Din rail mounted energy meter modbus

address

This manual is applicable to the product model

-DDS1946-2P

-DDSF1946-2P

ELECNOVA

1
Content

1. MODBUS-RTU COMMUNICATION ............................ 3


1.1 MESSAGE FORMAT..................................................... 3
1.2 COMMUNICATION ADDRESS INFORMATION TABLE ........... 5
2. DL/T 645 COMMUNICATING PROTOCOL ............... 21
2.1 TRANSFER CHARACTERISTIC .................................... 21
2.2 APPLICATION DESCRIPTION ....................................... 24
2.3.2 variable data ................................................... 29
2.3.3 parametric data............................................... 29
2.4 DL/T 645-2007 COMMUNICATING PROTOCOL ............ 31
2.4.1 electric energy data ........................................ 32
2.4.2 variable data ................................................... 33
2.4.3 parametric data............................................... 34

2
1. Modbus-RTU communication
1.1 Message format
Read data register value (function code 0x03/0x04)

numeric data code


addre
frame Start check
ss FC Number of
structure register code
code registers
address
occupied
1byte 1byte 2byte 2byte 2byte
master byte
request 1 ~
data area 0x03/0x04 Max 100 CRC16
247
examples
of 0x00 0xC5
0x01 0x03 0x00 0x06
message 0x00 0xC8
s
addre numeric data code
frame check
ss FC Register register
structure code
code bytes value
occupied
Slave 1byte 1byte 2byte 12byte 2byte
byte
response
examples
of
0x01 0x03 0x0C 12 CRC16
message
s

Note: The start register address of the host request is the data
header address of the query. The number of the registers is the

3
length of the query data. For example, the address of the upper start
register is the "0x0000", and the number of the registers is 6
(0x0006).

Write setting register (function code 0x10)


numeric data code
frame address Start Number
FC check code
structure code register of
address registers
master occupied
1byte 1byte 2byte 2byte 2byte
request byte
data area 1~247 0x10 0x0802 Max 100 CRC16
examples
0x00
of 0x01 0x10 0x08 0x02 0x2FE2
0x06
messages
numeric data code
frame address
FC Register register check code
structure code
bytes value
Slave occupied
1byte 1byte 2byte 12byte 2byte
response byte
examples
0x00
of 0x01 0x10 0x08 0x02 0xA269
0x01
messages

Note: Please set the information address table in strict accordance


with the following instrument when writing the setting register. Do not

4
attempt to modify the unused area. The write data does not allow
the setting range to be exceeded. The wrong write-setting register
has the potential to cause the instrument to work abnormally. Be
careful.

1.2 Communication address information table


Data register:

Address Format Data description Unit R/W


0000-0001 float voltage V R
0002-0003 float current A R
0004-0005 float active power kW R
0006-0007 float reactive power kvar R
0008-0009 float apparent output kVA R
000A-000B float power factor -- R
000C-000D Float frequency Hz R
000E-000F float positive active energy kWh R
0010-0011 float Reverse active power kWh R
0012-0013 float Forward reactive kvarh R
power
0014-0015 float reverse reactive kvarh R
energy
0016-00FF -- -- -- --
0100 Int Time (high bytes: R
year, low bytes:
month)

5
0101 Int Time (high bytes: day, R
low bytes: hours)
0102 Int Time (high bytes: R
minutes, low bytes:
seconds)
0103 Int Time (high bytes: R
week)
0104-0105 -- -- -- --
0106-0107 Long positive active energy 10Wh R
0108-0109 Long Reverse active power 10Wh R
010A-010B Long Forward reactive 10varh R
power
010C-010D Long reverse reactive 10varh R
energy
010E-010F Long apparent energy 10VAh R
0110-0111 Long first-quadrant 10varh R
reactive power
0112-0113 Long Second quadrant 10varh R
reactive power
0114-0115 Long third quadrant 10varh R
reactive power
0116-0117 Long fourth-quadrant 10varh R
reactive power
0118-0119 Long Active electric energy 10Wh R
[total]
011A-011B Long active energy[sharp] 10Wh R
011C-011D Long Active electric energy 10Wh R
[peak]

6
011E-011F Long Active power[flat] 10Wh R
0120-0121 Long Active electricity 10Wh R
[valley]
0122-0123 Long Active electricity 10Wh R
[total] this month
0124-0125 Long Active power of this 10Wh R
month[sharp]
0126-0127 Long Active power of this 10Wh R
month[Peaks]
0128-0129 Long Active power of this 10Wh R
month[Ping]
012A-012B Long Active power of this 10Wh R
month[Gu]
012C-012D Long Active electricity 10Wh R
[total] last month
012E-012F Long Active electricity [tip] 10Wh R
last month
0130-0131 Long last month active 10Wh R
energy[peak]
0132-0133 Long Active electricity [flat] 10Wh R
last month
0134-0135 Long last month active 10WH R
electric energy[valley]
0136-0137 Long Active electricity 10Wh R
[total] last month
0138-0139 Long The last month was 10Wh R
active [sharp].
013A-013B Long last month active 10Wh R

7
energy[peak]
013C-013D Long Last month active 10WH R
energy[Ping]
013E-013F Long Active electricity 10Wh R
[valley] last month
0140-01FF -- -- -- --
0200 Int voltage 0.1V R
0201 Int current 0.01A R
0202 Int active power 10W R
0203 Int reactive power 10var R
0204 Int apparent output 10VA R
0205 Int power factor 0.001 R
0206 Int frequency 0.01Hz R
0207-05FF -- -- -- --
0600 Int Maximum voltage 0.1V R
0601 -- -- -- --
0602 Int Maximum current 0.01A R
0603 Int Maximum active 10W R
power
0604 Int Maximum reactive 10var R
power
0605 Int Apparent power 10VA R
maximum
0606 Int Maximum active 10W R
power demand
0607 Int Maximum reactive 10var R
power requirement
0608 Int Apparent power 10VA R

8
requirement
maximum
0609 Int Maximum voltage of 0.1V R
this month
060A -- -- -- --
060B Int Current maximum of 0.01A R
current month
060C Int Maximum active 10W R
power of this month
060D Int Maximum reactive 10var R
power this month.
060E Int Apparent power 10VA R
maximum this month
060F Int Maximum active 10W R
power demand for
this month
0610 Int Maximum reactive 10var R
power requirement
this month.
0611 Int Maximum apparent 10VA R
power requirement
this month.
0612 Int Current active power 10W R
requirement
0613 Int Current reactive 10var R
power requirement
0614 Int Current apparent 10VA R
power requirement.

9
061C char Time of power-up R
recording (high byte:
times, low bytes:
years)
061D char Time for power-on
recording (high byte: R
month, low byte: day)
061E char Time recorded by
power on (high bytes:
R
time, low bytes:
minutes)
061F char Time recorded by
programming (high
bytes: number of R
times, low bytes:
year)
0620 char Programming
recording time (high
R
bytes: month, low
bytes: day)
0621 char Time to program the
record (high byte:, R
low byte: minutes)
0622 char Time to program the
record (high byte:, R
low byte: minutes)
0623 char Time for electricity to
clear zero (high R
bytes: month, low

10
bytes: day)
0624 char Time of energy zero
reset (high
R
bytes:hours, low
bytes:minutes).
FFF6-FFF7 Unsigned Serial number
R
long

Set register:

Data
Address format unit R/W
description
0802 Int high byte: 0x01:circular display R/W
circular !(0x01):Invalid cycle
display
Low bytes: 0x00:U, 0x01:I R/W
power on 0x02:F, 0x03:P
display 0x04:Q, 0x05:S
interface 0x06:PF, 0x07:E
0803 -- -- -- --
0804 Int High bytes: 1-247 (Default: 17) R/W
instrument
communicatio
n address
Low bytes: 0: 300bps R/W
communicatio 1: 600bps
n baud rate 2:1200bps

11
3:2400bps
4:4800bps
5:9600bps (Default)
0805 Int high byte: 0:N,8,1 R/W
data format 1:E,8,1
2:O,8,1
3:N,8,2
0806- -- -- -- --
081F
0820 Int demand item Default P/Q/S R
0821 Int Demand 0:Slip block R/W
working mode 1:Fixed block
0822 Int Demand slip 1~9999s R/W
time (t)
0823 Int Calculation 1~30t R/W
period
required (T)
0824- -- -- -- --
0843
0844 Char First set daily
rate table #1
Fixed 00h:00min R/W
period start
time.
8045 Char Starting time high byte :00-23hour R/W
of the first set lower byte :00-59
of daily fee minute
rates table # 2
8046 Char First set daily High Byte:00-23 R/W

12
rate table # 3 Low byte:00-59
time period
start time
8047 Char Starting time High Byte:00-23 R/W
of the first set Low byte:00-59
of daily fee
rates table # 4
8048 Char Starting time High Byte:00-23 R/W
of the first set Low byte:00-59
of daily fee
rates table # 5
8049 Char First set daily High Byte:00-23 R/W
rate table # 6 Low byte:00-59
time period
start time
804A Char Starting time High Byte:00-23 R/W
of the first set Low byte:00-59
of daily fee
rates table # 7
804B Char Starting time High Byte:00-23 R/W
of the first set Low byte:00-59
of daily fee
rates table # 8
804C Char First set daily High Byte:00-23 R/W
rate table # 9 Low byte:00-59
time period
start time
804D Char First set daily High Byte:00-23 R/W
rate table # 10 Low byte:00-59

13
time period
start time
804E Char First set daily High Byte:00-23 R/W
rate table # 11 Low byte:00-59
time period
start time
084F Char Starting time High Byte:00-23 R/W
of period#12 Low byte:00-59
of the first set
of daily rate
table.
0850 Char Second set of Fixed to 00h:00min. R/W
daily fee rate
table # 1 start
time
0851 Char Second set of High Byte:00-23 R/W
daily rate Low byte:00-59
table # 2 time
period start
time
0852 Char Second set of High Byte:00-23 R/W
daily fee rate Low byte:00-59
table # 3
starting time
0853 Char Second set of High Byte:00-23 R/W
daily rate Low byte:00-59
table # 4 start
time
0854 Char Second set High Byte:00-23 R/W

14
daily rate Low byte:00-59
table #5
period start
time.
0855 Char Second set of High Byte:00-23 R/W
daily fee rate Low byte:00-59
table # 6 start
time
0856 Char Second set of High Byte:00-23 R/W
daily fee rate Low byte:00-59
table # 7 start
time
0857 Char Second set of High Byte:00-23 R/W
daily fee rate Low byte:00-59
table # 8
starting time
0858 Char Second set of High Byte:00-23 R/W
daily rate Low byte:00-59
table # 9 time
period start
time
0859 Char Second set of High Byte:00-23 R/W
daily fee rate Low byte:00-59
table # 10
start time
085A Char Second set of High Byte:00-23 R/W
daily fee rate Low byte:00-59
table # 11
starting time

15
085B Char Second set of High Byte:00-23 R/W
daily fee rate Low byte:00-59
table # 12
start time
085C Char High bytes: # 1 time R/W
First set daily rate
rate table # 1 Low bytes: # 2 time
and # 2 period rate
rate 0-point,1-peak,2-
level,3-valley
085D Char First set daily High bytes: # 1 time R/W
rate table # 3, rate
# 4 period Low bytes: # 2 time
rateFirst set rate
daily rate 0-point,1-peak,2-
table # 3, # 4 level,3-valley
period rate
085E Char High bytes: # 1 time R/W
rate
First set daily
Low bytes: # 2 time
rate table # 5,
rate
# 6 period rate
0-point,1-peak,2-
level,3-valley
085F Char High bytes: # 1 time R/W
First set of rate
daily fee rates Low bytes: # 2 time
# 7, 8 time rate
rates 0-point,1-peak,2-
level,3-valley

16
0860 Char High bytes: # 1 time R/W
First set daily rate
rate table # 9, Low bytes: # 2 time
# 10 period rate
rate 0-point,1-peak,2-
level,3-valley
0861 Char High bytes: # 1 time R/W
First set daily rate
rate table # Low bytes: # 2 time
11, # 12 rate
period rate 0-point,1-peak,2-
level,3-valley
0862 Char High bytes: # 1 time R/W
Second set of rate
daily fee rate Low bytes: # 2 time
table # 1, 2 rate
time rate 0-point,1-peak,2-
level,3-valley
0863 Char High bytes: # 1 time R/W
Second set of rate
daily fee rate Low bytes: # 2 time
table # 3, 4 rate
time rate 0-point,1-peak,2-
level,3-valley
0864 Char High bytes: # 1 time R/W
Second set of
rate
daily fee rates
Low bytes: # 2 time
# 5, 6 time
rate
rates
0-point,1-peak,2-

17
level,3-valley
0865 Char High bytes: # 1 time R/W
The second
rate
set of daily
Low bytes: # 2 time
rates table#7,
rate
#8 period
0-point,1-peak,2-
rates.
level,3-valley
0866 Char High bytes: # 1 time R/W
Second set of rate
daily rate Low bytes: # 2 time
table # 9, # 10 rate
period rate 0-point,1-peak,2-
level,3-valley
0867 Char High bytes: # 1 time R/W
Second set of rate
daily fee rates Low bytes: # 2 time
# 11, 12 time rate
rates 0-point,1-peak,2-
level,3-valley
0868 Char Monthly fee High bytes: January R/W
scale daily fee table
(January, Low bytes: February
February) daily fee table
0869 Char High bytes: March R/W
daily fee table
Monthly rate
Low bytes: April daily
table (March,
fee table
April)
0: the first set of daily
fee rates

18
1: Second set of daily
rates.
086A Char 0: the first set of daily R/W
Monthly fee
fee rates
scale (May,
1: Second set of daily
June)
rates.
086B Char High byte: July day R/W
rate table.
Low Byte: August
Monthly fee
Day Rate Table
scale (July,
0: the first set of daily
August)
fee rates
1: Second set of daily
rates.
086C Char High byte: R/W
September day rate
table.
Monthly rate
Low bytes: October
table
daily fee table
(September,
0: the first set of daily
October)
fee rates
1: Second set of daily
rates.
086D Char High Byte: R/W
Monthly fee November Day Rate
scale Table
(November, Low Byte: December
December) Day Rate Table
0: the first set of daily

19
fee rates
1: Second set of daily
rates.
086E Char Meter reading High Byte:00-23 R/W
day setting Low byte:00-59

20
2. DL/T 645 Communicating protocol
2.1 Transfer characteristic
The main-slave half-duplex communication mode and the
establishment and cancellation of communication links are
controlled by the information frames sent by the main station.
Each frame has a frame starter, which is composed of seven parts:
station address domain, control code, data length, frame
information longitudinal check code and frame Terminator. Each
part consists of a number of bytes.
Half dual port communication mode, baud rate: 1200bps;
Byte format: each byte contains 8-bit binary code, with a
starting bit (0), an even check bit and a stop bit (1). The
transmission sequence as shown in figure 1.D0 is the lowest valid
bit of bytes and D 7 is the highest valid bit of bytes. Pass low first,
then pass high.

0 D0 D1 D2 D3 D4 D5 D6 D7 P 1
Transmission direction

Start bit 8-bit data Parity check bit stop

bit

Figure 1-byte transfer

explain code
frame start 68H
sequence

21
A0
A1
A2
address field A3
A4
A5
frame start 68
control code C
Data length domain L
data field DATA
check code CS
tailed 16H
The frame format is shown below.

Address field A0-A5:2-bit BCD code per byte. The low


address is before and the high address is after. When the address
is 99 99 99 99 99 H, it is the broadcast address.

The communication address uses the table number, and at least 2


bits or more of the low table number bit can be entered to
communicate. Less input can be easily operated.

Control code C: the format of the control code.

D7=0:The command frame sent by the master station.


D7=1:A response frame sent from the station.
D6=0:Answer correctly from the station.

22
D6=1:slave response to abnormal information.
D5=0:No post-read data frame.
D4~D0:Request and answer function code.
00001:read data
00100:Write data
01000:broadcast school
01111:Modify the password
Data length L: the number of bytes in the data field, hexadecimal
number.
The data field data: the data field includes data identification and
data whose structure changes with the function of the control code.
At the time of transmission, the sender adds the 33H process
according to the byte, and the receiver performs the 33H process
according to the byte.
The sum of the modulo 256 of all the bytes prior to the start of the
frame start to the check code, i. e., the binary arithmetic sum of
the bytes, and the overflow value of not more than 256.
The end of the frame information is indicated by the end of the
frame information 16h.
Preamble byte:Before sending frame information, send 1-4 FEHs
to wake up the receiver.
Transmission order: All data items should be first transferred to
lower byte and then high byte.
Transmission response:each communication is started by the
master station sending a request command frame to the slave
station selected according to the address field of the information
frame, and the requested slave station responds according to the
requirements of the control code in the command frame.
The response delay Td:20ms ≤ Td ≤ 500ms after receiving the

23
command frame,
Pause time between bytes Tb: Tb ≤ 500ms
Error control: the byte check is even, the frame check is
longitudinal information checksum, the receiver abandons the
information frame regardless of the parity error or longitudinal
information checksum error, and does not respond.

2.2 Application description


Read data:
Master station request frame
function request read data

Control code C =01H.

Data length L = 02H

Frame format:

Function from station to normal response


Control code C = 81H
Data length L ≤ 02H m (data length)
data frame format

Slave station anomaly response frame


The function receives an illegal data request or no such data from
the station
Control code C = C1H
Frame format:

24
Write data:
Write data request frame
The functional master station requests setting data (or
programming) from the slave station
Control code C = 04H
Data length L ≤ 02H m (data length) password 4 bytes
Frame format:

68 04 DI DI P P P1 P N 16
68H A0 .. A5 L N1 。
。 CS
H H 0 1 An 0N N 2N m H

From the station normal response frame.


the function informs the master station of the result of the
execution of the request command
Control code C = 84H
Data length L = 00H
Frame format:
68 A0 。 。。 A5 68H 84H 00H CS 16H
H
Slave station anomaly response frame
Control code C=C4H
Data length L = 01H
Frame format:
。 68 C4 01 ER
68H A0 A5 CS 16H
。。 H H H R

Broadcast school
Functions Synchronize slave and master station time.
Control code C = 08H

25
Data length L = 06H
Data field YYMMDDhhhmss
Frame format:
6 99 … 9 6 0 06 ss m hh D M Y C 1
8 H 9 8 8 H m D M Y S 6
H H H H H
Note:
1. No response is required when broadcasting school.
2. Broadcasting schools are not allowed to be implemented within
the range of 23 / 50 / 10.
3.School hours can only be allowed once a day, with a range of 30
seconds per minute. The maximum allowable error in broadcasting
school is ±20 minutes.

To modify the password:


Write password request frame
The function changes the current password from the station
Control code C = 0 FH
Data length L = 08H
Data domain PA 0 P 00 P 10 P 20 PAN P 0 NP 1 NP 2 N.
Frame format:
68H A0 … A 68 0 08 P P00 P P P P0 P1N P C 1
5 H F H A0 10 20 A N 2 S 6
H N N H
P00P10P20 is the password of the new password or higher
permission. PA0 represents the password permission:
P0NP1NP2N is the new password or the password to be set, PAN
is the permission of the new password. PA0, the value range of
PAN is 0 to 9, 0 is the higher the permission, the lower the

26
numerical permission.

Radio frozen electricity


Function: freeze the power immediately after receiving the
command from the station.
Control code: C = 05H
Data length: l ≤ 02H
Frame format:
68H 99 … 99 68 05 02 CS 16
H H H H H H

2.3 DL/T 645-1997 Communication Protocol.


2.3.1 Electrical energy data

Identificat Data format length unit Rea writ Data item name
ion code d e
9010 XXXXXX.XX 4 kWh * Positive active electric
energy [total]
9011 XXXXXX.XX 4 kWh * Forward active power
[tip]
9012 XXXXXX.XX 4 kWh * Positive active
energy[peak]
9013 XXXXXX.XX 4 kWh * Positive active power
[flat]
9014 XXXXXX.XX 4 kWh * Positive active
energy[valley]
901F 20 kWh * Forward active power
packet
9020 XXXXXX.XX 4 kWh * Reverse active power
9110 XXXXXX.XX 4 kvarh * Forward reactive
power

27
9120 XXXXXX.XX 4 kvarh * reverse reactive
energy
9130 XXXXXX.XX 4 kvarh * first-quadrant reactive
power
9140 XXXXXX.XX 4 kvarh * fourth-quadrant
reactive power
9150 XXXXXX.XX 4 kvarh * Second quadrant
reactive power
9160 XXXXXX.XX 4 kvarh * third quadrant
reactive power
9410 XXXXXX.XX 4 kWh * Active electricity [total]
last month
9411 XXXXXX.XX 4 kWh * Active electricity [tip]
last month
9412 XXXXXX.XX 4 kWh * last month active
energy[peak]
9413 XXXXXX.XX 4 kWh * Active electricity [flat]
last month
9414 XXXXXX.XX 4 kWh * last month active
electric energy[valley]
941F 20 kWh * last month active
power data packet
9810 XXXXXX.XX 4 kWh * Active electricity [total]
last month
9811 XXXXXX.XX 4 kWh * The last month was
active [sharp].
9812 XXXXXX.XX 4 kWh * last month active
energy[peak]
9813 XXXXXX.XX 4 kWh * Last month active
energy[Ping]
9814 XXXXXX.XX 4 kWh * Active electricity
[valley] last month
981F 20 kWh * Active power packet
last month
9FFF 88 kWh * All of the above power
packets

28
2.3.2 Variable data
Identific data format length unit read write Data item name
ation
code
B611 XXXX 2 V * voltage
B621 XX.XX 2 A * current
B630 XX.XXXX 3 kW * active power
B640 XX.XX 2 kvar * Total reactive
power
B650 X.XXX 2 0.001 * total power factor
B660 XX.XX 2 kVA * total apparent
power
B680 XX.XX 2 Hz * frequency
B6FF - 15 - * Instantaneous
power packet

2.3.3 Parametric data

Identifica data length unit rea write Data item name


tion code format d
C010 YYMMDD 4 Year, * * Date and This identity
WW month, week code is
day, invalid
week when there
C011 hhmmss 3 Time * * time is no
and duplicate
second rate
C117 DDhh 2 daytime * * Automati function
c meter
reading

29
date
C023 XX 1 * Power meter operation
status word 2 (see note)
C030 NNNNNN 3 imp/kW * * active pulse constant
h
C031 NNNNNN 3 imp/kva * * reactive pulse constant
rh
C032 NNNNNN 6 * * Table No. (Table No.
NNNNNN data is less than 247)
C331 hhmmNN 3 time- * * Period 1 The data
division (start time encoding
rate default is is not valid
00:00) when there
C332 hhmmNN 3 time- * * Period 2 is no
division complex
rate rate
C333 hhmmNN 3 time- * * Period 3 function.
division
rate
C334 hhmmNN 3 time- * * Period 4
division
rate
C335 hhmmNN 3 time- * * Period 5
division
rate
C336 hhmmNN 3 time- * * Time 6
division
rate
C337 hhmmNN 3 time- * * Period 7
division
rate
C338 hhmmNN 3 time- * * Period 8
division
rate
C339 hhmmNN 3 time- * * Period 9
division
rate

30
C33A hhmmNN 3 time- * * Period 10
division
rate
C33B hhmmNN 3 time- * * 11th
division Session
rate
C33C hhmmNN 3 time- * * Period 12
division
rate

Note:

The address of the device and the communication rate shall be


changed, and the communication protocol of the multi-function electric
energy meter shall be in accordance with the DL/ T645-1997
<multifunction electric energy meter communication protocol.

When you change the communication parameters,1 Byte (right) + 3


Byte (password) is required to place the identification code. The default
permissions and passwords are: 00000000.

3 meter running status word 2 [C023] (1: reverse, 0: forward)

Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0


total -- -- -- Total -- -- --
reactive active
directio power
n direction

2.4 DL/T 645-2007 communicating protocol

31
2.4.1 Electric energy data

Identificati data format length unit read write Data item name
on code
00010000 XXXXXX.X 4 kW * Positive active
X h electric energy [total]
00010100 XXXXXX.X 4 kW * Forward active
X h power [tip]
00010200 XXXXXX.X 4 kW * Positive active
X h energy[peak]
00010300 XXXXXX.X 4 kW * Positive active
X h power [flat]
00010400 XXXXXX.X 4 kW * Positive active
X h energy[valley]
0001FF00 20 kW * Forward active
h power packet
00020000 XXXXXX.X 4 kW * Reverse active
X h power
00030000 XXXXXX.X 4 kva * Forward reactive
X rh power
00040000 XXXXXX.X 4 kva * reverse reactive
X rh energy
00050000 XXXXXX.X 4 kva * first-quadrant
X rh reactive power
00060000 XXXXXX.X 4 kva * Second quadrant
X rh reactive power
00070000 XXXXXX.X 4 kva * third quadrant
X rh reactive power
00080000 XXXXXX.X 4 kva * fourth-quadrant
X rh reactive power
00010001 XXXXXX.X 4 kW * Active electricity
X h [total] last month
00010101 XXXXXX.X 4 kW * Active electricity [tip]
X h last month

32
00010201 XXXXXX.X 4 kW * last month active
X h energy[peak]
00010301 XXXXXX.X 4 kW * Active electricity [flat]
X h last month
00010401 XXXXXX.X 4 kW * last month active
X h electric
energy[valley]
0001FF01 20 kW * last month active
h power data packet
00010002 XXXXXX.X 4 kW * Active electricity
X h [total] last month
00010102 XXXXXX.X 4 kW * The last month was
X h active [sharp].
00010202 XXXXXX.X 4 kW * last month active
X h energy[peak]
00010302 XXXXXX.X 4 kW * Last month active
X h energy[Ping]
00010402 XXXXXX.X 4 kW * Active electricity
X h [valley] last month
0001FF02 20 kW * Active power packet
h last month

2.4.2 Variable data

Identifi data length unit read write Data item name


cation format
code
02010 XXX.X 2 V * voltage
100
02020 XXX.XXX 3 A * current
100
02030 XX.XXXX 3 kW * active power
000
02040 XX.XXXX 3 kvar * reactive power
000

33
02050 XX.XXXX 3 kVA * apparent output
000
02060 X.XXX 2 0.001 * power factor
000
02800 XX.XX 2 Hz * frequency
002

2.4.3 Parametric data

charact data length unit read write Data item name


eristic format
encode
d
040001 YYMMDD 4 Year, * * Date and This
01 WW month, week identity
day, code is
week invalid
040001 hhmmss 3 Time * * time when
02 and there is
second no
04000B DDhh 2 daytime * * Automatic duplicat
01 meter e rate
reading function
date
040005 XXXX 2 * Power meter
02 operation status word
2 (see note)
040004 XXXXXX 3 imp/kW * active pulse constant
09 h
040004 XXXXXX 3 imp/kva * reactive pulse
0a rh constant
040004 NNNNNN 6 * * Communication
01 NNNNNN address (data less
than 247)

34
040100 hhmmNN 3 time- * * Period 1 The data
01 division (start time encodin
(up to rate default is g is not
36 00:00) valid
bytes in hhmmNN 3 time- * * Period 2 when
length) division there is
rate no
complex
rate
function.
hhmmNN 3 time- * * Period 3
division
rate
hhmmNN 3 time- * * Period 4
division
rate
hhmmNN 3 time- * * Period 5
division
rate
hhmmNN 3 time- * * Period 6
division
rate
hhmmNN 3 time- * * Period 7
division
rate
hhmmNN 3 time- * * Period 8
division
rate
hhmmNN 3 time- * * Period 9
division
rate
hhmmNN 3 time- * * Period 10
division
rate
hhmmNN 3 time- * * Period 11
division
rate

35
hhmmNN 3 time- * * Period 12
division
rate

Note:

The communication address shall be written and the communication


protocol of the multi-function electric energy meter shall be in
accordance with the DL/ T645-2007 <multifunction electric energy meter
communication protocol.

When you change the communication parameters, a 4 Byte (password)


+ 4 Byte (operator code) is required to place the identification code. The
default password and operator code are: 01010102020202.

3 meter running status word 2 [04000502] (1: reverse, 0: forward)

Bit15 Bit14 Bit13 Bit12 Bit11 Bit10 Bit9 Bit8


leave leave leave leave out leave leave leave
out leave out out out out out
out
Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
reactive leave leave leave active leave leave leave
direction out out out direction out out out

36