GWH 09 Qds 6 DBC 2 Ai
GWH 09 Qds 6 DBC 2 Ai
Service Manual
Table of Contents
Table of Contents
Service Manual
Appendix:....................................................................................................................... 115
Appendix 1: Reference Sheet of Celsius and Fahrenheit.............................. 115
Appendix 2: Configuration of Connection Pipe................................................ 115
Appendix 3: Pipe Expanding Method.................................................................... 116
Appendix 4: List of Resistance for Temperature Sensor............................... 117
Table of Contents
Service Manual
GWH09QD-S6DBC2A/I
GWH12QD-S6DBC2A/I
GWH09QC-S6DBC8A/I
GWH12QC-S6DBC8A/I
GWH09QD-S6DBD2A/I
GWH12QD-S6DBD2A/I
GWH18QE-S6DBD2B/I
GWH24QE-S6DBD2A/I
GWH09QD-S6DBE4A/I
GWH12QD-S6DBE4A/I
GWH18QE-S6DBE4B/I
GWH24QE-S6DBE4A/I
GWH09QD-S6DBE6A/I
GWH12QD-S6DBE6A/I
GWH18QE-S6DBE6B/I
GWH24QE-S6DBE6A/I
GWH09QD-S6DBD6A/I
GWH12QD-S6DBD6A/I
GWH18QE-S6DBD6B/I
GWH24QE-S6DBD6A/I
Technical Information 1
Service Manual
Outdoor Unit:
GWH09YD-S6DBA2A/O
GWH12YD-S6DBA2A/O
GWH09ACC-S6DBA1A/O
GWH12ACC-S6DBA1A/O
GWH18ACE-S6DBA1A/O
GWH24YE-S6DBA2A/O
Remote Controller:
YAG1FB3(WiFi) YAG1FB2(WiFi)
Models List:
2 Technical Information
Service Manual
2. Specifications
2.1 Specification Sheet
Model GWH09QC-S6DBC8A GWH12QC-S6DBC8A
Product Code CB456007000 CB456006900
Rated Voltage V~ 220-240 220-240
Power
Rated Frequency Hz 50/60 50/60
Supply
Phases 1 1
Power Supply Mode Outdoor Outdoor
Cooling Capacity W 2700 3530
Heating Capacity W 3500 4200
Cooling Power Input W 580 840
Heating Power Input W 800 1000
Cooling Power Current A 3.66 5.6
Heating Power Current A 4.90 6.6
Rated Input W 2400 2500
Rated Current A 6.76 9
3
Air Flow Volume(SH/H/MH/M/ML/L/SL) m /h 680/550/500/460/430/400/320 680/620/560/490/450/420/390
Dehumidifying Volume L/h 0.8 1
EER W/W 4.66 4.20
COP W/W 4.38 4.20
SEER W/W 7.8 7.60
HSPF / /
SCOP(Awerage/Warmer/Colder) 4.7/5.8/3.8 4.6/5.5/3.7
Application Area m2 12-18 12-18
Model of indoor unit GWH09QC-S6DBC8A/I GWH12QC-S6DBC8A/I
Indoor Unit Product Code CB456N07000 CB456N06900
Fan Type Cross-flow Cross-flow
Diameter Length(DXL) mm Φ98X633.5 Φ98X633.5
Fan Motor Cooling Speed (SH/H/MH/M/ML/L/SL/
r/min 1300/1200/1120/1050/980/920/750/500 1350/1200/1120/1050/980/920/750/500
SM)
Fan Motor Heating Speed(SH/H/MH/M/ML/L/SL/
r/min 1300/1200/1140/1080/1020/960/900/- 1350/1200/1140/1080/1020/960/900/-
SM)
Output of Fan Motor W 20 20
Fan Motor RLA A 0.09 0.09
Fan Motor Capacitor μF / /
Input of Heater W / /
Indoor Evaporator Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Unit Pipe Diameter mm Φ5 Φ5
Row-fin Gap mm 2-1.4 2-1.4
Coil Length (LXDXW) mm 635X22.8X306.3 635X22.8X306.3
Swing Motor Model MP24BA/MP24EB MP24EB/MP24HF
Output of Swing Motor W 1.5/1.5 1.5/1.5
Fuse A 3.15 3.15
Sound Pressure Level (SH/H/MH/M/ML/L/SL/SM) dB (A) 41/39/36/34/32/31/25/- 42/39/36/35/33/31/25/22
Sound Power Level (SH/H/MH/M/ML/L/SL/SM) dB (A) 56/49/46/44/42/41/35/- 58/49/46/45/43/41/35/32
Dimension (WXHXD) mm 845X289X209 845X289X209
Dimension of Carton Box (LXWXH) mm 918X278X364 918X278X364
Dimension of Package (LXWXH) mm 921X281X379 921X281X379
Net Weight kg 10.5 11
Gross Weight kg 12.5 13
Technical Information 3
Service Manual
4 Technical Information
Service Manual
1.GWH09QD-S6DBC2A 2.GWH09QD-S6DBD2A
Model 3.GWH09QD-S6DBE4A 4.GWH09QD-S6DBE6A
5.GWH09QD-S6DBD6A
1.CB439014909 2.CB461006109
Product Code 3.CB470005009 4.CB465003309
5.CB460007009
Rated Voltage V~ 220-240
Power
Rated Frequency Hz 50/60
Supply
Phases 1
Power Supply Mode Outdoor
Cooling Capacity W 2700
Heating Capacity W 3500
Cooling Power Input W 550
Heating Power Input W 745
Cooling Power Current A 3.52
Heating Power Current A 4.63
Rated Input W 2400
Rated Current A 7.99
Air Flow Volume(SH/H/MH/M/ML/L/SL) m3/h 800/730/680/630/580/450/350
Dehumidifying Volume L/h 0.8
EER W/W 4.91
COP W/W 4.70
SEER W/W 8.50
HSPF W/W /
SCOP(Awerage/Warmer/Colder) 5.1/5.7/3.8
Application Area m2 12-18
1.GWH09QD-S6DBC2A/I 2.GWH09QD-S6DBD2A/I
Model of indoor unit 3.GWH09QD-S6DBE4A/I 4.GWH09QD-S6DBE6A/I
5.GWH09QD-S6DBD6A/I
1.CB439N14900 2.CB461N06100
Indoor Unit Product Code 3.CB470N05000 4.CB465N03300
5.CB460N07000
Fan Type Cross-flow
Diameter Length(DXL) mm Φ106X706
Fan Motor Cooling Speed r/min 1200/1100/1030/960/820/650/600/500
Fan Motor Heating Speed r/min 1300/1200/1120/1040/880/700/650/-
Output of Fan Motor W 60
Fan Motor RLA A 0.24
Fan Motor Capacitor μF /
Input of Heater W /
Evaporator Form Aluminum Fin-copper Tube
Indoor Unit Pipe Diameter mm Φ7
Row-fin Gap mm 2-1.4
Coil Length (LXDXW) mm 715X25.4X304.8
Swing Motor Model MP35CJ/MP24HF
Output of Swing Motor W 2.5/1.5
Fuse A 3.15
Sound Pressure Level (SH/H/MH/M/ML/
dB (A) 44/43/38/36/31/24/22
L/SL)
Sound Power Level (SH/H/MH/M/ML/L/
dB (A) 58/53/48/46/41/34/32
SL)
Dimension (WXHXD) mm 970X300X224
Dimension of Carton Box (LXWXH) mm 1038X380×X305
Dimension of Package (LXWXH) mm 1041X383X320
Net Weight kg 13
Gross Weight kg 16
Technical Information 5
Service Manual
6 Technical Information
Service Manual
1.GWH12QD-S6DBC2A 2.GWH12QD-S6DBD2A
Model 3.GWH12QD-S6DBE4A 4.GWH12QD-S6DBE6A
5.GWH12QD-S6DBD6A
1.CB439014808 2.CB461006208
Product Code 3.CB470005108 4.CB465003408
5.CB460006908
Rated Voltage V~ 220-240
Power
Rated Frequency Hz 50/60
Supply
Phases 1
Power Supply Mode Outdoor
Cooling Capacity W 3530
Heating Capacity W 4200
Cooling Power Input W 840
Heating Power Input W 950
Cooling Power Current A 5.10
Heating Power Current A 5.70
Rated Input W 2600
Rated Current A 8.2
Air Flow Volume(SH/H/MH/M/ML/L/SL) m3/h 800/730/680/630/580/450/350
Dehumidifying Volume L/h 1.40
EER W/W 4.20
COP W/W 4.42
SEER W/W 8.50
HSPF W/W /
SCOP(Awerage/Warmer/Colder) 5.1/5.7/4
Application Area m2 16-24
1.GWH12QD-S6DBC2A/I 2.GWH12QD-S6DBD2A/I
Model of indoor unit 3.GWH12QD-S6DBE4A/I 4.GWH12QD-S6DBE6A/I
5.GWH12QD-S6DBD6A/I
1.CB439N14800 2.CB461N06200
Indoor Unit Product Code 3.CB470N05100 4.CB465N03400
5.CB460N06900
Fan Type Cross-flow
Diameter Length(DXL) mm Φ106X706
Fan Motor Cooling Speed r/min 1200/1100/1030/960/820/650/600/500
Fan Motor Heating Speed r/min 1300/1200/1120/1040/880/700/650/-
Output of Fan Motor W 60
Fan Motor RLA A 0.24
Fan Motor Capacitor μF /
Input of Heater W /
Evaporator Form Aluminum Fin-copper Tube
Indoor Unit
Pipe Diameter mm Φ7
Row-fin Gap mm 2-1.4
Coil Length (LXDXW) mm 715X25.4X304.8
Swing Motor Model MP35CJ/MP24HF
Output of Swing Motor W 2.5/1.5
Fuse A 3.15
Sound Pressure Level (SH/H/MH/M/ML/L/
dB (A) 44/43/38/36/31/24/22
SL)
Sound Power Level (SH/H/MH/M/ML/L/SL) dB (A) 58/53/48/46/41/34/32
Dimension (WXHXD) mm 970X300X224
Dimension of Carton Box (LXWXH) mm 1038X380×X305
Dimension of Package (LXWXH) mm 1041X383X320
Net Weight kg 13.5
Gross Weight kg 16.5
Technical Information 7
Service Manual
The above data is subject to change without notice; please refer to the nameplate of the unit.
8 Technical Information
Service Manual
1.GWH18QE-S6DBD2B 2.GWH18QE-S6DBE4B
Model
3.GWH18QE-S6DBE6B 4.GWH18QE-S6DBD6B
1.CB461005900 2.CB470005200
Product Code
3.CB465003600 4.CB460006800
Rated Voltage V~ 220-240
Power
Rated Frequency Hz 50/60
Supply
Phases 1
Power Supply Mode Outdoor
Cooling Capacity W 5300
Heating Capacity W 6200
Cooling Power Input W 1180
Heating Power Input W 1450
Cooling Power Current A 5.9
Heating Power Current A 5.9
Rated Input W 3200
Rated Current A 15
Air Flow Volume(SH/H/MH/M/ML/L/SL) m3/h 1200/1150/1050/950/850/780/600
Dehumidifying Volume L/h 1.8
EER W/W 4.49
COP W/W 4.27
SEER 7.5
HSPF /
SCOP(Awerage/Warmer/Colder) 4.4/5.1/3.4
Application Area m2 23-34
1.GWH18QE-S6DBD2B/I 2.GWH18QE-S6DBE4B/I
Model of indoor unit
3.GWH18QE-S6DBE6B/I 4.GWH18QE-S6DBD6B/I
1.CB461N05900 2.CB470N05200
Indoor Unit Product Code
3.CB465N03600 4.CB460N06800
Fan Type Cross-flow
Diameter Length(DXL) mm Φ108X830
Fan Motor Cooling Speed (SH/H/MH/M/ML/L/SL/
r/min 1200/1150/1100/1000/900/850/800/600
SM)
Fan Motor Heating Speed(SH/H/MH/M/ML/L/SL/
r/min 1250/1150/1100/1000/800/700/650/-
SM)
Output of Fan Motor W 60
Fan Motor RLA A 0.24
Fan Motor Capacitor μF /
Input of Heater W /
Evaporator Form Aluminum Fin-copper Tube
Indoor
Pipe Diameter mm Φ7
Unit
Row-fin Gap mm 2-1.4
Coil Length (LXDXW) mm 845X25.4X342.9
Swing Motor Model MP35CJ/MP24HF
Output of Swing Motor W 2.5/1.5
Fuse A 3.15
dB Cooling:46/44/42/39/36/34/32/-
Sound Pressure Level (SH/H/MH/M/ML/L/SL/SM)
(A) Heating:47/44/43/40/32/28/25/-
dB Cooling:60/54/52/49/46/44/42/-
Sound Power Level (SH/H/MH/M/ML/L/SL/SM)
(A) Heating:57/54/53/50/42/38/35/-
Dimension (WXHXD) mm 1078X325X246
Dimension of Carton Box (LXWXH) mm 1145X410X335
Dimension of Package (LXWXH) mm 1148X413X350
Net Weight kg 16.5
Gross Weight kg 20
Technical Information 9
Service Manual
The above data is subject to change without notice; please refer to the nameplate of the unit.
10 Technical Information
Service Manual
1.GWH24QE-S6DBD2A 2.GWH24QE-S6DBE4A
Model
3.GWH24QE-S6DBE6A 4.GWH24QE-S6DBD6A
1.CB461006000 2.CB470005300
Product Code
3.CB465003500 4.CB460007100
Rated Voltage V~ 220-240
Power
Rated Frequency Hz 50/60
Supply
Phases 1
Power Supply Mode Outdoor
Cooling Capacity W 7034
Heating Capacity W 7034
Cooling Power Input W 1850
Heating Power Input W 1750
Cooling Power Current A 11
Heating Power Current A 10.76
Rated Input W 3800
Rated Current A 16.4
Rated Heating Current A 16.4
Air Flow Volume(SH/H/MH/M/ML/L/SL) m3/h 1200/1050/950/900/850/750/700
Dehumidifying Volume L/h 2
EER W/W 3.8
COP W/W 4
SEER W/W 6.5
HSPF W/W /
SCOP(Average/Warmer/Colder) 4.1/5.3/3.5
Application Area m2 32-50
1.GWH24QE-S6DBD2A/I 2.GWH24QE-S6DBE4A/I
Model of indoor unit
3.GWH24QE-S6DBE6A/I 4.GWH24QE-S6DBD6A/I
1.CB461N06000 2.CB470N05300
Indoor Unit Product Code
3.CB465N03500 4.CB460N07100
Fan Type Cross-flow
Diameter Length(DXL) mm Φ106X890
Fan Motor Cooling Speed r/min 1250/1100/1000/950/900/850/800/600
Fan Motor Heating Speed r/min 1400/1250/1100/1050/1000/900/850
Output of Fan Motor W 60
Fan Motor RLA A 0.24
Fan Motor Capacitor μF /
Input of Heater W /
Evaporator Form Aluminum Fin-copper Tube
Pipe Diameter mm Φ7
Indoor Unit
Row-fin Gap mm 2-1.5
Coil Length (LXDXW) mm 845X25.4X381
Swing Motor Model MP35CJ/MP24HF
Output of Swing Motor W 2.5/1.5
Fuse A 3.15
Technical Information 11
Service Manual
The above data is subject to change without notice; please refer to the nameplate of the unit.
12 Technical Information
Service Manual
09K
Cooling
110
100
Heating
90 250
200
Capacity ratio(%)
Capacity ratio(%)
80
150
70
100 Condition
Condition Indoor:DB 20°C
Indoor:DB 27°C WB19°C Indoor air flow:Super High
60 Indoor air flow: Super High 50 Pipe length:5m
Pipe length:5m
50 0
20 22 24 26 28 30 32 36 38 40 42 44 46 48 50 52 54 -30 -25 -20 -15 -10 -5 0 5 7 10
Outdoor temp. (°C) Outdoor temp(°C)
12K
Cooling
110 Heating
100
200
180
90 160
Capacity ratio(%)
140
Capacity ratio(%)
80 120
100
70 80 Condition
60 Indoor:DB 20°C
Condition
Indoor:DB 27°C WB19°C
Indoor air flow:Super High
60 Indoor air flow: Super High 40 Pipe length:5m
Pipe length:5m
20
50 0
20 22 24 26 28 30 32 36 38 40 42 44 46 48 50 52 54
-30 -25 -20 -15 -10 -5 0 5 7 10
Outdoor temp. (°C)
Outdoor temp(°C)
Technical Information 13
Service Manual
18/24K
Cooling
110
100
90 Heating
120
Capacity ratio(%)
80
100
Capacity ratio(%)
80
70
60 Condition
Condition
Indoor:DB 20°C
Indoor:DB 27°C WB19°C
60 40
Indoor air flow: Super High Indoor air flow:Super High
Pipe length:5/7.5m Pipe length:5/7.5m
20
50
0
21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 -30 -25 -20 -15 -10 -5 0 5 10 15 24
Outdoor temp. (°C)
Outdoor temp(°C)
Heating:
Rated heating Pressure of gas pipe Inlet and outlet pipe
Compressor
condition(°C) connecting indoor and temperature of heat Fan speed of Fan speed of
Model frequency
(DB/WB) outdoor unit exchanger indoor unit outdoor unit
(Hz)
Indoor Outdoor P (MPa) T1 (°C) T2 (°C)
20/- 7/6 9/12K 2.8 to 3.0 70 to 35 2 to 4 Super High High 60
20/- 7/6 18/24K 2.8 to 3.0 70 to 35 2 to 4 Super High High 77
Instruction:
T1: Inlet and outlet pipe temperature of evaporator
T2: Inlet and outlet pipe temperature of condenser
P: Pressure at the side of big valve
Connection pipe length: 5/7.5m.
14 Technical Information
Service Manual
60 60
58
50 Heating
Noise dB(A)
56
Noise dB(A)
40 54
Cooling
52
30 50
9/12K 48
20
46
20 30 40 50 60 70 80 90 100
10
Super Middle Middle Super Compressor frequency(Hz)
Low Low Low Middle High High High
60 60
58
50 Heating
Noise dB(A)
24K 56
Noise dB(A)
40 54
18K Cooling
52
30 50
48
20
46
20 30 40 50 60 70 80 90 100
10
Super Middle Middle Super Compressor frequency(Hz)
Low Low Low Middle High High High
Technical Information 15
Service Manual
W D
H
123.5 542 179.5
QC
Φ55 Φ55
35 35
124.7 83.2
Φ55 Φ55
38 38
190 140
QE
16 Technical Information
Service Manual
818
303
596
899 378
354
550 Unit:mm
GWH18ACE-S6DBA1A/O GWH18ACE-S6DBA1A/O
1003 427
395
Unit:mm
610
Technical Information 17
Service Manual
GAS SIDE
3-WAY VALVE
4-Way valve
Discharge
HEAT
EXCHANGE
(EVAPORATOR) Suction Accumlator
COMPRESSOR
D
HEAT
EXCHANGE
(CONDENSER)
LIQUID SIDE Intercooler
COOLING
HEATING
09/12/24K:
GAS SIDE
3-WAY VALVE
4-Way valve
Discharge
HEAT
EXCHANGE
(EVAPORATOR) Suction Accumlator
COMPRESSOR
D
HEAT
EXCHANGE
(CONDENSER)
LIQUID SIDE Intercooler
COOLING
HEATING
18 Technical Information
Service Manual
5. Electrical Part
5.1 Wiring Diagram
●Instruction
Note: Jumper cap is used to determine fan speed and the swing angle of horizontal lover for this model.
● Indoor Unit
GWH12QC-S6DBC8A/I GWH09QC-S6DBC8A/I
:,5(' :$51,1*
7(036(1625
7(036(1625
3OHDVHGRQ WWRXFKDQ\
&21752//(5
5(&(,9(5$1' :,), HOHFWURQLFFRPSRQHQWDQG
',63/$<%2$5' 02'8/( $3
WHUPLQDOZKHQWKHPDFKLQH
5220
78%(
LVUXQQLQJVWRSSLQJRU
$3 $3 KDVEHHQSRZHUHGRIIIRU
OHVVWKDQPLQXWHVWR
SUHYHQWHOHFWULFVKRFN
57 57 &211(&725 0$*1(7,& 7(50,1$/
5,1* %/2&.
/ %8 %8
287'22581,7
1 1
76(1625 ',63 ',63 :,), &200$18$/
&$3 %. %.
&20287
$30$,1%2$5' / %1 %1
-803 $&/
'5<&
'&02725 6:,1*8' 6:,1*/5 '225& <(*1 <(*1 <(*1
3(
+($/7+/ +($/7+1 &211(&7,1*
;7 &$%/(
3(
(9$325$725
0 0 5' %8
0
&2/'3/$60$
$3
)$1 83'2:1 /()75,*+7 *(1(5$725
'5<
02725 67(33,1* 67(33,1* &217$&7
60000700030904
02725 02725
237,21$/
Technical Information 19
Service Manual
237,21$/
52207(03
78%(7(03
:$51,1*
:,5(' 237,21$/ 3OHDVHGRQ WWRXFKDQ\
5(&(,9(5$1' &21752//(5 :,),02'8/(
6(1625
6(1625
HOHFWURQLFFRPSRQHQWRU
',63/$<%2$5' WHUPLQDOZKHQWKHPDFKLQH
$3 $3 LVUXQQLQJVWRSSLQJRUKDV
$3 EHHQSRZHUHGRIIIRUOHVV
WKDQPLQXWHVWRSUHYHQW
HOHFWULFVKRFN
57 57 &211(&725 &211(&725
7(50,1$/
%/2&.
287'22581,7
76(1625 ',63 ',63 &200$18$/ :,), / %8 %8
1 1
/ %. %.
&20287
&$3 $3 / %1 %1
$&/
-803 0$,1%2$5' <(*1
<(*1 &11(&7,1*
'5<& ;7 &$%/(
'&02725 6:,1*8' 6:,1*/5 '225& <(*1
3( 3(
+($/7+/ +($/7+1 (9$325$725
0 0 5' %8
0
&2/'3/$60$
83'2:1 /()75,*+7 $3 *(1(5$725
)$102725 67(33,1* 67(33,1* '5<&217$&7
02725 02725 237,21$/
60000700033807
● Outdoor Unit
GWH12ACC-S6DBA1A/O GWH09ACC-S6DBA1A/O
7(036(1625
7(036(1625
7(036(1625
7(036(1625
29(5/2$'
:$51,1*
:$<9$/9(
3527(&725 &203
28778%(
3OHDVHGRQ WWRXFKDQ\
28778%(
2875220
(;+$867
ULVNRIHOHFWULFVKRFN <9
5,1*
%8 %8 /
1 1 1
%. %. / $3
&20B,11(5
%1 %1 /
<(*1
/ $&B/ 35,17('&,5&8,7%2$5'
<(*1
;7 3( 2)$1 +($7 :$< )$ 5HG )$ :KLWH
%8 3(
1
/ %1 %. /
<(*1 0$*1(7,&
5,1* <(*1 0 3(
32:(5 (+ 97 97
3( <(*1 <(*1
)$102725 3( 3( (.9 (.9
1RWH0RWRUJURXQG %27720 <9 (/(&7521,& (/(&7521,&
60000706165401 RQO\DSSOLHVWRWKH %$1' 3( :$< (;3$16,21 (;3$16,21
LURQVKHOOPRWRU +($7(5 9$/9( 9$/9($ 9$/9(%
20 Technical Information
Service Manual
GWH12YD-S6DBA2A/O
7(036(1625
7(036(1625
7(036(1625
7(036(1625
29(5/2$'
:$51,1*
:$<9$/9(
3527(&725 &203
28778%(
3OHDVHGRQ WWRXFKDQ\
28778%(
2875220
(;+$867
WHUPLQDOZKHQWKHYROWDJH 6$7 8 &203 3(
<(*1
RIWHUPLQDO3 '& DQG 9 :
1 '& DW$3LVKLJKHU 5' 5' %8 <( 5'
WKDQ9WRSUHYHQWWKH 57 57 57 57 ;
3(
0$*1(7,&
ULVNRIHOHFWULFVKRFN <9
5,1*
. . . / / /
:+ %. :+ %8 <( 5'
7(50,1$/ 0$*1(7,& 8 %8 9 <( : 5'
%/2&. 5,1*
7B6(1625 6(1625 :$< 29&B&203
,1'22581,7
%8 %8 /
1 1 1
%. %. / $3
&20B,11(5
%1 %1 /
<(*1
/ $&B/ 35,17('&,5&8,7%2$5'
<(*1
;7 3( 2)$1 +($7 :$< )$ 5HG )$ :KLWH
%8 3(
1
/ %1 %. /
<(*1 0$*1(7,&
5,1* <(*1 0 3( 97 97
32:(5 (+
3( <(*1
<(*1
)$102725 3( 3( (.9 (.9
1RWH0RWRUJURXQG %27720 <9 (/(&7521,& (/(&7521,&
60000706225101 RQO\DSSOLHVWRWKH %$1' 3( :$< (;3$16,21 (;3$16,21
LURQVKHOOPRWRU +($7(5 9$/9( 9$/9($ 9$/9(%
GWH09YD-S6DBA2A/O
7(036(1625
7(036(1625
7(036(1625
7(036(1625
29(5/2$'
:$51,1*
:$<9$/9(
3527(&725 &203
28778%(
3OHDVHGRQ WWRXFKDQ\
28778%(
2875220
(;+$867
ULVNRIHOHFWULFVKRFN <9
5,1*
%8 / / %8
1 1 1
%. / / %.
&20B,11(5 $3
%1 / / %1
<(*1
/ $&B/ 35,17('&,5&8,7%2$5'
<(*1
;7 3( 2)$1 +($7 :$< )$ 5HG )$ :KLWH
%8 3(
1
/ %1 %. /
<(*1 0$*1(7,&
5,1* <(*1 0 3(97 97
32:(5 (+
3( <(*1
<(*1
)$102725 3( 3( (.9 (.9
1RWH0RWRUJURXQG %27720 <9 (/(&7521,& (/(&7521,&
600007062251 RQO\DSSOLHVWRWKH %$1' 3( :$< (;3$16,21 (;3$16,21
LURQVKHOOPRWRU +($7(5 9$/9( 9$/9($ 9$/9(%
Technical Information 21
Service Manual
GWH18ACE-S6DBA1A/O
:$51,1*
7(036(1625
7(036(1625
7(036(1625
7(036(1625
:$<9$/9(
3OHDVHGRQ WWRXFKDQ\ &203
28778%(
28778%(
2875220
(;+$867
WHUPLQDOZKHQWKHYROWDJH 8 &203
RIWHUPLQDO3 '& DQG
1 '& DW$3LVKLJKHU 0$*1(7,& 9 :
WKDQ9WRSUHYHQWWKH 5,1*
ULVNRIHOHFWULFVKRFN 57 57 57 57 / / /
<9 :+
%8 <( 5'
<(*1 . . . ;
,1'22581,7
GWH24YE-S6DBA2A/O
:$51,1*
7(036(1625
7(036(1625
7(036(1625
7(036(1625
:$<9$/9(
2875220
(;+$867
WHUPLQDOZKHQWKHYROWDJH 8 &203 3(
RIWHUPLQDO3 '& DQG <(*1
1 '& DW$3LVKLJKHU 0$*1(7,& 9 :
WKDQ9WRSUHYHQWWKH 5,1*
ULVNRIHOHFWULFVKRFN 57 57 57 57 / / /
<9 :+ 3(
%8 <( 5'
<(*1 . . . ;
,1'22581,7
These wiring diagrams are subject to change without notice; please refer to the one supplied with the unit.
22 Technical Information
Service Manual
1 2 3 4
No. Name
1 Neutral wire
2 Needle stand for indoor fan
3 Auto button
4 Up&down swing interface
13
14 5 Grounding wire
6 Interface of temperature sensor
Terminal for display board
12 15 7
connection
8 Terminal of jumper cap
16 9 Communication wire
10 Fuse
6 11 Live wire interface
Interface of health function
12
neutral wire
Interface of health function
13
5 7 live wire
14 Left&right swing interface
11 15 Terminal of wired controlle
16 Interface of gate control
10 17 Detecting plate(WIFI )
9 8 17
● Bottom view
Technical Information 23
Service Manual
● Outdoor Unit
09/12K
● Top view
No. Name
2 3 4 5 6 7 8 9 10 1 Terminal of compressor
Overload Terminal of
2
compressor
1 Terminal of temperature
3
sensor
Terminal of electronic
4
expansion valve 1
Terminal of electronic
5
expansion valve 2
Low-temperature cooling
11 6
sensor
7 Terminal of outdoor fan
Terminal of chassis electric
8
heater
9 Terminal of 2-way valve
12 10 Terminal of 4-way valve
Communication wire with
13 11
indoor unit
14 12 Live wire terminal
13 Earthing wire terminal
14 Neutral wire terminal
● Bottom view
24 Technical Information
Service Manual
18K
● Top view
1 2 3 4 5 6 7 8 9
No. Name
1 Interface of compressor
10
Interface of temperature
2
sensor
Terminal of compressor
3
overload protection
Low-temperature cooling
4
11 sensor
5 Cooling A valve
6 Cooling B valve
7 Interface of outdoor motor
12 8 Interface of 2-way valve
9 Interface of 4-way valve
Terminal of chassis electric
10
heating
Communication wire with
13 11
indoor unit
Live wire interface of power
12
cord
Earthing wire interface of cold
13
14 plasma
Neutral wire interface of power
14
cord
● Bottom view
Technical Information 25
Service Manual
24K
● Top view
1 2 3 4 5 6 7 8 9
No. Name
1 Interface of compressor
10 Interface of temperature
2
sensor
Te r m i n a l o f c o m p r e s s o r
3
overload protection
Low-temperature cooling
11 4
sensor
5 Cooling A valve
6 Cooling B valve
12 7 Interface of outdoor motor
8 Interface of 2-way valve
9 Interface of 4-way valve
Terminal of chassis electric
10
13 heating
Communication wire with
11
indoor unit
Live wire interface of power
12
14 cord
Earthing wire interface of cold
13
plasma
Neutral wire interface of
14
power cord
● Bottom view
26 Technical Information
Service Manual
1 ON/OFF button
2 FAN button
3 MODE button
4 +/- button
5 TURBO button
2
2 6 button
5 6
4 7 button
4 11
7
3
3 9
8 8 CLOCK button
10 12
1 13 WiFi
1 9 TIMER ON/
14 16
15 TIMER OFF button
10 TEMP button
11 / button
(before opening cover (after opening cover
12 I FEEL button
1 ON/OFF button 13 LIGHT button
2 FAN button 14 WiFi button
3 MODE button 15 QUIET button
4 +/- button 16 SLEEP button
● This is a general use remote controller, it could be used for the air conditioners with multifunction; For some function, which the
model doesn't have, if press the corresponding button on the remote controller that the unit will keep the original running status.
indicator (red indicator the colour is
different for different models).
Press this button, the unit will be turned on, press it once more, the unit will be turned off. Sleep function will be canceled, while unit off.
Technical Information 27
Service Manual
ATUO
Low fan Medium-low fan Medium fan Medium-high fan High fan
Note:
● It’s Low fan speed under Dry mode.
● X-FAN functionHold fan speed button for 2s in COOL or DRY mode, the icon “ ” is displayed and the indoor fan will continue
operation for a few minutes in order to dry the indoor unit even though you have turned off the unit. After energization, X-FAN OFF is
defaulted. X-FAN is not available in AUTO, FAN or HEAT mode.
This function indicates that moisture on evaporator of indoor unit will be blowed after the unit is stopped to avoid mould.
● Having set X-FAN function on: After turning off the unit by pressing ON/OFF button indoor fan will continue running for a few minutes. at
low speed. In this period, Hold fan speed button for 2s to stop indoor fan directly.
● Having set X-FAN function off: After turning off the unit by pressing ON/OFF button, the complete unit will be off directly.
Press " + " or " - " button once increase or decrease set temperature 1°C(°F). Holding " + " or " - " button, set temperature on remote
controller will change quickly. On releasing button after setting is finished, temperature indicator on indoor unit will change accordingly.
When setting TIMER ON, TIMER OFF or CLOCK, press " + " or " - " button to adjust time. (Refer to CLOCK, TIMER ON, TIMER OFF
buttons)
OFF
OFF
28 Technical Information
Service Manual
Note:
Outdoor temperature display is not available for some models. At that time, indoor unit receives " " signal, while it displays indoor
set temperature.
Press this button once, to turn on the I FEEL function, then the figure of "I FEEL"will be displayed, after every press of other function button,
every 200ms to sendI FEEL once, after this function started, the remote controller will send temperatureto the main un it in every 10 minutes.
When repress this button, this function will beturned off. When I FEEL function is turned on, the remote controller should be put within the
area where indoor unit can receive the signal sent by the remote controller.
WiFi button
Press " WiFi " button to turn on or turn off WiFi function. When WiFi function is turned on, the " WiFi " icon will be displayed on remote
controller; Under status of remote controller off, press "MODE" and " WiFi " buttons simultaneously for 1s, WiFi module will restore to
factory default setting.
● This function is only available for some models.
Press this button, the Quiet status is under the Auto Quiet mode (display" "and "Auto" signal) and Quiet mode (display " " signal)
and Quiet OFF (there is no signal of " " displayed), after powered on, the Quiet OFF is defaulted.Under the Quiet mode (Display " "
signal).
The Quiet function is only available for some models.
Press this button, can select Sleep 1 ( ), Sleep 2 ( ), Sleep 3 ( ) andcancel the Sleep, circulate between these, after electrified,
Sleep Cancel is de-faulted.
Sleep 1 is Sleep mode 1, in Cool modes: sleep status after run for one hour, the main unit setting temperature will increase 1, 2 hours,
setting temperatureincreased 2, the unit will run at this setting temperature; In Heat mode:sleep status after run for one hour , the setting
temperature will decrease 1, 2 hours, setting temperature will decrease 2 , then the unit will run at this settingtemperature .
Sleep 2 is sleep mode 2, that is air conditioner will run according to the presettinga group of sleep temperature curve.
In Cool mode:
(1) When setting the initial temperature 16-23, after turned on Sleep function,the temperature will be increased 1 in every hour ,
after 3 the temperaturewill be maintained, after 7hours, the temperature will be decreased 1, afterthat the unit will keep on running
under this temperature;
(2) When setting the initial temperature 24-27, after turned on Sleep function,the temperature will be increased 1 in every hour ,
after 2 the temperaturewill be maintained, after 7hours, the temperature will be decreased 1, afterthat the unit will keep on running
under this temperature;
(3) When setting the initial temperature 28-29, after turned on Sleep function,the temperature will be increased 1 in every hour ,
after 1 the temperature will be maintained, after 7hours, the temperature will be decreased 1, afterthat the unit will keep on running
under this temperature;
Technical Information 29
Service Manual
(4) When setting the initial temperature 30, under this temperature setting, after 7hours, the temperature will be decreased 1, after
that the unit will keep onrunning under this temperature;
In Heat mode:
(1) Under the initial presetting temperature 16, it will run under this setting temperature all along .
(2) Under the initial presetting temperature17-20, after Sleep function started up, the temperature will decrease 1 in every hour ,
after 1 decreased, thistemperature will be maintained.
(3) Under the initial presetting temperature 21-27, after Sleep function started up, the temperature will decrease 1 in every hou r,
after 2 decreased, thistemperature will be maintained.
(4) Under the initial presetting temperature 28-30, after Sleep function started up, the temperature will decrease 1 in every hou r,
after 3 decreased, thistemperature will be maintained.
Sleep 3 - the sleep curve setting under Sleep mode by DIY:
(1) Under Sleep 3 mode, press "Turbo" button for a long time, remote controller enters into user individuation sleep setting status, at this
time, the time of remotecontroller will display "1hour", the setting temperature "88" will display the corr-esponding temperature of last setting
sleep curve and blink (The first enteringwill display according to the initial curve setting value of original factory);
2) Adjust "+" and "-" button, could change the corresponding setting temperature,after adjusted, press "Trubo" button for confirmation;
(3) At this time, 1hour will be automatically increased at the timer postion on the remote controller, (that are "2hours" or "3hours" or "8hours"),
the place of setting temperature "88" will display the corresponding temperature of last settingsleep curve and blink;
(4) Repeat the above step (2)~(3) operation, until 8hours temperature setting finished,sleep curve setting finished, at this time, the remote
controller will resume theoriginal timer display; temperature display will resume to original setting temperature.
Sleep3 - the sleep curve setting under Sleep mode by DIY could be inquired:The user could accord to sleep curve setting method to inquire
the presetting sleepcurve, enter into user individuation sleep setting status, but do not change the temperature, press "Turbo" button directly
for confirmation.
Note: In the above presetting or enquiry procedure, if continuously within10s, thereis no button pressed, the sleep curve setting status will
be automatically quitand resume to display the original displaying. In the presetting or enquiry pr-ocedure, press "ON/OFF" button, "Mode"
button, "Timer" button or "Sleep" button, the sleep curve setting or enquiry status will quit similarly.
If “H1” is displayed on the remote controller while it’s not operated by the professional person/after-sales person, it belongs to the misoperation.
Please operate it as below to cancel it.Under the OFF status of remote controller, hold the Mode button for 5s to cancel “H1” display.
Note:
● If remote controller displays “H1”, it belongs to the normal function reminder. If the unit is defrosting under heating mode, it operates according
to H1 defrosting mode. “H1” won’t be displayed on the panel of indoor unit;
● Once you set H1 mode, if you turn off unit by remote controller, H1 will display 3 times on the remote controller and then disappear;
● Also, when you set H1 mode, when you change to heating mode, H1 will display 3 times on the remote controller and then disappear.
30 Technical Information
Service Manual
3
1. After powered on, press ON/OFF button, the unit will start 5
2
to run. (Note: When it is powered on, the guide louver of
main unit will close automatically.) 1
2. Press MODE button, select desired running mode. WiFi
battery
1. Press the back side of remote controller marked
reinstall
the cover of battery box along the arrow direction.
2. Replace two 7# (AAA 1.5V) dry batteries, and remove
make sure the position of "+" polar and "-" polar
are correct.
3. Reinstall the cover of battery box.
● During operation, point the remote control signal sender at the receiving
window on indoor unit.
● The distance between signal sender and receiving window should be no
more than 8m, and there should be no obstacles between them.
● Signal may be interfered easily in the room where there is fluorescent lamp
or wireless telephone; remote controller should be close to indoor unit during
operation.
● Replace new batteries of the same model when replacement is required.
● When you don’t use remote controller for a long time, please take out the
batteries.
● If the display on remote controller is fuzzy or there’s no display, please
replace batteries.
Technical Information 31
Service Manual
1 ON/OFF button
2 FAN button
3 MODE button
4 +/- button
5 TURBO button
2
2 6 button
5 6
4 7 button
4 11
7
3
3 9
8 8 CLOCK button
10 12
1 13 WiFi
1 9 TIMER ON/
14 16
15 TIMER OFF button
10 TEMP button
11 / button
(before opening cover (after opening cover
12 I FEEL button
1 ON/OFF button 13 LIGHT button
2 FAN button 14 WiFi button
3 MODE button 15 QUIET button
4 +/- button 16 SLEEP button
● This is a general use remote controller, it could be used for the air conditioners with multifunction; For some function, which the
model doesn't have, if press the corresponding button on the remote controller that the unit will keep the original running status.
indicator (red indicator the colour is
different for different models).
Press this button to turn on the unit. Press this button again to turn off the unit.
32 Technical Information
Service Manual
ATUO
Low fan Medium-low fan Medium fan Medium-high fan High fan
Note:
● It’s Low fan speed under Dry mode.
● X-FAN functionHold fan speed button for 2s in COOL or DRY mode, the icon “ ” is displayed and the indoor fan will continue
operation for a few minutes in order to dry the indoor unit even though you have turned off the unit. After energization, X-FAN OFF is
defaulted. X-FAN is not available in AUTO, FAN or HEAT mode.
This function indicates that moisture on evaporator of indoor unit will be blowed after the unit is stopped to avoid mould.
● Having set X-FAN function on: After turning off the unit by pressing ON/OFF button indoor fan will continue running for a few minutes. at
low speed. In this period, Hold fan speed button for 2s to stop indoor fan directly.
● Having set X-FAN function off: After turning off the unit by pressing ON/OFF button, the complete unit will be off directly.
Press " + " or " - " button once increase or decrease set temperature 1°C(°F). Holding " + " or " - " button, set temperature on remote
controller will change quickly. On releasing button after setting is finished, temperature indicator on indoor unit will change accordingly.
When setting TIMER ON, TIMER OFF or CLOCK, press " + " or " - " button to adjust time. (Refer to CLOCK, TIMER ON, TIMER OFF
buttons)
OFF
Press this button can select up & down swing angle. Fan blow angle can be selected circularly as below:
OFF
When selecting " ", air conditioner is blowing fan automatically. Horizontal louver will automatically swing up & down at maximum angle.
When selecting " ", air conditioner is blowing fan at fixed position.
Horizontal louver will stop at the fixed position.
● When selecting " ", air conditioner is blowing fan at fixed angle. Horizontal louver will send air at the fixed angle.
●Hold " " button above 2s to set your required swing angle. When reaching your required angle, release the button.
Notice :
" " may not be available. When air conditioner receives this signal, the air conditioner will blow fan automatically .
Technical Information 33
Service Manual
Attention: When displaying the outdoor ambient, the displaying range is 0-60 When it goes beyond the range, it keeps the threshold data
(the smallest—0 and the largest 60 ).
Warm tips: When operating buttons on the cover please make sure the cover is closed completely.
Note:
Outdoor temperature display is not available for some models. At that time, indoor unit receives " " signal, while it displays indoor
set temperature.
Press this button once, to turn on the I FEEL function, then the figure of "I FEEL"will be displayed, after every press of other function button,
every 200ms to sendI FEEL once, after this function started, the remote controller will send temperatureto the main un it in every 10 minutes.
When repress this button, this function will beturned off. When I FEEL function is turned on, the remote controller should be put within the
area where indoor unit can receive the signal sent by the remote controller.
WiFi button
Press " WiFi " button to turn on or turn off WiFi function. When WiFi function is turned on, the " WiFi " icon will be displayed on remote
controller; Under status of remote controller off, press "MODE" and " WiFi " buttons simultaneously for 1s, WiFi module will restore to
factory default setting.
● This function is only available for some models.
Press this button, the Quiet status is under the Auto Quiet mode (display" "and "Auto" signal) and Quiet mode (display " " signal)
and Quiet OFF (there is no signal of " " displayed), after powered on, the Quiet OFF is defaulted.Under the Quiet mode (Display " "
signal).
The Quiet function is only available for some models.
Press this button, can select Sleep 1 ( ), Sleep 2 ( ), Sleep 3 ( ) andcancel the Sleep, circulate between these, after electrified,
Sleep Cancel is de-faulted.
Sleep 1 is Sleep mode 1, in Cool modes: sleep status after run for one hour, the main unit setting temperature will increase 1, 2 hours,
setting temperatureincreased 2, the unit will run at this setting temperature; In Heat mode:sleep status after run for one hour , the setting
temperature will decrease 1, 2 hours, setting temperature will decrease 2 , then the unit will run at this settingtemperature .
Sleep 2 is sleep mode 2, that is air conditioner will run according to the presettinga group of sleep temperature curve.
In Cool mode:
(1) When setting the initial temperature 16-23, after turned on Sleep function,the temperature will be increased 1 in every hour ,
after 3 the temperaturewill be maintained, after 7hours, the temperature will be decreased 1, afterthat the unit will keep on running
under this temperature;
(2) When setting the initial temperature 24-27, after turned on Sleep function,the temperature will be increased 1 in every hour ,
after 2 the temperaturewill be maintained, after 7hours, the temperature will be decreased 1, afterthat the unit will keep on running
under this temperature;
(3) When setting the initial temperature 28-29, after turned on Sleep function,the temperature will be increased 1 in every hour ,
after 1 the temperature will be maintained, after 7hours, the temperature will be decreased 1, afterthat the unit will keep on running
under this temperature;
34 Technical Information
Service Manual
(4) When setting the initial temperature 30, under this temperature setting, after 7hours, the temperature will be decreased 1, after
that the unit will keep onrunning under this temperature;
In Heat mode:
(1) Under the initial presetting temperature 16, it will run under this setting temperature all along .
(2) Under the initial presetting temperature17-20, after Sleep function started up, the temperature will decrease 1 in every hour ,
after 1 decreased, thistemperature will be maintained.
(3) Under the initial presetting temperature 21-27, after Sleep function started up, the temperature will decrease 1 in every hou r,
after 2 decreased, thistemperature will be maintained.
(4) Under the initial presetting temperature 28-30, after Sleep function started up, the temperature will decrease 1 in every hou r,
after 3 decreased, thistemperature will be maintained.
Sleep 3 - the sleep curve setting under Sleep mode by DIY:
(1) Under Sleep 3 mode, press "Turbo" button for a long time, remote controller enters into user individuation sleep setting status, at this
time, the time of remotecontroller will display "1hour", the setting temperature "88" will display the corr-esponding temperature of last setting
sleep curve and blink (The first enteringwill display according to the initial curve setting value of original factory);
2) Adjust "+" and "-" button, could change the corresponding setting temperature,after adjusted, press "Trubo" button for confirmation;
(3) At this time, 1hour will be automatically increased at the timer postion on the remote controller, (that are "2hours" or "3hours" or "8hours"),
the place of setting temperature "88" will display the corresponding temperature of last settingsleep curve and blink;
(4) Repeat the above step (2)~(3) operation, until 8hours temperature setting finished,sleep curve setting finished, at this time, the remote
controller will resume theoriginal timer display; temperature display will resume to original setting temperature.
Sleep3 - the sleep curve setting under Sleep mode by DIY could be inquired:The user could accord to sleep curve setting method to inquire
the presetting sleepcurve, enter into user individuation sleep setting status, but do not change the temperature, press "Turbo" button directly
for confirmation.
Note: In the above presetting or enquiry procedure, if continuously within10s, thereis no button pressed, the sleep curve setting status will
be automatically quitand resume to display the original displaying. In the presetting or enquiry pr-ocedure, press "ON/OFF" button, "Mode"
button, "Timer" button or "Sleep" button, the sleep curve setting or enquiry status will quit similarly.
Technical Information 35
Service Manual
If “H1” is displayed on the remote controller while it’s not operated by the professional person/after-sales person, it belongs to the
misoperation.
Please operate it as below to cancel it.Under the OFF status of remote controller, hold the Mode button for 5s to cancel “H1” display.
Note:
● If remote controller displays “H1”, it belongs to the normal function reminder. If the unit is defrosting under heating mode, it operates
according to H1 defrosting mode. “H1” won’t be displayed on the panel of indoor unit;
● Once you set H1 mode, if you turn off unit by remote controller, H1 will display 3 times on the remote controller and then disappear;
● Also, when you set H1 mode, when you change to heating mode, H1 will display 3 times on the remote controller and then disappear.
3
1. After powered on, press ON/OFF button, the unit will start 5
2
to run. (Note: When it is powered on, the guide louver of
main unit will close automatically.) 1
2. Press MODE button, select desired running mode. WiFi
battery
1. Press the back side of remote controller marked
reinstall
the cover of battery box along the arrow direction.
2. Replace two 7# (AAA 1.5V) dry batteries, and remove
make sure the position of "+" polar and "-" polar
are correct.
3. Reinstall the cover of battery box.
● During operation, point the remote control signal sender at the receiving
window on indoor unit.
● The distance between signal sender and receiving window should be no
more than 8m, and there should be no obstacles between them.
● Signal may be interfered easily in the room where there is fluorescent lamp
or wireless telephone; remote controller should be close to indoor unit during
operation.
● Replace new batteries of the same model when replacement is required.
● When you don’t use remote controller for a long time, please take out the
batteries.
● If the display on remote controller is fuzzy or there’s no display, please
replace batteries.
36 Technical Information
Service Manual
Internet
Gree Cloud
Gree
intelligent Home Wi-Fi Cellular/
home Other Wi-FI
appliances
Home wireless router
Home Wi-Fi
GREE+ APP
Operating Systems
Scan the QR code or search "GREE+" in the application market to download and install it. When "GREE+" App is installed, register the
account and add the device to achieve long-distance control and LAN control of Gree smart home appliances.
For more information, please refer to "Help" in App.
Technical Information 37
Service Manual
Internet
Cloud
Operating Systems
Scan the QR code or search "Ewpe Smart" in the application market to download and install it. When "Ewpe Smart" App is installed,
register the account and add the device to achieve long-distance control and LAN control of smart home appliances.
For more information, please refer to "Help" in App.
38 Technical Information
Service Manual
Tpreset –2 ˚C
Stop cooling
≥ 6 min. ≥ 3 min. ≥ 6 min.
Outdoor fan
Compressor 3 min
30S
Outdoor fan
Indoor fan Preset speed
Run Stop
(2) Dehumidifying Mode
① Working conditions and process of dehumidifying
If Tamb.>Tpreset, the unit will enter cooling and dehumidifying mode, in which case the compressor and the outdoor fan will operate and the indoor
fan will run at low speed.
If Tpreset-2°C(3.6°F)≤Tamb.≤Tpreset, the compressor remains at its original operation state.
If Tamb.< Tpreset-2°C(3.6°F), the compressor will stop, the outdoor fan will stop with a time lag of 30s, and the indoor fan will operate at low speed.
② Protection function
Protection is the same as that under the cooling mode.
(3) Heating Mode
① The condition and process of heating
If Tamb.≤Tpreset+2°C(3.6°F), heating mode will act, the compressor, outdoor fan and reversal valve will run, the indoor fan will delay 3min to stop at
the latest
If Tpreset +2°C(3.6°F)<Tamb.<Tpreset +5°C(9°F),the unit will keep running in the original mode.
If Tamb.≥Tpreset+5°C(9°F), the compressor will stop, the outdoor fan will delay 30s to stop and indoor fan will blow 60s at low speed, the fan speed
cannot be shifted within blow residual heat.
◆ In this mode, the temperature setting range is 16 ~30°C(68~86°F).
◆ The air conditioner will adjust the running frequency of the compressor automatically according to the change of ambient temperature.
◆ When the unit is turned off in heating mode, or switched to other mode from heating mode, the four-way valve will be powered off after the
compressor stops.
Stop heating
Tpreset+5
Original operating status
Tpreset+2
Tamb.
6min. 3min. 6min. Start heating
Outdoor fan
60s 60s
Indoor fan <2 min. preset <2 min. preset
wind wind
Reversing valve
Run Stop
c.For heating and cooling unit, when 22°C(71.6°F)<Tindoor ambient<26°C(78.8°F) (for cooling only unit, 22°C(71.6°F)<Tindoor
ambient<26°C)(78.8°F), it will keep the original running mode. If the unit is energized for the first time, it will run in fan mode.
② Protection
a. In cooling operation, protection is the same as that under the cooling mode;
b. In heating operation, protection is the same as that under the heating mode;
c. When ambient temperature changes, operation mode will be converted preferentially. Once started, the compressor willremain
unchanged for at least 6 minutes.
(7)Common Protection Functions and Fault Display under COOL, HEAT, DRY and AUTO Modes
① Overload protection
Ttube: measured temperature of outdoor heat exchanger under cooling mode; and measured temperature of indoor heat exchanger under
heating mode.
1) Cooling overload
a.If T tube≤52°C(125.6°F), the unit will return to its original operation state.
b.If T tube≥55°C(131°F), frequency rise is not allowed.
c.If T tube≥58°C(136.4°F), the compressor will run at reduced frequency.
d.If T tube≥62°C(143.6°F), the compressor will stop and the indoor fan will run at preset speed.
2) Heating overload
a.If T tube≤50°C(122°F), the unit will return to its original operation state.
b.If T tube≥53°C(127.4°F), frequency rise is not allowed.
c.If T tube≥56°C(132.8°F), the compressor will run at reduced frequency.
d.If T tube≥60°C(140°F), the compressor will stop and the indoor fan will blow residue heat and then stop.
② Exhaust temperature protection of compressor
If exhaust temperature≥98°C(208.4°F), frequency is not allowed to rise.
If exhaust temperature≥103°C(217.4°F), the compressor will run at reduced frequency.
If exhaust temperature≥110°C(230°F),, the compressor will stop.
If exhaust temperature≤90°C(194°F), and the compressor has stayed at stop for at least 3 minutes, the compressor will resume its operation.
③ Communication fault
If the unit fails to receive correct signals for durative 3 minutes, communication fault can be justified and the whole system will stop.
④ Module protection
Under module protection mode, the compressor will stop. When the compressor remains at stop for at least 3 minutes, the compressor will
resume its operation. If module protection occurs six times in succession, the compressor will not be started again.
⑤ Overload protection
If temperature sensed by the overload sensor is over 115 , the compressor will stop and the outdoor fan will stop with a time lag of 30
seconds. If temperature is below 95 , the overload protection will be relieved.
⑥ DC bus voltage protection
If voltage on the DC bus is below 150V or over 420V, the compressor will stop and the outdoor fan will stop with a time lag of 30 seconds.
When voltage on the DC bus returns to its normal value and the compressor has stayed at stop for at least 3 minutes, the compressor will
resume its operation.
⑦ Faults of temperature sensors
Designation of sensors Faults
Indoor ambient temperature The sensor is detected to be open-circuited or short-circuited for successive 5 seconds
Indoor tube temperature The sensor is detected to be open-circuited or short-circuited for successive 5 seconds
Outdoor ambient temperature The sensor is detected to be open-circuited or short-circuited for successive 30 seconds
The sensor is detected to be open-circuited or short-circuited for successive 30 seconds, and no
Outdoor tube temperature
detection is performed within 10 minutes after defrost begins.
After the compressor has operated for 3 minutes, the sensor is detected to be open-circuited or
Exhaust
short-circuited for successive 30 seconds.
After the compressor has operated for 3 minutes, the sensor is detected to be open-circuited or
Overload
short-circuited for successive 30 seconds.
3. Other Controls
(1) ON/OFF
Press the remote button ON/OFF: the on-off state will be changed once each time you press the button.
(2) Mode Selection:
Press the remote button MODE, then select and show in the following ways: AUTO, COOL, DRY, FAN, HEAT, AUTO.
(3) Temperature Setting Option Button
Each time you press the remote button TEMP+ or TEMP-, the setting temperature will be up or down by 1°C(1.8°F). Regulating Range:
16(60.8°F)~30°C(86°F), the button is useless under the AUTO mode.
(4) Time Switch
You should start and stop the machine according to the setting time by remote control.
(5) SLEEP State Control
1. In cooling mode:
1.1 When the initial set temperature is16-23°C(60.8~73.4°F),the temperature will rise 1°C(1.8°F) by every hour after sleep function is set;the
temperature will not change after rising 3°C(5.4°F) ;after running for 7hours,the temperature will decrease1°C(1.8°F) and it will not change
after that.
1.2 When the initial set temperature is 24-27°C(75.2~80.6°F),the temperature will rise 1°C(1.8°F) by every hour after sleep function is set; the
temperature will not change after rising 2°C(3.6°F) ;after running for 7 hours, the temperature will decrease 1°C(1.8°F) and it will not change
after that.
1.3 When the initial set temperature is 28-29°C(82.4~84.2°F),the temperature will rise 1°C(1.8°F) by every hour after sleep function is set; the
temperature will not change after rising 1°C(1.8°F) ; after running for 7 hours, the temperature will decrease 1°C(1.8°F) and it will not change
after that.
1.4 When the initial set temperature is 30°C(86°F) , the unit will keep on running at this temperature; after running for 7 hours, the temperature
will decrease 1°C(1.8°F) and it will not change after that.
Relationship between set temperature and running time:
2. In heating mode:
2.1 When the initial set temperature is 16°C(60.8°F), the unit will keep on running at this temperature;
2.2 When the initial set temperature is 17-20°C(62.6~68°F), the temperature will decrease 1°C(1.8°F) by every hour after sleep function is set;
the temperature will not change after decreasing 1°C(1.8°F);
2.3 When the initial set temperature is 21-27°C(69.8~80.6°F), the temperature will decrease 1°C(1.8°F) by every hour after sleep function is
set; the temperature will not change after decreasing 2°C(3.6°F);
2.4 When the initial set temperature is 28-30°C(82.4~86°F), the temperature will decrease 1°C(1.8°F) by every hour after sleep function is set;
the temperature will not change after decreasing 3°C(5.4°F);
Relationship between set temperature and running time:
Initial Temp. Running time(T)
0(start) 1 2 3 4 5 6 7 8
16 16 16 16 16 16 16 16 16
17 16 16 16 16 16 16 16 16
18 17 17 17 17 17 17 17 17
19 18 18 18 18 18 18 18 18
20 19 19 19 19 19 19 19 19
21 20 19 19 19 19 19 19 19
22 21 20 20 20 20 20 20 20
23 22 21 21 21 21 21 21 21
24 23 22 22 22 22 22 22 22
25 24 23 23 23 23 23 23 23
26 25 24 24 24 24 24 24 24
27 26 25 25 25 25 25 25 25
28 27 26 25 25 25 25 25 25
29 28 27 26 26 26 26 26 26
30 29 28 27 27 27 27 27 27
(6) Indoor Fan Control
Indoor fan could be set at ultra-high, high, medium, low speed by wireless remote controller and operated as that speed.
Auto fan speed could be set as well, indoor fan will operate under auto fan speed as following:
1. Under heating mode: auto speed under heating or auto heating mode:
a. When Tamb.≤Tpreset+1°C(1.8°F), indoor fan will operate at high speed;
b. When Tpreset+1°C(1.8°F)<Tamb.<Tpreset+3°C(5.4°F), indoor fan will operate at medium speed;
c. When Tamb.≥Tpreset+3°C(5.4°F), indoor fan will operate at low speed;
There should be at least 180s operation time during switchover of each speed.
2. Under cooling mode: auto speed under cooling or auto cooling mode:
a. When Tamb.≥Tpreset+2°C(3.6°F), indoor fan will operate at high speed;
b. When Tpreset<Tamb.<Tpreset+2°C(3.6°F), indoor fan will operate at medium speed;
c. When Tamb.≤Tpreset, indoor fan will operate at low speed
There should be at least 210s operation time during switchover of each speed.
(7) Buzzer Control
The buzzer will send a “Di” sound when the air conditioner is powered up or received the information sent by the remote control or there is
a button input, the single tube cooler doesnt receive the remote control ON signal under the mode of heating mode.
(8) Auto button
If the controller is on, it will stop by pressing the button, and if the controller is off, it will be automatic running state by pressing the button,
swing on and light on, and the main unit will run based on the remote control if there is remote control order.
(9) Up-and-Down Swinging Control
Heating angle O(0°) Cooling angle Heating angle O(0°) Coolin
When power on, the up-and-down motor will firstly move the air
O(0°)
deflector to o counter-clockwise, close the air outlet.
After starting the machine, if you dont set the swinging functi on, L1
heating mode and auto-heating mode, the up-and-down air deflector L A1 L
will move to D clockwise; under other modes, the up-and-down A air B1 A
deflector will move to L1. If you set the swinging function whenB you start C1 B
the machine, then the wind blade will swing between L and D.CThe air D1 C
deflector has 7 swinging states: Location L, Location A, Location D B, Location C, D
Location D, Location L to Location D, stop at any location between L-D (the included angle between L~D is the same).
The air deflector will be closed at 0 Location, and the swinging is effectual only on condition that setting the swinging order and the inner
fan is running. The indoor fan and compressor may get the power when air deflector is on the default location.
(10) Display
① Operation pattern and mode pattern display
All the display patterns will display for a time when the power on, the operation indication pattern will display in red under standby status.
When the machine is start by remote control, the indication pattern will light and display the current operation mode (the mode light in-
cludes: Cooling, heating and dehumidify). If you close the light key, all the display patterns will close.
② Double-8 display
According to the different setting of remote control, the nixie light may display the current temperature (the temperature scope is from 16°C
(60.8°F)to 30°C(86°F)) and indoor ambient temperature. The set temperature displayed in auto cooling and fan mode is 25°C(77°F) and
the set temperature displayed in auto heating mode is 20°C(68°F). Under heating mode, nixie tube displays H1 or heating indicator is off 0.5s
and blinks 10s in defrosting.(If you set the fahrenheit temperature display, the nixie light will display according to fahrenheit temperature)(11)
Protection function and failure display
E2: Freeze-proofing protection E4: Exhausting protecti on E5: Overcurrent protection E6: Communication failure
F1: Indoor ambient sensor start and short circuit (continuously measured failure in 5s)
F2: Indoor evaporator sensor start and short circuit (continuously measured failure in 5s)
F3: Outdoor ambient sensor start and short circuit (continuously measured failure in 30s)
F4: Outdoor condenser sensor start and short circuit (continuously measured failure in 30s, and dont measure within 10 minutes after
defrosted)
F5: Outdoor exhausting sensor start and short circuit (continuously measured failure in 30s after the compressor operated 3 minutes)
H3: Overload protection of compressor H5: Module protection PH: High-voltage protection PL: Low-voltage protection
P1: Nominal cooling and heating test P2: Maximum cooling and heating test
P3: Medium cooling and heating test P0: Minimum cooling and heating test
(12) Drying Function
You may start or stop the drying function under the modes of cooling and dehumidify at the starting status (The modes of automatism,
heating and air supply do not have drying function). When you start the drying function, after stop the machine by pressing the switch
button, you should keep running the inner fans for 2 minutes under low air damper (The swing will operate as the D1 status within 2
minutes, and other load is stopped), then stop the entire machine; When you stop the drying function, press the switch button will stop the
machine directly.When you start the drying function, operating the drying button will stop the inner fans and close the guide louver.
(13) Memory Function
When interrupting the power supply memory content: mode, swing function, light, set temperature and wind speed.
After interrupted the power supply, the machine will start when recovering the power according to the memory content automatically.
Warnings
1. When installing or relocating the unit, be sure to keep the refrigerant circuit free from air or substances other than the
specified refrigerant.
Any presence of air or other foreign substance in the refrigerant circuit will cause system pressure rise or compressor rupture, resulting in
injury.
2.When installing or moving this unit, do not charge the refrigerant which is not comply with that on the nameplate or
unqualified refrigerant.
Otherwise, it may cause abnormal operation, wrong action, mechanical malfunction or even series safety accident.
3.When refrigerant needs to be recovered during relocating or repairing the unit, be sure that the unit is running in cooling
mode.Then, fully close the valve at high pressure side (liquid valve).About 30-40 seconds later, fully close the valve at low
pressure side (gas valve), immediately stop the unit and disconnect power. Please note that the time for refrigerant recovery
should not exceed 1 minute.
If refrigerant recovery takes too much time, air may be sucked in and cause pressure rise or compressor rupture, resulting in injury.
4.During refrigerant recovery, make sure that liquid valve and gas valve are fully closed and power is disconnected before
detaching the connection pipe.
If compressor starts running when stop valve is open and connection pipe is not yet connected, air will be sucked in and cause pressure
rise or compressor rupture, resulting in injury.
5.When installing the unit, make sure that connection pipe is securely connected before the compressor starts running.
If compressor starts running when stop valve is open and connection pipe is not yet connected, air will be sucked in and cause pressure
rise or compressor rupture, resulting in injury.
6.Prohibit installing the unit at the place where there may be leaked corrosive gas or flammable gas.
If there leaked gas around the unit, it may cause explosion and other accidents.
7.Do not use extension cords for electrical connections. If the electric wire is not long enough, please contact a local service
center authorized and ask for a proper electric wire.
Poor connections may lead to electric shock or fire.
8.Use the specified types of wires for electrical connections between the indoor and outdoor units. Firmly clamp the wires so
that their terminals receive no external stresses.
Electric wires with insufficient capacity, wrong wire connections and insecure wire terminals may cause electric shock or fire.
WARNING:
●Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacture.
Should repair be necessary,contact your nearest authorized Service Centre. Any repairs carried out by unqualified personnel
may be dangerous. The appliance shall be stored in a room without continuously operating ignition sources. (for example:
open flames, an operating gas appliance or an operating electric heater.)
●Do not pierce or burn.
●Appliance shall be installed, operated and stored in a room with a floor area larger than Xm2 .(Please refer to table "a" in
section of " Safety Operation of Inflammable Refrigerant" for Space X.)
●Appliance filled with flammable gas R32. For repairs, strictly follow manufacturer’s instructions only. Be aware that
refrigrants not contain odour. Read specialist’s manual.
Installation notes
●The air conditioner is not allowed to use in a room that has running fire (such as fire source,working coal gas ware,
operating heater).
●It is not allowed to drill hole or burn the connection pipe.
●The air conditioner must be installed in a room that is larger than the minimum room area.
The minimum room area is shown on the nameplate or following table a.
●Leak test is a must after installation.
table a - Minimum room area(m2)
Charge amount (kg) ≤1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2 2.1 2.2 2.3 2.4 2.5
floor location 4 14.5 16.8 19.3 22 24.8 27.8 31 34.3 37.8 41.5 45.4 49.4 53.6
Minimum
room window mounted 4 5.2 6.1 7 7.9 8.9 10 11.2 12.4 13.6 15 16.3 17.8 19.3
area( m 2 )
wall mounted 4 4 4 4 4 4 4 4 4 4.2 4.6 5 5.5 6
ceiling mounted 4 4 4 4 4 4 4 4 4 4 4 4 4 4
Maintenance notes
●Check whether the maintenance area or the room area meet the requirement of the nameplate.
— Its only allowed to be operated in the rooms that meet the requirement of the nameplate.
●Check whether the maintenance area is well-ventilated.
— The continuous ventilation status should be kept during the operation process.
●Check whether there is fire source or potential fire source in the maintenance area.
— The naked flame is prohibited in the maintenance area; and the “no smoking” warning board should be hanged.
●Check whether the appliance mark is in good condition.
— Replace the vague or damaged warning mark.
Welding
●If you should cut or weld the refrigerant system pipes in the process of maintaining, please follow the steps as below:
a. Shut down the unit and cut power supply
b. Eliminate the refrigerant
c. Vacuuming
d. Clean it with N2 gas
e. Cutting or welding
f. Carry back to the service spot for welding
●Make sure that there isnt any naked flame near the outlet of the vacuum pump and its well-ventilated.
●The refrigerant should be recycled into the specialized storage tank.
10. Pipe pliers, pipe cutter 11. Pipe expander, pipe bender 12. Soldering appliance, refrigerant container,
elsctronic scale
8. Installation
8.1 Installation Dimension Diagram
At least 15cm
At least 15cm
cm
3 00
lea
st n At least 250cm
At tio
uc
str
ob
o the
et
ac
Sp
Space to the obstruction
the
e to n
At least 50cm
ac tio
Sp truc
s st
ob
t lea
A cm
30
Space to th
e wall
on At least 50cm
u cti 0cm
str 20
ob st Space to the ob
he lea struction
ot At
et
ac
Sp
Installation procedures
Start installation
Finish installation
Note: this flow is only for reference; please find the more detailed installation steps in this section.
(2) Drill the screw fixing holes on the wall with impact drill (the 5. Connect the Pipe of Indoor Unit
specification of drill head should be the same as the plastic (1) Aim the pipe joint at the corresponding bellmouth.(As show
expansion particle) and then fill the plastic expansion particles in Fig.5)
in the holes. (2) Pretightening the union nut with hand.
(3) Fix the wall-mounting frame on the wall with tapping screws (3) Adjust the torque force by referring to the following sheet.
and then check if the frame is firmly installed by pulling the Place the open-end wrench on the pipe joint and place the
frame. If the plastic expansion particle is loose, please drill torque wrench on the union nut. Tighten the union nut with
another fixing hole nearby. torque wrench.(As show in Fig.6)
3. Install Wall-mounting Frame (4) Wrap the indoor pipe and joint of connection pipe with
(1) Choose the position of piping hole according to the direction insulating pipe, and then wrap it with tape.(As show in Fig.7)
of outlet pipe. The position of piping hole should be a little Open-end
lower than the wall-mounted frame.(As show in Fig.1) wrench
Wall Wall
QD: Mark in the middle of it Level meter
Space Space
to the to the
wall wall
above above
150mm 150mm
Left Right
Insulating pipe Fig.7
Φ55mm Φ55mm
Rear piping hole Rear piping hole
QE:
Wall
Mark in the middle of it Level meter
Wall
Refer to the following table for wrench moment of force:
Space Space
to the to the
wall wall
above
150mm
above
150mm
Hex nut diameter(mm) Tightening torque(N.m)
Left Right Φ6 15~20
Φ70mm Φ70mm
Rear piping hole Rear piping hole Fig.1 Φ9.52 30~40
Φ12 45~55
(2) Open a piping hole with the diameter of Φ55mm on the
Φ16 60~65
selected outlet pipe position.In order to drain smoothly, slant
Φ19 70~75
the piping hole on the wall slightly downward to the outdoor
side with the gradient of 5-10°.(As show in Fig.2)
6. Install Drain Hose
Indoor Outdoor
(1) Connect the drain hose to the outlet pipe of indoor unit.(As
show in Fig.8)
(2) Bind the joint with tape.(As show in Fig.9)
Φ55/70mm
5-10°
Fig.2 Fig.8
Note:
Drain hose
(1) Pay attention to dust prevention and take relevant safety Outlet pipe
measures when opening the hole.
(2) Make the power connection wire go through the cable-cross Indoor and
hole at the back of indoor unit and then pull it out from the front Indoor unit
outdoor power cord
Gas
side.(As show in Fig.12) pipe
Power connection
wire
Connection pipe Drain hose
Band
Fig.12
(3) Remove the wire clip; connect the power connection wire
and signal control wire to the wiring terminal according to the
Fig.15
color; tighten the screw and then fix them with wire clip.(As
Indoor power cord
show in Fig.13)
Note:
N(1) 2 3
(1) The power cord and control wire cant be crossed or
blue black brown yellow- winding.
green
(2) The drain hose should be bound at the bottom.
Note:
Indoor Outdoor
(1) All wires of indoor unit and outdoor unit should be
Wall pipe Fig.17
connected by a professional. Sealing gum Upper hook
(2) If the length of power connection wire is insufficient, please
contact the supplier for a new one. Avoid extending the wire by
yourself.
(3) For the air conditioner with plug, the plug should be
reachable after finishing installation.
(4) For the air conditioner without plug, an air switch must be Fig.16 Lower hook of
wall-mounting frame
installed in the line. The air switch should be all-pole parting
and the contact parting distance should be more than 3mm. Note:
Do not bend the drain hose too excessively in order to prevent
blocking.
8.6 Installation of Outdoor Unit (3) Pretightening the union nut with hand.
(4) Tighten the union nut with torque wrench .
1. Fix the Support of Outdoor Unit(Select it according to
Refer to the following table for wrench moment of force:
the actual installation situation)
(1) Select installation location according to the house structure.
Hex nut diameter(mm) Tightening torque(N.m)
(2) Fix the support of outdoor unit on the selected location with
Φ6 15~20
expansion screws.
Φ9.52 30~40
Note: Φ12 45~55
(1) Take sufficient protective measures when installing the Φ16 60~65
outdoor unit. Φ19 70~75
(2) Make sure the support can withstand at least four times the
unit weight. 5. Connect Outdoor Electric Wire
(3) The outdoor unit should be installed at least 3cm above the (1) Remove the wire clip; connect the power connection wire
floor in order to install drain joint.(As show in Fig.18) and signal control wire (only for cooling and heating unit) to the
(4) For the unit with cooling capacity of 2300W~5000W, 6 wiring terminal according to the color; fix them with screws.(As
expansion screws are needed; for the unit with cooling capacity show in Fig.23)
of 6000W~8000W, 8 expansion screws are needed; for the
unit with cooling capacity of 10000W~16000W, 10 expansion
screws are needed.
Handle
09 12K : 18/24K :
N(1) 2 3 N(1) 2 3 L N
N L
yellow- blue black brown brown blue yellow-
green (black) green
N L L N
Indoor unit connection POWER Indoor unit connection POWER
Drain vent Chassis
Outdoor drain joint Note: the wiring connect is for reference only,
Drain hose please refer to the actual one.
At least 3cm above the floor Valve cover Wall
Fig.23
Fig.18 Fig.19
(2) Fix the power connection wire and signal control wire with
U-shaped curve
2. Install Drain Joint(Only for cooling and heating unit) wire clip (only for cooling and heating unit).
Drain hose
(1) Connect the outdoor drain joint into the hole on the chassis.
Note:
(2) Connect the drain hose into the drain vent.
(As show in Fig.19) (1) After tightening the screw, pull the power cord slightly to
check if it is firm.
3. Fix Outdoor Unit (2) Never cut the power connection wire to prolong or shorten
(1) Place the outdoor unit on the support. the distance.
(2) Fix the foot holes of outdoor unit with bolts. (As show in
Fig.20) 6. Neaten the Pipes
(1) The pipes should be placed along the wall, bent reasonably
Foot holes and hidden possibly. Min. semidiameter of bending the pipe is
10cm.
Handle (2) If the outdoor unit is higher than the wall hole, you must set
a U-shaped curve in the pipe before pipe goes into the room,
in order to prevent rain from getting into the room.(As show in
Foot holes Fig.24)
At least 3cm above the floor Fig.21 Valve cover Wall
Fig.20
U-shaped curve
The drain hos
4. Connect Indoor and Outdoor Pipes can't raise
Handle Drain hose
upwards
(1) Remove the screw on the handle and valve cover of outdoor
unit and then remove the handle and valve cover.(As show in
Fig.21)
(2) Remove the screw cap of valve and aim the pipe jointValve
at thecover Wall
At least 3cm above the floor
bellmouth of pipe.(As show in Fig.22) Fig.25
Fig.24 U-shaped curve
Liquid pipe Pipe joint
Drain hose
Liquid gas pipe
valve
Union nut
gas valve
Fig.22
9. Maintenance
9.1 Error Code List
Display Method of Indoor Unit
1.Refrigerant leakage;
Refrigerant The Dual-8 Code Display will 2.Indoor evaporator temperature
3 leakage F0 show F0 and the complete unit sensor works abnormally;
protection stops. 3.The unit has been plugged up
somewhere.
High During cooling and drying
discharge operation, compressor and Please refer to the malfunction
4 temperature E4 outdoor fan stop while indoor analysis (discharge protection,
protection of fan operates. During heating overload).
compressor operation, all loads stop.
During cooling and drying
1. Supply voltage is unstable;
operation, compressor and
Overcurrent 2. Supply voltage is too low and
5 E5 outdoor fan stop while indoor
protection load is too high;
fan operates. During heating
3. Evaporator is dirty.
operation, all loads stop.
During cooling operation,
Communi- compressor stops while
Refer to the corresponding
6 cation E6 indoor fan motor operates.
malfunction analysis.
Malfunction During heating operation, the
complete unit stops.
Compressor
Min Showing during min. cooling or
23 P0
frequence in min. heating test
test state
Compressor
rated Showing during nominal cooling or
24 P1
frequenc e in nominal heating test
test state
Compressor
maximum Showing during max. cooling or
25 P2
frequence in max. heating test
test state
Compressor
intermediate Showing during middle cooling or
26 P3
frequence in middle heating test
test state
Static
32 dedusting H2
protection
Indoor unit
compressor and Outdoor fan Indoor unit and outdoor unit doesn't
and outdoor LP
motor can’t work match
40 unit doesn't
match
During cooling and drying
operation, compressor will stop
Failure start- while indoor fan will operate;
41 LC Refer to the malfunction analysis
up During heating operation, the
complete unit will stop
operation.
1.Main board of indoor unit is
damaged;
Malfunction Loads operate normally,
2.Detection board is damaged;
42 of detecting JF while the unit can’t be
3.The connection between
plate(WIFI) normally controlled by APP.
indoor unit and detection board
is not good;
No
No Is malfunction
eliminated
No
No Is malfunction Yes
eliminated
Replace it with a
temperature sensor with
the same model
Yes
No Is malfunction
eliminated
Yes
End
Start
Turn unit on
Yes to check whether the
No malfunction is
eliminated.
Turn unit on
No No to check whether the Yes
malfunction is
eliminated.
Connect power and restart the unit. It's the malfunction of main board.
Test whether the voltage between terminal 1 and terminal 2 No Replace a new main board that is
of motor interface is within 280~310VDC. of the same model.
Yes
Yes
Then check whether the voltage It's the malfunction of main board.
between terminal 2 and terminal 3 No Replace a new main board that is
of the same model.
of the motor interface is 15VDC.
Yes
Then check whether there is voltage It's the malfunction of main board.
between terminal 2 and terminal 4 No Replace a new main board that is
of the motor interface. of the same model.
Yes
Start
No Appearance of the
Is there jumper cap on the mainboard?
jumper cap
No Is malfunction
eliminated
No Is malfunction Yes
eliminated
Is malfunction Yes
eliminated
Yes
No
End
Start
No No
Is the supply voltage too low Yes Adjust the supply voltage to maintain it Is malfunction Yes
with overload? within normal range eliminated
No No
Is the indoor / outdoor Yes Clean the indoor and outdoor heat Is malfunction Yes
heat exchanger dirty,or are the air inlet exchangers and remove the blockage eliminated
and outlet blocked? of air inlet and outlet
No
No
The fan is abnormal? Fan Yes Check the motor and reinstall the Is malfunction Yes
speed is too low or fan doesnt rotate motor to have the fan run normally eliminated
No No
Yes No
Is there blockage inside the system? Yes Flush the heat exchangers with high
(Filth blockage, ice plug, greasy Is malfunction Yes
blockage, the cut off valve hasnt been pressure nitrogen eliminated
opened completely)
No No
No
End
5. Communication Malfunction E6
Start
Yes
No
Yes
No
Replace
Communication cord is damaged? Yes communication Malfunction eliminated? Yes
cord
No
No
Replace IDU's
main board
Yes
Replace ODU's
Malfunction eliminated? No
main board.
Yes
End
Start
Yes
End
Start
Yes
Is malfunction
eliminated
The end
Outdoor Unit
1. Capacity charging malfunction (outdoor unit malfunction) (AP1 below means control board of outdoor unit)
Main detection points:
● Detect if the voltage of L and N terminal of XT wiring board is between 210VAC-240VAC by alternating voltage meter;
● Is reactor (L) well connected? Is connection wire loosened or pulled out? Is reactor (L) damaged?
Malfunction of
Voltage higher Replace outdoor
Y the outdoor
than 200V? mainboard
mainboard AP1
Power supply is
abnormal; repair
Voltage within the power supply Power on and
N Is the Vmalfunction Y
180VAC~260VAC? to restore the range restart the unit
eliminated?
between 180VAC
~260VAC
Y
Connect the
If the wiring of connection Power on and
N Is the Vmalfunction Y
reactor L is normal? wire of reactor restart the unit
eliminated?
L correctly
Replace outdoor
mainboard AP1 N
End
2. IPM protection, phase current overcurrent (the control board as below indicates the control board
of outdoor unit) H5/P5
Mainly detect:
(1) Compressor COMP terminal (2) voltage of power supply (3) compressor
(4) Refrigerant-charging volume (5) air outlet and air inlet of outdoor/indoor unit
Troubleshooting:
1. Whether the heat exchangers of indoor unit and outdoor unit are Measure the resistance
dirty? Whether the radiation is affected because the unit is between three terminals (UVW)
covered by the objects? of compressor and the copper pipe
2. When indoor fan and outdoor unit are operate normally? with resistance measuring meter
3. Whether the system pressure is too high?
4. Whether the pressure is because there's too much refrigerant?
Whether the
resistance value is more than
500ohm?
Whether there's Correct it one by one
abnormal phenomenons according to the Service
described as above? Manual, and then turn on
the unit. Replace the
compressor
Replace control
board
End
3. High temperature and overload protection (E8)(AP1 below means control board of outdoor unit)
Main detection points:
● If the outdoor ambient temperature is in normal range;
● If the indoor and outdoor fan are running normally;
● If the radiating environment of indoor and outdoor unit is good.
E8 is displayed
N N
N
N
Y
Y
Replace Fan
Fan capacitor is broken? Y
capacitor
Replace outdoor
mainboard
N
Replace mainboard
End
4. Start-up failure (LC) (AP1 below means control board of outdoor unit)
Main detection points:
● If the compressor wiring is correct?
● If the stop time of compressor is sufficient?
● If the compressor is damaged?
● If the refrigerant charging amount is too much?
Replace outdoor
mainboard AP1
Is the malfunction
eliminated?
Replace the
compressor
End
H3 or E4 is displayed
No
Yes
Yes
Connect wire
If the wiring terminal FA of electronic according to wiring
No
expansion valve is well connected? diagram
No
Yes
No
No
No
Heat exchange of unit is not good (heat exchanger
is dirty and unit radiating environment is bad); Is the malfunction Y
Yes
improve the radiating environment and clean the eliminated?
heat exchanger
No
No
Replace outdoor
mainboard AP1
End
E6
No
No
Yes
Yes
Yes End
35 12
34 36
33
37
11 13
10
14
9
8 15
38 16
7
5
4 17
3
18
19
2 20
1 21
23 22
24
26 25
27
28
29
32
31
30
The component picture is only for reference; please refer to the actual product.
Part Code
Description
NO. GWH09QC-S6DBC8A/I GWH12QC-S6DBC8A/I Qty
Product Code CB456N07000 CB456N06900
1 Front Panel 20000300154T 20000300154T 1
2 Display Board 30565281 30565281 1
3 Front Case Assy 00000200045 00000200045 1
4 Guide Louver 1051293101 1051293101 1
5 Air Louver (left) 10512725 10512725 1
6 Swing Lever 10582459 10582459 1
7 Helicoid Tongue 26112436 26112436 1
8 Rear Case assy 00000100092 00000100092 1
9 Drainage Hose 05230014 05230014 1
10 Ring of Bearing 26152022 26152022 1
11 O-Gasket sub-assy of Bearing 76512051 76512051 1
12 Evaporator Support 24212179 24212179 1
13 Evaporator Assy 01100106039901 01100106016201 1
14 Wall Mounting Frame 01252484 01252484 1
15 Cross Flow Fan 10352056 10352056 1
16 Motor Press Plate 26112516 26112516 1
17 Fan Motor 150104060029 150104060029 1
18 Connecting pipe clamp 2611216401 2611216401 1
19 Rubber Plug (Water Tray) 76712012 76712012 1
20 Stepping Motor 1521210108 1521210108 1
21 Crank 73012005 73012005 1
22 Stepping Motor 1521210710 1521210710 1
23 Air Louver (Auto) 10512727 10512727 1
24 Electric Box Assy 100002067361 100002067346 1
25 Air Louver (right) 10512726 10512726 1
26 Axile Bush 10542036 10542036 1
27 Terminal Board 42011233 42011233 1
28 Jumper 4202021909 4202021920 1
29 Main Board 300002061087 300002061087 1
30 Shield Cover of Electric Box Cover 01592150 01592150 1
31 Electric Box Cover Sub-Assy 0140206501 0140206501 1
32 Electric Box Cover 2011220701 2011220701 1
33 Power Cord / / /
34 Connecting Cable 4002052317 4002052317 0
35 Connecting Cable / / /
36 Remote Controller 305001000139 305001000139 1
37 Cold Plasma Generator 1114001605 1114001605 1
38 Detecting Plate 30110144 30110144 1
QD
45
46
The component picture is only for reference; please refer to the actual product.
Part Code
Description
NO. GWH09QD-S6DBC2A/I GWH12QD-S6DBC2A/I Qty
Product Code CB439N14900 CB439N14800
1 Decorative Strip / / /
2 Front Panel 20000300070S 20000300070S 1
3 Display Board 30565278 30565278 1
4 Filter Sub-Assy 1112208906 1112208906 2
5 Decorative Board (Left) 20192662 20192662 1
6 Front Case 2002248401 2002248401 1
7 Guide Louver 1051276501 1051276501 1
8 Axile Bush 10542036 10542036 2
9 Air Louver 1 10512733 10512733 2
10 Helicoid Tongue 26112512 26112512 1
11 Left Axile Bush 10512037 10512037 1
12 Rear Case assy 00000100001 00000100001 1
13 Rubber Plug (Water Tray) 76712012 76712012 1
14 O-Gasket sub-assy of Bearing 76512203 76512051 1
15 Ring of Bearing 26152025 26152025 1
16 Evaporator Support 24212177 24212177 1
17 Evaporator Assy 01100100047201 01100100047201 1
18 Cross Flow Fan 10352060 10352060 1
19 Fan Motor 15012136 15012136 1
20 Motor Press Plate 26112511 26112511 1
21 Wall Mounting Frame 01362026 01362026 1
22 Connecting pipe clamp 2611218801 2611218801 1
23 Crank 73012005 73012005 1
24 Stepping Motor 1521240212 1521240212 1
25 Drainage Hose 05230014 05230014 1
26 Electric Box Assy 100002067337 100002067337 1
27 Lower Shield of Electric Box 01592139 01592139 1
28 Electric Box 2011221105 2011221105 1
29 Jumper 4202021923 4202021923 1
30 Main Board 300002061086 300002061086 1
31 Air Louver 10512736 10512736 1
32 Stepping Motor 1521210704 1521210704 1
33 Air Louver 2 10512735 10512735 1
34 Swing Lever 10512731 10512731 1
35 Decorative Strip 20192662 20192662 1
36 Screw Cover 2425201726 2425201726 3
37 Electric Box Cover2 20112210 20112210 1
38 Shield Cover of Electric Box Cover 01592176 01592176 1
39 Electric Box Cover 20112209 20112209 1
40 Terminal Board 42011233 42011233 1
41 Power Cord / / /
42 Connecting Cable 4002052317 4002052317 0
43 Connecting Cable / / /
44 Remote Controller 305001000139 305001000139 1
45 Detecting Plate 30110144 30110144 1
46 Cold Plasma Generator 1114001602 1114001602 1
Part Code
Description
NO. GWH09QD-S6DBD2A/I GWH09QD-S6DBE4A/I Qty
Product Code CB461N06100 CB470N05000
1 Decorative Strip / / /
2 Front Panel 200003000008 200003000064T 1
3 Display Board 30565278 300001000081 1
4 Filter Sub-Assy 1112208906 1112208906 2
5 Decorative Board (Left) 20192662 20192662 1
6 Front Case 2002248401 2002248401 1
7 Guide Louver 1051276501 1051276501 1
8 Axile Bush 10542036 10542036 2
9 Air Louver 1 10512733 10512733 2
10 Helicoid Tongue 26112512 26112512 1
11 Left Axile Bush 10512037 10512037 1
12 Rear Case assy 00000100001 00000100001 1
13 Rubber Plug (Water Tray) 76712012 76712012 1
14 O-Gasket sub-assy of Bearing 76512051 76512051 1
15 Ring of Bearing 26152025 26152025 1
16 Evaporator Support 24212177 24212177 1
17 Evaporator Assy 01100100047201 01100100047201 1
18 Cross Flow Fan 10352060 10352060 1
19 Fan Motor 15012136 15012136 1
20 Motor Press Plate 26112511 26112511 1
21 Wall Mounting Frame 01362026 01362026 1
22 Connecting pipe clamp 2611218801 2611218801 1
23 Crank 73012005 73012005 1
24 Stepping Motor 1521240212 1521240212 1
25 Drainage Hose 05230014 05230014 1
26 Electric Box Assy 100002067337 100002068255 1
27 Lower Shield of Electric Box 01592139 01592139 1
28 Electric Box 2011221105 2011221105 1
29 Jumper 4202021923 4202021923 1
30 Main Board 300002061086 300002061086 1
31 Air Louver 10512736 10512736 1
32 Stepping Motor 1521210704 1521210704 1
33 Air Louver 2 10512735 10512735 1
34 Swing Lever 10512731 10512731 1
35 Decorative Board (Right) 20192662 20192662 1
36 Screw Cover 2425201726 2425201726 3
37 Electric Box Cover2 20112210 20112210 1
38 Shield Cover of Electric Box Cover 01592176 01592176 1
39 Electric Box Cover 20112209 20112209 1
40 Terminal Board 42011233 42011233 1
41 Power Cord / / /
42 Connecting Cable 4002052317 4002052317 0
43 Connecting Cable / / /
44 Remote Controller 305001000139 305001000139 1
45 Detecting Plate 30110144 30110144 1
46 Cold Plasma Generator 1114001602 1114001602 1
Part Code
Description
NO. GWH09QD-S6DBE6A/I GWH12QD-S6DBD2A/I Qty
Product Code CB465N03300 CB461N06200
1 Decorative Strip 23000100001801 / 1
2 Front Panel 00000300009701 200003000008 1
3 Display Board 300001000036 30565278 1
4 Filter Sub-Assy 1112208906 1112208906 2
5 Decorative Board (Left) 20192662 20192662 1
6 Front Case 2002248401 2002248401 1
7 Guide Louver 1051276501 1051276501 1
8 Axile Bush 10542036 10542036 2
9 Air Louver 1 10512733 10512733 2
10 Helicoid Tongue 26112512 26112512 1
11 Left Axile Bush 10512037 10512037 1
12 Rear Case assy 00000100001 00000100001 1
13 Rubber Plug (Water Tray) 76712012 76712012 1
14 O-Gasket sub-assy of Bearing 76512051 76512051 1
15 Ring of Bearing 26152025 26152025 1
16 Evaporator Support 24212177 24212177 1
17 Evaporator Assy 01100100047201 01100100047201 1
18 Cross Flow Fan 10352060 10352060 1
19 Fan Motor 15012136 15012136 1
20 Motor Press Plate 26112511 26112511 1
21 Wall Mounting Frame 01362026 01362026 1
22 Connecting pipe clamp 2611218801 2611218801 1
23 Crank 73012005 73012005 1
24 Stepping Motor 1521240212 1521240212 1
25 Drainage Hose 05230014 05230014 1
26 Electric Box Assy 100002068270 100002067337 1
27 Lower Shield of Electric Box 01592139 01592139 1
28 Electric Box 2011221105 2011221105 1
29 Jumper 4202021923 4202021923 1
30 Main Board 300002061086 300002061086 1
31 Air Louver 10512736 10512736 1
32 Stepping Motor 1521210704 1521210704 1
33 Air Louver 2 10512735 10512735 1
34 Swing Lever 10512731 10512731 1
35 Decorative Board (Rifht) 20192662 20192662 1
36 Screw Cover 2425201726 2425201726 3
37 Electric Box Cover2 20112210 20112210 1
38 Shield Cover of Electric Box Cover 01592176 01592176 1
39 Electric Box Cover 20112209 20112209 1
40 Terminal Board 42011233 42011233 1
41 Power Cord / / /
42 Connecting Cable 4002052317 4002052317 0
43 Connecting Cable / / /
44 Remote Controller 305001000139 305001000139 1
45 Detecting Plate 30110144 30110144 1
46 Cold Plasma Generator 1114001602 1114001602 1
Part Code
Description
NO. GWH12QD-S6DBE4A/I GWH12QD-S6DBE6A/I Qty
Product Code CB470N05100 CB465N03400
1 Decorative Strip / 23000100001801 1
2 Front Panel 200003000064T 200003000042S 1
3 Display Board 300001000081 300001000036 1
4 Filter Sub-Assy 1112208906 1112208906 2
5 Decorative Board (Left) 20192662 20192662 1
6 Front Case 2002248401 2002248401 1
7 Guide Louver 1051276501 1051276501 1
8 Axile Bush 10542036 10542036 2
9 Air Louver 1 10512733 10512733 2
10 Helicoid Tongue 26112512 26112512 1
11 Left Axile Bush 10512037 10512037 1
12 Rear Case assy 00000100001 00000100001 1
13 Rubber Plug (Water Tray) 76712012 76712012 1
14 O-Gasket sub-assy of Bearing 76512051 76512051 1
15 Ring of Bearing 26152025 26152025 1
16 Evaporator Support 24212177 24212177 1
17 Evaporator Assy 01100100047201 01100100047201 1
18 Cross Flow Fan 10352060 10352060 1
19 Fan Motor 15012136 15012136 1
20 Motor Press Plate 26112511 26112511 1
21 Wall Mounting Frame 01362026 01362026 1
22 Connecting pipe clamp 2611218801 2611218801 1
23 Crank 73012005 73012005 1
24 Stepping Motor 1521240212 1521240212 1
25 Drainage Hose 05230014 05230014 1
26 Electric Box Assy 100002068255 100002068270 1
27 Lower Shield of Electric Box 01592139 01592139 1
28 Electric Box 2011221105 2011221105 1
29 Jumper 4202021923 4202021923 1
30 Main Board 300002061086 300002061086 1
31 Air Louver 10512736 10512736 1
32 Stepping Motor 1521210704 1521210704 1
33 Air Louver 2 10512735 10512735 1
34 Swing Lever 10512731 10512731 1
35 Decorative Board (Rifht) 20192662 20192662 1
36 Screw Cover 2425201726 2425201726 3
37 Electric Box Cover2 20112210 20112210 1
38 Shield Cover of Electric Box Cover 01592176 01592176 1
39 Electric Box Cover 20112209 20112209 1
40 Terminal Board 42011233 42011233 1
41 Power Cord / / /
42 Connecting Cable 4002052317 4002052317 0
43 Connecting Cable / / /
44 Remote Controller 305001000139 305001000139 1
45 Detecting Plate 30110144 30110144 1
46 Cold Plasma Generator 1114001602 1114001602 1
Part Code
Description
NO. GWH09QD-S6DBD6A/I GWH12QD-S6DBD6A/I Qty
Product Code CB460N07000 CB460N06900
1 Decorative Strip / / 1
2 Front Panel 200003000027S 200003000027S 1
3 Display Board 300001000042 300001000042 1
4 Filter Sub-Assy 1112208906 1112208906 2
5 Decorative Board (Left) 20192662 20192662 1
6 Front Case 2002248401 2002248401 1
7 Guide Louver 1051276501 1051276501 1
8 Axile Bush 10542036 10542036 2
9 Air Louver 1 10512733 10512733 2
10 Helicoid Tongue 26112512 26112512 1
11 Left Axile Bush 10512037 10512037 1
12 Rear Case assy 00000100001 00000100001 1
13 Rubber Plug (Water Tray) 76712012 76712012 1
14 O-Gasket sub-assy of Bearing 76512051 76512051 1
15 Ring of Bearing 26152025 26152025 1
16 Evaporator Support 24212177 24212177 1
17 Evaporator Assy 01100100047201 01100100047201 1
18 Cross Flow Fan 10352060 10352060 1
19 Fan Motor 15012136 15012136 1
20 Motor Press Plate 26112511 26112511 1
21 Wall Mounting Frame 01362026 01362026 1
22 Connecting pipe clamp 2611218801 2611218801 1
23 Crank 73012005 73012005 1
24 Stepping Motor 1521240212 1521240212 1
25 Drainage Hose 05230014 05230014 1
26 Electric Box Assy 100002068680 100002068680 1
27 Lower Shield of Electric Box 01592139 01592139 1
28 Electric Box 2011221105 2011221105 1
29 Jumper 4202021923 4202021923 1
30 Main Board 300002061086 300002061086 1
31 Air Louver 10512736 10512736 1
32 Stepping Motor 1521210704 1521210704 1
33 Air Louver 2 10512735 10512735 1
34 Swing Lever 10512731 10512731 1
35 Decorative Board (Rifht) 20192662 20192662 1
36 Screw Cover 2425201726 2425201726 3
37 Electric Box Cover2 20112210 20112210 1
38 Shield Cover of Electric Box Cover 01592176 01592176 1
39 Electric Box Cover 20112209 20112209 1
40 Terminal Board 42011233 42011233 1
41 Power Cord / / /
42 Connecting Cable 4002052317 4002052317 0
43 Connecting Cable / / /
44 Remote Controller 305001000139 305001000139 1
45 Detecting Plate 30110144 30110144 1
46 Cold Plasma Generator 1114001602 1114001602 1
QE
44
A1
dis
pla
y
B4
dis
pla
y
The component picture is only for reference; please refer to the actual product.
Part Code
Description
NO. GWH18QE-S6DBD2B/I GWH18QE-S6DBE4B/I Qty
Product Code CB461N05900 CB470N05200
1 Front Panel Assy 00000300234 200003000062T 1
2 Filter Sub-Assy 1101200703 1101200703 2
3 Screw Cover 2425245301 2425245301 3
4 Front Case Assy 00000200043 00000200043 1
5 Swing Lever 10512743 10512743 1
6 Air Louver 1 10512741 10512741 2
7 Helicoid Tongue sub-assy 26112384 26112384 1
8 Left Axile Bush 10512037 10512037 1
9 Rear Case assy 22202736 22202736 1
10 Rubber Plug (Water Tray) 76712012 76712012 1
11 Ring of Bearing 26152025 26152025 1
12 O-Gasket sub-assy of Bearing 76512051 76512051 1
13 Cross Flow Fan 10352057 10352057 1
14 Evaporator Support 24212178 24212178 1
15 Evaporator Assy 01100100007301 01100100007301 1
16 Wall Mounting Frame 01252229 01252229 1
17 Motor Press Plate 26112515 26112515 1
18 Fan Motor 15012136 15012136 1
19 Connecting pipe clamp 26112514 26112514 1
20 Drainage Hose 0523001405 0523001405 1
21 Stepping Motor 1521240212 1521240212 1
22 Crank 73012005 73012005 1
23 Air Louver 1 10512742 10512742 1
24 Air Louver 10512744 10512744 1
25 Stepping Motor 1521210704 1521210704 1
26 Guide Louver 1051232001 1051232001 1
27 Axile Bush 10542036 10542036 2
28 Electric Box 2011221105 2011221105 1
29 Terminal Board 42011233 42011233 1
30 Electric Box Cover 2 20112210 20112210 1
31 Main Board 300002061087 300002061087 1
32 Display Board 30565278 300001000081 1
33 Shield Cover of Electric Box 01592139 01592139 1
34 Electric Box Cover 20112209 20112209 1
35 Jumper 4202021928 4202021928 1
36 Lower Shield of Electric Box 01592139 01592139 1
37 Electric Box Assy 100002068273 100002068258 1
38 Power Cord / / /
39 Connecting Cable 4002052317 4002052317 0
40 Connecting Cable / / /
41 Temperature Sensor 3900031302 3900031302 1
42 Remote Controller 305001000139 305001000139 1
43 Cold Plasma Generator 1114001602 1114001602 1
44 Detecting Plate 30110144 30110144 1
Part Code
Description
NO. GWH18QE-S6DBE6B/I GWH24QE-S6DBD2A/I Qty
Product Code CB465N03600 CB461N06000
1 Front Panel Assy 00000300007801 00000300234 1
2 Filter Sub-Assy 1101200703 1101200703 2
3 Screw Cover 2425245301 2425245301 3
4 Front Case Assy 00000200043 00000200043 1
5 Swing Lever 10512743 10512743 1
6 Air Louver 1 10512741 10512741 2
7 Helicoid Tongue sub-assy 26112384 26112384 1
8 Left Axile Bush 10512037 10512037 1
9 Rear Case assy 22202736 22202736 1
10 Rubber Plug (Water Tray) 76712012 76712012 1
11 Ring of Bearing 26152025 26152025 1
12 O-Gasket sub-assy of Bearing 76512051 76512051 1
13 Cross Flow Fan 10352057 10352057 1
14 Evaporator Support 24212178 24212178 1
15 Evaporator Assy 01100100007301 011001000095 1
16 Wall Mounting Frame 01252229 01252229 1
17 Motor Press Plate 26112515 26112515 1
18 Fan Motor 15012136 15012136 1
19 Connecting pipe clamp 26112514 26112514 1
20 Drainage Hose 0523001405 0523001405 1
21 Stepping Motor 1521240212 1521240212 1
22 Crank 73012005 73012005 1
23 Air Louver 1 10512742 10512742 1
24 Air Louver 10512744 10512744 1
25 Stepping Motor 1521210704 1521210704 1
26 Guide Louver 1051232001 1051232001 1
27 Axile Bush 10542036 10542036 2
28 Electric Box 2011221105 2011221105 1
29 Terminal Board 42011233 42011233 1
30 Electric Box Cover 2 20112210 2011221001 1
31 Main Board 300002061087 300002060785 1
32 Display Board 300001000036 30565278 1
33 Shield Cover of Electric Box 01592139 01592139 1
34 Electric Box Cover 20112209 2011220901 1
35 Jumper 4202021928 4202021921 1
36 Lower Shield of Electric Box 01592139 01592139 1
37 Electric Box Assy 100002068297 100002068272 1
38 Power Cord / / /
39 Connecting Cable 4002052317 4002052317 0
40 Connecting Cable / / /
41 Temperature Sensor 3900031302 3900031302 1
42 Remote Controller 305001000139 305001000081 1
43 Cold Plasma Generator 1114001602 1114001602 1
44 Detecting Plate 30110144 30110144 1
Part Code
Description
NO. GWH24QE-S6DBE4A/I GWH24QE-S6DBE6A/I Qty
Product Code CB470N05300 CB465N03500
1 Front Panel Assy 200003000062T 00000300007801 1
2 Filter Sub-Assy 1101200703 1101200703 2
3 Screw Cover 2425245301 2425245301 3
4 Front Case Assy 00000200043 00000200043 1
5 Swing Lever 10512743 10512743 1
6 Air Louver 1 10512741 10512741 2
7 Helicoid Tongue sub-assy 26112384 26112384 1
8 Left Axile Bush 10512037 10512037 1
9 Rear Case assy 22202736 22202736 1
10 Rubber Plug (Water Tray) 76712012 76712012 1
11 Ring of Bearing 26152025 26152025 1
12 O-Gasket sub-assy of Bearing 76512051 76512051 1
13 Cross Flow Fan 10352057 10352057 1
14 Evaporator Support 24212178 24212178 1
15 Evaporator Assy 011001000095 011001000095 1
16 Wall Mounting Frame 01252229 01252229 1
17 Motor Press Plate 26112515 26112515 1
18 Fan Motor 15012136 15012136 1
19 Connecting pipe clamp 26112514 26112514 1
20 Drainage Hose 0523001405 0523001405 1
21 Stepping Motor 1521240212 1521240212 1
22 Crank 73012005 73012005 1
23 Air Louver 1 10512742 10512742 1
24 Air Louver 10512744 10512744 1
25 Stepping Motor 1521210704 1521210704 1
26 Guide Louver 1051232001 1051232001 1
27 Axile Bush 10542036 10542036 2
28 Electric Box 2011221104 2011221105 1
29 Terminal Board 42011233 42011233 1
30 Electric Box Cover 2 20112210 2011221001 1
31 Main Board 300002060785 300002060785 1
32 Display Board 300001000081 300001000036 1
33 Shield Cover of Electric Box 01592139 01592139 1
34 Electric Box Cover 20112209 2011220901 1
35 Jumper 4202021921 4202021921 1
36 Lower Shield of Electric Box 01592139 01592139 1
37 Electric Box Assy 100002068254 100002068300 1
38 Power Cord / / /
39 Connecting Cable 4002052317 4002052317 0
40 Connecting Cable / / /
41 Temperature Sensor 3900031302 3900031302 1
42 Remote Controller 305001000081 305001000081 1
43 Cold Plasma Generator 1114001602 1114001602 1
44 Detecting Plate 30110144 30110144 1
Part Code
Description
NO. GWH18QE-S6DBD6B/I GWH24QE-S6DBD6A/I Qty
Product Code CB460N06800 CB460N07100
1 Front Panel Assy 200003000023S 200003000023S 1
2 Filter Sub-Assy 1101200703 1101200703 2
3 Screw Cover 2425245301 2425245301 3
4 Front Case Assy 00000200043 00000200043 1
5 Swing Lever 10512743 10512743 1
6 Air Louver 1 10512741 10512741 2
7 Helicoid Tongue sub-assy 26112384 26112384 1
8 Left Axile Bush 10512037 10512037 1
9 Rear Case assy 22202736 22202736 1
10 Rubber Plug (Water Tray) 76712012 76712012 1
11 Ring of Bearing 26152025 26152025 1
12 O-Gasket sub-assy of Bearing 76512051 76512051 1
13 Cross Flow Fan 10352057 10352057 1
14 Evaporator Support 24212178 24212178 1
15 Evaporator Assy 01100100007301 011001000095 1
16 Wall Mounting Frame 01252229 01252229 1
17 Motor Press Plate 26112515 26112515 1
18 Fan Motor 15012136 15012136 1
19 Connecting pipe clamp 26112514 26112514 1
20 Drainage Hose 0523001405 0523001405 1
21 Stepping Motor 1521240212 1521240212 1
22 Crank 73012005 73012005 1
23 Air Louver 1 10512742 10512742 1
24 Air Louver 10512744 10512744 1
25 Stepping Motor 1521210704 1521210704 1
26 Guide Louver 1051232001 1051232001 1
27 Axile Bush 10542036 10542036 2
28 Electric Box 2011221105 2011221104 1
29 Terminal Board 42011233 42011233 1
30 Electric Box Cover 2 20112210 20112210 1
31 Main Board 300002061087 300002060785 1
32 Display Board 300001000042 300001000042 1
33 Shield Cover of Electric Box 01592139 01592139 1
34 Electric Box Cover 20112209 20112209 1
35 Jumper 4202021928 4202021921 1
36 Lower Shield of Electric Box 01592139 01592139 1
37 Electric Box Assy 100002068643 100002068639 1
38 Power Cord / / /
39 Connecting Cable 4002052317 4002052317 0
40 Connecting Cable / / /
41 Temperature Sensor 3900031302 3900031302 1
42 Remote Controller 305001000139 305001000081 1
43 Cold Plasma Generator 1114001602 1114001602 1
44 Detecting Plate 30110144 30110144 1
20 19 18 17 24 25 26 16 15
14
21
13
22
12
27
11
10
23
1 2 3 4 5 6 7 8 9
The component picture is only for reference; please refer to the actual product.
Part Code
Description
No. GWH09ACC-S6DBA1A/O GWH12ACC-S6DBA1A/O Qty
Product Code CB497W09200 CB497W10000
1 Front Grill 22413046 22413046 1
2 Cabinet 0153305105 0153305105 1
3 Brushless DC Motor 1501308519 1501308519 1
4 Clapboard Sub-Assy 01235094 01235094 1
5 Chassis Sub-assy 017000060317P 017000060383P 1
6 Compressor and Fittings 00900100022901 00900100022901 1
7 Valve Support Sub-Assy 01710400005P 01710400005P 1
8 Cut-off valve 1/4(N) 07130239 07130239 1
9 Cut-off valve 3/8(N) 071302391 071302391 2
10 Valve Cover 22243005 22243005 1
11 Left Side Plate 01303169P 01303169P 1
12 4-Way Valve Assy 030152060290 030152060290 1
13 Filtering Sub-Assy 030184000056 030184000042 1
14 Condenser Assy 011002060644 011002000422 1
15 Fixed Mount 01207800008 01207800008 1
16 Flash Vaporizer Assy 030070060008 030070060008 1
17 Coping 012049000006P 012049000006P 1
18 Main Board 300027060797 300027060800 1
19 Electric Box Assy 100002065314 100002065683 1
20 Motor Support Sub-Assy 01703237 01703180 1
21 Left Side Plate 01303169P 01303169P 1
22 Axial Flow Fan 10333011 10333011 1
23 Valve Cover 22243005 22243005 1
24 Terminal Board 422000060016 422000060016 1
25 Wire Clamp 71010003 71010003 1
26 Wire Clamp 71010103 71010003 1
27 Compressor Gasket 009012000026 009012000026 3
Part Code
Description
No. GWH09YD-S6DBA2A/O GWH12YD-S6DBA2A/O Qty
Product Code CB466W00109 CB466W00208
1 Front Grill 22413046 22413046 1
2 Cabinet 01433034P 01433034P 1
3 Brushless DC Motor 1501308519 1501308519 1
4 Clapboard Sub-Assy 01235094 01235094 1
5 Chassis Sub-assy 017000060383P 017000060383P 1
6 Compressor and Fittings 00900100022901 00900100022901 1
7 Valve Support Sub-Assy 01710400005P 01710400005P 1
8 Cut-off valve 1/4(N) 07130239 07130239 1
9 Cut-off valve 3/8(N) 071302391 071302391 2
10 Valve Cover 22243005 22243005 1
11 Left Side Plate 01303169P 01303169P 1
12 4-Way Valve Assy 030152000214 030152000214 1
13 Filtering Sub-Assy 030184000044 030184000042 1
14 Condenser Assy 011002000613 011002000422 1
15 Fixed Mount 01207800008 01207800008 1
16 Flash Vaporizer Assy 030070060011 030070060011 1
17 Coping 012049000006P 012049000006P 1
18 Main Board 300027000100 300027000056 1
19 Electric Box Assy 10000100924 100002000997 1
20 Motor Support Sub-Assy 01703180 01703180 1
21 Left Side Plate 01303169P 01303169P 1
22 Axial Flow Fan 10333011 10333011 1
23 Valve Cover 22243005 22243005 1
24 Terminal Board 422000060016 422000060016 1
25 Wire Clamp 71010003 71010003 1
26 Wire Clamp 71010103 71010103 1
27 Compressor Gasket 009012000026 009012000026 3
GWH18ACE-S6DBA1A/O GWH24YE-S6DBA2A/O
The component picture is only for reference; please refer to the actual product.
Part Code
Description
No. GWH24YE-S6DBA2A/O GWH18ACE-S6DBA1A/O Qty
Product Code CB466W00300 CB497W11000
1 Front Grill 22415011 22415011 1
2 Fan Motor 15010400000106 15010400000102 1
3 Electric Box (Fireproofing) 20115003 20115003 1
4 Radiator 4901521501 4901521501 1
5 Main Board 300027000308 300027060855 1
6 Electric Box Assy 100002000609 100002066754 1
7 Terminal Board Support sub-assy 01715016 01715016A 1
8 Terminal Board 422000060009 422000060009 1
9 Handle 26233053 26233053 1
10 Left Side Plate 01305043P 01305043P 1
11 Coping 01255020P 01255020P 1
12 Motor Support Sub-Assy 017012000015 017012000017 1
13 Condenser Support Plate 01175092 01175092 1
14 Clapboard Sub-Assy 017021000067 01235091 1
15 Condenser Assy 011002000285 011002000486 1
16 Rear Grill / / /
17 Wiring Clamp 26115004 26115004 1
18 Temp Sensor 3900030901 3900030901 1
19 Right Side Plate 0130504401P 0130504401P 1
20 Big Handle 26235001 26235001 1
21 Cut off Valve 07130239 07130239 1
22 Valve Support Sub-Assy 0170506101P 0170506101P 1
23 Baffle(Valve Support) 0170505701 0170505701 1
24 Electronic Expansion Valve 072009000019 072009000019 1
25 4-Way Valve Assy 030152000260 030152000260 1
26 Compressor and Fittings 00105274 00105274 1
27 Drainage Connecter 06123401 / 1
28 Chassis Sub-assy 017000000166P 017000060398P 1
29 Drainage hole Cap 06813401 / 1
30 Axial Flow Fan 10335013 10335013 1
31 Cabinet 01435004P 01435004P 1
32 Valve Cover 22245003 22245003 1
Step Procedure
Front panel
Groove
3. Remove panel
C2/C8/D2/D6 display
Screws Panel
a A1/B6/C2/C4 display: Screw off the 2 Front panel
screws that are locking the display board.
Separate the display board from the front
panel.
A2/A3 display: Screw off the 2 screws
that are locking the display board.
This display can be disassembled only
after removing the front case (refer to step
5 of disassembly).
A2/A3 display Panel rotation
A5/B2/B4/B8/C6/D2 display: Screw off
the 2 screws that are locking the display Screws
board.
Separate the panel rotation shaft from Groove
b
A5/B2/B4/B8/C6/D2/E4 display
removes the front panel.
Screws
Step Procedure
4. Remove electric box cover 2 and detecting plate(WIFI) Electric box cover 2
Screw
Remove the screws on the electric box
cover 2 and detecting plate(WIFI) to remove
the electric box cover 2 and detecting
plate(WIFI).
Screws
Detecting plate
(WIFI)
Note:
1.Open the screw caps before removing
the screws around the air outlet.
2.The quantity of screws fixing the front
Front case
case sub-assy is different for different
sub-assy Screw caps
models.
Screw
Clasp
b Loosen the connection clasps between
front case sub-assy and bottom case. Lift Front case
up the front case sub-assy and take it out. sub-assy
Vertical
louver
Clasps Vertical
louver
Step Procedure
Electric box
Shield cover of electric
box sub-assy
Indoor tube
temperature
Grounding screw sensor Electric box assy
b Take off the water retaining sheet.
Remove the cold plasma generator by
screwing off the locking screw on the
generator.
Take off the indoor tube temperature Cold plasma
sensor. generator
Screw off 1 grounding screw.
Remove the wiring terminals of motor and
stepping motor. Screw
Remove the electric box assy.
Water retaining Wiring
sheet terminal
of stepping
motor
Screw
Main board
c Twist off the screws that are locking
each lead wire and rotate the electric
box assy.
Twist off the screws that are locking the
wire clip. Loosen the power cord and
remove its wiring terminal. Lift up the
main board and take it off.
Power cord
Screw
Step Procedure
terminals.
soft sheath connector
2.Pull out the holder for some terminals at
Groove
Bottom case
c First remove the left side of the evaporator
from the groove of bottom case and then
remove the right side from the clasp on
the bottom case.
Clasp
Evaporator assy
Connection pipe
Step Procedure
Motor clamp
C
b Remove the screws at the connection Screw
place of cross flow blade and motor; lift Holder Motor
the motor and cross flow blade upwards sub-assy
to remove them.
Remove the bearing holder sub-assy.
Screws
Step motor
QD/QE
Front panel
Left filter
Front
Groove Right filter
case
Horizontal louver
Location of
Axile bush step motor
Screws
Groove
A5/B2/B4/B8/C4/C6/D2 display
Screws
4.Remove electric box cover 2 and detecting plate(WIFI) Electric box cover 2
Screws
Detecting plate
(WIFI)
a
Note:
ķ Open the screw caps before removing the
screws arround the air outlet.
ĸ
case sub-assy is different for different
models.
6.Remove display
Screws
Step Procedure
Swing motor
assy.
Indoor tube
b ķ Cut off the wire binder and pull out temperature s ensor
the indoor tube temperature sensor.
ĸ Screw off one grounding screw. Main
Ĺ Remove the wiring terminals of motor board
and stepping motor. G rounding
ĺ Remove the electric box assy. screw Wiring
Ļ Screw off the screws thar are locking terminal
each lead wire. of motor
Wire binder
Wiring
terminal
of stepping
Screw motor
Step Procedure
Groove
Rear case assy
Step Procedure
a
then remove the motor clamp.
remove them.
ĸ Remove the bearing holder sub-assy.
Ĺ
then remove the step motor.
1. Before disassembly
Twist off the screws used for fixing the handle and
valve cover, pull the handle and valve cover up
ward to remove it. handle
valve cover
panel
grille
6. Remove motor
motor
motor suppor
Remove screws fixing electric box assy and electric box cover
mid-isolation board, loosen the bonding tie, pull off the
wiring terminal, lift to remove the electric box assy.
electric box assy
big valve
condenser assy
18/24K
Steps Procedure
1.Remove handle
Twist off the screws used for fixing the handle and
valve cover, pull the handle and valve cover up
ward to remove it.
handle
valve cover
top panel
Remove the screws connecting the top
panel with the front panel and left&right
side plate, and then remove the top panel.
Steps Procedure
6.Remove motor
motor
Steps Procedure
electric box
Steps Procedure
9.Remove4-wayvalve assy
Steps Procedure
12.Remove compressor
compressor
Twist off the 3 foot nuts on compressor and then
remove the compressor.
Appendix:
Appendix 1: Reference Sheet of Celsius and Fahrenheit
Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1.8+32
Set temperature
Fahrenheit Fahrenheit Fahrenheit
display Fahrenheit display Fahrenheit display Fahrenheit
Celsius(°C) Celsius(°C) Celsius(°C)
temperature (°F) temperature (°F) temperature (°F)
(°F) (°F) (°F)
61 60.8 16 69/70 69.8 21 78/79 78.8 26
62/63 62.6 17 71/72 71.6 22 80/81 80.6 27
64/65 64.4 18 73/74 73.4 23 82/83 82.4 28
66/67 66.2 19 75/76 75.2 24 84/85 84.2 29
68 68 20 77 77 25 86 86 30
Ambient temperature
Fahrenheit Fahrenheit Fahrenheit
display Fahrenheit display Fahrenheit display Fahrenheit
Celsius(°C) Celsius(°C) Celsius(°C)
temperature (°F) temperature (°F) temperature (°F)
(°F) (°F) (°F)
32/33 32 0 55/56 55.4 13 79/80 78.8 26
34/35 33.8 1 57/58 57.2 14 81 80.6 27
36 35.6 2 59/60 59 15 82/83 82.4 28
37/38 37.4 3 61/62 60.8 16 84/85 84.2 29
39/40 39.2 4 63 62.6 17 86/87 86 30
41/42 41 5 64/65 64.4 18 88/89 87.8 31
43/44 42.8 6 66/67 66.2 19 90 89.6 32
45 44.6 7 68/69 68 20 91/92 91.4 33
46/47 46.4 8 70/71 69.8 21 93/94 93.2 34
48/49 48.2 9 72 71.6 22 95/96 95 35
50/51 50 10 73/74 73.4 23 97/98 96.8 36
52/53 51.8 11 75/76 75.2 24 99 98.6 37
54 53.6 12 77/78 77 25
Note: The additional refrigerant charging amount in Sheet 2 is recommendedvalue, not compulsory.
Improper pipe expanding is the main cause of refrigerant leakage.Please Pipe cutter
expand the pipe according to the following steps:
Leaning Uneven Burr
A:Cut the pip
● Confirm the pipe length according to the distance of indoor unit and outdoor unit.
● Cut the required pipe with pipe cutter.
● Remove the burrs with shaper and prevent the burrs from getting into the pipe. Shaper
Downwards
C:Put on suitable insulating pipe
Smooth surface
F:Inspection
● Check the quality of expanding port. If there is any blemish, expand the
Improper expanding
port again according to the steps above.
Resistance Table of Ambient Temperature Sensor for Indoor and Outdoor (15K)
Resistance Table of Tube Temperature Sensors for Indoor and Outdoor (20K)
For product improvement, specifications and appearance in this manual are subject to change without prior notice.