Indoor Unit Operation & Installation Manual
Indoor Unit Operation & Installation Manual
AWSI-CFV007-N11
AWSI-CFV009-N11
AWSI-CFV012-N11
AWSI-CFV016-N11
AWSI-CFV018-N11
AWSI-CFV024-N11
AWSI-CFV028-N11
AWSI-CFV030-N11
AWSI-CFV038-N11
AWSI-CFV048-N11
AWSI-CFV060-N11
No. 0150524399
Product Features:
1. Hanging-style installation to save space;
2. Automatic display of faults;
3. Function of central control (optional from our company).
4. The air conditioner is provided with the function of compensation for power supply. During operation, when the power
supply fails emergently and resumes again, the air conditioner returns to the working condition before power failure, if
provided with compensation function.
5. The operating methods and functions are same although the shapes of indoor units are different.
6. Now this indoor unit only has wired controller function,the indoor unit that has remote controller function need to set in
factory especially.
Air-inlet grille
Air filter (inside air-inlet grille)
1
Safety
• If the air conditioner is transferred to a new user, this manual shall be transferred to the user, together with the
conditioner.
• Before installation, be sure to read Safety Considerations in this manual for proper installation.
• The safety considerations stated below is divided into " Warning" and " Attention". The matters on severe accidents
caused from wrong installation, which is likely to lead to death or serious injury, are listed in " Warning". However, the
matters listed in " Attention" are also likely cause the severe accidents. In general, both of them are the important
items related to the security, which should be strictly abided by.
• After the installation, perform test run to make sure everything is in normal conditions, and then operate and maintain
the air conditioner in accordance with the User Manual. The User Manual should be delivered to the user for proper
keeping.
WARNING
• Please ask the special maintenance station for installation and repair. Water leakage, electric shocks or fire accidents
might be caused from improper installation if you conduct the installation by your own.
• The installation should be conducted properly according to this manual. Water leakage, electric shocks or fire accidents
might be caused from improper installation.
• Please make sure to install the air conditioner on the place where can bear the weight of the air conditioner. The air
conditioner can't be installed on the grids such as the non-special metal burglar-proof net. The place with insufficient
support strength might cause the dropdown of the machine, which may lead to personal injuries.
• The installation should be ensured against typhoons and earthquakes, etc. The installation unconformable to the
requirements will lead to accidents due to the turnover of the machine.
• Specific cables should be used for reliable connections of the wirings. Please fix the terminal connections reliably to
avoid the outside force applied on the cables from being impressed on the cables. Improper connections and fixings
might lead to such accidents as heating or fire accidents.
• Correct shapes of wirings should be kept while the embossed shape is not allowed. The wirings should be reliably
connected to avoid the cover and the plate of the electrical cabinet lipping the wiring. Improper installation might cause
such accidents as heating or fire accidents.
• While placing or reinstalling the air conditioner, except the specific refrigerant (R410A), don't let the air go into the
refrigeration cycle system. The air in the refrigeration cycle system might lead to the cracking or personal injuries due to
abnormal high pressure of the refrigeration cycle system.
• During installation, please use the accompanied spare parts or specific parts. If not, water leakage, electric shocks, fire
accidents or refrigerant leakage might be caused.
• Don't drain the water from the drainpipe to the waterspout where may exist harmful gases such as sulfureted gas to
avoid the harmful gases entering into the room.
• During installation, if refrigerant leakage occurs, ventilation measures should be taken, for the refrigerant gas might
generate harmful gases upon contacting the flame.
• After installation, check if any refrigerant leakage exists. If the refrigerant gas leaks in the room, such things as air
blowing heaters and stoves, etc. may generate harmful gases.
• Don't install the air conditioner at the places where the flammable gases may leak. In case the gas leakage occurs
around the machine, such accidents as fire disasters may be caused.
• The drainpipe should be properly mounted according to this manual as to ensure the smooth drainage. In addition, heat
preservation should be taken to avoid condensation. Improper drainpipe mounting might cause water leakage, which
will get the articles at home wet.
• The refrigerant gas pipe and liquid pipe should be heat insulated to preserve heat. For inappropriate heat insulation, the
water caused from the condensation will drop to get the article at home wet.
2
Safety
CAUTION
• The air conditioner should be effectively grounded. Electric shocks may occur if the air conditioner is ungrounded or
inappropriately grounded. The wire for earthing shouldn't be connected to the connections on the gas pipe, water pipe,
lightning rod or telephone.
• The breaker for electricity leakage should be mounted. If not, accidents such as electric shocks may happen.
• The installed air conditioner should be checked for electricity leakage by being powered.
• If the ambient humidity bigger than 80%, when the water discharge hole be blocked or the filter becomes dirty, or airflow
speed change, there maybe leads to condensing water drop down, and at the same time there maybe some drops of
water spit out.
Attention
• It is not allowed to put any heating apparatus under • Power should be cut off when the air conditioner is
the indoor units, for the heat may cause distortion of left unused for a long period. Power will be consumed
the units. if the air conditioner is not powered off. The power
• Pay attention to the aeration switch of the outdoor unit switch should be powered
condition to avoid anoxic on 12 hours in advance before operation to protect
symptom. the unit after a long period of storage.
• Flammable apparatus should not be placed in the • 3-minute protection
place where the air conditioner wind could reach To protect the unit, compressor can be actuated with
Notices during Operation
3
Maintenance
Attention
• Repair can only be performed by professional personnel.
• Before touching the connection line, all power supplies should be switched off. Only after switching off the power
supply can the operator clean the air conditioner as to avoid electric shock or injury.
• When cleaning the air cleaner, make sure to use a stable platform; don't flush the air conditioner with water, or the
electric shock might be caused.
Daily Maintenance:
Clean the air cleaner & air inlet grid.
• Don't dismantle the air cleaner if not cleaning, or faults might be caused.
• When the air conditioner operates in the environment with too much dust, clean the air conditioner more times (generally
once every two weeks).
1. Remove the air inlet grid as shown in the figure: press down the two locks on the grid (as shown in Fig. 1) to move it
close to the nearby grid, gently lift it 45 degree (as shown in Fig. 2), and then remove the air inlet grid.
2. Dismantle the gauze: press the outer frame of the air inlet grid by the thumb, and draw the base angle of gauze by the
forefinger and pull it out as to make the gauze disengage the locks, and dismantle the gauze (as shown in Fig. 3).
lock device
remove air inlet grid
frame of air inlet grid
(B) for too much dust, use soft-hair brush and mild detergent to clean.
(C) throw off water and then dry it at cool places.
Attention
• Don't clean it with hot water of over 50°C to avoid fading or distortion.
• Don't dry it on the fire, or the cleaner might cause fire.
4
Maintenance
Installing air cleaner and air inlet grid:
1. Mounting the gauze: opposite to the ways of dismantling the gauze
lock device
(as shown in Fig. 3 above).
lock port
2. Mounting the air inlet grid: as shown in the right figure, nip the
locks on the grid as directed by arrows, put the side with the locks
lock device into the lock port, and then put the side with locks
into the panel frame. Release the locks to position the grid after
determining that the grid is abutting upon the bottom of the panel
frame.
insert air inlet grid
Attention
• Don't use gasoline, benzene, diluents, polishing powder or liquid insecticide to clean them.
• Do not clean them with hot water of above 50°C to avoid fading or distorting.
5
Fault Checkup
Please check the following when consigning repair service:
Symptoms Reasons
Water flow sound can be heard when starting operation, during operation or
immediately after stopping operation. When it starts to work for 2-3 minutes,
Water flow sound
the sound may become louder, which is the flowing sound of refrigerant or
the draining sound of condensed water.
During operation, the air conditioner may make the cracking sound, which
Cracking sound is caused from the temperature changes or the slight dilation of heat
All these are not problems
exchanger.
The terrible smell, caused from walls, carpet, furniture, clothing, cigarette
Terrible smell in outlet air
and cosmetics, attaches on the conditioner.
When switching it on again after power failure, turn on the manual power
Flashing operating indicator
switch and the operating indicator flashes.
It displays the awaiting indication as it fails to perform refrigerating operation
while other indoor units are in heating operation. When the operator set it to
Awaiting indication
the refrigerating or heating mode and the operation is opposite to the setting,
it displays the awaiting indication.
To prevent oil and refrigerant from blocking the shutdown indoor units,
Sound in shutdown indoor unit or refrigerant flows in the short time and make the sounds of refrigerant flowing.
white steam or cold air Otherwise, when other indoor units performs heating operation, white steam
may occur; during refrigerating operation, cold air may appear.
Clicking sound when switching the When the conditioner is powered on, the sound is made due to the resetting
air condition on of the expansion valve.
Start or stop working automatically Check if it is in the state of Timer-ON and Timer-OFF.
Failure to work Check if there is a power failure.
Please make another check.
Under the following circumstances, immediately stop the operation, disconnect the manual supply switch and contact the
after-service personnel.
• When buttons are inflexible actuated;
• When fuse and breaker have been burnt over and over;
• When there are foreign objects and water in the refrigerator;
• When it cannot still be operated after removing the operation of protective unit;
• When other abnormal conditions occur.
6
Installation Procedures
The standard attached accessories of the units of this series refer to the packing list; prepare other accessories according
to the requirements of the local installation point of our company.
Indoor units should be installed in places with the environment of even circulation of cool and warm blows. The following
places should be avoided.
• places with high salinity (beach), high sulfureted gas(such as the thermal spring regions where copper tubes and soft
soldering are easy to be eroded), much oil(including mechanical oil) and steam; places where organic substance solvent
is used; where special spray is frequently used;
• places where machines generate the high frequency electromagnetic wave (abnormal condition will appear in the
control system);
• places where there is high humidity exists near the door or windows (dew is easily formed).
Warning:
protect the machine from gales or earthquake, make the installation according to the regulations. Improper installation
will cause accidents due to the overturn of the air conditioner.
Installation Space
Ensure the required space for installation and maintenance (refer to the following drawings).
The installation height should be kept within 2.7m.
When the height of the ceiling exceeds 2.7m, the warm air is hard to blow to the ground.
≥1500
≥1500
≥1500
H
above the ground
More than 2500
≥1000
≥1500
Outlet Suction inlet Outlet
≥1500
≥1500
Space required for installation (unit: mm)
Model H
CFV007~018 206
CFV024~028 227
CFV030~038 269
CFV048~CFV060 311
7
Installation Procedures
2. Location Relationship among Ceiling Hole, Unit and Hoisting Studs
890(ceiling opening)
850(indoor unit)
950(trim panel)
765(spacing of hanging screw)
850(indoor unit)
890(ceiling opening)
950(trim panel)
Hanger bracket
H
130
Model H
CFV007~018 236
Ceiling Trim panel
Distance between indoor CFV024~028 257
Distance between indoor unit
and ceiling≤20 unit and ceiling≤20 CFV030~038 299
Overlap between ceiling CFV048~CFV060 341
Overlap between ceiling and and trim panel≥30
trim panel≥30
Note:
Before suspending the indoor unit, select the installation location according to the piping and wiring in the ceiling, and
determine the lead direction of the piping. Prepare all pipes (refrigerator and drainage) and wiring (connection line for
remote control and connection line of indoor units and outdoor units) connected to indoor units before suspending the
indoor unit so as to make the connections right after the installation.
• In the situation with the ceiling, before suspending the unit, set refrigerant pipe, drainpipe, connection line in the room,
lead wire of line control to the locations of piping and wiring.
• Confirm the size of the indoor unit and fix it according to the requirements in the manual.
8
Installation Procedures
4. Hoisting Stud Installation
• To support the weight of the unit, use barb bolts in the situation with the ceiling. In the situation with the new ceiling, use
inlaid bolts, embedded bolts or other parts provided on site. Before proceeding the installation, adjust the gap between
the bolts and the ceiling.
• Use four M10 hoisting studs (provided on site) (when the height of the hoisting stud exceeds 0.9m, M10 studs should be
used.). The gaps should be kept according to the overall drawing of the air conditioner. Make the installation according
to regulations for various building structures as to ensure the safety. Use the level meter to perform the parallel
installation.
Ceiling Suspending
9
Installation Procedures
Installation
Refrigerant pipe
(1) Confirming the position of unit hanger Housing
Please confirm the installation position of the hanger Indoor unit
for indoor unit is about 130mm above the ceiling. For Drain pipe
details, please refer to the Instructions for Installation and
Maintenance of indoor unit.
(2) Removing the air-inlet grille
Open the air-inlet grille to make it at an angle of 45° to the
trim panel. As shown in the following figure, please remove 2 x U-shaped
the air-inlet grille as per the operation requirements. hooks
Step 3:
Gently Step 2:
push the Open the Trim panel
air-inlet 4x Bolts (M5*25)
air-inlet grille
grille in the to make it (including gaskets)
direction at 45°to the 5) When tightening the four (4) bolts, please make sure
of arrow. panel. there is no clearance between the panel fixing seat on the
Air-inlet side of the indoor unit and the panel fixing seat on the side
Step 1: Open the two
grille of the panel. That is to say: the bolts shall be fully tightened
snaps in the direction of arrow.
(see * in the figure). If there is a clearance, air leakage or
water leakage is likely to occur.
(3) Installing the panel
1) Please remove the four (4) angle trim panels. Removal Panel fixing seat
method: Flip the jack catches of the angle trim panel in the (Indoor unit side)
order of ①②③④ , as shown in the following figure. The
flipping direction is indicated by the arrows. Then the angle
trim panel can be removed.
Panel
fixing seat
Ceiling (Panel side)
Trim panel
Jack catch
1 Caution:
2 • Improper tightening of bolts would lead to the faults
Jack catch
3 shown in the following figure.
4
Jack catch
Air leakage
Jack catch
Ceiling
2) Pull out the two (2) U-shaped hooks on the indoor unit
pollution
from below. Water condensate, water dripping
3)Adjust the panel direction to make the angle side
engraved with"Pipe side" consistent with the refrigerant • After tightening the bolts, if there is a clearance between
pipe of the indoor unit, and make the angle side engraved the ceiling and the trim panel, please readjust the height
with "Drain side" consistent with the drain side of the indoor of the indoor unit.
unit. Then hang the 2 hooks in the inner side of the panel
on the 2 U-shaped hooks of the indoor unit.
4) Finally fix the panel on the indoor unit with the bolts
(M5*25) and gaskets delivered with the unit.
Caution: Gaskets must be used for fixing, or else the panel
would be easy to fall off. Clearance is not allowed
10
Installation Procedures
If the elevation level of the indoor unit and drain pipe are 8) Installing the air-inlet grille.
not affected, you can adjust the height of the indoor unit Install the air-inlet grille with the steps opposite to that for
through the corner pore on the trim panel. Please keep removing.
the unit horizontal in the process of adjustment, or else For reference
water leakage is easy to occur. The method for removing angle trim panels when the
installation of trim panel is complete:
a.Insert a straight screwdriver in the notch ① . Gently turn
the screwdriver downward, and slowly insert it in, and then
move it up and down to make the angle fall off.
b.Make the angle ② and ③ fall off in the same way.
c.Take off the angle trim panel by hand.
Straight screwdriver
Angle trim panel
• Please do not swing the louver blade by hand, or else the
blade mechanism would be damaged. ②
6) Connection of trim panel. Connect the black lead-out
terminal of the panel to the black lead-out terminal of the ③ ①
indoor unit housing.
Connecting terminal
Indoor unit
Connecting to the panel side
Requirements:
• The drainpipe of the indoor unit should be heat-insulated.
Connecting terminal • Heat insulation should be treated for the connection
Trim panel Connecting to the indoor with the indoor unit. Improper heat insulation may cause
unit side condensing.
• The drainpipe with the down gradient of over 1/100 can't
be in the S shape, or abnormal sound can be caused.
• The horizon length of the drainpipe should be kept with
20m. Under the condition of long pipes, supports can be
provided every 1.5~2m as to avoid unevenness.
7) When the installation of panel is complete, please fix the • The central piping should be connected according the
four (4) angle trim panels. following drawing.
• Hang and tighten the strap of the angle trim panel on the • Take care not to apply external force on the connection of
shackle of the trim panel, as shown in the figure. the drainpipes.
• Fix the angle trim panel on the trim panel.
1.5m~2m support bracket
s-shape
heat down gradient elbow
insulating over 1/100
material
11
Installation Procedures
Piping Materials & Heat Insulating Materials
Hard PVC tube VP31.5mm
As to prevent condensation, heat insulating treatment should be Piping Material
(inner bore)
performed. The heat insulating treatment for piping should be done
Heat Insulating Vesicant polythene thickness:
respectively.
Material over 7mm
Hose
The attached hoses can be used to adjust the eccentricity and angle of the hard PVC tube.
• Stretch the hose directly to make connections as to avoid distortion. The soft end of the hose should be positioned with
a clamp.
• The hose should be used in the horizon direction.
hose
hose
°
45
indoor unit
Confirming Drainage
360mm below
The drainage should be confirmed during the test run to make sure that there is
lifting 600mm below
lifting
• After mounting the electrical system, do cooling operation and meanwhile add under the ceiling
water and check.
• If the electrical installation hasn't been completed, pull out the terminal(2P)
of the floater switch on the electrical cabinet. After confirming the drainage, joint of drainpipe
connect the terminal of the floater switch and run the drainage pump for 5
minutes until it stops automatically.
• Confirm the sound of the motor:
Confirm the sound of the motor of the drainage pump and meanwhile check
the drainage.
12
Installation Procedures
Tubing Permissible Length & Height Difference
Please refer to the attached manual of outdoor units.
13
Electrical Wiring
WARNING
• Electrical construction should be made with specific mains circuit by the qualified personnel according to the installation
instruction. Electric shock and fire may be caused if the capacity of power supply is not sufficient.
• During arranging the wiring layout, specified cables should be used as the mains line, which accords with the local
regulations on wiring. Connecting and fastening should be performed reliably to avoid the external force of cables from
transmitting to the terminals. Improper connection or fastness may lead to burning or fire accidents.
• There must be the ground connection according to the criterion. Unreliable grounding may cause electrical shocks. Do
not connect the grounding line to the gas pipe, water pipe, lightening rod and telephone line.
Attention
• Only copper wire can be used. Breaker for electric leakage should be provided, or electric shock may occur.
• The wiring of the mains line is of Y type. The power plug L should be connected to the live wire and plug N connected
to null wire while should be connected to the ground wire. For the type with auxiliary electrically heating function, the
live wire and the null wire should not be misconnected, or the surface of electrical heating body will be electrified. If the
power line is damaged, replace it by the professional personnel of the manufacturer or service center.
• The power line of indoor units should be arranged according to the installation instruction of indoor units.
• The electrical wiring should be out of contact with the high-temperature sections of tubing as to avoid melting the
insulating layer of cables, which may cause accidents.
• After connected to the terminal tier, the tubing should be curved into be a U-type elbow and fastened with the pressing
clip.
• Controller wiring and refrigerant tubing can be arranged and fixed together.
• The machine can't be powered on before electrical operation. Maintenance should be done while the power is shut
down.
• Seal the thread hole with heat insulating materials to avoid condensation.
• Signal line and power line are separately independent, which can't share one line. [Note: the power line, signal line are
provided by users. Parameters for power lines are shown as below: 3×(1.0-1.5)mm2;
parameters for signal line: 2×(0.75-1.25)mm2 ( shielded line)]
• 5 butt lines (1.5mm) are equipped in the machine before delivery, which are used in connection between the valve box
and the electrical system of the machine. The detailed connection is displayed in the circuit diagram.
14
Electrical Wiring
Signal Wiring Drawing
PQABC
Outdoor units are of parallel connection via three lines with polarity. The main unit, central control and all indoor units are
of parallel connection via two lines without polarity.
There are three connecting ways between line control and indoor units:
A. One line control controls multiple units, i.e. 2-16 indoor units, as shown in the above figure, (1-5 indoor units). The
indoor unit 5 is the line-controlled main unit and others are the ine-controlled sub units. The remoter control and the
main unit (directly connected to the indoor unit of line control) are connected via three lines with polarity. Other indoor
units and the main unit are connected via two lines with polarity.SW01 on the main unit of line control is set to 0 while
SW01 on other sub units of line control are set to 1, 2, 3 and so on in turn. (Please refer to the code setting at page 17)
B. One line control controls one indoor unit, as shown in the above figure(indoor unit 6-19). The indoor unit and the line
control are connected via three lines with polarity.
C. Two line controls control one indoor unit, as shown in the figure (indoor unit 20). Either of the line controls can be set to
be the master line control while the other is set to be the auxiliary line control. The master line control and indoor units,
and the master and auxiliary line controls are connected via three lines with polarity.
When the indoor units are controlled by the remote control, switch over the modes by Switching Mode of Line-
Controlled Main Unit/ Line-Controlled Sub Units/ Remote-Controlled Types. The signal terminals needn't to be
equipped with wires and connected to the line control.
15
Electrical Wiring
The wiring for the power line of indoor unit, the wiring between indoor and outdoor units as well as the wiring between
indoor units:
Items Rated current of residual Cross Sectional
Rated Area of Signal Line
Cross Circuit Breaker(A)
Length Current of
Total Section Ground Fault
(m) Overflow Outdoor -indoor Indoor -indoor
Current of (mm2) Interruptor(mA)
Breaker(A) (mm2) (mm2)
Indoor Units(A) Response time(S)
<10 2 20 20 20 A,30 mA,0.1S or below
≥10 and <15 3.5 25 30 30 A,30 mA,0.1S or below 2 cores×0.75-2.0mm2
≥15 and <22 5.5 30 40 40 A,30 mA,0.1S or below shielded lin
≥22 and <27 10 40 50 50 A,30 mA,0.1S or below
• The electrical power line and signal lines must be fastened tightly.
• Every indoor unit must have the ground connection.
• The power line should be enlarged if it exceeds the permissible length.
• Shielded lays of all the indoor and outdoor units should be connected together, with the shielded lay at the side of signal
lines of outdoor units grounded at one point.
• It is not permissible if the whole length of signal line exceeds 1000m.
16
Electrical Wiring
Dipswitch Setting
Indoor Units PCB
In the following table, 1 represents ON and 0 represents OFF.
Definition principles of code switches:
SWO1 is used to set capabilities of master and slave indoor units as well as indoor unit; SW03 is used to set indoor unit
address (combine original communication address and address of centralized controller).
(A) Definition and description of SW01
[1] [2] [3] [4] Address of wire controlled indoor unit (group address)
0 0 0 0 0# (wire controlled master unit) (default)
0 0 0 1 1# (wire controlled slave unit)
SW01_1 0 0 1 0 2# (wire controlled slave unit)
SW01_2 Address of wire
0 0 1 1 3# (wire controlled slave unit)
SW01_3 controlled indoor unit
SW01_4 0 1 0 0 4# (wire controlled slave unit)
0 1 0 1 5# (wire controlled slave unit)
∙∙∙ ∙∙∙ ∙∙∙ ∙∙∙ ∙∙∙
1 1 1 1 15# (wire controlled slave unit)
[5] [6] [7] [8] Capability of indoor unit
0 0 0 1 0.8HP (CFV007)
0 0 1 0 1.0HP (CFV009)
0 0 1 1 1.2HP (CFV012)
SW01_5 0 1 0 1 1.7HP (CFV016)
SW01_6 0 1 1 0 2.0HP (CFV018)
Capability of indoor unit
SW01_7 0 1 1 1 2.5HP (CFV024)
SW01_8 1 0 0 0 3.0HP (CFV028)
1 0 0 1 3.2HP (CFV030)
1 0 1 0 4.0HP (CFV038)
1 0 1 1 5.0HP (CFV048)
1 1 0 0 6.0HP (CFV060)
17
Electrical Wiring
(B) Definition and description of SW03
[1] Address setting mode
Address setting
SW03_1 0 Automatic setting (default)
mode
1 Code-set address
Address of centralized
[2] [3] [4] [5] [6] [7] [8] Address of indoor unit
controller
0 0 0 0 0 0 0 0# (Default) 0# (Default)
0 0 0 0 0 0 1 1# 1#
Code-set indoor 0 0 0 0 0 1 0 2# 2#
SW03_2 unit address … … … … … … … … …
~ and centralized
0 1 1 1 1 1 1 63# 63#
SW03_8 controller address
(Note *) 1 0 0 0 0 0 0 0# 64#
1 0 0 0 0 0 1 1# 65#
1 0 0 0 0 1 0 2# 66#
… … … … … … … … …
1 1 1 1 1 1 1 63# 127#
Note *:
• Set the address by code when connecting the centralized controller or gateway or charge system.
• Address of centralized controller=communication address+0 or+64.
SW03_ 2=OFF, address of centralized controller=communication address+0=communication address
SW03_ 2=ON, address of centralized controller=communication address+64 (applies when centralized controller is
used and there are more than 64 indoor units)
• To use with 0010451181A in use, it is required to use code for address setting. Set SW03_1=0N
and SW03_ 2=OFF; SW03_3, SW03_ 4, SW03_5, SW03_6, SW03_7 and SW03_ 8 are address codes which are set
according to actual address.
• Address setting function of wired controller for ultrathin card machine is disnabled.
18
Test Run & Fault Code
Before Test Run
• Before switching it on, test the supply terminal tier (L, N terminals) and grounding points with 500V megaohm meter and
check if the resistance is above 1MΩ. It can't be operated if it is below 1MΩ.
• Connect it to the power supply of outdoor units to energize the heating belt of the compressor. To protect the
compressor at startup, power it on 12 hours prior to the operation.
Check if the arrangements of the drainpipe and connection line are correct.
The drainpipe shall be placed at the lower part while the connection line placed at the upper part. Heat preservation
measures should be taken such as winding the drainpipe esp. in the indoor units with heating insulating materials.
The drain pipe should be made a slope type to avoid protruding at the upper part and concaving at the lower part on the
way.
Checkup of Installation
check if the mains voltage is matching check if the installation place meets the requirement
check if there is air leakage at the piping joints check if there is too much noise
check if the connections of mains power and indoor & outdoor check if the connecting line is fastened
units are correct check if the connectors for tubing are heat insulated
check if the serial numbers of terminals are matching check if the water is drained to the outside
check if the indoor units are positioned
Fault Remedies
When any fault appears, consult the fault code of line control or the flashing times for LED5 of computer panel of indoor
units/health lamp of receiving window of remote control and find out the faults as shown in the following table to remove
all faults.
Indoor Unit Faults
PCB LED5(Indoor Units)/
Failure code at
Receiver Timer Lamp(Remote Fault Descriptions
wired controller
Controller)
01 1 Fault of indoor unit ambient temp. transducer TA
02 2 Fault of indoor unit pipe temp. transducer TC1
03 3 Fault of indoor unit pipe temp. transducer TC2
04 4 Fault of indoor unit dual heat source temp. transducer
05 5 Fault of indoor unit EEPROM
06 6 Fault of communication between indoor & outdoor units
07 7 Fault of communication between indoor unit and wired control
08 8 Fault of indoor unit water drainage
09 9 Fault of duplicate indoor unit address
0A 10 Fault of communication between indoor unit and Display Board
0C 12 Fault of zero cross sing
0E 14 Fault of DC fan
Outdoor Unit
20 Corresponding faults of outdoor units
Code
19