Product information Fr. Sauter Ltd.

, CH-Basle
Product information
Information produit
englisch (GB) - e / DoNo.: D100005167 Release date: 16.02.2007

EY3600 novaPro Open Suite 2.2

Release of novaPro Open 2.2

Version 2.2 of novaPro Open is now on sale and can be ordered from stock at
SBA with immediate effect.

Information on how to order can be found in:

Price notification No. 07-782


PDS 99.410 YZP 410, 416-422: EY3600 novaPro Open

LIST OF CONTENTS
1. Ordering information ........................................................................................................... 3
2. Contents of novaPro Open Suite 2.2 .................................................................................. 3
2.1 CD No 1: novaPro Open Suite 2.2 ......................................................................................... 3
2.2 CD No 2:................................................................................................................................ 4
2.3 Cluster ................................................................................................................................... 4
3. New features of novaPro Open Suite 2.2............................................................................ 5
3.1 Calling up the multiple tag list in novaPro Open Studio .......................................................... 5
3.2 AAM user time table in the web.............................................................................................. 6
3.3 User administration shift planner in the web........................................................................... 6
3.4 Alarm definition: action on alarm ............................................................................................ 7
3.5 The 'Inhibit alarm' page in the national language.................................................................... 7
3.6 Alarm objects in pictures support alarm filters ........................................................................ 7
3.7 Alarm template....................................................................................................................... 8
3.8 Context .................................................................................................................................. 8
3.9 Support of ActiveX elements in pictures................................................................................. 9
3.10 BACnet generation – Object Generator................................................................................ 11
3.11 Object Generator Wizard ..................................................................................................... 13
3.12 Tag and Alarm Editor ........................................................................................................... 15
4. List of fixes......................................................................................................................... 16
5. System requirements......................................................................................................... 17
pi_07-186e_SCP / D-ID: 443004 R.: 04 / V.: 01 1 / 20
5.1 Hardware ............................................................................................................................. 17
5.2 Software .............................................................................................................................. 17
6. Known problems................................................................................................................ 18
7. Installation.......................................................................................................................... 18
7.1 Pre-conditions...................................................................................................................... 18
7.2 Installing novaPro Open Suite 2.2 on a PC ......................................................................... 19
7.3 Installing novaPro Open Suite 2.2 in a network.................................................................... 19
8. Updating project data ........................................................................................................ 20
9. Documentation................................................................................................................... 20
10. Training .............................................................................................................................. 20
11. FAQs ................................................................................................................................... 20

D-ID: 443004 Rev.: 04/Vers.: 01 2/20


DoNr. D100005167
1. Ordering information
novaPro Open 2.2 can be ordered from stock at SBA under Order Nos.
YZP410F001, YZP410F101, YZP410F201 and YZP410F304.

Please note:
Use version upgrade
YZP 420 F003 to upgrade from V2.1 to V2.2
YZP 420 F004 to upgrade from V1.x or V2.0 to V2.2

2. Contents of novaPro Open Suite 2.2


2.1 CD No 1: novaPro Open Suite 2.2
novaPro Open Suite is an application generator. This means that all the control and monitoring
facilities are already built into the system, and only the project definitions need to be provided by the
application engineer. Minimal computer or programming skills are required.
novaPro Open Suite enables you to integrate your application with your Internet/Intranet network,
promoting real-time Supervisory and Control using real-time graphics and event-driven information
updates from any computing platform. It combines the benefits of SCADA, Java, HTML, the Internet
and BACnet.
¾ novaPro Open 2.2 SCADA system, management level
novaPro Open 2.2 takes advantage of the powerful, pre-emptive, multi-
tasking capabilities of the Windows XP Pro/2000/2003/NT operating
systems and a built-in event-driven mechanism to achieve utmost
performance and data integrity. It also uses its interface mechanisms to
implement clear and efficient visualization of its components.
¾ novaScheduler 2.2 Scheduler, operable via web browser
novaScheduler 2.2 the new generation Internet -based Scheduler
enables you to create daily or weekly task-orientated schedules
remotely. Accessed through an Internet browser or by clicking on an
icon, the Scheduler is extremely user friendly, efficient and economical.
Being both task and time orientated the Scheduler can be used to
create unlimited tasks, actions and states. Tasks can be modified,
enabled/disabled and have many states such as On/Off attached to
them. An unlimited number of actions, which are basic operations, can
be attached to each task.
With option YZP416F311 BACnet Driver it allows you to schedule tasks
for all connected BACnet devices.

D-ID: 443004 Rev.: 04/Vers.: 01 3/20


DoNr. D100005167
¾ novaPLC Soft PLC for Microsoft Windows
novaPLC - CoDeSys V2.3
novaPLC – CoDeSys V2.3 is included in the basic licence of novaPro
Open up to 500 tags. With option YZP421F002 novaPLC can be
extended to 65’000 tags.
AAM Advanced alarm management.
This module is on the CD, but has to be enabled separately, if
applicable, with the YZP 418 F001 licence.
¾ Sauter Components Drivers: EY2400, EY3600, BACnet, LON OPC Server, MBus, Shape
Tools: BACnet Utils, Conv2400, Alarm.prt, Object Generator Wizard
ƒ EY3600 driver Driver for exchanging data with Sauter system EY3600 BMS
ƒ EY2400 and EY2400 These drivers are on the CD, but have to be enabled separately, if
Numotel driver: applicable, with the YZP 416 F101 licence.
ƒ BACnet driver Native BACnet driver (vpiwnbcn.dll) YZP416F311
ƒ BACnet Util BACnet Utilities for testing purposes.
WizReport XL Reporting Tool (requires the YZP423F001 licence)
CONV EY2400 2.2 Auxiliary program for automatically converting the EY2400 address
area into the novaPro Open address area. To do so, the addresses of
the control centre should be exported into a TXT file using the
‘V PRO AD’ command. The program reads the TXT file and creates
CSV files for importing into novaPro Open.
2.2 CD No 2:
¾ Cluster Library with over 160 symbols for making plant schematics for HVAC
applications
¾ Documentation novaPro Open 2.0 User’s manual I + II
¾ Project Template novaPro Open project template with symbol libraries for all Sauter
systems such as EY3600, EY2400 and BACnet
¾ EY2400 Web Time Fully browser-based tool for configuration of EY2400 time
programme V2.2 programmes.
¾ EY3600 Web Time Fully browser-based tool for configuration of EY3600 time programmes
programme V2.1 SR1 and AS-based calendar functionalities.

D-ID: 443004 Rev.: 04/Vers.: 01 4/20


DoNr. D100005167
3. New features of novaPro Open Suite 2.2
novaPro Open 2.2 is a full version and requires dongle version 930 (novaPro Open Suite 2.2).
Former novaPro Open releases can be updated to novaPro Open 2.2 with the options YZP 420 F003
and YZP 420 F004. Please see PDS and Price Notification.
If version update 2.2 is ordered using order no. YZP 420 F00X, a CD with version 2.2 will
automatically be supplied. The latest novaPro Open Suite 2.2 CD can be ordered using type no.
YZP420 F999.

3.1 Calling up the multiple tag list in novaPro Open Studio


The tag table in novaPro Open Studio for displaying and modifying on-line values for novaPro Open
tags has been replaced by the more convenient multiple tag list.
The multiple tag list can now be called up directly from within novaPro Open Studio, and also from
within novaPro Open pictures using a trigger object.

Advantages:
o Uniform appearance when working with lists in a novaPro Open application.
o Calls are made via dynamic tag filters. Thus it is possible to install one tag filter for
each plant or section. Selecting the desired filter will exclusively display data points
from the desired plant or section.
It allows convenient operation of the novaPro Open application via plant-specific data
point lists.
o You now have direct access to all the parameters for tag definition from the tag list
with on-line data on call from the novaPro Open Studio.
o Tag address and sampling rate
o Activating or deactivating tag reading.
o Forced reading of every tag displayed in the list.

Fig. 1: Calling up the Tag List from the Studio

Fig. 2: Previous presentation Fig. 3: New presentation

D-ID: 443004 Rev.: 04/Vers.: 01 5/20


DoNr. D100005167
3.2 AAM user time table in the web
The alarm user time table now has a web-enabled, Java-based user interface.

Advantages:
o Remote configuration and operation of the user time table from any PC in the network
using Internet Explorer.
o The user time table can be called up from within a novaPro Open picture via a trigger
object with the URL: http://PCname/docs/UsersTimeTable.html

Fig. 4: User time table

3.3 User administration shift planner in the web


The user administration shift planner now has a web-enabled, Java-based user interface.

Advantages:
o Remote configuration and operation of the user time table from any PC in the network
using Internet Explorer.
o The user time table can be called up from within a novaPro Open picture via a trigger
object with the URL: http://PCname/docs/ShiftManagement.html

D-ID: 443004 Rev.: 04/Vers.: 01 6/20


DoNr. D100005167
3.4 Alarm definition: action on alarm
When setting a picture jump in the
alarm definition window, in addition to
the picture itself it is now possible to
set the window (*.vim) in which the
picture will be opened.
It is also possible to determine a tag
context when pictures are called up.

Fig. 5: Determining 'Window' and 'Context'

3.5 The 'Inhibit alarm' page in the national language


The 'Inhibit alarm' web page (Inhibit.asp) is
now available in the various national
languages.

Fig. 6: Example: German

3.6 Alarm objects in pictures support alarm filters


It is now possible to animate alarm
objects in pictures in dependence
on the result of an alarm filter.

Advantages:
o Easy visualisation of batch
alarms in pictures.
o You can simply copy alarm
filters (AFM.XML) from one
application (project) to
another project.

Fig. 7: Selecting an alarm filter

D-ID: 443004 Rev.: 04/Vers.: 01 7/20


DoNr. D100005167
3.7 Alarm template
A context can now be used for selecting a
filter in the filter definition for an event
window. This allows the display of various
context-dependent alarms in the event
window.

Fig. 8: Alarm filter selection with context Fig. 9: Calling up an event window via a trigger object
from within a picture with context details.

3.8 Context
The tag context for pictures and trends was introduced with novaPro Open 2.1. The tag context
enables the efficient generation of group pictures.
novaPro Open 2.2 also allows the use of context in event windows and alarm objects via alarm filters,
and in the tag list (Tag Lock) and analysis via tag filter.
JavaAPIs are available for Java programmers:
o changeLayoutContext(context)
o ChangeContext(window, context)
o loadPicture(window, image, context)
Advantages:
o Allows you to call up a specific alarm list for each room in group pictures (hotel rooms). You
only need to generate one alarm list.

Fig. 10: Using 'Context'

D-ID: 443004 Rev.: 04/Vers.: 01 8/20


DoNr. D100005167
3.9 Support of ActiveX elements in pictures
What is an ActiveX?
An ActiveX is a small program (usually a dll or ocx file) with a graphic user interface. The graphic
user interface can be integrated in a novaPro Open picture.
ActiveX elements are either supplied by a third party and will enable specific functions, or
programmed using a C++, VB, Java or .Net development environment.

ActiveX elements available in novaPro Open must be listed in the file ActiveX.ini.

Fig. 11: ActiveX.ini file

Embedding the Windows Media Player in a novaPro Open picture:

Fig. 12: Windows Media Player as ActiveX

Enter the video file to be played by default when the picture is opened under 'Default file'. You can
also use a novaPro Open tag to dynamically send the video file to Windows Media Player.
To do so, create a dummy tag of the type 'String'. You can now assign the name of the video file to
the tag.

Application example:
Allocate the file to be played as an instruction for the user in the event of an alarm to the 'Video' tag.

D-ID: 443004 Rev.: 04/Vers.: 01 9/20


DoNr. D100005167
Embedding the Web Explorer in a novaPro Open picture:

Fig. 13: Web Explorer as ActiveX

Enter the website to be opened by default when the picture is loaded under 'Default URL'. You can
also use a novaPro Open tag to dynamically send the URL to the Web Explorer.
To do so, create a dummy tag of the type 'String'. You can now assign the URL to the tag.

Embedded Windows Media Player


Embedded website for
displaying current weather
data

Fig. 14: Example of a novaPro Open picture with embedded Media Player and Web Explorer

D-ID: 443004 Rev.: 04/Vers.: 01 10/20


DoNr. D100005167
3.10 BACnet generation – Object Generator
Advantages:
o On-line generation of BACnet objects.
o Off-line generation of BACnet objects from EDE files. An on-line connection to BACnet
stations is now no longer required for setting the parameters for a novaPro Open BACnet
application. This makes engineering easier, especially in multi-vendor projects. The exchange
of data with the BACnet stations to be integrated occurs via the standardised data exchange
format EDE.
o View (Preview) of imported data points and alarms prior to definitive adoption

Data generated automatically by the Object Generator:


o The Object Generator automatically scans the network for connected BACnet automation
stations and generates the tags for novaPro Open and corresponding lists with the BACnet
State Texts for multi-stage switching commands.
o The Object Generator automatically generates the Alarm Rules required for BACnet together
with the corresponding alarm filters.
o In addition to on-line generation, the Object Generator will also allow you to import BACnet
objects via an EDE file.

Fig. 15: BACnet object selection

D-ID: 443004 Rev.: 04/Vers.: 01 11/20


DoNr. D100005167
Illus. 16: Rules for naming tags Fig. 17: Preview of created tags

Fig. 18: Rule for creating alarms Fig. 19: Preview of created alarms

Variables permitted in dialogues Illus. 16: Rules for naming tags and Fig. 18: Rule for creating
alarms:
%DevInst%
%DevName%
%ObjType%
%ObjTypeName%
%ObjInst%
%ObjName%
%PropId%
%PropName%
%Description%
%KeyName%
%Counter%
Enter '%' – this will display a selection list of the variables %EventTypeName%
available. %EventStateName%

Fig. 20: Variables permitted in dialogues, Fig. 16: Rules for naming tags, and Fig. 18: Rules for creating
alarms

Start the Object Generator from the Windows Start Menu:


Menu 'Start/Programs/novaPro Open/Utilities/ObjGenerator

D-ID: 443004 Rev.: 04/Vers.: 01 12/20


DoNr. D100005167
3.11 Object Generator Wizard
The new 'Object Generator Wizard' enables the import and automatic creation of novaPro Open tags
for data points of the EY3600 system. The data points are imported directly from CASE FBD or
CASE Engine. It is not necessary to first export the data points as a BMTL_Export.
The 'Object Generator Wizard' replaces the conversion program 'CONV EY3600' used up until now.

An EDE file can be created directly from CASE FBD or CASE Engine data for projects in EYK220,
EYK230 or EYK300.
The EDE file in BACnet projects serves the exchange of data between automation level and
management level. The EDE file permits the parameterisation of the management level without
having to create an on-line connection to the automation stations (see also 3.10)

Advantages:
o Import direct from CASE FBD or CASE Engine project data without previously exporting the
date in an intermediate format.
o Generation of the novaPro Open tags for EY3600 novaNet
o Generation of the novaPro Open alarms for EY3600 novaNet
o Generation of the EDE file for EY3600 BACnet
o Automatic generation of tag filters based on the house address structure. Tag filters are used
in the 'Tag Table', 'Multiple Tag List' to display a plant address list. 3.1 Calling up the multiple
tag list in novaPro Open Studio
o Automatic creation of novaPro Open text tables (*.tbl), for instance to display comparators as
text. A *.tbl is created automatically for multi-stage switching commands based on the
definitions in CASE.
o Automatic creation of alarm filters (see also 3.6 Alarm objects in pictures support alarm filters,
3.7 Alarm template)
o View (Preview) of imported data points and alarms prior to definitive adoption

Data generated by the Object Generator Wizard is stored under UCVT_Data in the project directory.
Example when using the Project Template: D:\EY3600\Hotel Bellevue\Private_Data\UCVT_Data

D-ID: 443004 Rev.: 04/Vers.: 01 13/20


DoNr. D100005167
The 'Object Generator Wizard' is called up from the Quick
Access Bar in novaPro Open Studio.

Fig. 21: Call-up from Studio

Fig. 22: 3.11.2 Import of EY3600 novaNet data points from


CASE FBD or CASE Engine and preview of generated tags

Fig. 23: Import of EY3600 novaNet data points from CASE FBD or CASE Engine and preview of
generated alarms

Fig. 24: Import of EY3600 novaNet data points from CASE FBD or CASE Engine and preview of the
BACnet EDE file

D-ID: 443004 Rev.: 04/Vers.: 01 14/20


DoNr. D100005167
3.12 Tag and Alarm Editor
The new Tag and Alarm Editor in novaPro Open makes editing tags and alarms more efficient.
It is now possible to conveniently perform the following frequent tasks using a list view.
o Supplementing or changing tag descriptions and alarm texts
o Adding or changing user rights for tags and alarms
o Supplementing or changing attributes such as, for instance, 'record historically', DDE, etc.
o Supplementing or changing driver addresses
o Changing assigned drivers
o Supplementing or changing the notification group in the event of alarms
o Allocation of Help files to alarms
o Creation of the definitions file ZP3600.ini for the graphic time programme ZP3600_Web.
o etc.

Advantages:
o Efficient modification of properties of a large number of tags or alarms.
o The 'Export, process with Excel and re-import' method used to date no longer applies. Data is
modified directly in the novaPro Open database.
o Reduction of work steps required to modify tag and alarm properties.
Ö More efficient, i.e. faster and safer method of working.

The 'Tag and Alarm Editor' is called up from the Quick


Access Bar in novaPro Open Studio.

Fig. 25: Call-up from the Studio

Fig. 26: Tag Editor Fig. 27: Alarm Editor

D-ID: 443004 Rev.: 04/Vers.: 01 15/20


DoNr. D100005167
Fig. 28: Creating the configuration file ZP3600.ini

4. List of fixes
BACnet:
2006/1334 nPO repeats Read-Range all the time without end.
2006/1271 BCC: No way to cancel when reading object.
2006/1249 BCN is blocked, if you poll non available device.
2006/1218 Event_Notification are ignored by nPO.
2006/1217 No 'Remove_List_elements' after shut-down from nPO.
2006/1216 BCC: property Device 'active_cov_subscritions'
2006/1136 CHANGE_OF_BITSTRING event type algorithms
2006/1099 Trending & name-based address format
2006/1029 The WebScheduler does not check the Bacnet error Message.

novaNet Driver EY3600:


ECR 2908: When a read on NOVANET tag is forced, the tag falls in error status.
ECR 2909: Tag $ALARM is set to error state, in case of replugging the bus.
ECR 2910: Description of tag DA, value 10 has to be removed
Module: vpis36.hlp version 6.9.7.0 38904
ECR 2911: Description of tag NDA has to be added.
Module: vpis36.hlp version 6.9.7.0 38904
ECR 2918: Description of tags IFG, TIME_OUT, MAX_INIT_TIME, MODEM, TIME_RING_OFF
have to be defined more precisely.
Module: vpis36.hlp version 6.9.7.0 38904
ECR 2919: Adding a filter on station connection/disconnection.
ECR 2951: If an AS is disconnected from the BUS, we get a popup each minute.
ECR 2952: On HI tag, add possibility to define :N in order not to read
automatically the history databank when it's full.

EY2400:
ECR 3367: S24 driver is modified to run on Master/Backup architecture.

OPC:
ECR 2569: When you start the Wizcon client OPC with a wrong server name in COM
start-up takes a long time.
ECR 3297: On reconnection with the DEF OPC Server, our OPC client is not notified
anymore and values are frozen.
Applicom:
ECR 3314: Dual sampling on Master/Backup application with Applicom driver.

General:

D-ID: 443004 Rev.: 04/Vers.: 01 16/20


DoNr. D100005167
ECR 3125: Loading a chart can crash Wizcon (Message in errors.dat :VFI5FST: Error,
SearchBoundRecordFromFile.......)
ECR 3148: When editing properties of a cluster in nPO 2.1 and selecting the object
again sometimes the image freezes.
ECR 3206: Not possible to use '#' in text tables.
ECR 3255: French translation errors.
Module: WizSQL Version 9.3.0.18 15/12/2006
ECR 3261: Wizpro uses 100% CPU, if scheduler has been activated and there is no
plug.
ECR 3268: Wrong translation in event-summary (status filter) German.
ECR 3274: Wrong translation in Wpack French version.
ECR 3292: Using Tags Export tool when adding multiple Tags at the same time the
station name is not added anymore.
ECR 3295: With nPO 2.2 tags updated by add-ons are not refreshed in nPO studio.
ECR 3299: Not possible to install Wizcon if CAA is already installed.
ECR 3303: When using SQL Server for Audit Trail after inserting more then around
5000 records a 'GoTo Zone' is very slow.
ECR 3317: Custom action consume one handle each time a right click is executed on
an Image object.
ECR 3321: Aladin plug from version 5.* can not be upgrade to version 9.2.
ECR 3343: Month and Day of Alarm is not clearly spoken when using Vocal service in
AAM.

5. System requirements
Before you install the application, verify that you have the following:-
5.1 Hardware
Processor: Pentium III 800 MHz (recommended 1 GHz and up)
RAM: 256 MByte RAM (recommended 512 MB)
Hard disk: at least 1.8 GB (9 GB recommended, depending on size of
system)
Monitor adaptor 32 MB
Monitor resolution 800x600 or higher
Display: VGA, SVGA, or any graphic adaptor that supports the
operation system desktop. Colour depth should be at least
256 colours.
CD reader: for the installation
Ports: 1 mouse
2 serial RS-232
1 network connection
1 USB port for dongle
5.2 Software
Operating system: Microsoft's Windows NT 4.0 SP6a, Windows 2000 SP4,
Windows XP SP2 or Windows 2003 Server
Correctly configured TCP/IP: IP address can be fixed or provided by a DHCP server,
except for HotBackup stations and web server which should
have a fixed IP address set manually.

D-ID: 443004 Rev.: 04/Vers.: 01 17/20


DoNr. D100005167
Microsoft Internet Explorer: Use Internet Explorer 5.5 with SP2 or Internet Explorer 6.0.
If you use the latter, ensure that Java Virtual Machine is also
installed: SUN JAVA plug-in version 1.4 (recommended
1.4.2_03)
HTML editor Any HTML editor may be used. (Optional)
Internet information server Under Windows XP, use IIS 5.1 (which can be installed from
(IIS): Control Panel/Software/ Add Remove Windows Component)
Under Windows 2000, use IIS 5.0 (which is on the CD for
Windows 2000)
Under Windows NT 4 SR6, use IIS 4.0 (IIS4.0 can be
downloaded from www.microsoft.com).

6. Known problems
• Before installing the current version of the product, always uninstall the currently installed
version from your computer.
• In the rare event that you cannot uninstall novaPro Open from the Control Panel 'Add/Remove
Programs', uninstall it with help of the file Setup.exe from the location where you performed
the installation (i.e. from the CD or a local folder).
• There are a number of online Help subjects that appear in English only.
• Advanced Alarm Management: Backup User option does not function.
• Image: when a metafile .EMF or .WMF is imported to the Image module text conversion is not
supported during the file’s conversion.
• In the rare event that you cannot launch novaScheduler, you must give write access control to
the Internet Guest Account 'IUSR_<<computer name>>' in the novaPro Open application
folder where the file WebScheduler.mdb is located

7. Installation
7.1 Pre-conditions
• Before you start the installation of novaPro Open, ensure that the operating system, the
internet information server (IIS) and Microsoft’s Internet Explorer have been installed.
• Backup your project data
• Backup the INI-files from AAM as followed:
e.g. Email.ini
ermes.ini
Fax.ini
Jericho.ini
Pager.ini
tap.ini
These files can be found in:
C:\Program\Sauter\EY3600\novaPro_Open Suite\novaPro Open\Bin
• Deinstall any older versions of novaPro Open before starting the installation, and save your
project data.

D-ID: 443004 Rev.: 04/Vers.: 01 18/20


DoNr. D100005167
• Copy your AAM INI-files (Email.ini. ermes.ini...) into
C:\Program\Sauter\EY3600\novaPro_Open Suite\novaPro Open\Bin

Change the path of AAM configuration files:

The file 'Jericho.cfg' can be found in the folder C:\Program Files\Sauter\EY3600\novaPro Open\Bin .
The file is empty by default.
Add the path of your project data:
e. g.: D:\EY3600\SkyTower\Private_Data

From now on, all configuration files with extension *.ini are saved in your project folder.

7.2 Installing novaPro Open Suite 2.2 on a PC


CD No 1:
ƒ Insert the program CD into your CD-ROM drive. After a few seconds, the following window
opens (assuming Autostart has not been deactivated):-
ƒ Start the installation of novaPro Open Suite by pressing the 2.2 button. Follow the instructions
given by the installation program.
CD No 2:
ƒ Install ZP2400web and ZP3600web
ƒ Install the documentation

Fig. 29: Installation CD 1 Fig. 30: Installation CD 2

7.3 Installing novaPro Open Suite 2.2 in a network


Please note that, in a novaPro Open network, all the network computers should always be using the
same version.

D-ID: 443004 Rev.: 04/Vers.: 01 19/20


DoNr. D100005167
8. Updating project data
To update your project data automatically with the help of 'appupdate”, proceed as follows:
1. Make a back-up copy of your project data
2. Start your application
3. Start appupgrade.exe
from C:\Program Files\Sauter\EY3600\novaPro_Open Suite\novaPro Open\Utilities– Java classes
are automatically updated
– All viewports are saved
– All HTML-files are updated
4. For information on the upgrade of your novaPLC application please refer to the dedicated
documentation for this topic on the CD.

9. Documentation
novaPro Open Suite 2.1 has an extensive, integrated, online help function. In addition, the user’s
manuals I + II 2.0 are provided on the CD as PDF files.

BACnet PICS and BIBBS have all been updated and are available on Sauter-Intra for downloading.

10. Training
Training courses on novaPro Open are held regularly at SBA. For the exact dates, please consult
Sauter's training schedule.

11. FAQs
Answers and possible solutions to frequently-asked questions can be found in the Sauter Intr@net at:
https://www.sauter-intra.ch/download/documentation/faq_36novaproopen_001.pdf.

Peter Schoenenberger
Product Manager

D-ID: 443004 Rev.: 04/Vers.: 01 20/20