VRF SOLUTIONS

LG Air Conditioning Technologies


ABOUT LG

About LG Electronics USA


LG Electronics USA, Inc., based in Englewood Cliffs, N.J., is the North American subsidiary of LG Electronics, Inc., a $68
billion global innovator in technology and manufacturing. In the United States, LG sells a wide range of innovative home
appliances, home entertainment products, commercial displays, air conditioning products, energy solutions and vehicle
components. LG is a 2023 ENERGY STAR® Partner of the Year-Sustained Excellence. The company’s commitment
to environmental sustainability and its “Life’s Good” marketing theme encompass how LG is dedicated to people’s
happiness by exceeding expectations today and tomorrow. Please visit www.lg.com.

About LG Air Conditioning Technologies USA


LG Electronics USA’s Air Conditioning Technologies business is based in Alpharetta, GA. LG is a leading player in the
global air conditioning market, distributing both commercial and residential air conditioners and building management
solutions. From consumer and individual units to industrial and specialized air conditioning solutions, LG provides
a wide range of products for heating, ventilating and air conditioning. The company’s industry-leading variable
refrigerant flow (VRF) technology minimizes efficiency losses, provides sustainable energy savings, and offers some of
the lowest lifecycle costs compared to other systems on the market today. Ten-time ENERGY STAR® Partner of the
Year, LG Electronics USA (based in Englewood Cliffs, NJ), is the North American subsidiary of LG Electronics Inc., a $68
billion global technology and manufacturing. Visit www.lghvac.com for more information.

1 LG Air Conditioning Technologies


ABOUT LG VRF
A Variable Refrigerant Flow (VRF) solution is a single refrigerant circuit that connects many indoor units to one
outdoor unit. VRF is a superior way to heat and cool any space, providing improved humidity control, individual
set points per indoor unit, and a quiet comfort experience. In the heat recovery configuration, VRF also allows for
heating and cooling simultaneously in different zones, further enhancing energy savings and increasing occupant
comfort. Energy efficient and easy to design, install, and maintain, a VRF solution has low lifecycle cost compared to
other traditional HVAC systems on the market today.

Why LG VRF?
The benefits of LG VRF are numerous: less piping for installers, energy efficiency for owners, and modern indoor units
that complement every setting. Furthermore, LG Inverter scroll compressors optimize energy efficiency.

With the addition of LGRED° heating capability, the Multi V™ 5 provides operational performance
with heating down to -22˚F and cooling up to 122˚F for all units with no additional accessories
LGRED
Powerful Heat Technology
or modifications to the equipment, making it a robust solution for all climates. R E L I A B L E TO E X T R E M E D E G R E E S

1. High Elevation Piping Distances 2. Optimized Heat Recovery Piping


3,280 ft. • Flexible piping layout reduces materials and labor costs
Total piping length NOTE: All piping lengths are equivalent. during installation
738 ft.
Longest piping length • LG Heat Recovery Unit (HRU) is quiet, compact, lightweight,
360 ft.
and does not need condensate drains1
Height
between
• Configured for fully independent heating and cooling,
ODU-IDU ensuring occupant comfort

131 ft.
Height
between
IDU-IDU

4. Quiet Operation
• Quiet indoor unit operation
down to 23 dB(A), comparable 50 dB(A)
Conversation
to the sound of rustling leaves at Home

40 dB(A) 60 dB(A)
Bird Calls Conversation
in Restaurant

3. Operation Range 23 dB(A) 70 dB(A)


LG Low-Static Vacuum
• Industry-leading operation ranges without additional Ducted Indoor Cleaner
Unit
accessories or performance deficits:
• Heating: -22˚F to 61˚F WB
• Cooling: 5˚F to 122˚F DB
LGRED
Powerful Heat Technology
Noise Level Comparison dB(A)

• Simultaneous Operation: 14˚F to 81˚F DB R E L I A B L E TO E X T R E M E D E G R E E S 1. Down to 31 dB(A). See page 44 for HRU specification details.

2
LG VRF ADVANTAGES
Efficiency
Advanced features for superior efficiency • LG Inverter Scroll Compressor
Innovative high side-shell design creates a more
• Advanced Smart Load Control
compact unit providing the same capacity output,
Automatically adjusts system target pressures
with greater reliability in cold climates.
based on outdoor temperature and humidity
for increased cooling performance. • HiPOR™ (High-Pressure Oil Return)
• Active Refrigerant Control Oil is returned to the compressor through a
Depending on the operating mode and separate inlet pipe, so compressor energy is used to
conditions, the system refrigerant level is compress refrigerant only.
automatically adjusted for increased part load • Smart Oil Control
and heating efficiency. Eliminates timed oil-return cycles and takes hours
off of the time required to return oil compared to
• Variable Path Heat Exchanger
systems that use a timed oil-recovery cycle.
Depending on the operating mode and
conditions, both the refrigerant flow path and • Intelligent Heating
velocity are adjusted for improved efficiency. By monitoring the outdoor humidity, system
• Advanced Printed Circuit Board Cooling target pressures can be reduced to extend heating
Improved cooling performance of the inverter operation, delay defrost operation and reduce
printed circuit board by using liquid refrigerant power consumption.
instead of heat sink cooling methods.
Performance
Expansive operating range in cooling and heating without
adding accessories:
• LG Multi V™ 5 uses vapor injection technology
for improved heating performance in ambient
conditions as low as -22˚F.
• Using a variable path heat exchanger, LG Multi V™ 5
performs in low ambient conditions to provide
cooling down to 5˚F.

Comfort
• Quiet Operation
Multi V™ indoor units are among the quietest in
the industry, with rated sound levels as low as
23dB(A). In addition to temperature, airflow and
dehumidification, low sound levels contribute to a
Design Flexibility relaxing environment.
• Individualized Zone Control
• Higher-Elevation Piping Technology
Multi V™ solutions allow the user to control the
More floors with fewer systems. LG Multi V™ 5
space to the temperature desired. This further
eliminates the need to invest in extra systems
enhances comfort while promoting reduced
and saves on installation. Enjoy no heating
power consumption.
capacity losses due to long pipe length.
• Indoor Air Quality
• Compact & Lightweight
All Multi V™ indoor units incorporate a reusable,
More indoor zones, less outdoor space. When
washable filter. Since distribution and return ducts
space or access is at a premium, Multi V™ 5
are not required for this system, dust accumulation
offers significant cost advantages on large
is reduced, contributing to improved indoor air
projects.
quality.

3 LG Air Conditioning Technologies


TRAINING

MA

NJ

CA

GA
TX

Training
LG US Air Conditioning Technologies is headquartered near Atlanta in Alpharetta, Georgia, along with a full training
academy. Additional training academies are located in California, Texas, New Jersey, and Massachusetts. Since 2008,
our academies have trained thousands on the advantages of LG air conditioning products, and even more have been
trained through LG’s online training modules. World-class trainers with years of experience teach classes in duct-
free technology, with topics covering everything from installation to service for the full range of LG air conditioning
products. LG also has a number of strategically placed partner academies throughout the United States that offer a
number of LG-focused training classes as well.
For HVAC professionals, LG offers online instruction via our Learning Management System and classroom training at
our training academies, strategically placed throughout the country. Training is open to all contractors; ask your LG
Electronics authorized distributor for details. For more information and to find out how you can be part of the next
training class near you, visit https://lghvac.com/training.

Engineering and Service Tools


As part of our commitment to innovation, LG has developed inventive ways to enhance the engineer’s and service
technician’s experience with these tools:
• LG Monitoring View (LGMV) Software and Mobile App both connect to LG Multi V™ Solutions to allow technicians
to troubleshoot accurately and evaluate equipment performance by interfacing directly with the unit. The software
provides an accurate picture of an operating system without the need to check system temperatures manually,
access the refrigerant circuit for system pressures, or perform time-consuming resistance and voltage tests. This
service tool provides the most effective troubleshooting method for LG Multi V™ equipment.
• LATS HVAC is an integrated piping sizing tool for LG Air Conditioning Technologies products, including Multi V™,
Multi F, Single Zone, DOAS, and ERV. Also available to assist with pipe diameter selection and advise on the
unit selection process are an Autodesk Revit® plug-in (LATS Revit) and Bluebeam Revu® tool sets for LG HVAC
products. Using drag and drop functionality, layout your LG products quickly with these tools. In addition, LATS
Revit can calculate critical details like output capacity and additional refrigerant and confirm pipe lengths are
within allowable tolerances based on inputted data. Reach out to your local LG representative for help with using
LATS to save time.
Autodesk and Revit are registered trademarks or trademarks of Autodesk, Inc., in the USA and other countries.
Bluebeam and Revu are registered trademarks of Bluebeam, Inc.

4
5 LG Air Conditioning Technologies
TABLE OF CONTENTS

AIR SOURCE

Multi V™ 5 with LGRED° 12

Multi V S® with LGRED° 23

Multi V S® 24

WATER SOURCE

Multi V WATER® 5 Heat Pump and 28


Heat Recovery

AIR TECHNOLOGIES

Energy Recovery Ventilator (ERV) 35

Outside Air Unit (OAU) 36

Air Handling Unit (AHU) Conversion Kits 37

Rooftop DOAS 39

Split Compact DOAS 40

OUTDOOR UNIT ACCESSORIES

Heat Recovery Unit 41

Accessories 42

6
OUTDOOR UNIT
Lineup
System
Frames 2 3 4 5 6 8 10 12
Type

•• •• •• ••
• Heat Pump and Heat
Multi V™ 5 Recovery in the same
chassis
LGRED
Powerful Heat Technology • Available in 208-
RELIABLE TO EXTREME DEGREES
230V and 460V

Air
Source

• • • •• • •
• Heat Pump or Heat
Recovery Systems 1 1
Multi V S® • Single-Phase Power
Three-Phase Power
1

Multi V S® • Heat Pump and Heat


Recovery Systems
LGRED
Powerful Heat Technology • Single-Phase Power
RELIABLE TO EXTREME DEGREES

Multi V
WATER® 5 • Heat Pump and Heat
208-230V Recovery Systems

Water
Source

Multi V
• Heat Pump and Heat
WATER® 5 Recovery Systems
460V

7 LG Air Conditioning Technologies


OUTDOOR UNIT
•• = Heat Pump
= Heat Recovery
= Heat Pump and Heat Recovery
Unit : Tons

14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 48

•• •• •• ••
•• •• •• •• •• •• ••

LINEUP
•• •• •• ••

8
INDOOR UNIT Lineup
Chassis 5 7 9 12 15 18

Gallery
• •
• • • • • •
Art Cool™

Mirror

Standard Wall Mounted


• • • • • •
1-Way
• • • •
2-Way

• • • • • •
Ceiling Cassette

4-Way (2’x2’)

4-Way (3’x3’)
• • • • •
Ceiling
Suspended
Ceiling Mounted

Low Static
• • • • •
Ceiling
Concealed
Convertible
Mid Static • • • • •
Ducted
Mid Static

High Static
• • • • •
Multi-
Position
Air Handler
Unit
Vertical / Horizontal
• •
With Case
• • • • •
• • • • •
Floor Standing

Without Case

9 LG Air Conditioning Technologies


INDOOR UNIT
LG indoor units offer a wide range of styles and features to fit all of your cooling and heating needs. With cassettes that mount flush to
the ceiling, ducted units that are completely concealed in the ceiling, and LG's award-winning Art Cool Gallery and mirror-finished, wall-
mounted units that fit into any décor, the Multi V™ solution offers unparalleled aesthetic design and indoor units to fit into multiple
applications.

Unit : kBtu/h
24 28 30 36 42 48 54 76 96


• • •

LINEUP

• • • • •
• • •


• • • • •
• • • • • • •
• • • • • •


10
AIR SOURCE
SOLUTIONS

MULTI V™ 5 MULTI V S®
Heat Pump and Heat Pump and
Heat Recovery Heat Recovery
6 to 42 Tons 3 to 4 Tons

LGRED
Powerful Heat Technology
LGRED
Powerful Heat Technology
R E L I A B L E TO E X T R E M E D E G R E E S R E L I A B L E TO E X T R E M E D E G R E E S

MULTI V S®
Heat Pump or
Heat Recovery
2 to 8 Tons

AHRI Certified - Unitary Small HP


AHRI Standard 210/240
AHRI Certified - Variable Refrigerant Flow (VRF) Multi-Split AC and HP Certification applies only when the complete system
AHRI Standard 1230 is listed with AHRI.

11 LG Air Conditioning Technologies


MULTI V™ 5
LGRED
Powerful Heat Technology

MULTI V™ 5
R E L I A B L E TO E X T R E M E D E G R E E S

ARUM072BTE5 ARUM***BTE5
Specifications Unit ARUM072BTE5 ARUM096BTE5 ARUM121BTE5 ARUM144BTE5
Frames ARUM072BTE5 ARUM096BTE5 ARUM121BTE5 ARUM144BTE5
Tons 6 8 10 12
Cooling Btu/h 72,000 96,000 119,700 144,000
Nominal Capacity
Heating Btu/h 81,000 108,000 135,000 162,000
Cooling Btu/h 69,000 92,000 114,000 138,000
Rated Capacity1
Heating Btu/h 77,000 103,000 129,000 152,000
Power Voltage V / Hz / Ø 208-230/60/3 208-230/60/3 208-230/60/3 208-230/60/3
Power/Communication Wiring No x AWG 2 x 18 2 x 18 2 x 18 2 x 18
Cooling ˚F 5 ~122 5 ~122 5 ~122 5 ~122

Operating Range Heating ˚F -22 ~ 61 -22 ~ 61 -22 ~ 61 -22 ~ 61


Simultaneous ˚F 14 ~ 81 14 ~ 81 14 ~ 81 14 ~ 81
Operation2
36-5/8 x 66-17/32 x 48-13/16 x 66-17/32 x 48-13/16 x 66-17/32 x 48-13/16 x 66-17/32 x
Dimensions (W×H×D) Body in
29-29/32 29-29/32 29-29/32 29-29/32
Net lbs 430 507 507 639
Weight
Shipping lbs 452 534 534 666
Sound Pressure3 dB(A) 58.0 58.0 59.0 60.0
Rated CFM 6,600 7,400 8,400 9,300
Fan (Propeller)
Max. CFM 8,470 11,300 11,300 11,300
Type DC Scroll DC Scroll DC Scroll DC Scroll
Compressor (DC Scroll) Oil Type PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D
Quantity 1 1 1 2
Coating Black Coated Fin™ Black Coated Fin™ Black Coated Fin™ Black Coated Fin™
Heat Exchanger
Rows/Fins per Inch 2/17 2/17 2/17 3/17
Liquid Line in 3/8 3/8 1/2 1/2
Piping L/P Vapor Line in 3/4 7/8 1-1/8 1-1/8
H/P Vapor Line4 in 5/8 3/4 3/4 7/8
Type R410A R410A R410A R410A
Refrigerant Charge lbs 14.3 23.2 23.2 26.5
Control EEV EEV EEV EEV
Maximum Number of Indoor Units5 13 16 20 24

1. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.
2. Temperatures shown are for Simultaneous operation - primarily cooling. The simultaneous operation range (primarily heating) is 14°F to 61°F.
3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
4. Used in Heat Recovery Systems only.
5. The System Combination Ratio must be between 50 and 130%.
6. Due to our commitment to continued innovation, some specifications may be changed without notification.

12
MULTI V™ 5
LGRED
Powerful Heat Technology
R E L I A B L E TO E X T R E M E D E G R E E S

ARUM***BTE5
Specifications Unit ARUM168BTE5 ARUM192BTE5 ARUM216BTE5 ARUM241BTE5

Frames ARUM168BTE5 ARUM192BTE5 ARUM216BTE5 ARUM241BTE5

Tons 14 16 18 20
Cooling Btu/h 168,000 192,000 216,000 233,100
Nominal Capacity
Heating Btu/h 189,000 216,000 243,000 243,000
Cooling Btu/h 160,000 184,000 206,000 222,000
Rated Capacity1
Heating Btu/h 180,000 206,000 230,000 230,000
Power Voltage V / Hz / Ø 208-230/60/3 208-230/60/3 208-230/60/3 208-230/60/3
Power/Communication Wiring No x AWG 2 x 18 2 x 18 2 x 18 2 x 18
Cooling ˚F 5 ~122 5 ~122 5 ~122 5 ~122

Operating Range Heating ˚F -22 ~ 61 -22 ~ 61 -22 ~ 61 -22 ~ 61


Simultaneous ˚F 14 ~ 81 14 ~ 81 14 ~ 81 14 ~ 81
Operation2
Dimensions (W×H×D) Body in 48-13/16 x 66-17/32 x 29-29/32 48-13/16 x 66-17/32 x 29-29/32 48-13/16 x 66-17/32 x 29-29/32 48-13/16 x 66-17/32 x 29-29/32
Net lbs 639 659 666 666
Weight
Shipping lbs 666 688 694 694
Sound Pressure3 dB(A) 61.0 62.0 64.0 65.0
Rated CFM 10,300 10,300 10,300 10,300
Fan (Propeller)
Max. CFM 11,300 11,300 11,300 11,300
Type DC Scroll DC Scroll DC Scroll DC Scroll
Compressor (DC Scroll) Oil Type PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D
Quantity 2 2 2 2
Coating Black Coated Fin™ Black Coated Fin™ Black Coated Fin™ Black Coated Fin™
Heat Exchanger
Rows/Fins per Inch 3/17 3/17 3/17 3/17
Liquid Line in 5/8 5/8 5/8 5/8
Piping L/P Vapor Line in 1-1/8 1-1/8 1-1/8 1-3/8
H/P Vapor Line4 in 7/8 1-1/8 1-1/8 1-1/8
Type R410A R410A R410A R410A
Refrigerant Charge lbs 26.5 30.9 37.5 37.5
Control EEV EEV EEV EEV
Maximum Number of Indoor Units5 29 32 35 39

1. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.
2. Temperatures shown are for Simultaneous operation - primarily cooling. The simultaneous operation range (primarily heating) is 14°F to 61°F.
3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
4. Used in Heat Recovery Systems only.
5. The System Combination Ratio must be between 50 and 130%.
6. Due to our commitment to continued innovation, some specifications may be changed without notification.

13 LG Air Conditioning Technologies


MULTI V™ 5
LGRED
Powerful Heat Technology
R E L I A B L E TO E X T R E M E D E G R E E S

MULTI V™ 5
ARUM***BTE5
Specifications Unit ARUM264BTE5 ARUM288BTE5 ARUM312BTE5 ARUM336BTE5
ARUM096BTE5 ARUM096BTE5 ARUM096BTE5 ARUM121BTE5
Frames
ARUM168BTE5 ARUM192BTE5 ARUM216BTE5 ARUM216BTE5

Tons 22 24 26 28
Cooling Btu/h 264,000 288,000 312,000 336,000
Nominal Capacity
Heating Btu/h 297,000 324,000 351,000 378,000
Cooling Btu/h 252,000 276,000 298,000 320,000
Rated Capacity1
Heating Btu/h 282,000 308,000 332,000 358,000
Power Voltage V / Hz / Ø 208-230/60/3 208-230/60/3 208-230/60/3 208-230/60/3
Power/Communication Wiring No x AWG 2 x 18 2 x 18 2 x 18 2 x 18
Cooling ˚F 5 ~122 5 ~122 5 ~122 5 ~122

Operating Range Heating ˚F -22 ~ 61 -22 ~ 61 -22 ~ 61 -22 ~ 61


Simultaneous ˚F 14 ~ 81 14 ~ 81 14 ~ 81 14 ~ 81
Operation2
Dimensions (W×H×D) Body in 97-5/8 x 66-17/32 x 29-29/32 97-5/8 x 66-17/32 x 29-29/32 97-5/8 x 66-17/32 x 29-29/32 97-5/8 x 66-17/32 x 29-29/32
Net lbs 507+639 507+659 507+666 507+666
Weight
Shipping lbs 534+666 534+688 534+694 534+694
Sound Pressure3 dB(A) 63.0 63.0 65.0 65.0
Rated CFM 17,700 17,700 17,700 18,700
Fan (Propeller)
Max. CFM 22,600 22,600 22,600 22,600
Type DC Scroll DC Scroll DC Scroll DC Scroll
Compressor (DC Scroll) Oil Type PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D
Quantity 3 3 3 3
Coating Black Coated Fin™ Black Coated Fin™ Black Coated Fin™ Black Coated Fin™
Heat Exchanger
Rows/Fins per Inch 2/17+3/17 2/17+3/17 2/17+3/17 2/17+3/17
Liquid Line in 3/8 + 5/8 3/8 + 5/8 3/8 + 5/8 1/2 + 5/8
Piping L/P Vapor Line in 7/8 + 1-1/8 7/8 + 1-1/8 7/8 + 1-1/8 1-1/8 + 1-1/8
H/P Vapor Line4 in 3/4 + 7/8 3/4 + 1-1/8 3/4 + 1-1/8 3/4 + 1-1/8
Type R410A R410A R410A R410A
Refrigerant Charge lbs 23.2+26.5 23.2+30.9 23.2+37.5 23.2+37.5
Control EEV EEV EEV EEV
Maximum Number of Indoor Units5 42 45 52 55

1. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.
2. Temperatures shown are for Simultaneous operation - primarily cooling. The simultaneous operation range (primarily heating) is 14°F to 61°F.
3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
4. Used in Heat Recovery Systems only.
5. The System Combination Ratio must be between 50 and 130%.
6. Due to our commitment to continued innovation, some specifications may be changed without notification.

14
MULTI V™ 5
LGRED
Powerful Heat Technology
R E L I A B L E TO E X T R E M E D E G R E E S

ARUM***BTE5
Specifications Unit ARUM360BTE5 ARUM384BTE5 ARUM408BTE5
ARUM144BTE5 ARUM168BTE5 ARUM192BTE5
Frames
ARUM216BTE5 ARUM216BTE5 ARUM216BTE5

Tons 30 32 34
Cooling Btu/h 360,000 384,000 408,000
Nominal Capacity
Heating Btu/h 405,000 432,000 459,000
Cooling Btu/h 344,000 366,000 390,000
Rated Capacity1
Heating Btu/h 384,000 410,000 434,000
Power Voltage V / Hz / Ø 208-230/60/3 208-230/60/3 208-230/60/3
Power/Communication Wiring No x AWG 2 x 18 2 x 18 2 x 18
Cooling ˚F 5 ~122 5 ~122 5 ~122

Operating Range Heating ˚F -22 ~ 61 -22 ~ 61 -22 ~ 61


Simultaneous ˚F 14 ~ 81 14 ~ 81 14 ~ 81
Operation2
Dimensions (W×H×D) Body in 97-5/8 x 66-17/32 x 29-29/32 97-5/8 x 66-17/32 x 29-29/32 97-5/8 x 66-17/32 x 29-29/32
Net lbs 639+666 639+666 659+666
Weight
Shipping lbs 666+694 666+694 688+694
Sound Pressure3 dB(A) 66.0 66.0 66.0
Rated CFM 19,600 20,600 20,600
Fan (Propeller)
Max. CFM 22,600 22,600 22,600
Type DC Scroll DC Scroll DC Scroll
Compressor (DC Scroll) Oil Type PVE/FVC68D PVE/FVC68D PVE/FVC68D
Quantity 4 4 4
Coating Black Coated Fin™ Black Coated Fin™ Black Coated Fin™
Heat Exchanger
Rows/Fins per Inch 3/17 x 2 3/17 x 2 3/17 x 2
Liquid Line in 1/2 + 5/8 5/8 + 5/8 5/8 + 5/8
Piping L/P Vapor Line in 1-1/8 + 1-1/8 1-1/8 + 1-1/8 1-1/8 + 1-1/8
H/P Vapor Line4 in 7/8 + 1-1/8 7/8 + 1-1/8 1-1/8 + 1-1/8
Type R410A R410A R410A
Refrigerant Charge lbs 26.5+37.5 26.5+37.5 30.9+37.5
Control EEV EEV EEV
Maximum Number of Indoor Units5 58 61 64

1. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.
2. Temperatures shown are for Simultaneous operation - primarily cooling. The simultaneous operation range (primarily heating) is 14°F to 61°F.
3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
4. Used in Heat Recovery Systems only.
5. The System Combination Ratio must be between 50 and 130%.
6. Due to our commitment to continued innovation, some specifications may be changed without notification.

15 LG Air Conditioning Technologies


MULTI V™ 5
LGRED
Powerful Heat Technology
R E L I A B L E TO E X T R E M E D E G R E E S

MULTI V™ 5
ARUM***BTE5

Specifications Unit ARUM432BTE5 ARUM456BTE5 ARUM480BTE5 ARUM504BTE5


ARUM121BTE5 ARUM121BTE5 ARUM121BTE5 ARUM121BTE5
Frames ARUM121BTE5 ARUM121BTE5 ARUM144BTE5 ARUM168BTE5
ARUM192BTE5 ARUM216BTE5 ARUM216BTE5 ARUM216BTE5
Tons 36 38 40 42
Cooling Btu/h 430,500 455,700 476,700 504,000
Nominal Capacity
Heating Btu/h 486,000 513,000 540,000 567,000
Cooling Btu/h 410,000 434,000 454,000 480,000
Rated Capacity 1

Heating Btu/h 460,000 484,000 510,000 534,000


Power Voltage V / Hz / Ø 208-230/60/3 208-230/60/3 208-230/60/3 208-230/60/3
Power/Communication Wiring No x AWG 2 x 18 2 x 18 2 x 18 2 x 18
Cooling ˚F 5 ~122 5 ~122 5 ~122 5 ~122

Operating Range Heating ˚F -22 ~ 61 -22 ~ 61 -22 ~ 61 -22 ~ 61


Simultaneous ˚F 14 ~ 81 14 ~ 81 14 ~ 81 14 ~ 81
Operation2
Dimensions (W×H×D) Body in 146-7/16 x 66-17/32 x 29-29/32 146-7/16 x 66-17/32 x 29-29/32 146-7/16 x 66-17/32 x 29-29/32 146-7/16 x 66-17/32 x 29-29/32
Net lbs 507+507+659 507+507+666 507+639+666 507+639+666
Weight
Shipping lbs 507+507+688 534+534+694 534+666+694 534+666+694
Sound Pressure3 dB(A) 66.0 66.0 67.0 67.0
Rated CFM 27,100 27,100 28,000 29,000
Fan (Propeller)
Max. CFM 33,900 33,900 33,900 33,900
Type DC Scroll DC Scroll DC Scroll DC Scroll
Compressor (DC Scroll) Oil Type PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D
Quantity 4 4 5 5
Coating Black Coated Fin™ Black Coated Fin™ Black Coated Fin™ Black Coated Fin™
Heat Exchanger
Rows/Fins per Inch 2/17 x 2 + 3/17 2/17 x 2 + 3/17 2/17 + 3/17 x 2 2/17 + 3/17 x 2
Liquid Line in 1/2 + 1/2 + 5/8 1/2 + 1/2 + 5/8 1/2 + 1/2 + 5/8 1/2 + 1/2 + 5/8
Piping L/P Vapor Line in 1-1/8 + 1-1/8+ 1-1/8 1-1/8 + 1-1/8+ 1-1/8 1-1/8 + 1-1/8+ 1-1/8 1-1/8 + 1-1/8+ 1-1/8
H/P Vapor Line4 in 3/4 + 3/4 + 1-1/8 3/4 + 3/4 + 1-1/8 3/4 + 7/8 + 1-1/8 3/4 + 7/8 + 1-1/8
Type R410A R410A R410A R410A
Refrigerant Charge lbs 23.2+23.2+30.9 23.2+23.2+37.5 23.2+26.5+37.5 23.2+26.5+37.5
Control EEV EEV EEV EEV
Maximum Number of Indoor Units5 64 64 64 64

1. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.
2. Temperatures shown are for Simultaneous operation - primarily cooling. The simultaneous operation range (primarily heating) is 14°F to 61°F.
3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
4. Used in Heat Recovery Systems only.
5. The System Combination Ratio must be between 50 and 130%.
6. Due to our commitment to continued innovation, some specifications may be changed without notification.

16
MULTI V™ 5
LGRED
Powerful Heat Technology
R E L I A B L E TO E X T R E M E D E G R E E S

ARUM072DTE5 ARUM***DTE5

Specifications Unit ARUM072DTE5 ARUM096DTE5 ARUM121DTE5 ARUM144DTE5


Frames ARUM072DTE5 ARUM096DTE5 ARUM121DTE5 ARUM144DTE5
Tons 6 8 10 12
Cooling Btu/h 72,000 96,000 119,700 144,000
Nominal Capacity
Heating Btu/h 81,000 108,000 135,000 162,000
Cooling Btu/h 69,000 92,000 114,000 138,000
Rated Capacity1
Heating Btu/h 77,000 103,000 129,000 152,000
Power Voltage V / Hz / Ø 460/60/3 460/60/3 460/60/3 460/60/3
Power/Communication Wiring No x AWG 2 x 18 2 x 18 2 x 18 2 x 18
Cooling ˚F 5 ~122 5 ~122 5 ~122 5 ~122

Operating Range Heating ˚F -22 ~ 61 -22 ~ 61 -22 ~ 61 -22 ~ 61


Simultaneous ˚F 14 ~ 81 14 ~ 81 14 ~ 81 14 ~ 81
Operation2
Dimensions (W×H×D) Body in 36-5/8 x 66-17/32 x 29-29/32 48-13/16 x 66-17/32 x 29-29/32 48-13/16 x 66-17/32 x 29-29/32 48-13/16 x 66-17/32 x 29-29/32
Net lbs 430 507 507 639
Weight
Shipping lbs 452 534 534 666
Sound Pressure3 dB(A) 58.0 58.0 59.0 60.0
Rated CFM 6,600 7,400 8,400 9,300
Fan (Propeller)
Max. CFM 8,470 11,300 11,300 11,300
Type DC Scroll DC Scroll DC Scroll DC Scroll
Compressor (DC Scroll) Oil Type PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D
Quantity 1 1 1 2
Coating Black Coated Fin™ Black Coated Fin™ Black Coated Fin™ Black Coated Fin™
Heat Exchanger
Rows/Fins per Inch 2/17 2/17 2/17 3/17
Liquid Line in 3/8 3/8 1/2 1/2
Piping L/P Vapor Line in 3/4 7/8 1-1/8 1-1/8
H/P Vapor Line4 in 5/8 3/4 3/4 7/8
Type R410A R410A R410A R410A
Refrigerant Charge lbs 14.3 23.2 23.2 26.5
Control EEV EEV EEV EEV
Maximum Number of Indoor Units5 13 16 20 24

1. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.
2. Temperatures shown are for Simultaneous operation - primarily cooling. The simultaneous operation range (primarily heating) is 14°F to 61°F.
3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
4. Used in Heat Recovery Systems only.
5. The System Combination Ratio must be between 50 and 130%.
6. Due to our commitment to continued innovation, some specifications may be changed without notification.

17 LG Air Conditioning Technologies


MULTI V™ 5
LGRED
Powerful Heat Technology
R E L I A B L E TO E X T R E M E D E G R E E S

MULTI V™ 5
ARUM***DTE5

Specifications Unit ARUM168DTE5 ARUM192DTE5 ARUM216DTE5 ARUM241DTE5


Frames ARUM168DTE5 ARUM192DTE5 ARUM216DTE5 ARUM241DTE5
Tons 14 16 18 20
Cooling Btu/h 168,000 192,000 216,000 233,100
Nominal Capacity
Heating Btu/h 189,000 216,000 243,000 243,000
Cooling Btu/h 160,000 184,000 206,000 222,000
Rated Capacity 1

Heating Btu/h 180,000 206,000 230,000 230,000


Power Voltage V / Hz / Ø 460/60/3 460/60/3 460/60/3 460/60/3
Power/Communication Wiring No x AWG 2 x 18 2 x 18 2 x 18 2 x 18
Cooling ˚F 5 ~122 5 ~122 5 ~122 5 ~ 122

Operating Range Heating ˚F -22 ~ 61 -22 ~ 61 -22 ~ 61 -22 ~ 61


Simultaneous ˚F 14 ~ 81 14 ~ 81 14 ~ 81 14 ~ 81
Operation2
Dimensions (W×H×D) Body in 48-13/16 x 66-17/32 x 29-29/32 48-13/16 x 66-17/32 x 29-29/32 48-13/16 x 66-17/32 x 29-29/32 48-13/16 x 66-17/32 x 29-29/32
Net lbs 639 659 666 666
Weight
Shipping lbs 666 688 694 694
Sound Pressure3 dB(A) 61.0 62.0 64.0 65.0
Rated CFM 10,300 10,300 10,300 10,300
Fan (Propeller)
Max. CFM 11,300 11,300 11,300 11,300
Type DC Scroll DC Scroll DC Scroll DC Scroll
Compressor (DC Scroll) Oil Type PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D
Quantity 2 2 2 2
Coating Black Coated Fin™ Black Coated Fin™ Black Coated Fin™ Black Coated Fin™
Heat Exchanger
Rows/Fins per Inch 3/17 3/17 3/17 3/17
Liquid Line in 5/8 5/8 5/8 5/8
Piping L/P Vapor Line in 1-1/8 1-1/8 1-1/8 1-3/8
H/P Vapor Line4 in 7/8 1-1/8 1-1/8 1-1/8
Type R410A R410A R410A R410A
Refrigerant Charge lbs 26.5 30.9 37.5 37.5
Control EEV EEV EEV EEV
Maximum Number of Indoor Units5 29 32 35 39

1. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.
2. Temperatures shown are for Simultaneous operation - primarily cooling. The simultaneous operation range (primarily heating) is 14°F to 61°F.
3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
4. Used in Heat Recovery Systems only.
5. The System Combination Ratio must be between 50 and 130%.
6. Due to our commitment to continued innovation, some specifications may be changed without notification.

18
MULTI V™ 5
LGRED
Powerful Heat Technology
R E L I A B L E TO E X T R E M E D E G R E E S

ARUM***DTE5

Specifications Unit ARUM264DTE5 ARUM288DTE5 ARUM312DTE5 ARUM336DTE5

ARUM096DTE5 ARUM096DTE5 ARUM096DTE5 ARUM121DTE5


Frames
ARUM168DTE5 ARUM192DTE5 ARUM216DTE5 ARUM216DTE5

Tons 22 24 26 28
Cooling Btu/h 264,000 288,000 312,000 336,000
Nominal Capacity
Heating Btu/h 297,000 324,000 351,000 378,000
Cooling Btu/h 252,000 276,000 298,000 320,000
Rated Capacity1
Heating Btu/h 282,000 308,000 332,000 358,000
Power Voltage V / Hz / Ø 460/60/3 460/60/3 460/60/3 460/60/3
Power/Communication Wiring No x AWG 2 x 18 2 x 18 2 x 18 2 x 18
Cooling ˚F 5 ~122 5 ~ 122 5 ~ 122 5 ~ 122

Operating Range Heating ˚F -22 ~ 61 -22 ~ 61 -22 ~ 61 -22 ~ 61


Simultaneous ˚F 14 ~ 81 14 ~ 81 14 ~ 81 14 ~ 81
Operation2
Dimensions (W×H×D) Body in 97-5/8 x 66-17/32 x 29-29/32 97-5/8 x 66-17/32 x 29-29/32 97-5/8 x 66-17/32 x 29-29/32 97-5/8 x 66-17/32 x 29-29/32
Net lbs 507+639 507+659 507+666 507+666
Weight
Shipping lbs 534+666 534+688 534+694 534+694
Sound Pressure3 dB(A) 63.0 63.0 65.0 65.0
Rated CFM 17,700 17,700 17,700 18,700
Fan (Propeller)
Max. CFM 22,600 22,600 22,600 22,600
Type DC Scroll DC Scroll DC Scroll DC Scroll
Compressor (DC Scroll) Oil Type PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D
Quantity 3 3 3 3
Coating Black Coated Fin™ Black Coated Fin™ Black Coated Fin™ Black Coated Fin™
Heat Exchanger
Rows/Fins per Inch 2/17+3/17 2/17+3/17 2/17+3/17 2/17+3/17
Liquid Line in 3/8 + 5/8 3/8 + 5/8 3/8 + 5/8 1/2 + 5/8
Piping L/P Vapor Line in 7/8 + 1-1/8 7/8 + 1-1/8 7/8 + 1-1/8 1-1/8 + 1-1/8
H/P Vapor Line4 in 3/4 + 7/8 3/4 + 1-1/8 3/4 + 1-1/8 3/4 + 1-1/8
Type R410A R410A R410A R410A
Refrigerant Charge lbs 23.2+26.5 23.2+30.9 23.2+37.5 23.2+37.5
Control EEV EEV EEV EEV
Maximum Number of Indoor Units5 42 45 52 55

1. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.
2. Temperatures shown are for Simultaneous operation - primarily cooling. The simultaneous operation range (primarily heating) is 14°F to 61°F.
3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
4. Used in Heat Recovery Systems only.
5. The System Combination Ratio must be between 50 and 130%.
6. Due to our commitment to continued innovation, some specifications may be changed without notification.

19 LG Air Conditioning Technologies


MULTI V™ 5
LGRED
Powerful Heat Technology
R E L I A B L E TO E X T R E M E D E G R E E S

MULTI V™ 5
ARUM***DTE5
Specifications Unit ARUM360DTE5 ARUM384DTE5 ARUM408DTE5
ARUM144DTE5 ARUM168DTE5 ARUM192DTE5
Frames
ARUM216DTE5 ARUM216DTE5 ARUM216DTE5

Tons 30 32 34
Cooling Btu/h 360,000 384,000 408,000
Nominal Capacity
Heating Btu/h 405,000 432,000 459,000
Cooling Btu/h 344,000 366,000 390,000
Rated Capacity1
Heating Btu/h 384,000 410,000 434,000
Power Voltage V / Hz / Ø 460/60/3 460/60/3 460/60/3
Power/Communication Wiring No x AWG 2 x 18 2 x 18 2 x 18
Cooling ˚F 5 ~ 122 5 ~ 122 5 ~ 122

Operating Range Heating ˚F -22 ~ 61 -22 ~ 61 -22 ~ 61


Simultaneous ˚F 14 ~ 81 14 ~ 81 14 ~ 81
Operation2
Dimensions (W×H×D) Body in 97-5/8 x 66-17/32 x 29-29/32 97-5/8 x 66-17/32 x 29-29/32 97-5/8 x 66-17/32 x 29-29/32
Net lbs 639+666 639+666 659+666
Weight
Shipping lbs 666+694 666+694 688+694
Sound Pressure3 dB(A) 66.0 66.0 66.0
Rated CFM 19,600 20,600 20,600
Fan (Propeller)
Max. CFM 22,600 22,600 22,600
Type DC Scroll DC Scroll DC Scroll
Compressor (DC Scroll) Oil Type PVE/FVC68D PVE/FVC68D PVE/FVC68D
Quantity 4 4 4
Coating Black Coated Fin™ Black Coated Fin™ Black Coated Fin™
Heat Exchanger
Rows/Fins per Inch 3/17 x 2 3/17 x 2 3/17 x 2
Liquid Line in 1/2 + 5/8 5/8 + 5/8 5/8 + 5/8
Piping L/P Vapor Line in 1-1/8 + 1-1/8 1-1/8 + 1-1/8 1-1/8 + 1-1/8
H/P Vapor Line4 in 7/8 + 1-1/8 7/8 + 1-1/8 1-1/8 + 1-1/8
Type R410A R410A R410A
Refrigerant Charge lbs 26.5+37.5 26.5+37.5 30.9+37.5
Control EEV EEV EEV
Maximum Number of Indoor Units5 58 61 64

1. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.
2. Temperatures shown are for Simultaneous operation - primarily cooling. The simultaneous operation range (primarily heating) is 14°F to 61°F.
3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
4. Used in Heat Recovery Systems only.
5. The System Combination Ratio must be between 50 and 130%.
6. Due to our commitment to continued innovation, some specifications may be changed without notification.

20
MULTI V™ 5
LGRED
Powerful Heat Technology
R E L I A B L E TO E X T R E M E D E G R E E S

ARUM***DTE5
Specifications Unit ARUM432DTE5 ARUM456DTE5 ARUM480DTE5 ARUM504DTE5
ARUM121DTE5 ARUM121DTE5 ARUM121DTE5 ARUM121DTE5
Frames ARUM121DTE5 ARUM121DTE5 ARUM144DTE5 ARUM168DTE5
ARUM192DTE5 ARUM216DTE5 ARUM216DTE5 ARUM216DTE5
Tons 36 38 40 42
Cooling Btu/h 430,500 455,700 476,700 504,000
Nominal Capacity
Heating Btu/h 486,000 513,000 540,000 567,000
Cooling Btu/h 410,000 434,000 454,000 480,000
Rated Capacity 1

Heating Btu/h 460,000 484,000 510,000 534,000


Power Voltage V / Hz / Ø 460/60/3 460/60/3 460/60/3 460/60/3
Power/Communication Wiring No x AWG 2 x 18 2 x 18 2 x 18 2 x 18
Cooling ˚F 5 ~ 122 5 ~ 122 5 ~ 122 5 ~ 122

Operating Range Heating ˚F -22 ~ 61 -22 ~ 61 -22 ~ 61 -22 ~ 61


Simultaneous ˚F 14 ~ 81 14 ~ 81 14 ~ 81 14 ~ 81
Operation2
Dimensions (W×H×D) Body in 146-7/16 x 66-17/32 x 29-29/32 146-7/16 x 66-17/32 x 29-29/32 146-7/16 x 66-17/32 x 29-29/32 146-7/16 x 66-17/32 x 29-29/32
Net lbs 507+507+659 507+507+666 507+639+666 507+639+666
Weight
Shipping lbs 534+534+688 534+534+694 534+666+694 534+666+694
Sound Pressure3 dB(A) 66.0 66.0 67.0 67.0
Rated CFM 27,100 27,100 28,000 29,000
Fan (Propeller)
Max. CFM 33,900 33,900 33,900 33,900
Type DC Scroll DC Scroll DC Scroll DC Scroll
Compressor (DC Scroll) Oil Type PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D
Quantity 4 4 5 5
Coating Black Coated Fin™ Black Coated Fin™ Black Coated Fin™ Black Coated Fin™
Heat Exchanger
Rows/Fins per Inch 2/17 x 2 + 3/17 2/17 x 2 + 3/17 2/17 + 3/17 x 2 2/17 + 3/17 x 2
Liquid Line in 1/2 + 1/2 + 5/8 1/2 + 1/2 + 5/8 1/2 + 1/2 + 5/8 1/2 + 1/2 + 5/8
Piping L/P Vapor Line in 1-1/8 + 1-1/8+ 1-1/8 1-1/8 + 1-1/8+ 1-1/8 1-1/8 + 1-1/8+ 1-1/8 1-1/8 + 1-1/8+ 1-1/8
H/P Vapor Line4 in 3/4 + 3/4 + 1-1/8 3/4 + 3/4 + 1-1/8 3/4 + 7/8 + 1-1/8 3/4 + 7/8 + 1-1/8
Type R410A R410A R410A R410A
Refrigerant Charge lbs 23.2+23.2+30.9 23.2+23.2+37.5 23.2+26.5+37.5 23.2+26.5+37.5
Control EEV EEV EEV EEV
Maximum Number of Indoor Units5 64 64 64 64

1. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.
2. Temperatures shown are for Simultaneous operation - primarily cooling. The simultaneous operation range (primarily heating) is 14°F to 61°F.
3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
4. Used in Heat Recovery Systems only.
5. The System Combination Ratio must be between 50 and 130%.
6. Due to our commitment to continued innovation, some specifications may be changed without notification.

21 LG Air Conditioning Technologies


LIGHT COMMERCIAL
AND RESIDENTIAL
LG Multi V S® utilizes single-phase and three-phase power so it can be used
residentially as well as in a wide range of commercial applications, offering overall
increased flexibility and efficiency for property owners.

MULTI V S® MULTI V S®
WITH LGRED° Heat Pump or Heat Recovery
Heat Pump and Heat Recovery 2 to 8 Tons
3 to 4 Tons

22
MULTI V S® WITH LGRED°

HEAT PUMP AND HEAT RECOVERY

Continuous heating down to -13 °F.


100% heating capacity at 5°F.

ARUM036GSS5
ARUM048GSS5

Model Specifications Unit ARUM036GSS5 ARUM048GSS5


Heat Pump / Heat Recovery Heat Pump and Heat Recovery Heat Pump and Heat Recovery
Tons 3 4
Nominal Cooling Capacity1 Btu/h 36,000 48,000
Nominal Heating Capacity1 Btu/h 42,000 54,000
Capacity
Rated Cooling Capacity2 Btu/h 36,000 48,000
Rated Heating Capacity2 Btu/h 42,000 54,000
Voltage V / Hz / Ø 208-230/60/1 208-230/60/1
Power
Power/Communication Wiring5 No. x AWG 2 x 18 2 x 18
Cooling Operation Range6 °F 23 ~ 122 23 ~ 122
Operating Range
Heating Operation Range °F -13 ~ 61 -13 ~ 61
Dimensions Dimensions (WxHxD) in 37-13/32 x 54-11/32 x 13 37-3/32 x 54-11/32 x 13
Net lbs 263 263
Weight
Shipping lbs 294 294
Sound Pressure4 dB(A) 50/53 52/54
Cooling/Heating Axial Flow Fan x2 Axial Flow Fan x2
Fan
Air Flow Rate CFM 4238 4238
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Compressor Oil Type FVC68D FVC68D
Quantity 1 1
Coating Black Coated Fin™ / Hydrophilic / Cooper Tube Black Coated Fin™ / Hydrophilic / Cooper Tube
Heat Exchange
Rows/Fins per inch 3 / 14 3 / 14
Liquid Line (OD) in 3/8 3/8
Piping for Heat Recovery
HP/Vapor Line (OD) in 5/8 5/8
Operation
Liquid Line (OD) in 3/4 3/4

Piping for Heat Pump Liquid Line (OD) in 3/8 3/8


Operation7 Liquid Line (OD) in 5/8 5/8
Type R410A R410A
Refrigerant Charge lbs 7.7 lbs. 7.7 lbs.
Control EEV EEV
Number of Indoor Units3 Minimum / Maximum 2/6 2/8

1. Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft. of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All
capacities are net with a Combination Ratio between 95–105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80°F dry bulb (DB) and 67°F wet bulb (WB) and outdoor ambient conditions of 95°F dry bulb (DB) and 75°F wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70°F dry bulb (DB) and 59°F wet bulb (WB) and outdoor ambient conditions of 47°F dry bulb (DB) and 43°F wet bulb (WB).
2. Rated capacity is certified under AHRI Standard 210/240. See www.ahrinet.org for information.
3. The System Combination Ratio must be between 50–130%.
4. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5. Power wiring is field provided, solid or stranded, and must comply with all local and national codes. Refer to the engineering manual for detailed electrical data.
6. Cooling range with the Low Ambient Baffle Kit (sold separately) is down to -9.9°F.
7. Multi V S® units with LGRED° ship from the factory configured for heat recovery operation. For heat pump operation, the DIP switch settings must be set accordingly. See the product installation manual for details.
ENERGY STAR® and the ENERGY STAR mark are registered trademarks owned by the U.S. Environmental Protection Agency.
Due to our commitment to continued innovation, some specifications may be changed without notification.

23 LG Air Conditioning Technologies


MULTI V S® HEAT PUMP

MULTI V S®
ARUN024GSS4
ARUN038GSS4
ARUN048GSS4
ARUN060GSS4

Model Specifications Unit ARUN024GSS4 ARUN038GSS4 ARUN048GSS4 ARUN060GSS4


Heat Pump / Heat Recovery Heat Pump Heat Pump Heat Pump Heat Pump
Tons 2 3 4 5
Nominal Cooling Capacity1 Btu/h 24,000 39,500 50,000 60,000

Nominal Heating Capacity1 Btu/h 27,000 44,000 56,500 64,000


Capacity
Rated Cooling Capacity2 Btu/h 24,000 38,000 48,000 60,000
Rated Heating Capacity2 Btu/h 27,000 42,000 54,000 64,000
Voltage V / Hz / Ø 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/1
Power
Power/Communication Wiring5 No. x AWG 2 x 18 2 x 18 2 x 18 2 x 18
Cooling Operation Range6 °F 23 ~ 122 23 ~ 122 23 ~ 122 23 ~ 122
Operating Range
Heating Operation Range °F -4 ~ 61 -4 ~ 61 -4 ~ 61 -13 ~ 61
Dimensions Dimensions (WxHxD) in 37-13/32 x 32-27/32 x 13 37-13/32 x 54-11/32 x 13 37-13/32 x 54-11/32 x 13 37-13/32 x 54-11/32 x 13
Net lbs 159 207 207 260
Weight
Shipping lbs 176 218 218 291
Sound Pressure4 dB(A) 50 50 51 57
Type Axial Flow Fan Axial Flow Fan Axial Flow Fan Axial Flow Fan
Fan
Air Flow Rate CFM 2,119 3,885 3,885 3,885
Type DC Inverter DC Inverter DC Inverter Scroll Inverter
Compressor Oil Type PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D
Quantity 1 1 1 1
Gold Fin / Hydrophilic / Gold Fin / Hydrophilic / Gold Fin / Hydrophilic / Gold Fin / Hydrophilic /
Coating
Heat Exchanger Copper Tube Copper Tube Copper Tube Copper Tube
Rows/Fins per inch 2 / 14 2 / 14 2 / 14 3 / 14
Liquid Line (OD) in 3/8 3/8 3/8 3/8
Piping
Vapor Line (OD) in 5/8 5/8 5/8 3/4
Type R410A R410A R410A R410A
Refrigerant Charge lbs 4.0 6.6 6.6 7.7
Control EEV EEV EEV EEV
Number of Indoor Units3 Minimum / Maximum 2/4 2/6 2/8 2 / 12

1. Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft. of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All
capacities are net with a Combination Ratio between 95–105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80°F dry bulb (DB) and 67°F wet bulb (WB) and outdoor ambient conditions of 95°F dry bulb (DB) and 75°F wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70°F dry bulb (DB) and 59°F wet bulb (WB) and outdoor ambient conditions of 47°F dry bulb (DB) and 43°F wet bulb (WB).
2. Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
3. The System Combination Ratio must be between 50–130%.
4. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5. Power wiring is field provided, solid or stranded, and must comply with all local and national codes. Refer to the engineering manual for detailed electrical data.
6. Cooling range with the Low Ambient Baffle Kit (sold separately) is -9.9°F to +122°F.
Due to our commitment to continued innovation, some specifications may be changed without notification.

24
MULTI V S® HEAT RECOVERY

ARUB060GSS4

Model Specifications Unit ARUB060GSS4


Heat Pump / Heat Recovery Heat Recovery
Tons 5
Nominal Cooling Capacity1 Btu/h 60,000

Nominal Heating Capacity1 Btu/h 60,000


Capacity
Rated Cooling Capacity2 Btu/h 60,000
Rated Heating Capacity2 Btu/h 60,000
Voltage V / Hz / Ø 208-230/60/1
Power
Power/Communication Wiring5 No. x AWG 2 x 18
Cooling Operation Range6 °F 23 ~ 122
Operating Range
Heating Operation Range °F -13 ~ 61
Dimensions Dimensions (WxHxD) in 37-13/32 x 54-11/32 x 13
Net lbs 260
Weight
Shipping lbs 291
Sound Pressure4 dB(A) 57
Type Axial Flow Fan
Fan
Air Flow Rate CFM 3,885
Type Scroll Inverter
Compressor Oil Type PVE/FVC68D
Quantity 1
Coating Gold Fin / Hydrophilic / Copper Tube
Heat Exchange
Rows/Fins per inch 3 / 14
Liquid Line (OD) in 3/8
Piping HP/Vapor Line (OD) in 5/8
LP/Vapor Line (OD) in 3/4
Type R410A
Refrigerant Charge lbs 7.7
Control EEV
Number of Indoor Units3 Minimum / Maximum 2/12

1. Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft. of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All
capacities are net with a Combination Ratio between 95–105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80°F dry bulb (DB) and 67°F wet bulb (WB) and outdoor ambient conditions of 95°F dry bulb (DB) and 75°F wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70°F dry bulb (DB) and 59°F wet bulb (WB) and outdoor ambient conditions of 47°F dry bulb (DB) and 43°F wet bulb (WB).
2. Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
3. The System Combination Ratio must be between 50–130%.
4. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5. Power wiring is field provided, solid or stranded, and must comply with all local and national codes. Refer to the engineering manual for detailed electrical data.
6. Cooling range with the Low Ambient Baffle Kit (sold separately) is down to -9.9°F.
Due to our commitment to continued innovation, some specifications may be changed without notification.

25 LG Air Conditioning Technologies


MULTI V S® HEAT PUMP
T H R E E - P HAS E

MULTI V S®
ARUN072BSS5
ARUN096BSS5

Model Specifications Unit ARUN072BSS5 ARUN096BSS5


Heat Pump / Heat Recovery Heat Pump Heat Pump
Tons 6 8

Nominal Cooling Capacity1 Btu/h 72,000 96,000


Nominal Heating Capacity1 Btu/h 81,000 108,000
Capacity
Rated Cooling Capacity2 Btu/h 69,000 92,000
Rated Heating Capacity2 Btu/h 77,000 103,000
Voltage V / Hz / Ø 208-230/60/3 208-230/60/3
Power
Power/Communication Wiring5 No. x AWG 2 x 18 2 x 18
Cooling Operation Range6 °F 23 to 122 23 to 122
Operating Range
Heating Operation Range °F -13 to 61 -13 to 61
Dimensions Dimensions (WxHxD) in 42-29/32 x 63-3/8 x 17-17/32 42-29/32 x 63-3/8 x 17-17/32
Net lbs 348 348
Weight
Shipping lbs 379 379
Sound Pressure4 dB(A) 55 / 57 59 / 60
Cooling/Heating Axial Flow Fan Axial Flow Fan
Fan
Air Flow Rate CFM 7,416 7,416
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Compressor Oil Type PVE/FW68D PVE/FW68D
Quantity 1 1
Coating Black Coated Fin™ / Hydrophilic / Cooper Tube Black Coated Fin™ / Hydrophilic / Cooper Tube
Heat Exchange
Rows/Fins per inch (3 x 14) x 2 (3 x 14) x 2
Liquid Line (OD) in 3/8 3/8
Piping
Vapor Line (OD) in 3/4 7/8
Type R410A R410A
Refrigerant Charge lbs 13.2. 13.2
Control EEV EEV
Number of Indoor Units3 Minimum / Maximum 2/13 2/16

1. Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft. of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All
capacities are net with a Combination Ratio between 95–105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80°F dry bulb (DB) and 67°F wet bulb (WB) and outdoor ambient conditions of 95°F dry bulb (DB) and 75°F wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70°F dry bulb (DB) and 59°F wet bulb (WB) and outdoor ambient conditions of 47°F dry bulb (DB) and 43°F wet bulb (WB).
2. Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
3. The System Combination Ratio must be between 50–130%.
4. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5. Power wiring is field provided, solid or stranded, and must comply with all local and national codes. Refer to the engineering manual for detailed electrical data.
6. Cooling range with the Low Ambient Baffle Kit (sold separately) is -9.9°F to +122°F.
Due to our commitment to continued innovation, some specifications may be changed without notification.

26
WATER SOURCE
SOLUTIONS

MULTI V WATER® 5
Heat Pump & Heat Recovery
6 to 48 Tons
LG Multi V WATER® 5 systems permit synchronous cooling and heating in different zones at
the same time. Units are available from 6 Tons to 48 Tons.

AHRI Certified - Variable Refrigerant Flow (VRF) Multi-Split AC and HP


AHRI Standard 1230

27 LG Air Conditioning Technologies


MULTI V WATER® 5 (208-230V)
HEAT PUMP /
HEAT RECOVERY

MULTI V WATER® 5
ARWM***BAS5

Specifications Unit ARWM072BAS5 ARWM096BAS5 ARWM121BAS5 ARWM144BAS5


Frames ARWM072BAS5 ARWM096BAS5 ARWM121BAS5 ARWM144BAS5
Tons 6 8 10 12
Cooling Btu/h 72,000 96,000 119,700 144,000
Nominal Capacity
Heating Btu/h 81,000 108,000 135,000 162,000
Cooling Btu/h 69,000 92,000 114,000 138,000
Rated Capacity1
Heating Btu/h 77,000 103,000 129,000 152,000
Power Voltage V / Hz / Ø 208-230/60/3 208-230/60/3 208-230/60/3 208-230/60/3
Power/Communication Wiring No x AWG 2 x 18 2 x 18 2 x 18 2 x 18
Dimensions (W×H×D) Body in 30-13/32x44-3/32x21-17/32 30-13/32x44-3/32x21-17/32 30-13/32x44-3/32x21-17/32 30-13/32x44-3/32x21-17/32
Net lbs 322 322 322 322
Weight
Shipping lbs 340 340 340 340
Sound Pressure2 dB(A) 48 (62) 50 (62) 56 (62) 56 (62)
Cooling ˚F 50 ~ 113 50 ~ 113 50 ~ 113 50 ~ 113
Water Temperature Range Heating ˚F 23 ~ 113 23 ~ 113 23 ~ 113 23 ~ 113
Synchronous ˚F 23 ~ 113 23 ~ 113 23 ~ 113 23 ~ 113
Type High-Side Shell DC Scroll High-Side Shell DC Scroll High-Side Shell DC Scroll High-Side Shell DC Scroll
Compressor (Inverter Scroll) Oil Type PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D
Quantity 1 1 1 1
Type Stainless Steel Plate Stainless Steel Plate Stainless Steel Plate Stainless Steel Plate
Heat Exchanger Flow Rate Nominal GPM 20.3 25.4 30.4 35.5
Pressure Drop ft wg 3.47 5.20 7.23 9.63
Liquid Line in (OD) 3/8 3/8 1/2 1/2
High Pressure Vapor Line in (OD) 3/4 3/4 7/8 7/8
Low Pressure Vapor Line
Piping in (OD) 3/4 7/8 1-1/8 1-1/8
(Heat Recovery only)
Water Inlet / Outlet in (ID) 1-1/2 1-1/2 1-1/2 1-1/2
Condensate Pipe in (ID) 3/4 3/4 3/4 3/4
Type R410A R410A R410A R410A
Refrigerant Charge lbs 7.7 7.7 7.7 7.7
Control EEV EEV EEV EEV
Maximum Number of Indoor Units3 13 16 20 23

1. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.
2. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. Value is parenthesis is the maximum sound pressure at those conditions.
3. The System Combination Ratio must be between 50 and 130%.
Due to our commitment to continued innovation, some specifications may be changed without notification.

28
MULTI V WATER® 5 (208-230V)
HEAT PUMP /
HEAT RECOVERY

ARWM***BAS5

Specifications Unit ARWM168BAS5 ARWM192BAS5 ARWM216BAS5 ARWM240BAS5 ARWM264BAS5 ARWM288BAS5

ARWM072BAS5 ARWM096BAS5 ARWM096BAS5 ARWM121BAS5 ARWM121BAS5 ARWM144BAS5


Frames
ARWM096BAS5 ARWM096BAS5 ARWM121BAS5 ARWM121BAS5 ARWM144BAS5 ARWM144BAS5

Tons 14 16 18 20 22 24
Cooling Btu/h 168,000 192,000 216,000 239,400 264,000 287,700
Nominal Capacity
Heating Btu/h 189,000 216,000 243,000 269,000 297,000 324,000
Cooling Btu/h 160,000 184,000 206,000 228,000 252,000 274,000
Rated Capacity1
Heating Btu/h 180,000 206,000 230,000 256,000 282,000 308,000
Power Voltage V / Hz / Ø 208-230/60/3 208-230/60/3 208-230/60/3 208-230/60/3 208-230/60/3 208-230/60/3
Power/Communication Wiring No x AWG 2 x 18 2 x 18 2 x 18 2 x 18 2 x 18 2 x 18
64-3/16 x 64-3/16 x 64-3/16 x 64-3/16 x 64-3/16 x 64-3/16 x
Dimensions (W×H×D) Body in
44-3/32 x 21-17/32 44-3/32 x 21-17/32 44-3/32 x 21-17/32 44-3/32 x 21-17/32 44-3/32 x 21-17/32 44-3/32 x 21-17/32
Net lbs 322 x 2 322 x 2 322 x 2 322 x 2 322 x 2 322 x 2
Weight
Shipping lbs 340 x 2 340 x 2 340 x 2 340 x 2 340 x 2 340 x 2
Sound Pressure2 dB(A) 52 (65) 53 (65) 57 (65) 59 (65) 59 (65) 59 (65)
Cooling ˚F 50 ~ 113 50 ~ 113 50 ~ 113 50 ~ 113 50 ~ 113 50 ~ 113
Water Temperature Range Heating ˚F 23 ~ 113 23 ~ 113 23 ~ 113 23 ~ 113 23 ~ 113 23 ~ 113
Synchronous ˚F 23 ~ 113 23 ~ 113 23 ~ 113 23 ~ 113 23 ~ 113 23 ~ 113
High-Side Shell High-Side Shell High-Side Shell High-Side Shell High-Side Shell High-Side Shell
Type
DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll
Compressor (Inverter Scroll) Oil Type PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D
Quantity 2 2 2 2 2 2
Type Stainless Steel Plate Stainless Steel Plate Stainless Steel Plate Stainless Steel Plate Stainless Steel Plate Stainless Steel Plate
Heat Exchanger Flow Rate Nominal GPM 20.3 + 25.4 25.4 + 25.4 25.4 + 30.4 30.4 + 30.4 30.4 + 35.5 35.5 + 35.5
Pressure Drop ft wg 3.47 / 5.20 5.20 / 5.20 5.20 / 7.23 7.23 / 7.23 7.23 / 9.63 9.63 / 9.63
Liquid Line in (OD) 3/8 + 3/8 3/8 + 3/8 3/8 + 1/2 1/2 + 1/2 1/2 + 1/2 1/2 + 1/2
High Pressure Vapor Line in (OD) 3/4 + 3/4 3/4 + 3/4 3/4 + 7/8 7/8 + 7/8 7/8 + 7/8 7/8 + 7/8
Low Pressure Vapor Line
Piping in (OD) 3/4 + 7/8 7/8 + 7/8 7/8 + 1-1/8 1-1/8 + 1-1/8 1-1/8 + 1-1/8 1-1/8 + 1-1/8
(Heat Recovery only)
Water Inlet / Outlet in (ID) 1-1/2 + 1-1/2 1-1/2 + 1-1/2 1-1/2 + 1-1/2 1-1/2 + 1-1/2 1-1/2 + 1-1/2 1-1/2 + 1-1/2
Condensate Pipe in (ID) 3/4 + 3/4 3/4 + 3/4 3/4 + 3/4 3/4 + 3/4 3/4 + 3/4 3/4 + 3/4
Type R410A R410A R410A R410A R410A R410A
Refrigerant Charge lbs 7.7 + 7.7 7.7 + 7.7 7.7 + 7.7 7.7 + 7.7 7.7 + 7.7 7.7 + 7.7
Control EEV EEV EEV EEV EEV EEV
Maximum Number of Indoor Units3 29 32 35 39 42 45

1. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.
2. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. Value is parenthesis is the maximum sound pressure at those conditions.
3. The System Combination Ratio must be between 50 and 130%.
Due to our commitment to continued innovation, some specifications may be changed without notification.

29 LG Air Conditioning Technologies


MULTI V WATER® 5 HEAT PUMP (208-230V)
HEAT PUMP /
HEAT RECOVERY

MULTI V WATER® 5
ARWM***BAS5

Specifications Unit ARWM360BAS5 ARWM432BAS5


ARWM121BAS5 ARWM144BAS5
Frames ARWM121BAS5 ARWM144BAS5
ARWM121BAS5 ARWM144BAS5
Tons 30 36
Cooling Btu/h 360,000 430,500
Nominal Capacity
Heating Btu/h 405,000 486,000
Cooling Btu/h 344,000 410,000
Rated Capacity1
Heating Btu/h 384,000 460,000
Power Voltage V / Hz / Ø 208-230/60/3 208-230/60/3
Power/Communication Wiring No x AWG 2 x 18 2 x 18

Dimensions (W×H×D) Body in 99-7/32 x 44-3/32 x 21-17/32 99-7/32 x 44-3/32 x 21-17/32

Net lbs 322 x 3 322 x 3


Weight
Shipping lbs 340 x 3 340 x 3
Sound Pressure2 dB(A) 61 (67) 61 (67)
Cooling ˚F 50 ~ 113 50 ~ 113
Water Temperature Range Heating ˚F 23 ~ 113 23 ~ 113
Synchronous ˚F 23 ~ 113 23 ~ 113
High-Side Shell High-Side Shell
Type
DC Scroll DC Scroll
Compressor (Inverter Scroll) Oil Type PVE/FVC68D PVE/FVC68D
Quantity 3 3
Type Stainless Steel Plate Stainless Steel Plate
Heat Exchanger Flow Rate Nominal GPM 30.4 + 30.4 + 30.4 35.5 + 35.5 + 35.5
Pressure Drop ft wg 7.23 + 7.23 + 7.23 9.63 + 9.63 + 9.63
Liquid Line in (OD) 1/2 + 1/2 + 1/2 1/2 + 1/2 + 1/2
High Pressure Vapor Line in (OD) 7/8 +7/8 +7/8 7/8 +7/8 +7/8
Low Pressure Vapor Line
Piping in (OD) 1-1/8 + 1-1/8 + 1-1/8 1-1/8 +1-1/8 + 1-1/8
(Heat Recovery only)
Water Inlet / Outlet in (ID) 1-1/2 + 1-1/2 +1-1/2 1-1/2 + 1-1/2 +1-1/2
Condensate Pipe in (ID) 3/4 + 3/4 + 3/4 3/4 + 3/4 + 3/4
Type R410A R410A
Refrigerant Charge lbs 7.7 + 7.7 + 7.7 7.7 + 7.7 + 7.7
Control EEV EEV
Maximum Number of Indoor Units3 58 64

1. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.
2. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. Value is parenthesis is the maximum sound pressure at those conditions.
3. The System Combination Ratio must be between 50 and 130%.
Due to our commitment to continued innovation, some specifications may be changed without notification.

30
MULTI V WATER® 5 (460V)
HEAT PUMP /
HEAT RECOVERY

ARWM***DAS5

Specifications Unit ARWM072DAS5 ARWM096DAS5 ARWM121DAS5 ARWM144DAS5 ARWM168DAS5 ARWM192DAS5

Frames ARWM072DAS5 ARWM096DAS5 ARWM121DAS5 ARWM144DAS5 ARWM168DAS5 ARWM192DAS5

Tons 6 8 10 12 14 16
Cooling Btu/h 72,000 96,000 119,700 144,000 168,000 192,000
Nominal Capacity
Heating Btu/h 81,000 108,000 135,000 162,000 189,000 216,000
Cooling Btu/h 69,000 92,000 114,000 138,000 160,000 184,000
Rated Capacity 1

Heating Btu/h 77,000 103,000 129,000 152,000 180,000 206,000


Power Voltage V / Hz / Ø 460/60/3 460/60/3 460/60/3 460/60/3 460/60/3 460/60/3
Power/Communication Wiring No x AWG 2 x 18 2 x 18 2 x 18 2 x 18 2 x 18 2 x 18
30-13/32x 30-13/32x 30-13/32x 30-13/32x 30-13/32x 30-13/32x
Dimensions (W×H×D) Body in
44-3/32x21-17/32 44-3/32x21-17/32 44-3/32x21-17/32 44-3/32x21-17/32 44-3/32x21-17/32 44-3/32x21-17/32
Net lbs 322 322 322 322 328 328
Weight
Shipping lbs 340 340 340 340 370 370
Sound Pressure2 dB(A) 48 (62) 50 (62) 56 (62) 56 (62) 58 (62) 60 (62)
Cooling ˚F 50 – 113 50 – 113 50 – 113 50 – 113 50 – 113 50 – 113
Water Temperature Range Heating ˚F 23 ~ 113 23 ~ 113 23 ~ 113 23 ~ 113 23 ~ 113 23 ~ 113
Synchronous ˚F 23 ~ 113 23 ~ 113 23 ~ 113 23 ~ 113 23 ~ 113 23 ~ 113
High-Side Shell High-Side Shell High-Side Shell High-Side Shell High-Side Shell High-Side Shell
Type
DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll
Compressor (Inverter Scroll) Oil Type PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D
Quantity 1 1 1 1 1 1
Type Stainless Steel Plate Stainless Steel Plate Stainless Steel Plate Stainless Steel Plate Stainless Steel Plate Stainless Steel Plate
Heat Exchanger Flow Rate Nominal GPM 20.3 25.4 30.4 35.5 45.7 50.7
Pressure Drop ft wg 3.47 5.20 7.23 9.63 8.32 10.08
Liquid Line in (OD) 3/8 3/8 1/2 1/2 5/8 5/8
High Pressure Vapor Line in (OD) 3/4 3/4 7/8 7/8 7/8 7/8
Low Pressure Vapor Line
Piping in (OD) 3/4 7/8 1-1/8 1-1/8 1-1/8 1-1/8
(Heat Recovery only)
Water Inlet / Outlet in (ID) 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2
Condensate Pipe in (ID) 3/4 3/4 3/4 3/4 3/4 3/4
Type R410A R410A R410A R410A R410A R410A
Refrigerant Charge lbs 7.7 7.7 7.7 7.7 9.9 9.9
Control EEV EEV EEV EEV EEV EEV
Maximum Number of Indoor Units3 13 16 20 23 29 32

1. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.
2. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. Value is parenthesis is the maximum sound pressure at those conditions.
3. The System Combination Ratio must be between 50 and 130%.
Due to our commitment to continued innovation, some specifications may be changed without notification.

31 LG Air Conditioning Technologies


MULTI V WATER® 5 (460V)
HEAT PUMP /
HEAT RECOVERY

MULTI V WATER® 5
ARWM***DAS5

Specifications Unit ARWM191DAS5 ARWM216DAS5 ARWM240DAS5 ARWM264DAS5 ARWM288DAS5 ARWM360DAS5


ARWM096DAS5 ARWM096DAS5 ARWM121DAS5 ARWM121DAS5 ARWM144DAS5 ARWM168DAS5
Frames
ARWM096DAS5 ARWM121DAS5 ARWM121DAS5 ARWM144DAS5 ARWM144DAS5 ARWM192DAS5

Tons 16 18 20 22 24 30
Cooling Btu/h 192,000 216,000 239,400 264,000 287,700 360,000
Nominal Capacity
Heating Btu/h 216,000 243,000 269,000 297,000 324,000 405,000
Cooling Btu/h 184,000 206,000 228,000 252,000 274,000 344,000
Rated Capacity 1

Heating Btu/h 206,000 230,000 256,000 282,000 308,000 384,000


Power Voltage V / Hz / Ø 460/60/3 460/60/3 460/60/3 460/60/3 460/60/3 460/60/3
Power/Communication Wiring No x AWG 2 x 18 2 x 18 2 x 18 2 x 18 2 x 18 2 x 18
64-3/16 x 64-3/16 x 64-3/16 x 64-3/16 x 64-3/16 x 64-3/16 x
Dimensions (W×H×D) Body in
44-3/32 x 21-17/32 44-3/32 x 21-17/32 44-3/32 x 21-17/32 44-3/32 x 21-17/32 44-3/32 x 21-17/32 44-3/32 x 21-17/32
Net lbs 322 x 2 322 x 2 322 x 2 322 x 2 322 x 2 348 x 2
Weight
Shipping lbs 340 x 2 340 x 2 340 x 2 340 x 2 340 x 2 370 x 2
Sound Pressure2 dB(A) 53 (65) 57 (65) 59 (65) 59 (65) 59 (65) 62 (65)
Cooling ˚F 50 – 113 50 – 113 50 – 113 50 – 113 50 – 113 50 – 113
Water Temperature Range Heating ˚F 23 ~ 113 23 ~ 113 23 ~ 113 23 ~ 113 23 ~ 113 23 ~ 113
Synchronous 23 ~ 113 23 ~ 113 23 ~ 113 23 ~ 113 23 ~ 113 23 ~ 113
High-Side Shell High-Side Shell High-Side Shell High-Side Shell High-Side Shell High-Side Shell
Type
DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll DC Scroll
Compressor (Inverter Scroll) Oil Type PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D PVE/FVC68D
Quantity 2 2 2 2 2 2
Type Stainless Steel Plate Stainless Steel Plate Stainless Steel Plate Stainless Steel Plate Stainless Steel Plate Stainless Steel Plate
Heat Exchanger Flow Rate Nominal GPM 25.4 + 25.4 25.4 + 30.4 30.4 + 30.4 30.4 + 35.5 35.5 + 35.5 45.7 + 50.7
Pressure Drop ft wg 5.2 + 5.2 5.2 + 7.23 7.23 + 7.23 7.23 + 9.63 9.63 + 9.63 8.32 + 10.08
Liquid Line in (OD) 3/8 + 3/8 3/8 + 1/2 1/2 + 1/2 1/2 + 1/2 1/2 + 1/2 5/8 + 5/8
High Pressure Vapor Line in (OD) 3/4 + 3/4 3/4 + 3/4 7/8 + 7/8 7/8 + 7/8 7/8 + 7/8 7/8 + 7/8
Low Pressure Vapor Line
Piping in (OD) 7/8 + 7/8 7/8 + 1-1/8 1-1/8 + 1-1/8 1-1/8 + 1-1/8 1-1/8 + 1-1/8 1-1/8 + 1-1/8
(Heat Recovery only)
Water Inlet / Outlet in (ID) 1-1/2 +1-1/2 1-1/2 +1-1/2 1-1/2 +1-1/2 1-1/2 +1-1/2 1-1/2 +1-1/2 1-1/2 +1-1/2
Condensate Pipe in (ID) 3/4 + 3/4 3/4 + 3/4 3/4 + 3/4 3/4 + 3/4 3/4 + 3/4 3/4 + 3/4
Type R410A R410A R410A R410A R410A R410A
Refrigerant Charge lbs 7.7 + 7.7 7.7 + 7.7 7.7 + 7.7 7.7 + 7.7 7.7 + 7.7 9.9 + 9.9
Control EEV EEV EEV EEV EEV EEV
Maximum Number of Indoor Units3 32 35 39 42 45 58

1. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.
2. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. Value is parenthesis is the maximum sound pressure at those conditions.
3. The System Combination Ratio must be between 50 and 130%.
Due to our commitment to continued innovation, some specifications may be changed without notification.

32
MULTI V WATER® 5 (460V)
HEAT PUMP /
HEAT RECOVERY

ARWM***DAS5

Specifications Unit ARWM432DAS5 ARWM504DAS5 ARWM576DAS5


ARWM144BAS5 ARWM144DAS5 ARWM192DAS5
Frames ARWM144BAS5 ARWM168DAS5 ARWM192DAS5
ARWM144BAS5 ARWM192DAS5 ARWM192DAS5
Tons 36 42 48
Cooling Btu/h 430,500 504,000 571,200
Nominal Capacity
Heating Btu/h 486,000 567,000 648,000
Cooling Btu/h 410,000 480,000 545,000
Rated Capacity1
Heating Btu/h 460,000 534,000 610,000
Power Voltage V / Hz / ø 460/60/3 460/60/3 460/60/3
Power/Communication Wiring No x AWG 2 x 18 2 x 18 2 x 18
Dimensions (W×H×D) Body in 99-7/32x44-3/32x21-17/32 99-7/32x44-3/32x21-17/32 99-7/32x44-3/32x21-17/32
Net lbs 322 x 3 322 + 348 x 2 348 x 3
Weight
Shipping lbs 340 x 3 340+ 370 x 2 370 x 3
Sound Pressure2 dB(A) 61 (67) 63 (67) 65 (67)
Cooling ˚F 50 - 113 50 - 113 50 - 113
Water Temperature Range Heating ˚F 23 ~ 113 23 ~ 113 23 ~ 113
Synchronous ˚F 23 ~ 113 23 ~ 113 23 ~ 113
Type High-Side Shell DC Scroll High-Side Shell DC Scroll High-Side Shell DC Scroll
Compressor (Inverter Scroll) Oil Type PVE/FVC68D PVE/FVC68D PVE/FVC68D
Quantity 3 3 3
Type Stainless Steel Plate Stainless Steel Plate Stainless Steel Plate
Heat Exchanger Flow Rate Nominal GPM 35.5 + 35.5 + 35.5 35.5 + 45.7 + 50.7 50.7 + 50.7 + 50.7
Pressure Drop ft wg 9.63 + 9.63 + 9.63 9.63 + 8.32 + 10.08 10.08 + 10.08 + 10.08
Liquid Line in (OD) 1/2 + 1/2 + 1/2 1/2 + 5/8 + 5/8 5/8 + 5/8 + 5/8
High Pressure Vapor Line in (OD) 7/8 +7/8 + 7/8 7/8 +7/8 + 7/8 7/8 +7/8 + 7/8
Low Pressure Vapor Line
Piping in (OD) 1-1/8 + 1-1/8 + 1-1/8 1-1/8 + 1-1/8 + 1-1/8 1-1/8 + 1-1/8 + 1-1/8
(Heat Recovery only)
Water Inlet / Outlet in (ID) 1-1/2 + 1-1/2 +1-1/2 1-1/2 + 1-1/2 +1-1/2 1-1/2 + 1-1/2 +1-1/2
Condensate Pipe in (ID) 3/4 + 3/4 + 3/4 3/4 + 3/4 + 3/4 3/4 + 3/4 + 3/4
Type R410A R410A R410A
Refrigerant Charge lbs 7.7 + 7.7 + 7.7 7.7 + 9.9 + 9.9 9.9 + 9.9 + 9.9
Control EEV EEV EEV
Maximum Number of Indoor Units3 64 64 64

1. Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.
2. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. Value is parenthesis is the maximum sound pressure at those conditions.
3. The System Combination Ratio must be between 50 and 130%.
Due to our commitment to continued innovation, some specifications may be changed without notification.

33 LG Air Conditioning Technologies


AIR
TECHNOLOGIES
ENERGY RECOVERY VENTILATOR (ERV)
35

OUTSIDE AIR UNIT (OAU)


36

AIR HANDLING UNIT (AHU) MODULES


37

ROOFTOP DOAS (DEDICATED OUTDOOR AIR SYSTEM)


39

SPLIT COMPACT DOAS (DEDICATED OUTDOOR AIR SYSTEM)


40

34
ERV (ENERGY RECOVERY VENTILATOR)

ARVU*****A2

The LG ERV system allows users to exchange indoor air with outdoor air in order to improve the air quality by reducing the
temperature and humidity of incoming fresh air. Easy to maintain while providing superior energy savings and performance,
LG ERV is an ideal solution for hotels, dormitories, restaurants, hospitals, retail establishments, theaters, schools and office
buildings.
Specifications Unit 053ZE 063ZE 093ZF 123ZF
Capacity CFM 470 590 880 1,180
Performance
Power Input (SH1) Watts 360 470 720 930
Operation Range °F DB 14 ~113 14 ~113 14 ~113 14 ~113
Air-to-Air Heat Exchanger Cross-Flow Fixed Core Cross-Flow Fixed Core Cross-Flow Fixed Core Cross-Flow Fixed Core
Heat Exchanger Data
Quantity 1 1 1 1
Temperature Cooling (Fan Speed SH) % 62 59 62 59
Exchanger
Efficiency Entering Water Temp Range °F 41~113 53-167

Enthalpy Exchange Cooling (Fan Speed SH) % 37 34 37 34


Efficiency Heating (Fan Speed SH) % 52 49 52 49
Sound Pressure dB(A) 40/37/31 41/39/33 44/41/35 45/41/35
Net Unit Weight lbs 148 148 331 331
Unit Data
Shipping Weight lbs 177 177 397 397
Dimensions (W×H×D) in 44-7/8 x 41-13/16 x 14-3/8 44-7/8 x 41-13/16 x 14-3/8 44-7/8 x 41-13/16 x 29-1/16 44-7/8 x 41-13/16 x 29-1/16
Rated Amps A 2.8 3.44 5.62 6.82
Power Supply V / Hz / Ø 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/1
Electrical Data
Power Input (Cooling) Watts 360/270/165 470/385/210 720/540/340 930/770/420
Power Input (Heating) Watts 360/270/165 470/385/210 720/540/340 930/770/420
Type Cross Flow Cross Flow Cross Flow Cross Flow
Quantity 2 2 2 2

Fan Motor/Drive BLDC BLDC BLDC BLDC


Airflow Rate (SH/H/L) CFM 471/471/388 589/589/471 883/883/706 1177/1177/942
External Static Pressure
in wg 0.80/0.44/0.24 0.64/0.36/0.20 0.80/0.44/0.24 0.64/0.36/0.20
(SH/H/L)
Quantity 2 2 4 4
Filters
Size in 41-9/16” x 8-3/8” x 13/32” 41-9/16” x 8-3/8” x 13/32” 41-9/16” x 8-3/8” x 13/32” 41-9/16” x 8-3/8” x 13/32”

Accessories
Description Model
PI-485 PFNFP14A0

1. SH - Super-high condensate drain not required. ERV temperature and enthalpy exchange efficiencies are in
accordance with AHRI 1060 test conditions, 100% airflow, and 0” external static pressure. AHRI Certified - Air-to-Air ERV
Cooling: Outdoor 95°F DB, 78°F WB; Exhaust 75°F DB, 63°F WB AHRI Standard 1060
Heating: Outdoor 35°F DB, 33°F WB; Exhaust 70°F DB, 58°F WB Energy Recovery COMPONENT is certified. Actual performance is
Due to our commitment to continued innovation, some specifications may be changed without notification. in packaged equinment may vary.
.

35 LG Air Conditioning Technologies


OAU (OUTSIDE AIR UNIT)

ARNU483B8Z4
ARNU763B8Z4
ARNU963B8Z4

Specifications Unit ARNU483B8Z4 ARNU763B8Z4 ARNU963B8Z4


Capacity Btu/h 48,100 76,400 95,900
Cooling Mode Performance
Power Input1 W 180 230 360

Heating Mode Capacity Btu/h 46,115 73,080 91,360


Performance Power Input1 W 180 230 360
Cooling Max °F WB 90 90 90
Entering Air

TECHNOLOGIES
Heating Min °F DB 23 23 23
Refrigerant Type2 R410A R410A R410A

AIR
Refrigerant Control EEV EEV EEV
Sound Power3 dB(A) 54 56 57
Unit Data Dimensions (W×H×D) in 61-1/2 x 18-1/8 x 27-1/8 61-1/2 x 18-1/8 x 27-1/8 61-1/2 x 18-1/8 x 27-1/8
Net Unit Weight lbs 161 161 161
Shipping Weight lbs 191 191 191
Communication Cable4 No. x AWG 2 x 18 2 x 18 2 x 18
Type Sirocco Sirocco Sirocco
Motor 1 1 1
Fan Motor/Drive Brushless Digitally Controlled / Direct Brushless Digitally Controlled / Direct Brushless Digitally Controlled / Direct
Airflow Rate (H/M/L) CFM 708/477/477 837 / 446 / 446 1,261 / 837 / 837
External Static Pressure in wg 0.7 0.87 0.87
Liquid Line (OD) in 3/8 Flare 3/8 Flare 3/8 Flare
Piping (Main Coil)
Vapor Line (OD) in 5/8 Brazed 3/4 Brazed 7/8 Brazed
Condensate Condensate Line (OD) in 1 1 1
MCA A 2.7 2.7 2.7
Electrical Data MOP A 15 15 15
Power Supply V / Hz / Ø 208-230/60/1 208-230/60/1 208-230/60/1

Accessories
Model
Description Model
High-Capacity Filter Box for B8 HSD Chassis ZFBXB801A

1. The power input is rated at high speed.


2. Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
4. All communication cables to be minimum 18 AWG, four-conductor, stranded, and shielded, and must comply with applicable local and national codes.
Due to our commitment to continued innovation, some specifications may be changed without notification.

36
AIR HANDLING UNIT (AHU) CONVERSION KIT
Solution to extend LG VRF technology to third-party Air Handling Units.

Communication Kit
PAHCMR000 PAHCMS000

Specifications
Combination Dimensions (in)
Type Model Name Description
Outdoor Expan- Central
EEV Kit controller W H D Weight
unit sion Kit

MULTI V™, Return/room air by remote controller or dry


PAHCMR000 11-13/16 11-13/16 6-1/8 13.7 lb
Single Split contact control
Communication Kit
MULTI V™, Discharge air or supply air (capacity) control
PAHCMS000 14-3/4 11-13/16 6-1/8 16.4 lb
Single Split by DDC

NOTE: Available functions/features may differ based on the connected system. Due to our commitment to continued innovation, some specifications may be changed without notification.

Function list for Communication Kit


Specification
List Description PAHCMR000 PAHCMS000
Min Type Min Max
Digital input**
Outdoor Unit Operation On/Off By wired controller* - -
(Non-voltage)

Digital input
Mode Cooling/Heating only - -
(Non-voltage)
Controlling

Digital input
Fan Step High/mid/low (three steps) Applied Not Applied
(Non-voltage)

Room Temperature Control Cooling 64 ~ 86oF, Heating 60 ~ 86oF By wired controller* Analog input 0V 10 V

Supply Air Temperature Compressor Off, Compressor Off & Fan Off,
- Analog input 0V 10 V
(by outdoor capacity control) 40 ~ 100% capacity control

Outdoor Unit Operation Digital input**


On/Off - Max : AC 250 V, DC 30 V, 1A
(Non-voltage)

AHU Communication Kit Digital input


On/Off - Max : AC 250 V, DC 30 V, 1A
Operation (Non-voltage)
Monitoring

Outdoor Mode Digital input


Fan/defrost/cooling/heating - Max : AC 250 V, DC 30 V, 1A
(Non-voltage)

Fan Mode Digital input


High/mid/low (three steps) Max : AC 250 V, DC 30 V, 1A
(Non-voltage)

Error Status Digital input


No error/error occurred Max : AC 250 V, DC 30 V, 1A
(Non-voltage)

* Optional accessory, recommended model : PREMTB10U


** Binary input and output (Open and short), DO is normal open

CSA Group® is a registered trademark of Canadian Standards Association

37 LG Air Conditioning Technologies


EEV Kit
PRLK048A0
PRLK096A0
PRLK396A0
PRLK594A0

Specifications
Dimensions (in)
Type Model Name Capacity Range
W H D

TECHNOLOGIES
PRLK048A0 8 Tons maximum 8-5/8 15-15/16 3-5/16

AIR
PRLK096A0 16 Tons maximum 8-5/8 15-15/16 3-5/16
EEV Kit
PRLK396A0 32 Tons maximum 8-1/2 13-1/2 7-1/8

PRLK594A0* 48 Tons maximum 11 13-1/2 7-1/8

Can be used in combination with or without indoor units. Several EEV kits can be connected to a single outdoor unit.
* In order for the PRLK594A0 to work with the PAHCMS000 the EV Control Module is required - PAEEVA020. This module will come in the box with the PRLK594A0.

System Architecture
MULTI V™ Application (in Combination with third-party AHU)
Field Supplied
Controller Comm. kit
Refrigerant Piping *DDC

Communication Wire
Sensor Signal
*DDC : Digital Direct Controller Return Air Exhaust Air Outdoor Air Supply Air

EEV kit

ODU

IDU
CTRL

CSA Group® is a registered trademark of Canadian Standards Association

38
ROOFTOP DOAS

AR-DC**-**A
Tested to UL1995 AR-DE**-**A
AR-DR**-**A
The LG Rooftop DOAS product line ranges from 3 to 70 Tons in cooling capacity and up to 18,000 CFM of airflow capacity.
Rooftop DOAS units are highly configurable to meet any local design requirement such as heating options including indirect gas
furnace with modulating gas controls, SCR controlled electric, or hot water coil options. Available with inverter scroll or digital
scroll compressors, split systems, bottom or side discharge.
Cabinet Chassis Size 02 123 223 32 35
AR-DR02-03A AR-DC12-05A AR-DC22-15A AR-DC22-15A AR-DC35-30A
AR-DR02-04A AR-DC12-07A AR-DC22-17A AR-DC22-17A AR-DC35-40A
AR-DR02-05A AR-DC12-10A AR-DC22-20A AR-DC22-20A AR-DC35-50A
AR-DR02-06A AR-DC12-12A AR-DC22-25A AR-DC22-25A AR-DC35-60A
AR-DR02-07A AR-DC12-15A AR-DC22-30A AR-DC22-30A AR-DC35-70A
AR-DE12-05A AR-DE22-15A AR-DE32-25A AR-DE35-30A
AR-DE12-07A AR-DE22-17A AR-DE32-30A AR-DE35-40A
Model Numbers1,2 AR-DE12-10A AR-DE22-20A AR-DE32-40A AR-DE35-50A
AR-DE12-12A AR-DE22-25A AR-DE32-50A AR-DE35-60A
AR-DE12-15A AR-DE22-30A AR-DR32-25A AR-DE35-70A
AR-DR12-05A AR-DR22-15A AR-DR32-30A AR-DR35-30A
AR-DR12-07A AR-DR22-17A AR-DR32-40A AR-DR35-40A
AR-DR12-10A AR-DR22-20A AR-DR32-50A AR-DR35-50A
AR-DR12-12A AR-DR22-25A AR-DR35-60A
AR-DR12-15A AR-DR22-30A AR-DR35-70A

Nominal Tons 3, 4, 5, 6, 7 5, 7.5, 10, 12.5, 15 15, 17.5, 20, 25, 30 25, 30, 40, 50 30, 40, 50, 60, 70

Minimum (CFM) 500 800 2,250 3,750 3,900


Airflow
Maximum (CFM) 2,500 5,750 9,550 16,000 18,000

Inverter Scroll Standard Standard Standard Standard Standard

Cooling Components Digital Scroll Not Available Not Available Not Available Not Available Not Available

Modulating Hot Gas Reheat Optional Optional Optional Optional Optional

Minimum (MBH) 75 100 300 600 600

Indirect Gas Furnace Maximum (MBH) 200 300 500 1,200 1,200

Turndown up to 16:1 up to 16:1 up to 16:1 up to 16:1 up to 10:1

Minimum (KW) 4 15 35 35 50

Electric Heat Maximum (KW) 60 60 120 230 200

SCR Modulation Standard Standard Standard Standard Standard

Hot Water Heat Not Available Optional Optional Optional Optional

Accessories
LG Rooftop DOAS units are highly customizable with many accessories available to meet your application needs. To design an LG
Rooftop DOAS unit and determine which accessory models are appropriate, use the LG CAPS (Computer-Aided Product
Selection) software available through myLGHVAC.com.

1. AR-DR unit types include cooling and heating. AR-DE unit types include cooling, heating, and an ERV wheel.
2. Voltages are selectable between 208, 230, or 460 volts (all 3ø).
3. Air-Source Heat Pump option is available for the 12 and 22 DOAS cabinet chassis size, up to 30 Tons, with inverter compressors as standard.

39 LG Air Conditioning Technologies


SPLIT COMPACT DOAS

ARND093DCR4

LG Split Compact Dedicated Outdoor Air System (DOAS) units provide 100% outdoor air in heating, cooling, and
dehumidification modes. Working with LG VRF systems, the LG Split Compact DOAS unit optimizes energy savings and
performance.

Specifications Unit ARND093DCR4 ARND153DCR4 ARND203DCR44


Cooling Mode Performance Capacity Btu/h 70,000 120,000 143,100

TECHNOLOGIES
Moisture Removal Capacity lb/h 33.0 55.0 67

AIR
Heating Mode Performance Capacity Btu/h 40,000 51,000 59,900
Cooling Max °F DB/WB 122/78 122 / 78 122 / 78
Entering Air
Heating Min °F DB 14 (10)144 14
Refrigerant Type1 R410A R410A R410A
Refrigerant Control EEV EEV EEV
Sound Power2 dB(A) 60 75 72
Unit Data Dimensions (W×H×D) in 75 x 21-11/16 x 45 75 x 21-11/16 x 45 75 x 21-11/16 x 45
Net Unit Weight lbs 342 397 397
Shipping Weight lbs 381 437 437
Communication Cable3 No. x AWG 4 x 18 4 x 18 4 x 18
Type Sirrocco 3D Plug 3D Plug
Motor (HP/W) 0.33 / 250 1 / 750 1 / 750
Fan Motor/Drive ECM / Direct ECM / Direct ECM / Direct
Airflow Rate5 CFM 500 - 900 1,000 - 1,500 1,000 - 2,000
External Static Pressure in wg 1.0 2.0 1.5
Liquid Line (OD) in 3/8 Brazed 1/2 Brazed 1/2 Brazed
Piping High Pressure Vapor (OD) in 5/8 Brazed 7/8 Brazed 3/4 Brazed
Low Pressure Vapor (OD) in 3/4 Brazed 1-1/8 Brazed 1-1/8 Brazed
Condensate Condensate Line (OD) in 1 1 1
MCA A 2.5 7.5 7.3
Electrical Data MOP A 15 15 15
Power Supply V / Hz / Ø 208-230/60/1 208-230/60/1 208-230/60/1

Filter Outdoor 2" Merv 8 (25"x20") 2” Merv 8 (25” x 20”) 2” Merv 8 (25” x 20”)

Accessories
LG DOAS units are highly customizable with many accessories available to meet your application needs. To design an LG DOAS
unit and determine which accessory models are appropriate, use the LG CAPS (Computer-Aided Product Selection) software
available through myLGHVAC.com.
1. Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
2. Sound power levels are tested under AHRI 260 Standard.
3. All communication cable to be minimum 18 AWG, 4-conductor, twisted, stranded, shielded and must comply with applicable local and national codes. Ensure the communication cable is properly grounded at
the outdoor unit only. Do not ground the communication cable from the outdoor unit to the DOAS unit at any other point.
4. A maximum of (2) DOAS units connected to (1) ODU. A minimum 12 Ton ODU for (1) DOAS unit connection and minimum 30 Ton ODU for (2) DOAS unit connection.
5. Both ARND153DCR4 and ARND203DCR4 can be utilized for applications requiring CFM as low as 900CFM. A minimum 6-Ton unit or 8-Ton LG MV 5 HR unit is required based on the application
CSA Group® is a registered trademark of Canadian Standards Association

40
HEAT RECOVERY UNIT

PRHR023A
PRHR033A
PRHR043A
PRHR023A PRHR033A PRHR043A
PRHR063A (2-branch Unit) (3-branch Unit) (4-branch Unit)
PRHR083A

PRHR063A PRHR083A
Features (6-branch Unit) (8-branch Unit)

• Max. 64 indoor units can be connected (Max. eight indoor units per branch)
• Easy installation with auto pipe detect
• Delivers maximum efficiency using the subcooling cycle within the HR Unit

Models Applied
• MULTI V™ 5 Heat Recovery
• MULTI V WATER® 5 Heat Recovery
• Multi V S® Heat Recovery

Specifications
Specification Unit PRHR023A PRHR033A PRHR043A PRHR063A PRHR083A
Number of Indoor Unit Ports2 2 3 4 6 8
Power Input (Cooling / Heating) Watts 39.8 / 37.2 39.8 / 37.2 39.8 / 37.2 75.9 / 72.1 75.9 / 72.1
Each Port Btu/h 60,000 60,000 60,000 60,000 60,000
Max Port Capacity
Sum of Ports Btu/h 120,000 180,000 230,000 230,000 230,000
Power Supply V/Hz/Ø 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/1
Electrical
Rated Amps A 0.06 0.06 0.06 0.09 0.09
Port Liquid Line in 3/8 3/8 3/8 3/8 3/8
Port Vapor Line in 5/8 5/8 5/8 5/8 5/8
Piping System Liquid Line in 3/8 1/2 5/8 5/8 5/8
System Vapor Line High in 3/4 7/8 7/8 7/8 7/8
System Vapor Line Low in 7/8 1 1/8 1 1/8 1 1/8 1 1/8
Cooling Mode dB(A) 31 31 31 31 31
Sound Pressure Data Heating Mode dB(A) 31 31 31 31 31
Simultaneous dB(A) 38 38 38 38 38
Net Unit Weight lbs 33 37 40 60 68
Weight
Shipping Weight lbs 46 50 53 75 82
30-15/16 x 25-7/8 x 30-15/16 x 25-7/8 x 30-15/16 x 25-7/8 x 43-13/16 x 25-7/8 x 43-13/16 x 25-7/8 x
Dimensions W×D×H in
8-9/16 8-9/16 8-9/16 8-9/16 8-9/16

1. All refrigerant pipes require insulation.


2. Each port can allow up to eight indoor units with a maximum capacity of 60k Btu/h per port.
3. All communication cable to be minimum 18 AWG, 2-conductor, twisted, stranded, shielded and must comply with applicable local and national code.
4. Kit components must be kept dry and free of debris before installation.
5. Must follow installation instructions in the applicable LG installation manual.
6. Power wiring cable size must comply with the applicable local and national code.
7. This unit comes with a dry nitrogen charge.
CSA Group® is a registered trademark of Canadian Standards Association
Due to our commitment to continued innovation, some specifications may be changed without notification.

41 LG Air Conditioning Technologies


ACCESSORIES
Outdoor Accessories

Air Guide Air Guide Hail Guard Low Ambient Baffle Kit Wind Baffle Low Ambient Kit Cool/Heat Variable Water
Selector Flow Control
Kit

ZAGDKA51A ZAGDKA52A ZHGDKA51A ZLABKA51A ZLABGP04A PRVC2 PRDSBM PWFCKN000


ZHGDKA52A ZLABKA52A (for use with Multi V S®)

Type Model Description Used with


ZAGDKA51A Air Guide Multi V™ 5 (6 Ton Chassis)
Air Guide
ZAGDKA52A Air Guide Multi V™ 5 (8 to 20 Ton Chassis)
ZHGDKA51A Hail Guards Kit Multi V™ 5 (6 Ton Chassis)
Hail Guard
ZHGDKA52A Hail Guards Kit Multi V™ 5 (8 to 20 Ton Chassis)
ZLABKA51A Low Ambient Baffle Kit (requires PRVC2) Multi V™ 5 (6 Ton Chassis)
Low Ambient Baffle Kit
ZLABKA52A Low Ambient Baffle Kit (requires PRVC2) Multi V™ 5 (8 to 20 Ton Chassis)
Wind Baffle ZLABGP04A Low Ambient Baffle Kit (two required per unit) Multi V S®
Variable Water Flow Control Kit PWFCKN000 Variable Water Flow Control Kit for Multi V WATER® 5 Multi V WATER® 5
Low Ambient Control Kit PRVC2 Low Ambient Control Kit (supports cooling down to -9°F) Multi V™ 5
Cool/Heat Selector PRDSBM Cool/Heat Mode selector for Multi V™ solutions Multi V™ 5, Multi V S®, Multi V WATER® 5

ACCESSORIES
Type Model Description Used with
PQSH1200 Drain Pan Heater ARUN024GSS4 & ARUN060GSS4
ZPLT1A51A Drain Pan Heater (208/230V) Multi V™ 5 (6 Ton Chassis)
ZPLT1A52A Drain Pan Heater (208/230V) Multi V™ 5 (8 to 20 Ton Chassis)
Drain Pan Heater Base
ZPLT2A51A Drain Pan Heater (460V) Multi V™ 5 (6 Ton Chassis)
ZPLT2A52A Drain Pan Heater (460V) Multi V™ 5 (8 to 20 Ton Chassis)

42
UNIT NOMENCLATURE
Outdoor Units and Heat Recovery Units

Outdoor Units (ODU)

ARU M 072 B T E 5
Family Type Capacity Electrical Airflow Efficiency Generation
Ratings Configuration

Family ARU Multi V™ Outdoor Unit (Refrigerant R410A)

Type M Combination (Heat Pump or Heat Recovery)


N Heat Pump
B Heat Recovery

Capacity 024 24 121 121 264 264 408 408


(cooling capacity 038 38 144 144 288 288 432 432
in kBtu/h) 048 48 168 168 312 312 456 456
060 60 192 192 336 336 480 480
072 72 216 216 360 360 504 504
096 96 241 240 384 384

Electrical Ratings B 208–230V/60Hz/3Ph


D 460V/60Hz/3Ph

Airflow T Top Discharge


Configuration

Efficiency E High Efficiency

Generation 5 Fifth

Heat Recovery Units (HRU)

PRHR 02 3A
Family Number of Ports Series
Number

Family PRHR Multi V™ Heat Recovery (HR) unit (Refrigerant R410A)

02 Two Ports 06 Six Ports


Number of Ports 03 Three Ports 08 Eight Ports
04 Four Ports

Series Number 3A Series Number

Due to our commitment to continued innovation, some specifications may be changed without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.

43 LG Air Conditioning Technologies


Multi V WATER® 5

ARW M 072 B A S 5
Family Type Capacity Electrical Airflow Efficiency Generation
Ratings Configuration

Family ARW Multi V WATER® 5 Water Source Unit (Refrigerant R410A)

Type M Inverter Heat Pump and Heat Recovery

Capacity 072 72 191 192 288 288 576 576


(cooling capacity 096 96 192 192 360 360
in kBtu/h) 121 120 216 216 432 432
144 144 240 240 480 480
168 168 264 264 504 504

Electrical Ratings B 208–230V/60Hz/3Ph


D 460V/60Hz/3Ph

Airflow Configuration A Not Applicable

Efficiency S Standard

Generation 5 Fifth

44
NEED IMAGE

45 LG Air Conditioning Technologies


NOTES:

46
Variable Refrigerant Flow (VRF) Multi-Split AC and HP
AHRI Standard 1230

LG Electronics USA, Inc. Distributed by

Air Conditioning Technologies


4300 North Point Parkway, Alpharetta, GA 30022
www.lghvac.com

©2024 LG Electronics U.S.A., Inc. All rights reserved. Document Number: PC_VRF_Systems_05_24

The AHRI Certified® mark indicates LG Electronics (LG) participation in the AHRI Certification program. For verification of individual certified products, go to www.ahridirectory.org.
CSA Group® is a registered trademark of Canadian Standards Association. All indoor and outdoor units are certified by the CSA Group.
USGBC® and the related logo are trademarks owned by the U.S. Green Building Council and are used with permission.

You might also like