Thermolators advantageSKLEmanual
Thermolators advantageSKLEmanual
#082 07/06
COVERING
INSTALLATION
OPERATION
MAINTENANCE
TABLE OF CONTENTS
1.0 GENERAL 9
1.1 Safety 10
1.2 Efficiency 10
1.3 Typical Label Placement 10
1.4 Component placement 11
2.0 INSTALLATION 13
2.1 General 14
2.2 To and from process connections 14
2.3 Water supply connection 15
2.4 Drain connection 15
2.5 Electrical connection 16
4.0 TROUBLESHOOTING 33
4.1 Unit will not start (Power light off) 34
4.2 Unit will not start (Power light on) 34
4.3 Unit stops 34
4.4 Unit overheats 35
4.5 Unit underheats 36
4.6 Pressure relief valve leaks 37
4.7 Cooling valve fault 38
5.0 MAINTENANCE 39
5.1 Pump seal replacement 40
5.2 Heating cylinder replacement 43
5.3 AVTTM cooling valve service 45
5.4 Probe calibration 49
5.5 Voltage changeover 51
5.6 Sensor probe service 53
5.7 Pressure switch service 55
5.8 Sentra LE instrument service 56
5.9 Configuring temperature display units 58
5.10 Configuring alarm temperature parameter 59
5.11 Configuring communications rate 60
8.0 APPENDIX 75
8.1 Specifications 76
8.2 Sentra Model # and suffix coding 77
8.3 Interpretation of process pressure gauges 78
8.4 Mold purge operation 79
8.5 Closed Circuit Operation 80
8.6 SPI commands 81
8.7 Optional alarm operation 84
8.8 AVTTM Valve Components 85
8.9 Sentra AS5 pump parts list - 1/2 HP to 1 HP 86
8.10 Sentra AS5 pump parts list - 1 1/2 HP to 3 HP 87
8.11 Sentra parts list - LE instrument 88
UNIT INSTALLED TO 'TO PROCESS' TO 'WATER IN' ON 'FROM PROCESS' TO 'WATER OUT' ON
NO ...
PROCESS CORRECTLY? PROCESS MANIFOLD PROCESS MANIFOLD
YES
NO
NO
WATER SUPPLY YES
PRESSURE SWITCH OPEN
ENGAGE POWER
PRESSURE LOW?
NO SUPPLY UNIT WITH 15 PSI
INSTRUMENT DEFECTIVE
REPLACE
SENTRA STOPS
NO
WATER SUPPLY YES
PRESSURE SWITCH OPEN
ENGAGE POWER
PRESSURE LOW? SUPPLY UNIT WITH 20 PSI
NO
INSTRUMENT DEFECTIVE
REPLACE
SENTRA OVERHEATS
LOW PROCESS CHECK FOR A CLOSED KINKED HOSE OR BLOCKED WATER CHANNEL
YES OR OR
FLOW RATE? PROCESS VALVE EXCESSIVE PIPE FITTINGS IN TOOLING OR MOLD
NO
INSTRUMENT DEFECTIVE
REPLACE
SENTRA UNDERHEATS
INSTRUMENT DEFECTIVE
REPLACE
Page: 8
Temperature Control Units : Sentra with ‘LE’ Series Instrument
1.0 GENERAL
1.1 SAFETY
1.2 EFFICIENCY
1.3 TYPICAL LABEL PLACEMENT
1.4 COMPONENT PLACEMENT
1.1 SAFETY
1.2 EFFICIENCY
Warning Label
Summarizes the safety precautions
when unit is in use.
Instrument
(Not visible in this photograph.)
Pressure Gauges
Thermoformed Cover
Panel
Heater
Flow Meter
(Inside cooling cylinder.)
Pump Motor
Pump
Vented Stainless
Steel Cabinet
Caster
Electrical Panel
Lift-Off Cover
Panel
2.0 INSTALLATION
2.1 GENERAL
2.2 TO AND FROM PROCESS CONNECTIONS
2.3 WATER SUPPLY CONNECTION
2.4 DRAIN CONNECTION
2.5 ELECTRICAL CONNECTION
2.1 GENERAL
Drain connection:
connect to one of the following:
(depending on water supply source)
• plant’s open drain
• tower water system return
• chilled water system return
To process connection:
connect to “water in” on process manifold
B. Connect the unit’s From Process port to the Water Out port on the
process manifold.
A. Connect the unit’s Water Supply port to the plant’s city water, well
water, tower water or chilled water supply.
OPERATING TEMPERATURE
180°F 190°F 200°F 210°F 220°F 230°F 240°F 250°F
20 PSI 25 PSI 30 PSI 35 PSI 40 PSI 45 PSI 50 PSI 55 PSI
WATER SUPPLY PRESSURE
Figure 2.2A
D. CAUTION: the unit must never be operated with a closed drain line
valve. A closed drain line valve prevents adequate system cooling
and will lead to unit overheating. Overheating of the unit may lead to
unit damage and/or serious personal injury.
A. NEMA 1 MODELS
B. NEMA 12 MODELS
D. GENERAL
1. Make certain all ground Control circuit transformer fuse Figure 2.5C
3.0 OPERATIONS
3.1 GENERAL
3.2 MACHINE START UP/OPERATIONS PROCEDURE
3.3 INSTRUMENT OPERATION
3.4 SHUT DOWN/DISCONNECT PROCEDURE
3.1 GENERAL
A. SYSTEM FILL
2. Once the water supply source is open, the unit will fill
automatically. Allow a few moments for the the unit to
completely fill. The operator can determine the unit is
properly filled when the To Process pressure gauge and the
From Process pressure gauge stabilize at equal or closely
similar pressure.
3. The operator must check for any water leakage in the unit’s
mechanical system, the process, and throughout the plant’s
water supply system. If a water leak is observed, the
operator must disengage the water supply system, relieve
all pressure, and repair the leak. The operator must verify
the leak is repaired by refilling the system as outlined in this
procedure.
1. The operator must determine and set proper water flow rate
for the most efficient and trouble free operation.
Figure 3.3A
A. INSTRUMENT START-UP
B. INSTRUMENT OPERATION
2. When the unit is turned on, the instrument will display the
previously selected setpoint temperature in the Setpoint
window. The setpoint temperature is displayed continuously.
C. INSTRUMENT CONTROLS
10. °C: illuminates when the DIP switch #8 is set to “off” (see
figure 3.3B).
A. PRECAUTIONS/WARNINGS
Page: 32
Temperature Control Units : Sentra with ‘LE’ Series Instrument
4.0 TROUBLESHOOTING
4.1 UNIT WILL NOT START (POWER LIGHT IS NOT ILLUMINATED)
4.2 UNIT WILL NOT START (POWER LIGHT IS ILLUMINATED)
4.3 UNIT STOPS
4.4 UNIT OVERHEATS
4.5 UNIT UNDERHEATS
4.6 PRESSURE RELIEF VALVE LEAKS
4.7 COOLING VALVE FAULT “ULU”
A. One or more fuses at the main disconnect device are open (blown).
Determine continuity at each fuse. If continuity is not determined,
replace the fuse. Then determine cause of blown fuse.
A. The operator should determine the main power supply to the unit is
ON by an illuminated Power light on the display. With the main
power supply “on”, the unit will be prevented from starting by the
following conditions:
B. The operator should check the Power light on the display. The
operator should check the following conditions:
A. The unit has a 150 psi pressure relief valve mounted in the cooling
cylinder. If the valve is found to be leaking, the operator should
check the following:
5.0 SERVICE/MAINTENANCE
5.1 PUMP SEAL REPLACEMENT
5.2 HEATING CYLINDER SERVICE
5.3 AVTTM COOLING VALVE SERVICE
5.4 PROBE CALIBRATION
5.5 VOLTAGE CHANGEOVER
5.6 SENSOR PROBE SERVICE
5.7 PRESSURE SWITCH SERVICE
5.8 INSTRUMENT SERVICE
5.9 CONFIGURING TEMPERATURE DISPLAY UNITS
5.10 CONFIGURING ALARM TEMPERATURE PARAMETER
5.11 CONFIGURING COMMUNICATIONS RATE
carbon/ceramic shaft
seal assembly including
a stationary member,
rotating member and
tension spring (figure
5.1A).
use, operating
temperature and water
quality. Poor water quality is the
primary reason for premature pump
seal failure.
1. Disengage process
operations and relieve all
system pressure.
Remove lift-off access panel Figure 5.1B
2. Disengage main power
supply. Verify the Power
light on the display is “off”.
Mounting flange
Figure 5.3A
Coupling
Valve
Home switch
Motor / Gearbox
Figure 5.3B
MTG Screws
Switch
Lobe
Coupling
17. Replace the top plate, the micro switch mounting plate and
the 4 mounting bolts. Tighten the 4 mounting bolts
alternating to the opposite bolts.
18. Once power is reapplied, the instrument will align the AVTTM
modulating valve to “home base”. Home base is the
reference point from which the controller is able to open the
valve incrementally. Process operations can resume. If the
unit is not able to find home, a valve fault ULU will appear in
the temperature display. Readjust the home switch to clear
the fault. Adjust the home switch as needed (as outlined in
Step 11).
7. Reduce the unit’s set point, via the Down Arrow push button
to 32°F.
c. Use a non-conductive
device, to adjust the
potentiometer.
Adjust the Calibration port Figure 5.4C
potentiometer until
the “to process” temperature on the display equals
the temperature of the ice bath.
10. Shut down the unit. The operator must be certain to remove
the 1/2” plug and replace the sensor probe. Restart
operations.
1. Heater (rewiring)
2. Motor (rewiring)
3. Transformer (rewiring)
4. Motor overloads (replacement)
Wiring schematics for 230 and 460 volt heaters Revised 9/98 Figure 5.5A
6. Rewire the pump motor for the new voltage. Most Sentra
pump motors are dual voltage. Figure 5.5B shows the wiring
schematic for 230 and 460 voltages.
208/230 460/480
4 4
6 7
5
1
L1
8
7
6
2
L2
9
8
3 1 L1
L3 2 L2
9 3 L3
Wiring schematics for 230 and 460 volt pump motors Figure 5.5B
7. Thread one 1/2” nut onto the pressure switch and then
place the pressure switch through the panel in the original
mounting hole. Thread the second 1/2” nut from the bottom
of the pressure switch. Tighten to lock the pressure switch
in place.
5. The instrument is
mounted on the
electrical cabinet panel
cover. The instrument is
secured by four Connections Figure 5.8B
mounting bolts. A series
of electrical connections
link the instrument to the mechanical components of the
unit (Figure 5.8B).
9. Place the instrument into the panel mount, aligning the four
mounting stems. Once the instrument is aligned, tighten the
nuts to secure the instrument.
13. The operator can now start the unit as outlined in section 3
of this manual. The operator must reconfigure (if necessary)
the instrument to restore the preferred operating
parameters.
assembly.
C. HEATER/PUMP DISCHARGE
CYLINDER. The heater/pump
discharge cylinder is a custom cast
tank. The tank is flanged mounted
to the pump casing. Reinforced
machined bosses accept the “to
process/high temperature limit”
sensor probe and the “to process” Heater Figure 6.1E
Discharge tank
connection (figure 6.1E).
AVT valve
F. SENSOR PROBES. The unit uses two sensor probes. The “to
process” temperature sensor and the “high temperature limit” safety
switch” are housed in the same assembly and mounted in the
Instrument service
connections
Page: 66
Temperature Control Units : Sentra with ‘LE’ Series Instrument
To Process
Instrument
Drain
Pressure Gauges
From Process
26 5/8
Water Supply
GROUND
1 1 1
7.2
2 2
3
3 3
M1 H1
1 MOL
VIO
S SNUBBER
STATUS
SENTRA ELECTRICAL
TO PROCESS
ORG 50
°F H1 HEATER CONTACTOR
POWER SAFETY ALARM VENT
°C
ALARM
ACTIVE/INACTIVE
YEL 50
SETPOINT ALARM (OPTIONAL)
(USED ONLY ON BEACON ALARMS)
PUMP HEAT COOL
WHT
UNIT
ON/OFF
RS-485
BLK
BLK
WHT
RED
www.AdvantageEngineering.com
ADVANTAGE ENGINEERING, INC.
Page: 69
Temperature Control Units : Sentra with ‘LE’ Series Instrument
HEATER
TO PROCESS
PRESSURE GAUGE
TO PROCESS
CONNECTION
TO PROCESS SENSOR
HI TEMP SAFETY
DRAIN CONNECTION
FROM PROCESS
CONNECTION
DISCHARGE TANK
WATER SUPPLY
CONNECTION FROM PROCESS
PRESSURE GAUGE
SUCTION TANK
PUMP
DRAIN
TO PROCESS
FROM PROCESS
DRAIN
SENTRA '1"
DRAIN CONNECTION
SENTRA '2"
FROM PROCESS
CONNECTION
DRAIN CONNECTION
TO PROCESS
CONNECTION
TO PROCESS CONNECTION
°C °F POWER SELECT
CONNECTION
SETUP
FLOW
START STOP
PUMP ON LPM GPM
CAPACITY % ®
TEMPERATURE CONTROLLER
RS-485
TEMPERATURE CONTROLLER
TM
®
FROM PROCESS
®
CONNECTION
WATER SUPPLY
CONNECTION
WATER SUPPLY
MANIFOLD
CONNECTIONS
TO PROCESS
CONNECTION
TEMPERATURE
POWER SELECT
TO FROM °C °F
PUMP ON
SETUP
NETWORK MACHINE
FLOW
LPM GPM
START STOP
CAPACITY % ®
TEMPERATURE CONTROLLER
DRAIN
RS-485
®
CONNECTION
TEMPERATURE CONTROLLER
TM
FROM PROCESS
CONNECTION
WATER SUPPLY
CONNECTION
CONNECTION TO CONNECTION TO
21.5" 29" PLANT WATER SUPPLY PLANT DRAIN
Page: 74
Temperature Control Units : Sentra with ‘LE’ Series Instrument
8.0 APPENDIX
8.1 SPECIFICATIONS
8.2 SENTRA MODEL # AND SUFFIX CODING
8.3 INTERPRETATION OF PROCESS PRESSURE GAUGES
8.4 OPERATION OF MOLD PURGE
8.5 CLOSED CIRCUIT OPERATION
8.6 SPI COMMANDS
8.7 OPTIONAL ALARM OPERATION
8.8 AVTTM VALVE COMPONENTS
8.9 SENTRA AS5 PUMP PARTS LIST - 1/2 HP TO 1 HP
8.10 SENTRA AS5 PUMP PARTS LIST - 1.5 HP TO 3 HP
8.11 SENTRA PARTS LIST - LE INSTRUMENT
8.1 SPECIFICATIONS
SENTRA SPECIFICATIONS SK- 1020 1035 1045 1065 1075 1080 1090 10100
HEATER1 KW 10 10 10 10 10 10 10 10
PROCESS PUMP HP 1/2 3/4 1 11/2 2 3 5 71/2
GPM 20 35 45 62 75 80 90 100
PSI 30 30 30 30 30 30 34 54
FULL LOAD AMPERAGE 230 volt 27.0 27.8 28.6 30.2 31.8 34.6 40.3 47.1
@3ø/60hz2 460 volt 13.5 13.9 14.3 15.1 15.9 17.3 20.2 23.5
DIMENSIONS (inches) Height 27 27 27 27 27 27 44 44
Width 11 11 11 11 11 11 16 16
Depth 16 16 16 16 16 16 24 24
CONNECTIONS (inches) T/F3 11/4 11/4 11/4 11/4 11/4 11/4 11/2 11/2
S/D4 1
/2 1/2 1
/2 1
/2 1
/2 1
/2 1
/2 1
/2
WEIGHT (pounds) Shipping 5 198 200 208 208 213 223 275 290
SENTRA SPECIFICATIONS SK- 1620 1635 1645 1665 1675 1680 1690 16100
HEATER1 KW 16 16 16 16 16 16 16 16
PROCESS PUMP HP 1/2 3/4
1 11/2 2 3 5 71/2
GPM 20 35 45 62 75 80 90 100
PSI 30 30 30 30 30 30 34 54
FULL LOAD AMPERAGE 230 volt 42.0 42.8 43.6 45.2 46.8 49.6 55.4 62.2
@3ø/60hz2 460 volt 21.0 21.4 21.8 22.6 23.4 24.8 27.7 31.1
DIMENSIONS (inches) Height 27 27 27 27 27 27 44 44
Width 11 11 11 11 11 11 16 16
Depth 16 16 16 16 16 16 24 24
CONNECTIONS (inches) T/F3 11/4 11/4 11/4 11/4 11/4 11/4 11/2 11/2
S/D4 1/2 1/2 1/2 1
/2 1/2 1/2 1/2 1/2
WEIGHT (pounds) Shipping 5 200 205 210 210 220 225 285 300
SENTRA SPECIFICATIONS SK- 2435 2445 2465 2475 2480 2490 24100
HEATER1 KW 24 24 24 24 24 24 24
PROCESS PUMP HP 3/4
1 11/2 2 3 5 71/2
GPM 35 45 65 75 80 90 100
PSI 30 30 30 30 30 34 54
FULL LOAD AMPERAGE 230 volt 63.1 63.9 65.5 67.1 69.9 75.5 82.3
@3ø/60hz2 460 volt 31.6 32.0 32.8 33.6 35.0 37.8 41.2
DIMENSIONS (inches) Height 44 44 44 44 44 44 44
Width 16 16 16 16 16 16 16
Depth 24 24 24 24 24 24 24
CONNECTIONS (inches) T/F3 11/4 11/4 11/4 11/4 11/4 11/2 11/2
S/D4 1
/2 1
/2 1
/2 1
/2 1
/2 1
/2 1
/2
WEIGHT (pounds) Shipping 5 270 275 280 285 290 295 310
SENTRA SPECIFICATIONS SK- 3435 3445 3465 3475 3480 3490 34100
HEATER1 KW 34 34 34 34 34 34 34
PROCESS PUMP HP 3/4
1 11/2 2 3 5 71/2
GPM 35 45 65 75 80 90 100
PSI 30 30 30 30 30 34 54
FULL LOAD AMPERAGE 230 volt 88.2 89.0 90.6 92.2 95.0 100.6 107.4
@3ø/60hz2 460 volt 44.1 44.5 45.3 46.1 47.5 50.3 53.7
DIMENSIONS (inches) Height 44 44 44 44 44 44 44
Width 16 16 16 16 16 16 16
Depth 24 24 24 24 24 24 24
CONNECTIONS (inches) T/F3 11/4 11/4 11/4 11/4 11/4 1 1/2
11/2
S/D4 1/2 1/2 1/2 1/2 1/2 1/2 1/2
WEIGHT (pounds) Shipping 5 280 285 290 295 300 305 320
Notes:
1. Derate heater output by 25% for 208/3/60 operation.
2. Consult factory for 50hz operations.
3. T - to process; F - from process.
4. S - water supply; D - drain.
5. Approximate unit shipping weight.
MODEL # SUFFIX
S K - 1 0 4 5 - HE - 4 1 C X
HEATER KILOWATTS
6 = 6 KW
10 = 10 KW
16 = 16 KW
24 = 24 KW
36 = 36 KW
GPM BY HP
35 = 35 GPM @ 3/4 HP
45 = 45 GPM @ 1 HP
65 = 65 GPM @ 1 1/2 HP
75 = 75 GPM @ 2 HP
90 = 90 GPM @ 5 HP
100 = 100 GPM @ 7 1/2 HP
INSTRUMENTATION
LE = LE instrument
HE = HE instrument
VOLTAGE
2 = 208-230/3/60
3 = 380/3/50
4 = 460/3/60
5 = 575/3/60
6 = 415/3/60
ELECTRICS
1 = NEMA 1
2 = NEMA 12
J = JIC
VALVE SIZE
A = None
B = 1/4"
C = 3/8"
D = 1/2"
E = 3/4"
F = 1"
SPECIAL OPTIONS
Consult factory for more information
LINE TO DRAIN
CHECK VALVE
DRAIN CONNECTION prevents compressed air from purging
unit
AVT VALVE
TO PROCESS CONNECTION
closed to prevent purge of unit
SOLENOID VALVE
opens to purge water to drain
BYPASS VALVE
FROM PROCESS
TO PROCESS WATER
SUPPLY
HEAT
DRAIN EXCHANGER
AVT VALVE
BYPASS VALVE
HEAT
EXCHANGER
FROM PROCESS
WATER SUPPLY
DRAIN
Note in the above example that different device types may have the
same address. This is because the SPI Protocol uses the device
type as part of its internal address.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
PROCESSING
ALARM - SYSTEM
ALARM - PROCESS
ALARM - MACHINE
ALARM - HIGH TEMPERATURE
ALARM - LOW TEMPERATURE
ALARM - LOW FLOW*
POLL SELECT
C1 C2 C1 C2 COMMAND DESCRIPTION
20 42 Status Machine 1
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
PROCESSING
ALARM - SYSTEM
ALARM - PROCESS
ALARM - MACHINE
ALARM - HIGH TEMPERATURE
ALARM - LOW LOW PRESS
ALARM - HIGH CURRENT
ALARM - PHASE
POLL SELECT
C1 C2 C1 C2 COMMAND DESCRIPTION
20 44 Status Machine 2
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
PROCESSING
ALARM - SYSTEM
ALARM - PROCESS
ALARM - MACHINE
ALARM - SENSOR
POLL SELECT
C1 C2 C1 C2 COMMAND DESCRIPTION
20 48 20 49 Machine
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
ALARM - ACKNOWLEDGE
ALARM - ON/OFF
POLL SELECT
C1 C2 C1 C2 COMMAND DESCRIPTION
20 4A 20 4B Protected mode - machine
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
MACHINE - ON/OFF
ON/OFF ALLOWED
ALARM - ACKNOWLEDGE
POLL SELECT
C1 C2 C1 C2 COMMAND DESCRIPTION
20 70 Temperature to process
20 72 Temperature from process*
20 78 Flow rate from unit GPM*
20 E0 Blanket Poll
Returns: 20 30 Setpoint
20 32 High alarm deviation
20 34 Low alarm deviation
20 40 Status process
20 70 To process temperature
Gear Box
Home Switch
AVTTM VALVE COMPONENTS
www.AdvantageEngineering.com
ADVANTAGE ENGINEERING, INC.
Page: 85
Temperature Control Units : Sentra with ‘LE’ Series Instrument
PART # DESCRIPTION
PART # DESCRIPTION
Note: typical parts list shown. Please supply model and serial numbers when order-
ing parts
PART # DESCRIPTION
299082 Bracket, home switch SI MD-1642
781000 Caster 2” swivel #EY459R
1835050 Contactor #3030APS 30 AMP
1843601 Adapter coupling SI MD-1642
2735358 Sentra top SS - DWG #EP-103
2746237 Electrical enclosure door SS - DWG #EP-103
2761201 Electrical sub panel - DWG #EP-103
2851112 Gauge panel - DWG #EP-103
2877542 Base - DWG #EP-103
3581000 Pressure gauge 0-160 PSI 2” face
3708505 Plastic handle P2-41
3775510 Heater 10KW 2/4/3/60 square flange
3520005 Heater flange gasket 4.50” OD
4439900 Instrument kit SK-SI
4713377 Drip Cover SI MD-1642
6207000 Motor/pump assembly AS5 3/4HP ODP 230/460
414 Adapter iron C2-4551 AS5
771599 Pump case iron 137-001-166 AS5
3444400 Tank gasket 2-3/8” A-9159 AS5
3444401 Gasket, tank flange 4-1/2” AS5
4310602 Impeller B2-5264 4.5” AS5
4310611 Impeller AS5 #100345 4.5” mfg. after 2-97
4714466 Motor 3/4HP 113-000-354T 2/4/3/60
4757862 Motor AE5/AS5/A5W 3/4HP #S-2772R
5486522 Nut S-4989 AS5
5622271 O-ring case 116.000.252
6490000 Shaft seal niresist 5/8”
6491000 Shaft seal ceramic 5/8”
6748201 Cap screw #102RO3A2
9118502 Impeller washer #100301
7370000 Motor starter CR354AB3AA1B
1733456 Auxiliary contact kit #353XAAA
7541000 Panel mount pressure switch #82681
7732250 Heater cylinder AS5 #D2-1841
8240000 Transformer 9T58B42
8764940 AVT valve SI #Eh-89C 1/2”
8764939 AVT SI repair kit #EH-124
8764949 AVT drive kit for 3/8” and 1/2” valves #977700
9060000 Pressure relief valve #150 PSI
RE 1 7/06