-SUB-0001 PE:95 4200-FE-001
E14A E14A E08C
E30 4200-SWG-2101-SM EDG SYNCHRONIZATION MODULE PE:35 3 E08C C1 PE
E08C
E08C*3
FE
PE
185
E07P
E99X*9
C1 4200-B-PDPU-001 PDP UPS PE:95 95 E08C*4 4200-PE-003 E03A E08A
35 E08A 4200-PE-005 -QUANTITY
C2 4200-B-PDPN-001 0 PDP NON UPS PE:95 0 16 C2 E03B E03A*2 SEE DETAIL "A" E08A*5
-IF NOT INDICATED, QUANTITY SHALL BE ONE (1)
E08D PE PE PE E08A PE PE PE PE E08A*6 E08C E08D
C3 4200-B-EWS-001 PCS THIN CLIENT DESK - -MTO CODE
FE FE FE E08C*2 E08F*3
E07T
E08C*3 E08C*7 E08C*4 FE FE FE FE
E13 E14
-E99X REPRESENTS TYPICAL INSTALLATION DETAIL NUMBER
C4 4200-B-PLC-006 PLC PANEL FOR PACKAGE MAIN BLOWER-1A PE:35 FE:35 E08D*2 E14A
F C22 C23 C24 E14A C4 C5 C20 C21 E08F*3
SAFETY EQUIPMENT F
C5 4200-B-PLC-007 PLC PANEL FOR PACKAGE MAIN BLOWER-2A PE:35 FE:35
6000

C6 4200-B-OFP-001 FO PATCH PANEL PE:35 E08C C8 C12 E14A E08A E08C E08C E08C SPACE
E08C E08D E08C*6 185 0
C7 4200-B-OFP-002 FO PATCH PANEL PE:35 16 FE FE FE FE FE FE
C8 4200-B-NC-001 NETWORK CABINET 0 PE:35 FE:35
E08C*3 PE PE PE PE PE PE PE PE E12A E12B E12C EYE-WASH FACILITY
C16 95 E11
C9 - - E08C*10
35 35 C6 C7 C10 C13 C14 C12 E08C
C10 4200-B-PCS-001 AS CABINET PE:35 FE:35 PE 16 16 35 35
16 35 16 16 16 35 16 16
C11 4200-B-FAP-001 FIRE ALARM PANEL PE:35 E08C FE 16
CHEMICAL
C12 4200-COM-5101 SCADA PANEL PE:35 FE:35 4 FILTER UNIT E08D C11 C3 C18 C19
PE

95 95
FE PE

E08C 95 95 E08D 185 E08D*2 185 E08C*2 E08D E08D*2


C13 4200-LAN-5001 TELECOM CABINET (LAN/TELEPHONE) PE:35 FE:35
C14 4200-PAS-5001 TELECOM CABINET (PAGA) PE:35 FE:35 185 4200-PE-001 185
95 E01A E03B E03A*2 E01A
TELECOM CABINET E07R SEE DETAIL "B" E07R*4 E07P E07P
C15 4850-TEL-5001 PE:35 FE:35 E08F*3 E08A E08A*2 E08F*3
E08D*2 E03A*3 4200-FE-002
(SECURITY SYSTEM AND CCTV) E08A E08C*7 4200-PE-004 E08C*6
4200-EP-009
E08A*1
SEE DETAIL "B" 95 95 4200-EP-008
0
TELECOM CABINET E08C*16 E14A E08D*3
C16 4850-ISC-5001 PE:35 FE:35
(ACCESS INTELLIGENT CONTROLLER)
PN. 361.000
E08D*3 E08F
E14A PN. 309.500
FOR CONSTRUCTION
G C17 - - E14A G
C18 4200-PDB-5001 TELECOM PDP - UPS PE:95 0 PE. 759.000
MATCHLINE TO DWG. NO. MS-DD-4200-ELE-DWG-0503 PE. 759.000

C19 4200-PDB-5002 TELECOM PDP - NON UPS PE:95


5 0 5 10
C20 4200-B-PLC-008 PLC PANEL FOR PACKAGE LUREC BLOWER-1A PE:35 FE:35
C21 4200-B-PLC-009 PLC PANEL FOR PACKAGE LUREC BLOWER-1B PE:35 FE:35
C22 4200-B-PLC-010 PLC PANEL FOR PACKAGE PREHEATER PE:35 FE:35 SCALE 1 : 100 ( METERS )
C23 4200-B-PLC-011 PLC PANEL FOR PACKAGE PREHEATER PE:35 FE:35
C24 4200-B-PLC-012 PLC PANEL FOR PACKAGE BURNER PE:35 FE:35 0 MS-DD-4200-ENG-PP-0001 AREA PLOT PLAN ACID PLANT COMMON GAS CLEANING ALL RIGHTS RESERVED
PROJECT
D3 - SPACE DESK/CHAIR
0
MS-DD-4200-ELE-DWG-0281~0287 CABLE TRAY LAYOUT / SECTION DRAWING - GAS CLEANING AND ACID PLANT SUBSTATION (1)~(7)
THIS DOCUMENT WAS PREPARED FOR THE EXCLUSIVE USE OF PT FREEPORT INDONESIA (PTFI) AND CHIYODA GROUP
PURSUANT TO THE ENGINEERING, PROCUREMENT AND CONSTRUCTION AGREEMENT BETWEEN PTFI AND PT
MS PROJECT
CHIYODA INTERNATIONAL INDONESIA. THIS DOCUMENT IS THE PROPERTY OF PTFI, AND THIS DOCUMENT, DATA AND
MS-DD-4200-ELE-LST-0271 SECTION LIST FOR ABOVE ROUTE - GAS CLEANING AND ACID PLANT SUBSTATION INFORMATION MAY BE DISCLOSED TO THIRD PARTIES ONLY FOR THE MANYAR SMELTER PROJECT. CHIYODA GROUP TITLE
SHALL NOT BE LIABLE FOR USE OR RELIANCE ON THIS DRAWING BY ANY THIRD PARTY NOT UNDER THE DIRECTION
OF CHIYODA GROUP, UNLESS OTHERWISE AGREED IN WRITING.
MS-DD-4200-ELE-DWG-0101 SUBSTATION EQUIPMENT LAYOUT - GAS CLEANING AND ACID PLANT SUBSTATION (4200-SUB-0001)
0 MS-DD-3700-ELE-STA-0401 / 405~418 TYPICAL INSTALLATION DETAIL FOR EARTHING DRAWN CHECKED APPROVED DATE EARTHING LAYOUT DRAWING -
MS-DD-3000-ICS-DWG-0021 INSTRUMENT EARTHING PHILOSOPHY
H
MS-DD-3000-ELE-STA-0618 ELECTRICAL STANDARD SYMBOL LEGEND - WIRING LAYOUT A. BONSAY K. SHINAGAWA/ T. KUBO AUG. 01, 2022 GAS CLEANING AND ACID PLANT H
D. NARISHIGE
MS-DD-3000-ELE-STA-0612 ELECTRICAL STANDARD SYMBOL LEGEND - PLOT LAYOUT - LIGHTING & EARTHING SUBSTATION
A. BONSAY
K. SHINAGAWA/
T. KUBO AUG. 01, 2022 ISSUED FOR CONSTRUCTION MS-DD-3000-ELE-STA-0004 / 401~419 TYPICAL INSTALLATION DETAIL FOR EARTHING WIRING JOB NO. SIZE SCALE
0 D. NARISHIGE 0
A. BONSAY
K. SHINAGAWA/
T. KUBO JAN. 07, 2022 ISSUED FOR OWNER APPROVAL MS-DD-3000-ELE-SPE-0022 CONSTRUCTION SPECIFICATION FOR ELECTRICAL ANX17 A1 1 : 100
E D. NARISHIGE
K. SHINAGAWA/ VENDOR DRAWING NO. REV. DRAWING NO. REV.
A A. BONSAY D. NARISHIGE T. KUBO DEC. 03, 2021 ISSUED FOR INTERNAL REVIEW MS-DD-3000-ELE-SPE-0001 GENERAL SPECIFICATION FOR ELECTRICAL
NO. DRAWN CHECKED APPROVED DATE DESCRIPTION DWG NO. REFERENCE DRAWINGS MS-DD-4200-ELE-DWG-0501 0