Topic - 4 (Load Calcualtion)
Topic - 4 (Load Calcualtion)
Ventilation &
Air
Conditioning
System
Desgin
Bridging the Gap to Success
https://www.btcm360.com/
BRIDGE
academy Cert No: SIS180422S037
Bridg T.C.M
No: 118, Lake Circus, Kolabagan, Dhaka-1205 Bridg TCM
1
survey and estimate 1
SYSTEM DESIGN MANUAL
applied psychrometrics 8
INDEX
2
Part 1. Load Estimating | Chapter 1. Building Survey And Load Estimate
3
Part 1. Load Estimating | Chapter 1. Building Survey And Load Estimate
of people on the basis of square feet per 16. Thermal storage – Includes system operating
person, or on average traffic. schedule (12, 16 or 24 hours per day)
12. Lighting - Wattage at peak. Type- specifically during peak outdoor conditions,
incandescent, fluorescent, recessed, ex- permissible temperature swing in space
posed. If the lights are recessed, the type of during a design day, rugs on floor, nature of
air flow over the lights, exhaust, return or surface materials enclosing the space (see
supply, should be anticipated. At times, it is Chapter 3).
required to estimate the wattage on a basis of 17. Continuous or intermittent operation – Whether
watts per sq ft, due to lack of exact system be required to operate every business
information. day during cooling season, or only
13. Motors – Location, nameplate and brake occasionally, such as churches and
horsepower, and usage. The latter is of great ballrooms. If intermittent operation, determine
significance and should be carefully duration of time available for precooling or
evaluated. pulldown.
The power input to electric motors is not
necessarily equal to the rated horsepower LOCATION OF EQUIPMENT AND SERVICE
divided by the motor efficiency. Frequently The building survey should also include information
these motors may be operating under a which enables the engineer to select equipment location,
continuous overload, or may be operating at and plan the air and water distribution systems. The
less than rated capacity. It is always advisable following is a guide to obtaining this information:
to measure the power input wherever
possible. This is especially important in 1. Available spaces – Location of all stairwells,
estimates for industrial installations where the elevator shafts, abandoned smokestacks, pipe
motor machine load is normally a major shafts, dumbwaiter shafts, etc., and spaces
portion of the cooling load. for air handing apparatus, refrigeration
14. Appliances, business machines, electronic machines, cooling towers, pumps, and
equipment – Location, rated wattage, steam or services (also see Item 5).
gas consumption, hooded or unhooded, 2. Possible obstructions – Locations of all
exhaust air quantity installed or required, and electrical conduits, piping lines, and other
usage. obstructions or interferences that may be in
Greater accuracy may be obtained by the way of the duct system.
measuring the power or gas input during times 3. Location of all fire walls and partitions –
of peak loading. The regular service meters Requiring fire dampers (also see Item 16).
may often be used for this purpose, provided 4. Location of outdoor air intakes – In reference
power or gas consumption not contributing to to street, other buildings, wind direction, dirt,
the room heat gain can be segregated. and short-circuiting of unwanted
Avoid pyramiding the heat gains from various contaminants.
appliances and business machines. For 5. Power service – Location, capacity, current
example, a toaster or a waffle iron may not be limitations, voltage, phases and cycle, 3 or 4
used during the evening, or the fry kettle may wire; how additional power (if required) may
not be used during morning, or not all be brought in and where.
business machines in a given space may be 6. Water service – Location, size of lines,
used at the same time. capacity, pressure, maximum temperature.
Electronic equipment often requires individual 7. Steam service – Location, size, capacity,
air conditioning. The manufacturer’s re- temperature, pressure, type of return system.
commendation for temperature and humidity 8. Refrigeration, brine or chilled water (if
variation must be followed, and these furnished by customer) – Type of system,
requirements are often quite stringent. capacity, temperature, gpm, pressure.
15. Ventilation – Cfm per person, cfm per sq ft, 9. Architectural characteristics of space – For
scheduled ventilation (agreement with selection of outlets that will blend into the
purchaser), see Chapter 6. Excessive smoking space design.
or odors, code requirements. Exhaust fans- 10. Existing air conveying equipment and ducts –
type, size, speed, cfm delivery. For possible reuse.
4
Part 1. Load Estimating | Chapter 1. Building Survey And Load Estimate
5
Part 1. Load Estimating | Chapter 1. Building Survey And Load Estimate
6
Part 1. Load Estimating | Chapter 1. Building Survey And Load Estimate
5. The wind blowing against a side of the Table 48, page 100.
building- Wind causes the outdoor air that is 2. Lights – Illuminants convert electrical power
higher in temperature and moisture content to into light and heat (refer to Chapter 7). Some
infiltrate thru the cracks around the doors and of the heat is radiant and is partially stored
windows, resulting in localized sensible and (see Chapter 3).
latent heat gains. All or part of this infiltration 3. Appliances – Restaurants, hospitals,
may be offset by air being introduced thru the laboratories, and some specialty shops
apparatus for ventilation purposes. Chapter 6 (beauty shops) have electrical, gas, or steam
contains the estimating data. appliances which release heat into the space.
6. Outdoor air usually required for ventilation Tables 50 thru 52, pages 101-103, list the
purposes – Outdoor air is usually necessary to recommended heat gain values for most
flush out the space and keep the odor level appliances when not hooded. If a positive
down. This ventilation air imposes a cooling exhaust hood is used with the appliances, the
and dehumidifying load on the apparatus heat gain is reduced.
because the heat and/or moisture must be 4. Electric calculating machines – Refer to
removed. Most air conditioning equipment manufacturer’s data to evaluate the heat gain
permits some outdoor air to bypass the from electric calculating machines. Normally,
cooling surface (see Chapter 8). This not all of the machines would be in use
bypassed outdoor air becomes a load within simultaneously, and, therefore, a usage or
the conditioned space, similar to infiltration; diversity factor should be applied to the full
instead of coming thru a crack around the load heat gain. The machines may also be
window, it enters the room thru the supply air hooded, or partially cooled internally, to
duct. The amount of bypassed outdoor air reduce the load on the air conditioning
depends on the type of equipment used as system.
outlined in Chapter 8. Table 45, page 97, 5. Electric motors – Electric motors are a
provides the data from which the ventilation significant load in industrial applications and
requirements for most comfort applications should be thoroughly analyzed with respect to
can be estimated. operating time and capacity before estimating
The foregoing is that portion of the load on the air the load (see Item 13 under “Space
conditioning equipment that originates outside the space Characteristics and Heat Load Sources”). It
and is common to all applications. is frequently possible to actually measure this
load in existing applications, and should be so
INTERNAL LOADS done where possible. Table 53, page 105,
Chapter 7 contains the data required to estimate the provides data for estimating the heat gain from
heat gain from most items that generate heat within the electric motors.
conditioned space. The internal load, or heat generated 6. Hot pipes and tanks – Steam or hot water
within the space, depends on the character of the pipes running thru the air conditioned space,
application. Proper diversity and usage factor should be or hot water tanks in the space, add heat. In
applied to all internal loads. As with the solar heat gain, many industrial applications, tanks are open to
some of the internal gains consist of radiant heat which is the air, causing water to evaporate into the
partially stored (as described in Chapter 3), thus space. Tables 54 thru 58, pages 107-109
reducing the load to be impressed on the air conditioning provide data for estimating the hear gain from
equipment. these sources.
Generally, internal heat gains consist of some or all of 7. Miscellaneous sources – There may be other
the following items: sources of heat and moisture gain within a
1. People – The human body thru metabolism space, such as escaping steam (industrial
generates heat within itself and releases it by cleaning devices, pressing machines, etc.),
radiation, convection, and evaporation from absorption of water by hygroscopic material
the surface, and by convection and (paper, textiles, etc.); see Chapter 7.
evaporation in the respiratory tract. The In addition to the heat gains from the indoor and
amount of heat generated and released outdoor sources, the air conditioning equipment and duct
depends on surrounding temperature and on system gain or lose heat. The fans and pumps required
the activity level of the person, as listed in to distribute the air or water thru the system add heat;
7
Part 1. Load Estimating | Chapter 1. Building Survey And Load Estimate
heat is also added to supply and return air ducts running HIGH ALTITUDE LOAD CALCULATIONS
thru warner or hot spaces; cold air may leak out of the Since air conditioning load calculations are based on
supply duct and hot air may leak into the return duct. The pounds of air necessary to handle a load, a decrease in
procedure for estimating the heat gains from these density means an increase in cfm required to satisfy the
sources in percentage of room sensible load, room latent given sensible load. The weight of air required to meet
load, and grand total heat load is contained in Chart 3, the latent load is decreased because of the higher latent
page 110, and Tables 59 and 60, pages 111-113. load capacity of the air at higher altitudes (greater gr per
lb per degree difference in dewpoint temperature). For
HEATING LOAD ESTIMATE the same dry-bulb and percent relative humidity, the
The heating load evaluation is the foundation for wetbulb temperature decreases (except at saturation) as
selecting the heating equipment. Normally, the heating the elevation above sea level increases.
load is estimated for the winter design temperatures The following adjustments are required for high
(Chapter 2) usually occurring at night; therefore, no credit altitude load calculations (see Chapter 8, Table 66, page
is taken for the heat given off by internal sources (people, 148):
lights, etc.). This estimate must take into account the heat
loss thru the building structure surrounding the spaces 1. Design room air moisture content must be
and the heat required to offset the outdoor air which may adjusted to the required elevation.
infiltrate and/or may be required for ventilation. Chapter 5 2. Standard load estimating methods and forms
contains the transmission coefficients and procedures for are used for load calculations, except that the
determining heat loss. Chapter 6 contains the data for factors affecting the calculations of volume
estimating the infiltration air quantities. Fig. 2 illustrates a and sensible and latent heat of air must be
heating estimate form for calculating the heat loss in a multiplied by the relative density at the
building structure. particular elevation.
Another factor that may be considered in the 3. Because of the increased moisture content of
evaluation of the heating load is temperature swing. the air, the effective sensible heat factor must
Capacity requirements may be reduced when the be corrected.
temperature within the space is allowed to drop a few
degrees during periods of design load. This, of course, EQUIPMENT SELECTION
applies to continuous operation only. Table 4, page 20, After the load is evaluated, the equipment must be
provides recommended inside design conditions for selected with capacity sufficient to offset this load. The
various applications, and Table 13, page 37, contains the air supplied to the space must be of the proper
data for estimating the possible capacity reduction when conditions to satisfy both the sensible and latent loads
operating in this manner. estimated. Chapter 8, “Applied Psychrometrics,”
The practice of drastically lowering the temperature provides procedures and examples for determining the
to 50 F db or 55 F db when the building is unoccupied criteria from which the air conditioning equipment is
precludes the selection of equipment based on such selected (air quantity, apparatus dewpoint, etc.).
capacity reduction. Although this type of operation may
be effective in realizing fuel economy, additional
equipment capacity is required for pickup. In fact, it may
be desirable to provide the additional capacity, even if
continuous operation is contemplated, because of pickup
required after forced shutdown. It is, therefore, evident
that the use of storage in reducing the heating load for
the purpose of equipment selection should be applied
with care.
8
Part 1. Load Estimating | Chapter 1. Building Survey And Load Estimate
9
Part 1. Load Estimating | Chapter 2. Design Conditions
This chapter presents the data from which the apparatus; use a moisture content corresponding to the
outdoor design conditions are established for various normal design wet-bulb temperature and 80 % rh for
localities and inside design conditions for various selecting the dehumidifier (dehydrator)
applications. The design conditions established Daily range is the average difference between the
determine the heat content of air, both outdoor and high and low dry-bulb temperatures for a 24-hr period
inside. They directly affect the load on the air on a design day. This range varies with local climate
conditioning equipment by influencing the transmission conditions.
of heat across the exterior structure and the difference
in heat content between the outdoor and inside air. For MAXIMUM DESIGN CONDITIONS-SUMMER
further details, refer to Chapters 5 and 6. Maximum summer design conditions are
recommended for laboratories and industrial
OUTDOOR DESIGN CONDITIONS – SUMMER applications where exceeding the room design
AND WINTER conditions for even short periods of time can be
The outdoor design conditions listed in Table 1 are detrimental to a product or process.
the industry accepted design conditions as published The maximum design dry-bulb and wet-bulb
in ARI Std. 530-56 and the 1958 ASHAE Guide. The temperatures are simultaneous peaks (not individual
conditions, as listed, permit a choice of outdoor dry- peaks). The moisture content is an individual peak, and
bulb and wet-bulb temperatures for different types of is listed only for use in the selection of separate cooling
applications as outlined below. and dehumidifying systems for closely controlled
spaces. Each of these conditions can be expected to
NORMAL DESIGN CONDITIONS – SUMMER be exceeded no more than 3 hours in a normal
Normal design conditions are recommended for use summer.
with comfort and industrial cooling applications where
it is occasionally permissible to exceed the design NORMAL DESIGN CONDITIONS – WINTER
room conditions. These outdoor design conditions are Normal winter design conditions are recommended
the simultaneously occurring dry-bulb and wet-bulb for use with all comfort and industrial heating
temperatures and moisture content, which can be applications. The outdoor dry-bulb temperature can be
expected to be exceeded a few times a year for short expected to go below the listed temperatures a few
periods. The dry-bulb is exceeded more frequently times a year, normally during the early morning hours.
than the wet-bulb temperature. And usually when the The annual degree days listed are the sum of all the
wet-bulb is lower than design. days in the year on which the daily mean temperature
When cooling and dehumidification (dehydration) falls below 65 F db, times the number of degrees
are performed separately with these types of between 65 F db and the daily mean temperature.
applications, use the normal design dry-bulb
temperature for selecting the sensible cooling
10
11
12
13
14
15
16
17
18
Part 1. Load Estimating | Chapter 2. Design Conditions
19
equipment. Applications of inherently high sen-sible
The commercial inside design conditions are heat factor (relatively small latent load) usually result in
recommended for general comfort air conditioning the most economical equipment selection if the higher
applications. Since a majority of people are dry-bulb temperatures and lower relative humidities are
comfortable at 75 F or 76 F db and around 45% to 50% used. Applications with low sensible heat factors (high
rh, the thermostat is set to these temperatures, and latent load) usually result in more economical
these conditions are maintained under partial loads. As equipment selection if the lower dry-bulb temperatures
the peak loading occurs (outdoor peak dry-bulb and and higher relative humidities are used.
wet-bulb temperatures, 100% sun, all people and lights,
etc.), the temperature in the space rises to the design INSIDE COMFORT DESIGN CONDITIONS-
point, usually 78 F db. WINTER
If the temperature in the conditioned space is forced For winter season operation, the inside design
to rise, heat will be stored in the building mass. Refer conditions listed in Table 4 are recommended for
to Chapter 3, “Heat Storage, Diversity and general heating applications. With heating, the
Stratification,” for a more complete discussion of heat temperature swing (variation) is below the comfort
storage. With summer cooling, the temperature swing condition at the time of peak heating load (no people,
used in the calculation of storage is the difference lights, or solar gain, and with the minimum outdoor
between the design temperature and the normal temperature). Heat stored in the building structure
thermostat setting. during partial load (day) operation reduces the required
The range of summer inside design conditions is equipment capacity for peak load operation in the same
provided to allow for the most economical selection of manner as it does with cooling.
20
.
INSIDE INDUSTRIAL DESIGN CONDITIONS required conditions and comfort conditions to maintain
Table 5 lists typical temperatures and relative high quality commensurate with low production cost.
humidities used in preparing, processing, and Generally, specific inside design conditions are
manufacturing various products, and for storing both required in industrial applications for one or more of the
raw and finished goods. These conditions are only following reasons:
typical of what has been used, and my vary with
applications. They may also vary as changes occur in 1. A constant temperature level is required for close
processes, products, and knowledge of the effect of tolerance measuring, gaging, machining, or
temperature and humidity. In all cases, the grinding operations, to prevent expansion and
temperature and humidity conditions and the contraction of the machine parts, machined
permissible limits of variations on these conditions products and measuring devices. Normally, a
should be established by common agreement with the constant temperature is more important than the
customer. temperature level. A constant relative humidity is
Some of the conditions listed have no effect on the secondary in nature but should not go over 45% to
product or process other than to increase the efficiency minimize formation of heavier surface moisture film.
of the employee by maintaining comfort conditions. Non-hygroscopic materials such as metals, glass,
This normally improves workmanship and uniformity, plastics, etc., have a property of capturing water
thus reducing rejects and production cost. In some molecules within the microscopic surface crevices,
cases, it may be advisable to compromise between the forming an invisible, non-continuous surface film.
The density of this film increases when relative
21
Part 1. Load Estimating | Chapter 2. Design Conditions
22
23
24
Part 1. Load Estimating | Chapter 3. Heat Storage, Diversity And Stratification
The normal load estimating procedure has been to This degree should be determined by the engineer from
evaluate the instantaneous heat gain to a space and to project requirements and customer desires. A system
assume that the equipment will remove the heat at this so designed, full reduction on refrigeration load and
rate. Generally, it was found that the equipment less than full reduction on air side or room load, meets
selected on this basis was oversized and therefore all of the flexibility requirements, except at time of peak
capable of maintaining much lower room conditions load. In addition, such a system has a low owning and
than the original design. Extensive analysis, research operating cost.
and testing have shown that the reasons for this are:
1. Storage of heat in the building structure. STORAGE OF HEAT IN BUILDING
2. Non-simultaneous occurrence of the peak of STRUCTURES
the individual loads (diversity). The instantaneous heat gain in a typical comfort
3. Stratification of heat, in some cases. application consists of sun, lights, people, transmission
This chapter contains the data and procedures for thru walls, roof and glass, infiltration and ventilation air
determining the load the equipment is actually picking and, in some cases, machinery, appliances, electric
into account the above factors. Application of these calculating machines, etc. A large portion of this
data to the appropriate individual heat gains results in instantaneous heat gain is radiant heat which does not
the actual cooling load. become an instantaneous load on the equipment,
The actual cooling load is generally considerable because it must strike a solid surface and be absorbed
below the peak total instantaneous heat gain, thus by this surface before becoming a load on the
requiring smaller equipment to perform a specific job. equipment. The breakdown on the various
In addition, the air quantities and/or water quantities are instantaneous heat gains into radiant heat and
reduced, resulting in a smaller overall system. Also, as convected heat is approximately as follows:
brought out in the tables, if the equipment is operated
somewhat longer during the peak load periods, and/of RADIANT CONVECTIVE
the temperature in the space is allowed to rise a few HEAT GAIN SOURCE HEAT HEAT
degrees at the peak periods during cooling operation, a Solar, without inside 100% -
further reduction in required capacity results. The blinds
smaller system operating for longer periods at times of Solar, with inside blinds 58% 42%
Fluorescent Lights 50% 50%
peak load will produce a lower first cost to the customer Incandescent Lights 80% 20%
with commensurate lower demand charges and lower People* 40% 20%
operating costs. It is a well-known fact that equipment Transmission† 60% 40%
Infiltration and Ventilation - 100%
sized to more nearly meet the requirements results in a Machinery or 20-80% 80-20%
more efficient, better operating system. Also, if a Appliances‡
smaller system is selected, and is based on extended *The remaining 40% is dissipated as latent load.
periods of operation at the peak load, it results in a †Transmission load is considered to be 100% convective load.
more economical and efficient system at a partially This load is normally a relatively small part of the total load, and
loaded condition. for simplicity is considered to be the instantaneous load on the
Since, in most cases, the equipment installed to equipment.
perform a specific function is smaller, there is less ‡The load from machinery or appliances varies, depending upon
margin for error. This requires more exacting the temperature of the surface. The higher the surface
engineering including air distribution design and temperature, the greater the radiant heat load.
system balancing.
With multi-story, multi-room application, it is usually CONSTANT SPACE TEMPERATURE AND
desirable to provide some flexibility in the air side or EQUIPMENT OPERATING PERIODS
room load to allow for individual room control, load As the radiant heat from sources shown in the
pickup, etc. Generally, it is recommended that the full above table strikes a solid surface (walls, floor, ceiling,
reduction from storage and diversity be taken on the etc.), it is absorbed, raising the temperature at the
overall refrigeration or building load, with some degree surface of the material above that inside the material
of conservatism on the air side or room loads. and the air adjacent to the surface. This temperature
25
Part 1. Load Estimating | Chapter 3. Heat Storage, Diversity And Stratification
difference causes heat flow into the material by Heat Removed from the construction. Since all of the
conduction and into the air by convection. The heat heat coming into a space must be removed, these two
conducted away from the surface is stored, and theheat areas are equal.
convected from the surface becomes an instantaneous The relatively constant light load results in a large
cooling load. The portion of radiant heat being stored portion being stored just after the lights are turned on,
depends on the ratio of the resistance to heat flow into with a decreasing amount being stored the longer the
the material and the resistance to heat flow into the air lights are on, as illustrated in Fig. 4.
film. With most construction materials, the resistance to The upper and lower curves represent the
heat flow into the material is much lower than the air instantaneous heat gain and actual cooling load from
resistance; therefore, most of the radiant heat will be fluorescent lights with a constant space temperature.
stored. However, as this process of absorbing radiant The cross-hatched areas are the Heat Stored and the
heat continues, the material becomes warmer and less Stored Heat Removed from the construction. The
capable of storing more heat. dotted line indicates the actual cooling load for the first
The highly varying and relatively sharp peak of the day if the lights are on longer than the period shown.
instantaneous solar heat gain results in a large part of it Figs. 3 and 4 illustrate the relationship between the
being stored at the time of peak solar heat gain, as instantaneous heat gain and the actual cooling load in
illustrated in Fig. 3. average construction spaces. With light construction,
The upper curve in Fig. 3 is typical of the solar less heat is stored at the peak (less storage capacity
heat gain for a west exposure, and the lower curve is available), and with heavy construction, more heat is
the actual cooling load that results in an average stored at the peak (more storage capacity available), as
construction application with the space temperature shown in Fig. 5. This aspect affects the extent of zoning
held constant. The reduction in the peak heat gain is required in the design of a system for a given building;
approximately 40% and the peak load lags the peak the lighter the building construction, the more attention
heat gain by approximately 1 hour. The cross-hatched should be given to zoning.
areas (Fig. 3) represent the Heat Stored and the Stored The upper curve of Fig. 5 is the instantaneous solar
heat gain while the three lower curves are the actual
cooling load for light, medium and heavy construction
respectively, with a constant temperature in the space.
One more item that significantly affects the
storage of heat is the operating period of the air
conditioning equipment.All of the curves shown
inFigs.3, 4 and 5 illustrate the actual cooling load for
24-hour operation.If the equipment is shut down after
16 hours of operation, some of the stored heat remains
in the building construction. This heat must be removed
(heat in must equal heat out) and will appear as a
FIG. 3-ACTUAL COOLING LOAD, SOLAR HEAT GAIN, pulldown load when the equipment is turned on the
WEST EXPOSURE, AVERAGE CONSTRUCTION next day, as illustrated in Fig. 6.
26
Part 1. Load Estimating | Chapter 3. Heat Storage, Diversity And Stratification
27
Part 1. Load Estimating | Chapter 3. Heat Storage, Diversity And Stratification
The magnitude of the storage effect is determined B. The cooling load at 8 p.m. for the same conditions.
largely by the thermal capacity or heat holding capacity Solution:
of the materials surrounding the space. The thermal The weight per sq ft of floor area of this room (values
capacity of a material is the weight times the specific obtained from Chapter 5) is:
heat of the material. Since the specific heat of most
construction material is approximately 0.20 Btu/ (lb) (F), Outside wall = (20x8) – (16x5) X126lb/sq ft
20x20
the thermal capacity is directly proportional to the
weight of the material. Therefore, the data in the tables (Table 21, page 66)
is based on weight of the materials surrounding the = 25.2 lb/sq ft floor area
space, per square foot of floor area. 20x8x3
Partitions = ½ 20x20 X22lb/sq ft
Use of Tables 7 thru 12 (Table 26, page 70)
Storage Load Factors, = 13.2 lb/sq ft floor area
Solar and Light Heat Gain
12-, 16-, and 24-hour Operation, Floor =½ 20x20 X59lb/sq ft
20x20
Constant Space Temperature
Table 7 thru 11 are used to determine the actual (Table 29, page 73)
coolingload from the solar heat gain with a constant = 29.5 lb/sq ft floor area
temperature maintained within the space for different 20x20
types of construction and periods of operation. With Ceiling = ½ 20x20 X59lb/sq ft
both the 12- and 16-hour factors, the starting time is
assumed to be 6 a.m. suntime (7 a.m. Daylight Saving (Table 29, page 73)
Time). The weight per sq ft of types of construction are = 29.5 lb/sq ft floor area
listed in Tables 21 thru 33, pages 66-76.
The actual cooling load is determined by NOTE: One-half of he partition, floor and ceiling thickness is
multiplying the storage load factor from these tables for used, assuming that the spaces above and below are
any or all times by the peak solar heat gain for the conditioned and are utilizing the other halves for
particular exposure, month and latitude desired. Table storage of heat.
6 is a compilation of the peak solar heat gains for each Total weight per sq ft of floor area
exposure, month and latitude. These values are = 25.2 + 13.2 + 29.5 + 29.5 = 97.4 lb/sq ft.
extracted from Table 15, page 44. The peak solar heat The overall factor for the window with the white venetian blind is
gain is also to be multiplied by either or both the 0.56 (Table 16, page 52) and the correction for steel sash =
applicable over-all factor for shading devices (Table 1/.85.
16, page 52) and the corrections listed under Table 6. A. Storage factor, 4 p.m. = 0.66 (Table 7)
Reduction in solar heat gain from the shading of the The peak solar heat gain for a west exposure in July at 40°
window by reveals and/or overhang should also be North latitude = 164 Btu/(hr)(sq ft), (Table 6).
utilized. Actual cooling load
Example 1 – Actual Cooling Load, Solar Heat Gain = (5 x 16 x 164 x .56 x 1 ) x 0.66 = 5700 Btu/hr
Given: .85
A 20 ft × 20 ft × 8 ft outside office room with 6-inch sand B. Storage factor, 8 p.m. = .20 (Table 7)
aggregate concrete floor, with a floor tile finish, 21/2-inch Actual cooling load
solid sand plaster partitions, no suspended ceiling, and a
12-inch common brick outside wall with 5/8-inch sand = (5 x 16 x 164 x .56 x 1 ) x .20 = 1730
aggregate plaster finish on inside surface. A 16 ft×5 ft .85
steel sash window with a white venetian blind is in the Table 12 is used to determine the actual cooling
outside wall and the wall faces west. load from the heat gain from lights. These data may
Find: also be used to determine the actual cooling load from:
A. The actual cooling load from ths solar heat gain in 1. People – except in densely populated areas
July at 4 p.m., 40° North latitude with the air such as auditoriums, theaters, etc. The radiant
conditioning equipment operating 24 hours during heat exchange from the body is reduced in
the peak load periods and a constant temperature situations like this because there is relatively
maintained within the room.
28
Part 1. Load Estimating | Chapter 3. Heat Storage, Diversity And Stratification
less surface available for the body to radiate maintained at 78 F db with 24-hour operation during the
to. peak load periods.
2. Some appliances and machines that operate Find:
periodically, with hot exterior surfaces such as The actual cooling load at 4 p.m. (with the lights turned on
ovens, dryers, hot tanks, etc. as the people arrive at 8 a.m.).
NOTE: For Items 1 and 2 above, use values listed for Solution:
fluorescent exposed lights. The time elapsed after the lights are turned on is 8 hours (8
a.m. to 4 p.m.).
Example 2 – Actual Cooling Load, Lights and People Storage load factor = .87 (Table 12).
Given: Sensible heat gain from people = 215 Btu/hr
The same room as in Example 1 with a light heat gain of 3 (Table 48, page 100)
watts per sq ft of floor area not including ballast, exposed Actual cooling load
fluorescent lights and 4 people. The room temperature to be = [(3×3.4×1.25×20×20) + (4×215) ] × .87
= 5190 Btu/hr.
29
Part 1. Load Estimating | Chapter 3. Heat Storage, Diversity And Stratification
†Solar heat gain on North exposure (inNorth Latitudes) or on South exposure (in South latitudes) consists primarily of diffuse radiation which is
essentially constant throughout the day. The solar heat gain values for this exposure are the average for the 12 hr period (6 a.m. to 6 p.m.). The
storage factors in Tables 7 thru 11 assume that the solar heat gain on the North (or South) exposure is constant.
30
Part 1. Load Estimating | Chapter 3. Heat Storage, Diversity And Stratification
31
Part 1. Load Estimating | Chapter 3. Heat Storage, Diversity And Stratification
32
Part 1. Load Estimating | Chapter 3. Heat Storage, Diversity And Stratification
*Internal shading device is any type of shade located on the inside of the glass.
†These factors apply when maintaining a CONSTANT TEMPERATURE in the space during the operating period. Where the temperature is
allowed to swing, additional storage will result during peak load periods. Refer to Table 13 for applicable storage factors.
§ Weight per sq ft of floor- (Weight of Outside Walls, lb) + ½ (Weight of Partitions, Floor and Ceiling, lb)
Room on Bldg Exterior (One or more outside walls) =
Floor Area in Room, sq ft
½ (Weight of Partitions, Floor and Ceiling, lb)
Room in Bldg Interior (No outside walls) =
Floor Area in Room, sq ft
(Weight of Outside Walls, lb) + (Weight of Floor, lb) + ½ (Weight of Partitions and Ceiling, lb)
Basement Room (Floor on ground) =
Floor Area in Room, sq ft
(Weight of Outside Wall, Partitons, Floors, Ceilings, Structural Members and Supports,lb)
Entire Building or Zone =
Air Conditioned Floor Area, sq ft
With rug on floor-Weight of floor should be multiplied by 0.50 to compensate for insulating effect of rug.
Weights per sq ft of common types of construction are contained in Tables 21 thru 33, pages 66 thru 76.
33
Part 1. Load Estimating | Chapter 3. Heat Storage, Diversity And Stratification
‡Bare glass-Any window with no inside shading device. Windows with shading devices on the outside or shaded by external projections are
considered bare glass.
†These factors apply when maintaining a CONSTANT TEMPERATURE in the space during the operating period. Where the temperature is
allowed to swing, additional storage will result during peak load periods. Refer to Table 13 for applicable storage factors.
§ Weight per sq ft of floor- (Weight of Outside Walls, lb) + ½ (Weight of Partitions, Floor and Ceiling, lb)
Room on Bldg Exterior (One or more outside walls) =
Floor Area in Room, sq ft
½ (Weight of Partitions, Floor and Ceiling, lb)
Room in Bldg Interior (No outside walls) =
Floor Area in Room, sq ft
(Weight of Outside Walls, lb) + (Weight of Floor, lb) + ½ (Weight of Partitions and Ceiling, lb)
Basement Room (Floor on ground) =
Floor Area in Room, sq ft
(Weight of Outside Wall, Partitons, Floors, Ceilings, Structural Members and Supports,lb)
Entire Building or Zone =
Air Conditioned Floor Area, sq ft
With rug on floor-Weight of floor should be multiplied by 0.50 to compensate for insulating effect of rug.
Weights per sq ft of common types of construction are contained in Tables 21 thru 33, pages 66 thru 76.
34
Part 1. Load Estimating | Chapter 3. Heat Storage, Diversity And Stratification
With rug on floor-Weight of floor should be multiplied by 0.50 to compensate for insulating effect of rug.
Weights per sq ft of common types of construction are contained in Tables 21 thru 33, pages 66 thru 76.
35
Part 1. Load Estimating | Chapter 3. Heat Storage, Diversity And Stratification
24 100 .24 .56 .63 .68 .72 .75 .78 .80 .82 .84 .86 .40 .34 .29 .25 .20 .18 .17 .15 .14 .12 .10 .09 .08
Incandescent Lights.
Ceiling or Exposed
30 .17 .65 .77 .84 .88 .92 .94 .95 .97 .98 .98 .35 .23 .16 .11 .07 .05 .04 .03 .02 .01 .01 0 0
Fluorescent
150 & over .58 .75 .79 .80 .80 .81 .82 .83 .84 .86 .87 .39 .35 .31 .28 .25
16 100 .46 .73 .78 .82 .82 .82 .83 .84 .85 .87 .88 .40 .34 .29 .25 .20
30 .22 .69 .80 .86 .89 .93 .94 .95 .97 .98 .98 .35 .23 .16 .11 .07
150 & over .69 .86 .89 .90 .91 .91 .92 .93 .94 .95 .95 .50
12 100 .58 .85 .88 .88 .90 .92 .93 .94 .94 .94 .95 .48
30 .40 .81 .88 .91 .93 .96 .97 .97 .98 .99 .99 .35
150 & over .23 .33 .41 .47 .52 .57 .61 .66 .69 .72 .74 .59 .52 .46 .42 .37 .34 .31 .27 .25 .23 .21 .18 .16
Fluorescent or Incandescent
Ceiling and Ceiling Plenum
Lights Recessed in Susp.
24 100 .17 .33 .44 .52 .56 .61 .66 .69 .74 .77 .79 .60 .51 .37 .37 .32 .30 .27 .23 .20 .18 .16 .14 .12
30 0 .48 .66 .76 .82 .87 .91 .93 .95 .97 .98 .52 .34 .16 .16 .11 .07 .05 .04 .02 .02 .01 0 0
Return System.
150 & over .57 .64 .68 .72 .73 .73 .74 .74 .75 .76 .78 .59 .52 .42 .42 .37
16 100 .47 .60 .67 .72 .74 .77 .78 .79 .80 .81 .82 .60 .51 .37 .37 .32
30 .07 .53 .70 .78 .84 .88 .91 .93 .95 .97 .98 .52 .34 .16 .16 .11
150 & over .75 .79 .83 .84 .86 .88 .89 .91 .91 .93 .93 .75
12 100 .68 .77 .81 .84 .86 .88 .89 .89 .92 .93 .93 .72
30 .34 .72 .82 .87 .89 .92 .95 .95 .97 .98 .98 .52
†These factors apply when maintaining a CONSTANT TEMPERATURE in the space during the operating period. Where the temperature is
allowed to swing, additional storage will result during peak load periods. Refer to Table 13 for applicable storage factors.
with lights operating the same number of hours as the time of equipment operation, use a load factor of 1.00.
†Lights On for Shorter or Longer Period than 10 Hours 3. Equipment operating for 12 hours:
Occasionally adjustments may be required to take account of lights Follow procedure in Step 2, except in Step 2b add values of 12th
operating less or more than the 10 hours on which the table is based. The hour to that designated 0, 13th hour to the 1st hour, etc.
following is the procedure to adjust the load factors: B-WITH LIGHTS IN OPERATION FOR LONGER PERIOD THAN 10 HOURS
A-WITH LIGHTS IN OPERATION FOR SHORTER PERIOD THAN 10 HOURS and the equipment operating 12, 16 or 24 hours at the time of the overall peak
and the equipment operating 12, 16 or 24 hours at the time of the overall peak load, extrapolate load factors as follows:
load, extrapolate load factors as follows: 1. Equipment operating for 24 hours:
1. Equipment operating for 24 hours: a. Use the load factors as listed through 10th hour and extrapolate
a. Use the storage load factors as listed up to the time the lights are beyond the 10th hour at the rate of the last 4 hours.
turned off. b. Follow the same procedure as in Step 1b of “A” except shift load
b. Shift the load factors beyond the 10th hour (on the right of heavy line) factors beyond 10th hour now to the right, dropping off the last few
to the left to the hour the lights are turned off. This leaves last few hours.
hours of equipment operation without designated load factors. 2. Equipment operating for 16 hours or 12 hours:
c. Extrapolate the last few hours at thee same rate of reduction as the a. Use the load factors in 24-hour equipment operation table as listed
end hours in the table. through 10th hour and extrapolate beyond the 10th hour at the rate of
2. Equipment operating for 16 hours: the last 4 hours.
a. Follow the procedure in Step 1, using the storage load factor values b. Follow the procedure in Step 1b of “A” except shift the load factors
in 24-hour equipment operation table. beyond 10th hour now to the right.
b. Now construct a new set of load factors by adding the new values c. For 16-hour equipment operation, follow the procedure in Steps 2b
for the 16th hour to that denoted 0, 17th hour to the 1st hour, etc. and 2c of “A”.
b. The load factors for the hours succeeding the switching- off the d. For 12-hor equipment operation, follow the procedure in Step 3 of
lights are as in Steps 1b and 1c. “A”.
36
Part 1. Load Estimating | Chapter 3. Heat Storage, Diversity And Stratification
Example
Adjust values for 24-hour equipment operation and derive new values for 16-hour equipment operation for fluorescent lights in operation 8
and 13 hours, and an enclosure of 150 lb/sq ft of floor.
EQUIP WEIGHT§ LIGHTS
OPERATION (lb per sq ft NUMBER OF HOURS AFTER LIGHTS ARE TURNED ON ON
Hours of floor area) 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Hours
.37 .67 .71 .74 .76 .79 .81 .83 .84 .86 .87 .89 .90 .92 .29 .26 .23 .20 .19 .17 .15 .14 .12 .11 13
24 150 .37 .67 .71 .74 .76 .79 .81 .83 .84 .29 .26 .23 .20 .19 .17 .15 .14 .12 .11 .10 .09 .08 .07 .06 8
.37 .67 .71 .74 .76 .79 .81 .83 .84 .86 .87 .29 .26 .23 .20 .19 .17 .15 .14 .12 .11 .10 .09 .08 10
.60 .87 .90 .91 .91 .93 .93 .94 .94 .95 .95 .96 .96 .97 .29 .26 13
16 150 .51 .79 .82 .84 .85 .87 .88 .89 .90 .29 .26 .23 .20 .19 .17 .15 8
.60 .82 .83 .84 .84 .84 .85 .85 .86 .88 .90 .32 .28 .25 .23 .19 10
§ Weight per sq ft of floor- (Weight of Outside Wall, lb) + ½ (Weight of Partitions, Floor and Ceiling, lb)
Room on Bldg Exterior (One or more outside walls) =
Floor Area in Room,sq ft
½(Weight of Partitions, Floor and Ceiling, lb)
Room in Bldg Interior (No outside walls) =
Floor Area in Room,sq ft
(Weight of Outside Wall, lb) + (Weight of Floor, lb) + ½ (Weight of Partitions and Ceiling, lb)
Basement Room (Floor on ground) =
Floor Area in Room,sq ft
(Weight of Outside Wall, Partitions, Floors, Ceilings, Structural Members and Supports, lb)
Entire Building or Zone =
Air Conditioned Floor Area, sq ft
With rug on floor-Weight of floor should be multiplied by 0.50 to compensate for insulating effect of rug.
Weights per sq ft of common types of construction are contained in Tables 21 thru 33, pages 66 thru 76.
SPACE TEMPERATURE SWING The solid curve is the actual cooling load from the
In addition to the storage of radiant heat with a solar heat gain on a west exposure with a constant
constant room temperature, heat is stored in the space temperature, 24-hour operation. Assume that
building structure when the space temperature is the maximum cooling capacity available is represented
forced to swing.If the cooling capacity supplied to the by A, and that the capacity is controlled to maintain a
space matches the cooling load, the temperature in constant temperature at partial load. When the actual
thespace remains constant throughout the operating cooling load exceeds the available cooling capacity,
period. On the other hand, if the cooling capacity the temperature will swing as shown in the lower curve.
supplied to the space is lower than the actual cooling The actual cooling load with temperature swing is
load at any point, the temperature in the space will rise. shown by the dotted line. This operates in a similar
Ad the space temperature increases, less heat is manner with different periods of operation and with
convected from the surface and more radiant heat is different types of construction.
stored in the structure. This process of storing NOTE: When a system is designed for a temperature swing, the
additional heat is illustrated in Fig. 11. maximum swing occurs only at the peak on design days,
which are defined as those days when all loads
simultaneously peak. Under normal operating conditions,
the temperature remains constant or close to constant.
Basis of Table 13
-- Storage Factors,
Space Temperature Swing
The storage factors in Table 13 were computed
FIG. 11-ACTUAL COOLING LOAD WITH VARYING using essentially the same procedure as Tables 7 thru
ROOM TEMPERATURE 12 with the exception that the equipment capacity
37
Part 1. Load Estimating | Chapter 3. Heat Storage, Diversity And Stratification
available was limited and the swing in room directly proportional to the weight of the material.
temperature computed. Therefore, the data in the tables is based on weight of
The magnitude of the storage effect is determined the materials surrounding the space, per square foot of
largely by the thermal capacity or heat holding capacity floor area.
of the materials surrounding the space. It is limited by
the amount of heat available for storage. Load patterns Use of Table 13
for different applications vary approximately as shown -- Storage Factors,
in the first column of Table 13. For instance, an office Space Temperature Swing
building has a rather large varying load with a high Table 13 is used to determine the reduction in
peak that occurs intermittently. An interior zone has an cooling load when the space temperature is forced to
intermittent peak but the load pattern is relatively swing by reducing the equipment capacity below that
constant. A hospital, on the other hand, has a constant required to maintain the temperature constant. This
base load which is present for 24 hours with an reduction is to be subtracted from the room sensible
additional intermittent load occurring during daylight heat.
hours. The thermal capacity of a material is the weight NOTE: This reduction is only taken at the time of peak cooling
times the specific heat of the material. Since the load.
specific heat of most construction material is
approximately 0.20 Btu/(lb)(F), the thermal capacity is
38
Part 1. Load Estimating | Chapter 3. Heat Storage, Diversity And Stratification
Example 3 – Space Temperature Swing theater, etc., where the precooled temperature can be
Given: maintained as the control point and the temperature
The same room as in Example 1, page 28. swing increased to 8 F or 10 F.
Find:
The actual cooling load at 4 p.m. from sun, lights, and DIVERSITY OF COOLING LOADS
people with 3 F temperature swing in the space. Diversity of cooling load results from the probable
Solution: non-occurrence of part of the cooling load on a design
The peak sensible cooling load in this room from the sun, day. Diversity factors are applied to the refrigeration
lights, and people (neglecting transmission infiltration, capacity in large air conditioning systems. These
ventilation and other internal heat gain) is factors vary with location, type and size of the
5700+5190 = 10,890 Btu/hr. (Examples 1 and 2.) application, and are based entirely on the judgment of
NOTE: The peak cooling load in this room occurs at the engineer.
approximately 4 p.m. The solar and light loads are Generally, diversity factors can be applied to people
almost at their peak at 4 p.m. Although the transmission and light loads in large multi-story office, hotel or
across the large glass window peaks at about 3 p.m., the apartment buildings. The possibility of having all of the
peak infiltration and ventilation load also occurs at 3 p.m. people present in the building and all of the lights
and the relatively small transmission load across the wall operating at the time of peak load are slight. Normally,
peaks much later at about 12 midnight. The sum of these in large office buildings, some people will be away from
loads results in the peak cooling load occurring at about the office on other business. Also, the lighting
4 p.m. in the spaces with this exposure. arrangement will frequently be such that the lights in the
The weight of the materials surrounding the room in Example 1 is vacant offices will not be on. In addition to lights being
97.4 lb/sq ft of floor area. off because the people are not present, the normal
Reduction in cooling load for a 3 F swing (Table 13) maintenance procedure in large office buildings usually
= 20 × 20 × 1.4 × 3 = 1680 Btu/hr results in some lights being inoperative. Therefore, a
Cooling load = 10,890 - 1680 = 9210 Btu/hr. diversity factor on the people and light loads should be
(For comparison purposes, the instantaneous heat gain applied for selecting the proper size refrigeration
from sun, lights, and people in this particular room is equipment.
14,610 Btu/hr.) The size of the diversity factor depends on the size
Since the normal thermostat setting is about 75 F or 76 F db, the of the building and the engineer’s judgment of the
design temperature (78 F = 75 F thermostat setting +3 F swinng) circumstances involved. For example, the diversity
occurs only on design peak days at the time of peak load. factor on a single small office with 1 or 2 people is 1.0
Under partial load operation, the room temperature is between or no reduction. Expanding this to one floor of a
75 F db and 78 F db, or at the thermostat setting (75 F), building with 50 to 100 people, 5% to 10% may be
depending on the load. absent at the time of peak load, and expanding to a 20,
30 or 40-story building, 10% to 20% may be absent
PRECOOLING AS A MEANS OF INCREASING during the peak. A building with predominantly sales
STORAGE offices would have many people out in the normal
Precooling a space below the temperature normally course of business.
desired increases the storage of heat at the time of This same concept applies to apartments and
peak load, only when the precooling temperature is hotels. Normally, very few people are present at the
maintained as the control point. This is because the time the solar and transmission loads are peaking, and
potential temperature swing is increased, thus adding the lights are normally turned on only after sundown.
to the amount of heat stored at the time of peak load. Therefore, in apartments and hotels, the diversity factor
Where the space is precooled to a lower temperature can be much greater than with office buildings.
and the control point is reset upward to a comfortable These reductions in cooling load are real and
condition when the occupants arrive, no additional should be made where applicable. Table 14 lists some
storage occurs. In this situation, the cooling unit shuts typical diversity factors, based on judgment and
off and there is no cooling during the period of warming experience.
up. When the cooling unit begins to supply cooling
again, the cooling load is approximately up to the point
it would have been without any precooling.
Precooling is very useful in reducing the cooling
load in applications such as churches, supermarkets,
39
Part 1. Load Estimating | Chapter 3. Heat Storage, Diversity And Stratification
TABLE 14-TYPICAL DIVERSITY FACTORS is about 25% (the rest is radiation); the light load is
FOR LARGE BUILDINGS about 50% with fluorescent (20^ with incandescent),
(Apply to Refrigeration Capacity) and the wall transmission load about 40%.
TYPE OF DIVERSITY FACTOR In any room with a high ceiling, a large part of the
APPLICATION People Lights convection load being released above the supply air
Office .75 to .90 .70 to .85 stream will stratify at the ceiling or roof level. Some will
Apartment, Hotel .40 to .60 .30 to .50 be induced into the supply air stream. Normally, about
Department Store .80 to .90 .90 to 1.0
Industrial* .85 to .95 .80 to .90 80% is stratified and 20% induced in the supply air. If
Equation: air is exhausted through the ceiling or roof, this
Cooling Load (for people and lights), Btu/hr convection load released abovethe supply air may be
= (Heat Gain, Btu/hr, Chapter 7) subtracted from the air conditioning load. This results in
× (Storage Factor, Table 12) ×(Diversity Factor, a large reduction in load if the air is to be exhausted. It
above table) is not normally practical to exhaust more air than
*A diversity factor should also be applied to the machinery load. necessary, as it must be made up by bringing outdoor
Refer to Chapter 7. air through the apparatus. This usually results in a
larger increase in load than the reduction realized by
Use of Table 14 exhausting air.
-- Typical Diversity Factors for Large Buildings Nominally, about a 10 F to 20 F rise in exhaust air
The diversity factors listed in Table 14 are to be temperature may be figured as load reduction if there is
used as a guide in determining a diversity factor for any enough heat released by convection above the supply
particular application. The final factor must necessarily air stream.
be based on judgment of the effect of the many Hot air stratifies at the ceiling event with no exhaust
variables involved. but rapidly builds up in temperature, and no reduction
in load should be taken where air is not exhausted
STRATIFICATION OF HEAT through the ceiling or roof.
There are generally two situations where heat is With suspended ceilings, some of the convective
stratified and will reduce the cooling load on the air heat from recessed lights flows into the plenum space.
conditioning equipment: Also, the radiant heat within the room (sun, lights,
1. Heat may be stratified in rooms with high people, etc.) striking the ceiling warms it up and causes
ceilings where air is exhausted through the roof heat to flow into the plenum space. These sources of
or ceiling. heat increase the temperature of air in the plenum
2. Heat may be contained above suspended space which causes heat to flow into the underside of
ceilings with recessed lighting and/or ceiling the floor structure above. When the ceiling plenum is
plenum return systems used as a return air system, some of the return air flows
The first situation generally applies to industrial through and over the light fixture, carrying more of the
applications, churches, auditoriums, and the like. The convective heat into the plenum space.
second situation applies to applications such as office Containing heat within the ceiling plenum space
buildings, hotels, and apartments. With both cases, the tends to “flatten’ both the room and equipment load.
basic fact that hot air tends to rise makes it possible to The storage factors for estimating the load with the
stratify load such as convection from the roof, above conditions are contained in Table 12.
convection from lights, and convection from the upper
part of the walls. The convective portion of the roof load
40
Part 1. Load Estimating | Chapter 4. Solar Heat Gain Thru Glass
41
Part 1. Load Estimating | Chapter 4. Solar Heat Gain Thru Glass
2. The inside film coefficient is approximately 1.8 Btu/ (hr) (sq NOTE: The sash area equals
ft) (deg F) because, in the average system design, air approximately 85% of the masonry
velocities across the glass are approximately 100-200 fpm. opening (or frame opening with
3. If outdoor temperature is equal to room temperature, the frame walls) with wood sash
glass windows, 90% of masonry
temperature is above both. Therefore absorbed heat opening with double hung metal
sash windows, and 100% of
flowing in = 1.8x100 = 39.2%,or 40% masonry opening with casement
1.8+2.8 windows.
Absorbed heat flowing out = 2.8x100 = 60.8%, or 60%
1.8+2.8 FIG. 14
4. As the outdoor temperature rises, the glass temperature WINDOW AREAS
also irises, causing more of the absorbed heat to flow into
the space. This can be accounted for by adding the 2. No haze in the air.
transmission of heat across the glass (caused by 3. Sea level elevation.
temperature difference between inside and outdoors) to the 4. A sea level dewpoint temperature of 66.8 F (95 F
constant 40% of the absorbed heat going inside. db, 75 F wb) which approximately corresponds
5. This reasoning applies equally well when the outdoor to 4 centimeters of precipitable water vapor.
temperature is below the room temperature. Precipitable water vapor is all of the water vapor
in a column of air from sea level to the outer
Basis of Table 15 edge of the atmosphere.
- Solar heat Gain thru Ordinary Glass If these conditions do not apply, use the correction
Table 15 provides data for 0°, 10°, 20°, 30°, 40°, factors at the bottom of each page of Table 15.
and 50° latitudes, for each month of the year and for
each hour of the day. This table includes the direct and Use of Table 15
diffuse radiation and that portion of the heat absorbed - Solar Heat Gain thru Ordinary Glass
in the glass which gets into the space. It does not The bold face values in Table 15 indicate the
include the transmission of heat across the glass maximum solar heat gain for the month for each
caused by a temperature difference between the exposure. The bold face values that are boxed
outdoor and inside air. (See Chapter 5 for “U” values.) indicate the yearly maximums for each exposure.
The data in Table 15 is based on the following Table 15 is used to determine the solar heat gain
conditions:- thru ordinary glass at any time, in any space, zone or
1. A glass area equal to 85% of the sash area.This building.
is typical for wood sash windows. For metal sash To determine the actual cooling load due to the
windows, the glass area is assumed equal to 100% of solar heat gain, refer to Chapter 3, “Heat Storage,
the sash area because the conductivity of the metal Diversity and Stratification.”
sash is very high and the solar heat absorbed in the
sash is transmitted almost instantaneously. CAUTION – Where Estimation Multi-Exposure Rooms
Or Buildings
If a haze factor is used on one exposure to
determine the peak room or building load, the diffuse
component listed for the other exposures must be
divided by the haze factor to result in the actual room or
building peak load. This is because the diffuse
component increases with increasing haze, as
explained on page 41.
42
Part 1. Load Estimating | Chapter 4. Solar Heat Gain Thru Glass
43
Part 1. Load Estimating | Chapter 4. Solar Heat Gain Thru Glass
44
Part 1. Load Estimating | Chapter 4. Solar Heat Gain Thru Glass
45
Part 1. Load Estimating | Chapter 4. Solar Heat Gain Thru Glass
46
Part 1. Load Estimating | Chapter 4. Solar Heat Gain Thru Glass
47
Part 1. Load Estimating | Chapter 4. Solar Heat Gain Thru Glass
48
Part 1. Load Estimating | Chapter 4. Solar Heat Gain Thru Glass
49
Part 1. Load Estimating | Chapter 4. Solar Heat Gain Thru Glass
°
°
50
Part 1. Load Estimating | Chapter 4. Solar Heat Gain Thru Glass
NOTE: Actually the reaction on the solar heat reflected back 6. Outdoor canvas awnings ventilated at sides and top.
through the glass from the blind is not always identical (See Table 16 footnote).
tot he first pass as assumed in this example. The first 7. Since Table 15 is based on the net solar heat gain
pass through the glass filters out most of solar radiation thru ordinary glass, all calculated solar heat factors
that is to be absorbed in the glass, and the second are divided by .88 (Fig. 12).
pass absorbs somewhat less. For simplicity, the 8. The average absorptivity, reflectivity and
reaction is assumed identical, since the quantities are transmissability for common glass and shading
normally small on the second pass. devices at a 30° angle of incidence along with
shading factors appear in the table below.
Basis of Table 16
Over-all Factors for Solar Heat Gain thru Glass, Use of Table 16
With and Without Shading Devices - Over-all Factors for Solar Heat Gain thru Glass,
The factors in Table 16 are based on: With and Without Shading Devices
1. An outdoor film coefficient of 2.8 Btu/(hr) (sq ft) The factors in Table 16 are multiplied by the values
(deg F) at 5 mph wind velocity. in Table 15 to determine the solar heat gain thru
2. An inside film coefficient of 1.8 Btu/(hr) (sq ft) (deg different combinations of glass and shading devices.
F), 100-200 fpm. This is not 1.47 as normally used, The correction factors listed under Table 15 are to be
since the present practice in well designed used if applicable. Transmission due to temperature
systems is to sweep the window with a stream of difference between the inside and outdoor air must be
air. added to the solar heat gain to determine total gain thru
3. A 30° angle of incidence which is the angle at glass.
which most exposures peak. The 30° angle of Example 3 – Partially Drawn Shades
incidence is approximately the balance point on Occasionally it is necessary to estimate the cooling load in a building
reduction of solar heat coming through the where the blinds are not to be fully drawn. The procedure is illustrated in the
atmosphere and the decreased transmissibility of following example:
glass. Above the 30° angle the transmissibility of Given:
glass decreases, and below the 30° angle the West exposure, 40° North latitude
atmosphere absorbs or reflects more. Thermopane window with white venetian blind on inside, 3 4 drawn.
4. All shading devices fully drawn, except roller Find:
shades. Experience indicates that roller shads are Peak solar heat gain.
seldom fully drawn, so the factors have been Solution:
slightly increased. By inspection of Table 15, the boxed boldface values for peak solar heat
5. Venetian blind slats horizontal at 45° and shading gain, occurring at 4:00 p.m. on July 23
screen slats horizontal at 17°. = 164 Btu/(hr) (sq ft)
*Factors for various draperies are given for guidance only since †Compared to ordinary glass.
the actual drapery material may be different in color and ‡For a shading device in combination with ordinary glass.
texture; figures in parentheses are ounces per sq yd, and yarn
count warp/filling. Consult manufacturers for actual values.
51
Part 1. Load Estimating | Chapter 4. Solar Heat Gain Thru Glass
52
Part 1. Load Estimating | Chapter 4. Solar Heat Gain Thru Glass
53
Part 1. Load Estimating | Chapter 4. Solar Heat Gain Thru Glass
*Factors include correction for no sash with glass block windows. †Use the summer factors for all latitudes, North or South. Use the winter
factor for intermediate seasons, 30° to 50° North or South latitude.
Where:
Equations: Bi = Instantaneous transmission factor from Table 17.
Solar heat gain without shading devices Ba = Absorption transmission factor from Table 17.
= (Bi×li) + (Ba×la) li = Solar heat gain value from Table 15 for the desired time
Solar heat gain with outdoor shading devices and wall facing.
= (Bi×lI+ Ba×la×.25 la = Solar heat gain value from Table 15 for 3 hours earlier than
Solar heat gain with inside shading devices li and same wall facing.
= (Bi×lI+ Ba×la)×.90
54
Part 1. Load Estimating | Chapter 4. Solar Heat Gain Thru Glass
55
Part 1. Load Estimating | Chapter 4. Solar Heat Gain Thru Glass
56
Part 1. Load Estimating | Chapter 4. Solar Heat Gain Thru Glass
57
Part 1. Load Estimating | Chapter 4. Solar Heat Gain Thru Glass
58
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
59
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
60
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
NOTE: The thermal capacity of a wall or roof is the Example 1 – Equivalent Temperature Difference, Roof
density of the material in the wall or roof, times Given:
the specific heat of the material, times the A flat roof exposed to the sun, with built-up roofing,1 1 2 in. insulation,3 in.
volume. wood deck and suspended acoustical tile ceiling.
This progression of heat gain to the interior may Room design temperature = 80 F db
occur over the full 24-hour period, and may result in a Outdoor design temperature = 95 F db
heat gain to the space during the night. If the Daily range = 20 deg F
equipment is operated less than 24 hours, i.e. either Find:
skipping the peak load requirement or as a routine Equivalent temperature difference at 4 p.m. July.
procedure, the peak load requirement or as a routine Solution:
procedure, the nighttime radiation to the sky and the Wt/sq ft = 8 + 2 + 2 = 12 lb/sq ft (Table 27, page 71)
lowering of the outdoor temperature may decrease the Equivalent temperature difference
transmission gain and often may reverse it. Therefore, = 43 deg F (Table 20, interpolated)
the heat gain estimate (sun and transmission thru the
roof and outdoor walls), even with equipment operating Example 2 – Daily Range and Design Temperature Difference
less than 24 hours, may be evaluated by the use of the Correction
equivalent temperature data presented in Tables 19 At times the daily range may be more or less than 20 deg F; the difference
and 20. between outdoor and room design temperatures may be more or less than 15
Basis of Tables 19 and 20 deg F. The corrections to be applied to the equivalent temperature difference
- Equivalent Temperature Difference for Sunlit and for combinations of these two variables are listed in the notes following Tables
Shaded Walls and Roofs 19 and 20.
Table 19 and 20 are analogue computer Given:
calculations using Schmidt’s method based on the The same roof as in Example 1
following conditions: Room design temperature = 78 F db
1. Solar heat in July at 40° North latitude. Outdoor design temperature = 95 F db
2. Outdoor daily range of dry-bulb temperatures, Daily range = 26 deg F
20 deg F. Find:
3. Maximum outdoor temperature of 95 F db and Equivalent temperature difference under changed conditions
a design indoor temperature of 80 F db, i.e. a Solution:
design difference of 15 deg F. Design temperature difference = 17 deg F
4. Dark color walls and roofs with absorptivity of Daily range = 26 deg F
0.90. For light color, absorptivity is 0.50; for Correction to equivalent temperature difference
medium color, 0.70. = -1 deg F (Table 20A, interpolated)
5. Sun time. Equivalent temperature difference = 43 – 1 = 42 deg F
The specific heat of most construction materials is
approximately 0.20 Btu/(lb)(deg F); the thermal Example 3 – Other Months and Latitudes
capacity of typical walls or roofs is proportional to the Occasionally the heat gain thru a wall or roof must be known for months and
weight per sq ft; this permits easy interpolation. latitudes other than those listed in Note 3 following Table 20. This equivalent
temperature difference is determined from the equation in Note 3. This
Use of Tables 19 and 20 equation adjusts the equivalent temperature difference for solar radiation only.
- Equivalent Temperature Difference for Sunlit and Additional correction may have to be made for differences between outdoor
Shaded Wall and Roofs and indoor design temperatures other than 15 deg F. Refer to Tables 19 and
The equivalent temperature differences in Tables 20, pages 62 and 63, and to the correction Table 20A. Corrections for these
19 and 20 are multiplied by the transmission differences must be made first; then the corrected equivalent temperature
coefficients listed in Tables 21 thru 33 to determine the differences for both sun and shade must be applied in corrections for latitude.
heat gain thru walls and roofs per sq ft of area during Given:
the summer. The total weight per sq ft of walls and 12 in. common brick wall facing west, with no interior finish, located in
roofs is obtained by adding the weights per sq ft of New Orleans, 30° North latitude.
each component of a given structure. These weights Find:
and shown in italics and parentheses in Tables 21 thru Equivalent temperature difference in November at 12 noon.
33. Find:
Equivalent temperature difference in November at 12 noon.
61
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
Solution: = 95 – 15 = 80 F
The correction for design temperature difference is as follows: With and 80 F db room design, the outdoor to indoor difference is 80 – 80 = 0
deg F
Example 3, contd Average daily range in New Orleans
Summer design dry-bulb for New Orleans = 13 deg F (Table 1, page 11)
= 95 F db (Table 1, page 11) The design difference of 0 deg F and a 13 deg F daily range results in a –11.5
Winter design dry-bulb for New Orleans deg F addition to the equivalent temperature difference, by interpolation in
= 20 F db (Table 1 page 11) Table 20A.
Yearly range = 75 deg F Equivalent temperature differences for 12 in. brick wall in New Orleans at 12
Correction in outdoor design temperature for November and a noon in November:
yearly range of 75 deg F ∆tem for west wall in sun
= -15 F (Table 3, page 19) = 7 (Table 19)-11.5 = -4.5 deg F
Outdoor design dry-bulb temperature in November at 3 p.m.
62
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
∆te8 for west wall in shade Wt/sq ft of wall = 120 lb/sq ft (Table 21)
= 0 (Table 19) – 11.5 = -11.5 deg F
No correction is needed for the time of day; this is accounted for in ∆tes = - 11.5 deg F as corrected (Table 19 and 20A)
Table 19.
∆tem = - 4.5 deg F as corrected (Table 19 and 20A)
The correction for different solar intensity is
Rs = 116 Btu/hr (Table 15, page 44)
Rs (∆t ∆t ) = Rs ∆t + (1- Rs ) ∆t
∆te = ∆tes +
Rm em es Rm em Rm es Rm = 164 Btu/hr (Table 15, page 44)
∆te = -11.5+ 116
164 [-45-.5-(-11.5)]
= - 6.5 deg F ( Novemder , 12 Noon)
63
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
Corrections to Equivalent Temperature Differences in Tables 19 & ∆te8 = equivalent temperature difference for same wall or roof in
20 for Conditions Other Than Basis of Table shade at desired time of day, corrected if necessary for
1. Outdoor Design Temperature Minus Room Temperature Greater design conditions.
or Less Than 15 deg F db, and/or Daily Range Greater or Less ∆tem = equivalent temperature difference for wall or foof
Than 20 deg F db: exposed to the sun for desired time of day, corrected if
Add the corrections listed in Table 20A, where the outdoor necessary for design conditions.
design temperature (Table 1, page 10) minus the room or indoor R8 = maximum solar heat gain in Btu/(hr) (sq ft) thru glass for
design temperature (table 4, page 20) is different from 15 deg F wall facing or horizontal for roofs, for month and latitude
db, or the daily range is different from the 20 deg F db on which desired, Table 15, page 44, or Table 6, page 29.
Table 19 and 20 are based. Rm = maximum solar heat gain in Btu/(hr)(sq ft) thru glass for
This correction is to be applied to both equivalent temperature wall facing or horizontal for roofs, for July at 40 North
difference values, exposed to sun and shaded walls or roof. latitude, Table 15, page 44, or Table 6, page 29.
2. Shaded walls Example 3 illustrates the procedure.
For shaded walls on any exposure, use the values of equivalent 4. Light or medium color wall or roof
temperature difference listed for north (shade), corrected if Light color wall or roof:
necessary as shown in Correction 1.
3. Latitudes other than 40° North and for other months with different .50 (∆t - ∆t ) = .55 ∆t + .45 ∆t
∆te = ∆tes +
solar intensities. Tables 19 and 20 values are approximately .90 em es em es
correct for the east or west wall in any latitude during the hottest Medium color wall or roof:
weather. In lower latitudes when the maximum solar altitude is
80° to 90° (the maximum occurs at noon), the temperature ∆te = ∆tes + .70 (∆t - ∆t ) = .78 ∆t + .22 ∆t
difference for either south or north wall is approximately the same .90 em es em es
64
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
Note: Light color = white, cream, etc. conditions, the coefficient for summer conditions
Medium color = light green, light blue, gray, etc. will be:
Dark color = dark blue, dark red, dark brown, etc. 1. Thermal resistance R (winter) of wall
5. Other latitude, other month, light or medium color walls or roof.
The combined formulae are: = 1 = 1 = 3.33
U 0.3
Light color walls or roof
Rs ∆tem + (1- .55 Rs ) ∆tes 2. Outdoor film thermal resistance (winter)
∆te = .55 + = 0.17 (Table 34)
Rm Rm 3. Thermal resistance of wall without outdoor air film
(winter = 3.33 – 0.17 = 3.16
Medium color walls or roof. 4. Outdoor film thermal resistance (summer)
Rs ∆tem + (1- .78 Rs ) ∆tes = 0.25 (Table 34)
∆te = .78 + 5. Thermal resistance of wall with outdoor air film
Rm Rm (summer) = 3.16 + 0.25 = 3.41
6. Transmission coefficient U of wall in summer
5. For South latitudes, use the following exposure values from
Table 19: = 1 = 1 = 0.294
R 3.41
South Latitude Use Exposure Value
Northeast Southeast 7. Difference between summer and winter transmission
East East becomes greater with larger U values and less with
Southeast Northeast smaller U values.
South North (shade) Use of Tables 21 thru 33
Southwest Northwest - Transmission Coefficients U for Walls, Roofs, Partitions,
West West Ceilings, floors, Doors, and Windows
Northwest Southwest The transmission coefficients may be used for
North (shade) South calculating the heat flow for both summer and winter
conditions for the average application.
TRANSMISSION COEFFICIENT U Example 4 – Transmission Coefficients
Transmission coefficient or U value is the rate at Given:
which heat is transferred thru a building structure in Btu/ Masonry partition made of 8 in. hollow clay tile, both sides
(hr)(sq ft)(deg F temp diff). The rate times the finished, metal lath plastered on furring with 3 4 in. sand
temperature difference is the heat flow thru the structure. plaster.
The reciprocal of the U value for any wall is the total Find:
resistance of this wall to heat flow to the of heat. The total Transmission coefficient
resistance of any wall to heat flow is the summation of the Solution:
resistance in each component of the structure and the Transmission coefficient U
resistances of the outdoor and inside surface films. The = 0.18 Btu/(hr)(sq ft)(deg F), Table 26, page 70
transmission coefficients listed in Tables 21 thru 33 have Example 5 – Transmission Coefficient, Addition of Insulation
been calculated for the most common types of The transmission coefficients listed in Tables 21 thru 30 do not
construction. include insulation (except for flat roofs, Table 27, page 71).
Frequently, fibrous insulation or reflective insulation is included in
the exterior building structure. The transmission coefficient for the
Basis of Tables 21 thru 33 typical constructions listed in Table 21 thru 30, with insulation, may
- Transmission Coefficients U for Walls, Roofs, Partitions, be determined from Table 31, page 75.
Ceilings, Floors, Doors, and Windows Given:
Table 21 thru 33 contain calculated U values based Masonry wall consisting of 4 in. face brick, 8 in. concrete cinder
on the resistance listed in Table 34, page 78. The block, metal lath plastered on furring with 3 4 in. sand plaster
resistance of the outdoor surface film coefficient for and 3 in. of fibrous insulation in the stud space.
Find:
summer and winter conditions and the inside surface film Transmission coefficient.
is listed in Table 34. Solution:
Note: The difference between summer and winter Refer to Tables 22 and 31.
transmission coefficients for a typical wall is U value for wall without insulation
negligible. For example, with a transmission = 0.24 Btu/(hr)(sq ft)(deg F)
U value for wall with insulation
coefficient of 0.3 Btu/(hr)(sq ft) (F) for winter = 0.07 Btu/(hr)(sq ft)(deg F)
65
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
66
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
67
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
68
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
69
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
70
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
71
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
72
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
73
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
74
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
75
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
76
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
77
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
78
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
79
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
HEAT LOSS THRU BASEMENT WALLS AND Example 7- Heat Loss in a Basement
FLOORS BELOW THE GROUND LEVEL Given:
The loss through the floor is normally small and Basement-100’×40’×9’
relatively constant year round because the ground Basement temp-65 F db, heated continuously
temperature under the floor varies only a little throughout Outdoor temp-o° F db
the year. The ground is a very good heat sink and can Grade line-6 ft above basemen floor
absorb or lose a large amount of heat without an Walls and floors-12 in. concrete (80 lb/cu ft)
appreciable change in temperature at about the 8 ft level. Find:
Above the 8 ft level, the ground temperature varies with Heat loss from basement
the outdoor temperature, with the greatest variation at the Solution:
surface and a decreasing variation down to the 8 ft depth. 1. Heat loss above ground
The heat loss thru a basement wall may be appreciable H = UA1(tb - toa)
and it is difficult to calculate because the ground = 0.18 × (200+80) × 3 × (65-0) = 9828 Btu/hr
temperature varies with depth. Tables 35 thru 37 have 2. Heat loss thru walls and outside strip of floor below ground.
been empirically calculated to simplify the evaluation of H = LpQ (tb - toa)
heat loss thru basement walls and floors. = (200+80) × 1.05 × (65-0) = 19,100 Btu/hr
The heat loss thru a slab floor is large around the 3. Heat loss thru floor
perimeter and small in the center. This is because the H = UA2 (tb - tg)
ground temperature around the perimeter varies with the = 0.05×(100×40) ×(65-55) = 2000 Btu/hr
outdoor temperature, whereas the ground temperature in = 30,928 Btu/hr
the middle remains relatively constant, as with basement
floors. Total Heat Loss
where U = Heat transmission coefficient of wall above
Basis of Tables 35 thru 37 ground (Table 21) and floor (Table 35) in Btu/(hr)
- Heat Loss thru Masonry Floors and Walls in Ground (sq ft) (deg F)
Tables 35 thru 37 are based on empirical data. The A1 = Area of wall above ground, sq ft
perimeter factors listed in Table 36 were developed by A2 = Entire floor area, sq ft
calculating the heat transmitted for each foot of wall to an Lp = Perimeter of wall, ft
8 ft depth. The ground was assumed to decrease the Q = Perimeter factor (Table 36)
transmission coefficient, thus adding resistance between tb = Basement dry-bulb temp, F
the wall and the outdoor air. The transmission tg = Ground temp, F, (Table 37)
coefficients were then added to arrive at the perimeter toa = Outdoor design dry-bulb temp, F
factors.
TABLE 35-TRANSMISSION COEFFICIENT U-
Use of Tables 35 thru 37 MASONRY FLOORS AND WALLS IN GROUND
- Heat Loss thru Masonry Floors and Walls in Ground (Use only in conjunction with Table 36)
The transmission coefficients listed in Table 35 may Transmission
be used for any thickness of uninsulated masonry floors Floor or Wall Coefficient U
Btu/(hr) (sq ft) (deg f)
where there is good contact between the floor and the *Basement Floor .05
ground. Portion of Wall
The perimeter factors listed in Table 36 are used for exceeding 8 feet .08
below ground level
estimating heat loss thru basement walls and the outside
strip of basement floors. This factor can be used only *Some additional floor loss is included in perimeter factor, see
when the space is heated continuously. If there is only Table 36.
occasional heating, calculate the heat loss using the wall Equations:
or floor transmission coefficients as listed in Tables 21 Heat loss through floor, Btu/hr = (area of floor, sq ft)
thru 33 and the temperature difference between the × (U value) × (basement-ground temp).
basement and outdoor air or ground as listed in Table 37. Heat loss through wall below 8 foot line, Btu/hr
The heat loss in a basement is determined by adding = (area of wall below 8 ft line, sq ft) × (U value)
the heat transferred thru the floor, the walls and the × (basement-ground temp).
outside strip of the floor and the portion of the wall above
the ground level.
80
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
NOTE: The factors in Tables 35 and 36 may be used for any TRANSMISSION COEFFICIENTS-
thickness of uninsulated masonry wall or floor, but there must be a PIPES IN WATER OR BRINE
good contact (no air space which may connect to the outdoors) Heat transmission coefficients for copper and steel
between the ground and the floor or wall. Where the ground is dry pipes are listed in Tables 38 and 39. These coefficients
and sandy, or where there is cinder fill along wall or where the wall may be useful in applications such as cold water or brine
has a low heat transmission coefficient, the perimeter factor may be storage systems and ice skating rinks.
reduced slightly.
Basis of Tables 38 and 39
TABLE 36-PERIMETER FACTORS - Transmission coefficients, Pipes in Water or Brine
FOR ESTIMATING HEAT LOSS THROUGH BASEMENT WALLS Table 38 is for ice coated pipes in water, based on a
AND OUTSIDE STRIP OF BASEMENT FLOOR heat transfer film coefficient, inside the pipe, of 150 Btu/
(Use only in conjunction with Table 35) (hr)(sq ft internal pipe surface)(deg F).
Distance of Floor Perimeter Factor Table 39 is for pipes in water or brine based on a heat
From Ground Level (q) transfer of 18 Btu/(hr)(sq ft external pipe surface) (deg F)
2 Feet above .90
At ground level .60 in water, 14 Btu in brine. It is also based on a low rate of
2 Feet below .75 circulation on the outside of the pipe and 10 F to 15 F
4 Feet below .90 temperature difference between water or brine and
6 Feet below 1.05
8 Feet below 1.20 refrigerant. High rates of circulation will increase the heat
Equations: transfer rate. For special problems, consult heat transfer
Heat loss about perimeter, Btu/hr = (perimeter of wall, ft) reference books.
× (perimeter factor) × (basement-outdoor temp).
81
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
82
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
83
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
84
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
CONDENSATION OF WATER VAPOR Concealed condensation may cause wood, iron and
Whenever there is a difference of temperature and brickwork to deteriorate and insulation to lose its
pressure of water vapor across a structure, conditions insulating value. These effects may be corrected by the
may develop that lead to a condensation of moisture. following methods:
This condensation occurs at the point of saturation 1. Provide vapor barriers on the high vapor pressure
temperature and pressure. side.
2. In winter, ventilate the building to reduce the vapor
As water vapor flows thru the structure, its pressure within. No great volume of air change is
temperature decreases and, if at any point it reaches the necessary, and normal infiltration alone is frequently
dewpoint or saturation temperature, condensation begins. all that is required.
As condensation occurs, the vapor pressure decreases, 3. In winter, ventilate the structure cavities to remove
thereby lowering the dewpoint or saturation temperature vapor that has entered. Outdoor air thru vents
until it corresponds to the actual temperature. The rate at shielded from entrance of rain and insects may be
which condensation occurs is determined by the rate at used.
which heat is removed from the point of condensation. Condensation may also form on the surface of a
As the vapor continues to condense, latent heat of building structure. Visible condensation occurs when the
condensation is released, causing the dry-bulb surface of any material is colder than the dewpoint
temperature of the material to rise. temperature of the surrounding air. In winter, the
To illustrate this, assume a frame wall with wood condensation may collect on cold closet walls and attic
sheathing and shingles on the outside, plasterboard on roofs and is commonly observed as frost on window
the inside and fibrous insulation between the two. Also, panes. Fig. 29 illustrates the condensation on a window
assume that the inside conditions are 75 F db and 50% rh with inside winter design conditions of 70 F db and 40%
and the outdoor conditions are 0° F db and 80% rh. Refer rh. Point A represents the room conditions; point B, the
to Fig. 28. dewpoint temperature of the thin film of water vapor
The temperature and vapor pressure gradient adjacent to the window surface; and point C, the point at
decreases approximately as shown by the solid and which frost or ice appears on the window.
dashed lines until condensation begins (saturation point). Once the temperature drops below the dewpoint, the
At this point, the latent heat of condensation decreases vapor pressure at the window surface is also reduced,
the rate of temperature drop thru the insulation. This is thereby establishing a gradient of vapor pressure from
approximately indicated by the dotted line. the room air to the window surface. This gradient
Another cause of concealed condensation may be operates, in conjunction with the convective action within
evaporation of water from the ground or damp locations. Tive action within the room, to move water vapor
This water vapor may condense on the underside of the continuously to the window surface to be condensed, as
floor joints (usually near the edges where it is coldest) or long as the concentration of the water vapor is maintained
may flow up thru the outdoor side of the walls because of in a space.
stack effect and/or vapor pressure differences.
85
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
86
Part 1. Load Estimating | Chapter 5. Heat And Water Vapor Flow Thru Structures
87
Part 1. Load Estimating | Chapter 6. Infiltration And Ventilation
88
Part 1. Load Estimating | Chapter 6. Infiltration And Ventilation
In low buildings, air infiltrates thru open doors on the Use of Table 41
windward side unless sufficient outdoor air is introduced - Infiltration thru Windows and Doors, Summer
thru the air conditioning equipment to offset it; refer to The data in Table 41 is used to determine the
“Offsetting Infiltration with Outdoor Air.” infiltration thru windows and doors on the windward side
With doors on opposite walls, the infiltration can be with the wind blowing directly at them. When the wind
considerable if the two are open at the same time. direction is oblique to the windows or doors, multiply the
values in Tables 41a, b, c, d, by 0.60 and apply to total
Basis of Table 41 areas. For specific locations, adjust the values in Table
- Infiltration thru Windows and Doors, Summer 41 to the design wind velocity; refer to Table 1, page 10.
The data in Tables 41a, b and c is based on a wind During the summer, infiltration is calculated for the
velocity of 7.5 mph blowing directly at the window or windward side(s) only, because stack effect is small and,
door, and on observed crack widths around typical therefore, causes the infiltration air to flow in a downward
windows and doors. This data is derived from Table 44 direction in tall buildings (over 100 ft). Some of the air
which lists infiltration thru cracks around windows and infiltrating thru the windows will exfiltrate thru the windows
doors as established by ASHAE tests. on the leeward side(s), while the remaining infiltration air
Table 41d shows values to be used for doors on flows out the doors, thus offsetting some of the infiltration
opposite walls for various percentages of time that each thru the doors. To determine the net infiltration thru the
door is open. doors, determine the infiltration thru the windows on the
The data in Table 41e is based on actual tests of windward side, multiply this by .80, and subtract from the
typical applications. door infiltration. For low buildings the door infiltration on
the windward side should be included in the estimate.
89
Part 1. Load Estimating | Chapter 6. Infiltration And Ventilation
90
Part 1. Load Estimating | Chapter 6. Infiltration And Ventilation
91
Part 1. Load Estimating | Chapter 6. Infiltration And Ventilation
INFILTRATION THRU WINDOWS AND DOORS, and west sides will allow infiltration but the wind is only 60%
WINTER effective. Correction for wind direction is .6.
Infiltration thru windows and doors during the winter Since this building is over 100 ft tall, stack effect causes infiltration
is caused by the wind velocity and also stack effect. The on all sides at the lower levels and exfiltration at the upper levels.
temperature differences during the winter are The total infiltration on the windward sides remains the same
considerably greater than in summer and, therefore, the because the increase at the bottom is exactly equal to the
density difference is greater; at 75 F db and 30% rh, decrease at the top. (For a floor-by-floor analysis, use equivalent
density is .0738; at 0° F db, 40% rh, density is .0865. wind velocity formulas.) Infiltration thru windows on the windward
Stack effect causes air to flow in at the bottom and out at sides of the lower levels
the top, and in many cases requires spot heating at the = 12,000 × 2× 1.12 × .6× .98 = 15,810 cfm.
doors on the street level to maintain conditions. In The total infiltration thru the windows on the leeward sides of the
applications where there is considerable infiltration on the building is equal to the difference between the equivalent velocity
street level, much of the infiltration thru the windows in the at the first floor and the design velocity at the midpoint of the
upper levels will be offset. building.
Ve = √ V2 + 1.75b
Basis of Table 43
- Infiltration thru Windows and Doors, Winter = √ (16.8)2 + (1.75 x 240 ) = 22.2 mph
The data in Table 43 is based on a wind velocity of 2
15 mph blowing directly at the window or door and on Ve – V = 22.2 – 16.8 = 5.4 mph
observed crack widths around typical windows and Total infiltration thru windows in lower half of building (upper half is
doors. The infiltration thru these cracks is calculated from exfiltration) on leeward side
Table 44 which is based on ASHAE tests. = 12,000 × 2 × 1/2 × (5.4/15) × 1/2 ×.98
= 2160 cfm (Table 43)
Use of Table 43
- Infiltration thru Windows and Doors, Winter NOTE: This is the total infiltration thru the windows on the
Table 43 is used to determine the infiltration of air leeward side. A floor-by-floor analysis should be made to
thru windows and doors on the windward side during the balance the system to maintain proper conditions on
winter. The stack effect in tall buildings increases the each floor.
infiltration thru the doors and windows on the lower levels (on leeward side)
and decreases it on the upper levels. Therefore, = 10 ×7 × 3 × (5.4/15) × 30
whenever the door infiltration is increased, the infiltration = 2310 cfm (Table 43c, average use, 1 and 2 story
thru the upper levels must be decreased by 80% of the building).
net increase in door infiltration. The infiltration from stack
effect on the leeward sides of the building is determined Example 4-Offsetting Infiltration with Outdoor Air
by using the difference between the equivalent velocity Any outdoor air mechanically introduced into the building offsets
(Ve) and the actual velocity (V) as outlined in Example 3. some of the infiltration. In Example 3 all of the outdoor air is
The data in Table 43 is based on the wind blowing effective in reducing the window infiltration. Infiltration is reduced
directly at the windows and doors. When the wind on two windward sides, and the air introduced thru the apparatus
direction is oblique to the windows and doors, multiply exfiltrates thru the other two sides.
the values by 0.60 and use the total window and door
area on the windward sides. Given:
The building described in Example 1 with .25 cfm/sq ft
Example 3-Infiltration in Tall Buildings, Winter supplied thru the apparatus and 40,000 cfm being exhausted
Given: from the building.
The building described in Example 1. Find:
Find: The net infiltration into this building.
The infiltration thru the doors and windows. Solution:
Solution: Net outdoor air = (.25×10,000×20)-40,000 = 10,000 cfm
The prevailing wind in New York City during the winter is NW Net infiltration thru windows
at 16.8 mph (Table 1, page 10) = 15,800+2160-10,000 = 7970 cfm
Correction on Table 43 for wind velocity is 16.8/15= 1.12. Since Net infiltration thru doors = 2310 cfm (Example 3)
the wind is coming from the Northwest, the crackage on the north Net infiltration into building = 7970+2310 = 10,280 cfm
92
Part 1. Load Estimating | Chapter 6. Infiltration And Ventilation
93
Part 1. Load Estimating | Chapter 6. Infiltration And Ventilation
94
Part 1. Load Estimating | Chapter 6. Infiltration And Ventilation
95
Part 1. Load Estimating | Chapter 6. Infiltration And Ventilation
Example 6-Ventilation Air Quantity, Office Space 500 cfm will more than likely not maintain satisfactory conditions
within the space because the number of smokers is
Given: considerable. Therefore, 750 cfm should be used in this
A 5000 sq ft office with a ceiling height of 8 ft and 50 people. application.
Approximately 40% of the people smoke.
Find: NOTE: Many applications have exhaust fans. This means that the
The ventilation air quantity. outdoor air quantity must at least equal the exhausted air;
otherwise the infiltration rate will increase. Tables 46 and
Solution: 47 list the approximate capacities of typical exhaust fans.
The population density is typical, 100 sq ft per person, but the The data in these tables were obtained from published
number of smokers is considerable. ratings of several manufacturers of exhaust fans.
Recommended ventilation = 50 × 15 = 750 cfm (Table 45)
Minimum ventilation = 50 × 10 = 500 cfm (Table 45)
96
Part 1. Load Estimating | Chapter 6. Infiltration And Ventilation
97
Part 1. Load Estimating | Chapter 7. Internal And System Heat Gain
98
Part 1. Load Estimating | Chapter 7. Internal And System Heat Gain
99
Part 1. Load Estimating | Chapter 7. Internal And System Heat Gain
100
Part 1. Load Estimating | Chapter 7. Internal And System Heat Gain
Use of Tables 50 thru 52 The values in Tables 50 thru 52 are for unhooded
- Heat Gain from Restaurant Appliances and appliances. If the appliance has a properly designed
- Miscellaneous Appliances positive exhaust hood, reduce the sensible and the latent
The Maintaining Rate is the heat generated when the heat gains by 50%. A hood, to be effective, should extend
appliance is being maintained at operating temperature beyond the appliance approximately 4 inches per foot of
but not being used. height between the appliance and the face of the hood.
The Recommended for Average Use values are those The lower edge should not be higher than 4 feet above
which the appliance generates under normal use. These the appliance and the average face velocity across the
appliances seldom operate at maximum capacity during hood should not be less than 70 fpm.
peak load since they are normally warmed up prior to the
peak.
101
Part 1. Load Estimating | Chapter 7. Internal And System Heat Gain
102
Part 1. Load Estimating | Chapter 7. Internal And System Heat Gain
103
Part 1. Load Estimating | Chapter 7. Internal And System Heat Gain
load is normally a major portion of the cooling When the machine is outside the conditioned space,
load. multiply the watts by one minus the motor efficiency and
by the factor 3.4.
When reading are obtained directly in watts and Although the results are less accurate, it may be
when both motors and driven machines are in the air expedient to obtain power input measurements using a
conditioned space, the heat gain is equal to the number clamp-on ammeter and voltmeter. These instruments
of watts times the factor 3.4 Btu/(watt)(hr). permit instantaneous readings only. They afford means
When the machine is in the conditioned space and for determining the load factor but the usage factor must
the motor outside, multiply the watts by the motor be obtained by a careful investigation of the operating
efficiency and by the factor 3.4 to determine heat gain to conditions.
the space.
TABLE 53-HEAT GAIN FROM ELECTRIC MOTORS
CONTINUOUS OPERATION*
LOCATION OF EQUIPMENT WITH RESPECT TO
CONDITIONED SPACE OR AIR STREAM‡
NAMEPLATE† FULL LOAD Motor In- Motor Out- Motor In-
OR MOTOR Driven Machine in Driven Machine in Driven Machine out
BRAKE EFFICIENCY HP×2545 HP×2545 HP×2545 (1-% Eff)
HORSEPOWER PERCENT % Eff % Eff
1
Btu per Hour
/
1 20
40 320 130 190
/
1 12
49 430 210 220
18
/ 55 580 320 260
/1 6 60 710 430 280
1
/4 64 1,000 640 360
13
/ 66 1,290 850 440
/3 2 70 1,820 1,280 540
/4 72 2,680 1,930 750
11 79 3,220 2,540 680
1 /2 80 4,770 3,820 950
2 80 6,380 5,100 1,280
3 81 9,450 7,650 1,800
51 82 15,600 12,800 2,800
7 /2 85 22,500 19,100 3,400
10 85 30,000 25,500 4,500
15 86 44,500 38,200 6,300
20 87 58,500 51,000 7,500
25 88 72,400 63,600 8,800
30 89 85,800 76,400 9,400
40 89 115,000 102,000 13,000
50 89 143,000 127,000 16,000
60 89 172,000 153,000 19,000
75 90 212,000 191,000 21,000
100 90 284,000 255,000 29,000
125 90 354,000 318,000 36,000
150 91 420,000 382,000 38,000
200 91 560,000 510,000 50,000
250 91 700,000 636,000 64,000
*For intermittent operation, an appropriate usage factor should be used, preferably measured.
† If motors are overloaded and amount of overloading is unknown, multiply the above heat gain factors by the following
maximum service factors:
Maximum Service Factors
1
Horsepower /20 - 1/8 1
/6 - 1/3 1
/2 - 3/4 1 1 1/2 - 2 3 - 250
AC Open Type 1.4 1.35 1.25 1.25 1.20 1.15
DC Open Type -- -- -- 1.15 1.15 1.15
No overload is allowable with enclosed motors
‡For a fan or pump in air conditioned space, exhausting air and pumping fluid to outside of space, use values in last column.
104
Part 1. Load Estimating | Chapter 7. Internal And System Heat Gain
The following is a conversion table which can be the circuit from an outside source, the heat gain to the
used to determine load factors from measurements: water
3 × (58,500 - 7500) = 153,000 Btu/hr
TO FIND HP KILOWATTS would become a load on this outside source.
→ OUTPUT INPUT
Direct I×E×eff I×E
Current 746 1,000 PIPING, TANKS AND EVAPORATION OF WATER
1 I×E×pf×eff I×E×pf FROM A FREE SURFACE
Phase 746 1,000 Hot pipes and tanks add sensible heat to a space by
3 or 4 Wire I×E×pf×eff×1.73 I×E×pf×1.73
3 Phase 746 1,000 convection and radiation. Conversely, cold pipes remove
4 Wire I×E×pf×eff×2 I×E×2×pf sensible heat. All open tanks containing hot water
2 Phase 746 1,000 contribute not only sensible heat but also latent heat due
Where I = amperes eff = efficiency to evaporation.
E = volts pf = power factor In industrial plants, furnaces or dryers are often
NOTE: For 2 phase, 3 wire circuit, common conductor current encountered. These contribute sensible heat to the space
is 1.41 times that in either of the other two conductors. by convection and radiation from the outside surfaces,
Example 3-Electric Motor Heat Gain in a Factory and frequently dryers also contribute sensible and latent
(Motor Bhp Established by a Survey) heat from the drying process.
Given:
1. Forty-five 10 hp motors operated at 80% rated capacity, Basis of Tables 54 thru 58
driving various types of machines located within air - Heat Gain from Piping, Tanks and Evaporation of
conditioned space (lathes, screw machines, etc.). Water
Five 10 hp motors operated at 80% rated capacity, driving Table 54 is based on nominal flow in the pipe and a
screw machines, each handling 5000 lbs of bronze per hr. convection heat flow from a horizontal pipe of--
Both the final product and the shaving from the screw
machines are removed from the space on conveyor belts. 1 ).2X ( 1 ).181
Rise in bronze temperature is 30 F; sp ht is .01 Btu/(lb) (F). 1.016 X ( Dia T1
2. Ten 5 hp motors (5 bhp) driving fans, exhausting air to the
outdoors. × (temp diff between hot water or steam and
3. Three 20 hp motors (20 bhp) driving process water pumps, room).
water discarded outdoors. The radiation from horizontal pipes is expressed by-
Find:
Total heat gain from motors. 17.23 x 10–10 x emissivity x (T1 4 – T2 4 )
Solution:
Use Table 53. Sensible Heat Gain where T1 = room surface temp, deg R
Btu/hr
1. Machines-Heat gain to space T2 = pipe surface temp, deg R
= 45 × 30,000 × .80= 1,080,000 Tables 55 and 56 are based on the same equation
Heat gain from screw machines and an insulation resistance of approximately 2.5 per inch
= 5 × 30,000 × .80 = 120,000 Btu/hr of thickness for 85% magnesia and 2.9 per inch of
Heat removed from space from thickness with moulded type.
screw machine work Caution: Table 55 and 56 do not include an allowance
= 5000 × 5 × 30 × .01 = 7,500 Btu/hr for fittings. A safety factor of 10% should be
Net heat gain from screw machines added for pipe runs having numerous fittings.
to space Table 57 is based on an emissivity of 0.9 for painted
= 120,000 – 7500 = 112,500 metal and painted or bare wood and concrete. The
2. Fan exhausting air to the outdoors: emissivity of chrome, bright nickel plate, stainless steel,
Heat gain to space = 10 × 2800 = 28,000 or galvanized iron is 0.4. The resistance (r) of wood is
3. Process water pumped to outside 0.833 per inch and of concrete 0.08 per inch. The metal
air conditioned space surface temperature has been assumed equal to the
Heat gain to space =3 × 7500 22,500 water temperature.
Total heat gain from motors on NOTE: The heat gain from furnaces and ovens can be
machines, fans, and pumps = 1,243,000 estimated from Table 57, using the outside
NOTE: If the process water were to be recirculated and cooled in temperature of furnace and oven.
105
Part 1. Load Estimating | Chapter 7. Internal And System Heat Gain
106
Part 1. Load Estimating | Chapter 7. Internal And System Heat Gain
107
Part 1. Load Estimating | Chapter 7. Internal And System Heat Gain
SYSTEM HEAT GAIN Correction factors for different room temperatures, duct
The system heat gain is considered as the heat velocities and temperature differences are included
added to or lost by the system components, such as the below Chart 3. Values are plotted for use with
ducts, piping, air conditioning fan, and pump, etc. This uninsulated, furred and insulated ducts.
heat gain must be estimated and included in the load
estimate but can be accurately evaluated only after the Use of Chart 3
system has been designed. -- Percent Room Sensible Heat to be Added for Heat
Gain to Supply Duct
SUPPLY AIR DUCT HEAT GAIN To use this chart, evaluate the length of duct running
The supply duct normally has 50 F db to 60 F db air thru the unconditioned space, the temperature of
flowing through it. The duct may pass through an unconditioned space, the duct velocity, the supply air
unconditioned space having a temperature of, say, 90 F temperature, and room sensible heat subtotal.
db and up. This results in a heat gain to the duct before it
reaches the space to be conditioned. This, in effect, Example 5- Heat Gain to Supply Duct
reduces the cooling capacity of the conditioned air. To Given:
compensate for it, the cooling capacity of the air quantity 20 ft of uninsulated duct in unconditioned space at 100 F db
must be increased. It is recommended that long runs of Duct velocity – 2000 fpm
ducts in unconditioned spaces be insulated to minimize Supply air temperature – 60 F db
heat gain. Room sensible heat gain – 100,000 Btu/hr
Find:
Basis or Chart 3 Percent addition to room sensible heat
- Percent Room Sensible Heat to be Added for Heat Solution:
Gain to Supply Duct The supply air to unconditioned space temperature difference
Chart 3 is based on a difference of 30 F db between = 100 – 60 = 40 F db
supply air and unconditioned space, a supply duct From Chart 3, percent addition = 4.5%
velocity of 1800 fpm in a quare duct, still air on the Correction for 40 F db temperature difference and 2000 fpm
outside of the duct and a supply air rise of 17 F db. duct velocity = 1.26
Actual percent addition = 4.5 × 1.26 = 5.7%
108
Part 1. Load Estimating | Chapter 7. Internal And System Heat Gain
SUPPLY AIR DUCT LEAKAGE LOSS greatest variable, and duct leakages from 5% to 30%
Air leakage from the supply duct may be a serious have been found. The following is a guide to the
loss of cooling effect, except when it leaks into the evaluation of duct leakages under various conditions:
conditioned space. This loss of cooling effect must be 1. Bare ducts within conditioned space-usually
added to the room sensible and latent heat load. not necessary to figure leakage.
Experience indicates that the average air leakage 2. Furred or insulated ducts within conditioned
from the entire length of low velocity supply ducts, space-a matter of judgment, depending on
whether large or small systems, averages around 10% of whether the leakage air actually gets into the
the supply air quantity. Smaller leakage per foot of length room.
for larger perimeter ducts appears to be counterbalanced
by the longer length of run. Individual workmanship is the
109
Part 1. Load Estimating | Chapter 7. Internal And System Heat Gain
TABLE 59- HEAT GAIN FROM AIR CONDITIONING FAN HORSEPOWER, DRAW-THRU SYSTEM‡‡
FAN CENTRAL STATION SYSTEMS‡ APPLIED OR UNITARY SYSTEM**
TOTAL
PRESSURE† Temp Diff Temp Diff
(In. Room to Supply Air Room to Supply Air
of Water) 10 F 15 F 20 F 25 F 30 F 10 F 15 F 20 F 25 F 30 F
PERCENT OF ROOM SENSIBLE HEAT*
0.50 1.2 0.8 0.6 0.5 0.4 2.2 1.5 1.1 0.9 0.7
0.75 1.9 1.3 1.0 0.8 0.6 3.5 2.4 1.8 1.4 1.2
1.00 2.7 1.8 1.4 1.1 0.9 4.8 3.2 2.4 1.9 1.6
Fan Motor 1.25 3.9 2.6 1.9 1.6 1.3 6.5 4.3 3.2 2.6 2.2
Not in 1.50 4.6 3.1 2.3 1.9 1.6 7.8 5.2 3.9 3.1 2.6
Conditioned 1.75 5.4 3.6 2.7 2.2 1.8 9.1 6.1 4.6 3.6 3.0
Space 2.00 6.2 4.1 3.1 2.5 2.1 10.4 6.9 5.2 4.2 3.5
or 3.00 10.4 6.9 5.2 4.2 3.5 16.7 11.2 8.4 6.7 5.6
Air Stream 4.00 15.3 10.2 7.7 6.1 5.1
5.00 19.2 12.8 9.6 7.7 6.4
6.00 24.4 16.3 12.2 9.9 8.2
8.00 38.0 25.4 19.0 15.2 12.7
0.50 1.6 1.1 0.8 0.6 0.5 2.7 1.8 1.4 1.1 0.9
0.75 2.6 1.8 1.3 1.1 0.9 4.2 2.8 2.1 1.7 1.4
1.00 3.6 2.4 1.8 1.5 1.2 5.8 3.8 2.9 2.3 1.9
Fan Motor†† 1.25 5.0 3.4 2.5 2.0 1.7 7.6 5.1 3.8 3.1 2.6
in 1.50 6.0 4.0 3.0 2.4 2.0 9.2 6.1 4.6 3.7 3.1
Conditioned 1.75 7.0 4.7 3.5 2.8 2.4 10.7 7.2 5.4 4.3 3.6
Space 2.00 8.0 5.4 4.0 3.2 2.7 12.2 8.2 6.1 4.9 4.1
or 3.00 13.2 8.8 6.6 5.3 4.4 19.5 13.1 9.8 7.8 6.5
Air Stream 4.00 19.0 12.7 9.5 7.6 6.4
5.00 23.8 15.9 11.9 9.5 8.0
6.00 30.0 20.0 15.0 12.0 10.0
8.00 45.5 30.3 22.8 18.2 15.2
*Excludes from heat gain, typical values for bearing losses, etc. which are dissipated in apparatus room.
†Fan Total Pressure equals fan static pressure plus velocity pressure at fan discharge. Below 1200 fpm the fan total pressure
is approximately equal to the fan static. Above 1200 fpm the total pressure should be figured.
‡70% fan efficiency assumed.
**50% fan efficiency assumed.
††80% motor and drive efficiency assumed.
‡‡For draw-thru systems, this heat is an addition to the supply air heat gain and is added to the room sensible heat. For
blow-thru systems this fan heat is added to the grand total heat; use the RSH times the percent listed and add to the GTH.
3. All ducts outside the conditioned space- heat. With blow-through systems (fan blowing air through
assume 10% leakage. This leakage is a total the coil, etc.) the fan heat added is a load on the
loss and the full amount must be included. dehumidifier and, therefore, should be added to the
When only part of the supply duct is outside grand total heat (see “Percent Addition to Grand Total
the conditioned space, include that fraction of Heat”).
10% as the leakage. (Fraction is ratio of length
outside of conditioned space to total length of Basis of Table 59
supply duct.) Heat Gain from Air Conditioning Fan Horsepower
High velocity systems usually limit leakage to 1%. The air conditioning fan adds heat to the system in
the following manner:
HEAT GAIN FROM AIR CONDITIONING 1. Immediate temperature rise in the air due to
FAN HORSEPOWER the inefficiency of the fan.
The inefficiency of the air conditioning equipment fan 2. Energy gain in the air as a pressure and/or
and the heat of compression adds heat to the system as velocity rise.
described under “Electric Motors.” In the case of draw-
through systems, this heat is an addition to the supply air
heat gain and should be added to the room sensible
110
Part 1. Load Estimating | Chapter 7. Internal And System Heat Gain
3. With the motor and drive in the air stream or and (4) safety factor, as explained in the preceding
conditioned space, the heat generated by the paragraph.
inefficiency of the motor and drive is also an
immediate heat gain. Example 7-Percent Addition to Room Sensible Heat
The fan efficiencies are about 70% for central station Given:
type fans and about 50% for packaged equipment fans. Same data as Examples 5 and 6
Find:
Use of Table 59 Percent addition to room sensible heat gain sub-total
-- Heat Gain from Air Conditioning Fan Horsepower Solution:
The approximate system pressure loss and Supply duct heat gain = 5.7%
dehumidified air rise (room minus supply air temperature) Supply duct leakage (20 ft duct of total 100 ft) = 2.0%
differential must be estimated from the system Fan horsepower = 2.3%
characteristics and type of application. These should be Safety factor = 0.0%
checked from the final system design. Total percent addition to RSH = 10.0%
The normal comfort application has a dehumidified
air rise of between 15 F db and 25 F db and the fan total The percent additions to room latent heat for supply
pressure depends on the amount of ductwork involved, duct leakage loss and safety factor should be the same
the number of fittings (elbows, etc.) in the ductwork and as the corresponding percent additions to room sensible
the type of air distribution system used. Normally, the fan heat.
total pressure can be approximated as follows:
1. No ductwork (packaged equipment) – 0.5 to RETURN AIR DUCT HEAT AND LEAKAGE GAIN
1.00 inches of water. The evaluation of heat and leakage effects on return
2. Moderate amount of ductwork, low velocity air ducts is made in the same manner as for supply air
systems - 0.75 to 1.50 inches of water. ducts, except that the process is reversed; there is
3. Considerable ductwork, low velocity system- inward gain of hot moist air instead of loss of cooling
1.25 to 2.00 inches of water. effect.
4. Moderate amount of ductwork, high pressure Chart 3 can be used to approximate heat gain to the
system - 2.00 to 4.00 inches of water. return duct system in terms of percent of RSH, using the
5. Considerable ductwork, high pressure system following procedure:
– 3.00 to 6.00 inches of water. 1. Using RSH and the length of return air duct,
use Chart 3 to establish the percent heat gain.
Example 6- Heat Gain from Air Conditioning Fan 2. Use the multiplying factor from table below
Horsepower Chart 3 to adjust the percent heat gain for
Given: actual temperature difference between the air
Same data as Example 5 surrounding the return air duct and the air
80 ft of supply duct in conditioned space inside the duct, and also for the actual velocity.
Find: 3. Multiply the resulting percentage of heat gain
Percent addition to room sensible heat. by the ratio of RSH to GTH.
Solution: 4. Apply the resulting heat gain percentage to
Assume 1.50 inches of water, fan total pressure, and GTH.
20 F db dehumidifer rise. Refer to Table 59.
Heat gain from fan horsepower = 2.3% To determine the return air duct leakage, apply the
following reasoning:
SAFETY FACTOR AND PERCENT ADDITIONS TO 1. Bare duct within conditioned space – no in-
ROOM SENSIBLE AND LATENT HEAT leakage.
A safety factor to be added to the room sensible heat 2. Furred duct within conditioned space or furred
sub-total should be considered as strictly a factor of space used for return air – a matter of
probable error in the survey or estimate, and should judgment, depending on whether the furred
usually be between 0% and 5%. space may connect to unconditioned space.
The total room sensible heat is the sub-total plus
percentage additions to allow for (1) supply duct heat
gain, (2) supply duct leakage losses, (3) fan horsepower
111
Part 1. Load Estimating | Chapter 7. Internal And System Heat Gain
3. Ducts outside conditioned space – assume up PERCENT ADDITION TO GRAND TOTAL HEAT
to 3% inleakage, depending on the length of The percent additions to the grand total heat to
duct. If there is only a short connection compensate for various external losses consist of heat
between conditioned space and apparatus, and leakage gain to return air ducts, heat gain from the
inleakage may be disregarded. If there is a dehumidifier pump horsepower, and the heat gain to the
long run of duct, then apply judgment as to the dehumidifier and piping system.
amount of inleakage. These heat gains can be estimated as follows:
HEAT GAIN FROM DEHUMIDIFIER PUMP 1. Heat and leakage gain to return air ducts, see
HORSEPOWER above.
With dehumidifier systems, the horsepower required 2. Heat gain from dehumidifier pump horsepower,
to pump the water adds heat to the system as outlined Table 60.
under “Electric Motors”. This heat will be an addition to 3. Dehumidifier and piping losses:
the grand total heat. a. Very little external piping - 1% of GTH.
b. Average external piping - 2% of GTH.
Basis of Table 60 c. Extensive external piping - 4% of GTH.
-- Heat Gain from Dehumidifier Pump Horsepower 4. Blow-through fan system-add percent room
Table 60 is based on pump efficiencies of 50% for sensible heat from Table 59 to GTH.
small pumps and 70% for large pumps. Small pumps are 5. Dehumidifier in conditioned apparatus room-
considered to have a capacity of less than 100 gallons; reduce the above percentages by one half.
large pumps, more than 100 gallons.
Use of Table 60
-- Heat Gain from Dehumidifier Pump Horsepower
The chilled water temperature rise in the dehumidifier
and the pump head must be approximated to use Table
60.
1. Large systems with considerable piping and
fitting may require up to 100 ft pump head;
normally, 70 ft head is the average.
2. The normal water temperature rise in the
dehumidifier is between 7 F and 12 F.
Applications using large amounts of water
have a lower rise; those using small amounts of
water have a higher rise.
112
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
113
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
114
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
115
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
The room sensible heat factor line can also be drawn apparatus (mixture condition of outdoor and return room
on the psychrometric chart without knowing the condition air) and the condition of the air leaving the apparatus may
of supply air. The following procedure illustrates how to be plotted on the psychrometric chart and connected by
plot this line, using the calculated RSHF, the room design a straight line (1-2), Fig. 36. This line represents the
conditions, the sensible heat factor scale in the upper psychrometric process of the air as it passes through the
right hand corner of the psychrometric chart, and the conditioning apparatus, and is referred to as the grand
alignment circle at 80 F dry-bulb and 50% relative sensible heat factor line.
humidity: The slope of the GSHF line represents the ratio of
1. Draw a base line thru the alignment circle and the sensible and latent heat that the apparatus must handle.
calculated RSHF shown on the sensible heat factor This is illustrated in Fig. 36 by ∆hs (sensible heat) and ∆h1
scale in the upper right corner of psychrometric (latent heat).
chart (1-2), Fig. 35.
2. Draw the actual room sensible heat factor line thru
the room design conditions parallel to the base line
in Step 1 (3-4), Fig. 35. As shown, this line may be
drawn to the saturation line on the psychrometric
chart.
116
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
cfmsa = RSH
1.08(trm – tsa)
The air quantity required thru the conditioning
apparatus to satisfy the total air conditioning load
(including the supplementary loads) is calculated from
the following equation:
FIG. 38 – RSHF AND GSHF LINES PLOTTED ON TSH
SKELETON PSYCHROMETRIC CHART cfmda =
1.08(tm – tldb)
This neglects fan and duct heat gain, duct leakage The required air quantity supplied to the space is
losses, etc. In actual practice, these heat gains and equal to the air quantity required thru the apparatus,
losses are taken into account in estimating the cooling neglecting leakage losses. The above equation contains
load. Chapter 7 gives the necessary data for evaluating the term tm which is the mixture condition of air entering
these supplementary loads. Therefore, the temperature of the apparatus. With the exception of an all outdoor air
the air leaving the apparatus is not necessarily equal to application, the term tm can only be determined by trial
the temperature of the air supplied to the space as and error.
indicated in Fig. 38. One possible procedure to determine the mixture
Fig. 39 illustrates what actually happens when these temperature and the air quantities is outlined below. This
supplementary loads are considered in plotting the RSHF procedure illustrates one method of apparatus selection
and GSHF lines.
117
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
and is presented to show how cumbersome and time condition of the air normally falls on the RSHF line close to
consuming it may be. the saturation line. How close to the saturation line
1. Assume a rise (trm-tsa) in the supply air to the space, depends on the physical operating characteristics and
and calculate the supply air quantity (cfmsa) to the the efficiency of the conditioning equipment.
space. In determining the required air quantity, when
2. Use this air quantity to calculate the mixture neglecting the supplementary loads, the supply air
condition of the air (tm) to the space, (Equation 1, temperature is assumed to equal the condition of the air
page 150). leaving the apparatus (tsa-t1db). This is illustrated in Fig.
3. Substitute this supply air quantity and mixture 38. The calculation for the required air quantity still
condition of the air in the formula for air quantity remains a trial-and-error procedure, since the mixture
thru the apparatus (cfmda) and determine the temperature of the air (tm) entering the apparatus is
leaving condition of the air from the conditioning dependent on the required air quantity. The same
apparatus (tldb). procedure previously described for determining the air
4. The rise between the leaving condition from the quantity is used. Assume a supply air rise and calculate
apparatus and supply air condition to the space the supply air quantity and the mixture temperature to the
(tsa-t1db) must be able to handle the supplementary conditioning apparatus. Substitute the supply air quantity
loads (duct heat gain and fan heat). These and mixture temperature in the equation for determining
temperatures (t1db, tsa) may be plotted on their the air quantity thru the apparatus, and calculate the
respective GSHF and RSHF lines (Fig. 39) to leaving condition of the air from the apparatus. This
determine if these conditions can handle the temperature must equal the supply air temperature; if it
supplementary loads. If they cannot, a new rise in does not, a new supply air rise is assumed and the
supply air is assumed and the trial-and-error procedure repeated.
procedure repeated. Determining the required air quantity by either
method previously described is a tedious process, since
In a normal, well designed, tight system this it involves a trial-and-error procedure, plotting the RSHF
difference in supply air temperature and the condition of and GSHF ratios on a psychrometric chart, and in actual
the air leaving the apparatus (tsa-t1db) is usually not more practice accounting for the supplementary loads in
than a few degrees. To simplify the discussion on the determining the supply air, mixture and leaving air
interrelationship of RSHF and GSHF, the supplementary temperatures.
loads have been neglected in the various discussions, This procedure has been simplified, however, by
formulas and problems in the remainder of this chapter. relating all the conditioning loads to the physical
It can not be over-emphasized, however, that these performance of the conditioning equipment, and then
supplementary loads must be recognized when including this equipment performance in the actual
estimating the cooling and heating loads. These loads calculation of the load.
are taken into account on the air conditioning load This relationship is generally recognized as a
estimate in Chapter 1, and are evaluated in Chapter 7. psychrometric correlation of loads to equipment
The RSHF ratio will be constant (at full load) under a performance. The correlation is accomplished by
specified set of conditions; however, the GSHF ratio may calculating the “effective surface temperature,” “bypass
increase or decrease as the outdoor air quantity and factor” and “effective sensible heat factor.” These alone
mixture conditions are varied for design purposes. As the will permit the simplified calculation of supply air
GSHF ratio changes, the supply air condition to the space quantity.
varies along the RSHF line (Fig. 38).
The difference in temperature between the room and EFFECTIVE SURFACE TEMPERATURE (tes)
the air supply to the room determines the air quantity The surface temperature of the conditioning
required to satisfy the room sensible and room latent equipment varies throughout the surface of the apparatus
loads. As this temperature difference increases as the air comes in contact with it. However, the effective
(supplying colder air, since the room conditions are surface temperature can be considered to be the uniform
fixed), the required air quantity to the space decreases. surface temperature which would produce the same
This temperature difference can increase up to a limit leaving air conditions as the non-uniform surface
where the RSHF line crosses the saturation line on the temperature that actually occurs when the apparatus is in
psychrometric chart, Fig. 38; assuming, of course, that operation. This is more clearly understood by illustrating
the available conditioning equipment is able to take the the heat transfer effect between the air and the cooling
air to 100% saturation. Since this is impossible, the (or heating) medium. Fig. 40 illustrates this process and
118
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
119
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
120
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
121
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
122
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
123
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
The following section describes the characteristic items. Normally, performance requirements aestablished
psychrometric performance of air conditioning and then equipment is selected to meet the requirement
equipment.
Coils, sprays and sorbent dehumidifiers are the three COIL CHARACTERISTICS
basic types of heat transfer equipment required for air In the operation of coils, air is drawn or forcedover a
conditioning applications. These components may be series of tubes thru which chilled water, brine, volatile
used singly or in combination to control the psychrometric refrigerant, hot water or steam is flowing. As the air
properties of the air passing thru them. passes over the surface of the coil, it is cooled, cooled
The selection of this equipment is normally and dehumidified, or heated, depending upon the
determined by the requirements of the specific temperature of the media flowing thru the tubes. the
application. The components must be selected and media in turn is heated or cooled in the process.
integrated to result in a practical system; that is, one The amount of coil surface not only affects the heat
having the most economical owning and operating cost. transfer but also the bypass factor of the coil. The
An economical system requires the optimum bypass factor, as previously explained, is the measure of
combination of air conditioning components. It also air side performance. Consequently, it is a function of the
requires an air distribution system that provides good air type and amount of coil surface and the time available for
distribution within the conditioned space, using a contact as the air passes thru the coil. Table 61 gives
practical rise between supply air and room air approximate bypass factors for various finned coil
temperatures. surfaces and air velocities.
Since the only known items are the load in the space
and the conditions to be maintained within the space, the
selection of the various components is based on thes
124
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
125
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
126
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
6. Assume for this example that the apparatus selected for Example 2- Cooling and Dehumidification – High
9,000 cfm, 50 F adp, and GTH = 339,400, has a bypass Latent Load
factor that is equal, or nearly equal, to the assumed BF =
0.15. Also, assume that it is not necessary to physically Given:
bypass air around the apparatus. Application – Laboratory
Location – Bangor, Maine
(2000 x 95) + (7000 x 75) Summer design – 90 F db, 73 F wb
tedb = = 79.45 db (31) Inside design – 75 F db, 50% rh
9000
RSH – 120,000 Btu/hr
Read tewb where the tedb crosses the straight line plotted RLH – 65,000 Btu/hr
between the outdoor and room design conditions on the
psychrometric chart, Fig. 49. Ventilation – 2,500 cfmoa
tewb = 65.5 F wb Temp. diff. between room and supply air, 20 F maximum
tldb = 50+.15(79.45-50) = 54.4 F db (32) Find:
Determine that tlwb by drawing a straight line between the
adp and the entering conditions at the apparatus. (This is 1. Outdoor air load (OATH)
the GSHF line.) Where tldb intersects this line, read tlwb. 2. Effective sensible heat factor (ESHF)
tlwb = 52.7 F wb 3. Apparatus dewpoint (tadp)
4. Reheat required
Cooling and Dehumidification – High Latent Load 5. Supply air quantity (cfmsa)
Application 6. Entering conditions to coil (tedb, tewb, Wea)
On some applications a special situation exists if the 7. Leaving conditions from coil (tldb, tlwb)
ESHF and GSHF lines do not intersect the saturation line 8. Supply air condition to the space (tsa, Wsa)
when plotted on the psychrometric chart of if they do the 9. Grand total heat (GTH)
adp is absurdly low. This may occur where the latent load Solution:
is high with respect to the total loads (dance halls, etc.). 1. OASH = 1.08×2500×(90-75) = 40,500 Btu/hr (14)
In such applications, an appropriate apparatus dewpoint OALH = .68×2500× (95-65) = 51,000 Btu/hr (15)
is selected and the air is reheated to the RSHF line. OATH = 40,500+51,000 = 91,500 Btu/hr (17)
Occasionally, altering the room design conditions 2. Assume a bypass factor of 0.05 because of high latent load.
eliminates the need for reheat, or reduces the quantity of 120,000 + .05 (40,500)
reheat required. Similarly, the utilization of a large air side ESHF =
120,000 + .05 (40,500) + 65,000 + (.05) (51,000)
surface (low bypass factor) coil may eliminate the need
for reheat or reduce the required reheat. = .645 (26)
When plotted on the psychrometric chart, this ESHF (.645)
Once the ventilation air requirement is determined, intersects the saturation vurve at 35 F. With such a low adp
and if the supply air quantity is not fixed, the best an appropriate apparatus dewpoint should be selected and
approach to determining the apparatus dewpoint is to the air reheated to the RSHF line.
3. Refer to Table 65. For inside design conditions of 75 F db,
assume a maximum allowable temperature difference 50% rh, an ESHF of .74 results in an adp of 48 F which is a
between the supply air and the room. Then, calculate the reasonable minimum figure.
supply air conditions to the space. The supply air 4. Determine amount of reheat (Btu/hr) required to produce an
ESHF of .74.
conditions to the space must fall on the RSHF line to ESHF (.74) =
properly offset the sensible and latent loads in the space. 120,000 + .05 (40,500) + reheat
There are four criteria which should be examined, to 120,000 + .05 (40,500) + reheat + 65,000 + (.05) 51,000
aid in establishing the supply air requirements to the
space. These are: .74 = 122,025 + reheat (25)
1. Air movement in the space. 189,575 + reheat
2. Maximum temperature difference between the reheat = 70,230 Btu/hr
5. Determine dehumidifier air quantity (cfmda)
supply air and the room. ERSH
3. The selected adp should provide an economical cfmda = (36)
1.08 x (1 – BF) (trm – tadp)
refrigeration machine selection.
4. In some cases, the ventilation air quantity required 122,025 + 70,230
= = 6940 cfm
may result in an all outdoor air application. 1.08 (1 - .05) (75 – 48)
Example 2 is a laboratory application with a high cfmda is also cfmsa when no air is to be physically bypassed
latent load. In this example the ESHF intersects the around the cooling coil.
saturation line, but the resulting adp is too low.
127
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
128
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
7. Final apparatus dewpoint temperature (tadp,) When humidification is performed in the space, the
8. Recalculated dehumidified air quantity (cfmda) room sensible load is decreased by an amount equal to
Solution: the latent heat added, since the process is merely an
1. OASH = 1.08×1600×(95-75) = 34,600 Btu/hr (14) interchange of heat. The humidifier motor adds sensible
OALH = .68×1600× (98.5-71) = 30,000 Btu/hr (15) heat to the room but the amount is negligible and is
OATH = 34,500+30,000 = 64,600 Btu/hr (17) usually ignored.
2. Assume a bypass factor of 0.05 from Tables 61 and 62. Where humidification is required at design to reduce
50,000 + (.05) (34,600) the air quantity, then a credit to the room sensible heat
ESHF = should be taken in the amount of the latent heat from the
50,000 + (.05) (34,600) + 11,000 + (.05) (30,000)
added moisture. No credit to the room sensible load is
= .81 (26) taken when humidification is used to make up a
3. Table 65 shows that, at the given room design conditions
and effective sensible heat factor, tadp = 54.5 F. deficiency in the room latent load during partial load
operation.
50,000 + (.05) (34,600) When the humidifiers and sprays are used to reduce
4. cfmda = 1.08 (1 - .05) (75 – 54.5) = 2450 cfm (36)
the required air quantity, the latent load introduced into
the space is added to the room latent load.
Since 2450 cfm is larger than the ventilation requirements, When the humidifier or sprays are operated only to
and by code all OA is required, the O.A loads, the adp, and
the dehumidified air quantity must be recalculated using make up the room deficiency, the latent load introduced
2450 cfm as the OA requirements. into the room by the humidifier or auxiliary sprays in the
5. Recalculating outdoor air load space is not added to the room latent load.
OASH = 1.08×2450× (95-75) = 53,000 Btu/hr (14)
OALH = .68×2450× (98.5-71) = 46,000 Btu/hr (15) The introduction of this moisture into the space to
OATH = 53,000+46,000 = 99,000 Btu/hr (17) reduce the required air quantity decreases the RSHF,
ESHF and the apparatus dewpoint. This method of
50,000 + (.05) (53,000) reducing the required air quantity is normally
6. ESHF = (50,000) + (.05) (53,000) + 11,000 + (.05) (46,000) advantageous when designing for high room relative
= .80 (26) humidities.
7. tadp = 54 F The method of determining the amount of moisture
50,000 + (.05) (53,000) necessary to reduce the required air quantity results in a
8. cfmda = = 2500 cfm (36) trial-and-error procedure. The method is outlined in the
1.08 (1 - .05) (75 – 54) following steps:
This checks reasonably close to the value in Step 4, and 1. Assume an amount of moisture to be added and
recalculation is not necessary. determine the latent heat available from this
moisture. Table 64 gives the maximum moisture
Cooling With Humidification that may be added to a space without causing
Cooling with humidification may be required at partial condensation on supply air ducts and equipment.
load operation to make up a deficiency in the room latent 2. Deduct this assumed latent heat from the original
load. It may also be used at design conditions for effective room sensible heat and use the difference
industrial applications having relatively high sensible in the following equation for ERSH to determine tadp.
loads and high room relative humidity requirements. ERSH
Without humidification, excessively high supply air tadp = trm -
1.08 X (1 – BF) cfmda
quantities may be required. This not only creates air
distribution problems but also is often economically Cfmda is the reduced air quantity permissible in the
unsound. Excessive supply air quantity requirements can air distribution system.
be avoided by introducing moisture into the space to 3. The ESHF is obtained from a psychrometric chart or
convert sensible heat to latent heat. This is sometimes Table 65, using the apparatus dewpoint (from Step
referred to as a “split system.” The moisture is introduced 2) and room design conditions.
into the space by using steam or electric humidifiers or 4. The new effective room latent load is determined
auxiliary sprays. from the following equation:
1 - ESHF
ERLH = ERSH X
ESHF
NOTE : Numbers in parentheses at right edge of column refer to
equations beginning on page 150. The ERSH is from Step 2 and ESHF is from Step 3.
5. Deduct the original ERLH (before adding sprays or
129
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
130
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
131
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
132
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
ventilation air requirement, the .05 bypass factor is used considered to represent that portion of the air passing
again to determine a new tes, substituting the ventilation thru the spray chamber which contacts the spray water
air requirement for the dehumidified air quantity. The new surface. This contacted air is considered to be leaving
tes is 58.4 F. the spray chamber at the effective surface temperature of
the spray water. This effective surface temperature is the
temperature at complete saturation of the air.
Though not a straight line function, the effect of
saturation efficiency on the leaving air conditions from a
spray chamber may be determined with a sufficient
degree of accuracy from the following equation:
t –t W –W h -h
Sat Eft = tedb – tldb = W ea – W la = h ea - h la
edb es ea es ea es
133
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
SPRAY PROCESSES
FIG. 54- SPRAY PROCESSES
Sprays are capable of cooling and dehumidifying, Sensible Cooling
sensible cooling, cooling and humidifying, and heating If the spray water is cooled further, sensible cooling
and humidifying. Sensible cooling may be accomplished occurs. This process is represented by line (1-4).
only when the entering air dewpoint is the same as the Sensible cooling occurs only when the entering air
effective surface temperature of the spray water. dewpoint is equal to the effective surface temperature of
The various spray processes are represented on the the spray water; this condition is rare. In a sensible
psychrometric chart in Fig. 54. All process lines must go cooling process, the air leaving the spray chamber is
toward the saturation line, in order to be at or near lower in dry-and wet-bulb temperatures but equal in
saturation. moisture content to the entering air.
Adiabatic Saturation or Evaporative Cooling Cooling and Dehumidification
Line (1-2) represents the evaporative cooling If the spray water is cooled still further, cooling and
process. This process occurs when air passes thru a dehumidification takes place. This is illustrated by line (1-
spray chamber where heat has not been added to or 5). The leaving air is lower in dry-and wet-bulb
removed from the spray water. (This does not include temperatures and in moisture content than the air
heat gain from the water pump and thru the apparatus entering the spray chamber.
casing.) When plotted on the psychrometric chart, this
line approximately follows up the line of the wet-bulb Cooling and Humidification – With Heated Spray Water
temperature of the air entering the spray chamber. The When the spray water is heated to a limited degree
spray water temperature remains essentially constant at before it is sprayed into the air stream, the slope of the
this wet-bulb temperature. process line rises to a point above the evaporative
cooling line. This is illustrated by line (1-6). Note that the
Cooling and Humidification –With Chilled Spray Water leaving air is lower in dry-bulb temperature, but higher in
If the spray water receives limited cooling before it is wet-bulb temperature and moisture content, than the air
sprayed into the air stream, the slope of the process line entering the spray chamber.
will move down from the evaporative cooling line. This
process is represented by line (1-3). Limited cooling Heating and Humidification
causes the leaving air to be lower in dry-and wet-bulb If the spray water is sufficiently heated, a heating and
temperatures, but higher in moisture content, than the air humidification process results. This is represented by
entering the spray chamber. line (1-7). In this process the dry-bulb temperature, wet-
134
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
bulb temperature, and moisture content of the leaving air dry-bulb during the winter or intermediate season, a
is greater than that of the entering air. combination of preheat and reheat coils, or a reheat coil
and spray water heating, is required. The latter method
SPRAY PROCESS EXAMPLES changes the process from evaporative cooling to one of
The following descriptions and examples provide a the humidification processes illustrated by lines (1-6) or
better understanding of the various psychrometric (1-7) in Fig. 54.
processes involved in spray washer equipment. Evaporative cooling may be used in industrial
applications where the humidity alone is critical, and also
Cooling and Dehumidification in dry climates where evaporative cooling gives some
When a spray chamber is to used for cooling and measure of relief by removing sensible heat.
dehumidification, the procedure for estimating the load Example 6 illustrates an industrial application
and selecting the equipment is identical to the procedure designed to maintain the space relative humidity only
described on page 128 for coils. The “Air Conditioning
Load Estimate” form is used to evaluate the load; bypass Example 6-Evaporative Cooling
factor is determined by subtracting the selected Given:
saturation efficiency from one. Spray chamber An industrial application
dehumidifiers may not be rated in terms of apparatus Location – Columbia, South Carolina
dewpoint but in terms of entering and leaving wet-bulb Summer design – 95 F db, 75 F wb
temperatures at the apparatus. The apparatus dewpoint Inside design – 55% rh
must still be determined, however, to evaluate properly RSH – 2,100,000 Btu/hr
the entering and leaving wet-bulb temperatures and the RSHF – 1.0
dehumidified air quantity. Use all outdoor air at design load conditions
Although originally prepared to exemplify the Find:
operation of a coil, Example 1, page 128, is also typical 1. Room dry-bulb temperature at design (trm)
of the cooling and dehumidifying process using sprays. 2. Supply air quantity (cfmsa)
135
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
136
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
137
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
Example 8- Heating and Humidification- spray chamber, plot the mixture line of outdoor and return
With Heated Spray Water room air on the psychrometric chart, and read the wet-bulb
Given: temperature where tedb crosses the mixture line, Fig. 54.
An industrial application tewb= 32.4 F wb
Location – Richmond, Virginia The air leaving the spray chamber must have the same
Winter design – 15 F db moisture content as the air in the room.
Inside design – 72 F db, 35% rh Wrm= Wla = 41 gr/lb
Ventilation – 50,000 cfmoa (see explanation above) Since the spray chamber has a saturation efficiency of 95%,
Supply air – 85,000 cfmsa the moisture content of completely saturated air is
Design room heat loss – 2,500,000 Btu/hr calculated as follows:
Spray saturation efficiency – 95% Wla - Wea
RSHF (winter conditions) – 95% Wsat = + Wea
Sat Eff
Make-up water – 65 F
Find: = 41 - 17 + 17 = 42.3 gr/lb
1. Supply air conditions to the space (tsa) .95
2. Entering and leaving spray water temperature (tew, tlw) The heating and humidification process line is plotted on the
3. Heat added to spray water to select water heater. psychrometric chart between the moisture content of
Solution: saturated air (42.3 gr/lb) and the entering conditions to the
design room heat loss + t spray chamber (38.5 F db and 32.4 F wb), Fig. 57.
1. tsa = 1.08 x cfmsa rm The leaving conditions are read from the psychrometric
chart where the room moisture content line (41 gr/lb)
2,500,000 intersects the heating and humidification process line, Fig.
= + 72 = 99.2 Fdb
1.08 x 85,000 57.
To determine the wet-bulb temperature, plot the RSHF line tlwb = 43.6 F db
on the psychrometric chart and read the wet-bulb at the tlwb = 43.4 F wb
point where tsa crosses this line (Fig. 57). Supply air wet- The temperature of the leaving spray water is approximately
bulb to the space = 65.8 F wb. equal to the wet-bulb temperature of the air leaving the
2. To determine the entering and leaving spray water spray chamber.
temperature, calculate the entering and leaving air tlw = 43.4 F
conditions at the spray chamber:
NOTE: Numbers in parentheses at right edge of column refer to
(15 x 50,000) + (72 x 35,000) equations beginning on page 150.
tedb = = 38.5 F db (31)
85,000
To determine wet-bulb temperature of the air entering the
138
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
The temperature of the entering spray water is dependent In this example a reheat coil is required to heat the air
on the water quantity and the heat to be added or removed leaving the spray chamber, at 43.6 F db and at a
from the air. In this type of application, the water quantity is constant moisture content of 41 gr/lb, to the required
usually dictated by the cooling load design requirements. supply air temperature of 99.2 F db.
Assume, for illustration purposes, that this spray washer is The requirements of the application illustrated in
selected for 110 gpm for cooling. Example 8 can also be met by preheating the outdoor air
The heat added to the air as it passes through the washer and mixing it with the return air from the space. This
= cfmsa ×4.45× (hla-hea) mixture must then be evaporatively cooled to the room
= 85,000×4.45× (16.85-12) dewpoint (or room moisture content). And finally, the air
= 1,830,000 Btu/hr leaving the spray chamber must be reheated to the
The entering water temperature is determined from the required supply air temperature.
following equation:
heat added to air SORBENT DEHUMIDIFIERS
tew = tlw +
500 x gpm
Sorbent dehumidifiers contain liquid absorbent or
1,830,000
solid adsorbent which are either sprayed directly into, or
= 43.4 + located in, the path of the air stream. The liquid absorbent
500 x 110 changes either physically or chemically, or both, during
= 76.8 F the sorption process. The solid adsorbent does not
3. The heat added to the spray water (for selecting spray water change during the sorption process.
heater) is equal to the heat added to the air plus the heat As moist air comes in contact with either the liquid
added to the make-up water. The amount of make-up water absorbent or solid adsorbent, moisture is removed from
is equal to the amount of moisture evaporated into the air the air by the difference in vapor pressure between the air
and is determined from the following equation: stream and the sorbent. As this moisture condenses,
cfmsa (Wla – Wea)
Make-up water =
7000 x 12.7 x 8.34
where:
wea, Wla = moisture content of the air entering and
leaving the spray washer in grains per pound
of dry air
7000 = grains of moisture per pound of dry air
12.7 = volume of the mixture in cubic feet per pound
of dry air, determined from psychrometric
chart
8.34 = water in pounds per gallon
85,000 (41 – 17)
Make-up water = 7000 x 12.7 x 8.34 = 2.8 gpm
139
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
140
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
141
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
142
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
143
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
144
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
*The values shown in the gray areas indicate the lowest effective
sensible heat factor possible without the use of reheat. This limiting
condition is the lowest effective sensible heat factor line that
intersects the saturation curve. Note that the room dewpoint is
equal to the required apparatus dewpoint for an effective sensible
heat factor of 1.0.
NOTES FOR TABLE 65:
1. For Room Conditions Not Given; The apparatus dewpoint may
be determined from the scale on the chart, or may be calculated
as shown in the following equation:
1
ESHF = (Wrm – Wadp)
1 + .628
(trm – tadp)
This equation in more familiar form is:
0.244 (trm – tadp)
ESHF = 1076
0.244 (trm – tadp) + 7000 (Wrm – Wadp)
(Cont.)
145
Part 1. Load Estimating | Chapter 8. Applied Psychrometrics
where wrm = room moisture content, gr/lb of dry air 3. For Apparatus Dewpoint Below Freezing. The latent
Wadp = moisture content at apparatus dewpoint, gr/lb heat of fusion of the moisture removed is not included in
of dry air the calculation of apparatus dewpoint below freezing or
trm = room dry-bulb temperature in the calculation of room load, in order to simplify
tadp = apparatus dewpoint temperature estimating procedures. Use the same equation as in
0.244 = specific heat of moist air at 55 F dewpoint, Btu Note 1. The selection of equipment on a basis of 16 to
per deg F per lb of dry air 18 hour operating time provides a safety factor large
1076 = average heat removal required to condense enough to cover the omission of this latent heat of
one pound of water vapor from the room air fusion, which is a small part of the total load.
7000 = grains per pound.
2. For High Elevations. For effective sensible heat factors
at high elevations, see Table 66.
TABLE 66- EQUIVALENT EFFECTIVE SENSIBLE HEAT FACTORS FOR VARIOUS ELEVATIONS*
For use with sea level psychrometric chart or tables
Effective
Sensible Heat Elevation (Feet) and Barometric Pressure (Inches of Hg) at Installation
Factor from Air 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000
Conditioning (28.86) (27.82) (26.82) (25.84) (24.89) (23.98) (23.09) (22.12) (21.39) (20.57)
Load Estimate Equivalent Effective Sensible Heat Factor Referred to a Sea Level Psychrometric Chart or Tables
.95 .95 .95 .95 .96 .96 .96 .96 .96 .96 .96
.90 .90 .91 .91 .91 .92 .92 .92 .92 .93 .93
.85 .85 .86 .86 .87 .87 .88 .88 .88 .89 .89
.80 .81 .81 .82 .82 .83 .83 .84 .84 .85 .85
.75 .76 .76 .77 .78 .78 .79 .80 .80 .81 .81
.70 .71 .72 .72 .73 .74 .75 .75 .76 .77 .77
.65 .66 .67 .68 .68 .69 .70 .71 .71 .72 .73
.60 .61 .62 .63 .64 .64 .65 .66 .67 .68 .69
.55 .56 .57 .58 .59 .60 .61 .61 .62 .63 .64
.50 .51 .52 .53 .54 .55 .56 .57 .57 .58 .59
*Values obtained by use of equation equation was derived on this basis. The room wet-bulb
1 temperature must not be used because the wet-bulb
ESHFe = temperature corresponding to any particular condition, for
(p1) (1 – ESHF) example, 75 F db, 40% rh, at a high elevation is lower (except
+1
(po) (ESHF) for saturation) than that corresponding to the same condition
(75 F db, 40% rh) at sea level. For the same value of room
where po = barometric pressure at sea level relative humidity and dry-bulb temperature, and the same
p1 = barometric pressure at high elevation apparatus dew-point, there is a greater difference in moisture
ESHF = ESHF obtained from air conditioning load content between the two conditions at high elevation than at
estimate sea level. Therefore, a higher apparatus dewpoint is required
ESHFe = equivalent ESHF referred to a sea level at high elevation for a given effective sensible heat factor.
psychrometric chart or Table 66 2. Air conditioning load estimate (See Fig. 44). The factors 1.08
and .68 on the air conditioning load estimate should be
NOTES FOR TABLE 66: (p )
1. The required apparatus dewpoint for the high elevation is multiplied by the direct ratio of the barometric pressures (p1) .
o
determined from the sea level chart or Table 65 by use of the
equivalent effective sensible heat factor. The relative humidity Using this method, it is assumed that the air quantity (cfm) is
and dry-bulb temperature must be used to define the room measured at actual conditions rather than at standard air
condition when using this table because the above conditions. The outdoor and room moisture contents, grains
per pound, must also be corrected for high elevations.
3. Reheat-Where the equivalent effective sensible heat factor is
lower than the shaded values in Table 65, reheat is required.
146
A table 18 gain from, see heat
Apparatus dewpoint gain, internal
Abbreviations high altitude selection Condensation
Absorbent dehumidifier, see table 66 maximum room rh without
sorbent psychrometric principle con-densation
dehumidifiers table chart 2
Adiabatic saturation, see spray Appliances, heat gain from all maximum moisture added
processes types, see heat gain, to supply
Adsorbent dehumidifier, see. internal air without causing
sorbent Azimuth angles, solar condensation on supply
dehumidifiers table 18 ducts
Air table 64
By passed around Cooling and dehumidification
conditioning equipment B with coils, see coil
heat gain from outdoor processes
Air conditioning Bibliography with sprays, see spray
adiabatic saturation Building survey processes
cooling and heat load sources Cooling and humidification
dehumidification location of equipment with coils, see coil
cooling and humidification location of services processes
evaporate cooling space characteristics with sprays, see spray
heating and Bypass control, for partial load processes
dehumidification, see Bypass factor Cooling loads, diversity of
sorbent dehumidifiers coils table 14
heating and humidification table 61 Cooling processes
sensible cooling with coils, see coil
sensible heating sorbent processes
dehumidifiers C with sprays, see spray
Air conditioning apparatus processes
coil characteristics Crack method
sorbent dehumidifiers Centrifugal fan capacities summer infiltration thru
sprays characteristics table 46 doors
Air conditioning load estimate, Coil characteristics, bypass and
form factor windows
internal load table 61 table 44
outdoor load Coil processes winter infiltration thru doors
Air constants, derivation cooling and and
Air density difference effect on dehumidification windows
infiltration with all outdoor air table 44
Air quantity with high latent load
from air conditioning load cooling with humidification
estimate form sensible cooling
psychrometric calculations sensible heating
Altitude angles, solar Computers, electronic, heat
147
D see heat gain, internal appliances, steam heated,
Electronic computers, heat gain restaurant
from, see heat gain, internal table 51
Dehumidifier pump, heat gain to Equipment selection electronic computer
system, see heat gain, Equivalent temperature equipment
system difference latent, credit to room
Dehumidifier, sorbent, see roofs, sunlit and shaded sensible
sorbent dehumidifiers table 20 heat
Design conditions walls, sunlit and shaded lights
industrial processes table 19 table 49
table 5 Evaporative cooling, see spray moisture absorption motors,
inside factory comfort, processes electric
winter and summer table 53
table 4 people
inside summer comfort F table 48,
table 4 pipes, bare steel
inside winter comfort Factory, inside comfort design table 54
table 4 conditions pipes, insulated
maximum outdoor design, table 4 table 55
summer Pan capacity pipes, insulated cold
table 1 centrifugal, table 46 table 56
normal outdoor design, propeller, table 47 steam
summer Fan motors, heat gain to See storage factors for lights
table 1 heat gain, system table 12
normal outdoor design, Formulas, see psychrometric tanks, uninsulated
winter, table 1 formulas table 57
outdoor design corrections water surface
for time of day table 58
table 2 G Heat gain, solar
outdoor design corrections direct and diffuse
for time of year factors for glass block
table 3 Gas appliances, heat gain from table 17
Diversity, of cooling loads All types, see heat gain, internal over-all factors or types of
table 14 Grand sensible heat factor glass,
Door infiltration, see infiltration Ground temperature, for table 16
Duct calculating heat loss thru peak solar, thru ordinary
heat gain to return duct, see basement floors and walls glass
heat gain, system tables 16 table 6
heat gain to supply duct, storage factors or glass,
see heat gain, system bare or
leakage loss, supply and H external shade
return duct, see heat gain, table 8,24-hour operation
system Heat flow, thru building table 10, 16-hour operation
structures table 11,12-bour operation
Heat gain, internal storage factors for glass,
E appliances, electric and gas intern shade
burning, miscellaneous table 7, 24-hour operation
appliances, hooded table 9,16-hour operation
Effective sensible heat factor appliances, electric, table 11 12-hour operation,
Effective surface temperature restaurant, thru ordinary glass
Electric appliances, heat gain table 50 table 15
From all types, see heat appliances, gas burning, Heat gain, system
gain,internal restaurant air conditioning fan
Electric motors, heat gain from, table 51 horsepower
148
Heat stratification, storage of gain, internal
table 59 heat
dehumidifier pump Heat transmission coefficient,
horsepower see transmission coefficient L
table 60 U
percent addition to grand High altitude Lights, heat gain from, see heat
total heat apparatus dewpoints gain, internal
percent addition to room table 66
sensible and latent heat load calculation
return air duct heat gain Hooded appliances, see heat M
chart 3 gain, internal
return air duct leakage gain Moisture absorption, heat gain
safety factor to room from, see heat gain, internal
sensible and latent heat I Motors, heat gain from, see heat
supply air duct heat gain gain, internal, and heat
chart 3 gain, system
supply air duct leakage loss Industrial process design
Heating and dehumidification, conditions, inside design
see sorbent dehumidifiers table 5 0
Heating and humidification Infiltration
with sprays, see spray air density difference On-off control of air handling
processes offsetting with outdoor air, equipment, for partial load
Heating load estimate summer Control
form table 42
Heat loss stack effect, thru windows On-off control of refrigeration
thru basement floors and and doors summer equipment, for partial load
walls in the ground table 41 control
tables 35 thru 37 summer, crack method Outdoor design conditions
Heating table 44 corrections for time of day
with coils, see coil winter table 2
processes table 43 corrections for time of year
with sorbent dehumidifiers, winter, crack method table 3
see sorbent dehumidifiers table 44 maximum design, summer
with sprays, see spray wind velocity effect normal design, summer
processes Inside design conditions normal design, winter
Heat storage factory comfort summer and winter
factors for solar heat gain table 4 table 1
thru glass, bare or external industrial process
shade table 5
table 8, 24-hour operation summer and winter comfort P
table 10, 16-hour operation table 4
table 11 ,12-hour operation Insulated cold pipe Partial load control
factors for solar heat gain heat gain from, see heat bypass control
thru glass, internal shade gain, internal on-off control of air handling
table 7, 24-hour operation transmission coefficient for, equipment
table 9, 16-hour operation see transmission coefficient on-off control of refrigeration
table 11, 12-hour operation U equipment
factors -for space Insulated pipe refrigeration capacity
temperature heat gain from, see heat control
swing gain, internal reheat control
table 13 transmission coefficient for, volume control
precooling as means of see transmission coefficient People, heat gain from, see heat
increasing storage U gain, internal
stratification of heat Internal heat gain, see heat Pipe
149
heat gain from, see heat Restaurant appliances, heat cooling and humidification,
gain internal gain from, see heat gain, with chilled spray water
transmission coefficient for, internal cooling and humidification,
see transmission coefficient Return air duct with heated spray water
U heat gain to, see heat gain evaporative cooling
Precooling, as means of system evaporative cooling used
increasing storage, 1-3 leakage loss from, see heat with a split system
Propeller fan, capacity gain, system heating and humidification
table 47 Room sensible heat factor sensible cooling
Psychrometric chart Stack effect, on infiltration
Psychrometric formulas Steam appliances, heat gain
air mixing S from all types, see heat
bypass factor gain, internal
cooling load Saturation efficiency Steel pipe
derivation of air constants for sprays heat gain from, see heat
sensible heat factor table 63 gain, internal
temperature at cooling Scheduled ventilation transmission coefficient for,
apparatus Sensible cooling see transmission coefficient
temperature for supply air to with coils, see coil U
space processes Storage load factors
Psychrometric terms with sprays, see spray internal heat gain for lights
abbreviations processes table 12, 12- and 24-hour
apparatus dewpoint, see Sensible heat factor operation
effective surface Sensible heating, with coils, see solar heat gain thru glass,
temperature coil processes bare
table 65, standard Shading glass or external shade
conditions from reveals, overhangs, table 8, 24-hour operation
table 66, high altitude fins and adjacent buildings table 10, 16-hour operation
bypass factor chart 1 table 11, 12-hour operation
table 61, coil equipment table 18 solar heat gain thru glass,
effective sensible heat Solar altitude angles internal shade
factor effective surface table 18 table 7, 24-hour operation
temperature Solar azimuth angles table 9, 16-hour operation
grand sensible heat factor table 18 table 11, 12-hour operation
partial load control Solar heat gain, see heat gain, space temperature swing
required air quantity solar table 13
room sensible heat factor Sorbent dehumidifiers liquid Storage of heat
saturation efficiency absorbent building structures
table 63, sprays solid adsorbent constant space temperature
sensible heat factor Space precooling, as means of diversity of cooling loads
symbols increasing heat storage table 14
Pump, heat gain from, see heat Space temperature swing equipment operating
gain, system storage factors periods
table 13 heat stratification
Spray characteristics precooling space
R saturation efficiency Stratification of heat
table 63 Summer infiltration, see
Refrigeration capacity control, Spray processes infiltration
for partial load control adiabatic saturation Summer inside design
Reheat control, for partial load cooling and conditions,
Relative humidity, room, dehumidification see design conditions
maximum, without cooling Summer outdoor design
condensation, and dehumidification conditions, see design
chart 2 with all outdoor air conditions
150
Sun load, heat gain due to, see table 26 scheduled
heat gain, solar pipes, bare steel standards
Supply air duct table 54 table 45
heat gain to, see heat gain, pipes, ice coated, in water Volume control, for partial load
system leakage loss from, see table 38
heat gain, system pipes, immersed in water or
System heat gain, see heat brine
gain, system table 39 W
Symbols, see psychrometric pipes, insulated
terms, table 55 Water surface, heat gain from
pipes, insulated cold See heat gain internal
table 56 Water vapor transmission
T roofs, flat, covered with air space
built-up roofing table 40
Tanks table 27 building materials and
heat gain from, see heat table 32 structures
gain, internal roofs, pitched table 40
transmission coefficient for, table 28 ceilings
see transmission coefficient skylights table 40
U table 33 floors
Temperature swing, see heat tanks, uninsulated table 40
storage table 57 insulating materials
Thermal resistance R walls, frame table 40
air space and film table 25 packaging materials
table 34 walls, glass block table 40
building materials table 33 paint films
table 34 walls, industrial, light table 40
insulating materials construction paper
table 34 table 23 table 40
Transmission coefficient U walls, masonry paper, sheathing
air spaces table 2 table 40
table 31 walls, masonry, in ground partitions
ceilings, masonry table 35 table 40
construction, walls, masonry veneer roofs
table 29 table 22 table 40
table 30 windows roofing felt
doors table 33 table 40
table 33 walls
floors, frame construction table 40
table 29, U Window infiltration, see
heat flow up infiltration
table 30 Uninsulated tanks Wind velocity, effect on
heat flow down heat gain from, see heat infiltration, see infiltration
floors, masonry construction gain, internal Winter infiltration, see infiltration
table 29 transmission coefficient for, Winter inside design conditions,
table 30 see ransmission coefficient see design infiltration
floors, masonry, in ground U Winter outdoor design
table 35 conditions
insulation see design conditions
table 31
table 32
partitions, frame V
table 25
partitions, masonry Ventilation
151
Fig. 1 - Air Conditioning Load Estimate
Fig. 2 – Heating Load Estimate
Fig. 3 – Actual Cooling Load, Solar Heat Gain, West Exposure, Average Construction
Fig. 4 – Actual Cooling Load from Fluorescent Lights, Average Construction
Fig. 5 – Actual Cooling Load, Solar Heat Gain Lights, Average Construction
Fig. 6 – Pulldown Load, Solar Heat Gain, West Exposure, 16 Hour Operation
Fig. 7 – Actual Cooling Load, Solar Heat Gain, West Exposure, 16-hour Operation
Fig. 8 – Pulldown Load, Solar Heat Gain, West Exposure, 12 Hour Operation
Fig. 9 – Actual Cooling Load, Solar Heat Gain, West Exposure, 12-hour Operation
Fig. 10 – Actual Cooling Load from Fluorescent Light,12 and-16 hour Operation
Fig. 11 – Actual Cooling Load With Varying Room Temperature
Fig. 12 – Reaction on Solar Heat (R), Ordinary Glass, 30° Angle of Incidence
Fig. 13 – Reaction on Solar Heat (R), Ordinary Glass, 80° Angle of Incidence
Fig. 14 – Window Areas
Fig. 15 - Reaction on Solar Heat (R), 52% Heat Absorbing Glass, 30° Angle of Incidence
Fig. 16 - Reaction on Solar Heat (R),1 ⁄4 – Inch Plate Glass, White Venetian Blind, 30° Angle of Incidence
Fig. 17 - Reaction on Solar Heat (R),1 ⁄4 – Inch Plate Glass, White Venetian Blind, 1 ⁄4 – Inch Plate
Glass, 30° Angle of Incidence
Fig. 18 – Solar Angles
Fig. 19 – Shading by Wall Projections
Fig. 20 – Shading of Building by Adjacent Building
Fig. 21 – Shading of Reveal and Overhang
152
Fig. 22 – Solar Heat Absorbed in First Slice
Fig. 23 – Behavior of Absorbed Solar Heat during Second Time Interval
Fig. 24 - Behavior of Absorbed Solar Heat during Third Time Interval
Fig. 25 - Behavior of Absorbed Solar Heat during Second Time Interval plus Additional Solar Heat Absorbed
during This Interval
Fig. 26 - Behavior of Absorbed Solar Heat during Third Time Interval plus Additional Solar Heat Absorbed during
This Interval
Fig. 27– Outdoor wall
Fig. 28 – Condensation Within Frame Wall
Fig. 29 - Condensation on Window Surface
Fig. 30 – Conversion of Electric Power to Heat and Light With Incandescent Lights, Approximate
Fig. 31 – Conversion of Electric Power to Heat and Light With Fluorescent Lights, Approximate
Fig. 32 – Skeleton Psychrometric Chart
Fig. 33 – Typical Air Conditioning Process Traced on a Standard Psychrometric Chart
Fig. 34 – RSHF Line Plotted Between Room and Supply Air Conditions
Fig. 35 – RSHF Line Plotted on Skeleton Psychrometric Chart
Fig. 36 – GSHF Line Plotted Between Mixture Conditions to Apparatus and Leaving Condition From Apparatu
Fig. 37 – GSHF Line Plotted on Skeleton Psychrometric Chart
Fig. 38 – RSHF and GSHF Lines Plotted on Skeleton Psychrometric Chart
Fig. 39 – RSHF and GSHF Lines Plotted with Supplementary Load Line
Fig. 40 – Relationship of Effective Surface Temp to Supply Air and Chilled Water
Fig. 41 – RSHF and GSHF Lines Plotted on Skeleton Psychrometric Chart
Fig. 42 – RSHF, GSHF and ESHF Lines Plotted on Skeleton Psychrometric Chart
Fig. 43 – ESHF Lines Plotted on Skeleton Psychrometric Chart
Fig. 44 – Air Conditioning Load Estimate
Fig. 45 – Bypassing Mixture of Outdoor and Return Air
Fig. 46 – Bypassing Return Air Only or No Fixed Bypass
Fig. 47 – Entering and Leaving Conditions at Apparatus
Fig. 48 – Coil Processes
Fig. 49 – Coil and Dehumidification
Fig. 50 – Cooling and Dehumidification with High Latent Load
Fig. 51 – Cooling and Dehumidification Adding No Moisture to the Space
Fig. 52 – Cooling and Dehumidification Adding Moisture Into the Space
Fig. 53 – Sensible Cooling
153
Fig. 54 – Spray Processes
Fig. 55 – Evaporative Cooling, With Varying Saturation Efficiency
Fig. 56 – Evaporative Cooling, With Auxiliary Sprays Within the Space
Fig. 57 – Heating and Humidification, With Heating Spray Water
Fig. 58 – Sorbent Dehumidification Processes
Fig. 59 – Psychrometrics of Reheat Control
Fig. 60 – Psychrometrics of Bypass Control With Return Air Only
Fig. 61 – Schematic Sketch of Bypass Control With Return Air Only
154
TABLE 1 – OUTDOOR DESIGN CONDITIONS – SUMMER AND WINTER
TABLE 1 – OUTDOOR DESIGN CONDITIONS – SUMMER AND WINTER (CONT.)
TABLE 1 – OUTDOOR DESIGN CONDITIONS – SUMMER AND WINTER (CONT.)
TABLE 1 – OUTDOOR DESIGN CONDITIONS – SUMMER AND WINTER (CONT.)
TABLE 1 – OUTDOOR DESIGN CONDITIONS – SUMMER AND WINTER (CONT.)
TABLE 1 – OUTDOOR DESIGN CONDITIONS – SUMMER AND WINTER (CONT.)
TABLE 1 – OUTDOOR DESIGN CONDITIONS – SUMMER AND WINTER (CONT.)
TABLE 1 – OUTDOOR DESIGN CONDITIONS – SUMMER AND WINTER (CONT.)
TABLE 2 – CORRECTION IN OUTDOOR DESIGN TEMPERATURES FOR TIME OF DAY
TABLE 3 – CORRECTION IN OUTDOOR DESIGN TEMPERATURES FOR TIME OF DAY
TABLE 4 – RECOMMENDED INSIDE DESIGN CONDITIONS∗-SUMMER AND WINTER
TABLE 5 – TYPICAL INSIDE DESIGN CONDITIONS-INDUSTRIAL
TABLE 5 – TYPICAL INSIDE DESIGN CONDITIONS-INDUSTRIAL (Contd)
TABLE 6 – PEAK SOLAR HEAT GAIN THRU ORDINARY GLASS∗
TABLE 7 – STORAGE LOAD FACTORS, SOLAR HEAT GAIN THRU GLASS
TABLE 8 – STORAGE LOAD FACTORS, SOLAR HEAT GAIN THRU GLASS
TABLE 9 – STORAGE LOAD FACTORS, SOLAR HEAT GAIN THRU GLASS
TABLE 10 – STORAGE LOAD FACTORS, SOLAR HEAT GAIN THRU GLASS
TABLE 11 – STORAGE LOAD FACTORS, SOLAR HEAT GAIN THRU GLASS
TABLE 12 – STORAGE LOAD FACTORS, HEAT GAIN –LIGHT∗
TABLE 13 – STORAGE FACTORS, SPACE TEMPURATURE SWING
TABLE 14 – TYPICAL DIVERSITY FACTORS FOR LARGE BUILDINGS
TABLE 15 – SOLAR HEAT GAIN THRU ORDINARY GLASS
155
TABLE 15 – SOLAR HEAT GAIN THRU ORDINARY GLASS (Contd)
TABLE 15 – SOLAR HEAT GAIN THRU ORDINARY GLASS (Contd)
TABLE 15 – SOLAR HEAT GAIN THRU ORDINARY GLASS (Contd)
TABLE 15 – SOLAR HEAT GAIN THRU ORDINARY GLASS (Contd)
TABLE 15 – SOLAR HEAT GAIN THRU ORDINARY GLASS (Contd)
TABLE 16 – OVER-ALL FACTORS FOR SOLAR HEAT GAIN THRU GLASS
TABLE 17 – SOLAR HEAT GAIN FACTORS FOR GLASS BLOCK
TABLE 18 – SOLAR ALTITUDE AND AZIMUTH ANGLES
TABLE 19 – EQUIVALENT TEMPERATURE DIFFERENCE (DEG F)
TABLE 20 – EQUIVALENT TEMPERATURE DIFFERENCE (DEG F)
TABLE 20 A – CORRECTIONS TO EQUIVALENT TEMPERATURES (DEG F)
TABLE 21 – TRANSMISSION COEFFICIENT U-MASONRY WALLS ∗
TABLE 22 – TRANSMISSION COEFFICIENT U-MASONRY VENEER WALLS ∗
TABLE 23 – TRANSMISSION COEFFICIENT U-LIGHT CONSTRUCTION, INDUSTRIAL WALLS ∗
TABLE 24 - TRANSMISSION COEFFICIENT U-LIGHTWEIGHT, PREFABRICATED CURTAIN TYPE WALLS ∗
TABLE 25 - TRANSMISSION COEFFICIENT U-FRAME, WALLS AND PARTITIONS∗
TABLE 26 - TRANSMISSION COEFFICIENT U-MASONRY PARTITIONS∗
TABLE 27 - TRANSMISSION COEFFICIENT U-FLAT, ROOFS COVERED WITH BUILT-UP ROOFING ∗
TABLE 28 - TRANSMISSION COEFFICIENT U-PITCHED ROOFS ∗
TABLE 29 - TRANSMISSION COEFFICIENT U-CEILING AND FLOOR, (Heat Flow Up)
TABLE 30 - TRANSMISSION COEFFICIENT U-CEILING AND FLOOR, (Heat Flow Up)
TABLE 31 - TRANSMISSION COEFFICIENT U-WITH INSULATION & AIR SPACES
TABLE 32 - TRANSMISSION COEFFICIENT U-FLAT ROOFS WITH ROOF-DECK INSULATION
TABLE 33 - TRANSMISSION COEFFICIENT U-WINDOWS, SKYLIGHTS, DOOR&GLASS BLOCKWALLS -DECK
INSULATION
TABLE 34 – THERMAL RESISTANCES R-BUILDING AND INSULATING MATERIALS
TABLE 34 – THERMAL RESISTANCES R-BUILDING AND INSULATING MATERIALS (Contd)
TABLE 34 – THERMAL RESISTANCES R-BUILDING AND INSULATING MATERIALS (Contd)
TABLE 35 – TRANSMISSION COEFFICIENT U-MASONRY FLOORS AND WALL IN GROUP
TABLE 36 – PERMITER
TABLE 37 – GROUND TEMPERATURES
TABLE 38 – TRANMISSION COEFFICIENT U-ICE COATED PIPES IN WATER
156
TABLE 39 – TRANMISSION COEFFICIENT U-PIPES IMMERSED IN WATER OR BRINE
TABLE 40 – WATER VAPOR TRANSMISSION THRU VARIOUS MATERIALS
TABLE 40 – WATER VAPOR TRANSMISSION THRU VARIOUS MATERIALS (Contd)
TABLE 41 – INFILTRATION THRU WINDOWS AND DOORS-SUMMER∗
TABLE 41 – INFILTRATION THRU WINDOWS AND DOORS-SUMMER∗ (Contd)
TABLE 42 – OFFSETTING SWINGING DOOR INFILTRATION WITH OUTDOOR AIR-SUMMER
TABLE 43 – INFILTRATION THRU WINDOWS AND DOORS-WINTER ∗
TABLE 44 – INFILTRATION THRU WINDOWS AND DOORS-CRACK METHOD-SUMMER-WINTER ∗
TABLE 44 – INFILTRATION THRU WINDOWS AND DOORS-CRACK METHOD-SUMMER-WINTER ∗ (Contd)
TABLE 45 – VENTILATION STANDARDS
TABLE 46 – CENTRIFUGAL FAN CAPACITIES
TABLE 47 –PROPELLER FAN CAPACITIES-FREE DELIVERY
TABLE 48 – HEAT GAIN FROM PEOPLE
TABLE 49 – HEAT GAIN FROM LIGHTS
TABLE 50 – HEAT GAIN FROM RESTAURANT APPLIANCES
TABLE 51 – HEAT GAIN FROM RESTAURANT APPLIANCES
TABLE 52 – HEAT GAIN FROM MISCELLANEOUS APPLIANCES
TABLE 53 – HEAT GAIN FROM ELECTRIC MOTOR
TABLE 54 – HEAT TRANSMISSION COEFFICIENTS FOR BARE STEEL PIPES
TABLE 55 – HEAT TRANSMISSION COEFFICIENTS FOR INSULATED PIPES
TABLE 56 – HEAT TRANSMISSION COEFFICIENTS FOR INSULATED COLD PIPES
TABLE 57 – HEAT TRANSMISSION COEFFICIENTS FOR UNINSULATED TANKS
TABLE 58 – EVAPORATION FROM A FREE WATER SURFACE-LATENT HEAT GAIN
TABLE 59 – HEAT GAIN FROM AIR CONDITIONING FAN HORSEPOWER, DRAW-THRU SYSTEM
TABLE 60 – HEAT GAIN FROM DEHUMIDIFIER PUMP HORSEPOWER
TABLE 61 – TYPICAL BYPASS FACTORS
TABLE 62 – TYPICAL BYPASS FACTORS
TABLE 63 – TYPICAL SATURATION EFFICIENCY
TABLE 64 – MAXIMUM RECOMMENDED MOISTURE ADDED TO SUPPLY AIR
TABLE 65 – APPARATUS DEWPOINTS
TABLE 65 – APPARATUS DEWPOINTS (Continued)
TABLE 65 – APPARATUS DEWPOINTS (Continued)
TABLE 66 – EQUIVALENT EFFECTIVE SENSIBLE HEAT FACTORS FOR VARIOUS ELEVATIONS∗
157
CHART 1 - SHADING FROM REVEALS OVERHANGS, FINS AND ADJACENT BUILDINGS (1-57)
CHART 2 – MAXIMUM ROOM RELATIVE HUMIDITY WITHOUT CONDENSATION (1-88)
CHART 3 – HEAT GAIN TO SUPPLY DUCT (1-110)
158
159
160
161
162
Cooling load components:
✓ External sources
o Heat gain through glass due to conduction
o Heat gain through glass due to radiation
o Heat gain through skylight ( conduction & reflection)
o Heat gain through wall (sensible heat)
o Heat gain through door ( sensible heat)
o Heat gain through roof ( sensible heat)
o Heat gain through roof ( Sensible heat)
o Heat gain through partition, floor and ceiling due to conduction (sensible heat)
o Heat gain through ventilation due to convection ( Sensible & Latent heat)
o Heat gain through ventilation due to convection ( sensible & latent heat)
Note: Infiltrations termed for the unwanted air coming inside conditioned space due to
opening of doors
✓ Internal sources
o Heat gain through lighting ( sensible heat)
o Heat gain through people ( Sensible and latent heat)
o Kitchen appliances – rice cooker, coffee maker etc
Condition
U Value :
Thermal transmittance is the rate of transfer of heat through matter. The thermal transmittance of a
material (such as insulation or concrete) or an assembly (such as a wall or window) is expressed as a
U-value.
Although the concept of U-value (or U-factor) is universal, U-values can be expressed in different
units. In most countries, U-value is expressed in SI units, as watts per square metre-kelvin: W/(m2⋅K)
In the United States, U-value is expressed as British thermal units (Btu) per hour-square feet-degrees
Fahrenheit: Btu/(h⋅ft2⋅°F)
R Value:
www.bryair.com
Providing Complete Environmental
Control Systems to the World
Dehumidifiers for all Applications
Including but not limited to:
Ammunition Storage
• Military Applications
•
Archives
• Military Equipment Storage
•
Breweries
• Milk Powder
•
Candy Manufacturing
• Museums
•
Chemicals
• Optical (Polishing)
•
Chocolates
• Pharmaceuticals
•
Clean Rooms
• Photographic Materials
•
Computer Rooms
• Plant Lay-up
•
Corrosion Control
• Plastics
•
Defence Equipments
• Powder Storage
•
Electronics
• Pumping Stations
•
Fertilizers
• Razor Blades
•
Films
• Safety Glass
•
Food & Food Packaging
• Seed Drying
•
Glass Laminating
• Semiconductor Components
•
Hospitals
• Ship Lay-up
•
Ice Rinks
• Snack Foods
•
Indoor Arenas
• Steel-Belted Tyres
•
Laboratories
• Tea & Coffee
•
Leather
• Tyre & Rubber Manufacturing
•
Libraries
• Typewriter Ribbons (Coating)
•
Lithium Chloride Batteries
• Water & Waste Water
•
Machine Parts
• Welding Electrodes
•
Marine
• Wood Drying
•
TABLE OF CONTENTS Page
Introduction: Meet Bry-Air 1
The purpose of this manual 1
WHAT IS RELATIVE HUMIDITY? 2
PART ONE — USES OF DRY AIR 3
Food production 3
Pharmaceutical production 3
Industrial chemicals production 3
Humidity control of warehouse storage 4
Humidity control of rooms where equipment is operating 4
Humidity control of packaging equipment rooms 4
Organic product dehydration 4
Inorganic product 4
The effects of condensation 4
Hygroscopic raw materials storage 5
Marine and land-based sandblasting 5
Power plant and marine lay-up 5
PART TWO — HOW TO PRODUCE DRY AIR 6
Using compression to dry air 6
Using reduced temperatures to dry air 6
Using desiccants to dry air 6
PART THREE — CONSTRUCTION OF CONTROLLED SPACE 7
The nature of water vapor 7
Construction considerations 7
PART FOUR — CALCULATING THE VARIOUS MOISTURE LOADS 8
Calculate the permeating load through a structure 9
Moisture through intermittent openings 9
Moisture through fixed openings 10
Moisture originating in the controlled space 11
Ventilating air-vapor load 11
PART FIVE — SIZING THE DEHUMIDIFIER 12
Example I: Production of hard candy 12
Example II : Standby warehouse 17
Example III : Product drying 20
Example IV : Controlled humidity and temperature areas 24
Example V : Production of dry air for a specific purpose 28
Example VI : Water treatment plants 28
Example VII : Zero leak system for a low humidity space 29
PART SIX — BRY-AIR DEHUMIDIFIERS FOR PRODUCT DRYIN 30
Sizing the desiccant dehumidifier 31
Dehumidifier capacity control 34
APPENDICES
Appendix I, Processes and properties of air 35
Appendix II, Dehumidifier survey sheet 39
Appendix III, Determining moisture or latent loads 40
Appendix IV, Typical performance curves 44
Appendix V, Typical application standards 45
Appendix VI, Charts and miscellaneous formulas 48
www.bryair.com
INTRODUCTION: MEET BRY-AIR
Bry-Air (Asia) is an ISO 9001:2008 and ISO research and R&D in moisture control, air
14001:2004 certified company specializing in treatment and optimisation of energy usage. A
technologies and products with desiccants at the pioneer in the field of dehumidification, Bry-Air
core in relation to air. Bry-Air is known world wide has maintained the initiative, searching for new
for its expertise as a “solutions” company for ways to bring the benefits of research to satisfy
moisture and humidity control. customer needs. Bry-Air is the inventor of the
Today, Bry-Air (Asia) has a global presence Rotary Silica Gel Dehumidifier.
with a wide range of “airgineering” equipment, The latest innovation from Bry-Air is the Green
strong brands and a world wide global network . Dehumidifier 'EcoDry' incorporating the
Bry-Air (Asia) has wholly owned subsidiaries in innovative BRYSMART EMS (Energy
Malaysia, China and Germany, a licensee in Management System) (patent pending) which
Brazil and is the only Indian HVAC& R Company will allow energy savings up to 45%. This is the
to acquire an overseas dehumidification firm, 9th patent to the credit of the Bry-Air Group.
A+H, Hamburg, Germany. The China operations Our Range
have 4 offices in Shanghai, Beijing, Guangzhou
and Wuhan. Bry-Air also has representative Operating within a broad framework of
offices in Bangkok-Thailand, Johannesburg- “Environment and Energy”, Bry-Air today is a
South Africa, Perth-Australia, Muntinlupa- multi-product, multi-location company with plant
Philippines, Jakarta-Indonesia and Istanbul- locations in India, Malaysia, China, Brazil,
Turkey and office and warehouse in Sharjah- Germany and USA. The company's plants are
UAE amongst the most modern ones, supported by
computerized 3D designing, CNC fabricated and
HOW IT ALL BEGAN powder coating facilities and automated
….in USA conveying system.
In 1963, Arthur G. Harms, a Bryant sales The range of products manufactured by Bry-Air
representative decided to buy the Bryant division are:
of Carrier-Air Conditioning Corporation. Shortly • Desiccant Dehumidifiers
after the acquisition, Bry-Air began • Air and Gas Purification Systems,
manufacturing in Sunbury, Ohio. • Tray Dryers
...in India • Drying, Conveying & Blending equipments
• Flexible Barrier Storage Systems and
In India, it all started almost 30 years ago with the
• Complete Environmental Control Systems.
setting up of Arctic India Sales in 1979 as a
marketing company for environmental control Our Customers
products. Arctic India Sales started out by Our customers are from a plethora of industries
representing Bry-Air Inc. USA for its dehumidifier and our dehumidifiers are effectively being
in India. In 1981, it promoted the first joint venture employed in production, processing, storage and
in a small scale sector, Bry-Air India (Now Bry-Air packaging in: pharmaceuticals, chemicals,
Asia) with Bry-Air Inc. USA to become the first defense, safety glass, food and drinks, seeds,
dehumidifier manufacturing company, east of the fertilizer, paper and printing, plastics, wood ,
Suez. leather , cement etc. The products
Research and Development manufactured by Bry-Air are not only sold in the
Indian Market through its network, own direct
Bry-Air has always been in the forefront of
sales and service offices, but also exported to
technology and innovation through extensive
over 40 countries all over the world.
1
and dry air, plus details on the use of scenario. (For assistance in choosing the
dehumidifiers in numerous industrial dehumidifier to meet your particular needs, please
environments are incorporated in Manual. contact the dehumidifier experts at Bry-Air.)
Several real-life situations are also detailed. We at Bry-Air hope that this Manual will be of
Calculations help illustrate how to choose the significant assistance to all who consider
most suitably sized dehumidifier in each dehumidified air as a necessity.
RH
RH
RH
RH
2
PART ONE: USES OF DRY AIR
In many manufacturing processes, humidity In processing such powdery foods as cocoa,
control is necessary to completing a particular gelatin, and dehydrated concentrates, the
process successfully. Because failure of a presence of moisture in the surrounding
process can be directly tied to humidity level atmosphere can cause tiny particles of the
control, it is vital to know: powder to stick or cluster together, thus inhibiting
their free flow in manufacturing or packaging
·What equipment is available processes.
·How to choose appropriately sized Processing machinery can also be affected by
equipment moisture in the air, which can interfere with
·How to effectively use the equipment to operation and obstruct the free and easy
control moisture in the process area movement of the foodstuff.
Since dry air may be desired for many Obviously, when moisture can have such a
commercial applications, and specific problems profound effect on food and/or machinery, the
encountered may be as complex as the solution lies in conditioning the air surrounding
atmosphere itself, three important steps are the the processing and manufacturing area.
focus of this booklet: how to select, size, and PHARMACEUTICAL PRODUCTION
apply the correct Bry-Air Dehumidifier. Consider
the following dozen typical situations. Rapid technological advances in the
pharmaceutical industry have focused attention
FOOD PRODUCTION on a vast number of moisture control issues. For
When exposed to high relative humidity, such example, the presence or absence of a specific
familiar foods as potato chips, dry breakfast amount of moisture in the processing area may
cereals, and soda crackers exhibit an affinity for be required to grow certain organic cultures. Or,
water. These and similar foodstuffs are the presence of moisture may be absolutely
manufactured using high temperature necessary for the manufacture of a particular
processes, so we expect that excess water has drug. Similarly, the absence of moisture may be
been driven out and the foods are dry. However, equally imperative for the production of some
if these foodstuffs are allowed to remain exposed other drug. Strict control of moisture is a key
in a humid environment, even for a short time, factor in the manufacture of most drugs and
they will absorb water from the surrounding air. medicines.
Although the quality is not affected, these foods As with foodstuffs, many materials used to
characteristically become soggy and rubbery produce pharmaceuticals have a physical affinity
and generally not very appetizing. for moisture. This can cause lumping or caking of
powdered material. Further, some powders that
are bound into a capsule or formed into a tablet
under high pressures will adhere only when in a
dry state, Humidity can cause a tablet to crumble,
and in some cases, it can cause the drug to
decompose and diminish in its therapeutic value.
To assure consistently high quality drugs, the
processing area and machinery must be
surrounded by air whose dryness is accurately
known and controlled.
INDUSTRIAL CHEMICAL PRODUCTION
The same sort of lumping and caking of
powdered substances previously discussed is
also a major problem in industrial chemical
production. Some chemicals decompose in the
Controlled humidity is vital to successful storage of seeds presence of water vapor. In other situations,
and grain, and for food and pharmaceutical production
3
water vapor can actually cause a chemical Frequently, the equipment used to package
reaction that changes the character of the products will not function efficiently or properly if
product. the surrounding air is humid. Candy wrapping
machines and packaging machines for food
Atmospheric moisture is also a natural enemy to
powders or drug packets are typical examples.
many grinding and pulverizing operations. Water
Something as simple as a cake mix becomes a
vapor in contact with the product can make it
double problem; not only does the powdery mix
resilient and difficult to grind, causing it to cling to
clump and not flow properly in humid conditions,
the grinding machine and defy pneumatic
but the packaging equipment is also hindered by
conveyance from one process area to another.
the humidity.
HUMIDITY CONTROL OF WAREHOUSE
Depending on the product, it may be necessary
STORAGE to dry the packaging room and even go to the
Although mildew, rust, and corrosion are the extreme of providing a dry bath for storage bins or
enemies of goods in storage, they cease being hoppers, especially where powders are used. In
threats when the moisture is substantially situations where packages are heat-sealed, a
reduced in the storage area. Generally, an container's own moisture content may adversely
atmosphere of less than 40% RH keeps these affect the adhesion of the sealing material being
degradative processes dormant. used. Here neither the product nor the machinery
is directly responsible for the problem; instead,
Maintaining a dormant state is also important for the moisture content of the package is the culprit.
seed storage. For example, if corn seeds are Surrounding the area with dry air is the solution.
stored in ambient conditions, it's possible that as
few as 7% will germinate the following season. ORGANIC PRODUCT DEHYDRATION
Contrast that to seeds stored in a controlled
Organic products are particularly challenging
environment; they usually germinate in the 90%
because of their high degree of affinity for water.
range.
Unfortunately, it is often impossible to use heat to
HUMIDITY CONTROL OF ROOMS WHERE release this water because heat can have a
EQUIPMENT IS OPERATING damaging effect.
In many instances, moisture is detrimental to Dry, relatively cool air can be used to dry organic
functioning of electrical or mechanical devices. materials, but it must be circulated under varying
Thousands of electrical relays may be velocities, and this creates the problem of special
threatened by pitting due to excessive arcing handling that is required with finely divided
under high humidity conditions. Also, the particles, for example.
presence of water vapor may corrode the contact
INORGANIC PRODUCT DEHYDRATION
points of infrequently operated electrical
conductors resulting in poor closure of electrical Inorganic products are generally easier to dry
circuits. In extreme cases, there may be no than organic products because heat can be used
closure at all. as a drying agent. However, many inorganic
compounds absorb large quantities of water.
In other such places as radar stations and
This is not water of crystallization- that is, it does
industrial applications, electronic equipment is
not enter the lattice structure of the compound-
also subject to loss of efficiency and high
but it is nonetheless tightly held by the
maintenance costs when exposed to humid
compound. When water of crystallization is
conditions. And for work environments
involved, even the use of heat can be
containing computers and other data processing
impractical… or damaging.
systems, humidity control is essential for
assuring proper equipment function, Where But for most inorganic products, dry air may
practical, maintenance of dry enclosures may be enhance operational efficiency and product
necessary, Sometimes, it may be necessary to quality.
condition the equipment itself, since electrical
THE EFFECTS OF CONDENSATION
operating devices are often enclosed in their own
metal cases. Moisture sweating, particularly on moving parts,
can be very detrimental. For example sweating
HUMIDITY CONTROL OF PACKAGING
occurs as equipment is being cooled in polymer
EQUIPMENT ROOMS injection molding operations. Because molds are
4
artificially chilled, dehumidified air must be used exposes the base material-often metal-that will
to surround them, or condensation will form… receive a protective coating.
and water is one item that must be avoided here.
Inside ships, or in underground or land-based
Another example is the water pumping station storage tanks, a flow of dehumidified air on the
whose numerous valves, fittings and other parts newly prepared surfaces prevents rust or mildew
may become rusty and need periodic painting or formation while clean-up occurs and the coating
replacement. In a large facility, a major effort of step is prepared. Usually the dry air is forced
repainting, replacement, and mopping up may be inside the structure via normal ventilation lines.
necessary to deal with condensed water.
POWER PLANT AND MARINE LAY-UP
Insulating the pipes helps reduce the amount of
When a nuclear power plant is shut down for
dripping condensate. However, valves and other
refueling-a process that can take a whole year-
such fittings that remain uninsulated present a
dehumidified air can keep such non-nuclear
constant maintenance problem.
components as boilers, condensers, and
Dry air in the pumping station and pipe gallery turbines rust free.
provides a solution.
For fossil fuel power stations, the laying-up
HYGROSCOPIC RAW MATERIALS process is usually part of putting power
STORAGE production on hold. Here the reason may be for
furnace or boiler repair or the lay-up might be due
When such hygroscopic raw materials as rubber
to less expensive power becoming available from
and plastic are used, process difficulties can
a nearby source. During these periods, a flow of
occur in a humid atmosphere. Moulded products
dehumidified air in the facility is used to prevent
made of these materials can develop “air”
rust or other harmful, moisture-related problems.
pockets caused by stress; other imperfections
can result from moisture adsorbed by the raw Ships can also be layed-up. Some are
materials. In automobile production, it may be “mothballed” for indefinite storage. Many such
virtual impossibility to vulcanize tyre cord to vessels are later reactivated, cleaned-up, and set
rubber when the cord contains moisture. to sea. During the interim, dehumidified air keeps
rust, mildew, and corrosion from ruining the
Dry Air used for storage and possibly in the
engine room, cargo holds, and living or working
production area can alleviate this situation.
quarters.
MARINE AND LAND-BASED BLASTING Other ships are part of the “ready fleet”-anchored
In marine and land-based applications, at sea, fully equipped, and ready for a crew to
sandblasting removes surface damage and come on board and set sail almost immediately.
These, too, are protected by a steady flow of
dehumidified air that is continuously pumped
throughout the vessel.
5
PART TWO:
HOW TO PRODUCE DRY AIR
Because the amount of water that can be causes ice to form, which, in turn, reduces the
contained in air is a function of the temperature efficiency of the cooling system. So anti-icing
and pressure of that air, our next step is to look at devices or duel systems and defrost cycles may
ways to remove moisture by changing the be required.
temperature or pressure.
To prevent such cooling coil icing, a brine spray is
USING COMPRESSION TO DRY AIR commonly used. The brine must be reconstituted
periodically or continuously. This requires
As air is compressed, the dew-point or
additional equipment, maintenance and
temperature at which water will condense is
operating costs. Although this strategy is
raised. Therefore, to get dry air we need to find a
workable and often satisfactory, the complexities
way to cool the compressed air. But costs can be
associated with cycling and controlling are
prohibitive because equipment, space, and
detracting factors.
auxiliary equipment are necessary for the
process. However, if compressed air is already A special case involves a brine spray that can
used in the primary operation and only very small pick up moisture from the air at normal
amounts of dry air are needed for humidity temperatures. This brine must be cooled and
control, compression may be a feasible route to regenerated or reconcentrated either
dry air. continuously or periodically. To deliver air at very
low moisture, such a system is necessarily
When air at extremely high pressure (over 200
complex. For example, the brine must be
lb/sq in) is needed, small quantities of high
mechanically refrigerated, and at all levels of
pressure air may be used to maintain small
drying, cooling must be used during the moisture
enclosures at the required moisture level. It is
absorbing cycle and after the regenerating or
also possible to use small amounts of the high
reconstituting cycles.
pressure air with a smaller air facility to control
moisture on a limited scale. USING DESICCANTS TO DRY AIR
USING REDUCED TEMPERATURES TO DRY The most simple, straightforward way to obtain
AIR dry air is to use desiccants-that is, adsorbants or
materials that have a natural affinity for water. A
Lowering air temperature decreases the air's desiccant is able to take up the additional
ability to hold moisture. Thus, the air can be made moisture given up by the air without changing its
drier by cooling it. However cooling air just to dry size or shape. So as air stream can pass through
it is usually not practical. An exception might be a desiccant and become significantly drier
when cool air is needed anyhow, that air's without elaborate cooling, compression, cooling
dryness satisfies the needed moisture water, or other complex systems or controls.
conditions, and enough conditioned air is After the drying task is complete, the desiccant is
available. Normally, this method is reserved for regenerated via heat. Then the desiccant is
applications where outdoor air is being dried to ready to dry more air.
levels only slightly lower than the incoming
ambient-that is, the system air. A Bry-Air Dehumidifier utilizes only a relatively
small amount of desiccant at any one time and
To remove large amounts of water by cooling the constantly regenerates it as part of a continuous
air, over-cooling and subsequent reheating air cycle. This simple device is manufactured in two
required. But such procedures typically have designs and many sizes, from very small to very
problems with operation and maintenance, as large to meet various dry air requirements.
well as cycle and control; the method is
unsuitable for producing large quantities of dry An added feature of the Bry-Air Dehumidifier is its
air. Another limitation to this technique is the ability to function equally well at extremely low to
freezing point of water. When air is dried via very high levels of humidity with no regeneration
refrigeration, the cooling surfaces of the coils problems and no changes in cycle control. Its
may reach sub-freezing temperatures. This versatility in performing any type of application is
unique among most methods of drying air.
6
PART THREE:
CONSTRUCTION OF CONTROLLED SPACE
To prepare any space for humidity control, caulked joints are used).
certain precautions are necessary, regardless of
3. Insulation between vapor barriers can be a
the type of air drying equipment or the method
potential problem: if construction occurs in
used to do the drying.
humid weather, water can be “sealed in”
Satisfactory moisture control-better known as between the two vapor barriers.
customer satisfaction-depends on many
Sealed-in vapor will travel into the controlled
variables. Some are listed below.
space and impose an extra drying load on the
THE NATURE OF WATER VAPOR drying equipment. This extra load lasts only
until the insulation dries out, but meanwhile,
Consider two closed rooms, adjacent to one
humidity control is difficult.
another. If the partial pressure of the water vapor
in room 1 is greater than the partial pressure of If a heat source is present (even heat from
the water vapor in room 2, then the water vapor the sun), serious damage can be caused by
will travel through the wall into room 2 regardless the expanding trapped vapor. There have
of the composition of the wall. been cases when so-called “non-permeable”
materials have split open at a joint because
Let's take the hypothetical example a step
of vapor pressure. Examples include a floor
further. If the absolute humidity of the air in room
or tiled wall that has literally lifted from its
1 is greater than that of the air in room 2, then the
mounting surface because the surface was
water vapor pressure will be higher in room 1.
wet during application.
Therefore, when drying room 2, the problem of
new water coming through the wall from room 1 4. Final inside vapor barriers should be applied
must be considered. only after the enclosed area has been dried.
Drying equipment should be used to
A vapor barrier can slow down the passage of
withdraw as much moisture as possible
vapor from wet to drier areas, but it cannot keep
before the final barrier is applied. Of course,
water out; it can only slow the rate of penetration.
without a barrier in place equipment cannot
The choice of vapor barrier is based on the dry the air to design specifications, but a
degree of dryness required in the controlled significant amount of moisture can and
space, the efficiency of the equipment being should be removed before all the vapor
used for drying, and the cost of construction. barrier material is in place.
Commercial vapor barriers-moisture resistant (Although this strategy runs counter to
construction material, paints, and other coatings- most industrial planning suggestions,
offer a variety of design alternatives. the concept of drying the structure before
Manufacturers of vapor barrier materials can applying the final vapor barrier is a
supply specific information on their products. precaution that is often overlooked and
In addition to the vapor barrier, certain aspects of can help prevent customer dissatisfaction)
construction must be given careful attention. 5. All doors-service or personnel-should be
CONSTRUCTION CONSIDERATIONS weather-stripped or air-locked through
vestibules if the desired dryness warrants it.
Several techniques control the permeation of
Any crack or opening around a door will
water vapor:
admit vapor.
1. Any vapor barrier must be continuous,
When conveyor openings or similar elements
without breaks or tears.
are used, a drop curtain, shroud, or tunnel can
2. All lap joining must be tightly closed (this is restrain the movement of water vapor.
particularly critical when mechanical or
7
PART FOUR:
CALCULATING THE VARIOUS MOISTURE LOADS
The following methods have been used For standard types of construction, Bry-Air has
successfully to calculate vapor loads; replacing determined values for calculating the moisture
the extensive calculations and laboratory tests load entering a space at controlled humidity
that might otherwise be required when a designer levels. Usually these calculations are relatively
considers a new space humidity problem or easy. The following tables are aids for load
application. calculations.
Actual data from moisture loads entering a space Outside humidity levels shown in the Table 1 are
through walls, floors, and ceiling are available for deliberately higher than data for design
various moisture loads and classes of specifications. This compensates for days when
construction. A survey sheet, such as the sample the design wet-bulb temperatures are reached
in Appendix II, page 39 will help you gather data and the design dry-bulb temperatures are lower
for the needed calculations. than expected (thus creating higher total
humidity). Use the area design wet-bulb and the
TABLE I specific humidity figures shown here to
RECOMMENDED DESIGN OUTSIDE MOISTURE LEVEL accurately rate the moisture control situation.
DESIGN DESIGN Further information on design can be found in
Outside Specific Outside Specific Appendix I and in the ASHRAE Fundamentals
Wet Bulb Himidity Wet Bulb Himidity Handbook, “Weather Data and Design
°F gr/lb °F gr/lb Considerations”.
81 149 75 121
80 143 74 117
79 139 73 113
78 134 72 109
77 130 71 106
76 125 70 102
TABLE II
F1 FACTOR FOR GRAIN DIFFERENCE
Gr/lb F1
Difference Factor
35 1.0
40 1.12
50 1.35
60 1.59
70 1.82
80 2.06
90 2.29
100 2.53
110 2.76
120 3.00
Space moisture load is a combination of permeation and infiltration and both will be encountered in determining the load. Permeation is a straight
line function of the difference in interior and exterior vapor pressure (determined by gr/lb). As shown in Table III, infiltration, represented in air
changes per hour is not straight line because of the two factors involved:
1. Each pound of air entering the space will impose a moisture load determined by the difference in interior and exterior moisture content.
2. Since the vapor pressure differs as the moisture content, the vapor will move at a higher velocity than the air.
The combination of the two factors, results in the space moisture load increasing at an ever increasing rate as the difference between the interior
and exterior moisture contents increase.
In view of the above, the F-1 factor is used to adjust for the increased vapor velocity. Therefore, the combination of the F-1, and F-2 factors represent
the space moisture load anticipated from both permeation and infiltration.
TABLE IV
F3 FACTORS FOR CONTRUCTION F4 FACTORS FOR VAPOR BARRIERS
Masonry or Frame Construction 1.0 Laminated, mylar–metallic or polyethylene film 0.50
Sheet metal, steel welded 0.3 Two layers edge sealed moisture paper 0.67
Module panel, caulked and sealed 0.5 Two coats vapor proof paint 0.75
If the product of F3 x F4 is less than 0.5, use 0.5. If the room is completely vapor proofed, with continuous vapor barrier under the floor (or of all-metal,
welded material) the factor may be reduced to 0.3.
8
CALCULATE THE PERMEATING LOAD THROUGH A STRUCTURE
To determine the grains of moisture penetrating the construction into a controlled space, use the
following calculation.
V xD G x FB x FB x FB x FB = Grs/hr. (To determine grains/minute divide answer by 60).
C
= Amount of vapor able to permeate the closed space through
construction and vapor barriers.
V = volume of controlled space in question – ft.B
C = 14 = constant used to translate ft.B to pounds. This constant is used regardless of the
density of the air.
DG = difference between the grs/lb of outside air and the grs/lb desired in the controlled space.
FB = moisture difference factor (Multiplier from Table II).
FB = Permeation factor (Multiplier from Table III).
FB = Construction factor -
FB = Barrier Factor -
Table IV
Table IV {
See note with
Table IV.
The above equation can be used to solve a typical example as follows:
Problem – Find the amount of moisture that will permeate the room defined below.
Sample Calculation – Space to be controlled:
(1) Room with 12'' masonry walls.
(2) Two coats of aluminum paint as vapor barrier.
(3) Volume of room – 22,000 ft.3
(4) Outside Design: 95oF db 77oF wb (Table I Shows 130 gr/lb)
(5) Required – To hold in room – 40 gr/lb
V xD
G x FB x FB x FB x FB = Grains per hour.
C
V = 22,000
C = 14
G = 130 - 40 = 90. Problem stipulates 40 gr/lb in the room;
therefore, 130 - 40 = 90.
F1 = 2.29 From Table II (Factor for a moisture difference of 90 gr/lb).
F2 = 0.58 From Table III locate 22,000 on bottom line. Travel up and read
curve at 0.58.
F3 = 1.0 From Table IV.
F4 = .75 From Table IV - (Factor for 2 coats of paint)
9
Ohr = A xD G x F1 = Grains
C
Ohr = number of times each hour the door is opened. (If unknown assume personnel door to
be opened 2 times/hr for every occupant.)
A = area of the door opening in square feet.
C = 7 = constant
G
D = difference in specific humidity in grs/lb between controlled space and the adjacent
space. See table I for outside wb to determine adjacent specific humidity.
F1 = factor from Table II for moisture difference.
Example:
Door area – 3' x 7'
Door open - 6 times each hour
Moisture difference - 90 grs/lb
Solution:
Ohr x A x D G x F1 = grains per hour of additional load.
C
6 x 21 x 90 x 2.29 = 3710 grains per hour added to controlled space.
7
Note that if the door is open for longer periods, use the calculation scheme below.
A x 300 x D
G x F1 = grains per hour of load through fixed opening.
CxD
Where
A = Area of fixed opening in square feet,
300 = Experimental constant - velocity of vapor, ft/hr, at 35 gr difference,
C = 14 = constant factor to translate ft.3 to pounds,
D = feet = depth of opening,
DG = grains = difference in grs/lb between wet space and drier space.
F1 = Moisture Difference Factor from Table II.
Example:
Conveyor opening - 2 sq ft
Depth of opening - 1.5 sq ft
Moisture difference - 90 grains
Solution:
A x 300 x D
G x F1 = grains per hour
CxD
2 x 300 x 90 x 2.29 = 5,889 grains per hour
14 x 1.5
10
MOISTURE ORIGINATING IN THE
CONTROLLED SPACE
Moisture or vapor originating in the controlled
space comes from any of several sources,
depending on the intended use for the space.
Three basic sources of moisture are:
·Population load, including people and
animals
·Product load, brought in by the product
· Process load
Population Load
People working in an area add moisture to the air
because of breathing and the evaporation of
perspiration. When animals occupy the
controlled space, moisture release is contributed
by their excrement.
How much moisture do people or animals add to Other contributors include open stream
a controlled space? Such factors as the level of exhausts, unvented combustion cycles, and
activity and the ambient temperature, aging or curing cycles.
atmospheric pressure, and humidity are well
VENTILATING AIR-VAPOR LOAD
documented. (see Appendix III, page 40)
(VAPOR BROUGHT IN WITH OUTSIDE AIR)
For animals, weigh the amount of water
consumed during a given period and assume that Ventilating or make-up air from the outside
much water will be eliminated. contains moisture that must be removed. Some
designers add this moisture load to the total
Product Load
calculated internal load to determine the required
Any material manufactured in a controlled area capacity of the drying equipment.
can bring moisture with it and then release the
moisture into the work area. Material brought into However, Bry-Air recommends this air not be
a warehouse tends to become drier; it gives up considered part of the internal load. Rather, it
moisture over a period of time and loads the should be considered at its point of entry. If this
drying equipment accordingly. added, or make-up air from outside mixes with
the return air and all go through the dehumidifier,
All materials should be suspect. For example, then it is not added to the internal moisture load.
most metals bring very little moisture, but But if only part of this outside/return air mixture
nonmetals can carry surprisingly large amounts passes through the dehumidifier, then the part
of water. The material's supplier should have bypassing the dehumidifier must be added to the
information on its moisture carrying internal load of the room. The added air is only
characteristics. part of the total air used in controlling space
If such data are unavailable, a simple test should humidity. Since it rarely gets into the controlled
prevent an unexpected and substantial moisture space without first going through the
load problem. Place a sample of the material in a dehumidifier, consider it at its point of entry-at the
small, dry container, or place some material in a dehumidifier.
tall hopper and blow air over it to dry it. Measure
Moisture-laden air enters through the process
the moisture loss over an appropriate time
inlet and moves through the Brysorb PlusTM
interval to determine its dwell time, or how fast it
desiccant media. The desiccant adsorbs the
gives up moisture. In some cases, a small pilot
water vapor and the dehumidified air is then
plant can be used to acquire definite data.
delivered through the process outlet directly into
Process Load the controlled space or air stream. Then, as the
The manufacturing process itself may expel desiccant media rotates into the reactivation
moisture into the atmosphere of a controlled airstream, the hot air entering through the
space. Open tanks or trays of liquid will add to the reactivation inlet drives off the moisture and
moisture load. (See Appendix III.) exhausts it into the atmosphere. After
11
reactivation the hot, dry desiccant rotates back of the process air cools the desiccant so that it
into the process airstream where a small portion can begin the adsorption process all over again.
12
Physical Facts
1. Area to be conditioned – 60' x 42' x 16'
2. Outside design condition – 95°F db*; 75°F wb*
3. Controlled space requirement** - 75°F db; 35% RH
4. Physical openings – 1 door (6'7'); opened 6 times/hr.
5. Number of people working in area – 10
6. Construction – 8'' masonry
7. Make-up air specified by owner – 350 cfm.
* db = dry bulb value; wb = wet bulb value
** See Appendix V, page 45.
Problem
To determine the size of dehumidifier necessary to maintain the desired controlled space conditions.
Assumptions
1. The door is adequately weather stripped and is of standard construction.
2. Ten workers in the area maintain a moderate pace; each requires ventilating air.
3. The interior of the control space is constructed with two coats of vapor barrier paint.
4. There are no other openings in and out of the controlled space.
5. All physical cracks are sealed.
6. A vapor barrier is provided in or under the concrete floor.
Space Moisture Loads to be Computed
1. Permeation load
2. Load through the door
3. Population load
PERMEATION LOAD
V xD
G x F1 x F2 x F3 x F4 = Grains per hour
C
V = 60 x 42 x 16 = 40,320 ft.3
C = 14 (Specific volume of dry air @ 95oF)
DG = 75 grs/lb, outside design wet bulb of 75oF gives 121 gr/lb from Table I.
Controlled space requirement of 75oF db, 35% RH yields 46 grains per pound
from a standard Psychrometric chart. Therefore, 121-46 = 75 grs/lb.
F1 = 1.94 From Table II – Factor for moisture difference of 75 gr/lb – interpolated
F2 = .5 From Table III
F3 = 1.0 From Table IV - Factor for 8'' masonry
F4 = .75 From Table IV – Factor for 2 coats of paint
40,320 x 75 x 1.94 x .5 x 1.0 x .75 = 157,140 grs/hour
14
DOOR LOAD
Ohr x A x D G x F1 = grs/hr
C
Ohr = 6
A = 6 x 7 = 42 sq ft
C = 7
G = 75 grs/lb
F1 = 1.94
6 x 42 x 75 x 1.94 = 5238 gr/hr
7
13
POPULATION LOAD
At a db of 75° F and working at a moderate rate, a person will expel 2,540 grains each hour. (See
Appendix III)
Therefore, ten people will add
10 x 2,540 = 25,400 grains each hour
TOTAL LOAD
157,140 grs/hr – Permeation
5,238 grs/hr – Through door
25,400 grs/hr – Population load
187,778 grs/hr – Total
The drying system and load requirement are shown in the schematic below.
SPACE 75°F
"S" GR/B=46 GR/LB
TOTAL MOISTURE LOAD
187, 778 GR/HR
AFTER
BRY-AIR
COOLING
FILTER DEHUMIDIFIER
COIL
Note that 350- cubic feet per minute (cfm) outside air is based on a requirement of 30 cfm for each of 10
workers is introduced at the dehumidifier. The effect of this air on the ultimate dehumidifier size will be
handled below.
Proceed with the following calculation:
X = C x gr/hr ÷ (S-G)
60
Where : X = Delivery air rate from dryer to space in cfm
gr/hr = Total moisture load in grain per hour in the space
C =14 = constant
S = 46 = Grs/lb moisture requirement of controlled space. In the absence of a ventilation
requirement this would be the inlet condition at the dryer.
G = Grs/lb of air leaving dryer. Refer to Chart 1, Appendix IV, Enter curve at 46 grain “Inlet moisture
condition.” Intersect 75° Inlet air temp curve at 14 gr/lb.
14 x 187,778 ÷ (46 – 14) = 1369 cfm
60
From the above calculation the space moisture load is 187,778 gr/min. 1369 cfm air at 14 grs/lb will
maintain the space design conditions.
At this stage in the procedure, it is necessary to resort to the method of approximation to select the
correct dryer.
In addition to handling the space load the dryer must handle the moisture load contributed by the 350
14
cfm outside air requirement. So use a 2000 cfm Bry-Air Dryer (FLi - 4200).
If the dryer has a delivery rate of 2000 cfm, and if 350 cfm of outside air is to be introduced, there
remains 1650 cfm of air from the conditioned space. Tabulate this air mixture
350 cfm x 121 gr/lb = 42,350
1650 cfm x 46 gr/lb = 75,900
2000 cfm 118,250
15
FLi - 4200
130° F
16
EXAMPLE II: STANDBY WAREHOUSE
Moisture damage in a standby or storage warehouse can be avoided by surrounding the machinery,
equipment, or material with dry air.
Physical Facts
1. Area to be conditioned - 210' x 176' x 45' = 1,663,200 cubic feet
2. Outside design condition – 95°F db; 77°F wb
3. Controlled space requirement* - 85°F db; 40% RH
4. No physical openings nor appreciable amount of door openings or closing specified
5. No people working in the area
6. Construction – 8” masonry.
* See Appendix V
Problem
To determine the size of the dehumidifier required to maintain standby conditions.
Assumptions
1. All physical cracks are sealed and the floor properly vapor-proofed.
2. If the room is completely vapor-proofed, use Table 4 on page 8.
3. Two coats of vapor barrier paint have been applied externally for metal clad construction.
* External application is recommended because:
• Outside walls are usually easier to access than inside walls for paint application.
• Coating the outside walls discourages water permeation into the wall and thus minimizes water
accumulation in the wall structure itself.
Where:
V = 210 x 176 x 45 =1,663,200 cubic feet
C = 14 = Constant
DG = 58 grs/lb. Outside design wet bulb of 77oF gives 130 grs/lb from Table I, page 8.
Controlled space requirement of 85oF db, 40% RH yields 72. grs/lb from a standard
Psychrometric chart. Therefore, 130-72 = 58.
F1 = 1.54 from Table II - Factor for moisture difference of 63 grs/lb
F2 = 0.24 from Table III - extrapolated as straight line for a volume of 1,663,200 cubic feet.
F3 = 1.0 from Table IV - Factor for 8” masonry.
F4 = .75 from Table IV - Factor for 2 coats of paint.
Refer to schematic below which shows the load requirements and drying system.
X = C x gr/hr ÷ (S-G)
60
Where: X = cfm delivery air rate from dryer
C = 14 (constant)
S = 72 grs/lb moisture requirement of controlled space
17
G = grs/lb in air leaving the dryer. Refer to Chart 1, Appendix IV
Enter curve at 72° “Inlet Moisture condition”. Interpolate “Inlet Air
Temperature Curve” between 75° and 95° and find “leaving
moisture” at 33 grs/lb.
X = 14 x 1,910,019 ÷ (72 – 33)
60
X = 11,427 cfm
SPACE
1,663,200 CUBIC FEET
85'F "S" GR/B = 72 gr/#
BRY-AIR
DEHUMIDIFIER COOLING COIL
FILTER
Therefore 11,427 cfm of air (33 gr/lb) from the dehumidifier is needed to maintain a grain level of 72 gr/lb.
In a building of this size and shape, air distribution ducts are practical for effectively spreading the air so
it can return to a common point and re-enter the dehumidifier.
Recommendation
Use one Bry-Air FLB-25000, Dehumidifier at 12,500 CFM in this standby warehouse with a fan sized to
handle the necessary static pressure of the duct system.
18
FLB - 25000
138° F
19
EXAMPLE III: PRODUCT DRYING
Here we have a room used to remove water vapor from such products as cattle feed mixes, nylon or
rayon cord for tires, raw plastic material, granular chemicals, raw paper stock, cardboard stock for
coatings, or other similar products.
In this example, the room is used for drying cattle feed mixes, which are contained on drying carts that
stand in the room until the specified level of dryness is attained.
Space condition requirements and product movement rate are determined by the manufacturer.
Physical Facts
1. Drying room size – 40' x 65' x 16'
2. Outside design condition – 93°F; db; 73°F wb
3. Controlled space requirement – 95°F; 15% RH (36 gr/lb)
4. One double door; (a) 6' x 7' (b) Opens at 2 times/hr
5. There are no other openings
6. There are no workers in room except to bring mix in and out
7. Product movement rate – 1500 lb/hr (i.e. carts with trays of mix are moved into the drying room at
the rate of 1500 lb/hr)
8. Product enters room at 8% moisture and leaves at 4% moisture
9. Drying room wall construction – 8” masonry
10. 350 cfm outside air required by manufacturer
Problem
To determine the size of the dehumidifier
Assumptions
1. All physical cracks are sealed
2. The double door is weather stripped
3. Two coats of vapor barrier paint have been applied to the wall and ceiling construction of the drying
room; the floor is suitably protected against vapor permeation
Moisture Loads to be Computed
1. Product load
2. Permeation load
3. Door load
Product Load
Since the product will lose 4% moisture (by weight) and there are 1500 pounds of product
each hour:
1500 lb/'hr x (8 % - 4 %) = 60 lb/hr water removal
Since one pound of water equals 7000 grains, then:
60 x 7000 = 420,000 gr/hr product load
Note that the time needed to reduce the material to a 4% moisture level would have to be given or
experimentally determined. These data would determine the amount of material to process and the
size of the drying chamber needed.
PERMEATION LOAD
20
DG = 77 gr/lb, outside design wb of 73 o F gives 113 gr/lb. from Table-I.
Drying room space requirement of 95oF, 15% RH yields 36 gr/lb from the
Psychrometric Chart.
F1 = 1.99 From Table II - Factor for moisture difference of 84 grains.
F2 = 0.50 From Table III - Permeation factor
F3 = 1.0 From Table IV - Factor for 8” masonry.
F4 = 0.75 From Table IV - Factor for 2 coats paint.
21
Recommendation
FLB 12500 Dehumidifier, rated at 7500 cfm, should be adequate. However, the first step should be to
determine if this Dehumidifier has enough capacity to handle the 350 cfm outside air in addition to the
moisture load in the drying room.
If the dryer has a delivery rate of 7500 cfm and 350 cfm of outside air is to be introduced, there remains
7150 cfm from the conditioned space. Tabulate this air mixture as follows:
350 cfm x 113 gr/lb = 39,550
7150 cfm x 36 gr/lb = 257,400
7500 296,950
22
PROJECT: EXAMPLE III – PRODUCT DRYING
FLB - 12500
135° F
23
EXAMPLE IV: CONTROLLED HUMIDITY AND TEMPERATURE AREAS
Many air conditioned manufacturing areas often have a required air flow to handle a sensible load in
that space. This air quantity requirement and the accompanying dehumidifier size are usually greater`
than those needed to handle a latent load.
By designing, a system for the sensible load situation and then determining the appropriate dehumidifier
to handle the moisture load, the desired conditions for the space can be maintained.
Physical Facts
1. Area to be conditioned – 62.5' x 55' x 14'
2. Outside design conditions – 95oF db; 77oF wb
3. Controlled space requirement – 55oF db; 30 % RH; 20 gr/lb
4. Door – 1 (6' x 8'), 6 openings/hr; 1 (3' x 7'), 4 openings/hr
5. Other (fixed) openings – 2.8 sq. ft., w/tunnel 10' deep
6. Number of people working in area – 10
7. Air required for sensible temperature control – 24,715 cfm, 42oF
8. Construction – Block walls; drywall ceiling with vapor proofing; concrete floor on grade
9. Make-up air required – 2400 cfm
10. Air available for make-up – 50oF db/49oF wb; 50 gr/lb.
Problem
To determine the size of the dehumidifier needed in a controlled humidity and temperature area.
Moisture Load to be Computed
1. Permeation
2. Load through doors
3. Load through fixed openings
4. Population load
24
TOTAL ROOM MOISTURE LOAD
450,846 gr/hr Permeation
12,491 gr/hr Door Load
3,643 gr/hr Door Load
1,822 gr/hr Fixed Opening Load
11,000 gr/hr Population Load
479,802 gr/hr TOTAL ROOM LOAD
The total room latent moisture load is 479,802 gr/hr, which is added into the calculation below to find the
entering grain condition needed for the space.
Thus the air to the room must be 15.4 gr/lb and the air mixture (return from the room plus the
dehumidifier discharge) entering the main system fan should be 15 gr/lb. to allow for possible leakage
into the system duct work. Here one must resort to trial and error techniques to select the dehumidifier
size.
cfm x (S – G) x 60 = X cfm – 7500 cfm – dehumidifier capacity (trial)
14
14 = constant
S = 20 gr/lb. condition in the controlled space
G = 4 gr/lb. air leaving dehumidifier (Chart 1, Appendix IV) with entering air 53°F, 30 gr/lb.
7500 x (20-4) x 60 = 514,285 gr/hr
14
25
Note that the make-up air of 2400 cfm must mix with 5100 cfm of return air before entering the
dehumidifier.
RECOMMENDATION
The FLB - 12500 Dehumidifier will satisfy the room load conditions when mixed with the remaining
17,215 cfm of return air and delivered into the conditioned space.
26
FLB - 12500
96° F
27
EXAMPLE V: PRODUCTION OF DRY AIR moisture content of the outside air.
FOR A SPECIFIC PURPOSE EXAMPLE VI: WATER TREATMENT
Many applications require a specific quantity of PLANTS
outside air to be delivered at a given moisture
In most water pumping stations, filteration plants,
content and temperature. This requirement may
and waste water control plants, control of
be a need to make up air exhausted from a space
humidity in the pipe galleries, pump rooms, and
or to supply air for a process such as a drying
control rooms is of prime importance. By
oven.
reducing the dew-point temperature of the air
PHYSICAL FACTS below the temperature of the piping and walls,
sweating and condensation can be eliminated.
1. Maximum allowable moisture content – 17 By circulating warm, dry air through the areas,
gr/lb of dry air water accumulation is avoided, maintenance for
2. Maximum allowable temperature – 115°F electrical controls, motors, and instruments is
3. Quantity of air required – 6,000 cfm reduced, and paint lasts longer on the pipes,
4. Maximum condition of outside air – 95°F, 130 valves, and flanges.
gr/lb
A standard rule-of-thumb is used to approximate
From Chart 1, Appendix IV, it is obvious that 130 this type of application load:
grain air cannot be reduced to 17 grains in a
single pass through a dehumidifier, without other Volume of space to be conditioned = CFM dehumidifier
conditioning. Examination of Chart 1 shows that 25
to produce 17 grains air leaving the dehumidifier, (For each 25,000 cu.ft. space, supply 1,000 cfm
the inlet condition should be 64 grains or less at of dry air.)
60°F or less.
The use of an after-cooling coil for the dry air
This is accomplished as shown above by
discharge from the dehumidifier can be
installing a cooling coil upstream of the
dehumidifier to reduce the temperature and omitted in most installations since the warm,
28
dry air (low RH) will help heat the space during water seals on the condensate lines. Cooling
cool or winter conditions. Heat should not build devices, especially the coils and fan, and the
up to an objectionable level because the large filter box need to be handled properly when
piping and wall areas are at the same cleaned, and they, too, must be tight.
temperature as the water in the system. Warm Obviously, there are many factors that ban
air also has the advantage of reducing the RH restrict the zero leak principle.
and increasing the air's capacity to carry away
One way to maximize the chances for a zero
moisture.
leak system is with air treatment equipment
ZERO LEAK SYSTEM FOR A LOW and dehumidifiers designed to fit and operate
HUMIDITY SPACE together effectively. Buying directly from the
equipment manufacturer and not mixing
In a system where the ductwork and sources of various equipment components
components are outside the controlled space, focuses the accountability for moisture
dry air leaving the system will induce the flow of tightness.
humid air into the system. If the humid air is not
dehumidified, each cfm will induce a load Bry-Air constructs custom dehumidifiers and
absorbing the capacity provided by 5 to 10 cfm low dew-point AHUs for maximum efficiency.
of the dehumidified air. If all air that enters the This extra care in design and construction
system must pass through the dehumidifier, means zero leak performance. Proper
the additional load will be reduced by 50% or operating balance compensates for this
more. Typical air handling units (AHUs) are not situation.
built to be vapor tight. Standard sheet metal When end users, consulting engineers, or
type ductwork has lapped seams that allow other “specifiers” require a system to be
leakage. However, excellent silicone-based substantially air tight, they means there is no
sealants are available; for applications leakage at any joint.
requiring very dry spaces, the seams must be
welded shut. Assuring zero leak begins in the fabrication
and construction stages. We recommend
Having a “zero leak” condition means that all flanged or gasketed connections with welded
air leaving the controlled space is under seams and joints. As a minimum, all seams
positive pressure (to minimize infilteration), and joints should be caulked. Removable
and all the entering air passes through the panels and access doors should be completely
dehumidifier. The cost of dehumidification is enclosed. (Coils will leak where return bends
high when moisture levels must be low. In enter tube sheets.)
these situations, even a small leak can double
operating costs. Since ducts are a once-only Prior to insulating, the system should be tested
expense, attention to ductwork is vital. The and deficiencies corrected. The best method is
other approach to this situation-a higher to use an open flame, if permissible. This
capacity dehumidifier- means added costs, requires candles or other sources of flame. In
year after year. other situations, smoke devices or soap suds
could be used.
It is unusual to find air handling units
constructed for zero leak performance. Leaks When all these precautions in fabrication,
are anticipated at removable panels, bearing construction, and testing are complete, the
flanges, drain pans, and through condensate system will perform as designed. Periodic
drains with dry traps. Such units require inspection during operation will allow leaks to
additional sealing and check valves or positive be located and corrected.
29
PART SIX:
BRY-AIR DEHUMIDIFIERS FOR PRODUCT DRYING
Product drying applications include two general the best solution. For temperatures in the 120°F
types: bulk drying and continuous drying. In bulk to 140°F range, the decision depends on the
drying the material is loaded into a compartment product characteristics and the desired degree of
and the entire load is dried as a batch. With dryness.
continuous drying the wet material is Drying operations involve the removal of free
continuously fed into a drying chamber and moisture, hygroscopic moisture, or a
material continuously leaves the chamber, dried combination of both. Free moisture is water
to the desired moisture level. held on the surface or between molecules of a
substance. Free moisture occurs when actual
Drying potentials can be increased in two ways liquid water is used to mix or wash the product
by: prior to drying. Hygroscopic moisture is held
·Raising the product temperature by within the material's cells. Hygroscopic
exposing it to heated air moisture will take up or dispel water in relation
to the relative humidity of the air mixture to
·Physically removing moisture from the which it is exposed. When in equilibrium with air
surrounding air at 100% RH, the material will be
hygroscopically saturated. Any hygroscopic
The quantity of air needed for proper drying will material containing free moisture must be
vary widely with either type of drying system. But hygroscopically saturated.
the drying characteristics and the approach to the
problem are similar. The removal of free water is a surface
evaporation function and follows the calculation
The Bry-Air Dehumidifier performs no miracles shown in Appendix III of this manual. The surface
extracting moisture from the product into the water temperature should be assumed to be the
surrounding air. But by maintaining the air at a wet-bulb temperature of the surrounding air
lower moisture level, the Dehumidifier can mixture. Note that air velocity is critical the drying
increase the drying potential and the drying rate. speed.
More important, it can remove the variable of The removal of hygroscopic moisture depends
weather as a factor in a drying operation. on the relative humidity difference between that
of the products' equilibrium condition and that of
Heating is less expensive than drying, so the
the surrounding air. Velocity of the air over the
obvious questions is: Where do Bry-Air product has little or no bearing on the drying
Dehumidifiers apply? speed.
In most drying processes, the released moisture The figure Fig 1 shows a typical drying curve. The
goes into the air and must be physically removed sudden change in drying rate (at the critical point)
or diluted with outside air. However, without a denotes where the initial drying via removal of
desiccant dehumidifier, the lowest possible free moisture ends and hygroscopic drying takes
moisturelevel in the chamber will equal that of the over. In other words, the product has lost its free
outside make-up air. But in practical terms, the moisture, but is still hygroscopically saturated.
moisture content of the air in the chamber will
generally be somewhat higher than that of the Each material has a different physical form that
outside air. determines how it holds or gives up moisture.
Since many of the newer materials lack
When heat is used alone, the drying potential is published data on their drying rates, selecting
limited by the specific humidity of the outside air appropriate air drying equipment must be done
plus the safe temperature to which the product experimentally. The net effective drying surface
can be raised. Generally, a proper drying and the hygroscopic properties cannot be
potential can be established with heat and determined in any other way.
outside air if the temperature can be raised to
140°F or above. If the temperature can not be Most drying problems are really a request for
raised over 120°F, then a Bry-Air Dehumidifier is improving the speed or quality of an existing
30
enough to keep the RH in the surrounding air at
5% or less.
Continuous type drying system. Here one
must remove material samples at the start, finish,
and at regular intervals along the drying tunnel.
Such test points should be accurately marked
and related to the drying time. Each sample
should be weighed as soon as removed, then
thoroughly dried at elevated temperature and
reweighed. The dry-bulb temperature, wet-bulb
temperature, and air velocity over the product
should be determined at each point of product
supply as well as at the start and end of the drying
tunnel.
From this information the weight readings can be
converted into% of moisture and plotted against
drying time. Moisture content should be
expressed as a percentage of the product's bone
dry weight, not as a percentage weight of the test
drying operation. For example, before today's sample. If both free and hygroscopic water are
advanced dehumidifying equipment was removed from the sample, a characteristic curve
available, candy manufacturers could make their will resemble that shown in the figure 1 on page 31.
product only in winter. In summer, attempts to
manufacture candy might often end with a moldy SIZING THE DESICCANT DEHUMIDIFIER
product. Now, to meet production demands, the Bulk type drying. On the characteristic curve,
use of cooling equipment and a desiccant indicate the wet-bulb and dew-point
dehumidifier can imitate winter conditions all temperatures equivalent to the reading taken
year. during the test up to the critical point. From the
Solving a drying problem usually involves a critical point to the curve's end, show the dry-bulb
rather simple analysis of the drying cycle. If the temperature and the RH. The hygroscopic drying
analysis (that is, the test run) can occur during phase should be considered in making the first
weather conditions that consistently give the analysis (that is, the drying curve).
desired drying result, the problem is simplified. Some hygroscopic moisture (near the product's
Regardless, any test run will show the product's surface) is removed at the critical point. So make
characteristics and give clues for solving the two assumptions:
problem.
·The product is hygroscopically saturated at
The test run should be made under actual
this point.
production operation to secure information in
either of the two following categories. ·The product is substantially in equilibrium
with the final RH at the end of the test (when it
Bulk type drying system. Several trays in
reaches the desired moisture content).
different locations in the compartment should be
weighted and identified before being placed in Thus, the average drying potential for this part
average RH observed
the drying cabinet. They should be weighed at of the test is: – during the hygroscopic
the start and at predetermined intervals (usually drying portion of the test.
hourly), subtracting the tray weight, and quickly
returning the tray to its original position after
weighing. At the same time a wet-and dry-bulb
reading (average throughout the cabinet) and air
velocity reading over the product should be If our test took 12 hours and we want it to be
taken. Continue these procedures until the complete in 8 hours, or two-thirds the amount of
product in satisfactorily dried; weight should be time, then the hygroscopic portion of the test,
noted at this point. The purpose is to establish a which took 9 hours, needs to be completed in 6
totally dry weight. Temperature should be high hours. Further, the product's moisture level at the
31
critical point minus the moisture remaining after recirculated air (at the average specific humidity
complete drying equals the total weight of water already determined) and a minimum of 5%
to be removed in 6 hours. outside air (refer to Typical Flow Diagram). This
This amount can be converted into grains per establishes the level at which the dehumidifier
minute: must operate. From Chart I Appendix IV, the
leaving moisture is determined. The difference
Total hygroscopic water removed in lbs x 116.6
between the gr/lb. moisture level maintained in
Time in hrs
the dehumidifier and the same parameter in the
To accomplish this dryness faster, the drying air leaving the dehumidifier is the pick-up factor.
potential must be increased proportionately to This figure divided into the average required
the rate of test time vs. the desired time. But the moisture removal in gr/min determines the
product's average moisture level will be dehumidifier size in lb./min air capacity.
unchanged. Therefore, the average RH for
This unit capacity must be checked against the
drying is found by:
“free moisture” requirement this way:
Average product RH – Required RH potential.
Total weight of free moisture (gr/min)
The average product RH combined with the Dehumidifier air capacity (lb/min)
average dry-bulb temperature dictates the
= moisture pickup factor (gr/lb)
specific humidity that must be maintained and
defines the operating conditions for the Refer to Chart 1, Appendix IV. Knowing the
Desiccant Dehumidifier. desired drying temperature helps pinpoint the
inlet where the necessary moisture removal will
The drying temperature should be as high as
occur. For example, if 42 gr/lb. must be removed
practical (usually 10°F below the maximum
(the drying temperature is 95°F), then follow the
allowable product temperature). 95°F entering
95°F curve to the point where the difference
air is the highest recommended level (See Chart
between the inlet and outlet moisture is 42 gr/lb.
1, Appendix IV). Thus if temperatures greater
Here the result is nearly 60 gr/lb.; that is where
than 95°F are needed in the drying chamber, the
the leaving moisture is approximately 18 gr/lb.
recirculating air should be cooled to 95°F or
below. Here the cost of the cooling coil, booster To be safe, use a condition approximately 5 gr/lb.
fan, and water used will be offset by the gain in above that shown on the curve and allow for 5%
moisture removal capacity. (Reduced ratings for outside air. Then the needed dew-point and wet-
inlet temperatures up to 115°F can be calculated. bulb temperature values can be established.
See your Bry-Air representative for details.) Determine the vapor pressure equivalent for the
temperature using Appendix III. The difference
The Bry-Air Dehumidifier will handle a mixture of
between these items establishes the drying
potential. Then determine the average vapor
pressure difference for the test run from the same
table using the test dew-point and wet-bulb
readings. The ratio of vapor pressure difference
with the Bry-Air Desiccant Dehumidifier over that
measured during the test should equal or be
greater than the ratio of the drying time. (test vs.
desired.)
Since air velocity also affects free moisture
evaporation, drying can be some what controlled
by changing air velocity to as high a level as
possible without disturbing the product. Use a by-
pass or fans within the chamber to increase the
total circulation in the drying air circuit above the
Bry-Air Dehumidifier's capacity.
For the test run, establish a velocity factor:
(1 + test velocity in ft/min)
230*
32
* An established constant. Refer to Appendix IV, Chart 1 to calculate the
moisture level leaving the Dehumidifier and
Also establish a velocity factor for the actual
determine the removal per pound value;
design:
Total moisture removal load, (gr/min)
(1 + actual velocity in ft/min)
Moisture removed by Dehumidifier (gr/lb)
230
= Dehumidifier size lb/min air capacity
At any given vapor pressure difference, the
evaporation will vary directly according to the The next step is to check the performance of the
above factors. Dehumidifier in the hygroscopic drying section,
measured in gr/min.
Continuous drying. Since continuous drying
systems characteristically have open ends, they Dehumidifier performance (lb/min)
usually require a great deal of additional outside 2
or make-up air to make up for all the openings. + moisture level of air leaving Dehumidifier
For efficiency, keep such openings as small as
= average moisture content of air in this portion
practically possible. A minimum leakage
of the drying chamber
equivalent to a 200 fpm velocity through the area
should be positively introduced into the system. Use the curve in Appendix IV, Chart 2 to
determine the temperature of air leaving the
The typical flow pattern for a continuous drying
Dehumidifier. The departing moisture will have a
operation, has a separate circulating system for
cooling effect; to find the average temperature
free moisture removal; the dehumidifier
subtract 0.625°F for each gr/lb. pickup.
discharge is directed through the hygroscopic
moisture phase. This configuration takes Now that moisture content and temperature are
advantage of rapid circulation in the first space known, the average RH needed is easily
without carrying the wetter air into the final drying determined from a psychrometric chart.
space. Note the separate circulating system for Compare this figure with the necessary RH to
the free moisture removal stage. Dehumidifier insure proper drying within the bulk type
discharge is directed through the hygroscopic dehumidifier. This comparison will reveal
moisture phase. This arrangement allows rapid whether or not the dehumidifier has the capacity
circulation in the first space without carrying over to produce the desired drying rate.
moisture into the final drying space.
Maintaining drying temperature. As already
Use the bulk drying method to establish the vapor noted, water evaporation is a cooling process.
pressure difference to allow drying to proceed Approximately 1052 Btu are needed to evaporate
satisfactorily in the free moisture stage. Keep the one pound of water. In other words, 6.65 gr/lb.
velocity and temperature as high as practical. represent 1 Btu or 1 gr/lb. represents 0.625°F.
Design specifications will help establish the total
As a product is dried, it releases moisture.
circulation. The temperature plus necessary
Without proper control, this moisture can cool
vapor pressure difference will establish the
down the environment and result in an
specific humidity (in gr/lb), that must be
equilibrium condition where the drying practically
maintained.
ceases. So to maintain drying temperatures, heat
Express the total product moisture removal in must be supplied in an amount represented by
gr/min and add the moisture load introduced by the evaporation rate. Also, heat can be lost by
make-up air. This latter load derives from the conduction through cabinet walls. Thus it may be
difference in specific humidity between the necessary to control the product to drying
maximum design outdoor level and that temperature (heat or cool it), and heat the make-
maintained in the compartment multiplied by the up air to maintain the optimal drying temperature.
quantity of outdoor air (in lb./min). The
The process of adsorption is an exchange of heat
proportionate quantity of recirculated and outside
in a like amount in the reverse direction. Thus, air
air also determines the specific humidity of the
heats as it passes through the desiccant
mixture- which typifies air entering the
dehumidifier. Approximately 30% additional
Dehumidifier.
heat builds up in the desiccant from the previous
If the pre-cooling Bry-Air Desiccant Dehumidifier reactivation period, so the dehumidifier supplies
is used, the air temperature leaving the coil all the required heat for evaporation and an
determines the Dehumidifier operating level. additional 30% for other purposes. In some,
33
instances that additional heat is required; in other This strategy yields reduced energy
cases, cooling may be needed. consumption and supplies the minimum energy
needed to maintain the process condition.
DEHUMIDIFIER CAPACITY CONTROL
Modulation of reactivation inlet temperature
Several methods provide dehumidifier control. and air volume. By modulating the reactivation
On/Off control of the dehumidifier. Humidistat air volume and temperature at specific values,
or dew-point control monitoring of space or return the reactivation capability is increased and can
air is a method used where continuous process be used over a wide range of operating
air is not needed. Often the dehumidifier is conditions. This method also compensates for
installed as an independent unit and is not tied reductions in adsorption capacity.
into the make-up or outside air circulation Process face and bypass damper control.
system. Here the moisture control of leaving air is due to
On/Off control of reactivation heaters and varying the volume of air that bypasses the
blower. This control method applies to dehumidifier. However, a constant supply air
continuous process air flow situations. However, volume must be maintained. This is the best
the process air will have more variation in scanario for tight humidity control.
humidity than with other control methods.
CONCLUSION
Modulation of reactivation inlet temperature.
Information in this manual was prepared to help
customers choose the most effective hand
efficient dehumidifiers. Please contact Bry-Air's
dehumidifier experts for additional assistance
and for more detailed information about physical
characteristics and performance data relating to
Bry-Air Dehumidifiers.
Bry-Air procuced systems that are built to meet specific customer needs.
Many customers require heating, cooling, air filtration, etc, in addition to air drying.
34
APPENDIX I:
PROCESSES AND PROPERTIES OF AIR
Dry-bulb, wet-bulb, dew-point temperatures, per cubic foot are correct on a standard chart. But
relative humidity-these terms are so closely for given dry-bulb and wet-bulb readings at non-
related that if two properties are known, all others standard barometric pressures, all properties
shown in the figure 3 may be read from the chart. must be corrected.
When air is saturated, dry-bulb, wet-bulb, and
INTERPRETING THE AIR CONDITIONING
dew-point temperatures are identical. (See
Example 2.) CHARTS
Generally, in graphic presentations, humidifying
Enthalpy of air for any given condition is the
is shown by an upward line and dehumidifying is
enthalpy at saturation corrected by the enthalpy
shown by a downward line.
deviation due to the air not being in a saturated
state. The enthalpy (h) in Btu per pound of dry air Heating and cooling air without changes in
is the enthalpy at the saturation hwb plus the moisture content involve only a change in
enthalpy deviation hd See Example 2. sensible heat and appear as a horizontal line, to
right or left respectively. Changes occur in dry-
H + hwb + hd bulb, wet-bulb, RH, and enthalpy. Specific
If the air's moisture content increases or humidity and dew-point temperature remain
decreases in a psychometric process, the heat constant.
added (q) or removed (-q) is the difference In heating and humidifying, both sensible heat
between the enthalpy of the final or leaving air hla and specific humidity increase-shown as a line
and the initial or entering air hea minus the sloping upward and to the right. Changes occur in
enthalpy of the moisture (water in liquid or ice dry-bulb, wet-bulb, dew-point temperatures, and
state) added hw or rejected hw. enthalpy. A difference in RH depends on the
slope of the line.
q = h la - h ea - h w
For cooling and dehumidifying, both sensible
See Examples 4 and 5. heat and specific humidity decrease, so the line
The enthalpy of added or rejected moisture is slopes downward and to the left. Dry-bulb, wet-
shown in the small graphs at the top of the chart. bulb, dew-point temperatures, and enthalpy all
change. Changes in RH are dependent on the
Enthalpy of added or rejected moisture and slope of the line.
enthalpy deviation are usually omitted in
applications not requiring precise results- for Evaporative cooling refers to air brought in
example, comfort air conditioning. Errors due to contact with spray water at a temperature equal
omissions for wet-bulb temperatures below 32°F to the wet-bulb temperature of the air. The
is much larger than for omissions above 32°F. process takes place upward along the wet-bulb
line. As sensible heat of the initial air vaporizes
Sensible heat factor. This is part of certain the water, the air's dry-bulb temperature falls.
calculations for installing air conditioning The sensible heat used to vaporize the water
equipment. A scale along the right side of the enters the air as latent heat in added vapor; thus
figure in Example 4 used with an origin at 80°F no heat is added or removed. Wet-bulb
dry-bulb temperature and 50% RH provide a temperature remains constant. Dew-point
reasonable heat factor value. See Example 4. temperature, RH, specific humidity, and enthalpy
Barometric pressures. In comfort air increase. (In most evaporative cooling
conditioning, a mercury reading of one inch or installations, heat may be added or removed
less either above or below the standard 29.92 during the process due to outside sources, this
inches of mercury is considered a standard amount is usually negligible.)
reading. In chemical dehydration, the air that contacts the
When dry-bulb and dew-point temperatures are chemical either adsorbs or absorbs moisture
known for air at non-standard barometric from the air. Thus in this energy constant
pressures, values of % RH and grains of moisture process, heat is liberated and added to the air-
35
Follow horizontal line left to saturation curve,
read DP = 53.6°F.
Interpolate between lines representing cubic feet
per pound of dry air, read v = 13.53 cu ft.
Follow horizontal line to right, read grains of
moisture per pound of dry air, W=61.4 gr.
Grains of moisture per pound of dry air (61.4)
divided by cubic feet per pound of dry air (13.53)
= 4.54 gr per cu ft
EXAMPLE 2. Reading properties of Air
36
Locate the condition initial air on the chart. Exact Solution – Heat removed:
o
Follow horizontal line to 75 DB. q = hla – hca – hw = 23.21 – 33.13 – (0.08) = -9.84
o
Read:RH=15% : WB=51.5 F : DB=25.2 F. o Btu per lb dry air.
Read enthalpy at saturation initial air hcwb = q = hlwb – hcwb = 23.22 – 33.25 = -10.03 Btu per lb
10.10 Btu dry air.
Read enthalpy deviation initial air hcd = 0.06 Btu Approximate solution is 1.9% higher than exact
solution.
Enthalpy of initial air hca = hcwb + hcd = 10.10 + .06 =
10.16 Btu To determine Sensible Heat Factor, draw a line
between initial and final conditions. Draw a line
Read enthalpy at saturation of final air hlwb = 21.14 parallel to this line from reference point (80 DB,
Btu 50RH) to Sensible Heat Factor scale, read SHF =
0.68.
Read enthalpy deviation of final air hld = 0.10 Btu
EXAMPLE 5. Mixture of Air
Enthalpy of final air hla = hlwb + hld = 21.14 + (-0.10)
= 21.04 Btu
Heat added q = hla - hca =21.04 – 10.16 = 10.88 Btu
per lb of dry air
Approximate Solution – Head added: Locate on chart conditions of inside and entering
q = hlwb - hcwb = 21.14 – 10.10 = 11.04 Btu per lb of air. Draw line connecting two points. Measure off
dry air. distance equal to ¼ of line, starting from inside air
condition. Point thus established represents
The approximate solution is 1.5% higher than condition of mixture of inside and entering air.
exact solution.
EXAMPLE 4. Cooling and Dehumidifying
Process
(a) Moisture rejected as water condensate
37
38
II
MAKE - UP AIR
FIXED OPENINGS (CONVEYORS, WINDOWS, & ETC.) CFM FDB FWB gr / lb
NO. WIDTH HEIGHT DEPTH USAGE
FILTERS REQUIRED
TYPE TYPE %
PEOPLE RETURN AIR
NO. TYPE WORK (LT. MOD. HEAVY) PROCESS AIR
REACT AIR
PRODUCT LOAD STATIC PRESSURES
lbs / hr OR gr/hr REMOVED OUTLET INLET EXT
39
APPENDIX III:
DETERMINING MOISTURE OR LATENT LOADS
Moisture load can come from many sources, city is 95oF db (dry-bulb temperature) and 76oF
which provide the data needed to calculate the wb (wet-bulb temperature), this condition equals
total latent load on any air conditioning or drying 104 gr/lb. But there will be many days when 76oF
system. The total latent load equals the sum of wb. will occur at a lower dry-bulb temperature.
applicable individual loads. From the table below, the proper design specific
humidity for comfort would be 115 gr/lb; for
Outside design level. Bry-Air Dehumidifier
industrial work it would be 125 gr/lb. Figures
performance characteristics are expressed in
below assume that these levels will be reached or
terms of specific humidity or grains per pound of
exceeded on 30% of summer days for comfort
air. To determine the outside design moisture
work and 10% of days process work.
level, use the standard design dry-bulb and wet-
bulb conditions because this value measures the Ventilation latent load. Determining the latent
design total heat (wet-bulb) occurring with the load equivalent to the outside air by subtracting
highest practical dry-bulb. The design moisture the indoor or maintained specific humidity and
level will exist when a lower dry-bulb occurs with multiplying that amount by the pounds of outside
the design wet-bulb. This condition represents air brought into the system.
the same total heat, but a higher specific
EXAMPLE: If 1,000 cfm ventilation air is at 125
humidity. The table below lists the
gr/lb. design and the design inside condition is 70
recommended design specific humidity for
gr/lb., what is the ventilation latent load?
various design wet-bulb temperatures. Use the
standard accepted design wet-bulb for your
locality.
The average density of air is given as 14 cu.ft. per
EXAMPLE: If the accepted design level for your pound of air and is used regardless of the actual
density at design conditions
RECOMMENDED DESIGN OUTSIDE LATENT HEAT DISSIPATED BY
MOISTURE LEVEL ADULT OCCUPANTS
Evaportion from a wetted surface. Determine the amount of moisture evaportion from a pan, tank
or other wetted surface into a space using the following calcutions:
Where:
Gr. = moisture evaporated in grs/hr.
Vel = air velocity in F.P.M.
VL = vapor pressure equivalent to temperature of surface water- inches of mercury.
VA = vapor pressure equivalent to dewpoint temperature of air over surface – inches of mercury.
Activity factor
Activity factor
40
TYPE OF POOL ACTIVITY FACTOR
Residential 0.5
Condominium 0.65
Therapy 0.65
Hotel 0.80 (Maximum)
Public Schools 1.0 (Maximum)
Whirlpools Spa 1
Wave Pools 1.50 (Minimum)
DESIGN CONDITIONS
TYPE OF POOL AIR TEMP O F WATER TEMP O F
Recreational 75 to 85 75 to 85
Competition 78 to 85 76 to 82
Therapeutic 80 to 85 85 to 95
Diving 80 to 85 80 to 90
Whirlpools Spa 80 to 85 97 to 104
Moisture permeation. This is discussed in detail above relationship may exist. But after surface
in Part four. drying is complete, further drying will occur at a
rate that depends on the rate of diffusion within
Moisture loads in the table above represent the material; the rate varies with the degree of
unvented appliances. Although personal dryness within the material and is based on
judgement is used to determine vent or hood expected structural changes that occur during
efficiency, the hood efficiency should never be the drying process.
higher than 50%.
Establish the drying rate of hygroscopic materials
Drying hygroscopic materials. The in order to establish the hourly moisture load.
calculations shown above apply only to Unfortunately these rates must be determined
evaporation of free water from a surface. When experimentally in each situation.
hygroscopic materials are in the first stages of
drying-when the surface is actually wet-then the Usually, the desired outcome with hygroscopic
41
drying is to improve drying rate or degree of Storage of hydroscopic materials. When
dryness in the final product within an existing set hygroscopic materials enter a dry storage space,
up or with the addition of a Dehumidifier. In doing even for a short time, they contribute a moisture
so, the desired drying period is generally load that must be absorbed by the dehumidifier.
included with the total weight of material to be The table (Page 43) lists the moisture holding
handled. capacity of various materials in equilibrium with air
at the relative humidities shown. The % compare
Wt. of material entering – Average drying rate
the moisture to the substance's totally dry weight.
= Wt. of material leaving
If the incoming material has an unknown moisture
Drying time (hrs) content, assume that it is in equilibrium with 60%
One caution here; the drying period cannot be RH air. In winter, the materials will likely come into
arbitrarily assumed; it must be realistic. For a room in equilibrium with 90% RH air. However, in
example, if dry air circulates in a dehumidifier and winter most other sources of RH are lower, so the
cannot dry a material totally within 2 hours, then 2 summer figure (60%) can be used all year, unless
hours will be neither a possible nor a realistic the product loads makes up most of the entire total
desired drying time. and the permeation load is minor by comparison.
42
43
IV
44
V
45
46
The above applications represent a very small% of the needs and uses for dry air; the conditions cited
are typical of past uses. Specific needs change, as do technology and manufacturing process. Your
Bry-Air representative can determine appropriate values for a particular application.
47
VI
48
49
/
50
51
52
(9/5C + 32)
53
54
CONVERSION FACTORS
DENSITY
1 gram per cc g/cc = 0.036 1 lb/in3
1 pound per cu ft lb/ft3 = 16.02 kglm3
1 pound per cu ft lb/ft3 = 62.37 g/cc
1 pound per cu in lb/in3 = 0.027 7 kg/m3
ELECTRICAL
1 volt per mil V/mil = 25.4 kV/mm
ENERGY - WORK
1 erg dyn.cm = 1 x 10-7 J
1 Newton-meter N.m = 1J
55
1 watt-second W.s = 1J
1 foot-pound ft.lbf = 1.356 J
1 horsepower-hour hph = 2.685 x 106 J
1 kilowatt-hour kWh = 3.6 106 J
1 calorie cal = 4.19 J
1 British thermal unit Btu = 1.055 J
1 British thermal unit Btu = 0.000 11 cal
1 inch-pound in.lbf = 0.133 J
FORCE
1 dyne dyn = 1 x 10-5 N
1 kilogram-force kgf = 9.81 N
1 pound-force lbf = 4.448 N
1 ton-force tf = 9.810 N
IMPACT STRENGTH
2 2 2
1 foot pound per inch ft.lb/in = 0.475 5 kJ/m
1 foot pound per Inch of notch (Izod test) ft.lb/in = 0.018 73 J/m
1 kgcm/cm kgcm/cm = 10 J/m
LENGTH
1 kilometer km = 1,000 m
1 centimeter cm = 0.01 m
1 millimeter mm = 0.001 m
1 micron um = 1 x 10-6 m
1 nanometer nm = 1 x 10-9 m
1 Angstrom unit A = 1 x 10-10 m
1 inch in = 0.025 4 m
1 foot ft = 0.304 8 m
1 yard yd = 0.9144 m
1 mile mile = 1.609 Km
1 inch/inch per °F in./in./°F = 0.5567 mm/mm/°C
MASS
1 gram g = 0.001 kg
1 ounce oz = 28.4 g
1 pound lb = 0.453 6 kg
1 ton t = 1,000 kg
POWER
1 kilowatt kW = 1,000 W
1 horsepower hp = 746 W
1 foot pound per second ft.lbf/s = 1.356 W
SPECIFIC ENERGY
1 calorie per gram cal/gm = 4,190 J/kg
1 Btu per pound Btu/lb = 2,326 J/kg
1 hph per pound hph/lb = 5.92 x 106 J/kg
1 kWh per kg kWh/kg = 3.6 x 106 J/kg
1 Kwh per kg kWh/hg = 1.644 hph/lb
STRESS
1 dyne per cm2 dyn/cm2 = 0.1 Pa
1 Newton per meter2 N/m2 = 1 Pa
1 Joule per meter3 J/m3 = 1 Pa
1 atmosphere atm = 1.013 x 105 Pa
1 mm mercury mm Hg = 133.3 Pa
1 mm water mm H2O = 9.81 Pa
56
1 bar bar = 1 x 105 Pa
1 pound per inch2 psi = 6,890 Pa
1 megapascal MPa = 145 psi
TEMPERATURE
1 degree Farenheit °F = 1.8°C + 32
1 degree Celcius °C = 0.5555 (°F-32)
1 degree Kelvin °K = °C + 273.16
1 degree Rankine °R = °F + 459.69
THERMAL CONDUCTIVITY
1 gram = 419 J/ms.K
1 Kcal/m.h.°C = 1.163 J/ms.K
1 Btu/ft.hr. °F = 1.76 J/ms.K
1 Btu/in.ft2.h.°F = 0.144 J/ms.K
1 Btu/ft.s. °F = 6,230 J/ms.K
1 Wm.k = 1 J/ms.K
VISCOSITY
1 poise poise = 0.1 Pa.s
1 poise poise = 14.5 x 10-6 psi.s
1 poise poise = 1 dyne/cm2
1 poise-second/in2 psi.s = 6,897 Pa.s
VOLUME
1 x 10-6 m
3
1 cubic centimeter cc =
1 liter L = 0.001 m3
1 milliliter mL = 1 x 10-6 m3
1 cubic inch in3 = 1.639 x 10-5 m3
1 cubic foot ft3 = 0.028 32 m3
1 gallon US gal US = 0.003 785 m3
1 gallon UK gal UK = 0.004 546 m3
ABBREVIATION
A = Angstrom Unit kg = Kilogram
atm = Atmosphere L = Liter
BTU = British Thermal Unit lb = Pound
C = Degrees Celsius m = Meter
cal = Calorie ml = Milliliter
cc = Cubic Centimeter mm = Millimeter
cm = Centimeter Mpa = Megapascal
cu = Cubic N = Newton
f = Force oz = Ounce
dyn = Dyne Pa = Pascal
F = Degrees Farenheit psi = Pounds per Square Inch
ft = Foot R = Degrees Rankline
gal = Gallon s = Second
g = Gram t = Ton
h = Hour tn = Ton US
Hg = Mercury ton = Ton UK
Hp = Horsep V = Volts
in = Inch w = Watt
J = Joule yd = Yard
K = Degrees Kelvin
57
NOTES
58
NOTES
59