Power Network Analysis Notes
Power Network Analysis Notes
The primary winding is connected in delta and the secondary winding is connected in star
with neutral grounded. Thus it can be used to provide 3-phase 4-wire service.
This type of connection is mainly used in step-up transformer at the beginning of
transmission line.
The ratio of secodary to primary line voltage is √3 times the transformation ratio.
There is 30° shift between the primary and secondary line voltages.
Above transformer connection configurations are shown in the following figure.
Open Delta (V-V) Connection
Two transformers are used and primary and secondary connections are made as
shown in the figure below. Open delta connection can be used when one of the
transformers in Δ-Δ bank is disabled and the service is to be continued until the faulty
transformer is repaired or replaced. It can also be used for small three phase loads where
installation of full three transformer bank is un-necessary. The total load carrying capacity
of open delta connection is 57.7% than that would be for delta-delta connection.
Refer to fig (1) and (2), you may see that the primary sides of both transformers are
identical i.e. primary windings of both transformers wrapped in the same direction around
the core.
But in fig (2) you may notice that the secondary winding is wound around the core in the
opposite direction from the secondary winding in fig (1).
Consequently, the voltage induced in the Secondary winding in fig (2) is 180° out of
phase as compared with the induced voltage in secondary in fig (1) and the direction of
secondary current (IS) is opposite from the primary current (IP)
Figure 2.6.4 (b) Primary and Secondary voltage 180° out of Phase
[Source: “‘Electric Machinery Fundamentals” by Stephen J. Chapman, Page: 173]
So we see that
1. The primary and secondary voltage and current are in phase in fig (1)
2. The primary and secondary voltage and current are 180° out of phase in fig (2)
Dot Convention
To eliminate any confusion in the phase relation between primary and secondary
voltage and current, a dot convention has been adopted for transformer schematic
diagrams. Dots are placed on the top of primary and secondary terminals as shown in fig
(3) and (4)
In fig (3), we see that dots are placed at the top in both primary and secondary terminals. It
shows that the primary and secondary current and voltages are in phase. Moreover, the
primary and secondary voltages (VP and VS) have similar sine wave, also the primary and
secondary (IP and IS) currents are same in direction.
The story is opposite in fig (4). We can see that one dot is positioned at the top in
primary terminal and the other one (dot) is placed at bottom of secondary terminal. It
shows that the primary and secondary current and voltages are 180° out of phase. In
addition, the primary and secondary voltages (VP and VS) sine waves are opposite to each
other. Also the primary and secondary currents (IPand IS) are opposite in direction.
EE8301 ELECTRICAL MACHINES-I
ROHINI COLLEGE OF ENGINEERING & TECHNOLOGY
Figure 2.6.5 Phase relation between primary and secondary voltages and currents
[Source: “‘Electric Machinery Fundamentals” by Stephen J. Chapman, Page: 175]