TPSSL DOCUMENT NUMBER : TPS-070-EL-032

NTPC DOCUMENT NUMBER : 5754-004-PVE-Y-058

DRAWING TITLE : HT Cable data sheet and type test report

PROJECT : 160 MW SOLAR POWER PLANT,


JETSAR,RAJASTHAN.

“ Drawings Documents are being submitted to NTPC for


information”

“Since the drg/Document is identified as an Auto Archive type, hence


Contractor/ Vendor has the entire responsibility to ensure fulfilment for
technical specification and contractual requirement.

This drawing/document has been retained for information to NTPC”

Digitally signed by
Signature Not Verified
SAVITA
CHOUBEY
Date: 2020.02.19
11:08:13 IST
Reason: CAT
catrel
Location:
NTPCEOC

0 For Information 18-Feb-2020 AG VS BKCP

Prepared Checked Approved


Rev. No. Description Date
By By By
HAVELLS INDIA LTD. (CABLE DIVISION) - ALWAR
Technical Particulars
Customer : M/S TATA Power Solar Ltd.
Project : 160MW NTPC Jetsar Project
Our Ref. No . HIL/GTP/EA/0533/20, Dated -05.02.20 (Rev 01 Dated : 14.02.20) HV 19/33 KV XLPE INSULATED ALUMINIUM POWER CABLE
Sr.No. Descriptions Unit 1C X 300
1 Name of Manufacturer. HAVELLS INDIA LIMITED
2 Applicable Standard to which cable confirms IS: 7098 Part-2, 2011 With up to date amendment
3 Type of cable A2XWaY
4 Voltage Grade. KV 19/33 KV
Design life 25 Years
5 Conductor detail
~ Conductor material Aluminium H4 Grade
~ Nominal cross-sectional Area mm2 300
Min. Size shall be corresponding to meet the requirements of conductor Resistance
as per relevant clause of I.S. -8130/2013
~ Min Number of strands in each conductor. No. 36
~ Diameter of each conductor strand (Before stranding) 3.45
~ Conductor diameter (approx) 20
~ Shape of conductor Stranded compacted Circular as per class-2 of IS 8130/2013
6 Screening on Conductor :
~ Type & Material. Semiconducting Compound by extrusion
~ Approx. . Thickness mm 0.30
~ Continuous working temperature. Deg. C 90
~ Approx Diameter over Conductor screen mm 21
7 Insulation :
~ Material. X.L.P.E. conforming to IS: 7098 Pt.- 2 / 2011
~ Nominal thickness mm 8.80
~ Minimum Thickness. mm 7.82
8 Screening on Insulation :
Non metallic part

~Material / Type Black extruded Semiconducting compound Followed by semiconductiong tape

~Approx. thickness mm 0.30


metallic part Armour shall be constitute the metallic part of Screening
~Material / Type Not applicable
~Approx. thickness mm Not applicable
~ Approx Diameter over insulation screen mm 40
9 Identification of cores Not applicable
10 Filler material Not applicable
11 Inner Sheath : Not applicable
12 Armouring :
~ Material. Single layer of Hard Drawn Aluminium Round Wire
~ Type. Conforming to IS : 7098 PT-2
~ Nominal dimension of wire mm 2.50
~ Earth fault current carring capacity of armour KA/Sec 12.5 KA /1 Sec
~ Approx Number of Armour wires 43
~minimum coverage 90%
~ Approx Diameter under armour mm 40
~ Approx Diameter over armour mm 45
~ Fictitious Diameter under armour mm 40.1
~ Fictitious Diameter over armour mm 45.1
13 Outer Sheath :
~ Material. FRLSH P.V.C.
~ Type. Type-ST-2 conforming to IS : 5831/84
~ Thickness (Min.). mm 2.04
~ Colour of outer sheath BLACK
14 Approximate overall diameter. mm 49
15 Net weight of cable (approx.). kg/km 2650
16 Standard drum length Mtrs. 1000 ± 5%

CLASSIFICATION | PUBLIC
HAVELLS INDIA LTD. (CABLE DIVISION) - ALWAR
Technical Particulars
Customer : M/S TATA Power Solar Ltd.
Project : 160MW NTPC Jetsar Project
Our Ref. No . HIL/GTP/EA/0533/20, Dated -05.02.20 (Rev 01 Dated : 14.02.20) HV 19/33 KV XLPE INSULATED ALUMINIUM POWER CABLE
Sr.No. Descriptions Unit 1C X 300
1 Name of Manufacturer. HAVELLS INDIA LIMITED
17 Non Standard drum length Max. 5 % of ordered quantity
~ Overall Quatity Tolerance ± 2%
Continuous Current Rating for Standard IS Condition when Laid.
18
(Both ends bonded - Flat touching)
~ Direct in ground at 30°c Amps 343
~ in ducts Amps 282
~ In air at 40°c Amps 501

Circulating Current of Armour (A) when conductor carries rated


Amps 90.6
current (Ground 30 °C) (Both ends bonded)

~Allowable max. cond. Temp. when carrying cont. rated current Deg. C 90

19 Short Circuit Rating


Short Circuit current rating for 1 Sec.duration K.AMPS 28.20
Allowable max. cond. Temp. at the time of short circuit Deg. C 250
20 Electrical parameters
Conductor DC Resistance at 20°C. ( Max.) Ohms/Km 0.100
Conductor AC Resistance at 90°C( approx..). Ohms/Km 0.130
Approx. Reactance of cable at 50HZ Ohms/Km 0.122
Approx. capacitance of cable Micro F/Km 0.23
Impulse voltage withstand capacity KV 170
Insulation Resistance.( Volume resistivity )( Min)
at 27 Deg.C Ohms - cm 1 X 1014
at 90 Deg. C Ohms - cm 1 X 1012

HAVELLS 19/33 KV XLPE ELECTRIC CABLE (SIZE IN SQ.MM) (Year of mfg.) - FRLSH-
21 Marking detail (Embossing/printing)
SCREEN FAULT CURRENT 12.5 KA FOR 1 SEC. - NTPC JETSAR

22 Sequential marking of length Shall be printed on every meter of length on outer sheath
23 Packing Material Non Returnable wooden drums
24 Recommended min. Bending radius of cable mm 20 X D ( where D is overall diameter of cable in mm)
25 Recommended Max. Safe pullying force
i) When cond. Pulled by pullying eye N 30 x T( where T is total crossectional area of cond . In sqmm)
ii)When cable pulled by stocking N 9 X D2 ( where D is overall diameter of cable in mm)
FRLSH PROPERTIES
Oxygen Index Test min -29% (As per ASTM-D2863)
Temp.Index Test min -250 Deg C (As per ASTM-D2863)
Acid Gas Generation Max -20% (As per IEC-754 PT-1)
Smoke Generation test Max - 60% (As per ASTM-D2843)
Flammability Test As per IEC -332 -3
* Values indicated as " Approx." are for guidelines only
* In case of any Typographical Error / Discrepancy , relevant standards shall be prevailed.

CLASSIFICATION | PUBLIC
HAVELLS INDIA LTD. (CABLE DIVISION) - ALWAR

CROSS-SECTIONAL DRAWING

Customer : M/S TATA Power Solar Ltd.

Project : 160MW NTPC Jetsar Project

Item : 19/33 KV - 1X300 Sqmm - Aluminium cond./ XLPE insulation / Aluminium Wire armoured / FRLSH PVC Sheathed Cable As per IS
:7098-2/2011 In General

Sr. No. DESCRIPTION


1 STRANDED COMPACTED CIRCULAR ALUMINIUM CONDUCTOR
2 EXT. LAYER OF SEMI COND. COMPOUND
3 XLPE INSULATION
4 BLACK EXTRUDED SEMICONDUCTING COMPOUND FOLLOWED BY SEMICONDUCTIONG TAPE
5 ALUMINIUM ROUND WIRE ARMOUR
6 EXT. PVC ST2 OUTER SHEATH WITH FRLSH PROPERTIES

CLASSIFICATION | PUBLIC