AUMA MATIC Technical Data Sheet
AUMA MATIC Technical Data Sheet
1
Technical data Actuator controls AUMA MATIC
AM 02.1
Actuator controls AUMA MATIC AM 01.1/AM 02.1 for controlling multi-turn actuators of the SA/SAR type range and part-turn
actuators of the SG/SGR type range. For versions with fieldbus interfaces see separate documents.
Features and functions
Voltage supply Standard voltages:
3-ph AC 1-ph AC
voltages/frequencies voltages/frequencies
Volt 220 230 240 380 400 415 440 460 480 500 Volt 110,115,120 220,230,240
Hz 50 50 50 50 50 50 60 60 60 50 Hz 60 50
Special voltages:
3-ph AC 1-ph AC
voltages/frequencies voltages/frequencies
Volt 525 575 660 690 Volt 208
Hz 50 50 50 50 Hz 60
Permissible variation of the nominal voltage: ± 10 %
Permissible variation of the mains frequency: ± 5 %
Current consumption with controls depending on mains voltage:
100 to 120 V AC = max. 575 mA
208 to 240 V AC = max. 275 mA
380 to 690 V AC = max. 160 mA
External supply of the electronics 24 V DC + 20 % / – 15 %,
(option) Current consumption: Basic version approx. 200 mA, with options up to 500 mA
Switchgear Standard: Reversing contactors1) (mechanically and electrically interlocked)
For motor power up to 1.5 kW, nominal motor current up to 9 A
(OPEN - CLOSE duty) or 5.2 A (modulating duty)
Options: Reversing contactors1) (mechanically and electrically interlocked)
For motor power up to 7.5 kW, nominal motor current up to 20 A
(OPEN - CLOSE duty) or 18 A (modulating duty)
Thyristor unit (recommended for modulating actuators)
For motor power up to 1.5 kW, 500 V AC with internal fuses
For motor power up to 3.0 kW, 500 V AC with internal fuses
For motor power up to 5,5 kW, 500 V AC, external fuses required
Control Standard: Control inputs 24 V DC, OPEN - STOP - CLOSE (via opto-isolator,
with one common), current consumption: approx. 10 mA per input
Observe min. duration of impulse for modulating actuators
Option: Control inputs 115 V AC, OPEN - STOP - CLOSE (via opto-isolator,
with one common), current consumption: approx. 15 mA per input
Output signals Standard: 5 output relays with gold-plated contacts:
4 NO contacts with one common,
max. 250 V AC, 0.5 A (resistive load)
Standard configuration:
End position CLOSED, end position OPEN, selector switch REMOTE,
selector switch LOCAL
1 potential-free change-over contact, max. 250 V AC, 0.5 A (resistive load)
for collective fault signal:
Torque fault, phase failure, motor protection tripped
Option: Signals in combination with positioner (refer to page 2):
End position OPEN, end position CLOSED (requires tandem switch
within actuator)
Selector switch REMOTE, selector switch LOCAL via selector switch
2nd level
1 potential-free change-over contact, max. 250 V AC, 0.5 A (resistive load)
For collective fault signal:
torque fault, phase failure, motor protection tripped
Voltage output Standard: Auxiliary voltage 24 V DC, max. 50 mA to supply the control inputs,
galvanically isolated from internal voltage supply
Option: Auxiliary voltage 115 V AC, max. 30 mA to supply the control inputs2),
galvanically isolated from internal voltage supply
Local controls Standard: Selector switch LOCAL - OFF - REMOTE (lockable in all three positions)
Push buttons OPEN - STOP - CLOSE
3 indication lights:
End position CLOSED (yellow), collective fault signal (red), end position
OPEN (green)
Option: Protection cover, lockable
1) The reversing contactors are designed for a lifetime of 2 million starts. For applications requiring a high number of starts, we recommend the use of thyristor
units subject to little wear.
2) Not possible in combination with PTC tripping device
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.
Page 1 of 3
Issue 1.07
Y001.280/002/en
AM 01.1
Technical data Actuator controls AUMA MATIC
AM 02.1
Functions Standard:
Switch-off mode adjustable
limit or torque seating for end position OPEN and end position CLOSED
Overload protection against excessive torques over the whole travel
Excessive torque (torque fault) can be excluded from collective fault signal
Phase failure monitoring with automatic phase correction
Push-to-run operation or self-retaining in REMOTE
Push-to-run operation or self-retaining in LOCAL
Blinker transmitter signal of actuator can be switched on or off (option)
Options: Positioner3):
Nominal position value via analogue input E1 = 0/4 – 20 mA
Adjustable behaviour on loss of signal
Adjustable sensitivity (dead band) and pause time
Split Range operation
Motor protection evaluation Standard: Monitoring of the motor temperature in connection with thermoswitches
in the actuator motor
Options: Additional thermal overload relay in the controls in combination with
thermoswitches within the actuator motor
PTC tripping device in combination with PTC thermistors in the actuator
motor
Electrical connection Standard: AUMA plug/socket connector with screw type connection:
Threads for cable glands:
M-threads: 1 x M 20 x 1.5 and 2 x M 25 x 1.5
Pg-threads: 1 x Pg 13.5 / 2 x Pg 21
NPT-threads: 1 x ½" NPT / 2 x ¾" NPT
Options: M-threads: 1 x M 20 x 1.5 / 2 x M 25 x 1.5 / 1 x M 32 x 1.5
1 x M 20 x 1.5 / 1 x M 25 x 1.5 / 1 x M 32 x 1.5
Pg-threads: 1 x Pg 13.5 / 2 x Pg 21 / 1 x Pg 29
1 x Pg 13.5 / 1 x Pg 21 / 1 x Pg 29
NPT-threads: 2 x ¾" NPT / 1 x 1¼" NPT
G-threads: 2 x G ¾" / 1 x G 1" / 1 x G 1¼"
2 x G ¾" / 1 x G 1¼"
Special threads, other than standard mentioned above, possible
Gold-plated control plug (pins and sockets)
Parking frame for wall mounting of the disconnected plug
Protection cover for plug compartment (when plug is removed)
Wiring diagram (basic version) MSP 1110KC3--F18E1 KMS TP110/001
Further options for version with RWG in the actuator
Position feedback Analogue output E2 = 0/4 – 20 mA (load max. 500 Ω)
(option)
Service conditions
Enclosure protection according Standard: IP 67 (when mounted)
to EN 60 529 Options: IP 684)
Terminal compartment additionally sealed against interior (double sealed)
Corrosion protection Standard: KN Suitable for installation in industrial units, in water or
power plants with a low pollutant concentration
Options: KS Suitable for installations in occasionally or permanently aggressive
atmosphere with a moderate pollutant concentration
(e.g. wastewater treatment plants, chemical industry)
KX Suitable for installation in extremely aggressive atmosphere with
high humidity and high pollutant concentration
KX-G same as KX, however aluminium-free version (outer parts)
Finish coating Standard: Two-component iron-mica combination
Option: Special primer/special finish coat (customer’s choice)
Colour Standard: Grey (DB 702, similar to RAL 9007)
Option: Other colours than standard colour are possible on request
Issue 1.07
Y001.280/002/en
AM 01.1
Technical data Actuator controls AUMA MATIC
AM 02.1
Ambient temperature Standard: – 25 °C to + 70 °C
Options: – 40 °C to + 70 °C, low temperature version
– 50 °C to + 70 °C, extreme low temperature version incl. heating system
– 60 °C to + 70 °C, extreme low temperature version incl. heating system
Low temperature versions incl. heating system for connection to external power supply
230 V AC or 115 V AC.
Vibration resistance5) 1 g, from 10 Hz to 200 Hz
according to IEC 60 068-2-6
Weight approx. 7 kg (with AUMA plug/socket connector)
Accessories
Wall bracket6) AUMA MATIC mounted separately from the actuator, including plug/socket connector.
Connecting cables on request.
Recommended for high ambient temperatures, difficult access, or in case of heavy
vibrations during service.
Further information
EU Directives Electromagnetic Compatibility (EMC): (89/336/EEC)
Low Voltage Directive: (73/23/EEC)
Machinery Directive: (98/37/EC)
Reference documents: Product description, “Actuator controls AUMA MATIC”
Dimension sheets “Multi-turn actuators/part-turn actuators with integral controls AUMA
MATIC”
5) Resistant to vibrations during start-up or for failures of the plant. However, a fatigue strength may not be derived from this.
6) Cable length between actuator and AUMA MATIC max. 100 m. Not suitable for version with potentiometer in the actuator.
Instead of the potentiometer, an RWG has to be used in the actuator
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.
Page 3 of 3
Issue 1.07
Y001.280/002/en