Batch View
Batch View
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this
equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated
with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and
diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this
manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in
a hazardous environment, which may lead to personal injury or death, property damage, or
economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal
injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a
hazard, and recognize the consequence
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to
alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert
people that surfaces may reach dangerous temperatures.
Important: Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, Rockwell Software, and Rockwell Automation ControlLogix, eProcedure, FactoryTalk, RSBizWare, RSBizWare BatchHistorian, RSBizWare Historian, RSBizWare MaterialTrack, and RSLinx are
trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Table of contents
Chapter 1
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 3
Table of contents
Chapter 2
Chapter 3
Chapter 4
Index
Legal Notices
6 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
Chapter 1
The FactoryTalk Batch View is used to initiate and execute FactoryTalk Batch
automation processing. The FactoryTalk Batch View secured objects are located in
the FactoryTalk Diagnostics and are modified using the FactoryTalk
Administration Console. A system administrator can customize the FactoryTalk
Batch View security to meet the needs of the facility. The FactoryTalk Batch View
is used in conjunction with a Human-Machine Interface (HMI).
See also
FactoryTalk Batch Security for the FactoryTalk Batch View is implemented using the FactoryTalk
Security product policy settings defined in the FactoryTalk Directory. The system
View security administrator must configure FactoryTalk Security prior to using the FactoryTalk
Batch View. Instructions for configuring security are in the FactoryTalk Batch
Administrator Guide.
Any FactoryTalk Security user with the appropriate permissions can log on or off
of the FactoryTalk Batch View. The FactoryTalk Batch View can be configured to
require user authentication each time a command is issued. Users can log on or off
of the FactoryTalk Batch View without stopping or exiting ANY application. The
FactoryTalk Batch View security can automatically log off the current user if the
FactoryTalk Batch View is inactive for a period of time. Commands sent to the
FactoryTalk Batch Server from the FactoryTalk Batch View are logged in the
electronic batch record along with the name of the user who initiated the
command.
See also
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 7
Chapter 1 FactoryTalk Batch View Overview
Configure security for To tighten security for a FactoryTalk Batch View window, remove the All Users
the FactoryTalk Batch group from the corresponding product policy and then add the necessary user
accounts.
View windows
To configure security for the FactoryTalk Batch View windows:
2. Expand System > Policies > Product Policies > Batch > BatchView &
ActiveX.
4. Select the policy setting you want to configure and then click the
corresponding browse button.
• Add a user account or user group by clicking Add. This option displays
the Select User and Computer dialog box.
See also
Security for Configure FactoryTalk Security to require user confirmation for batch commands
FactoryTalk Batch and phase commands. A command that has the confirm feature enabled does not
execute until the user account is validated in the Log on to Confirm User dialog
commands box.
8 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View Overview Chapter 1
To enable the Confirm feature, configure the FactoryTalk Batch product policy
for the command and then set the associated <Command> Confirm policy setting
to True. These policy settings are defined in FactoryTalk Directory for each
command button within FactoryTalk Batch View and every phase command
issued from the Phase Control window.
The <Command> Confirm policy settings are found in the following locations:
See also
Configure security for To allow only specified users to issue commands against a batch or a phase, add
FactoryTalk Batch the appropriate users or user groups to the Command or Phase Command policy
commands setting. Then remove or restrict the All Users group.
2. Expand System > Policies > Product Policies > Batch > BatchView &
ActiveX.
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 9
Chapter 1 FactoryTalk Batch View Overview
4. Select the policy setting to configure and then select the corresponding
browse button.
• Select a user, user group, computer, or computer group and then select
OK.
• Select Create New to create and then add a new user, user group,
computer, or computer group.
See also
10 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View Overview Chapter 1
Enable the FactoryTalk If specific users and/or groups are assigned to a batch command or phase
Batch View confirm command and the corresponding Confirm policy setting is enabled, only the
settings specified users are allowed to issue the command. All commands in FactoryTalk
Batch View have a command confirmation option. If confirm is enabled for a
command, that command is not issued until a user with the appropriate
permissions is validated using the Log on to Confirm User dialog box. Users
validated in the Log on to Confirm User dialog box are not logged in to the
FactoryTalk Batch View.
2. Expand System > Policies > Product Policies > Batch > BatchView &
ActiveX.
5. Select True to require a user log on each time the command button is
clicked. Select False if no log on is required.
6. Click OK.
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 11
Chapter 1 FactoryTalk Batch View Overview
Tip: Restart all FactoryTalk Batch components to update changes made in the
FactoryTalk Directory.
See also
Set the automatic Configure a specified period of inactivity before logging off a user using
logoff time period FactoryTalk Batch View security. FactoryTalk Batch View uses the Windows
screen saver activation to send a log off message. If the Batch List window of
FactoryTalk Batch View is the top window in your system when the screen saver
activates, FactoryTalk Batch View logs off the current user, the status bar displays
No authenticated User, and FactoryTalk Batch View continues to run.
3. From the Display Properties dialog box, click the Screen Saver tab.
4. Select a screen saver from the list, and then enter the automatic log off time
period in the Wait box.
See also
Change the logged-on Configure your human-machine interface (HMI) to notify FactoryTalk Batch
user with your HMI View to change the logged on user. The HMI sends a user name and password so
the FactoryTalk Batch View can attempt to log on the specified user.
A Component Object Model (COM) component was created to log on and off of
FactoryTalk Batch either programmatically, or by using an HMI. The following
example, created in Visual Basic, is one way to implement external log-ons using
the COM component.
12 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View Overview Chapter 1
2. Create a Visual Basic form that allows a user to enter a user name and a
password.
3. Add two Command buttons, one for user log-ons and another to log off.
Here is an example of a Visual Basic form:
4. Create a new COM object and add code to support the log on functionality.
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 13
Chapter 1 FactoryTalk Batch View Overview
6. Run the executable to log users on and off of FactoryTalk Batch View.
See also
External security Use an external security device, such as a retinal scanner, with the FactoryTalk
devices Batch View. You must use a .dll with a function that collects the user name and
password. When the FactoryTalk Batch View security prompts the user for user
name and password, your .dll is called. Your function is expected to copy the user
name to <USERNAME> and the password to <PASSWORD>. The size limit on
each of these is 1023 bytes.
The following is an example of a function that would return the user name and
password to the FactoryTalk Batch View:
14 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View Overview Chapter 1
Any value other than 0 is an error and an entry is recorded in the Batchvew.log file.
If the .dll fails to load, the function is not found in the .dll, or the function causes
an exception, the log on mechanism is disabled. The standard logon dialog box
must then be used.
The FactoryTalk Batch Equipment Editor and FactoryTalk Batch Recipe Editor
also support an external security device. The product policies used to configure an
external security device for the FactoryTalk Batch Equipment Editor and
FactoryTalk Batch Recipe Editor are created in the following FactoryTalk Local
Directory locations.
• System > Policies > Product Policies > Batch > Equipment Editor >
Configuration > Options - External Login
• System > Policies > Product Policies > Batch > Recipe Editor >
Configuration > Options - External Login
See also
Enable an external security Use the FactoryTalk Administration Console to modify the required security
device policy settings for enabling an external security device. These policy settings are
located in the FactoryTalk Local Directory.
2. Expand System > Policies > Product Policies > Batch > BatchView &
ActiveX > Configuration.
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 15
Chapter 1 FactoryTalk Batch View Overview
Tip: Restart all FactoryTalk Batch components to update changes made in the
FactoryTalk Directory.
See also
Open FactoryTalk The FactoryTalk Batch View Single-SignOn product policy setting created in the
FactoryTalk Local Directory is used in conjunction with the FactoryTalk Use
Batch View single sign-on System policy setting to enable or disable the FactoryTalk single
sign-on feature. Use the FactoryTalk single sign-on feature to log on just once, per
directory, on a given computer.
Opening the FactoryTalk Batch View when the Batch View Single-SignOn
product policy setting is Enabled and the FactoryTalk Use single sign-on system
policy setting is True, the following scenarios are possible:
16 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View Overview Chapter 1
Opening the FactoryTalk Batch View when the Batch View Single-SignOn
product policy setting is Disabled or when the FactoryTalk Use single sign-on
system policy setting is False, the following scenarios are possible.
See also
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 17
Chapter 1 FactoryTalk Batch View Overview
Log into FactoryTalk Log into the FactoryTalk Batch View using the following steps.
Batch View Tip: If the Display Configuration dialog box opens, it means
that the Batch Server has been configured to allow
multiple instances of the Batch View. Select the desired
Batch View configuration file, and then click Start. (See
Running Multiple Instances of FactoryTalk Batch View in
the FactoryTalk Batch Administrator Guide for
information.)
1. With the FactoryTalk Batch Server active (and the FactoryTalk Batch
Phase Simulator, if running in Demo mode), click Start>All
Programs>Rockwell Software>FactoryTalk Batch Suite >FactoryTalk
Batch, and select View.
2. If the Log on to FactoryTalk dialog box opens, type your user name in the
Name box and your password in the Password box. Click OK. The
authenticated user displays in the FactoryTalk Batch View status bar.
4. Click the Login button to open the Log on to FactoryTalk dialog box.
5. To close the Log on to FactoryTalk dialog box without logging on, click
the Cancel button.
See also
18 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View Overview Chapter 1
FactoryTalk Batch Use the FactoryTalk Batch View to initiate and control the batch process. View a
graphical representation of a running batch and its associated data. The
View interface FactoryTalk Batch View can be resized or minimized. To disable the resize and
minimize features, use the System Configuration and Defaults dialog box.
See also
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 19
Chapter 1 FactoryTalk Batch View Overview
FactoryTalk Batch The FactoryTalk Batch View has ten different windows for viewing batch process
View toolbar and data. These windows can be accessed using the first ten buttons on the
toolbar. As you move your cursor over any of these buttons, an information tip
displays the button name.
Event Journal Open and view event data for batches. All
commands sent to the FactoryTalk Batch
Server are recorded in the electronic batch
record. This includes the user name who
initiated the command.
Unacknowledged View and respond to a list of prompts that
Prompts require operator input.
The FactoryTalk Batch View toolbar also contains buttons that access
configuration information, online help, HMI, security, and that exits the
FactoryTalk Batch View.
20 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View Overview Chapter 1
See also
FactoryTalk Batch The buttons along the right side of the FactoryTalk Batch View windows are
View command command buttons. They represent the actions that can be performed. When
changing windows in FactoryTalk Batch View, the available command buttons
buttons change based on the selected view.
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 21
Chapter 1 FactoryTalk Batch View Overview
See also
FactoryTalk Batch The bottom line of the FactoryTalk Batch View displays status information
View status bar regarding the data server and the Material Server. The ID of the currently selected
batch is displayed to the right of the Material Server status. The current user name
and system time are also located on the status bar.
See also
Communication The Data Server Status indicator that is located at the bottom of each FactoryTalk
Batch View window to the right of the time display indicates the communication
status for the status of the FactoryTalk Batch Server with the FactoryTalk Batch View, its data
FactoryTalk Batch server(s), and the control system.
Server and data
servers
22 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View Overview Chapter 1
The Data Server Status indicator displays the most severe conversation status of all
the data servers.
See also
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 23
Chapter 1 FactoryTalk Batch View Overview
View the Conversation The Conversation Status of Data Servers displays an overview of the current
Status of Data Servers conversation status between all OPC data servers communicating with the
FactoryTalk Batch Server. The dialog box cannot be opened if conversation status
dialog box between the FactoryTalk Batch View and the server has been lost. If the
FactoryTalk Batch View loses conversation with the server while the
Conversation Status of Data Servers dialog box is open, the dialog box closes.
See also
Communication status for the FactoryTalk Batch Server and data servers
on page 22
Communication In order to run material-based recipes, the FactoryTalk Batch Server and the
FactoryTalk Batch Material Server must communicate with each other. In the
status for the FactoryTalk Batch Equipment Editor, set up how the system handles batches if
FactoryTalk Batch the Batch Server loses communication with the Material Server. You can either set
Server and Material the Batch Server to fail and hold execution of material-based recipes. Or, you can
switch to manual processing, which prompts the operator to make binding
Server decisions until communication with the Material Server is restored. See the
FactoryTalk Batch Equipment Editor User Guide for more information on setting
the Material Server communication options.
The FactoryTalk Batch View displays the communication status between the
Material Server and the FactoryTalk Batch Server. The Material Server Status
indicator is located at the bottom of each View window to the right of the Data
Server Status indicator.
24 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View Overview Chapter 1
See also
Communication status for the FactoryTalk Batch server and data servers on
page 22
Process batches If the FactoryTalk Batch Server is configured to Failure and Hold, you cannot
without the Material continue running batches or add new batches to the Batch List view until
communication with the Material server is restored.
Server
If the FactoryTalk Batch Server is configured to Switch to Manual, you can
continue processing batches and add batches to the Batch List view without input
from the Material server. All material-based decisions or selections that are made
by the operator without communications with the Material server are reported in
the batch event journal as Loss of Material server and Loss of Material Tracking
events. When the material database becomes available, you must manually
reconcile the event journal with the material journal and update the material
database with the Amount, Lot, and Label information for material inventory.
See also
Batch creation when the When there is no communication with the Material server, the Material Server
Material server is not Not in Use warning is displayed in the Batch Creation dialog box for all recipes.
communicating You can create the batch or cancel and create the batch at another time when the
Material server is available.
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 25
Chapter 1 FactoryTalk Batch View Overview
If the failure to the Material server occurs when the Batch Creation dialog
box is open, the warning message does not show.
If you add a material class-based recipe to the batch list when the Material server is
unavailable, the materials will not be filtered by class when the recipe is run.
Instead, all materials in the material enumeration are shown.
If the failure to the Material server occurs when the Material Value
Selection dialog box is open, the warning message does not show.
See also
26 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View Overview Chapter 1
Prompt to bind unit The Data Not Supplied by Material Server warning displays in the Prompt to
requirement Bind Unit Requirement dialog box when there is no communication with the
Material server.
The dialog box displays data supplied by the area model in place of the data
normally supplied by the Material server. When the Material server is not
available, the first available binding is serviced as though it was prompt binding.
If the failure to the Material server occurs when the Prompt to Bind Unit
Requirement dialog box is open, the warning message does not show.
See also
Manual unit binding The Material Server Not in Use warning displays in the Manual Bind of Step
dialog box when there is no communication with the Material server.
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 27
Chapter 1 FactoryTalk Batch View Overview
The dialog box displays data supplied by the area model in place of the data
normally supplied by the Material server.
If the failure to the Material Server occurs when the Manual Bind of Step
dialog box is open, the warning message does not show.
See also
Prompt to bind a material For prompt binding, the list of container/phase pairs generated from the area
phase step model is substituted for the list that would have been produced if the Material
server were available. When the Material server is unavailable, material additions
may not be filtered by lot or label specification.
If you do not know which phase to select, you can look up some material
information on the computer where the Material server is installed and running.
If the failure to the Material server occurs when the Prompt to Bind a Material
Phase Step dialog box is open, the warning message does not show.
See also
28 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View Overview Chapter 1
Look up material If you do not know which phase to select when there is no communication with
information the Material server, you can look up material information on the computer where
the Material server is installed and running.
4. Check the Materials, Containers, and Inventory tabs and compare the
values to the Unit, Material, and Amount to Charge to determine which
phase can best accommodate the material phase step.
If the failure to the Material server occurs when the Prompt to Bind a Material
Phase Step dialog box is open, the warning message does not show.
See also
Phase control The Material Server Not in Use warning is displayed when there is no
communication with the Material server.
For material binding in manual phase control, the list of container-phase pairs
generated from the area model is substituted for the list that would have been
produced if the Material server were available. The list is filtered by the container
enumeration. All the data displayed is contained in the area model and the recipe.
The Label and Lot fields can only be supplied by the Material server and therefore
is blank when there is no communication with the Material server.
If the failure to the Material server occurs when the Phase Control dialog
box is open, the warning message does not show.
See also
System Configuration and Defaults dialog box - Phase Control tab on page
53
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 29
Chapter 1 FactoryTalk Batch View Overview
Reestablish Communication with the Material server is reestablished depending upon the
communications with FactoryTalk Batch Server configuration.
the Material server After communication with the Material server has been restored, any material-
based steps that were in a HELD state must finish executing to the COMPLETE
state before further processing can occur. You must acknowledge any
unacknowledged prompts before the batch will continue to run.
All Loss of Material Tracking and Loss of Material Server events indicate material
steps that took place without Material server communication. Use this
information to manually update the Amount, Lot, and Label information for the
material inventory in the material database. (See the FactoryTalk Batch Material
Editor User Guide for more information.)
See also
Held batches If the FactoryTalk Batch Server is configured to Failure and Hold, the server
automatically resumes communication with the material server when it becomes
available. The material server status indicator on the right of the status bar changes
to green and displays MT-G. Batches that were HELD continue to run.
See also
Reestablish If the FactoryTalk Batch Server is configured to Switch to Manual, you must
communication with the reestablish communication with the Material server when it becomes available
Material Server on manual again. When the Material Status indicator changes to Suspect (MT-S), the
batches Material server is available and you can attempt reconnection.
3. Manually reconcile the batch event journal with the material database.
30 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View Overview Chapter 1
See also
System The System Configuration and Defaults dialog box opens to the tab that
corresponds to the active FactoryTalk Batch View window. On each tab you can
Configuration and customize a specific portion of the FactoryTalk Batch View.
Defaults dialog box
Each FactoryTalk Batch View window can be customized to suit the needs of a
specific computer. You can specify the columns to be displayed, the column size,
and the row size. You can sort and filter on one field in certain windows, and set
the font for each View window. A system administrator can use the password
protection option on this dialog box to limit the information that is shown.
Password protection is defined in the FactoryTalk Directory using the
FactoryTalk Administration Console.
See also
Modify the Use the following steps as a general guideline for modifying the configuration of
configuration of the the FactoryTalk Batch View. Not all sections are available for all tabs.
FactoryTalk Batch To modify the configuration of the FactoryTalk Batch View:
View
1. Click the Configuration and Defaults button.
3. Select the tab for the portion of the FactoryTalk Batch View that you want
to customize.
4. Click OK to save any changes and close the System Configuration and
Defaults dialog box. Or, click Cancel to exit without saving any changes.
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 31
Chapter 1 FactoryTalk Batch View Overview
See also
System Configuration and In the System Configuration and Defaults dialog box, use the General tab to
Defaults dialog box - customize the configuration of the FactoryTalk Batch View.
General tab
You can specify the following:
Name Description
Human-Machine Interface Type the Title to be used for the HMI window. If you
(HMI) and Cross want to use a custom Go To HMI toolbar button, you
Invocation must specify the path and file name of the bitmap. The
bitmap should be 42 x 42 pixels.
If you select Enable Cross Invocation, in the
Invocation ProgID box, enter the identity of the
Automation Server. All information concerning the HMI
is disabled.
Equipment Bitmap Paths Type the location of the process cell and unit bitmaps.
Server Communications The FactoryTalk Batch Server communication time-out,
in seconds.
BatchID Editing Select to allow editing of the Batch ID. If you have
written a custom program to automatically generate
Batch IDs, you should disable BatchID Editing.
Important: Batch IDs must be unique or the
Arbitration view will not update
correctly.
Split Bar Size The size of the splitter bars used in the Procedure as
SFC view, Procedure as Table view, Event Journal
view and Phase Control view. Type the thickness, in
pixels, for the vertical and horizontal splitter bars.
Screen Size (%) Select the Allow Resize check box to allow the
FactoryTalk Batch View window to be resized.
Select the Allow Minimize check box to allow the
FactoryTalk Batch View window to be minimized.
Type the horizontal and vertical percentage of the
screen that is used by the FactoryTalk Batch View. The
FactoryTalk Batch View window occupies the specified
percentage of the screen, with its origin being in the
upper-left corner of the screen. You are able to move
the FactoryTalk Batch View window around on the
desktop.
Status Bar Font Select the font, size, and style to use for the status bar.
32 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View Overview Chapter 1
Tip: To connect the FactoryTalk Batch View to a server computer other than
that displayed in the Server Communications section, you must use the
Registry Editor to edit the .NET registry key. (See the FactoryTalk Batch
Administrator Guide for information on editing the .NET key.)
See also
Configure the General tab Customize the configuration of FactoryTalk Batch View using the General tab.
1. Type the path and file name for the HMI application or select the Enable
Cross Invocation box.
3. Type the thickness, in pixels, for the vertical and horizontal splitter bars.
4. Select the Allow Resize check box to allow the FactoryTalk Batch View
window to be resized.
5. Select the Allow Minimize check box to allow the FactoryTalk Batch View
window to be minimized.
6. Type the horizontal and vertical percentage of the screen that is used by the
FactoryTalk Batch View. The FactoryTalk Batch View window occupies
the specified percentage of the screen, with its origin being in the upper-left
corner of the screen. You are able to move the FactoryTalk Batch View
window around on the desktop.
8. Click OK to save the changes. (Some of the changes may not be applied
until you exit and reopen the FactoryTalk Batch View.) Or, click Cancel to
abort the changes.
See also
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 33
Chapter 1 FactoryTalk Batch View Overview
System Configuration and The Signatures tab in the System Configuration and Defaults dialog box
Defaults dialog box - corresponds to the Signature List view. In this tab, specify the columns to be
Signatures tab displayed, the column header text, the column width, filter specifications for a
specific column, the field and order in which the signatures are sorted, and the
font to use.
See also
Configure the Signatures tab Customize the configuration of the Signature List window using the Signatures
tab.
6. In the Filtering area, select a specific column and the column filter.
7. In the Sorting area, select a specific column to sort the Signature List
window.
34 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View Overview Chapter 1
8. In the Table Font area, click Select Font to customize the font, font size,
and font style.
11. Click OK to save the changes. (Some of the changes may not be applied
until you exit and reopen the FactoryTalk Batch View.) Or, click Cancel to
abort the changes.
See also
System Configuration and In the System Configuration and Defaults dialog box, use the Commands tab
Defaults dialog box - to customize the configuration of the commands that need confirmation and the
Commands tab font used for the status bar.
See also
Configure the Commands tab Customize which commands require confirmation using the Commands tab.
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 35
Chapter 1 FactoryTalk Batch View Overview
5. Select the check box for each of the commands that require a confirmation
prompt.
When a command is enabled, you are prompted to confirm that this is the
correct action to take.
6. (optional) Click the Select Font button to change the font used in the
status bar.
See also
System Configuration and The Batch List tab in the System Configuration and Defaults dialog box
Defaults dialog box - Batch corresponds to the Batch List view. In this dialog box, you specify which columns
List tab to view, the column header text, the column width, on which column to filter and
sort, the row height, and which font to use.
See also
Configure the Batch List tab Customize the configuration of the Batch List window using the Batch List tab.
6. In the Filtering area, select a specific column and the column filter.
7. In the Sorting area, select a specific column to sort the Batch List window.
8. In the Table Row Height box, enter the height of the table rows displayed
in the Batch List window.
9. In the Table Font area, click Select Font to customize the font, font size,
and font style.
See also
System Configuration and Defaults dialog box - Batch List tab on page 36
System Configuration and The Hierarchical Step List tab in the System Configuration and Defaults
Defaults dialog box - dialog box corresponds to the Procedural Hierarchy area in the Procedure as
Hierarchical Step List tab SFC and Procedure as Table views. In this dialog box, you specify which columns
to view, the column header text, the column width, the row height, and the font
to use.
See also
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 37
Chapter 1 FactoryTalk Batch View Overview
Configure the Hierarchical Customize the configuration of the Procedural Hierarchy area in the Procedure
Step List tab as SFC and Procedure as Table windows using the Hierarchical Step List tab.
6. In the Step List Font area, click Select Font to customize the font, font
size, and font style.
7. In the Table Row Height box, enter the height of the table rows displayed
in the Procedure as SFC and Procedure as Table windows.
9. Click OK.
See also
System Configuration and Defaults dialog box - Hierarchical Step List tab
on page 37
38 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View Overview Chapter 1
System Configuration and The SFC View tab in the System Configuration and Defaults dialog box
Defaults dialog box - SFC corresponds to the SFC area in the Procedure as SFC view. In this dialog box,
View tab you specify if the transition expressions show, the width of the lines used in the
SFC, and the font to use.
See also
Configure the SFC View tab Customize the configuration of the Procedure as SFC window using the SFC
View tab.
5. In the SFC Font area, click Select Font to customize the font, font size, and
font style.
b. Enter a value for the width of the lines used in the SFC.
8. Click OK.
See also
System Configuration and Defaults dialog box - SFC View tab on page 38
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 39
Chapter 1 FactoryTalk Batch View Overview
System Configuration and The Procedure Prompts tab in the System Configuration and Defaults dialog
Defaults dialog box - box corresponds to the Prompts tab in the Auxiliary Index view in the Procedure
Procedure Prompts tab as SFC view and Procedure as Table view. In this dialog box, you specify which
columns to view, the column header text, the column width, the priority and
order in which the prompts are sorted, the row height, and the font to use.
See also
Configure the Procedure Customize the Prompts tab in the Auxiliary Index view of the Procedure as
Prompts tab SFC and Procedure as Table windows using the Procedure Prompts tab.
6. In the Sorting Priority area, move the columns up and down based on
preferred priority order.
7. In the Sorting Order area, select Ascending or Descending for the sort
order.
8. In the Row Height box, enter the height of the rows displayed in the
Prompts tab in the Auxiliary Index view of the Procedure as SFC and
Procedure as Table windows.
9. In the Table Font area, click Select Font to customize the font, font size,
and font style.
40 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View Overview Chapter 1
11. Click OK to save the changes. (Some of the changes may not be applied
until you exit and reopen the FactoryTalk Batch View.) Or, click Cancel to
abort the changes.
See also
System Configuration and The Procedure Parameters tab in the System Configuration and Defaults
Defaults dialog box - dialog box corresponds to the Parameters tab in the Auxiliary Index view in the
Procedure Parameters tab Procedure as SFC view and Procedure as Table view. In this dialog box, you
specify which columns to view, the column header text, the column width, the
priority and order in which the parameters are sorted, the row height, and the font
to use.
See also
Configure the Procedure Customize the Parameters tab in the Auxiliary Index view of the Procedure as
Parameters tab SFC and Procedure as Table views using the Procedure Parameters tab.
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 41
Chapter 1 FactoryTalk Batch View Overview
6. In the Sorting Priority area, move the columns up and down based on
preferred priority order.
7. In the Sorting Order area, select Ascending or Descending for the sort
order.
8. In the Table Row Height box, enter the height of the table rows displayed
in the Parameters tab in the Auxiliary Index view of the Procedure as
SFC and Procedure as Table windows.
9. In the Table Font area, click Select Font to customize the font, font size,
and font style.
11. Click OK to save the changes. (Some of the changes may not be applied
until you exit and reopen the FactoryTalk Batch View.) Or, click Cancel to
abort the changes.
See also
42 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View Overview Chapter 1
System Configuration and The Procedure Reports tab in the System Configuration and Defaults dialog
Defaults dialog box - box corresponds to the Reports tab in the Auxiliary Index view in the Procedure
Procedure Reports tab as SFC view and Procedure as Table view. In this dialog box, you specify which
columns to view, the column header text, the column width, the priority and
order in which the reports are sorted, the row height, and the font to use.
See also
Configure the Procedure Customize the Reports tab in the Auxiliary Index view of the Procedure as SFC
Reports tab and Procedure as Table views using the Procedure Reports tab.
6. In the Sorting Priority area, move the columns up and down based on
preferred priority order.
7. In the Sorting Order area, select Ascending or Descending for the sort
order.
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 43
Chapter 1 FactoryTalk Batch View Overview
8. In the Table Row Height box, enter the height of the table rows displayed
in the Reports tab in the Auxiliary Index view of the Procedure as SFC
and Procedure as Table windows.
9. In the Table Font area, click Select Font to customize the font, font size,
and font style.
11. Click OK to save the changes. (Some of the changes may not be applied
until you exit and reopen the FactoryTalk Batch View.) Or, click Cancel to
abort the changes.
See also
System Configuration and The Procedure Binding tab in the System Configuration and Defaults dialog
Defaults dialog box - box corresponds to the Binding tab in the Auxiliary Index view in the Procedure
Procedure Binding tab as SFC view and Procedure as Table view. In this dialog box, you specify the
column header text, the column width, the sort order for the Unit Requirements,
Binding Requirements, and Binding Preferences areas, and the font to use. You
can also turn off the Binding Requirements and Binding Preferences areas if
dynamic unit allocation is not in use.
See also
44 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View Overview Chapter 1
Configure the Procedure Customize the Binding tab in the Auxiliary Index view of the Procedure as SFC
Binding tab and Procedure as Table views using the Procedure Binding tab.
5. In the Column Display area, enter the column header text and column
width in pixels.
6. In the Sorting Order area, select Ascending or Descending for the sort
order.
7. In the Row Height box, enter the height of the rows displayed in the
Binding tab in the Auxiliary Index view of the Procedure as SFC and
Procedure as Table windows.
8. (optional) Select Disable Binding Req and Pref screens to disable the
binding requirements and preferences screens if dynamic unit allocation is
not in use.
9. In the Table Font area, click Select Font to customize the font, font size,
and font style.
11. Click OK to save the changes. (Some of the changes may not be applied
until you exit and reopen the FactoryTalk Batch View.) Or, click Cancel to
abort the changes.
See also
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 45
Chapter 1 FactoryTalk Batch View Overview
System Configuration and The Procedures Table tab in the System Configuration and Defaults dialog
Defaults dialog box - box corresponds to the Procedures Table displayed in the Recipe Table area in
Procedures Table tab the Procedure as Table view. In this dialog box, you specify which columns to
view, the column header text, the column width, the number of parameters to
view, the row height, and the font to use.
See also
Configure the Procedures Customize the Procedures Table in the Recipe Table area of the Procedure as
Table tab Table view using the Procedures Table tab.
6. In the Table Row Height box, enter the height of the table rows displayed.
7. In the Table Font area, click Select Font to customize the font, font size,
and font style.
9. Click OK to save the changes. (Some of the changes may not be applied
until you exit and reopen the FactoryTalk Batch View.) Or, click Cancel to
abort the changes.
46 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View Overview Chapter 1
See also
System Configuration and The Unit Procedures Table tab in the System Configuration and Defaults
Defaults dialog box - Unit dialog box corresponds to the Unit Procedures Table displayed in the Recipe
Procedures Table tab Table area in the Procedure as Table view. In this dialog box, you specify which
columns to view, the column header text, the column width, the number of
parameters to view, the row height, and the font to use.
See also
Configure the Unit Customize the Unit Procedures Table in the Recipe Table area of the
Procedures Table tab Procedure as Table view using the Unit Procedures Table tab.
6. In the Table Row Height box, enter the height of the table rows displayed.
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 47
Chapter 1 FactoryTalk Batch View Overview
7. In the Table Font area, click Select Font to customize the font, font size,
and font style.
9. Click OK to save the changes. (Some of the changes may not be applied
until you exit and reopen the FactoryTalk Batch View.) Or, click Cancel to
abort the changes.
See also
System Configuration and Defaults dialog box - Unit Procedures Table tab
on page 47
System Configuration and The Operations Table tab in the System Configuration and Defaults dialog
Defaults dialog box - box corresponds to the Operations Table displayed in the Recipe Table area in the
Operations Table tab Procedure as Table view. In this dialog box, you specify which columns to view,
the column header text, the column width, the number of parameters and reports
to view, along with the height and width of the parameters and reports columns,
the table row height, and the font to use.
See also
Configure the Operations Customize the Operations Table in the Recipe Table area of the Procedure as
Table tab Table view using the Operations Table tab.
6. In the Column Display and Counts area, select the specific columns to
display.
7. In the Table Row Height box, enter the height of the table rows displayed.
8. In the Table Font area, click Select Font to customize the font, font size,
and font style.
10. Click OK to save the changes. (Some of the changes may not be applied
until you exit and reopen the FactoryTalk Batch View.) Or, click Cancel to
abort the changes.
See also
System Configuration and The Journal tab in the System Configuration and Defaults dialog box
Defaults dialog box - corresponds to the Event Journal view. In this dialog box, you specify which
Journal tab columns to view, the column header text, the column width, filter specifications
for up to three columns, the row height, and the font to use.
See also
Configure the Journal tab Customize the configuration of the Event Journal view using the Journal tab.
5. In the Column Display area, select the specific columns to show in the
Event Journal view.
6. In the Filtering area, select a specific column and the column filter for three
columns.
7. In the Table Font area, click Select Font to customize the font, font size,
and font style.
9. Click OK.
See also
System Configuration and The Unacknowledged Prompts tab in the System Configuration and Defaults
Defaults dialog box - dialog box corresponds to the Unacknowledged Prompts view. In this dialog box,
Unacknowledged Prompts you specify which columns to view, the column header text, the column width,
tab filter specifications for a specific column, the field and order in which the prompts
are sorted, the row height, and the font to use.
See also
50 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View Overview Chapter 1
Configure the Customize the configuration of the Unacknowledged Prompts view using the
Unacknowledged Prompts Unacknowledged Prompts tab.
tab
To configure the Unacknowledged Prompts tab:
5. In the Column Display area, select the specific columns to display in the
Unacknowledged Prompts view.
6. In the Filtering area, select a specific column and the column filter for three
columns.
7. In the Sorting area, select a specific column to sort on and select Ascending
or Descending for the sort order.
8. In the Table Row Height box, enter the height of the table rows displayed.
9. In the Table Font area, click Select Font to customize the font, font size,
and font style.
See also
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 51
Chapter 1 FactoryTalk Batch View Overview
System Configuration and The Alarm Summary tab in the System Configuration and Defaults dialog box
Defaults dialog box - Alarm corresponds to the Alarm Summary view. In this dialog box, you specify which
Summary tab columns to view, the column header text, the column width, filter specifications
for a specific column, the field and order in which the alarms are sorted, the row
height, and the font to use.
See also
Configure the Alarm Customize the configuration of the Alarm Summary view using the Alarm
Summary tab Summary tab.
5. In the Column Display area, select the specific columns to display in the
Unacknowledged Prompts view.
6. In the Filtering area, select a specific column and the column filter for three
columns.
7. In the Sorting area, select a specific column to sort on and select Ascending
or Descending for the sort order.
8. In the Table Row Height box, enter the height of the table rows displayed.
9. In the Table Font area, click Select Font to customize the font, font size,
and font style.
52 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View Overview Chapter 1
See also
System Configuration and The Phase Control tab in the System Configuration and Defaults dialog box
Defaults dialog box - corresponds to the Phase Control view. In this dialog box, you specify which font
Phase Control tab to use for the following:
• Equipment View
• Phase State
• Phase Messages
• Phase Parameters Listbox
• Phase Name
Also use this dialog box to determine whether to enable or disable the Obtain
[Batch ID] From Unit and Allow [Batch ID] Override options (not to be
confused with Auto Batch ID options).
See also
Configure the Phase Control Customize the configuration of the Phase Control view using the Phase Control
tab tab.
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 53
Chapter 1 FactoryTalk Batch View Overview
5. In the Equipment View Font area, click Select Font to customize the font,
font size, and font style.
6. In the Phase State Font area, click Select Font to customize the font, font
size, and font style.
7. In the Phase Messages Font area, click Select Font to customize the font,
font size, and font style.
8. In the Phase Parameters Listbox Font area, click Select Font to customize
the font, font size, and font style.
9. In the Phase Name Font area, click Select Font to customize the font, font
size, and font style.
10. In the Batch ID options area, enable or disable the following options:
a. Select Obtain From Unit to obtain the Batch ID from the unit.
See also
System Configuration and Defaults dialog box - Phase Control tab on page
53
System Configuration and The Phase Summary tab in the System Configuration and Defaults dialog box
Defaults dialog box - corresponds to the Phase Summary view. In this dialog box, you specify which
Phase Summary tab columns to view, the column header text, the column width, filter specifications
for a specific column, the field and order in which the phases are sorted, the row
height, and the font to use.
See also
54 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View Overview Chapter 1
Configure the Phase Customize the configuration of the Phase Summary view using the Phase
Summary tab Summary tab.
5. In the Column Display area, select the specific columns to display in the
Unacknowledged Prompts view.
6. In the Filtering area, select a specific column and the column filter.
7. In the Sorting area, select a specific column to sort on and select Ascending
or Descending for the sort order.
8. In the Table Row Height box, enter the height of the table rows displayed.
9. In the Table Font area, click Select Font to customize the font, font size,
and font style.
See also
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 55
Chapter 1 FactoryTalk Batch View Overview
Column Display area The Column Display area is included in the following tabs:
Several of the tabs also have filtering and sorting capabilities in the Column
Display area.
See also
Configure column displays in Specify how many columns display, the column header text, the column width,
the System Configuration filter specifications, sorting order, row height, and the font to use in the Column
and Defaults dialog box tabs Display area. Options are not available in all tabs.
1. Select the Visible? check boxes to display the columns. Clear the check
boxes for those you do not want to be shown.
56 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View Overview Chapter 1
For each column, you can change the text for the column header and the
width of the column.
3. Rows of data are sorted according to the field(s) selected in the Sorting area.
Sorting does not change the order of the columns. Specify sort priority by
selecting an item from the Column list.
6. Make any required row height changes by modifying the Table Row
Height value.
See also
Change the selected font You can change the font used in the status bar. The Select Font button that opens
in the status bar the Font dialog box is included on all tabs in the System Configuration and
Defaults dialog box.
2. Select the desired font options and click OK to close the Font dialog box.
See also
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 57
Chapter 1 FactoryTalk Batch View Overview
SFC Display area In the System Configuration and Defaults dialog box SFC View tab, you select
the Show Expressions check box to indicate that you want the transition
expressions to display in the SFC area of the Procedure as SFC view.
See also
Batch List view You can use the Batch List view to create and command a batch. Once a batch is
created it remains in the Batch List view until you remove it, or the FactoryTalk
Batch Server is re-started with a cold boot.
58 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View Overview Chapter 1
You can configure the information displayed in the Batch List view.
• Batch ID
• Recipe
• Description
• Start Time
• Elapsed Time
• State
• Mode
• Process Cell
• Unit
• Phase
• Failure
• Overrides
See also
Add a batch to the The Batch List view provides you with an overview of batches that are complete,
Batch List running and ready to run. Batches can be commanded from this window.
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 59
Chapter 1 FactoryTalk Batch View Overview
1. Click the Add Batch button. The Recipe List dialog box contains all
recipes that have been approved as Release Recipe to Production. The
dialog box allows you to specify the field on which to filter and sort.
2. Click Options.
5. From the Material list, select the material you want to use in this particular
batch, and then click Create.
Use extreme caution when operating without the Material Server. The
container/phase list is not filtered by the Material Server when it is
unavailable. Failure to select the correct container/phase pair could
result in a hazardous situation, depending on the material. (See Process
batches without the Material Server for more information.)
60 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View Overview Chapter 1
Tip: If the Batch ID box appears dimmed, you cannot change it. The option to
make the Batch ID editable is set by the system administrator in the
System Configuration and Defaults dialog box on the General tab.
7. In the Batch Scale box, type the percentage that you want to scale the
recipe, if the batch is to be run at a percentage other than 100%.
8. (optional) Select the Value cell in the Formula Values area and type a new
value if there are formula values that need to be assigned or modified.
• If this is a class-based recipe, and the recipe has a unit allocation method
of At Batch Creation or Operator Choice, you must specify the unit
allocation requirements.
• If the unit allocation method is At Batch Creation, you must choose a
specific unit from a list of the available units.
• If the unit allocation method is Operator Choice, then you can choose
from a list of available units, or you can select the Prompt or First
Available unit allocation methods.
9. Click the Bound Unit cell in the Unit Binding area to activate the Bound
Unit list. Make an appropriate selection.
Tip: If the recipe does not require that any formula values be assigned, the
Formula Values area contains a single blank row. Likewise, if the recipe
does not require any unit binding, the Unit Binding area contains a single
blank row.
10. Click Create to add the batch to the Batch List window. The Start Batch
command button is enabled.
Important: If control strategies are enabled for a recipe, changing the selected
control strategy after the recipe is added to the batch list could
corrupt that recipe.
See also
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 61
Chapter 1 FactoryTalk Batch View Overview
Remove a batch from To remove a batch from the Batch List view, selected the batch that is to be
the Batch List removed. The batch:
See also
Add a comment to an Comments can be added to an electronic batch record for a specific batch or all
electronic batch record batches that are currently in the batch list. An event type of Comment is placed in
the batch record of the specified batch(es). Comments are added from the Batch
List window.
1. In the Batch List view, select the batch that you want to add a comment.
4. (optional) If you want to add the comment to all batches that are currently
in the batch list, select the All Batches check box.
See also
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 63
Chapter 2
The FactoryTalk Batch View consists of ten different windows. The main View
interface and the Batch List view are described in the section titled FactoryTalk
Batch View Interface.
See also
Procedure as SFC The Procedure as SFC window displays the sequential function charts (SFCs) of
the currently selected batch. You can watch a batch execute its steps and
window transitions as well as review applicable recipe comments. You can also command a
batch from within the Procedure as SFC window by using the command
buttons.
The Procedure as SFC window consists of three distinct sections that are
separated by split bars: Procedural Hierarchy area, SFC area, and Auxiliary
Index View. You can click and drag any of the splitter bars to resize the individual
sections. If you drag the split bar that is between the SFC area and the command
buttons to the left, the Recipe Table area is revealed.
See also
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 65
Chapter 2 FactoryTalk Batch View windows
Commands available in Command a batch from within the Procedure as SFC window by using the
the Procedure as SFC command buttons.
window
• Start Step (if a batch is PAUSED, then the Start Step button becomes the
Resume Step button; if a batch is HELD, then the Start Step button
becomes the Restart Step button)
• Hold Step
• Stop Step
• Abort Step
• Timer Reset
• Timer Complete
• Manual
• Semi-Auto
• Auto
• Bind
• Active Step Change
• Clear All Failures
66 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View windows Chapter 2
See also
Procedural Hierarchy The Procedural Hierarchy area displays the details of the entire batch. Each
area procedural element can be displayed with each of the following:
• Current State
• Current Unit
• Current Mode
• Key Parameters
See also
SFC area The SFC area provides information regarding the running batch. At the top of the
area is the SFC area header. The header contains the view sizing buttons and
displays the level information.
The Recipe Level, Step Name, Step State, and Mode displays for the selected step.
The Binding Info or PAUSED text box also displays for the selected step. The
information varies depending on the current step state. If the selected step is in the
PAUSED mode, then PAUSED shows. Otherwise, the binding information for
the selected step shows. If the step is bound, the name of the unit to which it is
bound shows. If the step is not bound to a unit, then the unit requirement name
shows. Steps waiting for an operator prompt, or unit availability, display
BINDING in place of the unit name or unit requirement name.
The SFC structure is color coded, which allows you to easily recognize the state of
a specific step. The SFC structure displays the step name on the first line of the
step, regardless of the level being reviewed. Steps that represent unit procedures or
operations display their binding information on the second line in the step. If the
step is bound, then the name of the unit to which it is bound shows. If the step is
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 67
Chapter 2 FactoryTalk Batch View windows
not bound, then the unit requirement name shows. The step’s current state
displays in the lower left corner of the step, and the current mode displays in the
lower right corner of the step.
When a transition is paused, the SFC area displays PAUSED to the left of the
transition. When a step is acquiring resources, the SFC area displays
ACQUIRING to the left of the transition. To view the results of the transition
expression evaluation, double-click the transition to open the Transition
Expression dialog box. Transition expressions display to the right of the
transition.
See also
Auxiliary Index view The Auxiliary Index view displays information regarding the recipe, prompts,
parameters, reports, arbitration, and unit binding for the step that is selected in
the Procedural Hierarchy area or the Procedure as SFC view.
The Recipe Information tab displays general information about the selected
control recipe such as: name, product code, version, and procedure information.
The Prompts tab displays all prompts for the selected step of the control recipe.
You can also acknowledge prompts from this tab by double-clicking the prompt
item.
The Parameters tab displays the parameters for the selected step of the batch. If a
control strategy is enabled for the selected step, the control strategy displays at the
top of the list and all parameters assigned to that control strategy are displayed
below it. Parameters can be changed from this tab by double-clicking the
parameter item and typing a new value in the Update Parameter Value dialog
box. Deferred parameters can only be viewed. (See the FactoryTalk Batch Recipe
Editor User’s Guide for more information about deferred parameters.)
If a parameter expression was used to determine the value of the parameter, you
can display that information by double-clicking that parameter item to open the
View Expression Parameter Value dialog box.
The expression value cannot be changed. However, there may be times when you
must override the expression and assign a new value when responding to
extraordinary circumstances.
68 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View windows Chapter 2
The Reports tab displays the reports for the selected step of the batch. If a control
strategy is enabled for the selected step, only reports associated with that control
strategy show.
If an expression was used to determine the value of a report, you can display that
information by double-clicking a report item to open the View Expression
Report Value dialog box.
Tip: Once a batch is added to the Batch List view, control strategies
associated with the batch cannot be reassigned. However, parameter
and report values assigned to control strategies can be altered within
the pre-defined ranges.
The Binding tab displays the unit requirements for the step that is selected in the
Procedural Hierarchy area or the Procedure as SFC view. The information on
the Binding tab includes:
See also
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 69
Chapter 2 FactoryTalk Batch View windows
Binding Requirements and The Binding tab of the Auxiliary Index view is divided into 3 sections:
Preferences view
• Unit requirements
• Binding requirements
• Binding preferences
See also
Unit requirements Unit Requirements displays all the unit requirements for the batch procedure or
the unit requirement associated with the step that is selected in the Procedural
Hierarchy area or the Procedure as SFC view. At the unit procedure or operation
levels, there is only one unit requirement.
70 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View windows Chapter 2
See also
Binding requirements Binding Requirements is in the middle section of the Binding tab of the
Auxiliary Index view. When you select a step in the Procedure as SFC view or
Procedure as Table view for a batch procedure, the associated binding
requirements are displayed in the Binding Requirements area. If the recipe is a
unit procedure or operation, the binding requirements are displayed independent
of a step being selected.
Tip: When the Binding tab of the Auxiliary Index view is first
shown, the Binding Requirements associated with the
step selected in the Procedure as SFC view or
Procedure as Table view are shown. If no step is
selected, the Binding Requirements list is blank unless
the recipe is a Unit Procedure or Operation.
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 71
Chapter 2 FactoryTalk Batch View windows
See also
Binding requirement Double-clicking a binding requirement expression in the Auxiliary Index view
expression values opens the Binding Requirement Expression Values dialog box. In the dialog
box, you find a:
• List of units that are potential legal binding candidates for the unit
requirement.
• Value indicating whether those candidates currently meet the selected
binding requirement.
• List of the inputs used to evaluate the expression.
The content of the Expression is Boolean; it evaluates to Yes or No. This is the
only expression allowed for a binding requirement. The values dynamically update
as the inputs to the expression change.
See also
72 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View windows Chapter 2
Binding preferences On the Binding tab of the Auxiliary Index view, when you select a step in the
Procedure as SFC view or Procedure as Table view for a batch procedure, the
associated binding preferences are displayed in the Binding Preferences area. If
the recipe is a unit procedure or operation, the binding preferences are displayed
independent of a step being selected.
Tip: When the Binding tab of the Auxiliary Index view is first
shown, the Binding Preferences associated with the step
selected in the Procedure as SFC view or Procedure
as Table view are shown. If no step is selected, the
Binding Preferences list is blank unless the recipe is a
Unit Procedure or Operation.
See also
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 73
Chapter 2 FactoryTalk Batch View windows
Binding preferences The Binding Preference Expression Values dialog box displays the result of
expression values evaluating the binding preference expression for each of the units that are
potential legal binding candidates for the selected unit requirement. Double-click
a binding preference in the Auxiliary Index view opens the Binding Preference
Expression Values dialog box. In this dialog box, you find a:
• List of units that are potential legal binding candidates for the unit
requirement.
• Value indicating the evaluation of the selected binding preference
expression for that unit.
• List of the inputs used to evaluate the expression.
The content of the Expression depends on the Type selected. The following lists
the contents of the Expression field for each Type:
See also
74 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View windows Chapter 2
Procedure as Table The Procedure as Table window displays batches in table format. You can see
components of every procedural element in the currently selected batch. You can
window command a batch from within the Procedure as Table window using the
command buttons.
See also
Commands available in Command a batch from within the Procedure as Table window using the
the Procedure as Table command buttons.
window
The following commands can be issued from within the Procedure as Table
window:
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 75
Chapter 2 FactoryTalk Batch View windows
• Manual
• Semi-Auto
• Auto, Bind
• Active Step Change
• Clear All Failures
See also
Recipe table area The Recipe Table area displays batch information in a table format. One of the
following tables displays based on the recipe level selected in the Procedural
Hierarchy area:
• Procedure table
• Unit Procedure table
• Operation table
See also
Event Journal The Event Journal window displays the electronic batch record for a specific
batch. The electronic batch record contains information about the events that
window occur during batch execution or phases executed in the Phase Control window.
FactoryTalk Batch automatically creates the electronic batch record. You can view
the electronic batch record while the batch or phase is running or after processing
is complete. To specify the event types included in the electronic batch record, use
the FactoryTalk Batch Equipment Editor Server Options dialog box. (See the
FactoryTalk Batch Equipment Editor User Guide for more information.)
See also
76 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View windows Chapter 2
View the event journal View information about the events that occur during batch execution in the
after batch execution electronic batch record.
If the Filtering pane is hidden, drag the split bar to the right.
2. Click the Journal button to open the Event Data Files dialog box.
See also
Filter entries in an Specify the type of entries to display on the Filtering pane in an event journal, up
event journal to three fields at a time. You can view specific event types, for example, reports,
parameters, or step changes.
The wild card is an asterisk (*) character and can be used in conjunction with
other characters. For example, type A* in the Filter column for State. This limits
the batches that display in the Batch List view to only those batches that have been
ABORTED. Or, type *ED in the Filter column for State to display only those
batches whose states end in ED, such as ABORTED, STOPPED. The wild card
can begin, or end, or both start and end the Filter column.
1. With the appropriate event journal opened, from the Column list in the
Filtering pane, select the first field on which to filter.
4. Click Refresh to display the event data that meets the specified filter
criteria.
See also
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 77
Chapter 2 FactoryTalk Batch View windows
Unacknowledged The Unacknowledged Prompts window displays prompts for the currently
running batches. Prompts are used to alert operators when requests for phase
Prompts window parameter values are issued. Batch execution cannot complete until the prompt(s)
are acknowledged. When the Unacknowledged Prompts button flashes, click the
button to open the Unacknowledged Prompts window.
See also
Acknowledge a prompt Batch execution cannot complete until prompts are acknowledged. The prompt is
removed when the acknowledgment is complete.
To acknowledge a prompt:
4. Select Acknowledge.
See also
Acknowledge a Prompts alert operators when requests for parameter values are issued. Control
material phase step recipe execution cannot complete until the prompt(s) are acknowledged.
prompt To acknowledge a material phase step prompt:
1. Open the Prompt to Bind a Material Phase Step dialog box and select a
container and phase to use.
78 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View windows Chapter 2
4. Select a lot or storage container to bind the material to and click OK. The
prompt is acknowledged and removed from the Prompts List.
See also
Signature List The Signature List window displays signatures waiting to be acknowledged.
Signatures are requests for signoffs that require user permissions and optional
window comments. When a signature is generated against a batch, you acknowledge the
signature by completing the associated signoffs.
See also
Acknowledge a To acknowledge a signature, enter the signoff information that is required for
signature validation. Selecting the Close button without completing a signature closes the
dialog box and leaves the signature on the signature list.
To acknowledge a signature:
2. Click the flashing Signature List button to display the Signature List
window.
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 79
Chapter 2 FactoryTalk Batch View windows
See also
Set parameter If you change a parameter value in the FactoryTalk Batch View and a Param
signature overview Change verification policy is configured on the recipe parameter, the Signature
prompt begins flashing. Batch execution is suspended until the signature is
complete or canceled. The parameter value changes when the signature is
completed.
If a phase parameter has a Param Change verification policy and Deviation Limits
defined, then changing the parameter to a value outside the defined limits
generates two signature requests. The requests are displayed in the Generated
Signatures dialog box.
See also
80 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View windows Chapter 2
Command signature When a Command verification policy is configured in the area model, and that
overview command is issued against a batch, a signature request is generated and the
Command Signature dialog box opens.
The action associated with the command is not executed until the signature
request is complete. If a command signature request is canceled, then the
associated command is canceled. Command verification policies are configured in
the FactoryTalk Batch Equipment Editor.
• START • RESTART
• HOLD • MANUAL
• RESUME • PAUSE
• SEMI-AUTO • CLEAR FAILURES
• AUTO • ABORT
• DISCONNECT • TIMER RESET
• STOP • TIMER COMPLETE
See also
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 81
Chapter 2 FactoryTalk Batch View windows
Additional signature The area model supports several types of command verification policies that can
request types generate signature requests during batch execution, prior to batch execution, or
when batch execution is complete. If enabled, the following Signature requests
must be complete before the requested action executes:
• Remove/Reset Batch
• Active Step Change
• Force Transition
• Override Parameter Expression Value
• Clear Override
• Parameter Change
• Parameter Prompt Acknowledge
• Phase Bind
• Phase Bind Prompt Acknowledge
• Set Lots
• Set Labels
• Unit Bind
• Unit Bind Prompt Acknowledge
See also
82 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View windows Chapter 2
Signature request Signatures can be system canceled or user canceled. Selecting the Cancel
cancellation Signature button on a Signature dialog box displays the following dialog box.
Selecting Yes cancels the signature and the associated action. System cancelled
signatures are cancelled along with their associated actions.
See also
Signoff failures Electronic signatures are configured and authenticated using FactoryTalk
Security. Only FactoryTalk users with assigned permissions are authorized to
complete signature signoffs. If a user enters an invalid user name or password, an
entry is recorded in the Event Journal and the Signoff Failure dialog box opens.
(For more information on Electronic Signature security, see the FactoryTalk Batch
Administrator Guide.)
See also
Phase Control The Phase Control window shows phases relative to their physical units rather
than to recipes. From this window, you can view phase-specific information and
window run phases manually, independently of recipes. You can manually force the phase
logic to execute. For this reason, this window is very useful for testing purposes.
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 83
Chapter 2 FactoryTalk Batch View windows
You can issue the following commands for a selected phase from within the Phase
Control window:
• Start
• Pause
• Hold
• Stop
• Abort
• Reset
• Acquire
• Release
• Clear All Failures
• Disconnect
See also
84 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View windows Chapter 2
Process Cell or Unit The Process Cell and Unit Display area displays unit icons and flow path lines.
Display area The name of the selected Unit or Process Cell displays at the top of this section.
The button in the top right corner of this area is used as a toggle. The button is
only active if a process cell or unit is selected. If the unit(s) show, the button is
labeled Display Process Cells. If the process cell(s) show, the button is labeled
Display Units.
Tip: If Process Cell icons are changed, or units are added in the FactoryTalk
Batch Equipment Editor, you must close and restart the FactoryTalk
Batch View to display the changes in the Phase Control window.
If the area model exceeds the viewable area of the Unit Display area, a scroll bar is
shown that allows you to scroll through the area model. You can also click and
drag the vertical split bar between this area and the Phase List Display area to
enlarge or decrease the size of each area.
When a unit is selected in the Manual Phase Control window, cross invocation
does not pass the PATH or CREATEID information for the escape sequence,
%P. (See the FactoryTalk Batch Administrator Guide for more information.)
See also
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 85
Chapter 2 FactoryTalk Batch View windows
Phase List Display The Phase List Display area includes a button for each of the phases that belong
area to the unit selected in the Unit Display area. Each phase button displays the phase
name, phase state, step index (when running), and phase mode. The possible
modes are:
The State text and Step Index box are color coded to match the state of the active
phase. There is a series of three lights to the right of each phase button that
indicates the current owner of the phase. If the phase is owned, the appropriate
light is illuminated (Pr for Program, Opr for Operator, or Ext for External). If a
phase fails, FAILURE!!! displays in red text below the owner lights for the failed
phase.
The Next button is enabled if the unit contains more phases than can be displayed
in the area. Click the Next button to display the next group of phase buttons. The
Previous button is enabled after clicking the Next button. In the area below these
buttons, messages and failures related to the selected phase are shown.
See also
Phase Specific Information regarding the selected phase is displayed in the Phase Specific
Information Display Information Display area, including the phase name, phase state, batch ID, and
batch state. There is also an Unacknowledged Prompts area, where the prompts
area for the selected phase are displayed and can be acknowledged. Use the
Acknowledge button to open the Acknowledge dialog box for the selected
prompt. Requests for the selected phase are displayed below the prompts. The
86 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View windows Chapter 2
Mode options are used to specify the mode for the selected phase. The default
mode is Auto. These options are disabled until the phase is started, or on any
subsequent executions of this phase.
See also
Command phases in To directly command a phase, you must first acquire it. A phase can only be
the Phase Control acquired when it is not currently owned. You must release the phase when it is no
longer needed in order to make it available to other batches.
window
AUTO mode
You can run a phase using the AUTO mode in the Phase Control window.
When a phase is in the AUTO mode, an A is displayed next to the step index on
the phase button. While the phase is running, RUNNING displays on the phase
button. RUNNING also displays in the Phase Specific Information Display
area.
SEMI-AUTO mode
You can manually step through a phase using the SEMI-AUTO mode in the
Phase Control window, as long as the phase logic is programmed with break
points. Semi-auto processing allows you to test the functionality of the phase logic
prior to releasing the phase for general use. When a phase is in SEMI-AUTO
mode, an S displays next to the step index on the phase button. PAUSED displays
on the phase button, in dark blue text, on the line between the phase name and its
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 87
Chapter 2 FactoryTalk Batch View windows
current state. PAUSED also displays, along with the current state, in the Phase
Specific Information Display area.
The phase can be run from within the Phase Control view, in a process called
manual phase control. You must release the phase when it is no longer needed in
order to make it available to other batches.
See also
Acquire a phase To directly command a phase, you must first acquire it. A phase can only be
acquired when it is not currently owned.
To acquire a phase:
The Opr light for the selected phase turns green. The green indicates that
the operator has control of the phase. The mode changes to A.
Tip: If the phase you are attempting to acquire is running,
the phase is acquired upon completion of that phase.
See also
88 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View windows Chapter 2
Acquire a material phase To directly manipulate a phase, you must first acquire it. A phase is only acquired
when it is not currently owned.
The Opr light for the selected phase turns green. The green indicates that
the operator has control of the phase. The mode changes to A.
Tip: If the phase you are attempting to acquire is running, the
phase is acquired upon completion of that phase.
If not, the configured Feed Type for the material phase is listed and cannot
be changed.
6. Select a material to be acquired from the Material list, and click OK.
The Phase Control dialog box opens in which you bind the phase.
Any configured containers associated with the selected material are listed in
the Make a Selection to Bind Phase area.
7. Select a container that determines the requirements of the phase and the
material to bind the MATERIAL step, and click OK.
You are returned to the Phase Control window. The batch state displays
DOWNLOADING.
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 89
Chapter 2 FactoryTalk Batch View windows
See also
To start a phase:
2. In the Phases area, select the appropriate phase and acquire the phase.
3. Click Start to initiate the phase and then confirm the command.
5. (optional) If control strategies are enabled for the phase, select the
appropriate control strategy from the Control Strategy list.
6. Click OK.
Important: Batch IDs must be unique or the Arbitration window will not
update correctly.
See also
Acknowledge a prompt for Prompts alert operators when requests for parameter values are issued. Control
a phase recipe execution cannot complete until the prompt(s) are acknowledged.
90 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View windows Chapter 2
3. Click Acknowledge.
5. Click Acknowledge.
The prompt is removed from the list when the acknowledgment completes.
See also
To reset a phase:
1. In the Phases area, select the phase button for the phase to be reset.
If the phase has been run, it must be reset prior to being released.
See also
Release a phase Release the phase when it is no longer needed to make it available to other batches.
To release a phase:
2. Click Release. The Opr light for the selected phase turns gray, indicating
that you no longer own the phase.
See also
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 91
Chapter 2 FactoryTalk Batch View windows
Command a phase You can run a phase using the AUTO mode in the Phase Control window.
using AUTO mode When a phase is in the AUTO mode, an A is displayed next to the step index on
the phase button. While the phase is running, RUNNING displays on the phase
button. RUNNING also displays in the Phase Specific Information Display
area.
In the System Configuration and Defaults dialog box Phase Control tab, if the
Obtain From Unit option is enabled, a default batch ID is automatically created
based on the control recipe that currently has ownership of the unit in which the
phase is started. If no control recipe exists, the batch ID is assigned the default
BATCH_ID.
Important: Batch IDs must be unique or the Arbitration window will not update
correctly.
In the System Configuration and Defaults dialog box Phase Control tab, if the
Allow Override option is enabled, you can type a Batch ID other than the one
that is automatically created. If Allow Override is not enabled, the automatically
created Batch ID cannot be changed. The Allow Override option is only
applicable if the Obtain From Unit option is enabled.
2. Select the unit in the Unit Display area on which the desired phase resides.
The Phases List Display area displays the status and ownership of all phases
in the unit. Phases that are not running are in IDLE status.
4. Click the Acquire button and the Opr button turns green when the
phase acquisition is complete.
A confirmation dialog box displays that prompts you to confirm that you
want to start the phase.
The Phase button displays the current step index and the active state, both
in the appropriate color. The mode displays next to the step index box as an
A for operator-controlled AUTO mode. The phase transitions to the
92 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View windows Chapter 2
RUNNING state and then to the COMPLETED state after all steps are
executed.
Important: Batch IDs must be unique or the Arbitration window will not update
correctly.
8. Once the phase is complete, it must be reset. Click the appropriate Phase
button, and then click the Reset button.
See also
Semi-auto processing Semi-auto processing allows you to control the execution of steps in a specific
recipe level. SEMI-AUTO mode can be helpful when attempting to troubleshoot
a recipe. A recipe level can be placed in SEMI-AUTO mode when the batch is in
MANUAL or AUTO mode. When a batch or step is placed in SEMI-AUTO
mode, all higher level steps are placed in MANUAL mode, and all lower level steps
are placed in AUTO mode. You should select the lowest appropriate recipe level
and then place it in SEMI-AUTO mode. The step that is active at the time the
recipe level is placed in SEMI-AUTO mode completes, including its subordinate
steps. Batch execution then pauses at the next transition as the conditional
expression becomes TRUE. You must issue the RESUME command to initiate
the next step of the selected recipe level.
For example, assume you have a recipe with two unit procedures in succession.
The first unit procedure consists of three operations. The first two operations run
in parallel and the third follows the two parallel operations. Once you start the
batch, you place the first unit procedure within this recipe in SEMI-AUTO mode,
which places the procedure in MANUAL mode. The two parallel operations
execute normally, and execution pauses prior to starting the third operation. You
then issue the Resume command to continue the execution of the third operation.
However, execution of the batch halts prior to the second unit procedure because
the procedure is in MANUAL mode. To continue execution of the second unit
procedure, you must place the procedure in AUTO mode. The batch then
continues to execute normally and runs to completion.
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 93
Chapter 2 FactoryTalk Batch View windows
See also
Perform semi-auto Place a batch or step in SEMI-AUTO mode, to control the execution of steps in a
processing specific recipe level.
1. In the Batch List view, select the batch that is to be placed in SEMI-AUTO
mode.
5. Once you are ready to continue execution, select the step that is to be
resumed.
6. Click the Resume Batch button or Resume Step button and the step
transitions to the RUNNING state.
7. Repeat steps 5 and 6 until each of the subordinate steps have been run.
8. You can now place the batch in AUTO mode and continue normal
execution, perform an active step change, or perform semi-auto processing
at another recipe level.
See also
94 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View windows Chapter 2
Semi-auto phase You can manually step through a phase using the SEMI-AUTO mode in the
processing Phase Control window, as long as the phase logic is programmed with break
points. Semi-auto processing allows you to test the functionality of the phase logic
prior to releasing the phase for general use. When a phase is in SEMI-AUTO
mode, an S displays next to the step index on the phase button. PAUSED displays
on the phase button, in dark blue text, on the line between the phase name and its
current state. PAUSED also displays, along with the current state, in the Phase
Specific Information Display area.
See also
Perform semi-auto phase Manually step through a phase using the SEMI-AUTO mode in the Phase
processing Control window.
Tip: The phase logic must set the Paused bit where appropriate. These
programmed break points determine where the phase pauses while in
semi-auto processing.
1. Select the unit in the Unit Display area on which the desired phase resides.
2. Select the desired phase button in the Phases List Display area.
3. Click Acquire.
5. Click Yes to start the phase, or click No to cancel the phase initiation.
10. With the appropriate phase button selected, click Auto to return the phase
to the AUTO mode.
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 95
Chapter 2 FactoryTalk Batch View windows
See also
Arbitration window In the Arbitration window, you can view current resource allocation information,
acquire available resources, and release operator-owned resources.
• All Devices
• Devices List
• Command buttons
• Current Profile
• Priority List
See also
Acquire and release You can acquire a resource when it is not currently owned, or the number of
resources current owners is less than the defined maximum number of owners. Only the
current owner can release a resource.
1. Click the appropriate List Devices option to specify the device focus.
96 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
FactoryTalk Batch View windows Chapter 2
The Release button is only enabled if you currently own the resource.
See also
Alarm Summary The Alarm Summary window displays all phase failure and phase error messages
for the current batches. Each message listed includes the following columns:
window
• Phase
• State
• Failure
• Unit
• Batch ID
The Alarm Summary button flashes when an alarm is being generated and stops
flashing when the Alarm Summary window becomes the active FactoryTalk
Batch View window.
See also
View alarm messages View any phase failure or error messages that have not been cleared in the Alarm
Summary window.
See also
Clear failure messages You can clear all failure and error messages by clicking Clear All Failures from
any of the following windows:
• Batch List
• Procedure as SFC
• Procedure as Table
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 97
Chapter 2 FactoryTalk Batch View windows
See also
Phase Summary The Phase Summary window displays all equipment phases and their associated
status information in table format. The following information displays for each
window phase:
• Phase Name
• State
• Mode
• Unit
• Step Index
• Owner
• Batch ID
• Message
• Failure
When a phase is selected in the Phase Summary window, cross invocation does
not pass the CREATEID information for the escape sequence, %P. (See the
FactoryTalk Batch Administrator Guide for more information.)
See also
98 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
Chapter 3
Command a batch
Using FactoryTalk View, you can issue batch commands from the Batch List
view, the Procedure as SFC view, or the Procedure as Table view. The command
buttons are only enabled for commands that are valid for the batch’s current
conditions. The command buttons on the Batch List view affect the entire batch.
The same command buttons on the Procedure as SFC and Procedure as Table
views affect any currently selected step that is in O-AUTO mode.
While commanding a batch, you may receive prompts that require operator input
in order to continue processing the batch. These prompts display in the
Unacknowledged Prompts window of the FactoryTalk Batch View.
See also
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 99
Chapter 3 Command a batch
To start a batch:
See also
Hold a batch This command temporarily stops execution of the batch at a step. A HELD batch
can be RESTARTED, STOPPED, or ABORTED. A batch can be held from the
following FactoryTalk Batch View windows:
To hold a batch:
See also
100 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
Command a batch Chapter 3
Restart a batch Restarting a batch begins the execution of the batch that is in the HELD state.
Unless there is an active step change, the batch restarts with the step that was the
active step at the time the batch was HELD.
To restart a batch:
See also
Abort a batch The ABORT command is used to permanently stop the execution of a batch at
the current step. It is generally used in emergency situations, as you cannot restart
an ABORTED batch.
To abort a batch:
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 101
Chapter 3 Command a batch
See also
Stop a batch The STOP command is used to permanently stop the execution of a batch at the
current step in a non-emergency situation. A batch can be stopped from the
following FactoryTalk Batch View windows:
To stop a batch:
See also
Override an Like deferred parameter values, the expression value cannot be changed. However,
there may be times when it is imperative to override the expression and assign a
expression value new value when responding to extraordinary circumstances.
Once entered, the new expression value remains valid until you click the Clear
Override button, which commands the expression to evaluate again. The override
information is captured in the event journal for the batch.
102 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
Command a batch Chapter 3
1. Double-click the recipe parameter expression containing the value that you
want to override.
See also
Force a transition to The Force Transition command allows a transition to be fired immediately
without the necessity of performing an active step change. If a transition
fire expression references the report parameter and its value is preventing the
transition from firing, use the Force Transition option to force the transition to
fire.
2. Click the Force Transition button and then click OK to confirm that you
want the transition to fire.
See also
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 103
Chapter 3 Command a batch
• AUTO: The recipe automatically progresses from step to step when its
transition conditions become true.
• SEMI-AUTO: The recipe does not progress to the next step when its
transition conditions become true until the operator commands the recipe
to resume.
• MANUAL: The operator has complete control over the execution of steps
within a recipe.
See also
AUTO recipe mode In AUTO mode, the recipe automatically progresses from step to step when its
transition conditions become true. There are two types of AUTO mode:
The highest recipe level is usually in O-AUTO mode while all subordinate recipe
steps are in P-AUTO mode. Once the operator commands the highest level of the
recipe (which is in O-AUTO mode) to start, the subordinate steps further down
in the recipe hierarchy are automatically put into P-AUTO mode.
See also
104 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
Command a batch Chapter 3
SEMI-AUTO recipe In SEMI-AUTO mode, the recipe does not progress to the next step when its
mode transition conditions become true until the operator commands the recipe to
resume. In SEMI-AUTO mode, the FactoryTalk Batch Server stops normal
sequencing. Once you place a recipe step in SEMI-AUTO mode, all higher-level
recipe steps that contain the SEMI-AUTO step are automatically placed in
MANUAL mode. When a lower-level recipe step has stopped normal sequencing,
all higher-level recipe steps that contain it also stop normal sequencing.
See also
MANUAL recipe mode In MANUAL mode, the operator has complete control over the execution of
steps in a recipe. The FactoryTalk Batch Server stops normal sequencing. Once a
recipe step is placed in MANUAL mode, the lower level steps it contains are
placed in O-AUTO mode. As a result, if a step is placed in MANUAL mode, the
operator can command any lower level steps it contains. Furthermore, when a step
is placed in MANUAL mode, the higher-level steps that contain it are also
automatically placed in MANUAL mode. When a lower-level recipe step has
stopped normal sequencing, all higher-level recipe steps that contain it also stop
normal sequencing.
When a step is placed in MANUAL mode, the steps which contain it further up
in the recipe hierarchy are also automatically placed in MANUAL mode.
When you place a recipe level in MANUAL mode, two things happen:
• Any higher-level recipes that contain the step you put into MANUAL
mode, also go into MANUAL mode.
• Any lower-level steps contained by the recipe step in MANUAL mode go
into O-AUTO mode.
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 105
Chapter 3 Command a batch
A batch or step that is placed in MANUAL mode allows any lower-level active
step(s) to complete, but the lower-level steps will not automatically transition to
the next step.
You can place a batch or step in MANUAL mode from the following FactoryTalk
Batch View windows:
For example, assume you have a recipe consisting of two unit procedures in
succession. The first unit procedure consists of three operations: the first two
operations run in parallel and the third follows the two parallel operations.
Once you start the batch, you place the first unit procedure in this recipe into
MANUAL mode. This causes the FactoryTalk Batch software to place the
procedure into MANUAL mode. Since the unit procedure that contains the two
parallel operations is in MANUAL mode, the mode of the two parallel operations
changes to O-AUTO and they execute normally. Execution halts prior to starting
the next operation.
You must now either perform an Active Step Change to specify the next operation
to execute (which you can do since the mode of the operation is O_AUTO) or
return the unit procedure to AUTO mode. If you return the unit procedure to
AUTO mode, it continues to execute normally, but execution stops prior to
starting the second unit procedure because the procedure is still in MANUAL
mode. To start execution of the second unit procedure, you must place the
procedure in AUTO mode to resume normal sequencing.
See also
Timer procedure Timer procedures use modes the same way as Null steps. A timer step must be in
modes O-AUTO before it can be reset or forced to complete. However, a tmer step itself
cannot be placed into MANUAL or O-AUTO mode. The procedure, operation,
or unit procedure containing the timer step must be placed in MANUAL mode in
order to change the timer step to O-AUTO.
106 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
Command a batch Chapter 3
• If the level immediately above the procedure containing the timer step is
placed into MANUAL, the mode of the timer step changes to O-AUTO.
• If the procedure containing the timer step is placed into MANUAL, all
recipe levels above the timer step procedure are placed into MANUAL.
• If the procedure containing the timer step is placed into AUTO (only
possible when current mode is MANUAL), the timer step transitions to O-
AUTO mode.
Tip: While the mode of a tmer step has no effect on its
operation, the timer step must be in O-AUTO before it
can be reset or forced to complete.
See also
Place a batch in A batch or step that is in SEMI-AUTO or MANUAL mode must be placed in
AUTO mode to resume normal execution. A batch or step can be placed in the
AUTO mode AUTO mode from the following FactoryTalk Batch View windows:
To place the entire batch in AUTO mode, select the highest recipe level and
place it in AUTO mode (for example, operation, unit procedure, or
procedure).
3. Select the recipe level that you want to place in AUTO mode.
See also
Semi-auto Semi-auto processing allows you to control the execution of steps in a specific
recipe level. SEMI-AUTO mode can be helpful when attempting to troubleshoot
processing a recipe. A recipe level can be placed in SEMI-AUTO mode when the batch is in
MANUAL or AUTO mode. When a batch or step is placed in SEMI-AUTO
mode, all higher level steps are placed in MANUAL mode, and all lower level steps
are placed in AUTO mode. You should select the lowest appropriate recipe level
and then place it in SEMI-AUTO mode. The step that is active at the time the
recipe level is placed in SEMI-AUTO mode completes, including its subordinate
steps. Batch execution then pauses at the next transition as the conditional
expression becomes TRUE. You must issue the RESUME command to initiate
the next step of the selected recipe level.
For example, assume you have a recipe with two unit procedures in succession.
The first unit procedure consists of three operations. The first two operations run
in parallel and the third follows the two parallel operations. Once you start the
batch, you place the first unit procedure within this recipe in SEMI-AUTO mode,
which places the procedure in MANUAL mode. The two parallel operations
execute normally, and execution pauses prior to starting the third operation. You
then issue the Resume command to continue the execution of the third operation.
However, execution of the batch halts prior to the second unit procedure because
the procedure is in MANUAL mode. To continue execution of the second unit
procedure, you must place the procedure in AUTO mode. The batch then
continues to execute normally and runs to completion.
See also
Perform semi-auto Place a batch or step in SEMI-AUTO mode, to control the execution of steps in a
processing specific recipe level.
1. In the Batch List view, select the batch that is to be placed in SEMI-AUTO
mode.
5. Once you are ready to continue execution, select the step that is to be
resumed.
6. Click the Resume Batch button or Resume Step button and the step
transitions to the RUNNING state.
7. Repeat steps 5 and 6 until each of the subordinate steps have been run.
8. You can now place the batch in AUTO mode and continue normal
execution, perform an active step change, or perform semi-auto processing
at another recipe level.
See also
Place a batch in If you need to determine which step to execute next through a procedure called an
Active Step Change, place a batch or step in MANUAL mode.
MANUAL mode
To place a batch in MANUAL mode:
1. In the Batch List view, select the batch that contains the step.
3. Select the lowest appropriate recipe level containing the steps that you want
to command.
The batch then completes the active step and the step transitions to the
COMPLETE state. The batch must be placed in AUTO mode to resume
automatic execution.
See also
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 109
Chapter 3 Command a batch
Command timer If the recipe on the batch list contains one or more timer steps, you can reset the
timer step or force it to complete. The batch must be in MANUAL mode, which
steps places the timer step into O-AUTO mode.
See also
Reset a timer step When a timer step in the RUNNING or HELD state receives the Timer-Reset
command, the ELAPSED_TIME report will be reset to 0. If the timer step is
configured as a COUNT_DOWN timer, the REMAINING_TIME report will
be reset to the setpoint value. If the Timer-Reset command is issued and the
command is no longer valid, for example, due to a change of state, the command is
ignored.
2. In the Procedure as SFC view or Procedure as Table view, select the timer
step.
3. Click Timer-Reset.
See also
Force a timer step to When a timer step is in the RUNNING state and receives a Timer-Complete
complete command, the timer step will transition to the COMPLETE state. If a Timer-
Complete command is issued and the command is no longer valid, for example,
due to a change of state, the command is ignored.
2. In the Procedure as SFC view or Procedure as Table view, select the timer
step.
3. Click Timer-Complete.
110 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
Command a batch Chapter 3
See also
Change the setpoint of You can change the setpoint of a timer step whether or not it is currently active
a timer step and regardless of its state.
1. Select the Timer step in the Procedure as SFC view or Procedure as Table
view, and then click the Details button.
4. Type a new setpoint value in the Value box, and then click OK.
5. Click OK to close the Properties dialog box and apply the change.
See also
Perform an active Active step changes cannot be performed at the batch level. They can only be done
on the following:
step change
• Step level on procedures
• Unit procedures
• Operations
• Phases
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 111
Chapter 3 Command a batch
You can change the active step in a batch if the recipe level that contains the steps
requiring the active step change is in MANUAL mode.
For example, if you want to command phase steps, the operation must be in
MANUAL mode. Steps that are in the HELD state cannot be removed as the
active step. An active step change can be performed in the Procedure as SFC view
or Procedure as Table view, although it is recommended that it is performed
within the Procedure as SFC view.
4. Select the recipe level that contains the active step and place this recipe level
in MANUAL mode.
5. If the Procedure as SFC view is the active window, select the recipe level
that contains the active step to be changed. Place this recipe level in
MANUAL mode.
Tip: Double-click the selected step in the SFC. This displays the steps within
this recipe level.
6. If the Procedure as Table view is the active window, select the level that
requires the active step to be changed. Place this recipe level in MANUAL
mode.
b. Double-click the selected step in the SFC. This displays the steps within
this recipe level.
7. If a step to activate is a material phase step, you must first bind the step to a
phase before doing the active step change. Select each material step that you
want to activate and perform a manual bind.
112 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
Command a batch Chapter 3
Tip: The active step(s) changes to a gray background and is outlined in yellow
after clicking the Active Step Change button. In addition, the cursor
changes to a hand shape. Use the cursor to toggle steps between
activated and deactivated status.
9. A new set of command buttons displays: Execute ASC and Cancel ASC.
10. Position the hand cursor over the quiescent step(s) and click to deactivate
them.
11. Using the hand cursor, click the new step(s) to activate.
Tip: If you did not bind a material phase step to a phase, you are prompted to
bind the step, and then you must begin the active step change again.
14. Select the new active step in the Procedural Hierarchy view section; it is in
the READY state and in O_AUTO mode.
See also
Manual binding Manual binding is the process of binding a unit, or rebinding a previously bound
unit, to a step within a control recipe without being prompted. Manual binding is
performed from within the Procedure as SFC view or Procedure as Table view
or from the ProcedureView ActiveX control.
For units, the operator can select First Available, Prompt or one of a list of units
for binding. For material phases, the operator can select Automatic, Prompt or
any one of a list of container/phase/lot entries.
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 113
Chapter 3 Command a batch
Tip: All other steps within the recipe that are associated with the same unit
requirement are bound to the same unit.
Perform manual Manual binding is the process of binding a unit, or rebinding a previously bound
binding unit, to a step within a control recipe without being prompted to do so.
Tip: This procedure applies to steps (not batches) and can only be performed
at the step level.
1. In the Batch List view, select the batch that requires binding.
3. To bind a unit to a step, you must select the unit procedure in either the
SFC area, Recipe Table area, or the Procedural Hierarchy area.
4. Click Bind.
See also
Material binding Material binding is the process of binding activated material-enabled phase steps
to material phases. Or, the process of rebinding a previously bound material to a
step within a control recipe without being prompted. Material phase binding must
be performed from within the Procedure as SFC or Procedure as Table view or
the ProcedureView ActiveX control.
114 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
Command a batch Chapter 3
Tip: This procedure applies to steps (not batches) and can only be performed
at the Step level.
1. From the Batch List view, select the batch that requires binding.
3. To bind a material to a step, you must select the material step in either the
SFC area, Recipe Table area, or the Procedural Hierarchy. If the manual
binding criteria have been met, the Bind command button is enabled.
4. Click the Bind button, and the Prompt to Bind a Material Phase Step
dialog box displays with a list of legal binding options.
5. Select the material specification that determines the lot or storage container
to bind the material step. Then click OK.
See also
Prompted binding Prompted binding is the process of binding a unit to a step after a prompt is
generated. Only unit class requirements that are defined with the Prompted
Binding method generate a prompt, including those that are defined as such at the
time the batch is created.
The execution of the batch pauses when the transition above the unbound step
becomes True. A prompt displays in the Unacknowledged Prompts view and on
the Prompts tab of the Auxiliary Index view in the Procedure as SFC view or
Procedure as Table view.
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 115
Chapter 3 Command a batch
See also
1. In the Batch List view, select the batch that requires binding.
See also
Disconnect a phase When a phase becomes unusable, the Disconnect command can be used to
disconnect the FactoryTalk Batch Server from the unusable phase. The
Disconnect command can be executed on any step in O_AUTO or S_AUTO
mode that is connected to a phase and that is in any state other than
NOT_CONNECTED (READY). This applies to a phase that is under external
control, has a failure, is PAUSED, or is HELD.
To disconnect a phase:
116 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
Command a batch Chapter 3
Important: Reset the phase to an IDLE state before using it again with the
FactoryTalk Batch Server.
See also
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 117
Chapter 3 Command a batch
Cross invocation Cross invocation is the process of passing pre-configured context information to
an automation server. This information is relative to the element selected in the
FactoryTalk Batch View application. When you customize the FactoryTalk Batch
View in the System Configuration and Defaults option to enable cross
invocation and identify the automation server by the Invocation ProgID, a
shortcut menu becomes available by clicking the Go To HMI button.
The items in the shortcut menu are formatted using cross invocation strings
associated with the equipment resource to which the current selection in the
FactoryTalk Batch View corresponds. These cross invocation strings also contain
the context data that is passed to the automation server. (See the FactoryTalk
Batch Administrator Guide for more information on cross invocation strings and
the context data that can be configured.)
The following are the elements that can be selected for cross invocation from each
of the FactoryTalk Batch View windows.
See also
118 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
Command a batch Chapter 3
Perform cross Customize the FactoryTalk Batch View in the System Configuration and
invocation Defaults option to enable cross invocation and identify the automation server by
the Invocation ProgID.
Tip: Check with your system administrator to determine what context data is
configured for each of the shortcut menu items displayed on your system.
1. In the FactoryTalk Batch View window, select the available element, and
click the Go To HMI button.
See also
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 119
Chapter 4
When running batches, you may occasionally encounter situations that are
difficult to resolve. This section provides solutions to some of the problems you
may encounter.
Issue Solution
The following error displays Parallel steps requesting the same phase cannot
when running a batch: occur just after an AND divergence.
Recipe SFC Requires • Abort or Stop the batch. Remove the batch from
Illegal Use of Dedicated the batch list.
Resources.
• Revise the recipe to include a null procedure
before each of the parallel steps after the AND
As a result, the batch goes divergence.
into a HELD state.
• Create and run a batch using the new recipe. (See
the FactoryTalk Batch Recipe Editor User Guide
for information on adding null phases to a recipe.)
A batch seems to be Parallel steps requesting the same phase cannot
running, but it is not occur just before an AND convergence.
progressing as it should. • Abort or Stop the batch. Remove the batch from
No errors are generated. the batch list.
The status is RUNNING.
• Revise the recipe to include a null procedure after
each of the parallel steps before the AND
convergence.
• Create and run a batch using the new recipe. (See
the FactoryTalk Batch Recipe Editor User Guide
for information on adding null phases to a recipe.)
A failure is generated and Phases put into an external state can still be viewed
the batch is held because as binding candidates by the FactoryTalk Batch
the FactoryTalk Batch Server. (The external state is a tag in the controller
Server selected an that prevents the Server from controlling the phase.)
equipment phase under To remove a phase from being viewed as a binding
EXTERNAL control to bind candidate, you must take ownership of the phase.
to during batch execution. (For more information on the External attribute, see
the FactoryTalk Batch PCD Programmer Technical
Reference Guide.)
See also
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 121
Chapter 4 Troubleshoot batch issues
122 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
Index
comment 21
A disconnect 21
abort a batch 97 hold 21
acknowledge a prompt 75 manual 21
material phase step 76 remove 21
acknowledge a signature 77 semi-auto 21
acquire start 21
a material phase 85 stop 21
a phase 85 timer-complete 21
resources 92 timer-reset 21
active step change 106 command verification policies 79
add a batch 58 comment 61
alarm summary communication status 22
window 93 indicators 22
AND convergence-troubleshoot 115 configuration and defaults
AND divergence-troubleshoot 115 setting 31
arbitration create a batch 58
window 92 cross invocation 112
auto enable 32
mode 102 manual phase control window 81
phase processing 88 phase summary window 94
unacknowledged prompts window 75
current profile 92
B
batch
D
comment 61
mode 57 Data Servers
batch creation conversion status 23
without material server 25 device focus 92
batch scale 58 disconnect phase 111
Batch Server
incompatible version 17
E
batch state 57
error messages 93
event journal
C filter criteria 75
cancel a signature open 74
system canceled 80 sort criteria 75
clear failure messages 93 exit from View 19
clear override 98
command
F
phases 84
command buttons 21 failure messages 93
abort 21 filters 55, 75
add 21
auto 21 G
clear all failures 21
generated signatures 77
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 123
Index
H override
clear 98
HMI
Go To 32
hold a batch 96 P
parallel steps 115
I password 17
phase control
incompatible window 81
Batch Server 17 without Material Server 29
phase list display area 83
L phase specific information display area 83
phase summary
list devices 92 window 94
log on to Batch View 19 phases
login 17 acknowledge phase prompt 87
acquire 85, 92
M command 84
control 84
manual
release 88
mode 104
reset 87
phase control 84
start 86
phase control, material-enabled phase 85
priority list 92
manual unit binding
prompt
without Material Server 27
acknowledge 75
material phase
prompt binding
acquire 85
without Material Server 26, 28
Material Server
prompted binding 111
communication status 24
outage 24
reestablish communications 30 R
material value selection recipe list dialog box 58
without Material Server 25 release
messages phase 88
clear failure 93 resources 92
view 93 remove a batch 61
minimize the View 32 reset phase 87
mode 57 resize the View 32
auto 102 restart a batch 96
manual 104
semi-auto processing 90
mode column 57 S
multiple instances scale 58
Batch View 17 security 7
commands 7
O log on 7
semi-auto phase processing 91
open the View 17 semi-auto processing 90
124 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
Index
setpoint U
change 106
SFC area unacknowledged prompts
work in the 65 window 75
SFC View
window 63 V
signature list
window 76 View
signature requests configure 31
active step change 79 alarm summary 51
clear override 79 Batch List view 36
force transition 79 Cross Invocation 32
general usage signature 79 event journal 49
override expression value 79 Hierarchical Step List 37
parameter change 79 HMI 32
parameter deviation signatures 79 operations table 47
parameter prompt acknowledge 79 phase control 52
phase bind 79 phase summary 53
phase bind prompt acknowledge 79 procedure binding 44
remove batch 79 procedure parameters 41
report parameter deviation signatures 79 procedure prompts 39
reset batch 79 procedure reports 42
set all label 79 procedures table 45
set all lot 79 SFC view 38
timer complete 78 Signature List 34
timer reset 78 unacknowledged prompts 50
unit bind 79 unit procedures table 46
unit bind prompt acknowledge 79 login 17
signature template 76 View interface 19
Single-SignOn View 16 View security 7
SQL wildcards 55, 75 FactoryTalk Security 7
start Single-SignOn 16
a batch 95 View windows
a phase 86 alarm summary 93
stop arbitration 92
batch 21 Batch List 63
Batch List view 57
phase control 81
T phase summary 94
Table SFC View 63
window 72 signatures 76
timer step Table View 72
change the setpoint 106 unacknowledged prompts 75
complete 105
reset 105 W
toolbar-View 19
wildcard character 55
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 125
Legal Notices
You can view the Rockwell Automation End-User License Agreement ("EULA")
by opening the License.rtf file located in your product's install folder on your hard
drive.
Trademark Notices
Warranty
This product is warranted in accordance with the product license. The product’s
performance may be affected by system configuration, the application being
performed, operator control, maintenance, and other related factors. Rockwell
Automation is not responsible for these intervening factors. The instructions in
this document do not cover all the details or variations in the equipment,
procedure, or process described, nor do they provide directions for meeting every
possible contingency during installation, operation, or maintenance. This
product’s implementation may vary among users.
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017 127
Legal Notices
This document is current as of the time of release of the product; however, the
accompanying software may have changed since the release. Rockwell Automation,
Inc. reserves the right to change any information contained in this document or
the software at any time without prior notice. It is your responsibility to obtain the
most current information available from Rockwell when installing or using this
product.
Environmental compliance
128 Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
Rockwell Automation support
Rockwell Automation provides technical information on the web to assist you in using its products. At
http://www.rockwellautomation.com/support you can find technical and application notes, sample code, and links to software service packs. You
can also visit our Support Center at https://rockwellautomation.custhelp.com for software updates, support chats and forums, technical
information, FAQs, and to sign up for product notification updates.
In addition, we offer multiple support programs for installation, configuration, and troubleshooting. For more information, contact your local
distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/services/online-phone.
Installation assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact
Customer Support for initial help in getting your product up and running.
United States Contact your distributor. You must provide a Customer Support case number (call the
phone number above to obtain one) to your distributor to complete the return process.
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
Documentation feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the
feedback form, publication RA-DU002.
Rockwell Automation Publication FactoryTalk Batch View User Guide - February 2017
Copyright © 2017 Rockwell Automation Technologies, Inc. All rights reserved. Printed in the U.S.A.