Transmission Line Differencial Protection With Fuzzy Signal Processing Support
Transmission Line Differencial Protection With Fuzzy Signal Processing Support
1. Introduction Id
I d t I op k 2 I bias (k 2 k1 ) I s 2 I d 0 f or I bias t I s 2 (2) Classical (Boolean) logic based on the concept of truth/
falsity cannot effectively cope with the many ambiguities that
with arise during operation of the power system. Therefore, fuzzy
logic is increasingly being used in decision-making, whereas the
iS iR criteria signals are described by membership functions. The use
Id iS iR
I bias (3)
2 of fuzzy logic increases the confidence of the decision-making
where: iS and iR being currents measured at line terminals, Ibias – within an area of uncertainty, since the fuzzy logic can deal
amplitude of bias current, Id – amplitude of differential current, better (as compared to Boolean logic) with suspense and
Iop – relay operating current, In – line nominal load current. missing data. In addition, inferencing with multiple objectives in
The majority of external faults are usually not a big problem such systems is a natural way of processing information – it is
for the differential relay. Generally, CT errors due to saturation therefore utterly possible to use numerous criteria in parallel.
during external faults are compensated for by conventional Fig. 2 presents the structure of the new fuzzy protection. The
stabilized characteristic with adequate slope setting. However, main idea of action relies on fuzzification of differential current
when there is a mismatch in CTs’ load or they have non- Id that is further compared with fuzzy setting obtained on the
identical magnetizing characteristics, a possibility still exists basis of the stabilized characteristic (Fig. 1). Additionally, the
that one of the CTs saturates and not the other, which may lead criterion of phase difference is determined, value of which
to unwanted protection reaction [4].
I-162
1 I min(n) min {I d (n k )} (7)
Digital k 0 y( N / 4) 1
iS(n) filtering 2
Id(n) P(Id(n)) 1 ( N / 4)1
¦ I d (n k )
&
calculation
Fuzzification I av (n) (8)
iR(n) 6 N /4 k 0
of criteria
signals Fuzzy Tripping
comparison decision
I max(n) max {I d (n k )} (9)
k 0 y( N / 4) 1
3 5
Ibias(n), Calculation P(Iop(n))
Fuzzy setting where: N – measuring window length (here N=20).
MF(n) of Iop
An example of how the fuzzification of differential current
4 proceeds is shown in Fig. 3. Based on five samples of magnitude
Phase IP(n) of differential current (Fig. 3a) the adequate values are
comparison calculated according to equations (7), (8) and (9). Next, the
element
triangle membership function is formed as shown in Fig. 3b.
Calculation of Iop (block 3) – the value of operation current is
Fig. 2. Block scheme of the fuzzy adaptive differential calculated according to equations (1) and (2) – based on bias
protection of transmission line current Ibias.
Phase comparison element (block 4) – here the calculated
affects the degree of fuzzification of fuzzy setting. Below the phase difference, (4) or (5), is compared with the operation
various blocks of scheme from Fig. 2 are described in detail. characteristic (see Fig. 4). The adequate threshold values of the
Digital filtering and calculation of criteria signals (block 1) characteristic have been set according to the statistical
– here the main criteria signals (differential current Id (3), bias
current Ibias (3) and phase difference φF) are calculated with use a)
of full cycle Fourier filters. The variable φF can be expressed by 3.5
the formula:
- for asymmetrical faults it is calculated on the basis of 3
negative sequence current since it gives excellent fault
discrimination for such faults [6]: 2.5
i 2S 2
Id [A]
MF 180o arg
i 2R (4)
1.5
ªi º 0.7
ª1 1 1 º ª i L1S ( R ) º
« 0S ( R) » 1« »« » 0.6
« i1S ( R ) » 1 a a 2 » «i L 2 S ( R ) » (6)
3«
P(Id)
I-163
information gained through analysis of generated simulation P(Iop)
signals. The output value IP from phase comparison element 1
influences fuzzification of operation current. If the output value P(Idiff)
is close to 1.0 it indicates an external fault. Otherwise (internal
fault cases) the output is close to 0.0. P
Fuzzy setting (block 5) – based on the actual value of
operation current and information from phase comparison block
P(I)
the fuzzy setting is formed as it is illustrated in Fig. 5. The
parameters G1 and G2 determine the fuzzification of membership
function of fuzzy setting and they can be calculated according
to: P1
0.6
simulative testing in order to prove its efficiency. The basic
system with HV transmission line under study is shown in Fig.
0.4 7. The overhead transmission line is modeled as transposed one
with distributed parameters frequency dependent JMarti model
[8, 9]. The line of 50km length can be divided into two sections,
0.2 so that internal faults (FL) at almost arbitrary location along the
line can be simulated. External faults are those modeled at
0 busbars (location FBS(R) in Fig. 7).
0 20 40 60 80 100 120 140 160 180 The line is supplied from both sides, where the sending
MF [degrees] equivalent system is assumed to be strong (of high short-circuit
power), while the receiving one is weaker. The power flow can
Fig. 4. Operation characteristic for phase difference
be controlled by variable angle of the receiving source.
The transient response of CTs and the correct models in
1
ATP-EMTP simulation are very important for the evaluation of
0,9 high-speed relaying systems [10]. The 5P30 20VA 1000/1A
0,8 CTs were modeled using the TYPE-96 pseudo-nonlinear
element. In this model there is a possibility to set the residual
0,7
P(Iop(n))
Fig. 5. Formation of fuzzy setting Fig. 7. Model of the power system with transmission
I-164
flux in the CT core, which is very important for studying CT a)
saturation effects [3]. 1
[0: restraint 1.0: trip]
Detection
Thorough studies have been performed by varying the 400kV
power system parameters, which resulted in over 20000 0.5
different simulation cases. The parameters being changed as
systems strength, fault type, fault resistance, point on wave, 0
residual flux, etc. 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18
The figures below present testing results fuzzy scheme
proposed and standard differential relay [2] for internal and b)
external fault with CT saturation. 1
Detection
In Figs. 8-11 an example of three phase external fault at busbar [0: restraint 1.0: trip]
FBS with CTs saturation is presented. The CTs get saturated 0.5
especially in phase L1 at sending end (Fig. 8) and the standard
protection based on the stabilized characteristic with fixed 0
settings maloperates, since the differential-restraining trajectory
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18
(phase L1) enters the tripping zone (Fig. 9) and the trip
command is sent to the circuit breakers (Fig. 10a). On the Time (sec)
contrary, proposed algorithm remained fully stable without
Fig. 10. Relay response for L1-L2-L3 external fault (FBR):
issuing false tripping command – it effectively blocks this
a) standard differential protection, b) fuzzy differential
external fault (Fig. 10b).
protection
phase L1 (A)
5 side R external fault cases obtained from EMTP simulation. The testing
0 results proved that the proposed scheme is immune to external
-5 side S faults (zero percent of incorrect operation). Contrary, the
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 standard protection failed for a few percent of external fault
phase L2 (A)
cases.
Currents in
5
The developed adaptive protection scheme has also been
0 tested for the cases of internal faults, for which unambiguous
-5 tripping command should be issued. A case of L1-L2-L3 internal
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 fault (fault resistance 0Ω) at point FL (fault location 7km from
the sending end) is shown in Figs. 11-13. One can notice that
phase L3 (A)
Currents in
5 when an internal fault occurs the CTs at the sending end deeply
0 saturate (Fig. 11). The trajectory Id-Ibias enters the tripping zone
for all three phases and standard protection properly detects this
-5
case (Fig. 13a). The two algorithms (standard and proposed)
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16
detect this internal fault within less than 5ms after fault
Time (sec)
inception.
After analysis of testing results of both protection for over
Fig. 8. Line terminal current waveshapes in case of L1-L2-L3
21000 simulated internal fault cases one can say that average
external fault at busbar (FBR)
time detection of both protections are quite similar.
5
40
phase L1 (A)
Currents in
-20 side R
3.5 -40
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16
3 40
phase L2 (A)
Currents in
20
2.5 Operate 0
2 -20
-40
1.5 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16
40
phase L3 (A)
Currents in
1 Restrain 20
0.5 0
-20
0 -40
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16
Bias current, Ibias [A]
Time (sec)
Fig. 9. Line protection stabilized characteristic and Id-Ibias Fig. 11. Line terminal current waveshapes in case of L1-L2-
trajectory in case of L1-L2-L3 external fault at busbar (FBR) L3 internal fault at point FL
I-165
[4] I. Voloh, B. Kasztenny, C.B. Campbell, " Testing line
35 phase L1 current differential relays using real-time digital
phase L2
phase L3 simulators," in Proc. 2001 IEEE/PES Transmission and
30
Differential current, Idiff [A]
0
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18
Time (sec)
4. Conclusions
5. References
I-166