Chapter 2 Fault - Analysis
Chapter 2 Fault - Analysis
Technology
Chapter Two
Fault Analysis
By: Minale B.
11/20/2023 1
Fault Analysis
• A fault in a circuit is any failure which interferes with the normal flow of
current.
11/20/2023 2
o Why it is necessary to calculate fault currents?
Dimensioning of equipment:
Dynamic forces
Thermal forces
Insulation stresses (over voltages)
Breaking capacity of breakers
Setting of protective devices:
Stability and sensitivity of unit protections
Protection system overall selectivity
Minimum fault current versus maximum load current
Network stability
• Effects the power transfer capacity
Safety aspects
• Step and touch voltages during earth faults
Control aspects
• Allowed and preferred switching combinations
e
11/20/2023 3
Fault Types:
Short circuits (Shunt fault)
Open circuits (Series fault)
Simultaneous faults:
• Presence of two or more similar or different kind of faults
somewhere in the power system. For example: double earth fault
Winding faults:
• Faults which occur on machine and transformer windings
• Between windings, winding and earth, within winding or a mixture
11/20/2023 4
Two of the factors on which the proper selection of circuit breakers
depends are the current flowing immediately after the fault occurs
and the current which the breaker must interrupt.
11/20/2023 5
Symmetrical Faults
11/20/2023 6
11/20/2023 7
11/20/2023 8
11/20/2023 9
11/20/2023 10
11/20/2023 11
11/20/2023 12
Symmetrical Components
1. Positive-sequence components:
• Consisting of three phasors equal in magnitude, displaced from each
other by 120 degrees in phase, and having the same phase sequence
as the original phasors.
2. Negative-sequence components:
• Consisting of three phasors equal in magnitude, displaced from each
other by 120 degrees in phase, and having the phase sequence
opposite to that of the original phasors.
3. Zero-sequence components:
• Consisting of three phasors equal in magnitude and with zero phase
displacement from each other.
11/20/2023 13
Cont.
11/20/2023 14
Cont.
11/20/2023 15
Cont.
11/20/2023 16
Cont.
11/20/2023 17
Cont.
11/20/2023 18
Cont.
11/20/2023 19
Cont.
11/20/2023 20
Cont.
11/20/2023 21
Example 1
11/20/2023 22
Solution
11/20/2023 23
Example 2
11/20/2023 24
Sequence Networks of Impedance Loads
11/20/2023 25
Cont.
11/20/2023 26
Cont.
11/20/2023 27
Example 3
Solution
11/20/2023 28
Cont.
11/20/2023 29
Power in Sequence networks
11/20/2023 30
Unsymmetrical Faults
When an Unsymmetrical Fault occurs in an otherwise balanced system, the
sequence networks are interconnected only at the fault location. As such, the
computation of fault currents is greatly simplified by the use of sequence
networks.
Assumptions Commonly Made in Three Phase Fault Studies
The following assumptions are usually made in fault analysis in three phase
transmission lines.
• All sources are balanced and equal in magnitude & phase
• Sources represented by the Thevenin’s voltage prior to fault at the fault point.
• Large systems may be represented by an infinite bus-bars.
• Transformers are on nominal tap position.
• Resistances are negligible compared to reactance's.
• Transmission lines are assumed fully transposed and all 3 phases have same Z.
• Loads currents are negligible compared to fault currents.
• Line charging currents can be completely neglected.
11/20/2023 31
Basic Voltage Current Network Equations in Sequence Components
11/20/2023 32
Cont.
11/20/2023 33
Cont.
11/20/2023 34
Analysis of Asymmetrical Faults
11/20/2023 35
Cont.
11/20/2023 36
Cont.
11/20/2023 37
Cont.
11/20/2023 38
Line to Line faults (L – L faults)
11/20/2023 39
Cont.
11/20/2023 40
Cont.
11/20/2023 41
Cont.
11/20/2023 42
11/20/2023 43