COMPRESSOR
REPLACEMENT INSTRUCTIONS
BEFORE BEGINNING: CONTROL SIGNAL:
• Check if the system is not energized. Check what type of control signal is used in the original inverter.
To do so, check the Embraco code of the inverter located on the label (as
• Disconnect the system from the outlet before executing any type of
shown below) and check the list available on pages 08 through 11 to see
check or maintenance;
the control signal type.
• Never, under any circumstances, try to energize the Embraco Fullmotion
compressor with direct voltage from the network (“direct start”). This will
permanently damage the compressor;
VOLTAGE:
Check what the voltage of the original inverter which is installed in the
system is. The voltage can be checked on the label located on the inverter, as The inverter to be installed must contain the same control
shown on the image below: signal and inlet voltage features as the inverter originally used in the
system. This will ensure the appropriate functioning of the product.
With the control signal and inlet voltage information, check in the
table below the code of the inverter which must be acquired to execute
the change:
Grounding
3 cable
Power supply
1 cable
Compressor cable
Compressor cable
2 Signal
(Internal CN07) 4. Unscrew and remove the inverter from the system.
cable
2. Remove the inverter cover to have
access to the electrical connections;
Grounding
3 cable
Power
1 supply cable
Compressor cable
Fastening point
Fastening point