Digsilent: Application Guide
Digsilent: Application Guide
Application Guide
Heinrich-Hertz-Str. 9
72810 - Gomaringen
Germany
http://www.digsilent.de
[email protected]
r1035
Copyright ©2013, DIgSILENT GmbH. Copyright of this document belongs to DIgSILENT GmbH.
No part of this document may be reproduced, copied, or transmitted in any form, by any means
electronic or mechanical, without the prior written permission of DIgSILENT GmbH.
Contents
1 Introduction 3
3 Model Description 3
References 8
List of Figures 9
List of Tables 10
1 Introduction
This document describes the photovoltaic system template PhotovoltaicSystem 0.4kV 0.5MVA
that is delivered with PowerFactory 14.1. The template is a generic model for a photovoltaic
system. It represents the grid side converter and the photovoltaic cell (modelled in DSL). The
model represents one photovoltaic system with a rated apparent power of 0.5 MVA it is three
phase connected on 0.4 kV voltage level. The BESS model could be used for
• Balanced and unbalanced simulations (however control is implemented for the positive
sequence only)
For dynamic simulation is a variable step size possible. The minimum step size or the fix step
size should be lower than 5ms.
PowerFactory contains pre-defined templates of dynamic models for different generic wind tur-
bines, photovoltaic generators and a battery energy storing system. Using the templates is
simple, just click on the General Templates button ( ) and select the desired template in the
following window. Thereafter you could place the model in the single line diagram. For this you
have to click one time in the single line diagram, this shows the model connected to the mouse
pointer a second click creates a new model of the selected template in the single line diagram.
Each dynamic model consists of some elements in the single line diagram (mostly a terminal
with a generator) plus a composite model, which is located in the recording grid.
After you placed all models in the single line diagram you have to close the selection window
with the templates, this terminates the template inserting.
Do not delete the terminal to which the generator is connected - this would destroy the mea-
surement points of all measurement devices (located in the corresponding composite model).
You could delete a placed model directly by pressing the undo button ( ) or you could delete
the model also manually. If you want to delete a model manually you have to mind that the
model consists of visible elements in the single line diagram and also of a composite model
which is only visible in the Data Manager.
3 Model Description
The photovoltaic system is in the single line diagram represented by a static generator [1]. The
models of the controllers as well as the photovoltaic cell are collected in a composite model
Photovoltaic System. This composite model for the control could be found either through the
link Plant Model on the Basic Data page of the static generator or with the Data Manger in the
used grid.
The composite model Photovoltaic System is created from the frame definition Frame PV Sys-
tem this frame is shown in Figure 3.1.
The single slots are briefly described in Table 3.1. Each slot could be filled with either a DSL-
model, a measurement device or a PowerFactory element, such as a static generator. All mea-
surement devices are connected either to the terminal or to the cubicle, which connects the
generator with the terminal. This approach ensures that all measurement devices are correctly
connected after entering the model using the template.
You will find in this chapter a description how you could configure the model from the tem-
plate according to your specific needs. The configuration is sorted to the calculation functions
because there are fewer configurations needed for load flow calculation than for a dynamic
simulation.
The model is generic and therefore completely open - you could configure it according to your
needs. Following you will find a short manual for changing some settings of the PV-system. The
PV-system consists in the single line diagram of a static generator (the inverter) and of some
DSL models, all glued together in the composite model Photovoltaic System.
The rated power is for the load flow model only defined by the static generator data. If you
want to change the rated power you have to change this on the basic data page of the static
generator (don’t forget to change also the power setpoint on the load flow page).
The active power is for the load flow model only defined by the static generator data. If you want
to change the active power you have to change this on the load flow page of the static generator
(don’t forget to change also the rated power on the basic data page, point above).
You could also change the nominal voltage of the converter if your PV-system has a different
nominal grid side voltage. The only modification you have to do is changing the nominal voltage
of the terminal to which the static generator is connected.
Note: There is no saturation considered. It is assumed that the DC voltage is all the time high
enough.
The short circuit behaviour of the model is also completely determined by the element settings.
There are therefore no changes in the dynamic model parts necessary. It is important to note
that the standard short circuit methods could not give precise results for a controlled PV-system.
For results that are more precise are dynamic simulations needed.
The main purpose of the model created with the template is of course the dynamic simulation.
The great advantage of using a template for creating the PV-model is that all measurement
points are already correct defined and all common models are already configured.
The model is generic and therefore completely open - you could configure it according to your
needs. Following you will find a short manual for changing some settings of the PV-system.
The rated (peak) power is for the load flow model only defined by the static generator data. If
you want to change the rated power for RMS simulation you have to change this on the basic
data page, on the load flow page of the static generator and in the dynamic model. Open the
composite model Photovoltaic system via the plant model link on the basic data page of the
static generator:
The second row in the composite model contains the PV-array model (this is a model of the
photovoltaic cell). You have to change in this model the number of parallel modules (parameter
nParallelModules) for adjusting the rated power of the whole model. One module has a rated
peak power of 3.2 kW. The initial model has a rated peak power of 448kW - this corresponds to
a numer of 140 parallel modules.
The active power is for the load flow model only defined by the static generator data. If you want
to change the active power you have to change this on the load flow page of the static generator
(don’t forget to change also the rated power on the basic data page, point above). The radiation
is a result of the value entered on the load flow page of the static generator. The radiation is
1000W/m2 if the active power is 3.2 kW per module.
You could also change the nominal voltage of the converter if your PV-system has a different
nominal grid side voltage. The only modification you have to do is changing the nominal voltage
of the terminal to which the static generator is connected.
Note: There is no saturation considered. It is assumed that the DC voltage is all the time high
enough.
You could also disable the reactive current support if the PV-system in your project has not this
feature. The fastest way to do this is to remove or disable the AC voltage measurement:
1. Open the composite model Photovoltaic System. To find the correct composite model (if
you have more than one) you could double click on the static generator in the single line
diagram. On the basic data page is a link to the composite model:
2. Select the Voltage Measurement and either disable the measurement or remove it from
the composite model.
After these changes will the PV system generate all the time the reactive current given from the
load flow initialization.
The PV-model contains also a reactive current support characteristic. This characteristic is
activated during over- or undervoltage conditions (Figure 4.1). The parameter of the deadband
as well as the parameter for the slope (droop) could be changed in the Controller.
1. Open the composite model Photovoltaic System. To find the correct composite model (if
you have more than one) you could double click on the static generator in the single line
diagram. On the basic data page is a link to the composite model:
2. Open in the composite model the Controller and make the changes according to your
needs.
References
List of Figures
List of Tables