NSD70 Teleprotection
NSD70 Teleprotection
Teleprotection equipment.
ABB Automation
NSD 70 — the universal series of programmable teleprotection devices:
fast, reliable and secure —
the ideal solution regardless of transmission medium.
A B
TXC TXC
TX TX
RXC RXC
RX RX
NSD70 C
B
T
P L
TX Transmitter
TXC RXC RX Receiver P Communications cable
TXC Transmitted command (pilot wires)
RXC Received command L HV line or cable
■ NSD 70 C operating mode 1 for analogue communication ■ short transmission ■ maximum of two
with one or two independent single-tone command signals. times; 6 ms for single- command signals per
command signals and device; ideal for dou-
8 ms for dual-com- ble-circuit line protec-
mand signals in time- tion, several devices
saving applications operate in parallel on
different frequencies
■ NSD 70 D for digital communication with one to six indepen- ■ short transmission ■ up to six com-
dent command signals via a 64 kBit digital channel of a PCM multi- times; less than 3 ms mand signals per
plexer. The device is therefore especially suitable for the three-phase or less than 6 ms for device, for three-phase
protection of double-circuit lines. maximum security protection of double-
circuit lines
4
Highlights.
The well-tried All the units of the NSD 70 series have been developed and are manufactured
interface modules according to an established, well-tried concept. The entire series is subject
can be used in the to ongoing development to take account of changing user requirements and
to incorporate the latest technologies – without impairing compatibility or
same rack units
continuity.
in many different
fields of application. ■ The main advantages: maximum flexibility for all command transmission schemes
The greatest possible such as blocking, direct transfer tripping and permissive transfer tripping
flexibility and
■ protection of single or multiple teed feeders
adaptability are
thus achieved while ■ suitable for all transmission media, i.e. pilot wires, optical fibres,
PLC and radio
keeping stocks
of spares to a ■ extremely short transmission times
minimum. ■ reliable, secure and robust
■ digital signal pro- ■ 64 kbit/s electrical ■ 56 kbit/s or ■ optical fibre line ■ testing in opera-
cessing; special algo- line interfaces con- 64 kbit/s line interface interface with ranges tion; manual testing
rithms ensure highly forming to ITU-T conforming to EIA of 5 km and 18 km for and periodic self-test-
accurate signal evalua- standards G.703, Standards RS-422-A, multi-mode fibres and ing without disrupting
tion and high reli- V. 11, V. 36, X.21, RS-449 and RS-530 30 km for mono- normal operation,
ability X.24 and X.27 mode fibres plus interrogation of
the operating status at
the remote station
5
NSD 70 Technical Data.
The NSD 70 equipment family complies with IEC 60834-1 with the European EMC Directive 89/336/EEC and with the Low-Voltage
Directive 73/23/EEC.
Signals
TxC Signal input (transmit)
RxC Signal output (receive)
Rx AUX Auxiliary output
UB 1, 2 Unblocking outputs 1 and 2
S 1, 2 Terminals for supply 1 and 2
AF Tx AF output, transmit
AF Rx AF input, receive
Modules
G3HL CPU, signal processing module
G3HB Channel interface
G3HC/D Protection relay interface
G3HE Alarm interface
G3HF Trip counter (optional)
Displays
RDY Ready for service
GRD Guard signal, receive
TRP Trip signal, receive
LEV Level alarm
SNR Signal-to-noise ratio alarm
Tx Transmit signal
Rx Receive signal
Configuration of the NSD 70 C hardware. Protection, transmission and signal processing functions are strictly
divided, ensuring high immunity to electromagnetic interference and allowing modular design of the equipment.
In the NSD 70 D version for digital transmission, the AF interface is replaced by the PCM interface type G3HM,
the serial interface type G3HR or the optical interface type G3HS and the software in the central processing unit
is exchanged (DSP module type G3HP).
6
Receiver NSD 70 C mode 1 NSD 70 C mode 2/3 NSD 70 D
Input Level –30 to +2 dBm, adjustable, 600 Ohms balanced ITU-T V.11, EIA RS-422-A
Dynamic Range 30 dB 30 dB not applicable
Channel Centre 420 to 3660 Hz 420 to 3660 Hz not applicable
Frequencies in steps of 60 Hz in steps of 60 Hz
Bandwidth, or 120 / 240 / 360 / 480 / 960 / 1200 / 2400 Hz, 64 kbit/s gemäss ITU-T,
Signalling Rate according to the transmission time required 56 or 64 kbit/s according to EIA
Optical Interface not applicable not applicable 1300 nm; up to 5 km reach with
mulitmode fibres, up to 30 km
reach with monomode-fibres
Alarm Release loss of guard signal loss of guard signal loss of sync. or guard code
single component failure, invalid programming, self-test error
abnormal level, SNR abnormal level, SNR address, AIS, BER
7
1000 2.00 Printed in Switzerland