Characteristics and Suppression of Secondary Arc On 500 KV Transmission Lines For Single Pole Reclosure Purposes
Characteristics and Suppression of Secondary Arc On 500 KV Transmission Lines For Single Pole Reclosure Purposes
Abstract— Single phase to ground faults are the most Nowadays, there are many auto-reclosure failures in the
frequent problem in the extra high voltage overhead lines, and Java-Bali system due to secondary arc. The electrical utility
are temporary in most cases. This type of fault can be quickly company, PLN, has considered about using shunt reactor
eliminated using a single pole reclosure, but secondary arc with neutral reactor in order to solve this problem. But they
phenomenon often makes the reclosure fail to work. This study
haven’t found a good way to determine the optimum
aimed to obtain the characteristics of the secondary arc on the
500 kV transmission lines as well as obtain a solution to inductance, and since the loadings of EHV lines are usually
minimize the amplitude of secondary arc on both transposed high, the use of shunt reactor is less favored because it
and untransposed lines, so that the reclosure can work worsens voltage profiles of the lines. From those situation, a
properly and the system maintains its stability. The effect of new idea to suppress secondary arc current is considered,
high speed grounding speed and neutral reactor attachment at that is how if we use either high speed grounding switch or
neutral of shunt reactors on minimizing secondary arc and a switched shunt reactor, which would be connected to the
possibility to activate shunt reactor only during dead time are lines only during the dead time period of single phase auto
analyzed in this study. reclosure. Those ideas were simulated by using ATP-Draw, a
well-known graphical processor to ATP-EMTP.
interphase capacitances are transformed to wye-connection. real sets to find secondary arc magnitude. When the switch f
Then, each sequence voltage is applied and analyzed. The is closed, secondary arc If will flow, as shown in Figure 3.
results are shown below. The equations below show the magnitude of secondary
arc.
(5)
(1)
And if there are no shunt reactors installed on the lines,
(2) the magnitude is shown below.
(7)
(8)
Fig. 2. Equivalent of Source and Faulted Line Section, Neglecting the c) From both equations above we have:
Series Impedance [4]
(9)
a2E and aE can be expressed in real and imaginary sets of
voltage, and we find the secondary arc using superposition
theorem. The imaginary sets are balanced so they have no So we can install shunt reactors with phase reactance Xp
contribution to the secondary arc. We only need to focus on to compensate a chosen degree of capacitive compensation F
and neutral reactance Xn, which is one third of zero sequence
2
2014 Electrical Power, Electronics, Communications, Controls, and Informatics Seminar (EECCIS)
reactance minus positive sequence reactance. Those are IV. SECONDARY ARC CHARACTERISTICS
shown below. From the simulation performed using ATP-Draw, it is
found that generally secondary arc increases as the length of
(10) the lines increases, and decreases as the relative rotor
angleincreases. The capacitive susceptance increases as the
(11) length of the lines increases. Hence, capacitive coupling
between healthy phase and disturbed phase increases as well,
III. MODELLING OF THE SYSTEM resulting higher secondary arc amplitude.
As the loadings increase, the relative rotor angle
In the simulation, a small system consisting of sending
increases, and the voltage profiles across the lines changes,
end, transmission, and receiving end is modeled.
as shown in Figure 6. In order to derive phasor diagrams in
Figure 6, it is assumed that the lines are modeled as 4 T-
Transmission Lines equivalents. The secondary arc current is calculated by
Sending End Receiving End
applying equation 6 on every T-equivalent circuit.
Es, Er, In Figure 6, we can see that although the voltage
magnitude of the receiving end and sending end are the
same, the relative rotor angle affects the angle difference
Fig. 4. System Modeling among voltages across the lines, thus it affects the magnitude
of secondary arc. Figure 6 is observed with assumption that
Parameters of sending end and receiving end are given in the transmission lines consist of four T equivalents.
Table 1.
(b)
Fig. 5. (a) Effect of Length on Secondary Arc, (b) Effect of Relative
Rotor Angle on Secondary Arc (Phase A, Transposed Single Circuit)
3
2014 Electrical Power, Electronics, Communications, Controls, and Informatics Seminar (EECCIS)
V. SUPPRESSION OF SECONDARY ARC possibly switched only during the fault isolation if the
loadings of the lines are high.
A. Suppression of Secondary Arc on Untransposed
Procedures for calculating the reactance of shunt reactors
Transmission Lines
are developed as shown below.
For both untransposed single and double circuit lines, 1) Find phase to phase and phase to ground capacitive
Suppression can be done using high speed grounding switch susceptances of transmission lines
which will be switched on a moment after isolation of the
(a)
(b)
Time (s)
Fig. 6. Phasor Diagram of Secondary Arc Current and Voltage Across
the Lines (a) = 200, (b) =600 Fig. 8. Secondary Arc Current Consisting of DC Component
disturbed phase [6]. HSGS grounds the fault phase, and it is 2) Calculate zero, positive, and negative sequence of
able to reduce secondary arc current to below 20 A. The capacitive susceptance, BC0 = BCg, BC2 = BC1 = BCg+ 3BCh.
level of suppression is related to HSGS resistance. DC 3) Calculate positive sequence inductive susceptance
component of the current as the effect of switching can be needed for a chosen degree of compensation h. BL1 = h BC1.
minimized by setting the appropriate HSGS delay so that the 4) Minimize phase to phase capacitive susceptance
primary arc has been completely extinguished when the using equation BC1 - BC0 = BL1 - BL0, therefore we obtain BL0
HSGS is switched on. = BC1 (h – 1) + BC0.
In Figure 7, HSGS resistance is assumed to be 0.02Ω and 5) Calculate zero and positive sequence shunt reactance
the arc resistance varies. It should be noted that in reality, arc using equation XL1 = (BL1)-1, and XL0 = (BL0)-1.
resistance consists of arc path resistance, tower impedance, 6) Calculate phase reactance of shunt reactor, Xp= XL1
and grounding impedance. In Figure 8, a small arc resistance
and neutral reactance of shunt reactor Xn= (XL0 – XL1)/3,
is assumed in order to show the transient period, which
should we install the shunt reactors at only one end. If the
would be faster to reach zero with appropriate HSGS delay.
shunt reactors will be installed at both ends, Xp= 2XL1 and
neutral reactance is Xn= 2(XL0 – XL1)/3.
B. Suppression of Secondary Arc on Transposed Single Appropriate selection of neutral reactors with the
Circuit Transmission Lines abovementioned procedure will give optimum suppression of
Shunt reactors are used as both a positive sequence shunt secondary arc, and the AC part of the current can be reduced
compensator and a secondary arc suppressor. They can be to lower than 10 A. In the simulation using ATP Draw, the
4
2014 Electrical Power, Electronics, Communications, Controls, and Informatics Seminar (EECCIS)
result was found as shown in Figure 9. Jose Marty Not only do the transmission lines have phase to ground
transmission lines model was used in the simulation. and interphase susceptances, they also have
intercircuitsusceptances, which consist of intercircuit like
phase and intercircuit unlike phase susceptances. Since we
C. Suppression of Secondary Arc on Transposed Double
have a compensation scheme with only three different
Circuit Transmission Lines
reactances, of course it is impossible to completely
Once again, shunt reactors are used as both a positive compensate four different capacitive susceptances.
sequence compensator and a secondary arc suppressor, but it Therefore we must install capacitors connected among
is more complicated than on the single circuit. Shunt reactos intercircuit like phases in order to make all the
must completely compensate phase to ground, interphase, intercircuitsusceptances balanced so that a complete
and intercircuit capacitive susceptance. The scheme of shunt compensation can be done using scheme in Figure 10.
reactors we are using are shown in Figure 10. The symmetrical components of the capacitive
susceptances are calculated using the equation below.
Fig. 9. Effect of Shunt Rectors on Secondary Arc (Phase A, Transposed
Single Circuit)
For analyzing the symmetrical components of double Fig. 11. Six Symmetrical Components for Analyzing Double Circuits [5]
circuit lines, six symmetrical components are introduced as
With matrix T:
shown in Figure 11.
For the scheme as shown in Figure 10, we find that the
zero sequence reactance is XL0 = 6Xn + 3Xm + Xp, the third
sequence reactance is XL3 = 3Xm + Xp, and the first sequence
reactance is XL1 = Xp.
5
2014 Electrical Power, Electronics, Communications, Controls, and Informatics Seminar (EECCIS)
1) Find phase to ground, interphase, intercircuit like Appropriate selection of neutral and connecting reactors
phase, and intercircuit unlike phase capacitances of by using the abovementioned procedure will optimally
transmission lines. suppress the AC part of secondary arc to 5 A or lower, as
2) Calculate capacitance which we must install in order shown in Figure 13. This suppression fastens the arc
to make intercircuitsusceptances balanced. C = Ci – Cjif the extinction [5], and thus increases the success rate of single
capacitors are intalled at one end, and C = (Ci – Cj)/2if the pole auto reclosing, not to mention the other determining
capacitors are installed at both ends. factors such as recovery voltage and the arc characteristics
3) Calculate capacitive susceptances of the lines which are not discussed in this paper, and important subjects
4) Calculate symmetrical components of the lines’ of future research.
capacitive susceptance using equation 12.
(a)
VI. CONCLUSION
It has been shown that:
1) Secondary arc increases as the length of transmission
lines increases.
2) Generally, secondary arc increases as the relative
rotor angle decreases.
(b) 3) Secondary arc current can be suppressed using high
Fig. 12. (a)Secondary Arc If the Switching Delay of Shunt Reactors is speed grounding switch for untransposed transmission lines.
too Fast (b) Secondary Arc If the Switching Delay of Shunt Reactors 4) Shunt reactors can be used as both positive sequence
is Made Longer
compensator and secondary arcsuppressor, with
appropriate selection of reactance.
5) inimize intercircuit and interphase susceptances
5) In order to suppress secondary arc, shunt reactors
using equation BL1 - BL0 = BC1 - BC , therefore BL0 = BC1(h –
can be switched on only during dead time of SPAR if the
1) + BC0
lines are highly loaded.
6) Calculate third sequence inductive susceptance using
equation BC3 - BC0 = BL3 – BL0, therefore BL3 = BC3 +BC1(h – REFERENCES
1) [1] Yu Liu, Jun Wen, "Simulation Analysis of Single-Phase Adaptive
7) Calculate zero sequence, first sequence, and third Auto-Reclose on UHV Transmission Lines with Shunt Reactors,"
sequence shunt reactance using equation XL3 = (BL3)-1, XL1 = International Conference on Energy and Environment Technology
(ICEET '09), vol.2, pp.279-282, 16-18 October, 2009.
(BL1)-1, and XL0 = (BL0)-1.
[2] T. Lobos, P. Schegner, T. Sikorski, "Assessment of Transient
8) Calculate phase reactance of shunt reactors, Xp= XL1, Disturbances in HV Systems With Single-Phase Autoreclosures," XV
connecting reactance Xm= (XL3 - XL1)/3 and neutral International Symposium on Theoretical Engineering (ISTET), pp.1-
reactance Xn= (XL0 - 3Xm - Xp)/6 if the shunt reactors are 4, 22-24 June 2009.
[3] L. Prikler, M. Kizilcay, G. Ban, P. Handl, “Improved Secondary Arc
installed at one end, and phase reactance Xp= 2XL1, Models Based on Identification of Arc Parameters from Staged Fault
connecting reactance Xm= 2(XL3 - XL1)/3 and neutral Test Records,” 14th PSCC, pp.1-6, 24-28 June, 2002.
reactance Xn= 2(XL0 - 3Xm - Xp)/6 if the shunt reactors are [4] Edward W Kimbark, “Suppression of Ground-Fault Arcs on Single-
Pole- Switched EHV Lines by Shunt Reactors,” IEEE Winter Power
installed at both ends. Meeting, Paper 64-56, 2-7 February 1964.
[5] Edward W Kimbark, “Selective-Pole Switching of Long Double-
Circuit EHV Line,” IEEE Transactions on Power Apparatus and
Systems, Vol. Pas-95, No.1, January/February 1976.
6
2014 Electrical Power, Electronics, Communications, Controls, and Informatics Seminar (EECCIS)
[6] Lei Chen; Haijun Liu; Ming Wu; Delin Wei; MengNiu, "Study on
Compensation for Secondary Arc Current on UHV Double-Circuit
Lines," Power and Energy Engineering Conference (APPEEC), 2011
Asia-Pacific , vol., no., pp.1,4, 25-28 March 2011