Switchgear & Protection
Switchgear & Protection
Protection
POWER SYSTEM
Copyright © 2014-2020 TestBook Edu Solutions Pvt. Ltd.: All rights reserved
Download Testbook App
Introduction
A series of device whose main purpose is to protect person & primary electric pow-
er equipment from the effects of faults are known as protection system.
The apparatus or equipment and their associated auxiliaries employed for control-
ling, electrical circuit in the electrical power system is known as “Switchgear”.
Classification of switchgear
Low voltage switchgear High voltage switchgear
Functions of protection
It must identify the abnormal condition
Chances of fault is very high in transmission line as compared to machine & gener-
ator because transmission line are exposed in the environment.
Relay
The material used for fuse elements must have the following properties:
Low cost
The material mainly used for fuse element are tin, lead, silver, copper, zinc,
aluminum, and an alloy of lead and tin. An alloy of lead and tin is used for small
current rating fuses.
For current exceeding 15A This alloy is not used as the diameters of the wire will be
larger and after fusing the metal released will be excessive.
Circuit Breaker
A circuit breaker is a switching device that interrupts the abnormal or fault current.
Its basic function is to interrupt current flow after a fault is detected. So, it functions
as a protective device, overcurrent controlling device as well as a circuit interrupt-
ing device
It is designed based on the basis of maximum fault current (i.e., LLLG or symmet-
rical fault)
Fuse
The fuse wire should have low melting point so that it can get melt when current
more than rated flows in the circuit.
Fusing factor =
Where,
Load interrupter
Load interrupter disconnect the additional load in the system so that load is less
than the rated value.
Load Isolator
Load Isolator is used to Isolate the transmission line and it is connected in series
with load interrupter.
Note
These are finding their best applications in systems at 132 kV and above (up
to 400 kV) with breaking capacity up to 7500 MVA and above.
As the contacts are opened in oil, when the arc strikes, the surrounding oil is
evaporated as hydrogen gas.
Due to high electronegativity, the recovery of dielectric strength after the arc
interruption in the SF6 circuit breaker is very fast.
Ions are obviously much heavier than a free electron and the overall mobility
of charged particles in SF6 gas is much less compared to the other common
gases.
Advantages
4. Minimum maintenance.
Disadvantages
2. Puffer type design of SF6 CB needs high mechanical energy which is almost
five times greater than that of the oil circuit breaker.
These circuit breakers utilize oil as the interrupting media. It reduces the
requirement of oil. That’s why, these are called as minimum oil circuit breakers. As
a result, MOCB has less volume of oil.
There is a difficulty in removing the gases from the contact space in time.
In vacuum circuit breakers or VCB, the arc extinguishing medium is, well Vacuum.
Note
The space within the body surrounding the element is completely packed with a
filling powder
The filling material may be chalk, plaster of Paris, quartz or marble dust and acts as
an arc quenching and cooling medium
Under normal load conditions, the fuse element is at a temperature below its
melting point. Therefore, it carries the normal current without overheating.
When a fault occurs, the current increases and the fuse element melts before the
fault current reaches its first peak.
Advantages
6. They are cheaper than other circuit interrupting devices of equal breaking capacity
Disadvantages
2. The heat produced by the arc may affect the associated switches
Arc phenomenon
The arc is produced between the contacts of the CB provides a gradual transition
from the current carrying of the voltage – Isolating states of the contacts, but it is
dangerous on account of the energy generated in it in the form of heat which may
result in explosive forces.
Arc initiated at the instant of contact separation due to high field gradient or field
ionization.
The conductance of the arc is directly proportional to the number of free electrons
generated during ionization.
The conductance of the arc is directly proportional to the cross-section area of the
arc.
The path of the arc is purely resistive and it is having a negative temperature
coefficient (means if the temperature increases Rarc decreases and vice versa).
Note:
As the path of the arc is purely resistive, we know that for purely resistive elements
the voltage across the element is always in phase with current flowing through the
element. So, the arc voltage produced in the circuit breaker is always in phase with
the current.
Prospective voltage
The voltage developed across the circuit breaker contacts due to transfer of energy is
known as ‘Prospective voltage’.
Recovery voltage
It is the rms value of power frequency voltage
when arc is extinct is recovery voltage.
Recovery voltage =
Where,
Restriking voltage
Vr(max) = 2 ARV
Vr(avg) = ARV
Resistance switching
Resistance switching is used by connecting a resistance across the circuit breakers
contacts to prevent form a very high Voltage (i. e, prospective voltage) appears
across the CB.
Critical value of R
Critical damped
Under damped
Over damped
Breaking Capacity
Breaking capacity = √3 Ibreak Vrated
Where,
Making capacity
Protective relays
The relay ensures the safety of the circuit equipment from any damage which might
be otherwise caused by the fault.
Instantaneous relay
The operation of relay takes place after a very short duration of time
(generally t ≤ 0.1 sec)
Extremely inverse
Relay setting
Note
= Adjustable parameter
K2 = k3 = 0
So, Q = k1 |I|2 – k4
⇒ (pick up current)
K1 = k2 =k4 = 0
Distance Relays
These are the relays which occurs if fault occurs within a certain distance of relay.
Such a distance is called protective zones.
Types
Impedance relay
K3 = k4 = 0
Q = k1 |I|2 – k2 |V|2
Reactance relay
K2 = k4 = 0
⇒ or
Mho relays
K1 = k4 = 0
Note
Buchholz relay
Buchholz relay is a gas actuated relay and it is used to protect the transformer
against all internal faults
It is used in the transformer having the rating higher than 500 kVA
It causes alarm for minor fault and tripping for a major fault
The following fault can cause insulation failure in the stator winding.
Inter-turn fault
The stator winding faults are considered the most dangerous fault, therefore, auto-
matic protection is much necessary to clear the stator winding fault as soon as
possible.
For the protection of alternators against stator winding fault, the Differential meth-
od of Protection or, Merz-Price Protection is most commonly used because of its
greater sensitivity and reliability.
In this method of protection, currents at the two ends of the protected section are
compared.
The difference of the unequal currents under fault conditions is arranged to pass
through the operating coil of the relay. The relay then closes its contacts to isolate
the protected section from the system.
The secondary of each set of current transformers are connected to the star.
The two neutral points and the corresponding terminals of the two-star groups be-
ing connected together by means of a four-core pilot cable.
This pilot cable provided an independent path for the current circulation in each
pair of current transformers and the corresponding pilot P.
The relay coils are connected in star, the neutral point is connected to the current-
transformer common neutral, and the outer ends one to each of the other three
pilots.
The relays are connected across equipotential points of the three pilot wires and
these equipotential points would naturally be located at the middle of the pilot
wires.
In order to nullify the phase shift of the Power transformer (PT), The Current trans-
formers (CT) connected in a reverse configuration.
Overcurrent protection
Overcurrent protection is protection against excessive currents beyond the ac-
ceptable current rating of the equipment. It generally operates instantly magnetic
circuit breakers, fuses and overcurrent relays are commonly used to provide over-
current protection be the line.
When earth fault occurs, the electrical system gets short-circuited and the short-
circuited current flows through the system.
Earth fault relay, earth leakage circuit breaker, and ground fault circuit interrupter
are used for earth fault protection.
Note
Protection of Relay