WARDPOWER

LVAC Load Survey and


Generating Set Sizing Study
NG Keadby

September 2014

Document Reference: 1203-1743-D11 (A)


WARDPOWER

LVAC Load Survey and


Generating Set Sizing Study
NG Keadby
Executive Summary
An LVAC Load Survey and Generating Set Sizing Study has been undertaken at NG Keadby
to determine if the existing Generating Set and LVAC system are large enough to support
the proposed load for the forthcoming ISS system. The principle conclusions of this work are
as follows:
− The site has existing Generating Set and Transformer supplies rated at 800KVA.
− In assessing the WORST CASE load, it must be remembered that this is a subjective
calculation as to what the worst case diversity of loads for a site could be. Normal NG
policy is apply a diversity of 1.0 for all HV system essential loads and 0.8 for all others. In
this instance, we have also applied the following agreed additional diversity factors:
o General cooling load has been excluded as this is lower than heating load
o Small power has been given a demand factor of 0.1 based on fuse rating
o Reductions for additional water heaters in line with IEE guidance
o All manual motors/tap changers assumed not to be running
o In-rush for UPS/Battery Charger transformers not considered
o SGT cooling load reduced by 1/3 from its maximum
o Quad Booster Shunt Cooler Loads excluded.
The last two provisions are specific provisions made by NG Design Assurance for this
− Based on the above, the site’s existing WORST CASE continuous load was determined
as 672KVA EXCLUDING ISS or Flood Defence Loads or any allowance for future
expansion.
− ISS have proposed an additional load of 131KVA, taking the theoretical worst case load
to 803KVA, excluding flood defence or future expansion. This is larger than either the
mains or Generating Set supplies.
− With the current site loads (excluding ISS/Flood/Future), the existing Generating Set is
theoretically unable to start the second compressor with the first running in the worst
case load scenario as the starting load would exceed the Generating Set’s Peak Power
rating and the transients would also be outside allowable limits.
− With the ISS loads added, the existing Generating Set would theoretically be unable to
start either compressor in the worst case load scenario.
− With the ISS loads added, the Generating Set would also be unable to start any of the
Quad Booster 2 Series Stage Cooling Fans if compressors were running as these would
also mean that the Generating Set would exceed it’s Peak Power Rating.
− Based on all of the above it is therefore concluded that the existing Generating Set and
Tranformer Supplies are not large enough to accommodate the ISS load, the Generating
Set on the grounds of worst case average continuous load, peak power and transient
loads, and the Transformer Supplies based on worst case average continuous load
(remembering that the load level proposed leaves nothing for future expansion).
− It a separate Generating Set is supplied to support the ISS load only, this would need to
be rated at 185KVA.

Document Reference: 1203-1743-D11 (A) Page 2 of 11


WARDPOWER
LVAC Load Survey and Generating Set Sizing Study, NG Keadby

Table of Contents
Executive Summary .............................................................................................................. 2
Table of Contents ................................................................................................................. 3
1. Introduction ..................................................................................................................... 4
2. LVAC Load Survey.......................................................................................................... 4
2.1. Assumptions and Comments............................................................................... 4
2.2 Previous Load Analysis ....................................................................................... 5
2.3 Load Analysis ...................................................................................................... 5
2.4 Provision for Future Loads .................................................................................. 5
3. Generating Set Sizing Studies ........................................................................................ 6
Scenario B1: Existing Site Load ...................................................................................... 6
Scenario B2: ISS Load Only............................................................................................ 7
Release Information .............................................................................................................. 8
Revision History .................................................................................................................... 8
Contact Details ..................................................................................................................... 8
Appendix A: LV Load Survey ................................................................................................ 9
Appendix B: Generating Set Sizing Studies ........................................................................ 10
Scenario B1: Existing Site Load .....................................................................................10
Scenario B2: ISS Load Only...........................................................................................11

Document Reference: 1203-1743-D11 (A) Page 3 of 11


WARDPOWER
LVAC Load Survey and Generating Set Sizing Study, NG Keadby

1. Introduction
An LVAC Load Survey and Generating Set Sizing Study has been undertaken at NG
Keadby to determine if the existing Generating Set and LVAC system are large
enough to support the proposed load for the forthcoming ISS system.
Please remember that this is a calculation of WORST CASE load and may
represent a figure substantially larger than any load experienced on the site.

2. LVAC Load Survey


2.1. Assumptions and Comments
A full Load Survey of the site was undertaken (see Appendix B). Assumptions in
relation to individual or specific loads are given on the survey. The following more
general assumptions/comments are applicable:
− Load Survey has been conducted in accordance with WARDPOWER document
OS733, NG LV Sizing Methods Guidelines, Revision B.
− Where either the number of incidences for a given piece of equipment could not
be determined, or the rating of the equipment could not be determined, an
estimated figure has been used. Typical examples of this would be outdoor
lighting. These loads have marked Estimate.
− Again where either the number incidences or rating of equipment could not be
determined, a known typical figure has been used. Typical examples of this would
be Transformer Tap Changers or Garage Roller Shutter Doors. These loads have
been marked
− Where the number of fittings and load can be identified, this is marked on the
load schedule as “Fixture Count” although in some instance the identification of
load may be generic («looks like a 2KWe heater, assumed to be a 2KW
heater«).
− Any Tap Changers or other intermittent motors on the site (e.g. cranes, roller
shutters, gates) are excluded from the calculation of continual load. The largest
individual of these items, in this case the LARGEST LOAD, is then applied after
all other loads have been applied to ensure that the Generating Set will still be
capable of starting this load.
− Where cooling load is greater than heating load, or vice versa, then the diversity
of the lower load is set to 0 as a logical exclusion. Where air conditioning plant
can be used in either duty, it’s load is considered in both duties.
− In many instances, it was not possible to determine the phase for single phase
loads and as such, sensible assumptions have been made.
− Where motor starting information is not available, DOL start, starting current = 6x
running current, starting power factor 0.4 has been assumed.
− For this site, under guidance from NG Design Assurance:
o The whole of the cooling load for the Shunt units of the Quad Boosters has
been discounted.
o One third of the SGT Cooling Loads have been discounted.

Document Reference: 1203-1743-D11 (A) Page 4 of 11


WARDPOWER
LVAC Load Survey and Generating Set Sizing Study, NG Keadby

2.2 Previous Load Analysis


The following is an excerpt of the original sizing study done for this site in 2003-4:
This set has been sized based upon the PB Power report for Keadby. However, the rating was
confirmed on the basis of a full load test performed on site by Paul Balcon and SAP Pete
Sturmey.
Total steady state load to be applied. The needle on the ammeter recorded for general
loading:
'R' phase 600A (431KVA)
'Y' phase 540A (388KVA)
'B' phase 560A (403KVA)
When the compressor load was applied the needle went up to 900A (647KVA) steady state.
As we have recommended a 750KVA standby diesel system the total steady state load can be
supported.
It should be remembered that this is not a fool proof method as it does not take into
account loads that cannot be manually controlled such as, for example, the charge
state of the batteries. In the case of this site, the battery chargers are calculated as
up to 42KVA of the potential load. Similarly, heating is up to 93KVA of the site load.
How much of either of these would have been present in any test cannot be
determined.

2.3 Load Analysis


From the full load survey described in section 2.1. above the following loads were
determined:
Load (A) L1 L2 L3
Before Diversity 2,017 1,210 1,211
Including Diversity applicable when on Diesel Generator 1,418 751 738
Including Diversity applicable when on Mains 1,480 797 779
Conclusions based on these results are as follows:
− Based on a typical power factor of 0.8, this leads to an estimated load of 672KVA
on Generating Set and 706KVA on Mains Supply. This is before provision for
future expansion or addition of the ISS loads.
− The load is shown as having significant phase imbalance. This is due to the
impracticality of tracing back many of the Relay Room circuits to distribution
phases. Historical meter readings for the site shown unusual phase imbalance
and this is therefore not believed to be an issue for the site.

2.4 Provision for Future Loads


We are advised that the following loads are to be added for ISS (email from Chris
Steenson, 30-Jun-14):
I1 I2 I3
LVAC Room 1 69.2 54.5 61.6
LVAC Room 2 83.9 70.0 165.9
LVAC Room 20.6 20.7 19.0
This equates to a load of 131KVA/104KWe at 0.8pf. This load does not include for
transformer in-rush.

Document Reference: 1203-1743-D11 (A) Page 5 of 11


WARDPOWER
LVAC Load Survey and Generating Set Sizing Study, NG Keadby

It is also known that Flood Defence are to visit this site but no information is available
for the loads for this equipment.

3. Generating Set Sizing Studies


Scenario B1: Existing Site Load
The first scenario that has been considered is the Existing Generating Set against
the Existing Site Load but not including ISS loads and with no other allowance for
future expansion or Flood Defence loads.
From this Sizing Study, the following performance requirements for the Generating
Set were identified:
Worst Case Average Continuous Load 537KWe/671KVA
Peak Power 708KWe – 133% load
This is at 30s upon start of
Compressor 2, SGT Bank 2 Cooling,
Quad Booster later stage cooling.
Largest Transient Load 574KWe
Upon application of standing load.
Largest Transient 13.5% Frequency (Limit is 10%)
33.1% Voltage (Limit is 15%)
Conclusions based on these results are as follows:
− Based on the above, the determining sizing characteristic is seen to be peak
power
− Based on the above, the existing Generating Set would not be able to deal with
the existing worst case site load.
− It can be seen from this scenario that the starting loads of the two compressors
(285KWe and 266KWe) are a significant proportion of the sets rating (44% and
42% respectively). As the remainder of the existing site load excluding the
running load of these compressors is 442KWe then it can be seen that starting
either one compressor with the remainder of the standing load present would
take the set to 708KWe (in the case of the smaller one) against peak power for
the set of 708KWe. Starting the larger one would therefore exceed this. Starting a
second compressor when the first compressor was already running would
definitely exceed the maximum peak power rating of the set.
− If the ISS load of an additional 104KWe was added to the set then the same
position would exist but worst with a worst case continuous load of 546KWe.
Consequently, theoretically, the Generating Set would be unable to start either
compressor. In addition, the Quad Booster Series Stage Cooler Loads are
156KWe, so set would also be perilously close to being unable to start these
without exceeding its peak power limit (a 702KWe peak v a 708KWe limit) and
would not be able to start these if either compressor was running.
− From all of the above, it can be seen that the Existing Generating Set is not
capable of supporting the proposed existing worst case load plus the new ISS
load.
The following comments are applicable:
− Transient Performance is calculated in line with the requirements of NG
Engineering Bulletin 23/2012.

Document Reference: 1203-1743-D11 (A) Page 6 of 11


WARDPOWER
LVAC Load Survey and Generating Set Sizing Study, NG Keadby

Scenario B2: ISS Load Only


This is the sizing for a Generating Set to support the ISS loads only. 10% has been
included for future expansion. Transformer inrush loads have not been considered
but typical load staging has.
From this Sizing Study, the following performance requirements for the Generating
Set were identified:
Worst Case Average Continuous Load 115KWe/141KVA
Peak Power 115KWe –78% load
Largest Transient Load 115KWe
Upon application of standing load.
Largest Transient 6.8% Frequency (Limit is 10%)
8.1% Voltage (Limit is 15%)
Conclusions based on these results are as follows:
− Based on the above, the determining sizing characteristic is average continuous
load.

Document Reference: 1203-1743-D11 (A) Page 7 of 11


WARDPOWER
LVAC Load Survey and Generating Set Sizing Study, NG Keadby

Release Information
Name Date
Author K Marshall 12-Sep-14
Checked By V Law 12-Sep-14
Approved By K Marshall 12-Sep-14

Revision History
Rev Date Details
A 12-Sep-14 First Release

Contact Details
Sheaf Power Limited
Wardpower Works
Wicker Lane
Sheffield
S3 8HQ
Tel: 0114 273 8855
E-mail: [email protected]
Web www.wardpower.co.uk

Document Reference: 1203-1743-D11 (A) Page 8 of 11


WARDPOWER
LVAC Load Survey and Generating Set Sizing Study, NG Keadby

Appendix A: LV Load Survey

Document Reference: 1203-1743-D11 (A) Page 9 of 11


WARDPOWER

LV Site Load Survey (By Room)


Project No: 1203-1743 Site: NG Keadby
Survey Date: 27-Feb-14 Engineer: K Marshall

Note: In the following reports, Actual Loads given are after Demand Factor but are before diversity and do not include any loads from Sub-Distribution
Where a phase for a single phase load has not been identified, L1 is assumed. This is shown by an italic value for L1.
Actuals Diversity:
Circuit/Equipment: Q'ty Load Nature: L1: L2: L3: DG: TX: Actual Basis: Comments:
Control Building
1 LVAC Room Heating Density: 20.9 (W/m2)
Lighting Density: 0.6 (W/m2)
2KW Dimplex Wall Heater 3 Heating 32.5 0.0 0.0 80% 80% Fixture Count
415V LVAC Panel 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count
58W Single Tube 12 Lighting 3.8 0.0 0.0 80% 80% Fixture Count
Deakin 48V/15A BC 1 48V Battery Charger 3.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240. BC4 = QB2
Deakin 48V/15A BC 1 48V Battery Charger 3.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240. BC3 = QB1
Erskine 110V/15A BC 1 110V Battery Charger 9.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240. Unable to
ascertain rating, input device rating used.
Small Power Ring 1 Power 3.2 0.0 0.0 80% 80% Fixture Count
Trophy FT Fence Controller 3 Other 0.4 0.0 0.0 100% 100% Fixture Count
3 Workshop Heating Density: (W/m2)
Lighting Density: (W/m2)
1.1KVA 110VAC Transformer 1 Power 0.0 0.6 0.0 80% 80% Fixture Count
2KW Dimplex Wall Heater 1 Heating 10.8 0.0 0.0 80% 80% Fixture Count
3ph Pedastal Drill 2 Manual Motors 0.0 0.0 0.0 0% 80% Fixture Count
58W Single Tube 8 Lighting 2.5 0.0 0.0 80% 80% Fixture Count
Machine Lathe 1 Manual Motors 0.0 0.0 0.0 0% 80% Fixture Count No load information available for this but as it is a
manual motor this is not a concern.
Machine Lathe Emergency Stop Circuit 1 Manual Motors 0.0 0.0 0.0 0% 80% Fixture Count
Small Power Ring 1 Power 0.0 0.0 1.6 80% 80% Fixture Count
Workshop Fan 1 Cooling 0.0 0.0 16.2 0% 0% Typical Cooling less than heating
4 Entrance Hall Heating Density: 135.5 (W/m2)
Lighting Density: 4.9 (W/m2)
18W Quadruple Tube 3 Lighting 1.2 0.0 0.0 80% 80% Fixture Count Estimated rating
2KW Dimplex Wall Heater 1 Heating 10.8 0.0 0.0 80% 80% Fixture Count
Security Alarm Panel 1 Other 4.0 0.0 0.0 100% 100% Estimate
5 Ladies Toilet Heating Density: (W/m2)
Lighting Density: 12.1 (W/m2)
28W Waterproof Light 1 Lighting 0.0 0.2 0.0 80% 80% Fixture Count
3KW Water Heater 1 Water Heaters 0.0 16.2 0.0 25% 25% Fixture Count Is a smaller newey model - lower than 3KW

Document Reference: KXM/1203-1743/B Page 1 of 20


WARDPOWER
LV Site Load Survey
1203-1743 NG Keadby

Actuals Diversity:
Circuit/Equipment: Q'ty Load Nature: L1: L2: L3: DG: TX: Actual Basis: Comments:

6 General Office Heating Density: 157.3 (W/m2)


Lighting Density: 2.6 (W/m2)
18W Quadruple Tube 8 Lighting 0.0 3.1 0.0 80% 80% Fixture Count
AC Heating Mode 1 Heating 19.0 0.0 0.0 80% 80% Fixture Count
7 Control/Permit Office Heating Density: 174.5 (W/m2)
Lighting Density: 2.0 (W/m2)
2KW Dimplex Wall Heater 1 Heating 10.8 0.0 0.0 80% 80% Fixture Count
48VDC C/O Board 1 Sub Feed 0.0 0.0 0.0 100% 100% Fixture Count
58W Single Tube 6 Lighting 1.9 0.0 0.0 80% 80% Fixture Count
AC Heating Mode 1 Heating 13.0 0.0 0.0 80% 80% Fixture Count
SCS Control Desk 1 Other 0.0 0.0 0.0 100% 100% Fixture Count
SCS Cubicles 3 Other 0.0 0.0 0.0 100% 100% Fixture Count
8 Changing Room Heating Density: (W/m2)
Lighting Density: (W/m2)
2KW Dimplex Wall Heater 1 Heating 10.8 0.0 0.0 80% 80% Fixture Count
58W Single Tube 4 Lighting 1.3 0.0 0.0 80% 80% Fixture Count
58W Single Tube 2 Lighting 0.6 0.0 0.0 80% 80% Fixture Count In second part of store room
AC Heating Mode 1 Heating 13.0 0.0 0.0 80% 80% Fixture Count
Comments: The socket in this room is fed from the main office ring.

10 Mess Room Heating Density: 56.6 (W/m2)


Lighting Density: 2.0 (W/m2)
18W Quadruple Tube 9 Lighting 3.5 0.0 0.0 80% 80% Fixture Count
2KW Dimplex Wall Heater 1 Heating 0.0 10.8 0.0 80% 80% Fixture Count
3KW Water Heater 1 Water Heaters 0.0 0.0 16.2 25% 25% Fixture Count Not found - assumed rating
Cooker (with Socket) 1 Other 36.0 0.0 0.0 100% 100% Fixture Count
11 Gents Toilet Heating Density: 159.5 (W/m2)
Lighting Density: (W/m2)
2KW Dimplex Wall Heater 1 Heating 10.8 0.0 0.0 80% 80% Fixture Count
3KW Water Heater 2 Water Heaters 0.0 0.0 32.5 25% 25% Fixture Count Is a smaller newey model
12 Lobby Heating Density: (W/m2)
Lighting Density: 4.7 (W/m2)
28W Waterproof Light 2 Lighting 0.0 0.0 0.3 80% 80% Fixture Count
13 Generator Room Heating Density: (W/m2)
Lighting Density: (W/m2)
100W Light 6 Lighting 3.2 0.0 0.0 80% 80% Fixture Count
Fuel Transfer Pump 2 Other 5.2 0.0 0.0 100% 100% Fixture Count

Document Reference: KXM/1203-1743/B Page 2 of 20


WARDPOWER
LV Site Load Survey
1203-1743 NG Keadby

Actuals Diversity:
Circuit/Equipment: Q'ty Load Nature: L1: L2: L3: DG: TX: Actual Basis: Comments:
14 Compressor Room Heating Density: (W/m2)
Lighting Density: (W/m2)
3KVA 110VAC Transformer 1 Power 0.0 0.0 1.6 80% 80% Fixture Count Load adjusted for rated voltage of 230.
80W Double Tube 6 Lighting 0.0 0.0 5.2 80% 80% Fixture Count Load adjusted for rated voltage of 230.
Air Dryer No 1 1 Other 1.0 0.0 0.0 100% 100% Fixture Count Load adjusted for rated voltage of 240.
Air Dryer No 2 1 Other 1.0 0.0 0.0 100% 100% Fixture Count Load adjusted for rated voltage of 240.
Brook Hansen KC-F250MN 90KW 1 Compressors 171.2 171.2 171.2 100% 100% Fixture Count Load adjusted for rated voltage of 415.
Compressor
Brook Hansen KC-F250MN 90KW 1 Compressors 160.0 160.0 160.0 100% 100% Fixture Count
Compressor
Heater Distribution Board 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count
Radiant Heater 1 Heating 16.2 0.0 0.0 80% 80% Estimate Load adjusted for rated voltage of 230.
Radiant Heater 1 Heating 16.2 0.0 0.0 80% 80% Estimate Load adjusted for rated voltage of 230.
Radiant Heater 1 Heating 16.2 0.0 0.0 80% 80% Estimate Load adjusted for rated voltage of 230.
Radiant Heater 1 Heating 16.2 0.0 0.0 80% 80% Estimate Load adjusted for rated voltage of 230.
Radiant Heater 1 Heating 16.2 0.0 0.0 80% 80% Estimate Load adjusted for rated voltage of 230.
Ring Main (Typical) 1 Power 0.0 0.0 0.0 80% 80% Fixture Count Load adjusted for rated voltage of 230.
Roller Shutter (Typical) 2 Manual Motors 7.2 0.0 0.0 0% 80% Typical Load adjusted for rated voltage of 240. Typical
15 Diesel Fuel Store Room Heating Density: (W/m2)
Lighting Density: (W/m2)
28W Waterproof Light 6 Lighting 0.9 0.0 0.0 80% 80% Estimate
16 Site Services Store Room Heating Density: (W/m2)
Lighting Density: (W/m2)
2KW Dimplex Wall Heater 1 Heating 10.8 0.0 0.0 80% 80% Fixture Count
58W Single Tube 6 Lighting 1.9 0.0 0.0 80% 80% Fixture Count
Socket Ring 1 Power 1.6 0.0 0.0 80% 80% Fixture Count L&P 2 3L1

Document Reference: KXM/1203-1743/B Page 3 of 20


WARDPOWER
LV Site Load Survey
1203-1743 NG Keadby

Actuals Diversity:
Circuit/Equipment: Q'ty Load Nature: L1: L2: L3: DG: TX: Actual Basis: Comments:
General Office Building
1 Meeting Room Heating Density: 123.9 (W/m2)
Lighting Density: 2.2 (W/m2)
18W Quadruple Tube 9 Lighting 3.5 0.0 0.0 80% 80% Fixture Count
2KW Dimplex Wall Heater 1 Heating 0.0 10.8 0.0 80% 80% Fixture Count West Wall
2KW Dimplex Wall Heater 1 Heating 0.0 0.0 10.8 80% 80% Fixture Count North Wall
Air Conditioning Unit 1 Air Conditioning 0.0 13.0 0.0 80% 80% Fixture Count
Small Power Ring 1 Power 3.2 0.0 0.0 80% 80% Fixture Count
2 Rear Lobby Heating Density: (W/m2)
Lighting Density: 17.4 (W/m2)
18W Quadruple Tube 1 Lighting 0.4 0.0 0.0 80% 80% Fixture Count
Fire Alarm Unit 1 Other 0.0 4.0 0.0 100% 100% Typical Typical load based on device rating
3 Stores Heating Density: 337.8 (W/m2)
Lighting Density: 13.5 (W/m2)
2KW Dimplex Wall Heater 1 Heating 10.8 0.0 0.0 80% 80% Fixture Count
80W Single Tube 2 Lighting 0.9 0.0 0.0 80% 80% Fixture Count
Comms Cabinet 1 Other 0.0 0.0 0.0 100% 100% Fixture Count Load of this device not considered as this is powered
from the small power ring
Small Power Ring 1 Power 2.0 0.0 0.0 80% 80% Fixture Count
Comments: Room has a 63A RCCB marked KD LR/3, also referred to as Copier Room

4 Engineers Office Heating Density: (W/m2)


Lighting Density: 1.5 (W/m2)
18W Quadruple Tube 15 Lighting 0.0 5.8 0.0 80% 80% Fixture Count
Air Conditioning Unit 1 Air Conditioning 19.0 0.0 0.0 80% 80% Fixture Count
Small Power Ring 1 Power 0.0 3.2 0.0 80% 80% Fixture Count Right Hand
Small Power Ring 1 Power 0.0 3.2 0.0 80% 80% Fixture Count Left Hand
5 Team Leaders Room Heating Density: (W/m2)
Lighting Density: 3.7 (W/m2)
18W Quadruple Tube 6 Lighting 0.0 0.0 2.3 80% 80% Fixture Count
Air Conditioning Unit 1 Air Conditioning 0.0 0.0 13.0 80% 80% Fixture Count
Small Power Ring 1 Power 0.0 0.0 3.2 80% 80% Fixture Count
6 Entrance Lobby Heating Density: (W/m2)
Lighting Density: (W/m2)
Low Wattage Halogen 1 Lighting 0.0 0.0 0.5 80% 80% Fixture Count
Small Power Ring 1 Power 0.0 0.0 3.2 80% 80% Fixture Count
Storage Heater 1 Heating 0.0 0.0 0.0 80% 80% Other Disconnected, not in use

Document Reference: KXM/1203-1743/B Page 4 of 20


WARDPOWER
LV Site Load Survey
1203-1743 NG Keadby

Actuals Diversity:
Circuit/Equipment: Q'ty Load Nature: L1: L2: L3: DG: TX: Actual Basis: Comments:
7 External Heating Density: (W/m2)
Lighting Density: (W/m2)
28W Waterproof Light 1 Lighting 0.0 0.0 0.2 80% 80% Fixture Count

Document Reference: KXM/1203-1743/B Page 5 of 20


WARDPOWER
LV Site Load Survey
1203-1743 NG Keadby

Actuals Diversity:
Circuit/Equipment: Q'ty Load Nature: L1: L2: L3: DG: TX: Actual Basis: Comments:
Telecoms Building
1 Locker Room Heating Density: (W/m2)
Lighting Density: (W/m2)
2KW Dimplex Wall Heater 2 Heating 21.7 0.0 0.0 80% 80% Fixture Count
58W Single Tube 2 Lighting 0.6 0.0 0.0 80% 80% Fixture Count
KEADB23 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count
Shower 1 Water Heaters 16.2 0.0 0.0 80% 80% Fixture Count
Socket Ring 1 Power 1.5 0.0 0.0 80% 80% Fixture Count
Water Heater 1 Water Heaters 16.2 0.0 0.0 80% 80% Fixture Count
Comments: Tumble dryer in the room plugged in to socket.

2 Telecoms Room Heating Density: (W/m2)


Lighting Density: (W/m2)
110VAC TX 1 Power 0.0 0.0 0.9 80% 80% Fixture Count
3KW Xpelair Ventilation Fan 1 Cooling 16.2 0.0 0.0 0% 0% Fixture Count Cooling less than heating
3KW Xpelair Ventilation Fan 1 Cooling 0.0 16.2 0.0 0% 0% Fixture Count Cooling less than heating
48V Battery Charger No1 1 48V Battery Charger 0.0 3.0 0.0 100% 100% Fixture Count Load adjusted for rated voltage of 240.
48V Battery Charger No2 1 48V Battery Charger 3.0 0.0 0.0 100% 100% Fixture Count Load adjusted for rated voltage of 240.
80W Single Tube 6 Lighting 2.6 0.0 0.0 80% 80% Fixture Count Load adjusted for rated voltage of 230.
80W Single Tube 7 Lighting 0.0 3.0 0.0 80% 80% Fixture Count
AC Heating Mode 1 Heating 19.0 0.0 0.0 80% 80% Fixture Count
AC Heating Mode 1 Heating 0.0 13.0 0.0 80% 80% Fixture Count
DB6 Telecom's Room Lighting & Heating 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count
DB7 Telecoms Supplies 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count
DB7A Telecoms Supplies 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count This board has no live circuits.
DB8 Off Peak Supplies 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count
DB9 Outside Lighting Supply 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count
Lone Worker Unit 1 Other 3.6 0.0 0.0 100% 100% Typical
PAC Distribution Board 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count
PAC Unit 1 Other 3.6 0.0 0.0 100% 100% Typical Master
PAC Unit 1 Other 3.6 0.0 0.0 100% 100% Typical Slave
PAC Unit 1 Other 3.6 0.0 0.0 100% 100% Typical
Ring Main (Typical) 1 Power 0.0 0.0 3.2 80% 80% Typical Assumed socket strips in Energis cabinets
Small Power Ring 1 Power 0.9 0.0 0.0 80% 80% Fixture Count Load adjusted for rated voltage of 230. 2 x dbl sockets
Small Power Ring 1 Power 0.0 0.0 1.5 80% 80% Fixture Count 1 x dbl socket
Smll Vent Axia Fan 1 Cooling 5.4 0.0 0.0 0% 0% Estimate Cooling less than heating
Storage Heater 1 Heating 8.1 0.0 0.0 80% 80% Typical
Storage Heater 1 Heating 8.1 0.0 0.0 80% 80% Typical

Document Reference: KXM/1203-1743/B Page 6 of 20


WARDPOWER
LV Site Load Survey
1203-1743 NG Keadby

Actuals Diversity:
Circuit/Equipment: Q'ty Load Nature: L1: L2: L3: DG: TX: Actual Basis: Comments:
3 Battery Room Heating Density: (W/m2)
Lighting Density: (W/m2)
35W Double Tube 2 Lighting 0.0 0.0 0.8 80% 80% Fixture Count
4ft Twin Tubular Heater 1 Heating 0.0 0.0 2.6 80% 80% Fixture Count Load adjusted for rated voltage of 230.
High Liner Building
1 High Liner Room Heating Density: 43.3 (W/m2)
Lighting Density: 6.7 (W/m2)
15A RCD Socket 1 Power 1.5 0.0 0.0 80% 80% Fixture Count
15A RCD Socket 1 Power 0.0 1.5 0.0 80% 80% Fixture Count
15A RCD Socket 1 Power 0.0 0.0 1.5 80% 80% Fixture Count
15A RCD Socket 1 Power 0.0 0.0 1.5 80% 80% Fixture Count
20A 3ph Test Socket 1 Power 2.0 0.0 0.0 0% 80% Fixture Count
400W Flood Light (Internal) 1 Lighting 2.2 0.0 0.0 80% 80% Estimate
70W Double Tube 6 Lighting 0.0 4.5 0.0 80% 80% Fixture Count
80W Single Tube 2 Lighting 0.0 0.0 0.9 80% 80% Estimate
Double Element Radiant Heater 1 Heating 0.0 10.8 0.0 80% 80% Estimate
Double Element Radiant Heater 1 Heating 0.0 0.0 10.8 80% 80% Estimate
KEAD30DB 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count
KEAD31DB 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count
Roller Shutter (Typical) 1 Manual Motors 0.0 6.0 0.0 0% 80% Typical
Trophy FT Fence Controller 1 Other 0.0 0.0 0.1 100% 100% Fixture Count Fence Controller 3

Document Reference: KXM/1203-1743/B Page 7 of 20


WARDPOWER
LV Site Load Survey
1203-1743 NG Keadby

Actuals Diversity:
Circuit/Equipment: Q'ty Load Nature: L1: L2: L3: DG: TX: Actual Basis: Comments:
External
1 SGT1 Heating Density: (W/m2)
Lighting Density: (W/m2)
400/132 240MVA Parsons Peebles, Bank 1 SGT Cooling 26.9 26.9 26.9 66% 66% Fixture Count Load adjusted for rated voltage of 415. 4 x 4.6A Fans,
A Cooling 1 x 7.5A Pump
400/132 240MVA Parsons Peebles, Bank 1 SGT Cooling 26.9 26.9 26.9 66% 66% Fixture Count Load adjusted for rated voltage of 415. Load time
B Cooling delayed by 30s. 4 x 4.6A Fans, 1 x 7.5A Pump
Tap Changer (Typical) 1 Tap Changer 1.4 1.4 1.4 0% 0% Typical Load adjusted for rated voltage of 415.
2 SGT1 MK Heating Density: (W/m2)
Lighting Density: (W/m2)
Anti Condensation Heaters 4 Heating 2.2 0.0 0.0 80% 80% Fixture Count
3 SGT2 Heating Density: (W/m2)
Lighting Density: (W/m2)
Cooling 1 SGT Cooling 24.9 24.9 24.9 66% 66% Fixture Count Load adjusted for rated voltage of 415. From drawing,
6 x 1.6KW Fans, 1 x 4.2KW Pump, no time delay
SGT2 Drycol 1 Drycol 2.0 0.0 0.0 100% 100% Typical
Tap Changer 1 Tap Changer 0.7 0.7 0.7 0% 0% Fixture Count Load adjusted for rated voltage of 415. From manuals
4 SGT2 MK Heating Density: (W/m2)
Lighting Density: (W/m2)
Anti Condensation Heaters 2 Heating 1.6 0.0 0.0 80% 80% Fixture Count
Anti Condensation Heaters 2 Heating 1.1 0.0 0.0 80% 80% Fixture Count
5 SGT3 Heating Density: (W/m2)
Lighting Density: (W/m2)
Peebles Power Transformers 400/132 1 SGT Cooling 18.6 18.6 18.6 66% 66% Fixture Count Load adjusted for rated voltage of 415. FLC 4 x 3.1A
240MVA Cooling Bank A Fans, 1 x 5.5A Fan, StC 4 x 8.2A Fans, 1 x 24A Pump
Peebles Power Transformers 400/132 1 SGT Cooling 18.6 18.6 18.6 66% 66% Fixture Count Load adjusted for rated voltage of 415. Load time
240MVA Cooling Bank B delayed by 30s. FLC 4 x 3.1A Fans, 1 x 5.5A Fan,
StC 4 x 8.2A Fans, 1 x 24A Pump
SGT3 Drycol 1 Drycol 2.0 0.0 0.0 100% 100% Typical
Tap Changer 1 Tap Changer 0.7 0.7 0.7 0% 0% Fixture Count Load adjusted for rated voltage of 415.
6 SGT3 MK Heating Density: (W/m2)
Lighting Density: (W/m2)
Anti Condensation Heaters 2 Heating 0.6 0.0 0.0 80% 80% Fixture Count
Anti Condensation Heaters 1 Heating 0.5 0.0 0.0 80% 80% Fixture Count
7 Quad Booster 2 (Shunt) Heating Density: (W/m2)
Lighting Density: (W/m2)
Cooling Fans Bank AA 5 Reactor Cooling 36.3 36.3 36.3 0% 0% Fixture Count Load adjusted for rated voltage of 415. QB2

Document Reference: KXM/1203-1743/B Page 8 of 20


WARDPOWER
LV Site Load Survey
1203-1743 NG Keadby

Actuals Diversity:
Circuit/Equipment: Q'ty Load Nature: L1: L2: L3: DG: TX: Actual Basis: Comments:
Cooling Fans Bank AB 5 Reactor Cooling 36.3 36.3 36.3 0% 0% Fixture Count Load adjusted for rated voltage of 415. Load time
delayed by 10s. QB2
Cooling Fans Bank BA 5 Reactor Cooling 36.3 36.3 36.3 0% 0% Fixture Count Load adjusted for rated voltage of 415. Load time
delayed by 40s. QB2
Cooling Fans Bank BB 5 Reactor Cooling 36.3 36.3 36.3 0% 0% Fixture Count Load adjusted for rated voltage of 415. Load time
delayed by 50s. QB2
Drycol 2 Drycol 10.8 0.0 0.0 100% 100% Typical QB2
Oil Pump A1, A2 2 Reactor Cooling 11.7 11.7 11.7 0% 0% Fixture Count Load adjusted for rated voltage of 415. Load time
delayed by 30s. QB2
Oil Pump B1, B2 2 Reactor Cooling 11.7 11.7 11.7 0% 0% Fixture Count Load adjusted for rated voltage of 415. Load time
delayed by 60s. QB2
Tap Changer (Typical) 1 Tap Changer 1.4 1.4 1.4 0% 0% Typical Load adjusted for rated voltage of 415.
Comments: Alstom

8 Quad Booster 2 (Series) Heating Density: (W/m2)


Lighting Density: (W/m2)
Cooling Fans Bank AA 5 Reactor Cooling 27.4 27.4 27.4 100% 100% Fixture Count Load adjusted for rated voltage of 415. QB2
Cooling Fans Bank AB 5 Reactor Cooling 27.4 27.4 27.4 100% 100% Fixture Count Load adjusted for rated voltage of 415. Load time
delayed by 10s. QB2
Cooling Fans Bank BA 5 Reactor Cooling 27.4 27.4 27.4 100% 100% Fixture Count Load adjusted for rated voltage of 415. Load time
delayed by 40s. QB2
Cooling Fans Bank BB 5 Reactor Cooling 27.4 27.4 27.4 100% 100% Fixture Count Load adjusted for rated voltage of 415. Load time
delayed by 50s. QB2
Drycol 2 Drycol 10.8 0.0 0.0 100% 100% Typical QB2
Oil Pump A1, A2 2 Reactor Cooling 11.7 11.7 11.7 100% 100% Fixture Count Load adjusted for rated voltage of 415. Load time
delayed by 30s. QB2
Oil Pump B1, B2 2 Reactor Cooling 11.7 11.7 11.7 0% 0% Fixture Count Load adjusted for rated voltage of 415. Load time
delayed by 60s. QB2
Comments: Alstom

9 Quad Booster 2 (Shunt) MK Heating Density: (W/m2)


Lighting Density: (W/m2)
Anti Condensation Heater 2 Heating 1.1 0.0 0.0 80% 80% Typical Load adjusted for rated voltage of 230.
MK Socket 1 Power 0.9 0.0 0.0 80% 80% Fixture Count Load adjusted for rated voltage of 230.
Comments: Alstom

10 Quad Booster 2 (Series) MK Heating Density: (W/m2)


Lighting Density: (W/m2)
Anti Condensation Heater 2 Heating 1.1 0.0 0.0 80% 80% Typical Load adjusted for rated voltage of 230.
MK Socket 1 Power 0.9 0.0 0.0 80% 80% Fixture Count Load adjusted for rated voltage of 230.

Document Reference: KXM/1203-1743/B Page 9 of 20


WARDPOWER
LV Site Load Survey
1203-1743 NG Keadby

Actuals Diversity:
Circuit/Equipment: Q'ty Load Nature: L1: L2: L3: DG: TX: Actual Basis: Comments:

Comments: Alstom

11 Quad Booster 1 MK Heating Density: (W/m2)


Lighting Density: (W/m2)
Cubicle Heaters 1 Heating 3.8 0.0 0.0 80% 80% Fixture Count Load adjusted for rated voltage of 230.
Kiosk Socket 1 Power 1.0 0.0 0.0 80% 80% Fixture Count Load adjusted for rated voltage of 240.
Panel Lighting 1 Lighting 0.2 0.0 0.0 80% 80% Fixture Count Load adjusted for rated voltage of 230.
12 Quad Booster 1 (Shunt) Heating Density: (W/m2)
Lighting Density: (W/m2)
Series Cooler A2 Drycol 1 Drycol 1.1 0.0 0.0 100% 100% Fixture Count Load adjusted for rated voltage of 240.
Series Cooler B1 Drycol 1 Drycol 1.1 0.0 0.0 100% 100% Fixture Count Load adjusted for rated voltage of 240.
Series Cooler Fans Bank A1 6 Reactor Cooling 32.4 32.4 32.4 100% 100% Fixture Count Load adjusted for rated voltage of 415. Load time
delayed by 25s.
Series Cooler Fans Bank A2 6 Reactor Cooling 32.4 32.4 32.4 100% 100% Fixture Count Load adjusted for rated voltage of 415. Load time
delayed by 35s.
Series Cooler Fans Bank B1 6 Reactor Cooling 32.4 32.4 32.4 100% 100% Fixture Count Load adjusted for rated voltage of 415. Load time
delayed by 5s.
Series Cooler Fans Bank B2 6 Reactor Cooling 32.4 32.4 32.4 100% 100% Fixture Count Load adjusted for rated voltage of 415. Load time
delayed by 20s.
Series Cooler Pump Bank A1 1 Reactor Cooling 7.4 7.4 7.4 100% 100% Fixture Count Load adjusted for rated voltage of 415. Load time
delayed by 20s. Pump M410
Series Cooler Pump Bank A2 1 Reactor Cooling 7.4 7.4 7.4 100% 100% Fixture Count Load adjusted for rated voltage of 415. Load time
delayed by 20s. Pump M411
Series Cooler Pump Bank B1 1 Reactor Cooling 7.4 7.4 7.4 0% 0% Fixture Count Load adjusted for rated voltage of 415. Load time
delayed by 90s. Pump M412
Series Cooler Pump Bank B2 1 Reactor Cooling 7.4 7.4 7.4 0% 0% Fixture Count Load adjusted for rated voltage of 415. Load time
delayed by 120s. Pump M413
Shunt Cooler A2 Drycol 1 Drycol 1.1 0.0 0.0 100% 100% Fixture Count Load adjusted for rated voltage of 240.
Shunt Cooler B1 Drycol 1 Drycol 1.1 0.0 0.0 100% 100% Fixture Count Load adjusted for rated voltage of 240.
Shunt Cooler Fans Bank A1 4 Reactor Cooling 21.6 21.6 21.6 0% 0% Fixture Count Load adjusted for rated voltage of 415. Load time
delayed by 30s. 1.08KW, check pf, 18.2A SC
Shunt Cooler Fans Bank A2 4 Reactor Cooling 21.6 21.6 21.6 0% 0% Fixture Count Load adjusted for rated voltage of 415. Load time
delayed by 40s.
Shunt Cooler Fans Bank B1 4 Reactor Cooling 21.6 21.6 21.6 0% 0% Fixture Count Load adjusted for rated voltage of 415. Load time
delayed by 10s.
Shunt Cooler Fans Bank B2 4 Reactor Cooling 21.6 21.6 21.6 0% 0% Fixture Count Load adjusted for rated voltage of 415. Load time
delayed by 20s.
Shunt Cooler Pump Bank A1 1 Reactor Cooling 7.4 7.4 7.4 0% 0% Fixture Count Load adjusted for rated voltage of 415. Load time
delayed by 20s. 4.2KW, check pf, 45A SC, Pump
M310

Document Reference: KXM/1203-1743/B Page 10 of 20


WARDPOWER
LV Site Load Survey
1203-1743 NG Keadby

Actuals Diversity:
Circuit/Equipment: Q'ty Load Nature: L1: L2: L3: DG: TX: Actual Basis: Comments:
Shunt Cooler Pump Bank A2 1 Reactor Cooling 7.4 7.4 7.4 0% 0% Fixture Count Load adjusted for rated voltage of 415. Load time
delayed by 20s. Pump M311
Shunt Cooler Pump Bank B1 1 Reactor Cooling 7.4 7.4 7.4 0% 0% Fixture Count Load adjusted for rated voltage of 415. Load time
delayed by 90s. Pump M312
Shunt Cooler Pump Bank B2 1 Reactor Cooling 7.4 7.4 7.4 0% 0% Fixture Count Load adjusted for rated voltage of 415. Load time
delayed by 120s. Pump M313
Tap Changer (Typical) 1 Tap Changer 1.4 1.4 1.4 0% 0% Typical Load adjusted for rated voltage of 415.
0 Site Heating Density: (W/m2)
Lighting Density: (W/m2)
Security Gate 1 Manual Motors 16.0 0.0 0.0 0% 80% Typical
West Burton 1 Relay Room
1 West Burton 1 Relay Room Heating Density: 73.0 (W/m2)
Lighting Density: 5.4 (W/m2)
110V Battery Charger 1 110V Battery Charger 6.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240.
16A Socket 1 Power 1.6 0.0 0.0 80% 80% Fixture Count
2KW Wall Heater 2 Heating 0.0 0.0 0.0 80% 80% Fixture Count
30A Reyrolle 3ph Test Socket 1 Power 3.0 3.0 3.0 0% 80% Fixture Count
48V Battery Charger 1 48V Battery Charger 3.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240. 16A Input fuse
70W Double Tube 3 Lighting 0.0 0.0 0.0 80% 80% Fixture Count
8W External Light 1 Lighting 0.0 0.0 0.0 80% 80% Fixture Count
Essential Lighting Supply Distribution Board 0.0 0.0 0.0 100% 100%
KEAD24DB 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count Fed from supplies pillar ring
Relay Panels 3 Panel Lighting 0.0 0.0 0.0 80% 80% Typical
West Burton 2 Relay Room
1 West Burton 2 Relay Room Heating Density: (W/m2)
Lighting Density: 4.5 (W/m2)
16A Socket 1 Power 1.6 0.0 0.0 80% 80% Fixture Count
30A Reyrolle 3ph Test Socket 1 Power 3.0 3.0 3.0 0% 80% Fixture Count
58W Double Tube 4 Lighting 2.5 0.0 0.0 80% 80% Fixture Count
8W External Light 1 Lighting 0.0 0.0 0.0 80% 80% Fixture Count
Essential Lighting Supply 1 Distribution Board 0.0 0.0 0.0 100% 100% red phase 7 points
KEAD25DB 1 Distribution Board 0.0 0.0 0.0 100% 100%
PE Systems 110V/13A Battery Charger 1 110V Battery Charger 6.4 0.0 0.0 100% 100% Fixture Count Load adjusted for rated voltage of 230.
(2007)
PE Systems 48V/13A Battery Charger 1 48V Battery Charger 3.0 0.0 0.0 100% 100% Fixture Count Load adjusted for rated voltage of 230.

Document Reference: KXM/1203-1743/B Page 11 of 20


WARDPOWER
LV Site Load Survey
1203-1743 NG Keadby

Actuals Diversity:
Circuit/Equipment: Q'ty Load Nature: L1: L2: L3: DG: TX: Actual Basis: Comments:
SGT3 Relay Room
1 SGT3 Relay Room Heating Density: 109.5 (W/m2)
Lighting Density: 3.2 (W/m2)
110V Battery Charger 1 110V Battery Charger 6.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240.
16A Socket 1 Power 1.6 0.0 0.0 80% 80% Fixture Count
30A Reyrolle 3ph Test Socket 1 Power 3.0 3.0 3.0 0% 80% Fixture Count
3KW Xpelair Heated Fan 1 Heating 16.2 0.0 0.0 80% 80% Fixture Count
48V Battery Charger 1 48V Battery Charger 3.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240. 16A Input fuse
230v
80W Single Tube 3 Lighting 1.3 0.0 0.0 80% 80% Fixture Count
8W External Light 1 Lighting 0.0 0.0 0.0 80% 80% Fixture Count
Essential Lighting Supply Distribution Board 0.0 0.0 0.0 100% 100%
KEAD06DB 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count
Relay Panels 3 Panel Lighting 0.0 0.0 0.0 80% 80% Typical
Comments: db feeds somwe pumps

Drax Thorpe Marsh Relay Room


1 Drax Thorpe Marsh Relay Room Heating Density: (W/m2)
Lighting Density: (W/m2)
110V Battery Charger 1 110V Battery Charger 6.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240.
30A 3ph Test Socket 1 Power 3.0 3.0 3.0 0% 80% Fixture Count
3KW Xpelair Heated Fan 1 Heating 16.2 0.0 0.0 80% 80% Fixture Count
48V Battery Charger 1 48V Battery Charger 3.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240. 16A Input fuse
80W Single Tube 3 Lighting 1.3 0.0 0.0 80% 80% Fixture Count
8W External Light 1 Lighting 0.0 0.0 0.0 80% 80% Fixture Count
Essential Lighting Supply Distribution Board 0.0 0.0 0.0 100% 100%
KEAD07DB 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count
Relay Panels 8 Panel Lighting 0.0 0.0 0.0 80% 80% Typical

Document Reference: KXM/1203-1743/B Page 12 of 20


WARDPOWER
LV Site Load Survey
1203-1743 NG Keadby

Actuals Diversity:
Circuit/Equipment: Q'ty Load Nature: L1: L2: L3: DG: TX: Actual Basis: Comments:
Keadby Power 1 Relay Room
1 Keadby Power 1 Relay Room Heating Density: (W/m2)
Lighting Density: (W/m2)
110V Battery Charger 1 110V Battery Charger 6.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240.
30A 3ph Test Socket 1 Power 3.0 3.0 3.0 0% 80% Fixture Count
48V Battery Charger 1 48V Battery Charger 3.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240. 16A Input fuse
70W Single Tube 3 Lighting 1.1 0.0 0.0 80% 80% Fixture Count
8W External Light 1 Lighting 0.0 0.0 0.0 80% 80% Fixture Count
Essential Lighting Supply Distribution Board 0.0 0.0 0.0 100% 100%
KEAD24DB 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count Fed from supplies pillar ring
Relay Panels 9 Panel Lighting 0.0 0.0 0.0 80% 80% Typical
Bus Coupler 3 Relay Room
1 Bus Coupler 3 Relay Room Heating Density: (W/m2)
Lighting Density: (W/m2)
110V Battery Charger 1 110V Battery Charger 6.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240. 16A Input fuse
230v
30A 3ph Test Socket 1 Power 3.0 3.0 3.0 0% 80% Fixture Count
3KW Xpelair Heated Fan 1 Heating 16.2 0.0 0.0 80% 80% Fixture Count
48V Battery Charger 1 48V Battery Charger 3.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240. Erskine, no
input rating
80W Single Tube 3 Lighting 1.3 0.0 0.0 80% 80% Fixture Count
8W External Light 1 Lighting 0.0 0.0 0.0 80% 80% Fixture Count
Essential Lighting Supply Distribution Board 0.0 0.0 0.0 100% 100%
KEAD09DB 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count
Relay Panels 4 Panel Lighting 0.0 0.0 0.0 80% 80% Typical
Creyke Beck - Humber Refinery Relay Room
1 Creyke Beck - Humber Refinery Relay Room Heating Density: (W/m2)
Lighting Density: (W/m2)
110V Battery Charger 1 110V Battery Charger 6.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240. chloride 4a at
240 in
16A Socket 1 Power 1.6 0.0 0.0 80% 80% Fixture Count
30A Reyrolle 3ph Test Socket 1 Power 3.0 3.0 3.0 0% 80% Fixture Count
48V Battery Charger 1 48V Battery Charger 3.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240. 10A Input fuse
230v
85W Double Tube 3 Lighting 2.8 0.0 0.0 80% 80% Fixture Count
8W External Light 1 Lighting 0.0 0.0 0.0 80% 80% Fixture Count
Essential Lighting Supply Distribution Board 0.0 0.0 0.0 100% 100%
KEAD10DB 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count

Document Reference: KXM/1203-1743/B Page 13 of 20


WARDPOWER
LV Site Load Survey
1203-1743 NG Keadby

Actuals Diversity:
Circuit/Equipment: Q'ty Load Nature: L1: L2: L3: DG: TX: Actual Basis: Comments:
Killingholme Relay Room
1 Killingholme Relay Room Heating Density: (W/m2)
Lighting Density: (W/m2)
110V Battery Charger 1 110V Battery Charger 6.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240.
48V Battery Charger 1 48V Battery Charger 3.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240. erskine
58w Doiuble Tube 5 Lighting 3.1 0.0 0.0 80% 80% Fixture Count
8W External Light 1 Lighting 0.0 0.0 0.0 80% 80% Fixture Count
Essential Lighting Supply Distribution Board 0.0 0.0 0.0 100% 100%
KEAD11DB 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count
Main Bus Section 2 Relay Room
1 Main Bus Section 2 Relay Room Heating Density: (W/m2)
Lighting Density: (W/m2)
110V Battery Charger 1 110V Battery Charger 6.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240.
15A Socket 1 Power 1.5 0.0 0.0 80% 80% Fixture Count
30A Reyrolle 3ph Test Socket 1 Power 3.0 3.0 3.0 0% 80% Fixture Count
3KW Xpelair Heated Fan 1 Heating 16.2 0.0 0.0 80% 80% Fixture Count
48V Battery Charger 1 48V Battery Charger 3.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240. Deakin 16A
Input fuse 230v
85W Double Tube 3 Lighting 2.8 0.0 0.0 80% 80% Fixture Count
8W External Light 1 Lighting 0.0 0.0 0.0 80% 80% Fixture Count
Essential Lighting Supply Distribution Board 0.0 0.0 0.0 100% 100%
KEAD12DB 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count
Comments: Room has ceiling heating?

Reserve Bus Section 2 Relay Room


1 Reserve Bus Section 2 Relay Room Heating Density: (W/m2)
Lighting Density: (W/m2)
32A 3ph Test Socket 1 Power 3.2 3.2 3.2 0% 80% Fixture Count
3KW Xpelair Heated Fan 1 Heating 16.2 0.0 0.0 80% 80% Fixture Count
70W Single Tube 2 Lighting 0.8 0.0 0.0 80% 80% Fixture Count
8W External Light 1 Lighting 0.0 0.0 0.0 80% 80% Fixture Count
Fan 1 Cooling 16.2 0.0 0.0 0% 0% Estimate Cooling less than heating
KEAD13DB 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count
PE Systems 110V/9A Battery Charger 1 110V Battery Charger 4.3 0.0 0.0 100% 100% Fixture Count Load adjusted for rated voltage of 240.
PE Systems 48V/15A Battery Charger 1 48V Battery Charger 6.1 0.0 0.0 100% 100% Fixture Count
Relay Panels 3 Panel Lighting 0.0 0.0 0.0 80% 80% Typical

Document Reference: KXM/1203-1743/B Page 14 of 20


WARDPOWER
LV Site Load Survey
1203-1743 NG Keadby

Actuals Diversity:
Circuit/Equipment: Q'ty Load Nature: L1: L2: L3: DG: TX: Actual Basis: Comments:
Creyke Beck - Killingholme Relay Room
1 Creyke Beck - Killingholme Relay Room Heating Density: (W/m2)
Lighting Density: 9.6 (W/m2)
110V Battery Charger 1 110V Battery Charger 6.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240.
125W Double Tube 3 Lighting 4.1 0.0 0.0 80% 80% Fixture Count
15A Socket 1 Power 1.5 0.0 0.0 80% 80% Fixture Count
30A 3ph Test Socket 1 Power 3.0 3.0 3.0 0% 80% Fixture Count
48V Battery Charger 1 48V Battery Charger 3.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240. Erskine no
ratin g
8W External Light 1 Lighting 0.0 0.0 0.0 80% 80% Fixture Count
Essential Lighting Supply Distribution Board 0.0 0.0 0.0 100% 100%
KEAD14DB 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count
Comments: room has a ceiling heater

Grimsby West Relay Room


1 Grimsby West Relay Room Heating Density: (W/m2)
Lighting Density: (W/m2)
110V Battery Charger 1 110V Battery Charger 6.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240.
30A 3ph Test Socket 1 Power 3.0 3.0 3.0 0% 80% Fixture Count
48V Battery Charger 1 48V Battery Charger 3.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240. 15A Output
Erskine
58W Double Tube 5 Lighting 3.1 0.0 0.0 80% 80% Fixture Count
8W External Light 1 Lighting 0.0 0.0 0.0 80% 80% Fixture Count
Essential Lighting Supply Distribution Board 0.0 0.0 0.0 100% 100%
KEAD15DB 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count
Keadby Power 2 Relay Room
1 Keadby Power 2 Relay Room Heating Density: (W/m2)
Lighting Density: (W/m2)
110V Battery Charger 1 110V Battery Charger 6.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240.
30A 3ph Test Socket 1 Power 3.0 3.0 3.0 0% 80% Fixture Count
48V Battery Charger 1 48V Battery Charger 3.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240. 16A Input fuse
20A output 230v
70W Single Tube 3 Lighting 1.1 0.0 0.0 80% 80% Fixture Count
8W External Light 1 Lighting 0.0 0.0 0.0 80% 80% Fixture Count
Essential Lighting Supply Distribution Board 0.0 0.0 0.0 100% 100%
no nam e 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count
Relay Panels 10 Panel Lighting 2.2 0.0 0.0 80% 80% Typical

Document Reference: KXM/1203-1743/B Page 15 of 20


WARDPOWER
LV Site Load Survey
1203-1743 NG Keadby

Actuals Diversity:
Circuit/Equipment: Q'ty Load Nature: L1: L2: L3: DG: TX: Actual Basis: Comments:
Cottam 1 Relay Room
1 Cottam 1 Relay Room Heating Density: (W/m2)
Lighting Density: (W/m2)
32A 3ph Test Socket 1 Power 3.2 3.2 3.2 0% 80% Fixture Count
3KW Xpelair Heated Fan 1 Heating 16.2 0.0 0.0 80% 80% Fixture Count
70W Single Tube 3 Lighting 1.1 0.0 0.0 80% 80% Fixture Count
8W External Light 1 Lighting 0.0 0.0 0.0 80% 80% Fixture Count
KEAD16DB 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count
PE Systems 110V/9A Battery Charger 1 110V Battery Charger 5.0 0.0 0.0 100% 100% Fixture Count Load adjusted for rated voltage of 240.
(1999)
PE Systems 48V/15A Battery Charger 1 48V Battery Charger 4.1 0.0 0.0 100% 100% Fixture Count Load adjusted for rated voltage of 240.
(1999)
Relay Panels 3 Panel Lighting 0.0 0.0 0.0 80% 80% Typical
Small Vent Axia Fan 1 Cooling 5.4 0.0 0.0 0% 0% Estimate Cooling less than heating
Cottam 2 Relay Room
1 Cottam 2 Relay Room Heating Density: (W/m2)
Lighting Density: (W/m2)
32A 3ph Test Socket 1 Power 3.2 3.2 3.2 0% 80% Fixture Count
3KW Xpelair Heated Fan 1 Heating 16.2 0.0 0.0 80% 80% Fixture Count
70W Single Tube 3 Lighting 1.1 0.0 0.0 80% 80% Fixture Count
8W External Light 1 Lighting 0.0 0.0 0.0 80% 80% Fixture Count
KEAD17DB 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count
PE Systems 110V/9A Battery Charger 1 110V Battery Charger 5.0 0.0 0.0 100% 100% Fixture Count Load adjusted for rated voltage of 240.
(1999)
PE Systems 48V/15A Battery Charger 1 48V Battery Charger 4.1 0.0 0.0 100% 100% Fixture Count Load adjusted for rated voltage of 240.
(1999)
Relay Panels 3 Panel Lighting 0.0 0.0 0.0 80% 80% Typical
Small Vent Axia Fan 1 Cooling 5.4 0.0 0.0 0% 0% Estimate Cooling less than heating

Document Reference: KXM/1203-1743/B Page 16 of 20


WARDPOWER
LV Site Load Survey
1203-1743 NG Keadby

Actuals Diversity:
Circuit/Equipment: Q'ty Load Nature: L1: L2: L3: DG: TX: Actual Basis: Comments:
SGT2 Relay Room
1 SGT2 Relay Room Heating Density: (W/m2)
Lighting Density: (W/m2)
110V Battery Charger 1 110V Battery Charger 6.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240.
15A Socket 1 Power 1.5 0.0 0.0 80% 80% Fixture Count
30A 3ph Test Socket 1 Power 3.0 3.0 3.0 0% 80% Fixture Count
48V Battery Charger 1 48V Battery Charger 3.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240. Deaking 16A
Input fuse 240v
85W Double Tube 4 Lighting 3.7 0.0 0.0 80% 80% Fixture Count
8W External Light 1 Lighting 0.0 0.0 0.0 80% 80% Fixture Count
Essential Lighting Supply Distribution Board 0.0 0.0 0.0 100% 100%
KEAD18DB 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count
Comments: Ceilin gheater?

Bus Coupler 2 Relay Room


1 Bus Coupler 2 Relay Room Heating Density: (W/m2)
Lighting Density: (W/m2)
110V Battery Charger 1 110V Battery Charger 6.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240. 16A Input fuse
230v
125W Double Tube 3 Lighting 4.1 0.0 0.0 80% 80% Fixture Count
15A Socket 1 Power 1.5 0.0 0.0 80% 80% Fixture Count
30A 3ph Test Socket 1 Power 3.0 3.0 3.0 0% 80% Fixture Count
3KW Xpelair Heated Fan 1 Heating 16.2 0.0 0.0 80% 80% Fixture Count
48V Battery Charger 1 48V Battery Charger 3.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240. Deakin16A
Input fuse 230v
8W External Light 1 Lighting 0.0 0.0 0.0 80% 80% Fixture Count
Essential Lighting Supply Distribution Board 0.0 0.0 0.0 100% 100%
KEAD19DB 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count
Comments: Ceiling heating

Document Reference: KXM/1203-1743/B Page 17 of 20


WARDPOWER
LV Site Load Survey
1203-1743 NG Keadby

Actuals Diversity:
Circuit/Equipment: Q'ty Load Nature: L1: L2: L3: DG: TX: Actual Basis: Comments:
SGT1 Relay Room
1 SGT1 Relay Room Heating Density: (W/m2)
Lighting Density: (W/m2)
110V Battery Charger 1 110V Battery Charger 6.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240.
125W Double Tube 3 Lighting 4.1 0.0 0.0 80% 80% Fixture Count
15A Socket 1 Power 1.5 0.0 0.0 80% 80% Fixture Count
30A 3ph Test Socket 1 Power 3.0 3.0 3.0 0% 80% Fixture Count
48V Battery Charger 1 48V Battery Charger 3.0 0.0 0.0 100% 100% Estimate Load adjusted for rated voltage of 240. Deaking 16A
Input fuse 240v
8W External Light 1 Lighting 0.0 0.0 0.0 80% 80% Fixture Count
Essential Lighting Supply Distribution Board 0.0 0.0 0.0 100% 100%
KEAD20DB 1 Distribution Board 0.0 0.0 0.0 100% 100% Fixture Count
Comments: Ceiling Heating

Document Reference: KXM/1203-1743/B Page 18 of 20


WARDPOWER
LV Site Load Survey
1203-1743 NG Keadby

Actuals Diversity:
Circuit/Equipment: Q'ty Load Nature: L1: L2: L3: DG: TX: Actual Basis: Comments:

System Total: 2,017 1,210 1,211


DG Distribution Board Total including Diversity: 1,418 751 738
TX Distribution Board Total including Diversity: 1,480 797 779
DG Estimated Load at Site Voltage (assuming pf=0.8): 672KVA
TX Estimated Load at Site Voltage (assuming pf=0.8): 706KVA

Average Heating Density: 101.2 (W/m2)


Average Lighting Density: 5.1 (W/m2)
Totals by Load Nature (after Diversity)
110V Battery Charger DG Load: 114 0 0
TX Load: 114 0 0
48V Battery Charger DG Load: 68 3 0
TX Load: 68 3 0
Air Conditioning DG Load: 15 10 10
TX Load: 15 10 10
Compressors DG Load: 331 331 331
TX Load: 331 331 331
Drycol DG Load: 30 0 0
TX Load: 30 0 0
Heating DG Load: 347 36 19
TX Load: 347 36 19
Lighting DG Load: 57 13 8
TX Load: 57 13 8
Manual Motors DG Load: 0 0 0
TX Load: 19 5 0
Other DG Load: 62 4 0
TX Load: 62 4 0
Panel Lighting DG Load: 2 0 0
TX Load: 2 0 0
Power DG Load: 24 7 15
TX Load: 67 48 56
Reactor Cooling DG Load: 266 266 266
TX Load: 266 266 266

Document Reference: KXM/1203-1743/B Page 19 of 20


WARDPOWER
LV Site Load Survey
1203-1743 NG Keadby

Actuals Diversity:
Circuit/Equipment: Q'ty Load Nature: L1: L2: L3: DG: TX: Actual Basis: Comments:
SGT Cooling DG Load: 76 76 76
TX Load: 76 76 76
Water Heaters DG Load: 26 4 12
TX Load: 26 4 12

Total: DG Load: 1,418 751 738


TX Load: 1,480 797 779

Summary of Intermittant Loads (before Diversity)


Tap Changer Tap Changer (Typical) 1.4 1.4 1.4
Tap Changer 0.7 0.7 0.7
Tap Changer 0.7 0.7 0.7
Manual Motors Security Gate 16.0 0.0 0.0
Roller Shutter (Typical) 7.2 0.0 0.0
Roller Shutter (Typical) 0.0 6.0 0.0
3ph Pedastal Drill 0.0 0.0 0.0
Machine Lathe 0.0 0.0 0.0
Machine Lathe Emergency Stop Circuit 0.0 0.0 0.0

Key:
Estimate: Where either the number of fittings or the rating of the equipment is unknown and a reasonable estimate has been ma
Fixture Count: Where the number of fittings is known and either the rating has been specifically identified from the equipment or has been generically identified (e.g. a heater looks like a
2KW Heater so 2KWe has been allowed).

Measure: Where the rating has been measured using a Clamp meter or similar instrumentatio
Typical: Where the number fittings or rating of the equipment is unknown and a value has been used in accordance with agreed values from OS733 (e.g. 120W Panel Heat

Survey Notes:
No: Note:
1. Sizing is in accordance with WARDPOWER document OS733, NG LV Sizing Methods Guidelines, Revision B.
2. Special diversities have been applied to SGT Cooling and Quad Booster cooling in accordance with instructions from NG Design Assurance.

Survey Revisions:
Revision: Date: Revision Description:
A 27-Feb-14 First Release
B 12-Sep-14 Corrections to SGT Cooling phases, water heater diversities, application of NG Design Assurances specifically for Keadby - See Note 2.

Document Reference: KXM/1203-1743/B Page 20 of 20


WARDPOWER
LVAC Load Survey and Generating Set Sizing Study, NG Keadby

Appendix B: Generating Set Sizing Studies


Scenario B1: Existing Site Load

Document Reference: 1203-1743-D11 (A) Page 10 of 11


WARDPOWER

LV Site Load Analysis & Generating Set Sizing Study


Enquiry No.: 1203-1743 Customer: Siemens
Date: 12-Sep-14 Project: NG Keadby ISS
Engineer: KXM Scenario: A1: Assessment of Existing Site Load and Generating Set

Load Analysis

1. Scheme Information and Working Assumptions

This estimate has been prepared based upon the following scheme information and working assumptions:

System Voltage 400 V Frequency Transient 10%


System Frequency 50 Hz Voltage Transient 15%
Duty PRP Future Expansion 0%
Overload 10%
Rated PF 0.8

The following project specific information/assumptions is also used/made:


Sizing is based on site survey March 2014 with additional information supplied by Mark Gomersall of NG, in particular Quad Booster Shunt Cooling Systems to be discounted, SGT Cooling Load to be reduced by one third.

In addition, the following general assumptions are made:

- No regenerative loads
- Loads are applied in the groups given in 3 below with recovery times as given.

2. Loads

The following are the loads to be supported by the Generating Set:

Load Starting Running


Before Diversity Including Diversity Before Diversity Including Diversity
Circuit/Description Group Diversity PF I1 I2 I3 3ph I KWe KVA I1 I2 I3 3ph I KWe KVA PF I1 I2 I3 3ph I KWe KVA I1 I2 I3 3ph I KWe KVA

Standing Load Standing 1.0


1.0
110V BCs Standing 1.0 0.80 38.0 21 26 38 21 26 0.80 38.0 21 26 38 21 26
48V BCs Standing 1.0 0.80 23.7 13 16 24 13 16 0.80 23.7 13 16 24 13 16
Air Conditiioning Standing 1.0 0.80 11.7 6 8 12 6 8 0.80 11.7 6 8 12 6 8
Compressors 1.0 0.0 0
Compressor 1 Standing 1.0 0.40 1,027.2 285 712 1,027 285 712 0.80 171.2 95 119 171 95 119
Compressor 2 6 1.0 0.40 960.0 266 665 960 266 665 0.80 160.0 89 111 160 89 111
Drycol Standing 1.0 0.80 10.0 6 7 10 6 7 0.80 10.0 6 7 10 6 7
Heating Standing 1.0 0 0.80 134.0 74 93 134 74 93 0.80 134.0 74 93 134 74 93
Lighting Standing 1.0 0.80 26.0 14 18 26 14 18 0.80 26.0 14 18 26 14 18
Other Standing 1.0 0.80 22.0 12 15 22 12 15 0.80 22.0 12 15 22 12 15
Panel Lighting Standing 1.0 0.80 0.7 0 0 1 0 0 0.80 0.7 0 0 1 0 0
Small Power Standing 1.0 0.80 15.3 8 11 15 8 11 0.80 15.3 8 11 15 8 11
Reactor Cooling 1.0
Quad Booster 1 1.0
Shunt 1.0
Fans Bank A1 6 0.0 0.40 129.6 36 90 0 0 0 0.80 21.6 12 15 0 0 0
Fans Bank A2 8 0.0 0.40 129.6 36 90 0 0 0 0.80 21.6 12 15 0 0 0
Pump A1 4 0.0 0.40 44.4 12 31 0 0 0 0.80 7.4 4 5 0 0 0
Pump A2 4 0.0 0.40 44.4 12 31 0 0 0 0.80 7.4 4 5 0 0 0
Fans Bank B1 2 0.0 0.40 129.6 36 90 0 0 0 0.80 21.6 12 15 0 0 0
Fans Bank B2 4 0.0 0.40 129.6 36 90 0 0 0 0.80 21.6 12 15 0 0 0
Pump B1 13 0.0 0.40 44.4 12 31 0 0 0 0.80 7.4 4 5 0 0 0
Pump B2 14 0.0 0.40 44.4 12 31 0 0 0 0.80 7.4 4 5 0 0 0
0.0

Document Ref.: 1203-1743-C03 (A1) Page 1 of 5


WARDPOWER

LV Site Load Analysis & Generating Set Sizing Study


2. Loads (Continued«)

Load Starting Running


Before Diversity Including Diversity Before Diversity Including Diversity
Circuit/Description Group Diversity PF I1 I2 I3 3ph I KWe KVA I1 I2 I3 3ph I KWe KVA PF I1 I2 I3 3ph I KWe KVA I1 I2 I3 3ph I KWe KVA

Series 1.0 0.40 0 0 0 0 0.80 0 0 0 0


Fans Bank A1 5 1.0 0.40 194.4 54 135 194 54 135 0.80 32.4 18 22 32 18 22
Fans Bank A2 7 1.0 0.40 194.4 54 135 194 54 135 0.80 32.4 18 22 32 18 22
Pump A1 4 1.0 0.40 44.4 12 31 44 12 31 0.80 7.4 4 5 7 4 5
Pump A2 4 1.0 0.40 44.4 12 31 44 12 31 0.80 7.4 4 5 7 4 5
Fans Bank B1 1 1.0 0.40 194.4 54 135 194 54 135 0.80 32.4 18 22 32 18 22
Fans Bank B2 4 1.0 0.40 194.4 54 135 194 54 135 0.80 32.4 18 22 32 18 22
Pump B1 13 0.0 0.40 44.4 12 31 0 0 0 0.80 7.4 4 5 0 0 0
Pump B2 14 0.0 0.40 44.4 12 31 0 0 0 0.80 7.4 4 5 0 0 0
1.0
Quad Booster 2 1.0
Shunt 1.0
Fans Bank A1 Standing 0.0 0.40 217.8 60 151 0 0 0 0.80 36.3 20 25 0 0 0
Fans Bank A2 2 0.0 0.40 217.8 60 151 0 0 0 0.80 36.3 20 25 0 0 0
Pump A1/A2 6 0.0 0.40 70.2 19 49 0 0 0 0.80 11.7 6 8 0 0 0
Fans Bank B1 8 0.0 0.40 217.8 60 151 0 0 0 0.80 36.3 20 25 0 0 0
Fans Bank B2 10 0.0 0.40 217.8 60 151 0 0 0 0.80 36.3 20 25 0 0 0
Pump B1/B2 12 0.0 0.40 70.2 19 49 0 0 0 0.80 11.7 6 8 0 0 0
Series 0.0
Fans Bank A1 Standing 1.0 0.40 164.4 46 114 164 46 114 0.80 27.4 15 19 27 15 19
Fans Bank A2 2 1.0 1.40 164.4 159 114 164 159 114 0.80 27.4 15 19 27 15 19
Pump A1/A2 6 1.0 2.40 70.2 117 49 70 117 49 0.80 11.7 6 8 12 6 8
Fans Bank B1 8 1.0 0.40 164.4 46 114 164 46 114 0.80 27.4 15 19 27 15 19
Fans Bank B2 10 1.0 1.40 164.4 159 114 164 159 114 0.80 27.4 15 19 27 15 19
Pump B1/B2 12 0.0 2.40 70.2 117 49 0 0 0 0.80 11.7 6 8 0 0 0
SGT Cooling 1.0
SGT1 1.0
Bank A Standing 0.7 0.40 161.4 45 112 107 30 74 0.80 26.9 15 19 18 10 12
Bank B 6 0.7 0.40 161.4 45 112 107 30 74 0.80 26.9 15 19 18 10 12
SGT2 Standing 0.7 0.40 149.4 41 104 99 27 68 0.80 24.9 14 17 16 9 11
SGT3 0.7
Bank A Standing 0.7 0.40 111.6 31 77 74 20 51 0.80 18.6 10 13 12 7 9
Bank B 6 0.7 0.40 111.6 31 77 74 20 51 0.80 18.6 10 13 12 7 9
Water Heaters Standing 1.0 0.80 14.0 8 10 14 8 10 0.80 14.0 8 10 14 8 10
1.0
Manual & Intermittant Motors 1.0
Tap Changer Standing 1.0 0.40 8.4 2 6 8 2 6 0.80 0.0 0 0 0 0 0
Security Gate 16 1.0 0.40 32.0 9 22 32 9 22 0.80 0.0 0 0 0 0 0
1.0
ISS Loads 1.0
LVAC Room 1 Standing 0.0 0.80 69.2 54.5 61.6 34 43 0 0 0 0 0 0.80 69.2 54.5 61.6 34 43 0 0 0 0 0
LVAC Room 2 Standing 0.0 0.80 83.9 70.0 165.9 59 74 0 0 0 0 0 0.80 83.9 70.0 165.9 59 74 0 0 0 0 0
LVAC Room Standing 0.0 0.80 20.6 20.7 19.0 11 14 0 0 0 0 0 0.80 20.6 20.7 19.0 11 14 0 0 0 0 0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0

Document Ref.: 1203-1743-C03 (A1) Page 2 of 5


WARDPOWER

LV Site Load Analysis & Generating Set Sizing Study


2. Loads (Continued«)

Load Starting Running


Before Diversity Including Diversity Before Diversity Including Diversity
Circuit/Description Group Diversity PF I1 I2 I3 3ph I KWe KVA I1 I2 I3 3ph I KWe KVA PF I1 I2 I3 3ph I KWe KVA I1 I2 I3 3ph I KWe KVA

1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0

Totals: 0.52 6,653 6,624 6,726 6,479 2,404 4,619 4,376 4,376 4,376 4,376 1,620 3,032 0.80 1,493 1,464 1,566 1,319 836 1,045 969 969 969 969 537 671
Including Future Provision: 0.52 6,653 6,624 6,726 6,479 2,404 4,619 4,376 4,376 4,376 4,376 1,620 3,032 0.80 1,493 1,464 1,566 1,319 836 1,045 969 969 969 969 537 671

Document Ref.: 1203-1743-C03 (A1) Page 3 of 5


WARDPOWER

LV Site Load Analysis & Generating Set Sizing Study


3. Load Sequence

From the above loads, the following will be the starting and running loads for the Generating Set:
Load Group Loads Cumulative (Starting In Order) Starting Last
Timing (s) Can this Group be Starting Running Starting Running Starting
Load Group Description (From 0s) Started Last? KWe KVA KWe KVA KWe KVA KWe KVA KWe KVA

Standing Load Incl Compressor 1, QB2 A1 Fans, SGT1 A Bank Cooling, SGT2 Cooling, SGT3 A Bank Cooling 0 N 574 1,229 300 374 574 1,229 300 374
Load Group 1 QB1 Series B1 Fans 5 Y 54 135 18 22 353 509 317 397 573 783
Load Group 2 QB1 Shunt B1 Fans, QB2 A2 Fans 10 Y 159 114 15 19 477 511 333 416 681 766
Load Group 3 15 Y 0 0 0 0 333 416 333 416 537 671
Load Group 4 QB1 B2 Fans, QB1 A Pumps, 20 Y 78 196 26 33 411 612 359 449 589 835
Load Group 5 QB1 Series A1 Fans 25 Y 54 135 18 22 413 583 377 471 573 783
Load Group 6 Compressor 2, SGT1, SGT3 Bank B Cooling, QB1 Shunt A1 Fans, QB2 A Pumps 30 Y 433 839 112 140 809 1,310 489 611 858 1,370
Load Group 7 QB1 Series A2 Fans 35 Y 54 135 18 22 542 745 507 633 573 783
Load Group 8 QB1 Shunt A2 Fans, QB2 B1 Fans 40 Y 46 114 15 19 552 747 522 652 567 766
Load Group 9 45 Y 0 0 0 0 522 652 522 652 537 671
Load Group 10 QB2 B2 Fans 50 Y 159 114 15 19 681 766 537 671 681 766
Load Group 11 55 Y 0 0 0 0 537 671 537 671 537 671
Load Group 12 QB2 B Pumps 60 Y 0 0 0 0 537 671 537 671 537 671
Load Group 13 QB1 B1 Pumps 90 Y 0 0 0 0 537 671 537 671 537 671
Load Group 14 QB1 B2 Pumps 120 Y 0 0 0 0 537 671 537 671 537 671
Load Group 15 150 Y 0 0 0 0 537 671 537 671 537 671
Load Group 16 Manual motors 180 Y 9 22 0 0 546 693 537 671 546 693

The above figures include any given provision for future expansion if applicable.

4. Analysis

From the above, the Generating Set must be capable of: Site Loading Profile
KWe KVA pf
1,400
Worst Case Continuous Load 537 671 0.80
Peak Power 858 1,370
Largest Impact KVA 1,229 1,200
Largest Load Step 574
First Load Step 574
Largest Subsequent Step 433
Largest Phase (Expressed as Single Phase) 224 1,000

Is the first step the largest KWe step? YES


800
KVA/KWe

Phase Imbalance on Starting 2%


Phase Imbalance on Running 6%

600

400

KWe
200
KVA

0
-10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200
Time (s)

Document Ref.: 1203-1743-C03 (A1) Page 4 of 5


WARDPOWER

LV Site Load Analysis & Generating Set Sizing Study


Generating Set Selection & Verification

1. Component Selection & Performance

The following components are selected to meet this duty: Performance for these components would be as follows:

Engine: Perkins Frequency Transient: 10% Actuals Required


Model: 4006-23TAG3A Engine Rating: 683 KWm (Nett) ∆ KWm KWe KVA MCR ∆ KWm KWe KVA Check
Rated Load Factor 70%
Maximum Load Step: 66.0% Generator Rating (MCR) 683 643 800

Generator: CGT (Newage) Voltage Transient: 15% Peak Power 751 708 133% 858 Fail
Model: HCI634G Generator BCR: 800 KVA Continuous Load 478 450 83% 537 Ok
Generator Efficiency: 94.2% 800 84% 671 Ok
Maximum Load Step: 700 KVA
Maximum Frequency Transient 13.5% 10% Fail
Is this set fitted with a 50% rated Load Bank for Routine Testing? Y Y/N Maximum Voltage Transient 33.1% 15% Fail

Engine/Generator Ratio: 99% Generating Set Transient Performance


Generator Efficiency Curve Aspect: 100% 35%
Phase Imbalance as a proportion of Generator BCR 0%
Ratio Peak Power: Continuous Load 1.5977
30%

Notes:
- Peak Power as a proportion of MCR is calculated from KWe (Real Power) 25%
- Continuous Load as a proportion of MCR is calculated from KVA (Apparent Power)
- All KWm and KWe figures are Nett
- All figures are at site conditions 20%

15% Frequency Transient

Voltage Transient
10%
Frequency Limit
5%
Voltage Limit

0%
-10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200
Time (s)

2. Comments

The following comments are made concerning this selection:

- Engine Frequency Transients are approximate and may be the nearest quoted value for that load step. All Transients are calculated from no load condition.
- Power Factor is in the normal range.
- As this set is fitted with a 50% rated Loadbank for Routine Testing, Load Factor is not an issue for this application.
- Phase balance is acceptable.

Template F

Document Ref.: 1203-1743-C03 (A1) Page 5 of 5


WARDPOWER
LVAC Load Survey and Generating Set Sizing Study, NG Keadby

Scenario B2: ISS Load Only

Document Reference: 1203-1743-D11 (A) Page 11 of 11


WARDPOWER

LV Site Load Analysis & Generating Set Sizing Study


Enquiry No.: 1203-1743 Customer: Siemens
Date: 12-Sep-14 Project: NG Keadby ISS
Engineer: KXM Scenario: A2: ISS Load Only

Load Analysis

1. Scheme Information and Working Assumptions

This estimate has been prepared based upon the following scheme information and working assumptions:

System Voltage 400 V Frequency Transient 10%


System Frequency 50 Hz Voltage Transient 15%
Duty PRP Future Expansion 10%
Overload 10%
Rated PF 0.8

The following project specific information/assumptions is also used/made:

In addition, the following general assumptions are made:

- No regenerative loads
- Loads are applied in the groups given in 3 below with recovery times as given.

2. Loads

The following are the loads to be supported by the Generating Set:

Load Starting Running


Before Diversity Including Diversity Before Diversity Including Diversity
Circuit/Description Group Diversity PF I1 I2 I3 3ph I KWe KVA I1 I2 I3 3ph I KWe KVA PF I1 I2 I3 3ph I KWe KVA I1 I2 I3 3ph I KWe KVA

Standing Load Standing 1.0


1.0
ISS Loads 1.0
LVAC Room 1 Standing 1.0 0.80 69.2 54.5 61.6 34 43 69 54 62 34 43 0.80 69.2 54.5 61.6 34 43 69 54 62 34 43
LVAC Room 2 1 1.0 0.80 83.9 70.0 165.9 59 74 84 70 166 59 74 0.80 83.9 70.0 165.9 59 74 84 70 166 59 74
LVAC Room Standing 1.0 0.80 20.6 20.7 19.0 11 14 21 21 19 11 14 0.80 20.6 20.7 19.0 11 14 21 21 19 11 14
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
0.0

Document Ref.: 1203-1743-C03 (A2) Page 1 of 5


WARDPOWER

LV Site Load Analysis & Generating Set Sizing Study


2. Loads (Continued«)

Load Starting Running


Before Diversity Including Diversity Before Diversity Including Diversity
Circuit/Description Group Diversity PF I1 I2 I3 3ph I KWe KVA I1 I2 I3 3ph I KWe KVA PF I1 I2 I3 3ph I KWe KVA I1 I2 I3 3ph I KWe KVA

1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0

Document Ref.: 1203-1743-C03 (A2) Page 2 of 5


WARDPOWER

LV Site Load Analysis & Generating Set Sizing Study


2. Loads (Continued«)

Load Starting Running


Before Diversity Including Diversity Before Diversity Including Diversity
Circuit/Description Group Diversity PF I1 I2 I3 3ph I KWe KVA I1 I2 I3 3ph I KWe KVA PF I1 I2 I3 3ph I KWe KVA I1 I2 I3 3ph I KWe KVA

1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0

Totals: 0.80 174 145 247 0 104 131 174 145 247 188 104 131 0.80 174 145 247 0 104 131 174 145 247 188 104 131
Including Future Provision: 0.80 191 160 271 0 115 144 191 160 271 207 115 144 0.80 191 160 271 0 115 144 191 160 271 207 115 144

Document Ref.: 1203-1743-C03 (A2) Page 3 of 5


WARDPOWER

LV Site Load Analysis & Generating Set Sizing Study


3. Load Sequence

From the above loads, the following will be the starting and running loads for the Generating Set:
Load Group Loads Cumulative (Starting In Order) Starting Last
Timing (s) Can this Group be Starting Running Starting Running Starting
Load Group Description (From 0s) Started Last? KWe KVA KWe KVA KWe KVA KWe KVA KWe KVA

Standing Load 0 N 50 62 50 62 50 62 50 62
Load Group 1 5 Y 65 81 65 81 115 144 115 144 115 144
Load Group 2 10 Y 0 0 0 0 115 144 115 144 115 144
Load Group 3 15 Y 0 0 0 0 115 144 115 144 115 144
Load Group 4 20 Y 0 0 0 0 115 144 115 144 115 144
Load Group 5 25 Y 0 0 0 0 115 144 115 144 115 144
Load Group 6 30 Y 0 0 0 0 115 144 115 144 115 144
Load Group 7 35 Y 0 0 0 0 115 144 115 144 115 144
Load Group 8 40 Y 0 0 0 0 115 144 115 144 115 144
Load Group 9 45 Y 0 0 0 0 115 144 115 144 115 144
Load Group 10 50 Y 0 0 0 0 115 144 115 144 115 144
Load Group 11 55 Y 0 0 0 0 115 144 115 144 115 144
Load Group 12 60 Y 0 0 0 0 115 144 115 144 115 144
Load Group 13 90 Y 0 0 0 0 115 144 115 144 115 144
Load Group 14 120 Y 0 0 0 0 115 144 115 144 115 144
Load Group 15 150 Y 0 0 0 0 115 144 115 144 115 144
Load Group 16 180 Y 0 0 0 0 115 144 115 144 115 144

The above figures include any given provision for future expansion if applicable.

4. Analysis

From the above, the Generating Set must be capable of: Site Loading Profile
KWe KVA pf
160
Worst Case Continuous Load 115 144 0.80
Peak Power 115 144
Largest Impact KVA 81 140
Largest Load Step 65
First Load Step 50
Largest Subsequent Step 65 120
Largest Phase (Expressed as Single Phase) 63

Is the first step the largest KWe step? NO 100


KVA/KWe

Phase Imbalance on Starting 41%


Phase Imbalance on Running 41% 80

60

40
KWe
20
KVA

0
-10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200
Time (s)

Document Ref.: 1203-1743-C03 (A2) Page 4 of 5


WARDPOWER

LV Site Load Analysis & Generating Set Sizing Study


Generating Set Selection & Verification

1. Component Selection & Performance

The following components are selected to meet this duty: Performance for these components would be as follows:

Engine: Volvo Frequency Transient: 10% Actuals Required


Model: TAD732GE Engine Rating: 158 KWm (Nett) ∆ KWm KWe KVA MCR ∆ KWm KWe KVA Check
Rated Load Factor 70%
Maximum Load Step: 65.0% Generator Rating (MCR) 158 148 185

Generator: CGT (Newage) Voltage Transient: 15% Peak Power 174 163 78% 115 Ok
Model: HCI434C Generator BCR: 250 KVA Continuous Load 111 104 78% 115 Ok
Generator Efficiency: 93.7% 185 78% 144 Ok
Maximum Load Step: 260 KVA
Maximum Frequency Transient 6.8% 10% Ok
Is this set fitted with a 50% rated Load Bank for Routine Testing? Y Y/N Maximum Voltage Transient 8.1% 15% Ok

Engine/Generator Ratio: 135% Generating Set Transient Performance


Generator Efficiency Curve Aspect: 74% 16%
Phase Imbalance as a proportion of Generator BCR 31% See Comments
Ratio Peak Power: Continuous Load 1
14%

Notes:
12%
- Peak Power as a proportion of MCR is calculated from KWe (Real Power)
- Continuous Load as a proportion of MCR is calculated from KVA (Apparent Power)
- All KWm and KWe figures are Nett 10%
- All figures are at site conditions

8%
Frequency Transient
6%
Voltage Transient
4%
Frequency Limit

2%
Voltage Limit

0%
-10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200
Time (s)

2. Comments

The following comments are made concerning this selection:

- Engine Frequency Transients are approximate and may be the nearest quoted value for that load step. All Transients are calculated from no load condition.
- Power Factor is in the normal range.
- As this set is fitted with a 50% rated Loadbank for Routine Testing, Load Factor is not an issue for this application.
- From the load information provided, the phase imbalance is calculated as >5% of the Generator Rating. Voltage distortion may occur. This should be discussed with the manufacturer.

Template F

Document Ref.: 1203-1743-C03 (A2) Page 5 of 5