Input Output Module for R-ION R/TIO

• Compact input/output module for the


R-ION room controller
• Modbus RTU versions (M/TIO)
available
• 220 Vac or 120 Vac powered versions .
• Fused mains power output for field
devices .
• Two-wire combined communication
and power connection to the R-ION
touch screen controller
• Real-time clock Specifications
Time scheduling
Operating voltage 230 VAC +10% -5%, 50/60Hz
120 VAC +10% -5%, 50/60Hz
24 VAC +10% -5%, 50/60Hz
versions available
Dimensions (mm) Power consumption Max 3.5 VA (including R-ION touch screen,
excluding field devices)

Operating Temperature 5..50 ºC


Storage Temperature -25..+75 ºC
Relative Humidity %5...95 Rh, non-condensing

Weight (net / gross) 400 gr / 530 gr


750 gr / 890 gr (aux. 24Vac output versions)
Dimensions 158 x 86 x 60 mm
Installation Standard 35 mm rail mount

Protection IP30 according to EN 60529

Connections Screw terminals, max 1.5 mm² (AWG 16)

Universal inputs 8 inputs


(see table for sensor signal compatibility)

Relay outputs 4 Relays, 230 VAC / 5A


1 Relay, 230 VAC / 10A

Triac outputs 2 Triacs, (0.1A@230VAC / 0.5A@24VAC)

Modulating outputs 4 outputs 0(2)-10 VDC, 2mA max


(2 configurable as digital in)

Expansion port Ribbon cable connection to max 2 relay modules


(RK4)

Versions

Versions Supply Communication


R/TIO-L 24 Vac R-ION proprietary
R/TIO-U 120 Vac R-ION proprietary
R/TIO-H 230 Vac R-ION proprietary
M/TIO-L 220 Vac RS485 Modbus RTU slave
M/TIO-U 120 Vac RS485 Modbus RTU slave
M/TIO-H 230 Vac RS485 Modbus RTU slave

www.ontrol.com.tr KP0111C Subject to change without notice


R/TIO Input Output Module for R-ION
xs

R/MIO Description

General R/TIO modules provide a compact input/output solution for Ontrol's R-ION series programmable
touch-screen room controllers.
This combination greatly simplifies installation on the wall-unit side, as the IO module can be
located close to the terminal unit being controlled, with only communication wiring into the wall unit.
The mains powered versions eliminate the need for additional power-supplies or transformers
further reducing cost and installation labor.
R/TIO also hosts a battery backed-up real-time-clock. Therefore, time schedules can be
implemented directly on the device, fully configurable locally from the connected R-ION or remotely
from a supervisory system.
R/TIO input/output modules are not independently communicating devices. They can only be used
with the Ontrol's R-ION touch screen controllers. However, a modbus communicating version
(M/TIO) is also available for use on other systems.
Universal Inputs 8 inputs are provided, configurable as below :

Pt1000 NTC 0-10 VDC Voltage Free


Contact
In 1  
In 2  
In 3  
In 4  
In 5  
In 6   
In 7   
In 8   
Relay Outputs 5 relay outputs are provided. Each relay can be used independently, and a specific set of three can
be configured for 3-speed fan control.
Triac Outputs 2 triac outputs are provided with flexible configuration options, allowing control of on/off
thermoelectric (PWM) or floating actuators or relays. The triacs can be independently configured to
control different loads. However, due to internal connections, all loads must be supplied from the
same AC voltage. Floating (three-position) configuration requires use of both triacs.
Modulating Outputs Four 0-10VDC analog outputs are provided for controlling modulating valve or damper actuators.
Two of these can be configured to function as digital inputs.
Expansion port Up to two RK4 modules can be connected to the device with a ribbon cable, providing a total of 8
additional relay outputs
Real time clock 4 time-schedules can each be independently associated with a relay output through configuration
parameters. Each schedule allows 28 sets of start/stop times per day of the week.

Connections

KP0111C Subject to change without notice www.ontrol.com.tr