Huawei Smart String Ess 2 0mwh de Almacenamiento para PMGD Luna2000 2 0mwh 1h0 1h1 2h1 1 Min
Huawei Smart String Ess 2 0mwh de Almacenamiento para PMGD Luna2000 2 0mwh 1h0 1h1 2h1 1 Min
Huawei is a leading global provider of information and communications technology (ICT) infrastructure and smart devices.
With integrated solutions across four key domains – telecom networks, IT, smart devices, and cloud services – we are commit-
ted to bringing digital to every person, home and organization for a fully connected, intelligent world. Huawei's end-to-end
portfolio of products, solutions and services are both competitive and secure. Through open collaboration with ecosystem
partners, we create lasting value for our customers, working to empower people, enrich home life, and inspire innovation in
organizations of all shapes and sizes. At Huawei, innovation focuses on customer needs. We invest heavily in basic research,
concentrating on technological breakthroughs that drive the world forward.
9 44 2
S O L A R .H U A WE I . C O M / EU /
FusionSolar Smart String ESS Solution
DC Cable
AC Cable
Communication
Cable
Smart PV
Management System
Smart ACU
Distribution
Transformer
SO
O LLAARR. .HHUUAA
WWE IE. CI .OC M
OM
LUNA2000-2.0MWH-1H0/1H1/2H1
Smart String ESS
Battery Container
Model LUNA2000-2.0MWH-1H0 LUNA2000-2.0MWH-1H1 LUNA2000-2.0MWH-2H1
DC Rated Voltage 1,200 V 1,250 V 1,250 V
DC Max. Voltage 1,500 V 1,500 V 1,500 V
Nominal Energy
2,064 kWh 2,032 kWh 2,032 kWh
Capacity
Supported Charge &
≤1C ≤1C ≤ 0.5 C
Discharge Rate
Rated Power 344 kW * 6 338.7 kW * 6 338.7 kW * 3
Container
Configuration 6,058 x 2,896 x 2,438 mm 6,058 x 2,896 x 2,438 mm 6,058 x 2,896 x 2,438 mm
(W x H x D)
Container Weight ≤ 30 t ≤ 30 t ≤ 30 t
Operation
-30°C ~ 55°C -30°C ~ 55°C -30°C ~ 55°C
Temperature Range
Storage Temperature
-40°C ~ 60°C -40°C ~ 60°C -40°C ~ 60°C
Range
Operation Humidity
0 ~ 100% (Without Condensation) 0 ~ 100% (Without Condensation) 0 ~ 100% (Without Condensation)
Range
Max. Operating
4,000 m 4,000 m 4,000 m
Altitude
Cooling Method Smart Air Cooling Smart Air Cooling Smart Air Cooling
Configuration of
8 HVACs 8 HVACs 6 HVACs
HVAC
Fire Suppression
FM-200 / Novec 1230™ FM-200 / Novec 1230™ FM-200 / Novec 1230™
Agent
Communication
Ethernet / SFP Ethernet / SFP Ethernet / SFP
Interface
Communication
Modbus TCP / IEC104 Modbus TCP / IEC104 Modbus TCP / IEC104
Protocol
Protection Degree IP55 IP55 IP55
Certificates (more available upon request)
Environment RoHS6
Safety & Electrical IEC62477-1, IEC62040-1, IEC61000-6-2, EN55011, UL9540A, IEC62619, UN3536, etc.
SOLAR.HUA WEI.COM
LUNA2000-1.0MWH-1H1 (Preliminary)
Smart String ESS
Battery Container
Model LUNA2000-1.0MWH-1H1
DC Rated Voltage 1,250 V
DC Max. Voltage 1,500 V
Nominal Energy Capacity 1,016 kWh
Supported Charge & Discharge Rate ≤1C
Rated Power 344 kW * 3
Container Configuration
6,058 x 2,896 x 2,438 mm
(W x H x D)
Container Weight ≤ 20 t
Operation Temperature Range -30°C ~ 55°C
Storage Temperature Range -40°C ~ 60°C
Operation Humidity Range 0 ~ 100% (Without Condensation)
Max. Operating Altitude 4,000 m
Cooling Method Smart Air Cooling
Configuration of HVAC 3 HVACs
Fire Suppression Agent FM-200 / Novec 1230™
Communication Interface Ethernet / SFP
Communication Protocol Modbus TCP / IEC104
Protection Degree IP55
Certificates (more available upon request)
Environment RoHS6
IEC62477-1, IEC62040-1, IEC61000-6-2, EN55011, UL9540A, IEC62619,
Safety & Electrical
UN3536, etc.
SOLAR.HUA WEI.COM
Smart String ESS
Battery Pack & Smart Rack Controller
Battery Pack
General
LUNA2000-2.0MWH-1H1
Model LUNA2000-2.0MWH-1H0 LUNA2000-2.0MWH-2H1
LUNA2000-1.0MWH-1H1(Preliminary)
Cell Material LFP LFP LFP
Pack Configuration 16S 1P 18S 1P 18S 1P
Rated Voltage 51.2 V 57.6 V 57.6 V
Nominal Capacity 320 Ah / 16.38 kWh 280 Ah / 16.13 kWh 280 Ah / 16.13 kWh
Supported Charge & Discharge
≤1C ≤1C ≤ 0.5 C
Rate
Weight ≤ 140 kg ≤ 140 kg ≤ 140 kg
Dimensions (W x H x D) 442 x 307 x 660 mm 442 x 307 x 660 mm 442 x 307 x 660 mm
Efficiency
LUNA2000-2.0MWH-1H1
Model LUNA2000-2.0MWH-1H0 LUNA2000-2.0MWH-2H1
LUNA2000-1.0MWH-1H1
Max. Efficiency 99.0% 99.0% 99.0%
Battery Side
Rated Voltage 1,075.2 V 1,209.6 V 1,209.6 V
Operating Voltage Range 40 V ~ 1,400 V 40 V ~ 1,400 V 40 V ~ 1,400 V
Rated Power Voltage Range 1,075 V ~ 1,320 V 1,075 V ~ 1,320 V 1,075 V ~ 1,320 V
Min. Start Voltage 350 V 350 V 350 V
Bus Side
Max. DC Voltage 1,500 V 1,500 V 1,500 V
Rated Voltage 1,200 V 1,250 V 1,250 V
Rated Current 286.7 A 275.2 A 275.2 A
Rated Power 344,000 W 344,000 W 344,000 W
General
Dimensions (W x H x D) 600 x 270 x 820 mm 600 x 270 x 820 mm 600 x 270 x 820 mm
Weight ≤ 90 kg ≤ 90 kg ≤ 90 kg
Cooling Method Smart Air Cooling Smart Air Cooling Smart Air Cooling
Protection Degree IP66 IP66 IP66
SOLAR.HUA WEI.COM
LUNA2000-200KTL-H0
Smart PCS
99%
98%
L1 L2
97% +
BUS+ = AC
EMI
L1
L2
DC Soft Filter L3
EMI Start
96% Filter Circuit
-
BUS- ~ C
Relay Relay Residual
SPD
Load
SOLAR.HUA WEI.COM
LUNA2000-200KTL-H0
Technical Specifications
Efficiency
Max. Efficiency 99.0%
DC Side
Rated DC Voltage 1,180 V
Max. DC Voltage 1,500 V
Operating DC Voltage Range 1,180 V ~ 1,500 V
Max. DC Current 207.6 A
Max. Number of Inputs 1
AC Side
Rated AC Active Power 200,000 W @40°C
Rated AC Voltage 800 V
Rated AC Grid Frequency 50 Hz / 60 Hz
Max. AC Current 173.2 A
Adjustable Power Factor Range -1 ... +1
Max. Total Harmonic Distortion <3%
Protection
Anti-islanding Protection Yes
AC Overcurrent Protection Yes
DC Reverse-polarity Protection Yes
Insulation Resistance Detection Yes
Residual Current Protection Yes
DC Surge Protection1 Type II
AC Surge Protection1 Type II
Communication
Display LED Indicators, WLAN + APP
USB Yes
Ethernet Yes
General
Dimensions (W x H x D) 875 x 820 x 365 mm
Weight < 95 kg
Operating Temperature Range -25°C ~ 60°C
Cooling Method Smart Air Cooling
Max. Operating Altitude without Derating 4,000 m
Relative Humidity 0 ~ 100%
DC Connector OT/DT Terminal
AC Connector OT/DT Terminal
Protection Degree IP66
Topology Transformerless
SOLAR.HUA WEI.COM
DCBOX-9/5-H0
DC LV Panel
Electrical
Max. Input Voltage 1,500 V
Nominal Input Voltage 1,200 V
Max. Branch Current for Battery Rack Side 321 A
Max. Branch Current for PCS Side 193 A
Number of DC Circuit Breaker 14
Max. Input Number of Battery Rack 9
Max. Input Number of PCS 5
Max. Convergence Capacity 5 x 193 A
Protection
DC Overcurrent Protection Yes
Environment
Operating Temperature Range -30°C ~ 60°C
Relative Humidity 0 ~ 100%
Max. Operating Altitude 4,000 m
General
Cable Entries Top in for PCS & Bottom in for Battery Rack
Dimensions (W x H x D) 2,040 x 1,415 x 975 mm
Weight (Without Smart PCS) ≤ 750 kg
DC Connector / AC Connector OT Terminal
Protection Degree IP55
Installation Options Grounding
SOLAR.HUA WEI.COM
DTS-200K-D0
Distribution Transformer
Electrical
AC Power 210 kVA@ 400 Vac / 4 kVA@ 110 Vac
Rated Input Voltage 800 Vac
Max. Input Current at Nominal Voltage 151.6 A
Rated Output Voltage 400V (3P) /110V (1P)
Rated Frequency 50 / 60 Hz
Transformer Type Dry Type
Transformer Cooling Type AF
Transformer Vectoring Group Dyn11yn11
Transformer Tappings ± 2 x 2.5%
Transformer Winding Al
Transformer Insulation Class H
Transformer Impedance (at 145°C) 4%(±10%)@50Hz / 4.8%(±10%)@60Hz
Transformer No-load Loss ≤ 500 W (+15%)
Transformer Load Loss ≤ 3,044 W (+15%)
Cablings
Number of outputs Five MCCBs, each connected to two outputs
Cabling mode Routed in and out from the bottom
Protection
Protection Degree IP 55
LV SPD Type II
Transformer Protection Transformer Temperature Protection
Environment
Operating Temperature Range - 25℃ ~ 55℃ (-13°F ~ 131°F)
Relative Humidity 0% ~ 95%
Max. Operating Altitude 4,000 m
General
Dimensions (W x H x D) 900 x 2,100 x 1,200 mm
Weight < 1.3 t
Communication Mode Dry Contacts
Cooling Type Smart Cooling without Air-across for Higher Availability
Applicable Standards IEC 60076, IEC 61439
SOLAR.HUA WEI.COM
JUPITER-9000K-H0(Preliminary)
Smart Transformer Station
Simple Efficient
Prefabricated and Pre-tested, No Internal Cabling Needed Onsite High Efficiency Transformer for Higher Yields
Compact 20’ HC Container Design for Easy Transportation Lower Self-consumption for Higher Yields
Smart Reliable
Real-time Monitoring of Transformer, LV Panel and RMU Robust Design against Harsh Environments
High Precision Sensor of LV Electricity Parameters Optimal Cooling Design for High Availability and Easy O&M
Remote Control of ACB and MV Circuit Breaker Comprehensive Tests from Components, Device to Solution
Schematic Diagram
Transformer
LV Panel RMU
SOLAR.HUA WEI.COM
JUPITER-9000K-H0
Technical Specifications(Preliminary)
Input
Available Inverters SUN2000-200KTL / SUN2000-215KTL / SUN2000-185KTL / LUNA2000-200KTL
Max. LV AC Inputs 44
1
AC Power 9,000 kVA @40℃ / 8,250 kVA @50℃
Rated Input Voltage 800 V
LV Main Inputs ACB (4000 A / 800 V / 3P, 2 x 1 pcs), MCCB (250 A / 800 V / 3P, 2 x 22 pcs)
Output
Rated Output Voltage 22 kV, 30 kV, 33 kV 2 34.5 kV 2
Frequency 50 Hz 50 Hz
Transformer Type Oil-immersed, Conservator Type
Transformer Cooling Type ONAN
Transformer Tappings ± 2 x 2.5%
Transformer Oil Type Mineral Oil (PCB Free)
Transformer Vector Group Dy11-y11
Transformer Min. Peak Efficiency Index Tier 1 or Tier 2 In Accordance with EN 50588-1
RMU Type SF6 Gas Insulated
RMU Transformer Protection Units MV Vacuum Circuit Breaker Units
RMU Cable Incoming / Outgoing Units Direct Cable Unit or Cable Load Break Switch Unit
Auxiliary Transformer Dry Type Transformer, 3 kVA, li0
Output Voltage of Auxiliary Transformer 400 / 230 Vac or 220 / 127 Vac
Protection
Transformer Monitoring & Protection Oil Level, Oil Temperature, Oil Pressure and Buchholz
Protection Degree of MV & LV Room IP 54
Internal Arcing Fault of STS IAC A 20 kA 1s
MV Relay Protection 50/51, 50N/51N
LV Overvoltage Protection Type I+II
Anti-rodent Protection C5 Medium in accordance with ISO 12944
Features
2 kVA UPS Optional 3
General
Dimensions (W x H x D) 6,058 x 2,896 x 2,438 mm (20’ HC Container)
Weight < 28 t
Operating Temperature Range -25℃ ~ 60℃ 4 (-13°F ~ 140°F)
Relative Humidity 0% ~ 95%
Max. Operating Altitude 2,000 m 5 2,500 m 5
SOLAR.HUA WEI.COM
STS-6000K-H1
Smart Transformer Station
Simple Efficient
Prefabricated and Pre-tested, No Internal Cabling Needed Onsite High Efficiency Transformer for Higher Yields
Compact 20’ HC Container Design for Easy Transportation Lower Self-consumption for Higher Yields
Smart Reliable
Real-time Monitoring of Transformer, LV Panel and RMU Robust Design against Harsh Environments
High Precision Sensor of LV Electricity Parameters Optimal Cooling Design for High Availability and Easy O&M
Remote Control of ACB and MV Circuit Breaker Comprehensive Tests from Components, Device to Solution
Schematic Diagram
Transformer
LV Panel RMU
SOLAR.HUA WEI.COM
STS-6000K-H1
Technical Specifications
Input
Available Inverters / PCS SUN2000-200KTL / SUN2000-215KTL / SUN2000-185KTL / LUNA2000-200KTL
Maximum LV AC Inputs 34
1
AC Power 6,800 kVA @40℃
Rated Input Voltage 800 V
LV Main Switches ACB (2900 A / 800 V / 3P, 2 x 1 pcs), MCCB (250 A / 800 V / 3P, 2 x 17 pcs)
Output
Rated Output Voltage 11 kV, 15 kV, 20 kV, 22 kV, 30 kV, 33 kV, 35 kV 2 13.8 kV, 34.5 kV 2
Frequency 50 Hz 60 Hz
Transformer Type Oil-immersed, Conservator Type
Transformer Cooling Type ONAN
Transformer Tappings ± 2 x 2.5%
Transformer Oil Type Mineral Oil (PCB Free)
Transformer Vector Group Dy11-y11
Transformer Min. Peak Efficiency Index Tier 1 or Tier 2 In Accordance with EN 50588-1
RMU Type SF6 Gas Insulated
RMU Transformer Protection Units MV Vacuum Circuit Breaker Units
RMU Cable Incoming / Outgoing Units Direct Cable Unit or Cable Load Break Switch Unit
Auxiliary Transformer Dry Type Transformer, 5 kVA, Dyn11
Output Voltage of Auxiliary Transformer 400 / 230 Vac or 220 / 127 Vac
Protection
Transformer Monitoring & Protection Oil Level, Oil Temperature, Oil Pressure and Buchholz
Protection Degree of MV & LV Room IP 54
Internal Arcing Fault Classification of STS IAC A 20 kA 1s
MV Relay Protection 50/51, 50N/51N
LV Overvoltage Protection Type I+II
Anti-rodent Protection C5 Medium in accordance with ISO 12944
Features
2 kVA UPS Optional 3
General
Dimensions (W x H x D) 6,058 x 2,896 x 2,438 mm (20’ HC Container)
Weight < 22 t
Operating Temperature Range -25℃ ~ 60℃ 4 (-13°F ~ 140°F)
Relative Humidity 0% ~ 95%
Max. Operating Altitude 1,000 m 5 1,500 m 5
SOLAR.HUA WEI.COM
STS-3000K-H1
Smart Transformer Station
Simple Efficient
Prefabricated and Pre-tested, No Internal Cabling Needed Onsite High Efficiency Transformer for Higher Yields
Compact 20’ HC Container Design for Easy Transportation Lower Self-consumption for Higher Yields
Smart Reliable
Real-time Monitoring of Transformer, LV Panel and RMU Robust Design against Harsh Environments
High Precision Sensor of LV Electricity Parameters Optimal Cooling Design for High Availability and Easy O&M
Remote Control of ACB and MV Circuit Breaker Comprehensive Tests from Components, Device to Solution
Schematic Diagram
Transformer
LV Panel RMU
SOLAR.HUA WEI.COM
STS-3000K-H1
Technical Specifications
Input
Available Inverters / PCS SUN2000-200KTL / SUN2000-215KTL / SUN2000-185KTL / LUNA2000-200KTL
Maximum LV AC Inputs 17
1
AC Power 3,400 kVA @40℃
Rated Input Voltage 800 V
LV Main Switches ACB (2900 A / 800 V / 3P, 1 pcs), MCCB (250 A / 800 V / 3P, 17 pcs)
Output
Rated Output Voltage 11 kV, 15 kV, 20 kV, 22 kV, 30 kV, 33 kV, 35 kV 2 13.8 kV, 34.5 kV 2
Frequency 50 Hz 60 Hz
Transformer Type Oil-immersed, Conservator Type
Transformer Cooling Type ONAN
Transformer Tappings ± 2 x 2.5%
Transformer Oil Type Mineral Oil (PCB Free)
Transformer Vector Group Dy11
Transformer Min. Peak Efficiency Index Tier 1 or Tier 2 In Accordance with EN 50588-1
RMU Type SF6 Gas Insulated
RMU Transformer Protection Units MV Vacuum Circuit Breaker Units
RMU Cable Incoming / Outgoing Units Direct Cable Unit or Cable Load Break Switch Unit
Auxiliary Transformer Dry Type Transformer, 5 kVA, Dyn11
Output Voltage of Auxiliary Transformer 400 / 230 Vac or 220 / 127 Vac
Protection
Transformer Monitoring & Protection Oil Level, Oil Temperature, Oil Pressure and Buchholz
Protection Degree of MV & LV Room IP 54
Internal Arcing Fault Classification of STS IAC A 20 kA 1s
MV Relay Protection 50/51, 50N/51N
LV Overvoltage Protection Type I+II
Anti-rodent Protection C5 Medium in accordance with ISO 12944
Features
2 kVA UPS Optional 3
General
Dimensions (W x H x D) 6,058 x 2,896 x 2,438 mm (20’ HC Container)
Weight < 15 t
Operating Temperature Range -25℃ ~ 60℃ 4 (-13°F ~ 140°F)
Relative Humidity 0% ~ 95%
Max. Operating Altitude 1,000 m 5 1,500 m 5
SOLAR.HUA WEI.COM
SmartACU2000D
Smart Array Controller
Configuration
SmartLogger SmartLogger3000B x 1
SmartModule1000A Optional
RS485 Supported
Number of MBUS Module ¹ 1
Number of SmartPID2000 Module 0
Environment
Operating Temperature Range -40°C ~ 60°C (-40°F ~ 140°F)
Relative Humidity 4% ~ 100%
Max. Operating Altitude 4,000 m (13,123 ft.)
Electrical
AC Input Voltage for Cabinet 100 V~240 V, L / N (L)+ PE
AC Input Voltage for MBUS 380 V ~ 800 V, 3Ph
AC Input Voltage for PID 380 V ~ 800 V, 3Ph + FE (Functional Earth)
AC Input Frequency 50 Hz / 60 Hz
Power Supply Standard: 12 V DC, Optional: 24 V DC2
Mechanical
Cable Entries Bottom in & out
Maintenance Front
Dimensions (W x H x D) 640 x 770 x 315 mm (25.2 x 30.3 x 12.4 inch)
Weight 29 kg (63.9 lb.)
Protection Degree IP65
Installation Options Wall Mounting, Rack Mounting, Pole Mounting
SOLAR.HUA WEI.COM
Smart PVMS
Network Structure
Web Email
Internet
Internet
Ethernet Web
RS485 or MBUS ¹
Smart PVMS
Internet
SmartLogger SmartLogger
SOLAR.HUA WEI.COM
Smart PVMS Server Standard Version
Database Gauss DB
Network Ports Two PCIe NICs, each supporting four GE electrical ports
Weight 29 kg
SOLAR.HUA WEI.COM
Smart PVMS Server Premium Version
Internal Storage 2 * 1.2 TB + 8 * 1.8 TB, SAS 2.5” HDD, 10,000 RPM
Database Gauss DB
Network Ports Two PCIe NICs, each supporting four GE electrical ports
Weight 30 kg
SOLAR.HUA WEI.COM
Copyright © Huawei Technologies Co., Ltd. 2022. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means
without prior written consent of Huawei Technologies Co., Ltd.
Trademark Notice
, HUAWEI, and are trademarks or registered trademarks of Huawei Technologies Co., Ltd.
Other trademarks, product, service and company names mentioned are the property of their respective owners.
General Disclaimer
The information in this document may contain predictive statements including, without limitation, statements
regarding the future financial and operating results, future product portfolio, new technology, etc. There are a
number of factors that could cause actual results and developments to differ materially from those expressed or
implied in the predictive statements. Therefore, such information is provided for reference purpose only and
constitutes neither an offer nor an acceptance. Huawei may change the information at any time without notice.
The text and figures reflect the current technical state at the time of printing. Subject to technical changes. Errors and om issions excepted. Huawei assumes no liability for mistakes or printing errors. For more information, please
visit solar.huawei.com. Version No.:01-(201902)
SOLAR.HUAWEI.COM