Server & IDF Rooms Checklist

Project No: Site Address:


Project Title: Present:
Name of Client Rep: Prepared By:
Client Rep Contact No: Date Prepared:

Checklist Yes No Qty Comments Verified by Date

1. General
i.
Keys Received?

ii.
Hallway Clearance?

iii.
Site photographs taken?

Meter readings checked, agreed, recorded.


iv. Signed by all parties; i.e. room temp? room
humidity? Illumination readings? Testing
and commissioning results available?
v.
As-built drawings availability?

vi. Excess materials hauled? Dust free? White


glove clean?

2. Architectural - Office Space


i.
Ceiling surfaces – In good condition
ii.
Doors & Door Jamb – In good condition
iii.
Walls – In good condition

Page 1 of 8
Server & IDF Rooms Checklist

Checklist Yes No Qty Comments Verified by Date

iv. Raised Floor (High Pressure Laminate) – In


good condition
v. Miscellaneous – Are there any incomplete
works?

3. MEP – Office Space


i. Light Fittings, Installed and In – Working
Condition?
A/C Equipment – Are they installed?
ii. PACU for Server Room (Duty & Standby)
FCU for IDF Room (Duty and Standby)
Auto-change over switch
iii.
Exit Signs – Are they installed?
iv. Plug Points/ General Power Outlet – Are they
installed? Functioning?
v. Light Switches – Are they installed?
Functioning?
A/C Thermostats – Are they installed?
vi.
Functioning?
vii. Emergency Lights – Are they installed?
PA speakers – Are they installed?
viii.
Functioning?

Air Conditioning and Mechanical


Ventilation System
Linear air diffusers (supply) - in good
i
condition?
Square air diffusers (supply) - in good
ii
condition?

Page 2 of 8
Server & IDF Rooms Checklist

Checklist Yes No Qty Comments Verified by Date

Linear air diffusers (return) - in good


iii
condition?
Square air diffusers (return) - in good
iv
condition?
Duct insulation – in good condition?
v
Taped? Clean?
Volume control damper - are they
vi
installed for air balancing? Functionining?
Type of building Air Conditioning System:
• Chilled water AHU (constant
vii volume or VAV)
• Chilled water fan coil unit

Fire damper, Motorised damper installed


viii
(visual check only)?
Water balancing valve installed (visual
ix
check only)?

x Thermostats installed (visual check only)?

Any sign of condensation on:


Duct?
xi
Outlets?
Pipe?
AHU - in good condition (visual check
xii
only)?
VAV box - in good condition (visual check
xiii
only)?

Printed record of space temperature with


xiv
AHU running for at least 2 hours?

Page 3 of 8
Server & IDF Rooms Checklist

Checklist Yes No Qty Comments Verified by Date

Xv Ducting for PACU – installed?

Fire Protection System


Automatic fire suppression system -
i
sighted? Type? Installed? Functioning?
Identify the following locations and their
conditions (visual check only)
ii
 Main shut off valve (state the location)
 Flow switch (state the location)
Smoke detectors - sighted?
iii
Conventional or addressable system?
Heat detectors - sighted?
iv
Conventional or addressable system?
v Manual call points - sighted?
vi Alarm bells / Strobe light - sighted?
Main alarm panel (any fault on area under
vii
site possession)?
Portable fire extinguishers - sighted?
xi
Type?
Magnetic door with interface to fire alarm
xii
system - sighted? Functioning?

Fire stopping on floor and wall


xiii
penetration - in good condition?

Page 4 of 8
Server & IDF Rooms Checklist

Checklist Yes No Qty Comments Verified by Date

Plumbing System
i Any leakage - sighted?
waterproofing - functioning? Tested?
ii Results of flood test for at least 48 hours
presented?
iii Waterline – sighted? Functioning?
iv PACU drain line – sighted? Functioning?

Electrical Power System


Distribution board (DB) - in good
i
condition?
ii socket outlets - in good condition?
iii Electrical raceway - in good condition?
Electrical Twist lock - checked? In good
iv
condition?
v PDU - checked? In good condition?

Electrical Lighting System


i Light Fixture - in good condition?
ii Exit signs - functioning?
iii Emergency lights - functioning?
iv Light switches?

Page 5 of 8
Server & IDF Rooms Checklist

Checklist Yes No Qty Comments Verified by Date

Structured Cabling
i. IT Racks – in good condition?
ii. Patch panels – in good condition?
iii. Cable tie – in good condition?
Cables – in good condition? Harnessed?
iv.
Labelled?

v. Inter rack tie – Installed? Tested?

vi. Grounding system – Installed? Tested?


Coring works – completed? Covered? Fire
vii.
Sealed?

Security System
i.
CCTV – installed? Functional?
ii. Access control devices – installed?
Functional?
iii.
NVR – installed and working?
iv. Access control panels – installed? No stains?
Labeled?

Technology Team Requirements


Sufficient cooling temperature is
i. established 19-25 degrees Celsius / 40-60
humidity levels

Page 6 of 8
Server & IDF Rooms Checklist

Checklist Yes No Qty Comments Verified by Date

Primary and back-up airconditioning unit


ii. are operational (with the timer switchover
in place).
iii. Vendor sign-off for UPS electrical
requirements
iv.
Power sockets are ready
v.
Racks are properly grounded
vi.
Fire suppression should be signed-off.
vii. All fiber connectivity tested between the
MDF and IDF Rooms.
viii.
Clean and dust-free room
ix. All racks are complete and in good
condition.
x. OPTIONAL: Access Control (badge electronic
system) is in place.
xi. OPTIONAL: CCTV is in place outside the
designated area covering the MDF/IDF door

Inspection Conducted by: Accepted by:

W&C Technology W&C Technology

Name of Representative/ Signature W&C Facilities

Date
W&C Security
Contractors & Vendors

Name of Representative/ Signature

Page 7 of 8
Server & IDF Rooms Checklist

Date

Page 8 of 8