FF STP Specifications
FF STP Specifications
INSTALLATION GUIDE
The information in this publication is provided for reference only. While every effort has been made to ensure the reliability and accuracy of the
information contained in this manual at the time of printing, we recommend that you refer to “franklinfueling.com” for the most current version of this
manual. All product specifications, as well as the information contained in this publication, are subject to change without notice. Franklin Fueling Systems
does not assume responsibility and expressly disclaims liability for loss, damage, or expense arising out of, or in any way connected with, installation,
operation, use, or maintenance by using this manual. Franklin Fueling Systems assumes no responsibility for any infringement of patents or other rights
of third parties that may result from use of this manual or the products. We make no warranty of any kind with regard to this material, including, but not
limited to, the implied warranties of merchantability and fitness for a particular purpose.
Copyright © 2022 Franklin Fueling Systems, LLC, Madison, WI 53718. All world rights reserved. No part of this publication may be stored in a retrieval
system, transmitted, or reproduced in any way, including, but not limited to, photocopy, photograph, magnetic, or other record, without the prior written
permission of Franklin Fueling Systems.
For technical assistance, please contact:
Franklin Fueling Systems
3760 Marsh Rd.
Madison, WI 53718
USA
Web: franklinfueling.com
Tel: +1 608 838 8786 • Fax: +1 608 838 6433
Tel: USA & Canada +1 800 225 9787 • Tel: UK +44 (0) 1473 243300
Tel: Mex 001 800 738 7610 • Tel: DE +49 6571 105 380 • Tel: CN +86 10 8565 4566
Loctite* is a registered trademarks of Henkel Corporation
400604005 r24
REQUIRED TOOLS
• Standard 3/4" drive ratchet wrench or breaker bar (no sockets required)
• Standard flat head screwdriver
• Wire cutter and stripper
• 5/32" Allen wrench for securing set screw in telescoping pipe coupling (VL units only)
• Pipe wrench (36" minimum) for tightening 4" Riser
• 1/4" hex driver with socket and ratchet wrench, or 1/4" Allen wrench for attaching PMA
• Measuring tape (long enough to reach bottom of the tank from 30" to 70" above the tank)
IMPORTANT: All wiring must conform to guidelines in accordance with all federal, state, and local codes.
Failure to comply with all applicable guidelines could result in an unsafe installation. Use the following table for
maximum wire length to wire gauge ratios for submersible wiring:
1
INSTALLATION
The piping and underground storage tank must be installed using good standard industry practices. Listed
below are several publications that can be used for reference:
• Automotive and Marine Service Station Code, NFPA 30A, Flammable and Combustible Code, NFPA 30,
and National Electrical Code, NFPA 70 (NEC), National Fire Protection Association, Quincy, Mass.
• Recommended Practices for Installation of Underground Liquid Storage Systems, The Petroleum
Equipment Institute, PEI / RP100, Latest Edition.
• Recommended Practices for Installation of Aboveground Storage Systems for Motor Vehicle Fueling, The
Petroleum Equipment Institute, PEI / RP200, Latest Edition.
• Installation of Underground Petroleum Storage Systems, American Petroleum Institute, API
Recommended Practice 1615, Latest Edition.
• Installation of ATEX approved pumps should be done in compliance with the following Standards:
• EN 60079-14
• EN 60079-17
• EN 60079-19
• VDE 0100
NOTE: ATEX approved pumps to be installed in Zone 0 (category 1) locations require SIL-1 certified motor control.
NOTE: Review the Additional Information Sheet for ATEX Compliant Installations for details (Franklin Fueling
System’s document 401358001).
NOTE: The manufacturing of Submersible Turbine Pump meets the National Standards of GB/T3836.1-2021
<< Part 1 of Explosive Atmospheres: General Equipment Requirements>>, and GB/T3836.2-202 << Part 2 of
Explosive Atmospheres: Equipment protected by flameproof type “d”>>. The Explosion Proof certificate number
is on the Nameplate. Explosion-proof mark: Ex db sa IIA T4 Ga/Gb
IMPORTANT: All NPT threaded STP pipe fittings should be assembled using a non-hardening, UL classified,
gasoline resistant pipe sealing compound. Fittings should be installed hand tight, and then tightened until
wrench tight (without exceeding 3 turns for fittings up to and including 2" and 2 turns for larger fittings). To
ensure proper installation, the joint must be pressurized and checked that there is no leakage. This check is
essential and must be the specification for making sure a joint is
properly assembled.
NOTE: If your STP/IST does not operate correctly or there are any questions concerning installation or service,
please contact FFS.
2. Disconnect power to the submersible pump at the electrical supply box (if already installed).
3. Tag and lock out electrical circuit breakers so they are not turned on accidentally.
4. Do one of the following:
• If installing variable length pump, continue with this section.
• If installing fixed length pump (non-variable) with PMA mounted, go to SECURE TO TANK.
• If installing fixed length pump (non-variable) without PMA mounted, go to MOUNTING THE PMA,
and then go to SECURE TO TANK.
2
MOUNTING THE PMA
1. Lay packaged pump on a flat, open surface and remove the package.
2. Flatten pump packaging and lay the PMA on the end of the pump in preparation for mounting.
3. The PMA mounting hardware kit (# 152350902) is attached to the PMA packaging. It contains a gasket, a
tube of grease, and four 5/16" cap screws with lockwashers.
4. Remove the two packaging ends and the protective sleeve from the PMA.
5. Apply grease provided to the inside wall of the pump motor electrical connector, and the rubber of the
lead assembly connector.
6. Place the gasket on the end of the PMA, aligning locating pin and bolt holes).
7. Mount PMA onto discharge head by aligning locating pin on PMA with hole in discharge head, assuring
that the lead assembly in the motor discharge head is seated in its notched position, and that the PMA
gasket is properly in place.
8. Tighten PMA onto discharge head using four cap screws and lock washers supplied. A cross bolt-
tightening pattern is recommended for securing PMA.
WARNING: The motor discharge head must not be rotated more than one full rotation in either direction.
Rotation could cause damage to the electrical connections in the conduit, creating a risk of lethal electrical
shock or equipment failure.
3
NOTE: Before assembling the PMA to the discharge casting make sure the wire lead is properly set and aligned
in the discharge casting. Improper alignment could damage the wire lead or motor pins. Failure to push PMA
up snug against the discharge casting before tightening cap screws, or failure to use a cross-pattern while
tightening the bolts could break the discharge casting or strip the threads in the PMA.
NOTE: IST units without a VS4 suffix and STP units with a VS2 suffix can only be electrically connected to an
IST-VFC or MagVFC.
NOTE: STP or IST units with a VS4 suffix can only be electrically connected to a MagVFC or EcoVFC. Unlike
FFS’s standard pumps, the following pumps cannot be interchanged with competitive models:
• The variable speed PMA VS2 (which is part of IST units without the VS4 suffix or the STP units suffixed
with VS2)
• The PMA VS4 (which is part of the IST and STP units with the VS4 suffix)
9. Apply a non-hardening, UL classified, gasoline-resistant pipe sealing compound to the riser pipe threads,
if not already installed.
IMPORTANT: Failure to use a proper thread sealing compound could result in a lack of seal where the riser
threads into the tank opening, making it impossible to perform a tank-tightness test. This may also create a
potential site for fuel to leak into the environment and / or the containment sump.
10. Slide riser over the PMA and tighten into manifold threads. Maximum riser size is found by taking the
grade to tank mounting thread measurement and subtracting the manifold height and clearance (6"
clearance recommended).
11. Riser material required for pump is 4.5" outside diameter with a .188" wall. Minimum riser length
supplied by FFS is 7".
Example:
Grade to tank mounting threads (bury depth) 48"
Minus manifold height without leak detector (w / leak detector height = 12.50) -11"
Minus 6" for top clearance (2" minimum) -6
= Maximum riser size 31"
4
LENGTH SETTING
1. Cut wire tie(s) securing the motor wire at the top of the pump; lay the wires out above the pump head so
that wires can feed through conduit freely when setting length.
IMPORTANT: Failure to cut wire ties prior to setting pump length could result in damage to electrical motor
wires, presenting a risk of lethal electrical shock or equipment failure.
2. Measure from the bottom of the tank to the top of tank mounting threads. Subtract the distance for
clearance between the PMA and the bottom of the tank (6" recommended). This is the length to which
the pump should be extracted, measured from the bottom of the riser threads to the bottom of the
motor end bell.
NOTE: 6" clearance provides a 5" clearance from the pump motor end bell to the bottom of the tank once the
riser is screwed into tank mounting threads.
3. Hold the manifold securely to the surface to prevent damage while setting length.
To allow movement of the telescoping pipe, verify that none of the pipe coupling setscrews are
in contact with the pipe. Lay a tape measure out to accurately measure the distance from the
bottom of the riser to the bottom of the pump motor end bell.
4. Grasp the pump just above the PMA and pull firmly, extending to the length required).
NOTE: Make sure the electrical conduit wires at the top of the discharge manifold are not damaged during
length setting. If the column pipe is extended beyond the desired length, have a second person retract conduit
wires as the column pipe is shortened. This helps prevent damage to the conduit wires.
5
IMPORTANT: The motor discharge head must not be rotated more than one full rotation in either direction.
Rotating could cause damage to the electrical motor wires, presenting a risk of potentially lethal electrical shock
or equipment failure.
NOTE: O-ring seals inside the locking coupling may have sealed to the column pipe during shipping. Spin the
motor discharge head slightly (not more than one full rotation) while pulling to loosen the O-ring seals.
5. Once the length is correct, lock the STP length by tightening all three coupling setscrews. Tighten the
setscrews finger-tight, making sure they come into contact with the pipe.
Setscrews 3 places
NOTE: Loctite® 243 thread locker must be used on all ATEX approved pumps.
6. Tighten each setscrew an additional full turn minimum. The head of the setscrews should be flush or
below flush with the outer surface of the coupling.
NOTE: Failure to properly tighten the coupling setscrews at this stage could present a risk of death, serious
bodily injury and/or equipment damage due to movement of pipes during installation.
6
PMA WIRING
1. Measure 6" of wire from the discharge manifold. Cut off excess wire and discard.
2. Place the three wires through the plug assembly (from hardware pack p/n 400301XXX).
3. Using the screwdriver slide the contractors plug into its seat in the discharge manifold. Tighten the
screw(s) in the contractor plug to secure it in place.
4. Strip the wire insulation back approximately 3/8" on the three motor leads. Using the wire nuts or terminal
blocks supplied (from hardware pack p / n 400301XXX) connect to the wires from the electrical connector
orange to orange, black to black, and red to red.
NOTE: Terminal blocks are provided for wire connections on ATEX approved pumps. For terminal blocks, strip
5 mm insulation from the end of the wires. Torques terminal screws to 0.4 - 0.45 Nm.
5. Coil the wires and push into the discharge manifold cavity using care to ensure wires are not
damaged on discharge manifold threads.
7
IMPORTANT: Damage to the electrical conduit wires creates a risk of lethal electrical shock and equipment
failure. Do NOT use equipment if electrical wires have been damaged. Contact FFS for assistance.
6. Tighten the discharge head cover (from hardware pack p/n 400301XXX) in place using a 3/4" ratchet or
breaker bar.
SECURE TO TANK
NOTE: The bottom end-bell of the PMA is not designed to support the weight of the entire pump. Resting or
dropping the pump on this end-bell may damage the plastic end-bell and the plastic pump components inside.
This type of damage is not considered a manufacturing defect under FFS’s warranty.
1. Measure the pump, from the bottom of the threaded riser to the bottom of the pump-motor, and compare
this to the tank measurement, measured from the mounting flange to the inside of tank bottom. The
STP / IST and riser are sized to place the intake (at the bottom of the pump-motor) approximately 5 inches
off the bottom of the tank.
If the difference between the bottom of the pump motor and the bottom of the tank is more
than 6 inches or less than 4 inches, verify that this is the correct pump for this tank installation.
If it is not the correct pump and is outside the above specifications, contact FFS.
2. Apply a non-hardening, UL classified, gasoline-resistant pipe sealing compound to the riser pipe threads.
IMPORTANT: In order to perform a tank-tightness test, make sure you use a thread sealing compound to help
ensure a seal where the riser threads into the tank opening. A lack of seal may also create a place for fuel to leak
into the environment and/or the containment sump.
3. Carefully lower the unit into the tank, and engage the threaded riser of the pump into the threaded flange
on the tank. Tighten the riser into the tank using a large pipe wrench until a water/air tight joint has been
made. Do this by turning in the tightening (clock-wise) direction only.
Turning the pump in the loosening direction during the tightening process may scrape away the
thread sealing compound, making it impossible to perform a tank-tightness test. This may also
create a potential site for fuel to leak into the environment and / or the containment sump.
4. Connect the supply line piping to the discharge port in the discharge manifold assembly. The discharge
port is the 2-inch NPT vertical opening.
8
5. Connect the electrical conduit with approved fittings per NFPA 30, NFPA 30A, and NFPA 70 to the
junction box.
6. Remove the junction box cover (see Figure 15), and remove the compression seal (contractors plug) by
loosening the screw(s) (do not remove screw). A four hole compression seal (contractors plug) is provided
on all units,
On single phase units, there are two power wires, one ground wire and a blank (with celcon rod
supplied to fill forth hole). For three phase units, there are three power wires and one ground
wire.
8. Pull wires from power supply into the junction box and feed through the compression seal (contractors
plug).
9. Replace the compression seal and tighten into place securely. All wiring must be done in
accordance with the National Electrical Code (NEC) or European Norm (EN) and any other local,
state, or federal regulations required.
CAUTION: The compression seal (contractors plug) is not intended to replace the vapor explosion seals
required by the NEC. All materials used between the power supply box and the pump junction box must be
gasoline and oil resistant. Failure to comply with all applicable codes, could result in an unsafe installation.
• SINGLE PHASE UNITS: Connect the ground wire to the lug in the junction box; using the wire nuts
or terminal block supplied (from hardware pack p / n 400301XXX) connect the wires from the power
supply to the orange and black wires in the junction box. A capacitor is required and color-coding is
not necessary.
• THREE PHASE UNITS (except IST or STP units with VS2 or VS4 suffix): Connect the ground wire
to the lug in the junction box. Connect any three wires from the pump to any three wires from the
three-phase power source using the wire nuts or terminal block supplied (from hardware pack p / n
400301XXX). Capacitors are not needed for three phase units. Install a pressure gauge in the line
test port (see Figure 15), turn on the pump, and read the pressure gauge. Turn off the pump at the
power supply, and change the connection of any two wires at the pump. Turn the pump back on
and read the pressure gauge again. The electrical connection that gives the higher reading on the
pressure gauge is the correct one.
• IST UNITS or STP units with a VS2 or VS4 suffix: Connect the ground wire coming from indoors to the
ground lug in the junction box. Connect any three wires from the pump connector assembly to the
three power wires coming from the Variable Frequency Controller (VFC). Capacitors are not needed
for these units. Detailed installation instructions for the VFC should be referenced when connecting
the VFC. These are supplied with the VFC.
NOTE: Terminal blocks are provided for wire connections on ATEX approved pumps. For terminal blocks, strip
5 mm insulation from the end of the wires. Torques terminal screws to 0.4 - 0.45 Nm.
WARNING: Not installing a ground wire increases the risk of lethal electric shock and equipment failure. All
holes of the compression seal (contractors plug) must be filled with wires or a celcon rod to enable it to seal.
9
11. Replace the junction box cover and tighten securely.
CAUTION: The pump discharge manifold has two labeled ports: one for the syphon system and one for
the tank. A piston leak detector must be vented to the tank port (lower port) only. Do not connect a piston leak
detector to the syphon port because this will make the leak detector inoperative, resulting in an increased risk of
contamination of the environment.
12. Connect power to the submersible pump at the electrical supply box.
14. Turn off the dispenser switch. Feel the submersible pump to make sure that the pump has stopped running.
NOTE: If the pump does not turn off when the dispenser switch is turned off, this may indicate an electrical
problem in the dispenser or other wiring error or malfunction. Call this to the immediate attention of a
qualified electrician.
15. Visually check for leaks on the manifold head during pump operation and after.
16. Install a pressure gauge in the line test port to ensure that the STP / IST is providing proper
line pressure.
17. Turn on the STP / IST. While running, the pressure should be above 24 psi (1.65 bar). PMA size will affect psi.
18. Turn off the STP / IST and verify that the line pressure is holding.
20. Turn on the STP / IST and, again, visually check for any leaks.
WARNING: The product installation and use should meet the requirements of GB/T3836.15 standard, the
inspection and maintenance should meet the requirements GB/T3836.16, the product overhauls should meet
the requirements of GB3836.13.
10
Approximate STP/IST Specifications
Operating PMA S.F. Locked Winding Resistance
Model Description
Pressure (PSI) Length (in) Amps Rotor Amps R-B R-O B-O
STP33* 208 / 230 V, 60 Hz, 1 ph 27 16 3.1 11 27 19 8
STP75* 208 / 230 V, 60 Hz, 1 ph 30 18.25 6.1 27 20 17 3
STP150* 208 / 230 V, 60 Hz, 1 ph 32 21 10.5 39 15 13 2
STPH150* 208 / 230 V, 60 Hz, 1 ph 45 21.75 10.5 39 15 13 2
STP200+ 208 / 230 V, 60 Hz, 1 ph 36 23.75 11.4 41 4.6 3 1.8
STPH200+ 208 / 230 V, 60 Hz, 1 ph 46 24.5 11.4 41 4.6 3 1.8
STP75B++ 200 / 250 V, 50 Hz, 1 ph 37 20.5 5.6 23 27 23 4
STP150B++ 200 / 250 V, 50 Hz, 1 ph 38 22.75 8.8 28 16 13 3
STPH150B++ 200 / 250 V, 50 Hz, 1 ph 48 23.25 8.8 28 16 13 3
STP200B‡ 200 / 250 V, 50 Hz, 1 ph 37 25.75 9.5 37 5.5 3.5 2
STPH200B‡ 200 / 250 V, 50 Hz, 1 ph 44 26.25 9.5 37 5.5 3.5 2
STP75C 380-415 V, 50 Hz, 3 ph** 37 19.75 2.1 10 29 29 29
STP150C 380-415 V, 50 Hz, 3 ph** 38 21.75 3.0 14 14 14 14
STPH150C 380-415 V, 50 Hz, 3 ph** 48 22 3.0 14 14 14 14
STP200C 380-415 V, 50 Hz, 3 ph** 37 23.5 4.1 23 11.6 11.6 11.6
STPH200C 380-415 V, 50 Hz, 3 ph** 44 24 4.1 23 11.6 11.6 11.6
IST / STPVS2^ 190 V, 70 Hz, 3 ph† 24-42 20 6.7 N/A 2.5 2.5 2.5
ISTVS4 / STPVS4^^ 190 V, 70 Hz, 3 ph† 24-42 25 14.4 N/A 1.2 1.2 1.2
Symbols:
* Use a 15 µF, 370 V, single phase, 60 Hz capacitor
+ Use a 40 µF, 370 V, single phase, 60 Hz capacitor
++ Use a 15 µF, 440 V, single phase, 50 Hz capacitor
‡ Use a 40 µF, 440 V, single phase, 50 Hz capacitor
† 190 V, 70 Hz, 3 ph power to variable speed units is output from IST-VFC or MagVFC only (VFC’s are
powered by 200-250 V, 50 or 60 Hz, single or 3 phase input)
^ Use with EcoVFC or MagVFC controller only, No Capacitor
^^ Use with Mag/EcoVFC controller only, No Capacitor (3 phase input is required for full VS4 output))
** No capacitor is used with 3 phase pump motor assemblies
NOTE: The models listed in the table above may contain (ANZ) for ANZEX certified pumps, or either (ATXF) or
(ATXF1)ATEX certified pumps.
FFS’s STPs are designed for use with motor fuels and are UL listed for blend concentrations of:
Standard Models AG (Alcohol / Gasoline) Models
0% - 10% ethanol with gasoline 0% - 85% ethanol with gasoline
20% MTBE with 80% gasoline 20% MTBE with 80% gasoline
20% ETBE with 80% gasoline 20% ETBE with 80% gasoline
17% TAME with 83% gasoline 17% TAME with 83% gasoline
100% Diesel 0-20% BioDiesel Blend or 100% Biodiesel
NOTE: Diesel, fuel oil, avgas, jet fuel, or kerosene may also be used with our PMAs. The maximum liquid
viscosity for a product is 70 S.S.U. at 60° F.
NOTE: Using our PMA in liquids other than those mentioned above has not been tested. The reaction of other
liquids with seals and wetted surfaces of the pump is unknown. A hazardous situation may result from using
other liquids with our pump.
11
MANUAL PRESSURE RELIEF
The manual line pressure relief is in the center of the stationary manifold under a brass cap. You must relieve the
pressure in the piping when you perform maintenance or troubleshooting.
Remove the brass cap at the top of the stationary manifold, and turn the pressure relief screw counter-clockwise
until you reach the screw’s retaining ring (about 4 turns). This allows the pressure in the piping system to bleed
back to the storage tank. Next, turn the screw clockwise to its original position to close the path. (Do not over
tighten.) Replace the brass cap. Line side pressure is now relieved, and maintenance or troubleshooting can
be performed.
CLAMP VALVE (CHECK VALVE CLAMP)
The clamp valve is directly above the check valve inside the stationary manifold of the submerged pump. It
consists of a lead screw with a sealing disk attached. The head of the screw is accessible by removing the 1/4"
line test port pipe plug on the check valve cover of the STP / IST.
NOTE: The cavity under the 1/4" pipe plug is at full pump pressure and product will be released through this
opening. If the pump is equipped with a manual pressure relief, use it to relieve line pressure prior to removing
the plug.
For normal operation, rotate the clamp valve counter-clockwise where a star washer locks it in place. Be sure to
replace the 1/4" pipe plug. During a line test, the clamp valve should be rotated fully clockwise, where the sealing
disk secures against the check valve. This blocks the pressure relief valve in the check valve so it does not
relieve line pressure back to the tank.
TIGHTENING STP MANIFOLD FITTINGS
FFS recommends that NPT threaded STP pipe fittings should be assembled using a non-hardening, UL
classified, gasoline resistant pipe sealing compound. Fittings should be installed hand tight and then tightened
until wrench tight without exceeding 3 turns for fittings up to and including 2” and 2 turns for larger fittings. To
ensure proper installation, the joint must be pressurized and checked that there is no leakage. This check is
essential and must be the specification for making sure a joint is properly assembled.
12
WIRING DIAGRAM 1
WARNING: The Lockout switch is not a substitute for proper lock-out and tag-out of electrical circuit
breakers while installing or servicing this equipment or related equipment.
13
WIRING DIAGRAM 2
3-Phase
Power Supply Box
Control
Switch
Voltage source to
energize coil
A1
Factory-Installed
Jumper
A2
Reset extends
through cover
95 96
Motor Green
Motor Black
Motor Red
14
Intentionally Blank
15
PMA, RISER AND CHECK VALVE FOR VL AND FIXED LENGTH
Item Model Description Qty
1 400125001 3/16" × 15/8" spiral pin 1
2 400615001 Manual relief plug (400615002 AG compatible) 1
3 400211114 O-ring, MPR plug 1
4 400627001 Retaining ring, MPR 1
5 400616001 Manual relief screw (400616002 AG Compatible) 1
6 400333012 Relief screw, top O-ring 1
7 400333007 Relief screw, bottom O-ring 1
8 400628901 Manual relief plug assembly, includes items #2 and #3 (400628902 AG compatible) 1
9 400629901 Manual relief screw assembly, includes items #4, #5, #6, and #7 (400629902 AG compatible) 1
400259001 ¼" NPT pipe plug, may be purchased locally
10 3
403499001 ¼" NPT pipe plug, may be purchased locally (stainless steel, for AP models)
11 400137937 Syphon check valve -
400221930 Discharge manifold, includes #1, #8, #9, and two #10 1
12
400221931 Discharge manifold (includes item #1, #8, #9, and #10) (for AP models) -
151213930 156" lead assembly
13 1
151213932 240" lead assembly
14 Purchase locally Stationary vapor tube, 3/8 OD × 7/20 WT -
Riser, 4½" OD × 3/16" WT steel tubing (consult factory for lead times for 31"-60" lengths)
7" - 19"
4001689XX
20" - 30"
(XX = length)
31" - 49"
50" - 60"
15 1
Riser, 4½" OD × 4.12" ID (stainless steel, for AP models) consult factory for lead time
7" - 19"
4035229XX
20" - 30"
(XX = length)
31" - 49"
50" - 60"
16 Purchase locally ½" steel banding (stainless steel for AP models) -
400600002 5/16-24 × 7/16" set screw for variable lengths only 3
17
403432002 5/16-24 × 7/16" set screw for VL models only (stainless steel, for AP models) -
18 400333015 Lead assembly O-ring 4
400264009 5/16-18 × 11/8" socket head cap screw, may be purchased locally
19 5/16-18 × 11/8" socket head cap screw, may be purchased locally 4
403506001
(stainless steel, for AP models)
400263004 5/16" high-collar lock washer, may be purchased locally
20 5/16" high-collar lock washer, may be purchased locally 1
403505001
(stainless steel, for AP models)
21 403403001 PMA gasket (403403002 AG/AP compatible) 1
Pump motor assembly, includes item #30
22 PMA XXX 1
(XXX indicates options and horsepower)
400981001 3/8-16 × 1" Hex head screw 2
23
403504001 3/8-16 × 1" Hex head screw (stainless steel, for AP models)
400285002 3/8" standard lock washer, may be purchased locally 2
24
1117703 3/8" standard lock washer (stainless steel, for AP models)
400197930 Manifold assembly cover, includes #10, #26, two #23, and two #24 1
25
400197931 Manifold Assembly Cover (includes item #10, #23, #24, and #26 for AP models)
26 400333238 O-ring, manifold cover (AG compatible) 1
27 400147930 Clamp valve assembly (AG compatible) 1
28 400174930 Check valve spring 1
400988931 Standard check valve, includes item #26 (400988934 AG compatible)
400988932 Model R check valve, (for Veeder-Root™ PLLD) includes item #26 (400988935 AG compatible)
29 1
400988933 Model W check valve, (for Red Jacket PPM4000) includes item #26 (400988936 AG compatible)
402459931 Model 65 psi check valve, AG compatible (for secondary manifolded STPs with Veeder-Root™ PLLD)
30 152350902 PMA hardware pack, includes #21, and four #19 and #20 (152350904 AG compatible) -
AG compatible O-ring kit, includes items #3, #6, #7, and #26 on this page and items #2, #10, #13, #19 and #20
-- 400216905 -
on the Discharge Manifold Assembly page
16
2 8
1
3
4
9
5
6
7
SYPHON PORT
10
11
10
TANK PORT
13
12
10
23
14
24
25
26 15
27
16
28
VL MODELS ONLY
17
18
29 19
20
30
21
22
17
DISCHARGE MANIFOLD ASSEMBLY
1
10
12
3
11 10 13
4
18 14
17
15
16 5
7
6
19
7
20 8
21
LINE TEST PORT 9
14
18
SYPHON CHECK VALVE
11 8 5 2
LOCKOUT SWITCH
3
LINE STARTER
120 V COIL
DISPENSER
S M2 M1 N L1 L2
4
DISPENSER LIGHTS
OPTIONAL
5
NEUTRAL
D
GND
150 W MAX
L1
L2
SV 120/208 OR 240 V
SINGLE PHASE
30 W MAX POWER SUPPLY
6
DISPENSER MANUFACTURER FOR WIRING.
OPTIONAL - USE ONLY IF
POWER IS REQUIRED
TO DISPENSER.
McFarland, WI 53588
400819001 REV
19
11.70"
(297.18 mm)
7.55"
(191.77 mm) R
5.80"
(147.32 mm)
Riser / Column Pipe
Centerline
10.32"
(262.13 mm)
10.65"
(270.51 mm) Leak Detector Port
2" NPT
Syphon Port
¼" NPT
Tank Port
¼" NPT
Discharge Outlet
2" NPT
Riser Pipe
4" NPT
20
Intentionally Blank
Intentionally Blank
22
Intentionally Blank
23
400604005 r24