Key Considerations For Chiller Selection
Key Considerations For Chiller Selection
[email protected]
Key Factors for Chiller Selection
Consider cooling load, efficiency metrics (EER & COP), ambient conditions (temperature & humidity),
refrigerant selection (environmental impact), future expansion needs, common challenges (space &
budget constraints), maintenance access (for reliability), and noise levels (to meet regulations).
For an industrial application requiring cooling for machinery, we need to determine the chiller
load using the formula: Q=m˙⋅Cp⋅ΔT
Where:
• Q is the heat load in (kW) BTU/hr
• m˙ is the mass flow rate in (kg/s) (lb/hr)
• cp is the specific heat capacity in(J/kg°C) (BTU/lb°F)
• ΔT is the temperature difference in degrees Celsius (°C) (°F)
General Formula:
Q=m˙⋅Cp⋅ΔT
The mass flow rate of chilled water (m˙) is 2,500 pounds per hour.
The specific heat capacity of water (cp) is 1 BTU per pound per degree Fahrenheit.
The inlet temperature of the water is 60 degrees Fahrenheit, and the outlet temperature is 50 degrees
Fahrenheit.
Using the formula, we can calculate the chiller load (Q):
Q=m˙⋅Cp⋅ΔT
This calculation indicates that the chiller must be capable of removing 25,000 BTU/hr. (approximately
2.08 TR or 7.34 kW) of heat from the machinery to maintain optimal operating temperatures.
Designing the Heat Exchanger:
Once you've finalized the required cooling load for the building by Heat Load as mentioned above, (or from
Q=m˙⋅cp⋅ΔT for industrial applications), you can then equate it with Q=U⋅A⋅ΔT to determine the heat transfer
area.
Once you have the required heat transfer area (A), you can proceed to design the heat exchanger, selecting
the appropriate number, size, and arrangement of tubes depending on the desired surface area, material,
and flow characteristics. Tube selection will depend on parameters like, Tube diameter and length, Number
of tubes.
Example:
Chiller Rated Conditions (AHRI Standard):
Ambient air temperature: 35°C
Chilled water inlet temperature (evaporator): 12°C Chilled
water outlet temperature (evaporator): 7°C Condenser water
inlet temperature: 30°C
Chiller capacity: 100 TR (tons of refrigeration)
Manufacturers typically include these derating factors or performance charts in their product documentation
to ensure proper selection based on real-world operating conditions.
C. Key Factors for Chiller Selection-Efficiency Metrics:
• Units: EER is expressed in BTUs per watt, while COP is a unitless ratio (kW/kW).
• Application: EER is primarily used for cooling systems (air conditioning and chillers), whereas COP can be
used for both heating and cooling applications, such as chiller and heat pumps.
Both EER and COP are crucial for evaluating the energy efficiency of HVAC systems, influencing operational
costs and sustainability. Higher values for either metric indicate better performance and lower energy
consumption.
This type of derating specifically addresses performance degradation over time due to factors like, due to factors
such as fouling, corrosion, equipment aging, increased wear and tear and changes in refrigerant properties.
Manufacturers provide a fouling factor like 0.018 to predict chiller performance, which impacts the selection
process by ensuring the chiller is adequately sized for real-world conditions. This factor helps in determining the
cooling capacity loss due to fouling over time, which can lead to a significant reduction in effective capacity after 5
to 10 years if not addressed—potentially dropping from 100 TR to 85 TR. This factor is used to size the chiller
correctly and plan for regular cleaning and maintenance to keep it running efficiently.
Chiller approach is defined as the temperature difference between the evaporating refrigerant and the leaving water
(or air) at the evaporator or condenser. In a water-cooled system, it specifically refers to the difference between the
evaporating refrigerant temperature and the leaving chilled water temperature; in an air-cooled system, it's the
difference between the refrigerant and ambient air temperature.
Chiller approach Impact: Chiller approach temperature is a critical metric in assessing the efficiency and performance
of a chiller. A low approach indicates effective heat transfer, leading to better energy efficiency and lower
operational costs. Monitoring approach temperatures helps in early detection of issues like fouling, scaling, or
inadequate flow, enabling timely maintenance. Maintaining an optimal approach ensures efficient system design,
optimal chiller operation, and longer equipment life, while minimizing energy consumption. Typical evaporator
approach values range between 2°F to 6°F (1.1°C to 3.3°C), and condenser approach between 3°F to 7°F (1.7°C to
3.9°C).
Below are some additional considerations for chiller selection:
When assessing noise levels in chillers, check the manufacturer's decibel ratings for sound levels during operation,
aiming for around 60 dB for offices and below 55 dB for residential areas. Use standardized measurement
methods (e.g., ANSI/ASA S12.60) for consistency, and consider the chiller's installation location to minimize noise
transmission. To mitigate noise, select low-noise models, isolate vibrations with pads or mounts, and install
acoustic enclosures for sound absorption. Regular maintenance is crucial to prevent mechanical issues that can
lead to increased noise levels.
Shell and tube heat exchangers are widely used for efficient heat transfer, with fluids flowing through tubes and
the shell. They are available in different configurations like single-pass, multi-pass, and U-tube arrangements.
Proper support, like baffles and tube sheets, is crucial to prevent vibration and ensure stability during operation.
Testing methods, including hydrostatic tests (1.5 times the design pressure) and eddy current tests, verify the
integrity of the tubes and overall system.
The General allowable pressure drop across a chiller in the chilled water circuit is typically between 20 to 40 kPa
(approximately 3 to 6 psi).
In chiller design, selection, and installation, compliance with a comprehensive set of standards is crucial for
ensuring performance, safety, and regulatory adherence. These include ASHRAE 15, ASHRAE 23, ASHRAE 30, and
ASHRAE 34 for safety and testing; AHRI 550/590 for performance ratings; ISO 1940 and ISO 5151 for vibration
control, performance, and acoustics; ANSI B 31.5 for refrigeration piping; IEC 60335-2-40 for electrical safety; and
NFPA 70 and NFPA 90A for electrical and fire protection. Additionally, EPA Clean Air Act and EPA Section 608
ensure environmental compliance in refrigerant use and handling.