Module 04a - Axially Loaded Members of Timber - Part 1
Module 04a - Axially Loaded Members of Timber - Part 1
MEMBERS
ARC 1149
MODULE 04a
TIMBER: AXIALLY LOADED MEMBERS
COLUMNS AND OTHER COMPRESSION MEMBERS
- Columns or Posts
- Vertical wall studs
- Truss members subject to compression
- Horizontal struts for trusses and girders
TIMBER: AXIALLY LOADED MEMBERS
COLUMNS AND OTHER COMPRESSION MEMBERS
- Columns or Posts
- Vertical wall studs
- Truss members subject to compression
- Horizontal struts for trusses and girders
Columns that are long and slender when subjected to an axial compressive force can deflect
laterally/sideways if the applied force exceeds a critical value. This phenomenon is called buckling
𝑆𝑙𝑒𝑛𝑑𝑒𝑟 𝐶𝑜𝑙𝑢𝑚𝑛
𝐹 ≤ 𝐹 𝑐𝑟𝑖𝑡𝑖𝑐𝑎𝑙
TIMBER: AXIALLY LOADED MEMBERS
COLUMNS AND OTHER COMPRESSION MEMBERS
- Columns or Posts
- Vertical wall studs
- Truss members subject to compression
- Horizontal struts for trusses and girders
Columns that are long and slender when subjected to an axial compressive force can deflect
laterally/sideways if the applied force exceeds a critical value. This phenomenon is called buckling
𝑆𝑙𝑒𝑛𝑑𝑒𝑟 𝐶𝑜𝑙𝑢𝑚𝑛
𝐹 > 𝐹 𝑐𝑟𝑖𝑡𝑖𝑐𝑎𝑙
TIMBER: AXIALLY LOADED MEMBERS
DESIGN CONSIDERATIONS
- Axial Compressive Stress
- Slenderness Ratio
- Bending Stress
TIMBER: AXIALLY LOADED MEMBERS
DESIGN CONSIDERATIONS
- Axial Compressive Stress, fc
For prismatic columns where the axial force is applied at the cross-section’s center, we can assume
that the axial force is uniformly distributed throughout the column’s cross-section. The formula for
simple stress is applicable.
𝑃
𝜎=
𝐴
TIMBER: AXIALLY LOADED MEMBERS
SAMPLE PROBLEM 1
A square column is required to support an axial load of 200KN. Using Yakal, 80% Visually stress
graded, with an adjustment factor of 0.9 for compression, determine the following:
1. The reference design value for compression parallel to the grain
2. The allowable stress in compression
3. The smallest column dimension to carry the applied load
200 𝐾𝑁
TIMBER: AXIALLY LOADED MEMBERS
SOLUTION TO SAMPLE PROBLEM 1
A square column is required to support an axial load of 200KN. Using Yakal, 80% Visually stress
graded, with an adjustment factor of 0.9 for compression, determine the following:
1. The reference design value for compression parallel to the grain
𝐹 𝑐 =15.8 𝑀𝑃𝑎
TIMBER: AXIALLY LOADED MEMBERS
SOLUTION TO SAMPLE PROBLEM 1
A square column is required to support an axial load of 200KN. Using Yakal, 80% Visually stress
graded, with an adjustment factor of 0.9 for compression, determine the following:
3. The smallest column dimension to carry the applied load
We first determine the required cross-sectional area of the column by limiting actual stress to the
allowable stress
𝜎=
𝑃 200 𝐾𝑁
𝐴
𝑃
𝐹 𝑎𝑙𝑙𝑜𝑤=
𝐴
200 × 1000
14.22=
𝐴
𝐹 𝑎𝑙𝑙𝑜𝑤= 14.22 𝑀𝑃𝑎
TIMBER: AXIALLY LOADED MEMBERS
SOLUTION TO SAMPLE PROBLEM 1
A square column is required to support an axial load of 200KN. Using Yakal, 80% Visually stress
graded, with an adjustment factor of 0.9 for compression, determine the following:
3. The smallest column dimension to carry the applied load
We first determine the required cross-sectional area of the column by limiting actual stress to the
allowable stress
𝜎=
𝑃 200 𝐾𝑁
𝐴
𝑃
𝐹 𝑎𝑙𝑙𝑜𝑤=
𝐴
200 × 1000
14.22=
𝐴=14064.698 𝑚𝑚 2
𝐴
𝐹 𝑎𝑙𝑙𝑜𝑤= 14.22 𝑀𝑃𝑎
TIMBER: AXIALLY LOADED MEMBERS
SOLUTION TO SAMPLE PROBLEM 1
A square column is required to support an axial load of 200KN. Using Yakal, 80% Visually stress
graded, with an adjustment factor of 0.9 for compression, determine the following:
3. The smallest column dimension to carry the applied load
𝑠=√ 14064.698=118.595 𝑚𝑚
200 𝐾𝑁
𝑢𝑠𝑒𝑎150 𝑥150𝑚𝑚 𝑠𝑞𝑢𝑎𝑟𝑒𝑐𝑜𝑙𝑢𝑚𝑛 𝐴𝑁𝑆
𝐴=14064.698 𝑚𝑚 2
TIMBER: AXIALLY LOADED MEMBERS
DESIGN CONSIDERATIONS
- Slenderness ratio, SR
𝐿𝑒
𝑆𝑅=
𝑑
𝐿 𝑒= 𝐾 𝑒 × 𝐿
TIMBER: AXIALLY LOADED MEMBERS
TIMBER: AXIALLY LOADED MEMBERS
TIMBER: AXIALLY LOADED MEMBERS
TIMBER: AXIALLY LOADED MEMBERS
TIMBER: AXIALLY LOADED MEMBERS
TIMBER: AXIALLY LOADED MEMBERS
TIMBER: AXIALLY LOADED MEMBERS
TIMBER: AXIALLY LOADED MEMBERS
DESIGN CONSIDERATIONS
- Slenderness ratio, SR
[ ( )]
4
1 𝑆𝑅 𝐹 ′ 𝑐=
0.3 × 𝐸
𝐹 ′ 𝑐= 𝐹 𝑐 𝐹 ′ 𝑐 =𝐹 𝑐 1 − ×
3 𝐾 ( 𝑆𝑅 )2
𝐾 = 0.671 √ 𝐸 / 𝐹 𝑐
TIMBER: AXIALLY LOADED MEMBERS
SAMPLE PROBLEM 2
From the previous SAMPLE PROBLEM 1, if the column height is 3m having both end connections as
fixed, using the design section determine the following:
1. The governing slenderness ration
2. If the column is Short, Intermediate, Long, or needs to be revised
3. The allowable stress in compression considering slenderness effects only
4. If the computed section is still safe
200 𝐾𝑁
3𝑚
150 𝑋150𝑚𝑚
TIMBER: AXIALLY LOADED MEMBERS
SOLUTION TO SAMPLE PROBLEM 2
From the previous SAMPLE PROBLEM 1, if the column height is 3m having both end connections as
fixed, using the design section determine the following:
1. The governing slenderness ration
2. If the column is Short, Intermediate, Long, or needs to be revised
3. The allowable stress in compression considering slenderness effects only
4. If the computed section is still safe
𝐿 𝑒= 𝐾 𝑒 × 𝐿
3𝑚
150 𝑋150𝑚𝑚
TIMBER: AXIALLY LOADED MEMBERS
TIMBER: AXIALLY LOADED MEMBERS
SOLUTION TO SAMPLE PROBLEM 2
From the previous SAMPLE PROBLEM 1, if the column height is 3m having both end connections as
fixed, using the design section determine the following:
1. The governing slenderness ration
2. If the column is Short, Intermediate, Long, or needs to be revised
3. The allowable stress in compression considering slenderness effects only
4. If the computed section is still safe
𝐿 𝑒= 𝐾 𝑒 × 𝐿
150 ×150 𝑚𝑚
TIMBER: AXIALLY LOADED MEMBERS
SOLUTION TO SAMPLE PROBLEM 2
From the previous SAMPLE PROBLEM 1, if the column height is 3m having both end connections as
fixed, using the design section determine the following:
1. The governing slenderness ration
2. If the column is Short, Intermediate, Long, or needs to be revised
3. The allowable stress in compression considering slenderness effects only
4. If the computed section is still safe
𝐿𝑒
𝑆𝑅=
𝑑
Since column’s slenderness ratio is greater than 11, we need to solve for the value of K 200 𝐾𝑁
𝐾 = 0.671 √ 𝐸 / 𝐹 𝑐
From the table of reference design values, we’ve obtained the following:
3𝑚
[ ( )]
4
1 𝑆𝑅 𝐹 ′ 𝑐=
0.3 × 𝐸
𝐹 ′ 𝑐= 𝐹 𝑐 𝐹 ′ 𝑐 =𝐹 𝑐 1 − ×
3 𝐾 ( 𝑆𝑅 )2
𝐾 = 0.671 √ 𝐸 / 𝐹 𝑐
[ ( )] [ ( )]
4 4
1 𝑆𝑅 1 13
𝐹 ′ 𝑐 =𝐹 𝑐 1 − × 𝐹 ′ 𝑐 =15.8 1− ×
3 𝐾 3 16.694
3𝑚
𝐹 ′ 𝑐 =13.863 𝑀𝑃𝑎 𝐴𝑁𝑆
𝐹 𝑐 =15.8 𝑀𝑃𝐴
𝐾 =16.694
150 ×150 𝑚𝑚
𝑆 𝑅 =13
TIMBER: AXIALLY LOADED MEMBERS
SOLUTION TO SAMPLE PROBLEM 2
From the previous SAMPLE PROBLEM 1, if the column height is 3m having both end connections as
fixed, using the design section determine the following:
1. The governing slenderness ration
2. If the column is Short, Intermediate, Long, or needs to be revised
3. The allowable stress in compression considering slenderness effects only
4. If the computed section is still safe
We then compare the column’s actual compressive stress considering the applied load and the 200 𝐾𝑁
column’s design section
𝑃 𝑃 200 × 1000
𝜎= 𝑓 𝑎𝑐𝑡𝑢𝑎𝑙 = = =8.889 𝑀𝑃𝑎
𝐴 𝐴 150 ×150
3𝑚
8.889 𝑀𝑃𝑎 <13.863 𝑀𝑃𝑎
𝐹 ′ 𝑐 =13.863 𝑀𝑃𝑎
150 ×150 𝑚𝑚
TIMBER: AXIALLY LOADED MEMBERS
DESIGN CONSIDERATIONS FOR MACHINE GRADED LUMBER
- Slenderness ratio, SR
[ ( )]
4
1 𝑆𝑅 𝐹 ′ 𝑐=
0. 418× 𝐸
𝐹 ′ 𝑐= 𝐹 𝑐 𝐹 ′ 𝑐 =𝐹 𝑐 1 − ×
3 𝐾 ( 𝑆𝑅 )2
𝐾 = 0.792 √ 𝐸 / 𝐹 𝑐
END