DHL Kuthambakkam Handing Over Doucment File.
DHL Kuthambakkam Handing Over Doucment File.
CONTENTS:
Handing over report
User Manual, Do's & Don't, Inspection & Routine Maintenance, Trouble
Shooting.
Cold room controller Operating Instructions.
Test certificates
As build Drawings
DQ , IQ , OQ Documents
SOP Documents
Competency certificate
Escalation Matrix
KRM Plaza, nd Floor, No. 2, 2, Harrington Rd, Chetpet, Chennai, Tamil Nadu 600031
Date : 14.12.2023
TO,
DHL Supply Chain India Pvt. Ltd.
Survey No.389,400/2A,400/2C,
Kuthambakkam Village,
Poonamallee, Thiruvallur Distt.,
Chennai - 600 124.
Dear Sir,
We have commissioned Stagging, Embecta & Bigger room machines. The refrigeration units of Stagging,
Embecta & Bigger Room are working in good performance. We hereby hand over the rooms to you for
further storing of Products.
Thanking you and assuring you of our best services at all times, We remain
For Blue Star Limited For DHL SUPPLY CHAIN INDIA PRIVATE LIMITED
(RAVEENRAJ B)
Asst.Manager – Planning & Installation
Cold Storage Division
Basics
What is a Cold Room?
A Cold Room is a room in the shape of a cubic box, made with prefabricated
PUF insulated panels or with brick and mortar with insulation done at site,
maintaining desired inside temperature and humidity for the preservation of
the product stored inside.
3
Typical Cold Room Layout
4
Main Components of a Cold Room
5
Nomenclature
TYPE A A=AIRCOOLED
W=WATER COOLED
TEMPERATURE H H=HIGH
M=MEDIUM
L=LOW
REFRIGERANT 2 2=R22
4=R404
6
Operation
7
Do's & Don'ts
unit.
Do not block the air inlet & outlet sides of the outdoor units.
11
Inspection & Routine Maintenance
Regular Inspection
Regular inspection of the cooling unit and outdoor unit reduces failure and
assures continuous operation.
12
Troubleshooting
Diagnosing Faults
Faults and complaints in Cold Room systems can be broadly classified under
two areas. The most important step in troubleshooting is to diagnose the fault.
13
Condensing Unit Troubleshooting Chart
14
Symptoms Possible causes Possible corrective steps
Low suction 1. Lack of refrigerant 1. Check for leaks. Repair and
pressure add charge.
2. Evaporator dirty or load 2. Clean
3. Clogged liquid line filter 3. Replace cartridge(s)
drier.
4. Clogged suction line or 4. Clean strainers.
compressor suction gas
strainers.
5. Condensing temperature 5. Check means for regulating
too low. condensing temperature.
15
Wiring Diagrams
17
18
19
20
21
Index Index
Pg. Pg.
PARAMETER DESCRIPTION PARAMETER DESCRIPTION
No. No.
Introduction 4 QFD To set quick freeze duration. 15
Get to Know Your Controller 5 CND6 To set condenser on delay time. 15
Items Included. 5
CND7 To set condenser status at hot gas 15
Key Introduction 6 defrost.
Fault Messages. 7
L1 To set Evaporator Fan stop temperature. 16
LED Indication. 8
L2 To set Evaporator Restart Delay. 16
Parameter List. 9
L3 To set Evaporator Fan status at 16
SET POINT To set the cut-out point of the controller. 9 compressor off.
QFS To set the quick freeze set point. 9 L4 To set Evaporator Fan differential. 16
EXIT End of set mode 9 L5 To set Evaporator probe calibration. 17
To set other parameter 9 L7 To set Evaporator Fan status at Door 17
P2 To set allowable high temperature limit. 10 open condition.
P3 To set allowable low temperature limit. 10 L8 To set Evap Fan status during defrost. 17
P4 To set the differential for compressor 10 BUZ To enable / disable buzzer. 17
restart. AL This parameter is used to set power on 18
P5 To set probe calibration. 11 delay for alarm.
P6 To set time delay between relay restart 11 C-UL Under load limit for compressor current. 18
time.
C-OL Over load limit for compressor current. 18
P7 To set duration of defrost. 12
C2 Current sensing delay. 19
P8 To set defrost frequency. 12
D0 To enable or Disable HP sensing. 19
P9 To set power on defrost delay. 12
P10 To set type of defrost. 13 D1 To enable or disable LP sensing. 19
D2 Fault sensing logic. 20
P11 To set drip time for defrost. 13
D3 To set LP sensing delay. 20
P12 To set type of computation for defrost time. 13
D4 To set reset mode for HP fault. 20
P13 To set defrost stop temperature. 14
E1 To set Compressor Relay status on
DI-D To select AUX or compressor thermal Probe Failure. 21
trip digital I/P 14
TON To set On cycle at room probe fail. 21
OPS To Enable / Disable Oil Pressure Switch
(OPS) I/P. 14 TOFF To set Off cycle at room probe fail. 21
01 CRC-2052 CRC-2052 02
Index Introduction
The CRC-2052 is single set point cold room controller. The
Pg. Sub-Zero CRC-2052 is aesthetically superior versions of
PARAMETER DESCRIPTION
No.
their predecessors.
E7 To set Display at defrosting. 21
E8 Defrost duration during Coil probe failure. 22
LD To set time delay to switch off the light . 22 Features:
PDN To activate Solenoid Valve relay. 22 The controller controls the defrost in the system based on
PW To change password. 22 either an electrical heater where the compressor is stopped, or
CRH To view Compressor run Hours. 23 at cycle inversion using warm gas where the compressor
CCRH Clear Compressor Run Hours. 23
keeps on working.
ID To set Unit ID. 23
There are safety features which include shutting down the
LP To activate Keypad Lock. 23 system incase of a fault from a pressure control or similar
PO To enable/disable Power Switch. 23-24 device.
PDIS To set display at power OFF mode. 24
FS To restore default settings of the 24 A series of “safety controls” (delay at start-up, minimum disable
controller. time, minimum time between activation) protects the
EP End of programming. 24 compressors from close starts. In case of probe error or
Technical Data 25 temperature alarm, the instrument signals the event through
Suggested Wiring Diagram
acoustic signal and by closing the relay contact. By pressing
26
the mute key, the buzzer is silenced.
Wall Mount Dimensions 27 A number of parameters are displayed alphanumerically to set
Instruction Manual for LVM VMRC-10/3 28-35 up the instrument for each specific function.
Caution & Warranty 36-37 Computer Connectivity over RS485 and Remote
monitoring(Optional).
03 CRC-2052 CRC-2052 04
Get to Know Your Controller Key Introduction
Used to enter in manual defrost and to stop defrost if defrosting
is ON.
Fault Log
Used to enter into the Set mode. Also used as enter key if controller
is in Set mode/program mode.
PRG
Used to enter in display Amp. mode where compressor current can
be viewed.
Amp
Items included
1. CONTROLLER 1
3. CATALOGUE 1
05 CRC-2052 CRC-2052 06
Fault Messages : LED Indication
High temperature alarm for Room means, room temperature is Messages Mode Discription
Ht
equal or above the set value of P2 parameter.
On Comp. Relay On.
Low temperature alarm for Room means, room temperature is Off Comp. Relay Off.
Lt
equal or below the set value of P3 parameter. Flashing Comp. Relay Timedelay.
Room temperature fail means, Room sensor not connected or
PP On Cond. Relay On.
out of range. C Off Cond. Relay Off.
E-PP Evaporator temperature fail means, Evaporator sensor not On Evap. Relay On.
connected or out of range. Off Evap. Relay Off.
E
DO Door Input Fault. Flashing Evap. Relay Timedelay.
On Defrost Relay On.
SPPR SPPR Fault. Off Defrost Relay Off.
Flashing Defrost Relay Timedelay.
C-OL Compressor over load fault.
On LSV Relay On.
Off LSV Relay Off.
C-UL Compressor under load fault. On Alarm Relay On.
Off Alarm Relay Off.
HP HP fault. Flashing Controller is in drip time.
07 CRC-2052 CRC-2052 08
Min: MINIMUM Max : MAXIMUM Description of parameters and functions.
Fact. Set : FACTORY SETTING(DEFAULT)
Sr. Parameter Parameter setting method
Description of parameters and functions. No.
Sr. Parameter Parameter setting method 01 P2 Function : To set allowable high
No. Parameter temperature limit.
To set other parameter To change P2 parameter, Use UP/DOWN key to set desired value.
press the set key. Once set at a particular value, this will not
Press & hold SET key for Display will show ‘SET’ and scroll the allow the set point to go above this
2 seconds description of the parameter. value and below P3 setting.
Range
To go to other parameters,
Min Max Fact. Set Example : Setting this parameter
use up / down keys. at 30.00C will not allow the set point to go
SP+0.5ºC 50.0ºC 50.0ºC above 30.00C also if the temperature
01 SP To set the cut-out point of the controller.
reaches 30.00C, the display will show HT
To change Set Point parameter, Display will change to set value. HT (High Temperature). The alarm will be
(Message on Display) ON. But at power on till the AL delay is
press the set key. The set point value can now be changed
by using the UP/DOWN key. After desired over controller will not generate HT Alarm.
Range value, press the SET key & you will see “--
” which confirms that the set point has 02 P3 Function : To set allowable low
Min Max Fact. Set been stored in memory. Parameter temperature limit.
QFS P2-0.5ºC -20.0ºC To change P3 parameter, Use UP/DOWN key to set desired value.
press the set key. Once set at a particular value, this will not
QFS To set the quick freeze set point. allow the set point to go below this value
02 Range
and above P2 setting.
To change QFS parameter, Use UP/DOWN keys to set desired value. Min Max Fact. Set
press the set key. Example : Setting this parameter at
-50.0ºC SP-0.5ºC -50.0ºC -30.00C will not allow the set point to go
If controller is in quick freeze mode then
Range compressor will cut in/ cut out as per this below -30.00C also if the temperature
reaches -30.00C, the display will show LT
Min Max
set point till the quick freeze duration is
Fact. Set over. LT (Low Temperature). The alarm will be ON.
(Message on Display)
-50.0ºC SP -25.0ºC
SP : Set Point. 03 P4 Function : To set the differential for
Parameter compressor restart.
03 EXIT End of set mode To change P4 parameter, Use UP/DOWN keys to set desired value.
press the set key.
To set other parameter Example(Cooling Mode) : If the set point
Range
is set at 10.00C and differential is set at
Press & hold PRG key for Display will show ‘P2’ and scroll the Min Max Fact. Set 2.00C, then when the system reaches
2 seconds description of the parameter. 10.00C, the comp. relay will cutout. Since
To go to other parameters, use up / down 0.5ºC 20.0ºC 2.0ºC
the differential is 2.00C, the comp. Relay
PRG keys. will cutin at 12.00C
(10.00C + 2.00C).
09 CRC-2052 CRC-2052 10
Description of parameters and functions. Description of parameters and functions.
Sr. Parameter Parameter setting method Sr. Parameter Parameter setting method
No. No.
P5 Function : To set probe calibration. P7 Function : To set duration of defrost.
04 06
Parameter Parameter
To change P5 parameter, Use UP/DOWN keys to set desired value. To change the P7 Parameter Use UP/DOWN keys to set desired value.
press the set key. In time it may be possible that the display parameter, press the set key.
may be offset by a degree or so. This is maximum amount of time allowed
Range To compensate for this error, you may Range for defrost. If set to 0, there will be no
defrost cycle.
Min Max Fact. Set need to add or minus the degrees Min Max Fact. Set
required to achieve the correct
-10.0ºC 10.0ºC 0.0ºC temperature. Example : If P7 is set to 15 Mins and P8
0 Min 99 Min 30 Min
Example : The temperature on the parameter is set to 1 Hr. then after every 1
display is 28.0OC, whereas the actual Hr defrosting will take place for 15 mins.
temperature is 30.0OC. You will need to set
this parameter to 2.0OC, which means that
once out of the programming parameter, 07 P8 Function : To set defrost frequency.
the display will show the temperature Parameter
30.0OC (28.0OC + 2.0OC). To change the P8 Parameter Use UP/DOWN keys to set desired value.
parameter, press the set key. This is the amount of time between two
Range defrost cycles.
05 P6 Function : To set time delay between
Parameter relay restart time. Min Max Fact. Set Example : same as P7 parameter.
To change P6 parameter, Use UP/DOWN keys to set desired value.
1 Hr 31 Hrs 6 Hr
press the set key. This parameter is used to protect the fan
from restarting in a short period of time
Range and can be set between 0 to 20 minutes. P9 Function : To set power on defrost delay.
08
Min Max Fact. Set Parameter
Example : If this parameter is set at 3
1 Min 20 Min 3 Min To change the P9 Parameter Use UP/DOWN keys to set desired value.
minutes, the compressor will cut off at the
parameter, press the set key. This is the amount of time at power on
set temperature, but will not restart for a
minimum of 3 minutes, even if the Range after which defrosting will take place
differential is achieved earlier. This once.
parameter is good to protect the life of the Min Max Fact. Set
compressor when there are power 0 Min 99 Min 0 Min Example : If P9 parameter is 30 mins
fluctuations and the compressor is then at power after 30 mins defrosting will
switched off and on within a few seconds. take place once.
11 12
Description of parameters and functions. Description of parameters and functions.
Sr. Parameter Parameter setting method Sr. Parameter Parameter setting method
No. No.
09 P10 Function : To set type of defrost. P13 Function : To set defrost stop
12
Parameter Parameter temperature
To change the P10 Parameter Use UP/DOWN keys to set desired value. To change the P13 Parameter Use UP/DOWN keys to set desired value.
parameter, press the set key. parameter, press the set key.
HTR : Heater defrost where compressor If coil/Evap temperature is reached upto
is OFF. this temperature defrost will stop.
Range Range
HTG : Hot Gas defrost where compressor
Min Max Fact. Set is ON. Min Max Fact. Set Example : If this parameter is set to
7.0ºC,then if defrosting is in progress then
HTR HTG HTR -50.0ºC 50.0ºC 4.0ºC when temperature reaches 7.0ºC, the
defrost process will stop.
10 P11 Function : To set drip time for defrost.
Parameter
13 DI-D Function : To select AUX or
To change the P11 Parameter Use UP/DOWN keys to set desired value. Parameter compressor thermal trip digital I/P
parameter, press the set key. During this period Compressor, To change the DI Parameter Use UP/DOWN keys to set desired
Range Evaporator Fan, LSV relay and Heater parameter, press the set key. value.
will stay off so that the defrost water can
Min Max Fact. Set drain out. Range If Selected as “AUX” then at fault it will
0 Min 30 Min 1 Min Min Max Fact. Set display "AUX” on display.
P12 Function : To set type of computation AUX CTH CTH If Selected as “CTH” then at fault it will
11 display “CTH”.
Parameter for defrost time..
To change the P9 Parameter Use UP/DOWN keys to set desired value.
parameter, press the set key. REAL = Total of real time.
14 OPS Function : To Enable / Disable OPS I/P.
Range Example : This means that the time Parameter
calculation for defrost frequency will be
Min Max Fact. Set for the total hours the unit has been To change the OPS Parameter Use UP/DOWN keys to set desired
parameter, press the set key. value.
REAL CRH REAL running.
CRH - Sum of total compressor Range
operating times. This means that for time ENB : OPS I/P is enabled.
calculation, the unit will add the total time Min Max Fact. Set DIS : OPS I/P is disabled.
the compressor has been in an ON mode. DIS ENB ENB
It keeps a record of the hours worked +/-½
Hour incase of a power failure.
13 CRC-2052 CRC-2052 14
Description of parameters and functions. Description of parameters and functions.
Sr. Parameter Parameter setting method Sr. Parameter Parameter setting method
No. No.
15 QFD Function : To set quick freeze duration. 18 L1 Function : To set Evaporator Fan stop
Parameter Parameter temperature.
To change the QFD Parameter, Use UP/DOWN keys to set desired value. To change the L1 parameter, Use UP/DOWN keys to set desired value.
press the set key. press the set key.
This is the maximum amount of time This setting is used to limit the Max.
Range allowed for Quick Freeze. If set to “0”, Range temperature beyond which the Evap.Fan
Min Max Fact. Set there will be no quick freeze. Min Max Fact. Set will cut off.
0 Hr 12 Hrs 2 Hr Example : If QFS is set to -20.0 C, and -50.0ºC 50.0ºC 2.0ºC Example : If this parameter is set to
quick freeze duration is set to 1 hr ,then 2.0ºC, then Evap. Fan will cut off at 2.0ºC.
when it is in quick freeze mode, then the
Comp. will work on -20.0C set point for 19 L2 Function : To set Evaporator Restart
1hr. Parameter Delay.
CND6 Function : To set condenser on delay To change the L2 parameter, Use UP/DOWN keys to set desired value.
16 press the set key.
Parameter timings.
Example : If this is set at 3 minutes, Evap.
To change the CND6 Use UP/DOWN keys to set desired value. Range Fan relay will cut off at the set by Evap.
parameter, press the set key.
Min Max Fact. Set Fan Stop TC. Parameter but the Fan will
When Compressor delay over Condenser not come on for a minimum of 3 minutes
Range
Fan will come ON first, after cond. On 0 Min 20 Min 1 Min even if it’s differential is achieved earlier.
Min Max Fact. Set delay over Comp will come ON.
0 Sec 30 Sec 15 Sec 20 L3 Function : To set Evaporator Fan status
Parameter at compressor off.
CND7 Function : To set condenser status at To change the L3 parameter, Use UP/DOWN keys to set desired value.
17 press the set key.
Parameter hot gas defrost.
OFF : Evaporator Fan will be Off at
To change the CND7 Use UP/DOWN keys to set desired value. Range
compressor OFF.
parameter, press the set key. Min Max Fact. Set ON : Evaporator Fan will be On at
This function is used to decide the compressor OFF.
Range condenser status when hot gas defrost is OFF ON ON
Min Max Fact. Set on. This parameter is not applicable for L4 Function : To set Evaporator Fan
Heater defrost. 21
OFF ON OFF At hot gas defrost, Parameter differential.
OFF : Condenser will be OFF To change the L4 parameter, Use UP/DOWN keys to set desired value.
ON : Condenser will be ON press the set key.
Example : If Evaporator Fan Stop Tc
Range parameter is set to 2.0ºC, and if EVAP
Min Max Fact. Set DIFFERENTIAL parameter is set to
2.0ºC,then Evap. Fan will cut off at 2.0ºC
0.5ºC 20.0ºC 2.0ºC and restart only at 0.0ºC.
(2.0ºC-2.0ºC = 0.0ºC).
15 CRC-2052 CRC-2052 16
Description of parameters and functions. Description of parameters and functions.
Sr. Parameter Parameter setting method Sr. Parameter Parameter setting method
No. No.
L5 Function : To set Evaporator probe 26 AL Function : This parameter is used to set
22
Parameter calibration. Parameter power on delay for alarm.
To change the L5 parameter, Use UP/DOWN keys to set desired value. To change the AL Parameter Use UP/DOWN keys to set desired value.
press the set key. parameter, press the set key.
Example : If you set this parameter to 20,
In time it may be possible that the display Range
Range once the power is switched on, the alarm
may be offset by a degree or so. To
Min Max Fact. Set will not activate for 20 minutes after the
Min Max Fact. Set compensate for this error, you may need power is switched on. This
to add or minus the degrees required to 0 Min 99 Min 30 Min is most useful to avoid the nuisance
-10.0ºC 10.0ºC 0.0ºC achieve the correct temperature. Setting
alarms when the ambients are high when
value is from -10ºC to + 10ºC.
the machine is switched on after a
L7 Function : To set Compressor- long time.
23
Parameter Evaporator Fan status at Door open C-UL Function : Under load limit for
condition. 27
Parameter compressor current.
To change the L7 parameter, Use UP/DOWN keys to set desired value.
To change the C-UL parameter, Use UP/DOWN keys to set desired value.
press the set key.
press the set key.
At Door Open,
Range Example : If C-UL= 1.0A and compressor
NORM : Normal. Range current is less than 1.0A then and exists till
Min Max Fact. Set FAN : Evaporator Fan Off.
COMP : Compressor Off. Min Max Fact. Set C2 current sensing delay then it is
NORM F-C NORM F-C registered as UL fault. Compressor will
: Compressor and Evaporator Fan
0.0A (C-OL 1.0A get OFF on this fault. If after 3 retries
Off.
-1.0)A within 1 Hour current drawn is still less
24 L8 Function : To set Evaporator Fan than 1.0Amp the controller will trip the
Parameter status during defrost. compressor on fault and activate
To change the L8 Parameter Use UP/DOWN keys to set desired value. respective alarm relay. Also display will
parameter, press the set key. flash ‘C-UL’. Controller will go in manual
OFF : Evaporator Fan Off during reset mode.
Range defrost.
Min Max Fact. Set ON : Evaporator Fan On during 28 C-OL Function : Over load limit for
defrost. Parameter compressor current.
OFF ON OFF
To change the C-OL parameter, Use UP/DOWN keys to set desired value.
BUZ Function : To enable / disable buzzer. press the set key.
25 Example : If C-OL= 10 A and compressor
Parameter Range
To change the BUZ parameter, Use UP/DOWN keys to set desired value. current is greater than 10 A then and exist
press the set key. Min Max Fact. Set till C2 current sensing delay then C-OL
Example: fault exists and flash on display.
Range ENB : Buzzer enabled. (C-UL 18.0A 10.0A Compressor will be tripped on this fault.
+1.0) A
Min Max Fact. Set DIS : Buzzer disabled.
DIS ENB ENB
17 CRC-2052 CRC-2052 18
Description of parameters and functions. Description of parameters and functions.
Sr. Parameter Parameter setting method Sr. Parameter Parameter setting method
No. No.
19 CRC-2052 CRC-2052 20
Description of parameters and functions. Description of parameters and functions.
Sr. Parameter Parameter setting method Sr. Parameter Parameter setting method
No. No.
E1 Function : To set Compressor Relay E8 Function : Defrost duration during Coil
35 39
Parameter status on Probe Failure. Parameter probe failure.
To change E8 parameter, Use UP/DOWN keys to set desired value.
To change E1 parameter, Use UP/DOWN keys to set desired press the SET key.
press the set key. value. Example: If this is set to 10 min, then
Range
Range When set to manual defrost for 10 min will take place
ON : Relay will stay ON. Min Max Fact.
Fact. Set
Set during Coil probe fail.
Min Max Fact.
Fact. Set
Set CYC : Relay performs a duty cycle of
1 Min 10 Min 5 Min
ON OFF CYC as per TON & TOFF .
OFF : Relay will stay OFF.
40 LD Function : To set time delay to switch
TON Parameter off the light .
36 Function : To set On cycle at room
Parameter probe fail. To change LD parameter, Use UP/DOWN keys to set desired value.
press the SET key.
To change TON parameter, Use UP/DOWN keys to set desired value. This parameter is used set the time delay
press the set key. Range
At room probe fail condition when E1 to automatically switch off the light. If LD is
Range Min Max Fact.
Fact. Set
Set set to 0 then this parameter is disabled.
parameter is selected as 'CYC' then the
Min Max Fact. on cycle is specified by Ton parameter. 0 Min 30 Min 7 Min Example : If this parameter is set to 7 mins
Fact. Set
Set then, when light is switched on after 7 mins
1 Min 30 Min 10 Min it will be switch off automatically.
21 CRC-2052 CRC-2052 22
Description of parameters and functions. Description of parameters and functions.
Sr. Parameter Parameter setting method Sr. Parameter Parameter setting method
No. No.
CRH Function : To view Compressor run Range DIS : Disable power switch
43
Parameter Hours. ENB : Enables power switch
Min Max Fact.
Fact. Set
Set Controller has power switch, which if
It will display compressor run hours. It's a
read only parameter. DIS ENB DIS enable puts controller in active or stand by
state.
44 CCRH Function : Clear Compressor Run If press for 2 seconds controller will go in
Hours. stand by mode, display will be as per
Range If this parameter is set to ‘YES’ “PDIS” parameter.
compressor run hours (CRH) are cleared. To again switch to ACTIVE WORKING
Min Max Fact.
Fact. Set
Set MODE, press power switch again for 2
NO YES NO seconds. All leds and display will flash and
enter into NORMAL WORKING MODE.
45 ID Function : To set Unit ID.
Parameter 23 PDIS Function : To set display at power OFF
48
Parameter mode.
To change Unit ID This parameter is used to set the Unit ID
parameter, press the SET key. of the device. To change PDIS parameter, Use UP/DOWN keys to set desired value.
press the SET key.
Range At power OFF mode power OFF LED
Range
Min Max Fact. will glow & display will be as below,
Fact. Set
Set Min Max Fact.
Fact. Set
Set
1 240 - LED : Display Will be Blank.
LED TEMP LED
OFF : Display will show OFF.
46 LP Function : To activate Keypad Lock. TEMP : Display will show Temperature.
Parameter
To change Keypad Lock This parameter can lock the keypad so 23 FS Function : To restore default settings of
49
parameter, press the set key. that tempering is not possible by by- Parameter the controller.
standers. To change FS parameter, Use UP/DOWN keys to set desired value.
Range press the SET key.
NO : deactivates keypad lock. When set to YES all parameters are
Min Max Fact.
Fact. Set
Set YES : activates keypad lock. Range
programmed to factory values.
NO YES NO Min Max Fact.
Fact. Set
Set Useful to debug setting related problems.
On activation, all the parameters can only
be viewed, but not modified. NO YES NO
If the keypad is locked “LOCK” message
will be displayed.. 50 EP Function: To exit programming.
Parameter
23 PO Function : To enable/disable Power
47 To exit programming Once the set key is pressed, the controller
Parameter Switch.
parameter, press the SET key. goes into the normal mode and displays
To change PO parameter, Use UP/DOWN keys to get desired the Room Temperature and all settings
press the SET key. value & press SET key to confirm. are recorded.
23 CRC-2052 CRC-2052 24
Technical Data
Housing : ABS Plastic.
Dimensions : 400 x 300 x 135 mm
Mounting : Wall mounting.
Connection : Spring clamp terminal block.
4 sq. mm wire.
Display : 4 Digit, 1” Dot matrix Display and 14 LEDs for
indication.
Data Storage : Non-Volatile EEPROM Memory.
Power Input (Options) : 415Vac +/-10%, 50-60Hz.
3Phase Supply with Neutral
0 0
Operating Temp : 5 C to 50 C(non-condensing).
0 0
Storage temp : -20 C to 70 C(non-condensing).
Output :
Compressor Relay : 5A/230vac
Defrost Relay : 5A/230vac
Evap. Relay : 5A/230vac
Condenser Relay : 10A/230vac
Light Relay : 5A/230vac
Alarm Relay : 5A/230vac
LSV Relay : 10A/230vac
Sensors :
1) Temperature sensor:
Sensor Type : NTC Thermistor.
0
Resolution : 0.1 C.
Accuracy : +/-10C.
Probe Tolerance at 250C : +/-0.30C.
Room & Evap Temperature :
Range : -50.00C to 50.00C
Analog I/p:
Compressor current (R,Y,B)
Resolution : 0.1Amp.
Accuracy : +/-1 Amp.
Digital Inputs:
HP, LP, Auxiliary / CTH(Compressor Thermal) , Oil Pressure Switch(OPS),
Door, SPPR, R-Ph, Y-Ph, B- Ph.
Buzzer : Internal
25 CRC-2052
26
Wall Mount Dimensions
TOP
393.2mm
22.5mm
320mm
298mm
254mm
110mm
100mm
BOTTOM
27
Instruction Manual Introduction
LVM (Line Voltage Monitor) Three Phase VMRC-10/3 VMRC-10/3 is three phase Line voltage monitor (LVM) used to protect device
from Single Phasing, voltage unbalance, phase reversal and under/over
voltage. It shows real time voltages between phase and neutral.
Index
There is an Output of alarm relay is given to the controller as SPPR input.
Pg. Features are easily understood by examples in the instruction below.
PARAMETER DESCRIPTION
No.
Introduction 30
Get to know your Controller. 30
To set program mode. 31 Get to Know Your Controller
To set Reference Voltage. 31
To set Overvoltage Limits. 31
To set Undervoltage Limits. 32
To set Un Balance Value. 32
To set Time Delay. 32
To set fault recover delay. 33 R Y B N
15 17 19 18 21
To set Calibration of Voltage. 33
To set Calibration of Voltage. 33
249
To set Calibration of Voltage. 34
To set Display mode. 34
To Restore factory defaults. 34
End programming. 35
Technical Data. 36
Front View & Connection Diagram. 36
RELAY
NO C NC
7 8 9
28 VMRC-10/3 VMRC-10/3 29
Description of parameters and functions. Description of parameters and functions.
Sr. Parameter Parameter setting method Sr. Parameter Parameter setting method
No. No.
To set other parameter 03 Function : To set Undervoltage Limits.
Parameter
Press & hold PRG key for Display will show ‘rEF’ and scroll the To change the uV parameter, Use UP/DOWN keys to set desired value.
2 seconds description of the parameter. press the set key. If the a/c voltages goes below this
limit will trip respective a/c on
To go to other parameters, Range undervoltage(”Uv”) fault.
use up / down keys.
Min Max Fact. Set
Function : To set Reference voltage. Example : Under voltage is calculated
01 5V 75V 20V depending on Reference voltage - Uv
Parameter
value. i.e Uv Set Point = Ref - Uv , When
To change the rEF Parameter, Use UP/DOWN keys to set desired value. controller trip on Uv Fault it will recover
press the set key. Base reference voltage to calculate under when input voltage above (Ref – (Uv /2).
voltage and over voltage values.
Range
04 Function : To set Un Balance value.
Min Max Fact. Set Parameter
Min and Max value will change
381V 415V 415V according to display type for settings. To change the unb parameter, Use UP/DOWN keys to set desired
press the set key. value.
Example : If dsP is L-L then Min= 381V,
Max= 415V. Range Unbalance fault raised when voltage
Function : To set Overvoltage Limits. Min Max Fact. Set difference between any of two phases
02 goes above Unb value and recovers when
Parameter 10V 120V 60V the difference is less than (UNB/2).
To change the oV parameter, Use UP/DOWN keys to set desired
press the set key. value. Function : To set time delay.
05
If the a/c voltages goes above this Parameter
Range limit will trip respective a/c on
To change the ttd parameter, Use UP/DOWN keys to set desired
Min Max Fact. Set Overvoltage(”Ov”) fault. press the set key. value.
5V 75V 35V Example : Over voltage is calculated
Range Time delay provided to avoid false
depending on Reference voltage + Ov
value. i.e, Ov Set Point = Ref + Ov , When Min Max Fact. Set triggering, when any fault last more than
controller trip on Ov Fault it will recover TTD value then only fault is raised and this
when input voltage fall below (Ref - (Ov 0Sec 60Sec 10Sec fault is applicable to Under voltage, Over
/2). voltage and Unbalance fault.(i.e., In case
of Phase Loss or Phase sequence fault
alarm will come immediately).
30 VMRC-10/3 VMRC-10/3 31
Description of parameters and functions. Description of parameters and functions.
Sr. Parameter Parameter setting method Sr. Parameter Parameter setting method
No. No.
06 Function : To set fault recover delay. 09 Function : To set calibration of voltage
Parameter Parameter for r-b or b-n phase.
To change the tdr parameter, Use UP/DOWN keys to set desired To change the Crb parameter, Use UP/DOWN keys to set desired
press the set key. value. press the set key. value.
Range Time delay provided to add delay in fault Range This parameter provided to calibration
Min Max Fact. Set recover time, to avoid sudden fault Min Max Fact. Set voltage reading.
triggering and reset.
0Sec 240Sec 10Sec -15V 15V 0V When dsP is L-L then it sets calibration for
r-b.
Function : To set calibration of voltage When dsP is L-n then it sets calibration for
07 b-n.
Parameter for r-y or r-n phase.
To change the CrY Parameter, Use UP/DOWN keys to set desired
press the set key. value. 10 Function : To set view display mode.
Parameter
Range This parameter provided to calibration To change the dsP parameter, Use UP/DOWN keys to set desired
Min Max Fact. Set voltage reading. press the set key. value.
-15V 15V 0V When dsP is L-L then it sets calibration for Range There are two type of display output, Line
r-y. Min Max Fact. Set to Line Voltage (L-L) and Line to Neutral
When dsP is L-n then it sets calibration for (L-n), Depending on this parameter REF
r-n. L-L L-n L-L parameter also changes.
32 VMRC-10/3 VMRC-10/3 33
Description of parameters and functions. Technical Data
Sr. Parameter Parameter setting method
No. Main Functions : Voltage Monitoring.
Phase Sequence Monitoring.
12 Function :To end programming. Phase Loss and Phase Unbalance detection.
Parameter Uv and Ov Detection.
To change the end parameter, Once the set key is pressed, the controller Settable Uv and Ov Parameter.
press the set key. goes into the normal mode and displays Dimensions : Front : 70mm X 45mm,
the voltage readings. Depth : 72.3 mm
Input : R, Y, B Phases and Neutral Input.
Output : Alarm Relay : 5A Resistive.
General Specification :
Input Voltage Range from 100VAC to 265VAC.
Mounting : Din rail mounting.
Connections : Screw terminals : < 2.5sqmm one wire/terminal only.
OV UV SPPR
VMRC-10/3
PRG
HLD SET
R Y B N
15 17 19 18 21
1 2 3 7 8 9
NO C NC
RELAY
34 VMRC-10/3 VMRC-10/3 35
Controller Notice
Controller should be installed in a place protected by vibration, water and The information in this document is subject to change in order to improve
corrosive gasses and where ambient temperature does not exceed the values reliability, design or function without prior notice and does not represent a
specified in the technical data. commitment on the part of the company. In no event will the company be liable
for direct, indirect, special, incidental or consequential damage arising out of
Probe the use or inability to use the product or documentation, even if advised of the
possibility of such damages. No part of this manual may be reproduced or
To give a correct reading, the probe must be installed in a place protected from
transmitted in any form or by any means without the prior written permission of
thermal influences, which may affect the temperature to be controlled.
the company.
Caution
WIRING : The probe and its corresponding wires should never be installed
Disclaimer
in a conduit next to control or power supply lines. The electrical wiring This manual & its contents remain the sole property of A.S.Controls Pvt.Ltd.,
should be done as shown in the diagram. The power supply circuit should India and shall not be reproduced or distributed without authorization. Although
be connected to a protection switch. great care has been taken in the preparations of this document, the company
WARNING : Improper wiring may cause irreparable damage and personal or its vendors in no event will be liable for direct, indirect, special, incidental or
injury. Kindly ensure that wiring is done by qualified personnel only. consequential damage arising out of the use or inability to use the product or
documentation, even if advised of the possibility of such damages. No part of
Maintenance : Cleaning : Clean the surface of the controller with a soft this manual may be reproduced or transmitted in any form or by any means
moist cloth. Do not use abrasive detergents, petrol, alcohol or solvents. without the prior written permission of the company. A.S.Controls Pvt.Ltd.
reserves the right to make and changes or improvements without prior notice.
Warranty
This product is warranted against defects in materials and workmanship for a
period of one year from the date of purchase. During the warranty period,
product determined by us to be defective in form or function will be repaired or,
at our option, replaced at no charge. This warranty does not apply if the product
has been damaged by accident, abuse, and misuse or as a result of service or
modification other than by the company. This warranty is in lieu of any other
warranty expressed or implied. In no event shall the company be held liable for
incidental or consequential damages, such as lost revenue or lost business
opportunity arising from the purchase of this product.
36 CRC-2052 CRC-2052 37
OUR OTHER PRODUCTS
INDIA
Cold Room Controller
Chiller Controller
Two Compressors Controller
Heating Controller
Humidity Controller
Pressure Controller
R
Ball Valves
Globe Valves
Hand Valves
Flow Switches
Solenoid Valves
04 / 23.08.13
13350 NOTE:
7320
1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS
13350
1230 1230 1230 1230
OTHERWISE MENTIONED.
13975
1148
548
548
548
548
5650 LEGENDS:
825
D - 900 X 2100 MM D - 900 X 2100 MM
1500
1500
EMERGENCY
DOOR 1945 1945 1945
675
ADD -2
375
100 mm THK WALL PANEL (LAMINATION INSIDE PPGI-OUTSIDE PPGI)
525
525
525
EMERGENCY DOOR-1
5875
A
A
A
A
A
@
80 mm THK CEILING PANEL (LAMINATION INSIDE PPGI-OUTSIDE PPGI)
A
A
A
A
A
@
DS - HSD DOCK SHELTER 2650 X 2900 MM
A
A
A
A
A
@
A
A
A
A
A
@
A
A
A
A
A
@
2235
A
A
A
A
A
@
8410
2610/1310 C/C
2700/1400 Clear
200
988 210
200
1000
800kg 288
100
2000 800kg
Last Unit
Upright :6212
Height
Height :8012
:7200
A
Max Level
312
2000 100
800kg
2212
ELEVATION-A/AH
1800
A
@ @
COMMON
A
A
A
A
A
@
+25)
3700
280
100 mm PP/PP wall panel - 9mtr Ht
68080
68080
68080
66380
6709
6791
37070
1945
525
14300
12815
3000
6791
3359
8700
13150
1235
03 11-12-23 As build drawings RAVEEN RAMESH
Charging room 02 23-06-23 Issue For Approval RAVEEN RAMESH
1435
2010
635
Issue For Approval
7230
100mm W/P- 5.08 mtr Ht
18-05-23 RAVEEN
4495
01 RAMESH
2760
SLIDING DOOR
2000 X 2400 MM
ROLLING HSD DOOR-8 ROLLING HSD DOOR-7 ROLLING HSD DOOR-6 ROLLING HSD DOOR-5 ROLLING HSD DOOR-4 ROLLING HSD DOOR-3 ROLLING HSD DOOR-2 ROLLING HSD DOOR-1
635 VIEW GLASS 13
920
3000 X 4400 MM D-08 3000 X 4400 MM 3000 X 5000 MM D-07 3000 X 5000 MM D-ADD 3000 X 5000 MM 3000 X 5000 MM D-06 D-05 3000 X 5000 MM 3000 X 5000 MM D-04
1500 X 1000 MM
34100 48143
D-03
Canteen
20870
1500
Blue Star Limited,No.2,
D1,2&3 -
KRM Plaza,
5240
750 X 2100 MM
635 EL-02
TRAP DOOR
1839
1500
1839
Harrington Road,
4400
2
D-02
Chetpet,
1435
On Ceiling panel
630
Dock leveler 3 560
Dock leveler not available Dock leveler 8 Dock leveler not available 960
Dock leveler 6 Dock leveler 5 Dock leveler 2 Dock leveler 3 1360 Dock leveler 1 960 EL-03
EL-03
3250
D-01 Chennai-600 031
EL-02 DS-11 DS-10 DS-09 DS-08 DS-07 DS-06 DS-05 DS-04
898
905
905
905
DS-12 80mm PP/PP Wall Panel 4.98Mtr
DS-03 DS-02 GSD-01
300
EL-01
DOCK SHELTER -HSD
3150 X 5000 MM
DOCK SHELTER -HSD
2650 X 2900 MM
DOCK SHELTER -HSD
2650 X 2900 MM
DOCK SHELTER -HSD
2650 X 2900 MM
DOCK SHELTER -HSD
2650 X 2900 MM
DOCK SHELTER -HSD
2650 X 2900 MM
DOCK SHELTER -HSD
2650 X 2900 MM
DOCK SHELTER -HSD
2650 X 2900 MM
DOCK SHELTER -HSD
2650 X 2900 MM
DOCK SHELTER -HSD
2650 X 2900 MM
DOCK SHELTER -HSD
2650 X 2900 MM
DOOR
EL-01 COLD ROOM PLAN & ELEVATION LAYOUT
Steps
DS-12 DS-11 DS-10 DS-09 DS-08 DS-07 DS-06 DS-05 DS-04 2650 X 2900 MM
Ramp
DRAWING NO:
107380 BSL/23-24/001
DRAWN BY CHECKED BY APPROVED BY SCALE REVISION
RAVEEN RAMESH RAMESH N.T.S R2
DESIGN QUALIFICATION OF PAGE 1 OF 13
COLD ROOM
DESIGN QUALIFICATION OF
COLD ROOM
DESIGN QUALIFICATION OF PAGE 2 OF 13
COLD ROOM
Table of Content
1 DQ Approval 3
2 Abbreviations 4
3 Preamble 5
4 Objective 5
5 Scope 5
6 Refrigeration Principle 5
7 Technical Specifications 7
8 Safety Features 12
9 Control Logic 12
10 Annexure 13
11 Deviation 13
12 Conclusion 13
DESIGN QUALIFICATION OF PAGE 3 OF 13
COLD ROOM
1. DQ Approval
Planning &
Prepared by B RAVEENRAJ 04.12.23
Execution
2. Abbreviations
TR : Ton of Refrigeration
Hrs : Hours
HP : High Pressure
LP : Low Pressure
Amp : Ampere
HT : High Temperature
LT : Low Temperature
DESIGN QUALIFICATION OF PAGE 5 OF 13
COLD ROOM
3. Preamble:
This design qualification document pertains to the Cold Room designed for our esteemed
client M/s. DHL Supply Chain India Private Limited. The cold room shall be used to Pharma
products Storage.
4. Objective:
To design the cold room as per the user requirement specification to store the Pharma
products Storage at +15 to +25 ºC.
The design parameter includes both the ambient condition of surroundings of the building
and material load, which shall be kept inside the cold room.
5. Scope:
This design qualification document is applicable to Cold room in order to store Pharma
products Storage between +15 to +25 ºC.
6. Refrigeration Principle
Refrigeration is the process of maintaining the desired low temperature in the space by
removing heat continuously from the space and rejecting the same to the atmosphere. There are
many types of refrigeration system viz. Vapour Absorption, Vapour Compression, Steam Jet and so
on. However, the vapour compression refrigeration system is the most commonly used system in
Walk-in-coolers and freezers.
The refrigerant is mostly in liquid state at the inlet of the evaporator and gradually
becomes vapour as it flows through the evaporator by absorbing heat from the space to be cooled
and will be totally vapour at the outlet of the evaporator. The low pressure and low temperature
gaseous refrigerant goes to the compressor, where gaseous refrigerant is compressed to the
condensing pressure. During compression the gaseous refrigerant temperature also rises along
with the pressure. The high temperature and high pressure refrigerant gas then flows to the
condenser wherein the sum of heat absorbed in the evaporator, motor winding heat and heat of
compression are removed by cooling medium either air or water. The refrigerant in the condenser
changes its phase from gas to liquid the high-pressure liquid then flows through the expansion
valve wherein the temperature of the refrigerant drops due to drop in pressure. The refrigeration
finally enters the evaporator then completing the cycle.
DESIGN QUALIFICATION OF PAGE 7 OF 13
COLD ROOM
7. Technical Specifications:
Prefabricated Construction
Type of insulation
Floor lamination
DESIGN QUALIFICATION OF PAGE 8 OF 13
COLD ROOM
Lamination for door Pre - Painted Galvanized Iron Inside & Outside
11 Incoming Power Supply For system 415 Volt AC, 3 Phase, 50 Hz with Neutral
1 Make NA Emerson
1 Make NA Emerson
Coldroom- DSA1021R3-OA/ Air-Cooled
2 Model / Type NA Stagging room- DSA1321R3-OA
/ Air-Cooled
3 No. of evaporator per unit Nos. 1 No
1 Quantity 01
2 Model CRC-2052
3 Make Subzero
4 Purpose Local Display of Freezer room temperature
5 Range (sensor) -45oC to 35oC
6 Resolution 0.1oC
7 Accuracy + 1 oC
DESIGN QUALIFICATION OF PAGE 12 OF 13
COLD ROOM
8. Safety features
9. Control logic
The control logic for the refrigeration system for efficient working of system is as per follows:
The evaporator fan is interconnected with the compressor. First the evaporator fan starts, if the HP/LP
switch, thermostat and oil pressure switch are all found healthy then only compressor will start. This is
to protect the compressor. In case, if any of these are not working, the compressor will not start.
The compressor is interconnected with temperature controller. The sensor linked with temperature
controller sense the return air temp in room, if the temp is below the set parameter the compressor
will off and vise – versa.
The thermostatic expansion valve is provided in between condenser and near evaporator unit. The
need of expansion valve is to regulate the flow of refrigerant as per load in room. The probe
connected to valve is mounted just after the evaporator, it sense the refrigerant required as per the
requirement the valve regulate.
For safety of compressor the High pressure and Low pressure switch is provided in condenser unit. If
the discharge pressure is high the compressor will trip and if the suction pressure is low, the
compressor will trip automatically.
For the safety of compressor oil pressure switch is provided in the system. If the oil pressure is not up
to the mark then the compressor will not start.
DESIGN QUALIFICATION OF PAGE 13 OF 13
COLD ROOM
10. Annexure
11. Deviations
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
12. Conclusion
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
INSTALLATION QUALIFICATION OF
COLD ROOM
INSTALLATION QUALIFICATION OF PAGE 2 OF 17
COLD ROOM
Table of Contents
NA Cover Page 1
NA Table Of Contents 2
1. IQ Pre approval 3
3. Responsibility 4
6. Documents 5
9. Installation checklist 11
10. Deviation 14
11. Conclusion 14
1. IQ Pre approval
Planning &
Prepared by B RAVEENRAJ 04.12.23
Execution
Engineering &
Reviewed by
Maintenance
To provide the documented evidences that the proper installation of Cold room.
3. Responsibility
To install the Cold room as per approved designed specification and at designated place.
To record the observation along with DHL during execution of the installation qualification.
Quality Assurance
Engineering:
INSTALLATION QUALIFICATION OF PAGE 5 OF 17
COLD ROOM
Production
All the deviation if occurred during qualification shall be observed in the report.
The supporting reports shall be attached to the document and records shall be observed.
6. Documents
8. Component Checklist
INSTALLATION QUALIFICATION OF PAGE 6 OF 17
COLD ROOM
Room 1-
13350mm (W) x 68080 (D) x
9000mm (H)
Room size in
1
meter Room 2-
20650mm (W) x 68080 (D) x
9000mm (H)
2 Prefabricated Construction
Type of
PIR
insulation.
Cold room-Wall: 100 mm &
Ceiling:80mm.
Thickness of
insulation Stagging room- Wall & ceiling:
80mm
Sr. Remarks
Item Required Observation
No.
High speed Door-8 Nos / Sliding
3 Type of door Door- 1 Nos/ /Passage care door-
9/Emergency door- 2 Nos
HSD 3 M X 5 M - 6 Nos
HSD 3 M X 4.4 M - 3 Nos
Sliding door- 2 X 2.4 Mtr - 1 Nos
Size of door
5
clear opening Passage care door- 0.9 M x 2.1 M
- 9 Nos.
Emergency door- 0.9 M x 2.1 M -
2 Nos.
Type of
6 WALL
mounting
7 No. of doors 21
10 Compressor
Make Emerson
Type Hermetic-Scroll
No. of Cold room - 4 Working
compressors Stagging room- 3 Working
Refrigerant R410A
Total cooling
capacity/each 8.5TR - 4 Nos & 11 TR- 3 Nos
Circuit
Compressor
415+/-5%
motor voltage
Compressor
50 Hz
frequency
Control Panel Microprocessor based controller
Coldroom- DSA1021R3-OA/ Air-
Compressor Cooled
model no Stagging room- DSA1321R3-OA
/ Air-Cooled
11 Condenser
12 Evaporator coil
Cold room- BLUECOLD/BLC 455
M.2
Make / Model Stagging room-
Bluestar/DSA1321R3-IA
Tube/Fin
Copper / Aluminum
Materials
No. of Cold room - 4 Working
Evaporators Stagging room- 3 Working
No. Fins 6 per Inch
13 Electrical Data
Compressor
25A , TP, 415VAC
Contactor
MCB main 40Amp
14 HP / LP Switch
Type Auto
LP : 0 to 35 Psig
Range
HP : 0 to 400 Psig
Remarks:
INSTALLATION QUALIFICATION OF PAGE 10 OF 17
COLD ROOM
Make SUBZERO
Accuracy + 1 oC
16 Temperature sensor
Quantity/Unit 04
Type NTC
Accuracy + 1 °C
Type Axial
Discharge
Free
Type
No. Fans / unit 02
Remarks:
Sr. Remarks
Item Required Observation
No.
18 Condenser Fan Features
Type Axial
Discharge
Free
Type
No. Fans / unit Cold room-02
Remarks:
Sr. Remarks
Item Required Observation
No.
22 Safety Features
Remarks:
9. Installation Checklist
Sr. Observation
Requirement Remarks
No. Complies
The floor area shall be free from all
1
dust and debris.
Wall panels are then erected starting
with the corner wall panel and
2
successive panels are then assembled
by locking
Silicon sealant shall then applied on
3 the ceiling and wall panel joints to
ensure sealing.
The inside room corners [wall to wall]
4 and [wall to ceiling] are then fixed
with PP / PP angles.
Remarks:
Sr. Observation
Requirement Remarks
No. Complies
The condensing unit shall be located
1
outside, plat form.
The evaporator unit shall be
2 suspended on the ceiling of the cold
room.
The inter connecting refrigeration
piping shall be carried out with
suitable diameter copper pipes as
3
described below:
Suction Line - 1- 1/8"
Liquid Line - 1/2”
The suction line piping shall be
4 insulated (16mm) for the better
performance of the cold room
The piping shall be supported /
5
clamped on proper supports.
Remarks:
Remarks:
____________________________________________________________________
____________________________________________________________________
____________________________________________________________________
____________________________________________________________________
____________________________
11. Conclusion:
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
___________________________________________________________
INSTALLATION QUALIFICATION OF PAGE 17 OF 17
COLD ROOM
Planning &
Prepared by B RAVEENRAJ 04.12.23
Execution
Reviewed
Area Manager V RAMESH 04.12.23
by
Engineering &
Reviewed by
Maintenance
OPERATIONAL QUALIFICATION OF
COLD ROOM
OPERATIONAL QUALIFICATION OF PAGE 2 OF 16
Cold ROOM
Table of Contents
1. OQ Pre approval 3
3. Responsibility 5
5. Safety Checks 8
7. Results 14
9. Documents 14
11. Annexure 14
13. Conclusion 15
14. OQ Approval 16
OPERATIONAL QUALIFICATION OF PAGE 3 OF 16
Cold ROOM
1. OQ Pre approval
Planning &
Prepared by B RAVEENRAJ 04.12.23
Execution
Engineering &
Reviewed by
Maintenance
3. Responsibility
Quality Assurance:
Engineering:
To review OQ document
To review OQ report.
Production:
To review OQ document
To review OQ report.
OPERATIONAL QUALIFICATION OF PAGE 6 OF 16
Cold ROOM
Performed By
Sr. No Test Acceptance Criteria Observation (signature and
date)
Charge the refrigerant up
Charge the to 5 PSIG to equalizing
1
refrigerant pressure throughout the
system
Check the health of the
Check the control
2 control fuse provided in
fuse.
the control panel board.
The compressor
Check the
connection should be
3 connection for
removed at the time of
compressors I & II
idle charging.
Check the contactors
provided in the control
Check the
4 panels and ensure those
contactors
are healthy and properly
working.
Check the Ensure that the rotation of
5 evaporator and the fans is in the correct
condenser fans directions.
Reconnect the compressor
Start the terminals and start the
6 compressor systems. Note the Ampere
of the compressor at
starting and running.
7 Refrigerant Slowly charge the
charging refrigerant and monitor
the variation of pressure
in the gauges. Continue
the charging until the
recommended
discharge/suction pressure
achieved.
The unit will run along with
the compressor until the
8 Run the unit set point in the
temperature controller is
achieved.
Check the vibration The vibration / noise in
9 and noise of the the system to be checked
systems.
OPERATIONAL QUALIFICATION OF PAGE 7 OF 16
Cold ROOM
Performed By
Sr. No Test Acceptance Criteria Observation (signature and
date)
Check the sweating in the
return/ suction line. If not
Check the sweating
10 sweating, top up the
in the return line
refrigerant a little.
Remarks:
5. Safety Checks
Performed By
Sr. No Parameters Acceptance Criteria Observation (signature and
date)
Safety
1 Hooter fixed
Hooter
Enter into the Cold room.
Ask somebody to close the
Door Closing
door from outside. Door
2 system
should be opened from
inside.
Close the liquid line valve. :
3 HP Trip
HP switch should trip.
Remarks:
Pre checks:
Objective: This is to ensure that all the requirements are met before starting the activity.
Procedure:
1. Ensure that there is no disturbance in power supply and the equipment under study is in working
condition.
2. Ensure the calibration of the inbuilt temperature sensors and the temperature controller are done
before the start validation activity or are within valid calibration period.
3. Ensure the all data logger (Fourtec) is in calibrated state.
Procedure:
Calibrated Temperature sensors are placed as per the table provided (Refer Annexure-01).
Set the data logging interval in data logger as 5 Min.
Purpose: To verify that Temperature in the empty cold room is uniformly distributed for a period of 24
hours.
Procedure:
Purpose: To verify that Temperature in the loaded cold room is uniformly distributed for a period of 24
hours.
Procedure:
Purpose: To verify the cold room is capable of recovery to the acceptable limit after the power failure
and find out the recovery time.
Procedure:
Power failure study is done after the completion of temperature mapping study of refrigerator/cold
room.
Ensure that the refrigerator/cold room chamber is in loaded condition.
Switch off the power supply for a period of 10 minutes or up to one sensor goes out of range
whichever is earlier.
Log the temperature in the data logger for every 30 sec during the power failure period.
Switch on the power supply after 10 minutes or after the first sensor goes out of range whichever is
earlier.
Monitor the temperature until all the sensors at various locations achieves the temperature within the
acceptance range (+15 °C to +25 °C).
Analyze the temperature data to evaluate the performance of equipment during the power failure
period and find out the recovery time.
Set Temperature: +20°C
Acceptance Criteria : The Recovery time for all the sensors should be documented in the
report.
Observations:
Purpose: To verify the cold room is capable of recovery to the acceptable limit after keeping the door of
the cold room open / close and find out the recovery time.
Procedure:
Door opening study is done after the temperature mapping study for refrigerator/cold room.
Ensure that the refrigerator/cold room chamber is in loaded condition.
Open the cold room/refrigerator door for a period of 10 minutes or up to one sensor goes out of range
whichever is earlier.
Log the temperature in the data logger for every 30 Sec, during the door opening study period.
Close the door after 10 minutes or after the first sensor goes out of range whichever is earlier.
Monitor the temperature until all the sensors at various locations achieves the temperature within the
acceptance range (+15 °C to +25 °C).
Analyze the temperature data and find out the recovery time. Time taken by cold room/refrigerator to
achieve temperature of acceptance range (+15 °C to +25 °C) at all sensor locations.
Record the details of the study in the report.
Set Temperature: + 20°C
Acceptance Criteria: The Recovery time for all the sensors should be documented in the
report.
Observations:
7. Results
Cold room temperature observation shall be verified through Data Logger for the refrigeration
system.
8. Records and Certificates
The supporting reports shall be attached to the document and records shall be observed.
9. Documents
11. Annexure
13. Conclusion
OPERATIONAL QUALIFICATION OF PAGE 16 OF 16
Cold ROOM
Planning &
Prepared by B RAVEENRAJ
Execution
Engineering &
Reviewed by
Maintenance
COLD ROOM:
The setting of the controllers should not be changed. There is no user friendly parts for service. Always
contact Blue star service team for service.
Page 1 of 1
KRM Plaza, nd Floor, No. 2, 2, Harrington Rd, Chetpet, Chennai, Tamil Nadu 600031
Date: 11.12.2023
CERTIFICATE OF COMPETENCY
This certificate is presented to Mr. B. RAVEENRAJ has met the requirement of PUF PANEL ROOM
CONSTRUCTION by satisfactorily demonstrating compliance with relevant technical standards.
Certified By
Ramesh Venkatasamy
Area Manager - Cold Storages
Commercial Refrigeration Business Group
ESCALATION MATRIX:
The service call has to be logged through Toll Free number or by Blue star customer
service App, so that automatically email & SMS will be sent to respective Service in
After Handing over a unique number is created by Blue star called I-Base number. This
number has to be given at all times for logging a service call, by which site address &
1. Service call can be logged through our Blue star customer care App, which can be
2. Service call can be logged through our Toll Free: no:1800 2091 177, 1860 2666
666.
has to be logged
Page 1 of 1