Magnum Version 8 Manual
Magnum Version 8 Manual
www.mcscontrols.com
MCS Total
Solution
for all your
Control
Needs
Energy Efficient and RoHS Compliant
MCS-MAGNUM-V. 14 REVISION 3.2
The MCS Commitment: Our commitment is to provide practical solutions for the industry’s needs and to be both a leader
and partner in the effective use of microprocessor controls.
(Website contains product descriptions, manuals, software releases, troubleshooting aids, etc.)
All information contained within this document is considered to be proprietary information of Micro Control Systems, Inc.
No information or data from this document shall be published, used, reproduced, transmitted, or disclosed to others
outside your organization without the prior expressed written consent of Micro Control Systems, Inc. This document and
the information contained herein shall be treated as proprietary. Reasonable provisions shall be provided to ensure that this
information remains proprietary by your employees, agents and other personnel that may have access to this document.
Copyright 2015.
2
MCS-MAGNUM-V. 14 REVISION 3.2
Revision Page
3
MCS-MAGNUM-V. 14 REVISION 3.2
4
MCS-MAGNUM-V. 14 REVISION 3.2
1. Table of Contents
1. Table of Contents.....................................................................................................................................................5
2. Introduction to Magnum V14 Software.................................................................................................................10
2.1. Magnum V14 Software Control Point Capacity...........................................................................................10
2.2. Magnum Hardware Supported by Magnum V14 Software .........................................................................10
2.3. About this Manual........................................................................................................................................10
2.4. About the Magnum......................................................................................................................................11
2.5. MCS 485 Network.......................................................................................................................................11
2.6. MCS Ethernet Port .....................................................................................................................................11
3. PC Support Software for Magnum........................................................................................................................12
3.1. Requirements for PC Software....................................................................................................................12
4. Network Connection - Ethernet.............................................................................................................................13
5. Network Connection - Remote..............................................................................................................................14
6. Magnum Displays...................................................................................................................................................15
6.1. Magnum keypad and display.......................................................................................................................15
7. HVAC STATUS Display (MCS-Connect)................................................................................................................18
7.1. CENT Status Display (MCS-Connect).........................................................................................................20
8. Authorization Function..........................................................................................................................................22
9. Magnum Control States.........................................................................................................................................24
9.1. UNIT IN POWER UP (0).............................................................................................................................24
9.2. NO RUN- I/O LOST (2)................................................................................................................................24
9.3. UNIT IN LOCKOUT (3)................................................................................................................................24
9.4. UNIT IS OFF (4)..........................................................................................................................................24
9.5. UNIT IS HOLDING (5).................................................................................................................................24
9.6. UNIT UNLOADING (6) Only HVAC software...............................................................................................25
9.7. UNIT UNLDNG-VANE (6) Only CENT software..........................................................................................25
9.8. UNIT IS LOADING (7) Only HVAC software................................................................................................25
9.9. UNIT IS LOADNG-VANE (7) Only CENT software......................................................................................25
9.10. OFF-SMOKE ALARM (8).............................................................................................................................25
9.11. RUN/STOP SW OFF (9)..............................................................................................................................25
9.12. SCHEDULED OFF (10)...............................................................................................................................25
9.13. OFF- NO FLOW (11)...................................................................................................................................25
9.14. AMBIENT OFF (13).....................................................................................................................................26
9.15. UNIT IS UNLOADED (15)...........................................................................................................................26
9.16. UNIT IS LOADED (16).................................................................................................................................26
9.17. OFF TMP-ICE MADE (17)...........................................................................................................................26
9.18. ECONOMIZER ONLY (18)..........................................................................................................................26
9.19. SWITCHING MODES (19)..........................................................................................................................26
9.20. VaneOpen-SpdHold (19) Only with CENT Software...................................................................................26
9.21. UNIT SMOKE UNLDG (20).........................................................................................................................26
9.22. UNIT OFF UNLDING (21)...........................................................................................................................27
9.23. UNIT DMD UNLDING (22)..........................................................................................................................27
9.24. UNIT HEAT UNLDING (23).........................................................................................................................27
9.25. UNIT UNLDNG-VFD (24) Only with CENT Software...................................................................................27
9.26. UNIT LOADNG-VFD (25) Only with CENT Software...................................................................................27
10. Compressor Control States (number)..................................................................................................................28
10.1. LOST IO LOCKED (0).................................................................................................................................28
10.2. CMP LOCKED OUT (1)...............................................................................................................................28
10.3. SWITCHED OFF (2)....................................................................................................................................28
10.4. UNLD and PMPDWN (3).............................................................................................................................28
10.5. CMP ANTICYCE (4)....................................................................................................................................28
10.6. CMP OFF/READY (5)..................................................................................................................................28
5
MCS-MAGNUM-V. 14 REVISION 3.2
9
MCS-MAGNUM-V. 14 REVISION 3.2
Applications vary from control of a single compressor to complex multiple compressor systems. In all applications,
however, safety and operating efficiency is of primary importance. The controller interface is made to be informative
and meaningful, with built-in logic to prevent unsafe conditions from occurring. This helps reduce or even completely
eliminate nuisance alarms.
HVAC V14 - This software supports all types of compressors except centrifugals. It supports the configuration type
106 Chiller V14 CFG, as well as 109 Loop Control CFG. If this software is loaded into a Magnum with a different
type of configuration file, an invalid configuration type message will be generated.
CENT V14 - This software supports only centrifugal compressors, and requires a configuration type 119 CENT
MAG CFG. If this software is loaded into a Magnum with a different type of configuration file, an invalid configuration
type message will be generated.
These software types are very similar and most topics will apply to both. However, if a topic applies only to one type
it will be labeled as either ‘only HVAC’ or ‘only CENT’.
2.1. Magnum V14 Software Control Point Capacity
■■ Circuits (compressors) up to 20
■■ Steps per Compressor up to 4
■■ Relay Outputs up to 80
■■ Analog Outputs up to 20
■■ Sensor Inputs up to 112
■■ Setpoints 255
■■ Alarms 100
2.2. Magnum Hardware Supported by Magnum V14 Software
The following MCS boards can be connected together through the MCS-I/O communications terminal block:
■■ MCS-Magnum (10 RO’s, 12 SI’s, 4 Digital SI’s, and 4 AO’s)
■■ MCS-RO10 (10 RO)
■■ MCS-SI16-AO4 (16 SI and 4 AO)
The versatility of the Magnum offers the user much flexibility in configuring the controls in an economical way. The
limitation is not the number of boards but the total number of points.
2.3. About this Manual
The purpose of this manual is to document MCS’s V.14 software for the Magnum. This software requires a
configuration type 11 in MCS-Config. Any other type of configuration file will result in an invalid Config message and
the unit will not function.
This manual documents how the Magnum V.14 software functions. Since this is a large manual, it is structured in
logical sections for ease of reference. The Table of Contents will guide you through the sections but you are urged
to read the entire manual. This will provide an understanding of the capabilities of the Magnum Control System and
hopefully introduce other ways that you may benefit from the existing control strategies. Quick Reference sheets
and MCS Specification sheets are provided in the appendixes.
This manual was created using Microsoft Office, Word 2000. A printed copy may be ordered, please refer to our
Price Book. A PDF copy of this manual may be downloaded from our web site at www.mcscontrols.com free of
charge.
10
MCS-MAGNUM-V. 14 REVISION 3.2
An approved OEM of MCS may make copies and / or change any section of this manual to develop custom
documentation for a site where a Magnum controller is installed. In this way, MCS supports the documentation
requirements of individual customer sites.
Each Magnum in the network must be assigned a unique address in the configuration file. This address will be the
key in establishing communications with the appropriate Magnum system. It can be viewed or changed from the
LCD / keypad of the unit with Factory authorization.
Notes:
■■ RS 232 transmissions should not exceed 50’ in length.
■■ RS 485 transmissions should not exceed 1 mile without a repeater.
11
MCS-MAGNUM-V. 14 REVISION 3.2
MCS-Connect provides both local and remote communications to the Magnum independent of software type. Local
communications can be either through an RS485 or Ethernet connection. This program displays the status of the
controller, and changes can be made to the system with proper authorization. Configuration files can be transmitted
to or received from a Magnum unit. The Magnum automatically performs history logging and this program allows the
data to be presented in a useful graph form. A manual created in a PDF format is available on our web site: www.
MCScontrols.com, or available in other formats upon request.
To install and run the program we suggest the following system requirements:
12
MCS-MAGNUM-V. 14 REVISION 3.2
Ethernet Network
etwork
Windows & MCS-CONNECT
S-CONNECT
ERNET CABLE
RJ-45 ETHE
13
MCS-MAGNUM-V. 14 REVISION 3.2
Serial Connectio
n
MCS-485 GATEWAY
EM
OD
-M
CS
M
MCS-USB-RS232 CABLE
E
Remote PC with
Windows & MCS-CONNECT
M
14
MCS-MAGNUM-V. 14 REVISION 3.2
6. Magnum Displays
The following is an examination of all the information screens that can be accessed through both the Magnum
keypad and MCS-Connect program.
Press
15
MCS-MAGNUM-V. 14 REVISION 3.2
6.1.4 Purge
4.1.5.Status
Purge Screen (only if(only
Status Screen Purge cycles
if Purge are active)
cycles are active)
ACTUAL DISPLAY DESCRIPTION
17
MCS-MAGNUM-V. 14 REVISION 3.2
Relay
Outputs
Analog Outputs
Unit Status
The status of the Capacity Control States, Compressor Control States and EXV Control States can be viewed
from MCS-Connect by clicking the “Status” screen in the Unit Status quadrant. The following screen will be
displayed:
18 17
MCS-MAGNUM-V. 14 REVISION 3.2
The Control Status for centrifugal compressor portion of the Status screen is shown below.
20
MCS-MAGNUM-V. 14 REVISION 3.2
21
MCS-MAGNUM-V. 14 REVISION 3.2
8. Authorization Function
The authorization code is a special four-character code that enables access to the Magnum controller.
The code may consist of any valid alpha/numeric characters if the system is being accessed through MCS-Connect,
however, the code must be numeric with values between 1 and 8 if it is to be entered through the Keypad/Display.
Each Magnum can have up to 10 different authorization codes, with four levels of authorization which provide
differing levels of functionality. The authorization code and the associated level cannot be viewed or changed
through the Keypad/Display or MCS-Connect, but only when the configuration file is opened in MCS-Config. The
authorization codes should be protected and remain confidential, or unauthorized personnel may gain access to the
system and perhaps cause irreparable damage.
Based upon the authorization level the following changes can be made through the Keypad/Display:
FUNCTION VIEW USER SERVICE SUPERVISOR FACTORY
Sensor offsets NO NO YES YES YES
Sensor diagnostics NO NO YES YES YES
Clear alarm history NO NO NO NO NO
Clear point information NO NO NO NO NO
Date and time set YES YES YES YES YES
Day of week set YES YES YES YES YES
Change No Flow Lockout or shut down NO NO NO NO YES
Change rotate Yes or No NO NO NO NO YES
Change Manual/Auto settings NO NO NO YES YES
Change Setpoint values * * * * YES
Change operating schedules NO NO YES YES YES
Change holiday dates NO NO YES YES YES
Lockout Reset ** ** ** ** YES
Change RS485 network settings NO NO NO YES YES
Change Ethernet network settings NO YES YES YES YES
Adjust Keypad/Display contrast YES YES YES YES YES
Transmit Software NO NO YES YES YES
Transmit/Receive Configuration NO NO YES YES YES
* Setpoints may have individual authorization levels; you must have the proper authorization to view or edit them.
**See the Setup screen of the configuration for authorization level(s) that are allowed unlimited resets per day.
Authorization levels below ‘Auth Level Bypass’ are allowed only a limited number of resets. Authorization levels at
and above ‘Auth Level Bypass’ are allowed unlimited lockout resets.
22
MCS-MAGNUM-V. 14 REVISION 3.2
23
MCS-MAGNUM-V. 14 REVISION 3.2
As we review the various states, we must remember that a chiller package consists of a number of different parts
or functions: the compressors and their related items such as unloaders hot gas bypasses, etc.; evaporator; and
condensing functions.
Both the Capacity Control States and Compressor Control States are displayed in the Status screens on the Keypad
Display. To view the state of the chiller, select the Status option from the menu on the Keypad. You can then view
the entire status by using the page up / down function keys. The information can also be accessed through MCS-
Connect under status screen by clicking on the CONTROL STATUS button.
4.1. Unit Control States (number)
Note: All User Logic points can now access the Unit Control State. The value accessed is the number listed in
parenthesis in the following headings.
3) The temperature is below the control zone but the Rate of Change is greater than the (MAX ROC+, #28)
Setpoint. This indicates that the temperature is increasing toward the target. Therefore, no reduction in cooling is
needed at this time.
This state indicates that there is no need to adjust the capacity of the chiller package. This state will end when more
or less capacity is required.
25
MCS-MAGNUM-V. 14 REVISION 3.2
26
MCS-MAGNUM-V. 14 REVISION 3.2
27
MCS-MAGNUM-V. 14 REVISION 3.2
The action of the compressor control states may result in an increase or decrease in capacity. The Unit Control
States may affect or change the Compressor Control States or supersede them altogether.
28
MCS-MAGNUM-V. 14 REVISION 3.2
All of the following conditions must be met within the time allowed in Setpoint #41 “LUBE DELAY”. If the compressor
type is centrifugal an additional 10 seconds will be allowed for these conditions to be met.
1. Oil differential must be equal to or greater than the value in Setpoint #40 “LUBE OIL PSI”. If this Setpoint is not
active this test is bypassed.
2. Oil temperature must be equal to or greater than the calculated oil temperature target. If Setpoint #39 “LUBE
OIL TEMP” is not active this test is bypassed. If the compressor type is centrifugal and the option to use the
saturated temperature is indicated, then the value of the saturated temperature will be added to Setpoint #39
“LUBE OIL TEMP”, else the value of Setpoint #39 will be used by itself as the calculated oil temperature target.
3. The compressor must be unloaded. If there is an unloaded indicator it must be on. If it is a centrifugal
compressor, it is forced to stay in this state for minimum of 15 seconds. If the compressor has no unloaded
indicator it must stay in this state for a minimum of 10 seconds less than Setpoint #41 “LUBE DELAY”.
If all of these conditions are met within the allotted time, the compressor will move to another state.
If a fixed step compressor with an external oil pump the state will either be UNLOADED or LOADED, depending if
there are multiple compressor steps.
If a variable step compressor, then the percentage wanted on will be checked. If it is less than Setpoint #31 “MIN
SLIDE %”, or option “Use Min FLA” has been selected, the percentage wanted will be set to the value in Setpoint
#31 “MIN SLIDE %” and the state will be set to HOLDING.
If the compressor does not meet all of the conditions it will be LOCKED OUT and an error message will be
generated indicating the reason for the failure: pressure, temperature or time.
29
MCS-MAGNUM-V. 14 REVISION 3.2
30
MCS-MAGNUM-V. 14 REVISION 3.2
Fixed Step Compressors - This state is entered when a fully loaded compressor that has more than one step is
unloading due to high discharge pressure or temperature. One step of capacity will be turned off. The compressor
will remain in this state for a minimum of five minutes before returning to the LOADED state if the high discharge
condition has been corrected.
31
MCS-MAGNUM-V. 14 REVISION 3.2
Variable Step Compressors - Capacity is being held due to high discharge temperature or pressure. Once the
discharge returns to normal operating levels the compressor will return to its normal running state.
Variable Step Compressors - This state occurs after HI AMP UNLDING. It will remain in this state for the time
specified in Setpoint #101 “SAFETY HOLD DELAY”. If the amp draw is less than the FLA Setpoint for this
compressor, it will return to the normal operating state and the compressor will be able to load if necessary. In this
state the compressor will not load but it can be unloaded if needed.
32
MCS-MAGNUM-V. 14 REVISION 3.2
33
MCS-MAGNUM-V. 14 REVISION 3.2
34
MCS-MAGNUM-V. 14 REVISION 3.2
11. Standard
MAGNUM SION 8 MANUAL Control Options
VERS REV
VISION 3.1
7. Stan
The ndard
following Co ontrol
options Op ptions
are specified in MCS-Config when building the configuration. These options are used to
customize the system to meet the individual control requirements.
The
T following options
o are sp
pecified in MCS
S-Config whenn building the cconfiguration. These optionss are
used
u to custom
mize the system to meet the individual con
ntrol requiremeents.
11.1. General Options
■■7.1.
. Genera
Control method alcan
Options
be based upon the control zone or a voltage input indicating the number of stages to be on.
■■ The
control temperature
Control me ethod cansensor b can upon
be based be either
th the returning
he control zone or aleaving
e or voltagesensor.
input indicatin
ng the numberr of
■■ Electronic expansion
stages to be
b on. valves make dynamic adjustments based on capacity changes.
■■ Chilled
Thewater reset
contro from the Building
ol temperature e sensorManagement
can beb eitherSystem
the re (BMS).or lea
eturning aving sensor.
■■ Condenser
control maintaining
Electronic expansion va sufficient
alves make dyndischarge superheat
namic adjustm mentsfor goodo
based onoilcapacity
separation.
cha
anges.
■■ Evaporator
pump
Chilled wa control.
ater reset from the Building Management
M SSystem (BMS S).
■■ Anti-cycle
timers
Condense er(OFF
controltomain
ONntaining
and ONsufficie
to ON).
ent discharge superheat for good oil sepa aration.
■■ Maximum
of 20
Evaporato circuits per
or pump contro Magnum,
ol. with selectable compressor rotation.
■■ Warning
RO (turned
Anti-cycle timerson(OFF
for low
to suction
ON andunload, high discharge unload, etc.).
ON to ON).
■■ Alarm
RO (turned on whenever an alarm is generated).
Maximum of 20 circuits per Magnum, with selectablle compressorr rotation.
■■ Optional
auto rotation
Warning RO
R (turned for compressors.
on for low suction n unload, high h discharge un nload, etc.).
■■ Low
and/or high ambient
Alarm RO (turned on temperature
whhenever an shut
ala down.
arm is generatted).
Optional auto
a rotation fo
or compressors
s.
11.2. Magnum
Control
Low and/o Zone
or high ambien Logic e shut down.
nt temperature
7.2.
The . Magnum
control strategym ControltoZone
is designed modulateLogitheiccompressor(s) capacity to maintain the control sensor reading
within the specified control zone. To accomplish this, the Magnum will constantly monitor the control value, its rate of
The control
change, c and position
strateg
gyinisrelationship
designed toto modulate th
the controlhezone
compresso or(s) capacity
and make tto maintain
adjustments the
e control senso
accordingly. or
reading within the specified
s contrrol zone. To ac ccomplish thiss, the Magnum m will constantly monitor the control
value
The e, its ratefor
strategies of ch
ahange, andsystem,
fixed step pos sitionreciprocating
in relatio
onshipcompressor,
to the ccontrol zone an nd make
reciprocating adjusstments
compressor accor
with an rdingly.variable
inverter,
(slide) step system, or a screw compressor are all slightly different. The variable step system allows for infinite
The strategies
s of capacity
variations for a fixed
while step syystem,
the fixed stepreciproc
system cating
doescompre
not. essor, reciproccating compresssor with an in nverter,
variable (slide) step p system, or a screw compre essor are all sslightly differen
nt. The variable
e step system allows
for infinite variation
ns of capacity while
w the fixed step system d does not.
11.3. Common Definitions
7.2.1. Common
C De
efinitions
11.3.1 Target
The control target is7.2.1.1.
7 specified in
Ta rget #1. This will be the base of developing the control zone.
Setpoint
The control
c target is specified in Setpoint #1. This
T will be the
e base of deve
eloping the con
ntrol zone.
11.3.2 Control Zone
7.2.1.2.
7 Coontrol Zone
The control zone is developed by utilizing two more Setpoints to calculate the upper and lower limits. Setpoint #2
isThe control
c to the
added zone is
s developed
target to determine by
y the
utilizing two more
deadband Setpoint
to the uppertslimit,
to calculate the upper
and Setpoint #3 is and
d lower limits.
subtracted Setpoint
from the target to
#2 is added
determine theto the target
t
deadband totothe
deterrmine
lower the dead
limit. dband to the uupper limit, andd Setpoint #3 is subtracted ffrom the
et to determine
targe e the deadband d to the lower limit.
Example: Setpoint #1 Target = 45
Example:
E Setpoint
S #1 Tarrget = 45
Setpoint #2 Upper Deadband = 1
Setpoint
S #2 Upper Deadband d=1
Setpoint
S #3 Lower
Setpoint Deadband
#3 Lowwer Deadband =1d=1
5.2.1.3. Control Sensor
477
Temperature
46
6 Upper Lim
mit
ne + 1
Control Zon
45
5 Target Control Zo
one
ne - 1
Control Zon
44
4 Lower Lim
mit
43
3
Setpoints #2-18 contain the Cut-In and Cut-Out voltage thresholds. The status screen has been changed to
show the actual voltage on the top line and to indicate voltage control on the bottom line. The step delay between
adjustments is based on Setpoint #26 “STEP DELAY”.
Note: Liquid Injection and EXV logic are both disabled when this option is used.
As stated in the previous section, the control strategy is designed to modulate the system capacity to maintain the
control sensor reading within the specified control zone. The system capacity will be based upon the number of
compressors that are Wanted On. When the first, or an additional compressor, is turned on the system capacity will
be set to the calculated value. For the first compressor this will be the value of Setpoint #31 “MIN FLA %”. When
additional compressors are brought on, their capacity is calculated to provide the same percentage of capacity prior
to the change. The Magnum will adjust the required capacity between the calculated and the maximum value an as
specified in Setpoint #30 “MAX FLA %”. All compressors that are on will be adjusted together to meet the system
capacity.
When the maximum capacity value of the currently operating compressors has been reached, an additional
compressor, if available, will be Wanted On. The number of compressors Wanted On will be increased by one and
the system capacity will be set to the calculated value to maintain the same capacity as before the change and the
sequence will begin again. Once all available compressors are on, their maximum will be 100% regardless of the
value in Setpoint #30 “MAX FLA %”.
When the minimum calculated value has been reached, a compressor will be turned off. This will occur when the
reduced number of compressors can achieve the same capacity at 90%. The number of compressors Wanted On
will be decreased by one and the system capacity will be set to 90% and the sequence will begin again.
The compressor slide control is based upon the amps drawn by that compressor. For example, if Setpoint #31 “MIN
FLA %” is set to 30%, that means 30% of the calculated full load amperage for that compressor.
Screw compressors with slide pistons that are turned on can either be loading (load solenoids are pulsed),
unloading (unload solenoids are pulsed), or in a hold state (no action is taken). The state of each compressor
reflects this action.
36
MCS-MAGNUM-V. 14 REVISION 3.2
The Magnum will control the compressor speed in the same matter as the compressor slide. The same Setpoints
will be used. This allows a fixed staged compressor’s capacity to be varied. See section 13 for Setpoints associated
with variable capacity control logic.
STAGE 1
Compressor 1’s startup procedure has begun. Once on, the capacity will be adjusted from the minimum to the
maximum. All other compressors will be off. The steps Wanted On / Actual On will be 1 / 1.
STAGE 2
Compressor 2’s startup procedure has begun. Once on, the system capacity will be changed to the calculated %
and compressor 1 will be unloaded until it matches the calculated system capacity. Both compressors will be varied
from the calculated to the maximum. All other compressors will be off. The steps Wanted On / Actual On will be 2
/ 2. If the system capacity has been reduced to 45%, or the calculated % (whichever is larger) and less capacity is
needed, a compressor will be turned off and the system capacity will be set to the 90% or the maximum and the
system will return to Stage 1.
STAGE 3
Compressor 3’s startup procedure has begun. Once on, the system capacity will be changed to the calculated %
and compressors 1 and 2 will be unloaded until they equal the required capacity. All compressors will be varied from
the calculated to 100%. The steps Wanted On / Actual On will be 3 / 3. If the system capacity has been reduced to
60%, and less capacity is needed, a compressor will be turned off and the system capacity will be set 90% and the
system will return to Stage 2.
37
MCS-MAGNUM-V. 14 REVISION 3.2
The type of compressor will determine how the compressor is controlled and its particular Relay Output sequence.
38
MCS-MAGNUM-V. 14 REVISION 3.2
In this screen under the MAG V8 screen, compressor type is selected from a drop down list. Additional information
about the compressor and how it will be controlled is also provided in this section. Review all cells and input the
proper information.
The type of compressor will determine how the compressor is controlled and its particular Relay Output sequence.
In this screen under the MAG V8 screen, compressor type is selected from a drop down list. Additional information
about the compressor and how it will be controlled is also provided in this section. Review all cells and input the
proper information.
39
MCS-MAGNUM-V. 14 REVISION 3.2
Compressor information is provided per circuit in this section under the Circuit Base screen. Review all cells and
input the proper information about the compressor.
This screen relates to the above example. The compressor is a variable capacity compressor; therefore, the slide
information must be provided, this is used in calculating the amp draw of the compressor. Note the ‘Type’ column, for
COMP, the first compressor point, Screw NO EXV was selected from the drop down menu.
40
MCS-MAGNUM-V. 14 REVISION 3.2
This screen is an example of a variable capacity, screw, and compressor with EXV valves. Note the Type column
selection. The EXV data must be provided.
This information can be viewed and changed, with proper authorization, from MCS Connect. By double clicking on
the name field the following will be displayed.
Frequency Drive (VFD) it becomes simple and efficient to vary the speed of the compressor and operate at part
load.
To provide control for this unique type of compressor MCS has developed a new type software specific to centrifugal
units: CENT V8. Much of the control logic is similar to that found in HVAC V8. A target value and control zone are
calculated, and then compressor capacity is modulated to keep the control sensor within that zone. Input sensors
are monitored constantly and preventative action is taken to protect the unit from any potentially unsafe or damaging
conditions. Different from other types of units though, both compressor speed and vane position must be taken into
consideration since both affect cooling capacity.
41
MCS-MAGNUM-V. 14 REVISION 3.2
The software will then count the number of compressor surges that occur. If the number of surges is more than the
value in Setpoint #219 “ExcessSurges” within 5 minutes (value of Setpoint #219 ‘Time (sec)’ field) the system will
shut down and generate an “ExcessSurges” alarm. This safety condition will automatically restart the compressor
after the time in the Safety Down Time of the Setpoint #219. If a second “ExcessSurges” occurs within the time of
the Lockout Delay Field, the compressor will be placed in “Cmp Locked Out” state and a manual reset is required to
enable the compressor to restart again.
In the MAG CENT V8 screen the same information is required as for HVAC V8 setup. The compressor type must be
centrifugal.
The VFD for compressor speed control, VFD fault, and Vane Closed Indicator are specified in the Circuit Base
screen if they are used.
In the Circuit SI screen the sensors for the Turbine Inlet Pressure and Vane Position are specified if they are used.
For compressors with a VFD, a Vane Position sensor is required and is used for opening and closing the vanes.
For compressors without a VFD, a Vane Position sensor is optional. If unspecified then the amp sensor is used for
opening and closing the vanes. In the above example the Vane Position sensor is not specified; therefore, the vane
control will be based upon amp draw.
42
MCS-MAGNUM-V. 14 REVISION 3.2
Purge Enable RO – This relay will be turned ON when a purge cycle is active, else it will be off.
Purge Solenoid RO – This relay will be turned ON once the Purge Exhaust Pump has been on for 1 second.
Purge Exhaust Pump RO - This relay will be turned ON when a purge cycle is active, else it will be off.
Purge Mode Switch SI – This input’s type must be MODE SEL SW. This is an external three-way switch that can be
set to:
OFF - in this setting the purge system will not function, the purge state will be SWITCHED OFF.
MANON - in this setting the purge state will be either M-PRG OFF if the system is not purging or M-PRG
RUNNING if a purge cycle is active.
AUTO - in this setting the purge state will be either A-PRG OFF if the system is not purging or A-PRG RUNNING
if a purge cycle is active.
Purge Safety Switch SI - If this switch is on for longer than the value in Setpoint #164 “P-FaultTimer” all purge Relay
Outputs will be locked off and an error message will be generated. This will have no effect on the status of the unit.
43
MCS-MAGNUM-V. 14 REVISION 3.2
Purge Suction Temp SI – This sensor provides the suction line temperature of the auxiliary unit. When a purge cycle
is active this temperature is monitored. If it remains above the value in Setpoint #163 “PurgeTarget” the compressor
will not exhaust any non-condensables from the purge drum. However, if the temperature drops below this value
then the exhaust pump and solenoids must be on to capture the non-condensables.
Mode selection switch in MANUAL position: The suction line temperature of the auxiliary unit must be less than the
value in Setpoint #163 “Purge Target”.
Mode selection switch in OFF position: purge cycles will not run.
FLOAT FAULT - The purge safety switch has been on longer than the value in Setpoint #164 “Purge Fault”. All
purge Relay Outputs will be LOCKED OFF. When this switch returns to the normal off position, the purge Relay
Outputs will be changed to AUTO and the purge state will be either M-PRG OFF or A-PRG OFF.
M-PRG OFF – The mode selection switch is in the MANUAL position. All purge Relay Outputs are OFF. If the
suction line temperature of the auxiliary unit drops below the value in Setpoint #163 “PurgeTarget” the state will be
changed to M-PRG-RUNNING. Note, in this state the status of the compressor is not checked.
M-PRG RUNNING – The purge relay enable and the purge pump are turned on. The purge solenoid will be turned
on 1 second after the pump has started. If the suction line temperature of the auxiliary unit rises above the value
in Setpoint #163 “PurgeTarget” the purge solenoid will be turned off. 1 second later the purge relay enable and the
purge pump will be turned off and the state will be changed to M-PRG OFF,
A-PRG OFF - The mode selection switch is in the AUTO position. All purge Relay Outputs are OFF. If the
compressor is running and the suction line temperature of the auxiliary unit drops below the value in Setpoint #163
“PurgeTarget” the state will be changed to A-PRG-RUNNING. Note, in this state the status of the compressor is
checked.
A-PRG RUNNING - The purge relay enable and the purge pump will be turned on. The purge solenoid will be
turned on 1 second after the pump has started. If the compressor goes off or the suction line temperature of the
auxiliary unit rises above the value in Setpoint #163 “PurgeTarget” the purge solenoid will be turned off. 1 second
later the purge relay enable and the purge pump will be turned off and the state will be changed to A-PRG OFF.
The MCS-MAGNUM accumulates the amount of minutes a purge enable relay has been on for the last 24hrs (This
is a rolling 24hrs window). If (purge enable accumulated on minutes) is greater than the value of Setpoint #165 an
“Excess Purge” alarm is generated and the Warning relay is turned on. The (purge enable accumulated on minutes)
counter is set to zero when a lockout reset has been performed by the user. The Warning light is also turned off.
44
MCS-MAGNUM-V. 14 REVISION 3.2
The compressors set will be treated as one compressor. There will be one common suction pressure, suction
temperature, discharge pressure, and discharge temperature sensor for the package. Each compressor will have an
individual amperage sensor. These must be consecutive inputs.
Chiller states have been allocated for these patterns: “SCROLL STEP 1” through “SCROLL STEP 4”.
Set up compressor:
45
MCS-MAGNUM-V. 14 REVISION 3.2
Staging sequence
COMP A COMP B COMP C COMP D
Stage 1 ON OFF OFF OFF
Stage 2 OFF OFF ON ON
Stage 3 OFF ON ON ON
Stage 4 ON ON ON ON
Set up compressor:
46
MCS-MAGNUM-V. 14 REVISION 3.2
Staging sequence
COMP A COMP B COMP C COMP D
Stage 1 ON OFF OFF OFF
Stage 2 OFF OFF ON ON
Stage 3 OFF ON ON ON
Stage 4 ON ON ON ON
Set up compressor:
47
MCS-MAGNUM-V. 14 REVISION 3.2
The unloading and holding can result from high discharge and low suction pressure and high discharge
temperature.
Low and high amp drawn will be check for all compressors that are on. The standard amp safety checks will be
made and if one occurs the compressor will be off on a safety or a lock out if the same safety reoccurs.
Note, the standard Setpoints are used for all safety checks, unloading, and holding functions.
When this option is enabled, the Magnum will rotate the compressors based upon the value in Setpoint # 104
“CMP ROTATION”
If Setpoint # 104 is zero, rotation will occur with every complete capacity cycle and the next compressor will be
selected as the lead compressor.
If Setpoint # 104 is nonzero, the value is the number of days between rotations. At midnight the Magnum will
check if it is time to rotate compressors. If yes, the Magnum will check the run hours on each compressor and
select the one with the least amount of run hours to be the lead compressor.
If Setpoint # 104 is set up as an ALARM Setpoint type, a compressor rotation message will be generated each
time a compressor is rotated.
To activate this option Setpoint #103 “LEAD COMP” must be set up as follows:
Value: 0 (indicates auto rotation, must be 0)
Time (SEC): 0 (indicates first on first off, must be 0)
Select Value: DIGITAL/SW
Type of Setpoint: Target (must be Target type)
High Zone: 1 (this is the starting compressor following a reset; usually 1)
Low Zone: 1 (number to rotate, will default to 1)
Night Setback: 8 (number of compressors in the first barrel)
48
MCS-MAGNUM-V. 14 REVISION 3.2
If the Value, Time, and Type cells are not set as indicated, normal rotation using Setpoints #103 “LEAD COMP” and
#104 “COMP ROTATION” will be used.
The following examples have 16 compressors, dual barrels with 8 compressors in each. Barrel 1 has compressors
1 through 8 and 9 through 16 are in barrel 2. The wanted/actual ON will function as usual only the rotation and the
sequence of turning on the compressors have been changed.
Example 1: Compressor 1 is the lead capacity calls for 4 circuits to be ON (wanted 4/ actual 4), then reduced to 0/0.
Compressors 1, 2, and 3, then 4 will be turned ON. As capacity is reduced, Compressor 1 will be turned OFF
and the lead will be rotated to Compressor 2. Then Compressors 2, 3, and 4 will be turned OFF with the lead ending
with Compressor 5.
Example 2: Compressor 5 is now the lead and capacity calls for 6 compressors to be ON (6/6) then reduce to 0/0.
Compressors 5, 6, 7, and 8, then 1 and 2 will be turned ON (6/6). As capacity is reduced, Compressors 5, 6, 7,
and 8, then 1 and 2 will be turned OFF (0/0) and Compressor 3 will be the lead. Note, compressors in barrel 2 were
not turned ON.
Example 3: Compressor 3 is now the lead and capacity calls for 12 compressors to be ON (12/12) then reduce to 0/0.
Compressors 3, 4, 5, 6, 7, and 8, then 1 and 2 will be turned ON (8/8). At this point all compressors in barrel 1
are ON, as more capacity is needed Compressors 9 through 16 will be used. Compressors 9, 10, 11, and 12 will
be turned ON to reach 12/12. As capacity is reduced, Compressors 9 then 10, 11, and 12 will be turned OFF (8/8)
at this point. Now, all compressors in barrel 2 are OFF and all compressors in barrel 1 can now be turned OFF if
less capacity is needed. Compressor 3 followed by 4, 5, 6, 7, 8, and 1 then 2 will be turned OFF (0/0). At this point
Compressor 3 is the lead compressor.
If the controller loses power, the length of time that the system was down will be taken into consideration when
determining whether the compressor should be in an anti-cycle state and for how long.
Setpoints #4-#7 INACTIVE - If Setpoints #4-#7 are all inactive, then the HGB is enabled when the machine is
unloaded to within 25% of the minimum slide percentage. The HGB is disabled when the machine rises above 30%
of the minimum slide percentage. (These are just default values that can be overridden in the “Time(sec)” fields of
Setpoints #4 and #5. The “Time(sec)” field of Setpoint #4 contains the minimum slide percentage offset to enable
the HGB; the “Time(sec)” field of Setpoint #5 contains the minimum slide percentage offset to disable the HGB. For
example, if Setpoint #4 “Time(sec)” field has a value of 10 and Setpoint #5’s is15, then the HGB will enable when
the compressors FLA% is within 10% of Setpoint #31 “MIN FLA%” and will disable when FLA% goes above 15%.)
Only Setpoints #4-#5 ACTIVE - The HGB is on when the machine is unloaded and the leaving liquid goes below
the Cut In (Setpoint #4 “HGS TEMP ON”). HGB is turned off when the leaving liquid temperature goes above the
Cut Out (Setpoint #5 “HGS TEMP OFF”) or the machine leaves the unloaded state.
Only Setpoints #6-#7 ACTIVE- The HGB is on when the machine is unloaded and the suction pressure goes
below the Cut In (Setpoint #6 “HGS PSI ON”). HGB is turned off when the suction pressure goes above the Cut Out
(Setpoint #7 “HGS PSI OFF”) or the machine leaves the unloaded state.
Setpoints #4-#7 ACTIVE - If both groups of Setpoints are active, then the HGB is on when the machine is
unloaded and either the leaving liquid temperature or the suction pressure goes below the respective Cut In limit.
The HGB goes off when the machine leaves the unloaded state or both the leaving liquid temperature and the
suction pressure goes above the respective Cut Out limits.
50
MCS-MAGNUM-V. 14 REVISION 3.2
In the Liquid Injection column there is a dropdown menu for each compressor, giving options of No Liquid Injection,
1 Stage, or 2 Stage. If 2 Stage option is selected, the second stage relay must follow the list of available options, it
may not necessarily follow the first stage relay. Refer to section 12 for Relay Output order and options.
The first stage will be turned on if either the discharge temperature is greater than Setpoint #8 or suction pressure is
less than Setpoint #80 plus 5 psi (.5 Bar). If 2 Stage, the second relay will be turned on if the discharge temperature
is greater than Setpoint #8 plus 5.0° F (2.5° C) and the first relay has been on for a time greater that the ‘Time (sec)’
field of this Setpoint. If the Slide Multiplier cell of the Relay Output for the first stage of liquid injection is non-zero,
then this relay will be turned on during the fast unload logic.
OIL PUMP ALWAYS ON – The oil pump will start before the compressor to build up oil pressure and will always
be on when the associated compressor is on. If the oil pressure drops below Setpoint #74 “OIL PUMP OFF”,
then shut down the associated compressor and generate a LOW DIFFERENTIAL alarm. The oil pump will
continue running after the compressor is turned off regardless of the reason, for the time specified in Setpoint
#62 “PUMP DOWN DELAY”.
OIL PUMP CYCLES AS NEEDED – After the compressor has been running for 2 minutes and when the
differential pressure (discharge pressure minus suction pressure) is greater than Setpoint #74 “OIL PUMP OFF”,
then the oil pump will be turned off. If the differential pressure drops 10 PSI below the value of Setpoint #74,
then the oil pump will be turned on again.
OIL PUMP LUBE ONLY – After the compressor has been running for 2 minutes and when the differential
pressure (discharge pressure minus the suction pressure) is greater than Setpoint #74 “OIL PUMP OFF”, then
the oil pump will be turned off. If the differential pressure has not reached Setpoint #74 after 5 minutes, then shut
51
MCS-MAGNUM-V. 14 REVISION 3.2
down the associated compressor and generate a LOW DIFFERENTIAL alarm. If the differential pressure has
been reached and the oil pump turned off, then if the differential pressure drops 5 psi below the value of Setpoint
#74, shut down the associated compressor and generate a LOW DIFFERENTIAL alarm.
For fixed step compressors: The Magnum will turn off one step of capacity of the compressor(s) with low suction
until all steps except one are unloaded. The circuit state will be LO SUCT HOLD. The compressor will remain
in this state until the capacity control indicates that another step is to be unloaded or if the suction pressure has
returned to normal after the time in Setpoint #101 “SAFETY HOLD DELAY” has passed.
For variable step compressors: The Magnum will begin unloading the compressor(s) with low suction until the
suction pressure rises above the calculated value. During this time the circuit state is LO SUCT UNLOAD.
Once this pressure has been reached, the circuit state will be LO SUCT HOLD. The compressor will remain in
this state until the capacity control indicates that another step is to be unloaded or if the suction pressure has
returned to normal after the time in Setpoint #101 “SAFETY HOLD DELAY” has passed.
Normal suction pressure is defined as any value greater than Setpoint #77 “LOW SUCTION” plus Setpoint #79 “LO
SUCT RELD”. Refer to Setpoints #78 and #79 for additional information.
For fixed step compressors: The Magnum will turn off one step of capacity of the compressor(s) with high
discharge until all steps except one are unloaded. The circuit state will be HI DISC HOLD. The compressor will
remain in this state until the capacity control indicates that another step is to be unloaded or if the discharge
pressure has returned to normal after the time in Setpoint #101 “SAFETY HOLD DELAY” has passed.
For variable step compressors: The Magnum will begin unloading the compressor(s) with high discharge until
the discharge pressure drops below the calculated value. During this time the circuit state is HI DISC UNLOAD.
Once this pressure has been reached, the circuit state will be HI DISC HOLD. The compressor will remain in
52
MCS-MAGNUM-V. 14 REVISION 3.2
this state until the capacity control indicates that another step is to be unloaded or if the discharge pressure has
returned to normal after the time in Setpoint #101 “SAFETY HOLD DELAY” has passed.
Normal discharge pressure is defined as any value less than the calculated value of Setpoint #81 “HI DISC PSI”
minus Setpoint #83 “HI DISC RELD” and greater than Setpoint #85 “LO DISC PSI”. Refer to Setpoints #82 and #83
for additional information.
For fixed step compressors: The Magnum will turn off one step of capacity of the compressor(s) with low water
temperature until all steps except one are unloaded. The circuit state will be LO TMP HOLD. The compressor
will remain in that state until the capacity control indicates that another step is to be unloaded or if after 5
minutes the leaving liquid temperature has turned to normal.
For variable step compressors: The Magnum will begin unloading the compressor(s) with low water temperature
until the leaving liquid temperature rises above the calculated value. During this time the circuit state is LO
TMP UNLOAD. Once the leaving liquid temperature rises above the calculated temperature the circuit state will
change to LO TMP HOLD. The compressor will remain in that state until the capacity control indicates that less
capacity is needed or if after 5 minutes the leaving liquid temperature has turned to normal.
Normal leaving liquid temperature is defined as any value more than 3.0F (1.6C) above the freeze safety trip value.
53
MCS-MAGNUM-V. 14 REVISION 3.2
For example if “MAX SLIDE %” is 80% and the “MIN SLIDE %“ is 40%, the two-screw compressor system would be
ramped up as follows:
The Lead compressor will be started at 40% and increased up to 80%. If more capacity is needed the next
compressor will be started at 40% and the first compressor decreased to 40%. The two compressors will then have
their slide positions changed together. Since there are only two compressors, they will be ramped together up to
100% if required. If both compressors are at 40% and less capacity is needed, one compressor will be turned off
and the other increased to 80%.
If running compressors at 100% is not desired, then the “Last Stage to 100% (Override Setpoint)” cell in the
Compressor Information panel of the MAG V8 screen should be set to ‘No’. Then the maximum capacity allowed will
be the value in Setpoint #30. If ‘Yes’, then all compressors will load to the value in Setpoint #30 until all compressors
are on, then they will load to 100% together.
Setpoint #106 “LEAD PUMP” indicates whether the rotation option is active or which pump is the lead pump.
If Setpoint #106 is zero, then rotation of the pumps will occur whenever the lead pump is turned off. If no rotation
has occurred during the current day, a forced rotation at midnight will occur. This forces at least one rotation per day.
If Setpoint #106 is non-zero, then rotation of the pumps is inactive and the value will specify the lead pump. This
Setpoint can be changed in a live unit and the appropriate action will be taken.
The pump information must be set up in the Evaporator Information Panel under the MAG V8 screen. The following
information is required for each pump if used:
Pump Relay Output
Pump VFD Analog Output (if used)
54
MCS-MAGNUM-V. 14 REVISION 3.2
55
MCS-MAGNUM-V. 14 REVISION 3.2
If the unit type is changed, MCS-Config will give you an option to automatically change the values of all items in the
Setpoints to match the new type and will automatically adjust the display characters.
The ratio of discharge pressure divided by suction pressure is calculated. This ratio is blocked between 50 and 22.
The value of Setpoint #115 ”Vi DEADBAND” is added to and subtracted from this ratio to develop a control zone.
The control zone will be recalculated based upon the time in Setpoint #116 ”Vi DELAY”. Refer to Setpoints #117,
#118 and #119. The system will pulse the solenoids to keep the Vi reading within the calculated control zone.
56
MCS-MAGNUM-V. 14 REVISION 3.2
When this option is selected the Reheat Relay Outputs must be setup as follows:
These Hot Gas Reheat relays are required and they must be placed in the proper sequence to work correctly.
The following Setpoints must be active: #129 “RH CUTIN”, #130 “RH CUTOUT ADJ”, #131 “RH START DLY”, #132
“RH BLEED DLY”, #133 “RH STAGE DLY”.(see Section 13 for full Setpoint descriptions).
57
MCS-MAGNUM-V. 14 REVISION 3.2
The third solenoid (economizer) can be controlled either on the slide wanted
percentage or as the last step on for that compressor (Refer to section 13
Setpoints #98 and #99). Liquid line solenoids 2 and 3 will be turned on and off
as indicated in their Setpoints.
If the economizer/fluid cooler has separate fans (not associated with condensers) then
answer yes in the ‘Separate Economizer Fans?’ cell. If Yes, then four additional cells
will appear: ‘Starting Economizer Fan’ (select the first fan Relay Output), ‘# of Econ
Fans’ (specify the number of fan points), ‘Starting Economizer Fault’ (select the first
fan fault, this is a Sensor Input), and ‘# of Econ Faults’ (specify the number of faults)
In the above example there are two fans and two faults associated with the
economizer/fluid cooler. If there is more than one fan they must be consecutive Relay
Outputs. The same is true of the condenser faults.
The condenser fans can also be used to assist in the free cooling function when the system is not using mechanical
cooling. To set this up in the condenser information grid, select “Fluid Cooler Econo” equals “Yes”, else “No” if
condenser fans are not used. All types of condensers can be used. The above example has individual fans per
compressor. Whenever a compressor is running the control of its condenser fans will be based solely on the
discharge pressure of that compressor, while the condenser fans of compressors that are not running will be
controlled by the economizer function. If the type of condenser is common; if any compressor is on all of the fans will
be controlled by the highest discharge pressure and not by the economizer function.
The following Setpoints must be set up: #107 ”EcoDelayMech”, #115 “EcoVFDfanDely“, #119 “EcoOffsetON”, #120
“Eco Stg Dely”, #121 “Eco MIN VLV%”, #122 “Eco MAX VLV%”, #123 “Eco MAX ADJ”, #124 “EcoVlvAdjDly”, #125
“Eco StageDly”, #126 “Eco MULTI”, and #127 “Eco DIVIDE”
(Refer to section 13 for Setpoint descriptions)
If mechanical cooling has not been enabled (no steps are Wanted On or Actual On), when the economizer starts
the Unit State will be ECONOMIZER ONLY. In this state mechanical cooling will not be started until the economizer
58
MCS-MAGNUM-V. 14 REVISION 3.2
function has reached its maximum capacity (Economizer valve is at maximum opening, all available fans are turned
on, and the control temperature is still not in the target zone).
When the economizer logic starts, the Magnum will modulate the Analog Output to the economizer valve to
maintain the control sensor reading within the target zone. The valve will be modulated between Setpoint #121“Eco
MIN VLV%” and Setpoint #122 “Eco MAX VLV%” and will wait the time contained in Setpoint #124 “EcoVlvAdjDly”
before making each adjustment to the valve opening.
If control temperature is above the control target, Setpoints #1, and the control temperature rate of change is
greater than the value of Setpoint #27 “MAX ROC-”:
This indicates that the control temperature is too high and it is not approaching the target fast enough, therefore
the valve opening must be increased if possible. The adjustment value will be the difference between the target
(Setpoint #1) and the control sensor temperature multiplied by Setpoint #126 “Eco MULTI” and divided by
Setpoint #127 “Eco DIVIDE”. If the absolute adjustment is greater than the value of Setpoint #123 “Eco MAX
ADJ”, then it will be limited to this value. The economizer valve opening will be increase by this value.
If control temperature is below the economizer control zone (Setpoint #1 - Setpoint #3) and the control
temperature rate of change is less than the value of Setpoint #28 “MAX ROC+”:
This indicates that the control temperature is too low and it is not approaching the target fast enough, therefore
the valve opening must be decreased if possible. The adjustment value will be the difference between the
target (Setpoint #1) and the control sensor temperature multiplied by Setpoint #126 “Eco MULTI” and divided
by Setpoint #127 “Eco DIVIDE”. If the absolute adjustment is greater than the value of Setpoint #123 “Eco MAX
ADJ”, then it will be limited to this value. The economizer valve opening will be decrease by this value.
If control temperature is above the bottom of control zone (Setpoint #1 - Setpoint #3) but less than the control
target (Setpoint #1) no change to the economizer valve opening will be made.
Once the valve has reached its maximum opening (Setpoint #122), the Magnum will wait the time specified in
Setpoint #125 “Eco StageDly” before checking if there are any fans associated with the economizer function. If
there are the Magnum will stage the fans to maintain the control temperature with in the target zone. If a fan VFD
is present, then this will be modulated in the same manner. The delay between VFD adjustments will be the value
in Setpoint #115 “EcoVFDfanDely” if active, else Setpoint #124 will be used. Once all fans associated with the
economizer function are on, the Magnum will check if any condenser fans can also be used. If yes, then these fans
will then be staged to maintain the control temperature.
Once all the fans and/or VFD have been turned on and the control temperature is still greater than the control zone
for the time specified in Setpoint #107 “EcoDelayMech” if active (else the time in Setpoint #125 “Eco StageDly” will
be used) then mechanical cooling will be enabled.
If the ambient temperature rises above the offset in Setpoint #119 during economizer cooling mode, then the
economizer function will be terminated, its valve opening will be set to zero, and mechanical cooling will be
enabled.
If the control temperature is less than the target temperature (Setpoint #1) minus the 3 times value of Setpoint
#3, then the economizer function will be terminated, its valve opening will be set to zero, and all fans will be
turned off.
If during mechanical cooling mode the ambient temperature drops below the offset in Setpoint #119, then the
economizer function will begin. Note: the Unit State will not change, the economizer valve will be modulated as
described above, fans directly associated with the economizer will be used, and no fans associated with the
condensers will used.
The control rate of change is always checked before an adjustment to the valve is made. The purpose is to not
change the valve opening if the temperature is moving toward the target at an acceptable rate.
59
MCS-MAGNUM-V. 14 REVISION 3.2
The condenser type is common with VFD control and the Fluid Cooler Economizer option has been enabled. The
VFD of the condenser fan will be controlled by the economizer function unless any compressor is running. If a
compressor is running the VFD control will be based upon the highest discharge pressure.
Assume the following setup:
60
MCS-MAGNUM-V. 14 REVISION 3.2
The AO M-1 “3 WAY VLV” will be opened to its minimum valve of 0% (Setpoint #121) and it will be modulated
based upon the control temperature and the target (Setpoint #1). The first adjustment will be 48.5 – 44.0 = 4.5. This
value will be adjusted by multiplier of 3 (Setpoint #126) and divided by 2 (Setpoint #127) to give an adjusted value
of 6.7. This value is blocked; maximum allowed adjustment, by Setpoint #123 to allow an adjustment of 5.0%. The
economizer valve opening will be increased by this amount if the temperature control rate of change is greater than
the value of Setpoint #27.
The economizer function will wait 30 seconds (Setpoint #124) before determining the next adjustment. If the control
temperature is now 47.3F; the following adjustment will be calculated.
47.3 – 44.0 = 3.3 x 3 / 2 = 4.9. Since this is less than 5.0 the valve will be open an additional 4.9% if the temperature
control rate of change is greater than the value of Setpoint #27.
Each adjustment will be made after a delay of 30 seconds. If the control temperature is below the control target
(Setpoint #1) and above the bottom the control zone (43.0F to 44.0F) there will be no change to valve opening.
If the control temperature drops below the control zone the valve opening will be reduced. For example if the control
temperature is 42.6F then the following calculation will be made:
42.6 – 44.0 = 1.4 x 3 / 2 = 2.1. Since this is less than 5.0 the valve opening will be reduced an additional 2.1%.
When the valve reaches its maximum opening of 100.0% (Setpoint #122) the economizer function will use other
fans if they are available. In this example there are no fans that are associated only with economizer but the VFD
fan can now be used. At time delay of 120 seconds (Setpoint #125) be for the VFD will be modulated. Following this
initial delay the VFD will be opened to its minimum opening, Setpoint #54 of 20%.
At this point the unit state is ECONOMIZER ONLY, economizer valve is at 100% and VFD will be modulated
between its minimum (Setpoint #54) and it maximum (Setpoint #55). The delay between these adjustments will be
45 seconds (Setpoint #115).
Once the VFD opening is equal to its maximum (Setpoint #55) there will be a delay of 240 seconds (Setpoint #107).
At this time the unit state will be changed and mechanical cooling will be enabled.
The economizer AO has been selected and there are no separate economizer fans.
61
MCS-MAGNUM-V. 14 REVISION 3.2
The condenser type is RO Step Individual and the Fluid Cooler Economizer option has been enabled. The individual
compressor condenser fans will be controlled by the economizer function unless a compressor is running. If a
compressor is running, then the condenser fans associated with that compressor will be controlled based upon the
discharge pressure of the compressor that is running.
The ambient temperature is less than 44.0 (Setpoint #1) – 10.0 (Setpoint #119) and no mechanical cooling steps are
on, therefore the Unit state will be ECONOMIZER ONLY and the economizer function will be enabled.
The AO M-1 “ECONOMIZER” will be opened to its minimum valve of 10% (Setpoint #121) and it will be modulated
based upon the control temperature and the target (Setpoint #1). The first adjustment will be 49.7 – 44.0 = 5.7.
This value will be adjusted by multiplier of 2 (Setpoint #126) and divided by 1 (Setpoint #127) to give an adjusted
value of 11.4. This value is blocked by the maximum allowed adjustment (Setpoint #123) to 10.0%. The economizer
valve opening will be increased by this amount if the temperature control rate of change is greater than the value of
Setpoint #27. With Setpoint #126 equal to 2 and #127 equal to 1, the valve will be adjusted by 2% for every degree
difference from the target.
The economizer function will wait 30 seconds (Setpoint #124) before calculating the next adjustment. If the control
temperature is now 47.3F the following adjustment will be made.
47.3 – 44.0 = 3.3 x 2 / 1 = 6.6. Since this is less than 10.0 the valve will be open an additional 6.6% if the
temperature control rate of change is greater than the value of Setpoint #27.
Each adjustment will be made after a delay of 30 seconds. If the control temperature is below the control target
(Setpoint #1) and above the bottom the control zone (43.0F to 44.0F) there will be no change to valve opening.
If the control temperature drops below the control zone the valve opening will be reduced. For example if
the control temperature is 42.6F then the following calculation will be made:
42.6 – 44.0 = 1.4 x 2 / 1 = 2.8. Since this is less than 10.0 the valve opening will be reduced an additional 2.8%.
62
MCS-MAGNUM-V. 14 REVISION 3.2
When the valve reaches its maximum opening of 100.0% (Setpoint #122) the economizer function will use other
fans if they are available. In this example there are no fans that are associated only with economizer but the
condenser fans can now be used. After the time delay of 120 seconds (Setpoint #125) the first condenser fan will be
turned on (the first fan of the first compressor unless unavailable).
At this point the unit state is ECONOMIZER ONLY, the economizer valve is at 100%, and the compressor fans
will be used to aid in the economizer cooling. The delay between starting the condenser fans will be 30 seconds
(Setpoint #124). If all condenser fans are available and not manually turned off, the pattern of starting fans will be the
first fan on compressor 1, after the delay then the first fan of compressor 2, after the delay then the second fan on
compressor 1. This will continue until all available condenser fans have been turned on.
Once all of the condenser fans have been turned on there will be a delay of 240 seconds (Setpoint #107). At this
time the Unit State will be changed and mechanical cooling will be enabled. When a compressor is running, its
associated condenser fans will be controlled by the discharge pressure of the running compressors.
To add a high suction superheat safety, make Setpoint #203 “HiSuctSheat” active. If the suction superheat is greater
than the value of this Setpoint for the ‘Time(sec)’ field, an alarm will be generated and the compressor will be shut
down with a safety or Lockout state.
11.44. Low Temperature Safety and Unload (Low Saturated Suction Temperature)
The Magnum is set up to check for low refrigerant temperature safety and unload functions. To enable this test make
Setpoint #155 “LO REF TMP” active and point to the sensor in the ‘Refrigeration Temp’ column of the Compressor
SI grid in MCS-Config.
This safety will be checked only when the compressor is running. If the sensor value is less than Setpoint #155 for
the ‘Time(sec)’ field, then an alarm message will be generated and the associated compressor will either be placed
in a safety or Lockout state.
The Magnum will also determine if a low temperature condition occurs and to stop loading or unload if necessary. If
the sensor value is less than the value of Setpoint #155 plus Setpoint #156 “LO REF UNLD”, then the compressor
state will be LO TMP UNLOAD. Refer to state (21) in section 6.2.26.
By using the User Logic type sensor, we can test any value for a low condition. For example point the refrigerant
temperature index to a User Logic sensor that picks up the saturated suction temperature for that compressor. Make
Setpoint #155 active with the low temperature value that will trigger the safety and unload action and you have a low
saturated suction temperature condition.
63
MCS-MAGNUM-V. 14 REVISION 3.2
By clicking on the ‘EXV Control’ cell under the Circuit Base screen, the option will cycle between Suction Superheat,
Discharge Superheat, and Refrigerant Level control.
64
MCS-MAGNUM-V. 14 REVISION 3.2
65
MCS-MAGNUM-V. 14 REVISION 3.2
66
MCS-MAGNUM-V. 14 REVISION 3.2
67
MCS-MAGNUM-V. 14 REVISION 3.2
To view the EXV status through the Keypad LCD, select Status from the Main Menu and then page to the
EXV screen.
EXV States:
LOCKED OUT The compressor is in a Lockout state.
IS CLOSED The associated compressor is OFF and the valve is closed
PRE-PMPDWN The valve has been in a closed state and the system is now requiring the valve action.
IN STARTUP At startup the valve will remain in this state for the time in Setpoint #20. At that time the state will be changed to holding, at
this point the valve control logic will position the valve.
AT 100% This state will be entered when the valve opening reaches 100%.
IS HOLDING Refer to EXV Logic Chart, superheat is in control zone and ROC is acceptable.
IS OPENING Refer to EXV Logic Chart, superheat is in control zone but rising too fast, ROC less than 1.0.
IS CLOSING Refer to EXV Logic Chart, superheat is in the control zone and the rate of change is acceptable, ROC greater than –0.5.
LOW SPRHT Refer to EXV Logic Chart, force a course valve adjustment.
OPENING 4x Refer to EXV Logic Chart, superheat is above control zone.
OPENING 2x Refer to EXV Logic Chart, superheat is in control zone but rising too fast, the ROC is greater than 1.0.
LO PSI OPN Refer to EXV Logic Chart, state indicates that a low suction pressure condition exists. The suction pressure is less than
Setpoint #77 “LOW SUCTION” plus twice the value of Setpoint #79 “LOW SUCT RELOAD” and the superheat is greater
than Setpoint #9 “SUPERHT TRGT” plus twice the value of Setpoint #10 “SPRHT ZONE+-“.
CLOSING 2x Refer to EXV Logic Chart, superheat is in the control zone and the rate of change is acceptable, the ROC is less than -0.5
and greater than -1.0.
CLOSING 4x Refer to EXV Logic Chart, superheat is in control zone but falling too fast, ROC less than -1.0.
HI LVL CLS This state indicates that a high refrigerant level. This state is entered if Setpoint #109 “HiRefLevel” is active and the super-
heat is greater than the value of this Setpoint.
IS MOP CLS Refer to EXV Logic Chart. Maximum operating pressure option is active and it is forcing the EXV to close. In this state the
EXV valve’s opening will be reduced.
IS MOP HLD Refer to EXV Logic Chart. Maximum operating pressure option is active and it is forcing the EXV to hold.
68
MCS-MAGNUM-V. 14 REVISION 3.2
If the suction pressure is above the MOP control zone, then the EXV state will be changed to EXV IS MOP CLS.
The EXV valve opening will be closed by the value in Setpoint #201 with each adjustment. The ‘Time(sec)’ field of
Setpoint #201 will be the delay between making adjustments to the EXV valves. The EXV will remain in this state
until the suction pressure drops below the top of the MOP control zone. At this point the state will be changed to
EXV IS MOP HOLD.
In the EXV IS MOP HOLD state the EXV valve’s opening cannot be increased but it can be closed. The EXV will
remain in this state until the suction pressure drops below the MOP control zone. At that time the EXV control state
will change to EXV IS HOLDING and normal EXV control will resume.
(Refer to section 13 Setpoints #199, #200, and #201)
11.45.5 Example: One Compressor with One Step and Tandem EXV’s
In the General Information panel of the MAG V8 screen enter the number of compressors and steps:
In the Circuit Base screen the base compressor information will be entered. The active compressors information is
to be completed as normal and the tandem EXV information will be provided as needed. Note the Type of LLS cell
must be ‘EXV&LLS’ for the active compressor and ‘EXV only’ for the tandem compressor.
In the next section the EXV Output cell must be set up for both the EXV’s
In the next section the active compressor is associated with its tandem EXV in the ‘Tandem EXV Circuit #’ cell.
Circuit #1 ties to circuit #2, this is the tandem EXV. The Suction Group cells are 1 and 2 respectively.
69
MCS-MAGNUM-V. 14 REVISION 3.2
In the Compressor SI screen the active compressors information is to be completed as normal, while only the
Suction Pressure and Suction Temperature must be entered for the tandem EXV. The different suction temperature
provides separate control for the tandem EXV.
11.45.5.1. Example: Two Compressors with Four Steps and Tandem EXV’s
In the General Information panel of the MAG V8 screen enter the number of compressors and steps:
In the Circuit Base screen the base compressor information will be entered. The active compressors information is
to be completed as normal and the tandem EXV information will be provided as needed. Note the Type of LLS cell
must be ‘EXV&LLS’ for the active compressor and ‘EXV only’ for the tandem compressor.
In the next section the EXV Output cell must be set up for all the EXV’s
In the next section the active compressor is associated with its tandem EXV in the ‘Tandem EXV Circuit #’ cell.
Circuit #1 ties to circuit #3, and circuit #2 ties to circuit #4 (circuits #3 and #4 are the Tandem EXV’s). The Suction
Group cells are 1, 2, 3, and 4 respectively.
In the Compressor SI screen the active compressors information is to be completed as normal, while only
the Suction Pressure and Suction Temperature must be entered for the tandem EXV’s. The different suction
temperature provides separate control for the tandem EXV’s
70
MCS-MAGNUM-V. 14 REVISION 3.2
In the Compressor SI screen the active compressors information is to be completed as normal, while only
the Suction Pressure and Suction Temperature must be entered for the tandem EXV’s. The different suction
temperature provides separate control for the tandem EXV’s.
71
MCS-MAGNUM-V. 14 REVISION 3.2
The logic will work as follows: When the compressor starts the EXV will go to the value in the ‘EXV Start (when
lead)’ column, in this example it is 25%. The EXV will then modulate normally according to the controlling superheat
or refrigerant level, until the unit is ready to load another step of capacity. Assume the EXV has stayed at 35% when
the second step of capacity is ready to engage (turning off the Hot Gas Bypass). The EXV adjustment will be 50%
(the amount in the ‘EXV Load Adjust’ column of the current EXV position
‘EXV Load Adjust’ column (50%) × current EXV position (35%) = EXV adjustment (17.5%)
50% × 35% = 17.5%
Current EXV position (35%) + EXV adjustment (17.5%) = New EXV position (42.5%)
35% +17.5% = 42.5%
Therefore the final EXV valve position would be 42.5%
This same calculation will be repeated every time a new stage of capacity is turned on. Conversely, when the unit is
unloading, the EXV adjustment will be subtracted from the current EXV position for every step that turns off. Assume
the EXV is at 40% and the compressor is at 100% and is ready to unload a step (turning on Unload 75% solenoid).
‘EXV Unld Adjust’ column (30%)× current EXV position (40%)= EXV adjustment (12%)
30% × 40% = 12%
Current EXV position (40%) - EXV adjustment (12%) = New EXV position (28%)
40% - 12% = 28%
Therefore the final EXV valve position would be 28%
The values given in the example are only start points. You will need to adjust the values for your system. The idea
is to jump the EXV position so that the superheat would still be above the target slightly, and then the EXV control
logic would then adjust the value to achieve the target superheat. We do not want to open the EXV valve too much
when loading or close the valve too much when unloading so we do not cause low superheat or liquid flooding to the
compressor.
Window to Extend Safety Time: The amount of time after compressor startup (or “Sec to Ignore Safety” if used) in
which the “Safety Time Extension” field is added to the ”Time (sec)” field.
Safety Time Extension: The amount of time added to the “Time (sec)” field during the “Window to Extend Safety
Time”.
Eight new EXV related Setpoint have been added to provide flexibility:
Setpoint #65, EXV ZONE1
Setpoint #66, EXV ZONE2
Setpoint #67, EXV ROC ZONE
Setpoint #68, EXV ROC ZONE1
Setpoint #69, EXV ROC ZONE2
Setpoint #70, EXV ROC ZONE3
Setpoint #71, EXV TOO FAST
Setpoint #72, EXV CHANGING
72
MCS-MAGNUM-V. 14 REVISION 3.2
73
MCS-MAGNUM-V. 14 REVISION 3.2
The EXV logic will forced the state to “EXV MDP CLOSE” when the all of the following conditions are true:
1. Setpoint #205 “MDP MIN OIL DIFF” is active,
2. The compressor oil differential pressure is less than Setpoint #205 value field,
3. The compressor has been running for less than X mins or X is equal to zero (where X is the value contained in
Setpoint #205 “SEC to IGNORE SAFETY” field),
4. The compressor suction pressure is greater than or equal to (Setpoint #77 “LOW SUCTION” value plus Setpoint
#79 “LO SUCT RELD” value).
In this state the EXV will be closed by the adjustment value in Setpoint #205 “Lockout Delay” field. If this value is
positive the valve is closed, if this value is negative the valve will be opened.
The EXV logic will exit the “EXV MDP CLOSE” state and go to “EXV HOLDING” state when the any of the follow
conditions are true:
1. The compressor oil differential pressure is greater than (Setpoint #205 value field plus Setpoint #205 Time field),
2. The compressor has been running for more than X mins and X is not equal to zero (where X is the value
contained in Setpoint #205 “SEC to IGNORE SAFETY” field),
3. The compressor suction pressure is less than or equal to (Setpoint #77 “LOW SUCTION” value plus Setpoint
#78 “LO SUCT ULLD” value).
If discharge superheat is less than Setpoint #84 LO DISC SUPERHEAT for 1/3 of its safety time and both discharge
74
MCS-MAGNUM-V. 14 REVISION 3.2
temperature and pressure sensors are active, then add the value of Setpoint #110 LOW REFRIGERANT LEVEL
TARGET to Setpoint #9 EXV TARGET. This function takes precedence over the regular control zone logic.
11.68. Expanded Compressor Rotation to Check for Maximum Run Time (8.02-E)
In the Compressor Information panel of the MAG V8 screen in MCS-Config, there is now a check box to select how
compressors are to be rotated, based either on Run Time or First On/First Off.
11.69. New Option to test for Low Superheat on Suction or Discharge PSI (8.02-E)
In the Circuit Base screen under the EXV Control column select “Disc Sph” to test discharge pressure or “Suct Sph”
to test the suction pressure to determine low superheat.
from the Main Menu of the Magnum Keypad by pressing the F3 key.
Unit KW – virtual sensor that calculates the unit Kilowatt usage. The Power Factor (PF) sensor must be selected in
the ‘Temp. / GPM / CFM / Pwr Factor SI’ cell.
Kw = Amps * Volts * Power Factor * Internal Constant of .00173
Power Factor – Virtual sensor tied to a Setpoint where a manual value of the unit’s power factor may be defined. If
not specified, a hardcoded value of .85 will be used.
Unit Volts – Voltage being supplied to the unit. This sensor can be an actual voltage sensor or virtual point that reads
a static value from a Setpoint.
Unit Amps – Sensor reading the amperage of the entire unit. If no total unit amp sensor is specified, the software will
automatically sum all the individual compressor amp sensors to approximate the unit amps.
Unit Tons – a virtual sensor that calculates the unit tonnage. The Unit Flow (GPM or CFM) sensor must be selected
in the ‘Temp. / GPM / CFM / Pwr Factor SI’ cell, and the Enthalpy Differential or Temperature Differential sensor
(air and water cooling systems respectively) must be selected in the ‘Humd. SI / Temp. Diff. / Enthal. Diff.’ cell. Also
the correct values must be placed in the ‘Multiplier’ and ‘Divisor’ cells depending on the type of system; 45 and 10
respectively for air, 1 and 24 respectively for water (refer to pictures above).
Tonnage (air) = Flow (CFM) * Enthalpy Differential * 4.5
Tonnage (water) = Flow (GPM) * Temperature Differential / 24
Unit Flow (GPM or CFM) – Gallons per minute (for water) or cubic feet per minute (for air). This can be an actual
flow sensor or virtual point that reads a static value from a Setpoint. NOTE: It is essential for a correct calculation
that this sensor must be configured so as to have no decimal places.
76
MCS-MAGNUM-V. 14 REVISION 3.2
Water In and Out Temperatures – (Water only) Temperature sensors for Water In and Out.
Temperature Differential – (Water only) User logic that subtracts Water Out Temperature from Water In Temperature.
Temp Diff = Water In – Water Out
Supply and Return Humidity – (Air only) Humidity sensors for Return and Supply air.
Supply and Return Temperatures – (Air only) Temperature sensors for Return and Supply air.
Return Enthalpy – (Air only) Virtual sensor that calculates enthalpy for Return air. The Return Temperature sensor
must be selected in the ‘Temp. / GPM / CFM / Pwr Factor SI’ cell and the Return Humidity sensor must be selected
in the ‘Humd. SI / Temp. Diff. / Enthal. Diff.’ cell.
Supply Enthalpy – (Air only) Virtual sensor that calculates enthalpy for Supply air. The Supply Temperature sensor
must be selected in the ‘Temp. / GPM / CFM / Pwr Factor SI’ cell and the Supply Humidity sensor must be selected
in the ‘Humd. SI / Temp. Diff. / Enthal. Diff.’ cell.
Enthalpy Differential – (Air only) User logic that subtracts Supply Enthalpy from Return Enthalpy.
Enth Diff = Return Ent – Supply Ent
Once your Setpoints have been defined, go back to the SI screen. Find the respective sensor you wish to tie to a
Setpoint and select User Logic in the “Display Type” column. The “User Logic SI V11 Form” screen will pop up. First
select the same Display Type as you did in the “Select Value: # decimals & print char” cell for the respective
Setpoint. Next, select “Setpoints” in the first dropdown menu of the Operand #1 box, and select the respective
Setpoint in the second dropdown menu. Finally, select “None” in the middle dropdown menu (Operators). An
example User Logic displaying the value of a Setpoint is shown below:
77
MCS-MAGNUM-V. 14 REVISION 3.2
To set up the User logic for differential calculations, such as for Temperature Differential, first select User Logic as
the Display Type for that particular sensor. Again the “User Logic SI V11 Form” screen will pop up. This time you will
select the corresponding display type, as well as SI type for Operands #1 and #2. Then select Water In Temperature
for Operand #1 and Water Out Temperature for Operand #2 and subtraction from the middle drop down menu (See
picture below).
The Unit Tons value is selected in the “Evap. Tonnage” cell in the Evaporator Information panel under the MAG V8
screen.
The Unit Volts sensor is selected in the “Volts A” cell in the General Information panel. The Unit Amps sensor is
selected in the “Unit Amps” cell (If not used then the “Amps A” cell from each circuit in the Circuit SI screen will be
totaled together to calculate the amps value). The Unit KW sensor is selected in the “Unit KW” cell.
78
MCS-MAGNUM-V. 14 REVISION 3.2
The following screen has been added to the status screens in the keypad display to show Tonnage/KW information
(if available):
79
MCS-MAGNUM-V. 14 REVISION 3.2
During normal operation, VFD LOAD will be on, VFD BYPS will be off, and VFD ENAB will be on. The fan will be
modulated as required by the condenser or economizer logic. If a fault occurs, all relays will be turned off and the
VFD will be set to 0. The Magnum will wait for the time specified in Setpoint #90 “COND FAULT” before the fan will
be run without VFD control if it is needed by the condenser logic (economizer logic will not function in this condition).
Once this time has passed and the condenser logic calls for the fan, then VFD BYPS will be turned on thereby
turning the fan on, however it will NOT be modulated.
80
MCS-MAGNUM-V. 14 REVISION 3.2
The Magnum can also support a variable speed fan for all three of the air type of condensers. Each compressor can
support a variable speed fan. The variable speed must be on the first Relay Output associated with that compressor.
Note 1: The discharge temperature must be at least 117° F and the discharge superheat needs to be at least 20° F
to guarantee good oil separation.
Note 2: Condenser staging is critical if the Magnum is to function in different climates. The best option for air-cooled
chillers is to have each fan on its own contactor and a frequency drive on fan 1. This configuration allows the most
optimum control in all weather.
Condenser Relay Outputs will be turned on based upon the value in Setpoint #45 “CND STG1 ON”. When
discharge pressure reaches this value, the first condenser Relay Output is turned on. If additional condenser outputs
are present, they will be turned on when the pressure exceeds the cut in value plus the value contained in Setpoint
#47 “CND DIFF ON“. When discharge pressure falls, the condenser outputs will be turned off based upon the
Setpoint #46 “CND STG1 OFF” plus the value contained in Setpoint #48 “CND DIFF OFF”. The first step will be
turned off when discharge pressure falls below Setpoint #46 “CND STG1 OFF”.
The purpose of the variable speed fan is to reduce the cycling of the fans by adjusting the speed of the variable fan
point. This control works in conjunction with the Cut In and Cut Out logic of each compressor. When a fan is turned
on, the speed of the variable point for that compressor is set to maximum allowed percentage. As the discharge
pressure falls, the fan speed is adjusted proportionally. When the minimum is reached the fan will turn off.
81
MCS-MAGNUM-V. 14 REVISION 3.2
(Other SI) - The Magnum will not check for the compressor with the highest discharge pressure but will always use
the value of the sensor that is selected as the control.
82
MCS-MAGNUM-V. 14 REVISION 3.2
48 CND DIFF OFF Differential pressure added to Setpoint #46 to set the threshold at which each ad-
(RO Type) ditional stage of condenser capacity will turn off.
CND ADJ DELAY If active this is the time in seconds between condenser adjustments to the AO. If
(Modulating Type) inactive,
then 30 seconds will be used as the delay.
If type is DELAY: (required for condenser relay delays).
-MIN VFD Opening cell contains the time delay between turning on a relay
and moving
the AO to its minimum position (Setpoint #52).
-MAX VFD Opening cell contains the time delay between turning off a relay
and moving
the AO to 100%.
DUAL PSI DELTA Minimum difference in pressure before the second stage of condenser capacity
(Dual V8) can be started.
49 CND MIN RUN Once a condenser stage has been turned on, it will remain on for at least the
(RO Type) amount of minutes specified in this Setpoint.
DUAL TIME DE- Time delay once the pressure difference in Setpoint #48 has been reached before
LAY the second condenser stage can be started.
(Dual V8)
CND START % If active, then the value is the starting % for the AO when the RO that is tied to it
(Modulating Type) turns on. The value in the “Time (SEC)” cell is the AO starting stage. If no Relays
are used when CMP starts set value.
50 CND TRGT Target the logic will try to maintain by modulating the AO.
(Modulating Type)
LO AMB SUMP If active and ambient temperature is less than the value of this Setpoint, then the
OFF sump pump relay will be locked off if it is the starting condenser Relay Output.
(RO Type) When the ambient temperature rises above the value of this Setpoint plus two
times the value in Setpoint #192 “FRZ TEMP DIFF” if active (hardcoded 15°F if
inactive), then the sump pump relay will be allowed on again.
51 CND ADJ DIV Controls scaling of the amount the AO is adjusted (usually 1). The larger the num-
(Modulating Type) ber the smaller the AO adjustment as the adjustment will be divided by this value.
CND VFD MIN If there is a VFD associated with the condenser, this is the starting minimum
speed.
‘Time (sec)’ field: This field contains the condenser stage that must be on before
the VFD is modulated.
52 CND MIN % Minimum AO % allowed.
(Modulating Type) If compressor is off, then check the “Time (SEC)” field:
If 0, then the AO % will be set to the value of this Setpoint. If 2 and the run/stop is
set to run, then set the AO % to 100%, else set the AO % to 0%. This option is se-
lected in the “Default Valve Opening % when Comp. is OFF” box in the condenser
information section in the MAG HVAC screen.
53 CND ROC- Maximum negative rate of change allowed. If the rate of change is less than this
(Modulating Type) Setpoint, then stop modulating the AO. The absolute value of this Setpoint also
serves as the maximum positive rate of change allowed. If the rate of change is
greater than the absolute value of this Setpoint, then stop modulating the AO.
54 CND MIN SPD Minimum speed percentage for variable speed condenser control.
(RO Type)
83
MCS-MAGNUM-V. 14 REVISION 3.2
CND ADJ MULT Controls scaling of the amount the AO is adjusted. The larger the number the
(Modulating Type) larger the AO adjustment as the adjustment will be multiplied by this value.
55 CND MAX SPD Maximum speed percentage for variable speed condenser control.
(RO Type)
CND MIN ADJ The value in this Setpoint is the minimum % the AO will be modulated when a
(Modulating Type) change is made.
57 LO AMB PROC When this Setpoint is active and there is a process pump, the process pump will
be turned on when the ambient temperature is less than the value of this Setpoint.
The process pump will be turned off again when the ambient temperature is 5.0°
Fahrenheit greater than the value of this Setpoint.
90 COND FAULT For Condensers with Fault Indicators: If Setpoint is active, a condenser fault oc-
curs, and the Setpoint type is Alarm, then an alarm message will be generated.
If the type is Lockout, and a condenser fault occurs, then all of the compressors
associated with this fault will be locked off.
For Common VFD Fan Condensers with Bypass: Time in seconds before the by-
pass can be used when a fault has occurred.
193 CND HI/LO ZONE The value in this Setpoint is the high and low zone for your target of Setpoint #50
“CND TRGT“. If inactive then a default zone of 5 psi will be used, if metric .3 Bar.
194 CND 2ND ZONE The value in this Setpoint is the 2nd high and low zone for your target of Setpoint
#50 “CND TRGT“. If inactive then a default zone of 20 psi will be used, if metric
1.4 Bar.
197 COND LOW AMB Standard condenser logic dictates that a newly started compressor will use its
(Only CENT) own discharge pressure as the control for the first five minutes. If this Setpoint is
active and the ambient temperature sensor is reading less than the value of this
Setpoint, then this compressor’s discharge pressure will remain in control for the
additional time in seconds as specified in the ‘Time (sec)’ field.
204 COND LOW AMB Standard condenser logic dictates that a newly started compressor will use its
(Only HVAC) own discharge pressure as the control for the first five minutes. If this Setpoint is
active and the ambient temperature sensor is reading less than the value of this
Setpoint, then this compressor’s discharge pressure will remain in control for the
additional time in seconds as specified in the ‘Time (sec)’ field.
206 COND HI AMB If active, standard condenser control on compressor startup logic will be bypassed
when there is a high ambient temperature. If the condenser type is common and
the ambient temperature is above the value of this Setpoint, then the compressor
with the highest discharge pressure will have control of the condenser.
11.76.3.4. No Condenser
This option indicates there is no condenser associated with this unit.
84
MCS-MAGNUM-V. 14 REVISION 3.2
The RO Step Common of condenser has one bank of fans. Make sure that all compressors in the Circuit Base point
to the same common fan bank. The above example does not have a Fan Analog Output and there are three stages
of fans starting with CND FAN 1 relay. All stages must be consecutive Relay Outputs.
For example:
Setpoint # Name Value
45 CND STG1 ON 200.0P
46 CND STG2 OFF 170.0P
47 CND DIFF ON 15.0P
48 CND DIFF OFF 5.0P
Discharge control pressure is 200.0 P, CND FAN 1, first condenser stage will be turned on.
If control pressure is equal to or greater than 215.0 P then the second stage will be turned on. (200.0 + (15.0 * 1))
If control pressure is equal to or greater than 230.0 P then the third stage will be turned on. (200.0 + (15.0 * 2))
Discharge control pressure is above 230.0 P; all three condenser stages are on.
When the control pressure drops below 180.0P the third condenser stage will be turned off. (170.0 + (5.0 * 2))
When the control pressure drops below 175.0P the second condenser stage will be turned off. (170.0 + (5.0 * 1))
When the control pressure drops below 170.0P the first condenser stage will be turned off. (170.0)
Condenser Faults
This example has no condenser faults. If used, and any one of the digital inputs are ON for the time specified in
Setpoint #90 if active, then the unit will be locked out and an alarm message will be generated.
The above example is the same as the previous example with the addition of a Fan AO and two condenser faults.
85
MCS-MAGNUM-V. 14 REVISION 3.2
CND FAN 1 will be turned on when the control pressure is equal to or greater than 200.0, same as in previous
example. At this point the Fan AO speed will be set to its maximum value, Setpoint #55. If the pressure changes
between 170.0 and 214.9 the fan speed will also be modulated proportionally between its maximum and minimum
settings. If the pressure is at 185.0 the fan speed will be set to 61.2%. If the pressure is at 190.0 the fan speed will
increase to 75.0%. This will provide precision control in maintaining optimum discharge pressure.
If the pressure increases to 215.0 the condenser’s second stage will be turned on and the fan speed will also be
at 100.0%. If the pressure changes between 175.0 and 229.9 the fan speed will also be modulated proportionally
between its maximum and minimum settings.
If the pressure increases to 230.0 the condenser’s third stage will be turned on and the fan speed will also be at
100.0%. If the pressure changes between 180.0 and 229.9 the fan speed will also be modulated proportionally
between its maximum and minimum settings. If the pressure is at 230.0 and above the fan speed will be at 100.0%.
As the pressure decreases toward the Cut Out point the fan speed will decrease toward its minimum setting. Once a
stage is turned off, the fan speed will be set to 100.0% and again it will be modulated based upon the pressure.
Condenser Faults
This example has two condenser faults. They must be consecutive digital input types starting with FAN FLT 1. If
either of these digital inputs are ON for the time specified in Setpoint #90 if active, then the unit will be locked out
and an alarm message will be generated.
The RO Step Individual has a bank of fans for each compressor. The number and location of the fan are specified
under the Circuit Base screen.
# of Cond ROs –Total number of Relay Outputs of each compressor, in this example there are 3. The number of
fans in each compressor does not have to be the same.
Starting Condenser RO – The starting condenser Relay Output. All the Relay Outputs specified for each circuit
must follow consecutively to this point. In this example CND FAN 1 is the starting Relay Output for circuit 1 and the
other 2 fans follow consecutively in the RO screen.
Condenser Fan AO - If a condenser fan AO was specified in this cell it would function as described in the example
in section 7.74.3.6 RO Step Common with a Fan AO and Condenser Faults. There is no condenser fan AO in this
example.
Starting Condenser Fault - If there were condenser faults specified in this cell they would function as described in
the example in section 7.74.3.6 RO Step Common with a Fan AO and Condenser Faults. There are no condenser
faults in this example.
# Cond Faults – Total number of Condenser Faults.
Cond Fan Bank – In this type of condenser all compressors should have a different fan bank.
86
MCS-MAGNUM-V. 14 REVISION 3.2
Each compressor fan bank is controlled individually. The discharge pressure for each compressor is used to control
condenser logic.
The RO Step Combined has a bank of fans that are shared by two consecutive circuits. The number and location of
the fans are specified in the Circuit Base screen. This is similar to the RO Step Individual set up except only every
other compressor has a condenser fans associated with it.
Circuit 1 and 2 will share the same fan bank specified in the ‘Cond Fan Bank’ cell. Circuit 3 and 4 will also share the
same fan bank specified. The highest discharge pressure between the two compressors on each respective circuit
will be used as the control pressure for their fan bank.
Condenser Faults
If any of these digital inputs are ON for the time specified in Setpoint #90 if active, then both compressors sharing
that condenser will we will be locked out and an alarm message will be generated. This example has no condenser
faults.
11.76.3.9. Modulating
11.76.3.9.1. Modulating Common
This type of condenser uses water for condenser cooling. The AO Modulating Valve will modulate the cold water valve based
upon the system’s highest discharge pressure.
87
MCS-MAGNUM-V. 14 REVISION 3.2
48 CND ADJ DELAY If active this is the time in seconds between condenser adjustments to the AO. If inactive,
(Modulating Type) then 30 seconds will be used as the delay.
If type is DELAY: (required for condenser relay delays).
.-MIN VFD Opening cell contains the time delay between turning on a relay and moving the
AO to its minimum position (Setpoint #52).
.-MAX VFD Opening cell contains the time delay between turning off a relay and moving the
AO to 100%.
49 CND START % If active, then the value is the starting % for the AO when the RO that is tied to it turns on.
(Modulating Type) The value in the “Time (SEC)” cell is the AO starting stage. If no Relays are used when CMP
starts set value.
50 CND TARG Target the logic will try to maintain by modulating the AO.
(Modulating Type)
51 CND ADJ DIV Controls scaling of the amount the AO is adjusted (usually 1). The larger the number the
(Modulating Type) smaller the AO adjustment as the adjustment will be divided by this value.
Note 1: The purpose of Setpoint #193 ‘CND HI/LO ZONE’ and the delays in the MAX AND MIN VFD Opening
cells for Setpoint #48 ‘CND ADJ DELAY’ are to prevent repeated cycling of additional stages.
Note 2: The purpose of Setpoint #194 ‘CND 2nd ZONE’ is to prevent the discharge pressure from over
shooting the target (Setpoint #50 ‘CND TARG’). The way the logic works is if the discharge pressure is in
the 2nd Zone and the pressure is falling less than twice the CND ROC- (Setpoint #53 ‘CND ROC-‘) then a
negative adjustment will be made to the AO. If the discharge pressure is raising more than twice the rate of
change (Setpoint #53) then a positive adjustment will be made to the AO.
Note 3: The value in the “AO Starting Stage” cell under the MAG HVAC screen in the condenser info
section is the stage that has to be turned on to begin modulating the AO.
88
MCS-MAGNUM-V. 14 REVISION 3.2
The following applies to both the modulating common and individual water condenser types: The ‘Default
Valve Opening % when Comp. is OFF’ cell can be used to set the valve (1) to be completely closed (0%), (2) the
value of Setpoint #52 (Valve % defined by Setpoint #52), or (3) completely open (100% if the Run/Stop indicator =
ON else = 0%).
The delay timer will be decremented by a standard value of 1 every second, however if the control discharge
pressure is more than 15.0 psi (1.5 bar) away from the target Setpoint #50, then the delay will be decremented by 2;
if more than20.0 psi (2.0 bar) away from the target then the delay will be decremented by 4.
When the delay counts down to zero, an adjustment will be made based on the equation: (Control discharge
pressure – Setpoint #50) × Setpoint #54 ÷ Setpoint #51 = Adjustment Value.
When the control discharge pressure is greater than Setpoint #50 plus 5.0 psi (.5 bar) : If the control discharge
pressure rate of change is dropping too fast (more than twice the value of Setpoint #53), then close the valve by the
calculated adjustment. If the control discharge pressure rate of change is dropping too slowly (more than the value
of Setpoint #53), then open the valve by the calculated adjustment. Else make no adjustment.
When the control discharge pressure is less than Setpoint #50 minus 5.0 psi (.5 bar): If the control discharge
pressure rate of change is increasing too fast (more than twice the value of Setpoint #53) and the control discharge
pressure is greater than Setpoint #50 minus 20.0 psi (1.3 bar), then close the valve by the calculated adjustment. If
the control discharge pressure rate of change is increasing too slowly (more than the value of Setpoint #53), then
open the valve by the calculated adjustment. Else make no adjustment.
When the control discharge pressure is within the zone: If the control discharge pressure rate of change is
increasing more than the value of Setpoint #53, then close the valve by 1 percent. If the control discharge pressure
change is decreasing more than the value of Setpoint #53, then open the valve by 1 percent.
Modulating Condenser Type: If heat pump and the mode is HEAT (not in defrost) all condenser relays will be
turned on and the VFD set to 100% when compressor is turned on. If the control pressure is above the control
zone, the condenser will unload; if below the control zone the condenser will load else there will be no change.
When a RO is being used with an AO the AO will key off the RO turning on. The RO will turn on when the discharge
pressure enters the bottom of the CND HI/LO ZONE (Setpoint #193). At that time the AO will move to its starting %
(Setpoint #49). The AO will stay at its starting % until the discharge pressure gets outside the top of the CND HI/LO
ZONE (Setpoint #193). At that point the AO will modulate based on Setpoints #51, #53-55. Now if there are 2 RO’s
89
MCS-MAGNUM-V. 14 REVISION 3.2
tied to the AO and the “AO Starting Stage” is 1 then once the AO gets to 100% the 2nd RO will be turned on after a
delay (value in the ”MIN VFD Opening“ cell for Setpoint #48) and the AO will be set back to its minimum % (Setpoint
#52) and then modulate as described above. Now if the pressure begins to fall and goes below the CND HI/LO
ZONE (Setpoint #193) the AO will modulate. Once the AO gets to its minimum % (Setpoint #52) the 2nd RO will be
turned off after a delay (value in the “MAX VFD Opening” cell for Setpoint #48) and the AO will be set back to 100%
and continue to modulate as needed.
If the “AO Starting Stage” is 2 then when the discharge pressure enters the bottom of the CND HI/LO ZONE
(Setpoint #193) the 1st RO (stage 1) will be turned on. The 2nd RO will turn on once the discharge pressure gets
outside the Heating Info CND HI/LO ZONE (Setpoint #193) and the delay has been met (value in the “MIN VFD
Opening cell” for Setpoint #48) at that time AO will be set to its starting % (Setpoint #49). If the discharge falls
below the CND HI/LO ZONE (Setpoint #193) the AO will begin to modulate. Once the AO reaches its minimum %
(Setpoint #52) it will turn off the associated RO after a delay (value in the “MAX VFD Opening” cell for Setpoint #48).
The 1st RO will remain on until the discharge pressure falls below the CND HI/LO ZONE (Setpoint #193) and the
delay has been met (value in the “MAX VFD Opening” cell for Setpoint #48).
This type of condenser uses water to provide cooling to the compressors. The AO Modulating Valve will modulate
the cold water based upon this discharge pressure for each circuit. You may also select Relay Outputs to be turned
ON/OFF while modulating the Analog Output.
The control will be similar to the Modulating Common type, except that the discharge pressure for each circuit will
control its own condenser.
11.76.3.9.4. RO Shared
The RO Shared condenser has banks of fans that are shared between two consecutive circuits. The number and
location of the fans are specified under the Circuit Base screen. This is similar to the RO Step Individual set up.
90
MCS-MAGNUM-V. 14 REVISION 3.2
Circuits 1 and 2 will share the fan bank that is specified in the circuit 1 grid in the Circuit Base screen. The highest
discharge pressure of these two compressors will be used to control this bank of fans. Circuits 2 and 3 will share
the fan bank that is specified in the circuit 2 grid in the Circuit Base screen. The highest discharge pressure of these
two compressors will be used to control this bank of fans. In a unit with three circuits, circuit three will not have a fan
bank associated with it. It shares circuit 2’s fan bank.
11.76.3.9.5. Dual V8
This is a special type of condenser. It is a common circuit control type with two stages of fans and VFD. The
control of the fan speed will be different depending on whether one or two stages are on. All circuits are checked to
calculate the control discharge pressure, and should be in the same fan bank.
If the control discharge pressure is less than Setpoint #45, then both condenser stages are off and the fan speed is
zero.
If the control discharge pressure is greater than Setpoint #45 and less than Setpoint #46 stage 1 will be on. The fan
speed will be equal the value of (Setpoint #55 minus Setpoint #54) divided by (Setpoint #46 minus Setpoint #45)
and then multiplied by (control discharge pressure minus Setpoint #46) plus Setpoint #54.
If the control discharge pressure increases while in stage 1 above the value of Setpoint #46 plus Setpoint #48 for the
time contain in Setpoint #49 stage 2 will be entered. Both relays will be on and the fan speed will be equal the value
of (Setpoint #55 minus Setpoint #54) divided by Setpoint #46 and then multiplied by (control discharge pressure
minus Setpoint #46) plus Setpoint #54.
If the speed of the condenser fan is less than Setpoint #54 it will be set to that value or if the speed of the condenser
fan is greater than Setpoint #55 it will be set to that value.
The Common VFD Fan with a Bypass type of condenser has one fan. All circuits will use this fan; make sure that all
circuits in the Circuit Base point to the same common fan bank. The above setup shows that there is one condenser
stage. However this type requires the following three consecutive Relay Outputs to be set up. For example:
91
MCS-MAGNUM-V. 14 REVISION 3.2
This type of condenser requires one condenser fault. If the fault occurs then the VFD will be bypassed and the fan will run at
100% if needed.
45 CND STG1 ON When the discharge pressure is above this value, turn on the first stage of the
(RO Type) condenser fans.
‘Time (sec)’ field: (Applies to compressors with shared condensers) If non-zero,
then the compressor in startup state will not be in sole control of the condenser
fans, it will control off of highest discharge pressure. If zero, then compressor in
startup will have sole condenser control for 5 minutes. This option is selected in
in the ‘Newly started Comp Controls Common Fan Bank’ box in the ‘Condenser
Information’ panel under the MAG V8 screen.
46 CND STG1 OFF If stage 1 of condenser capacity is on and the discharge pressure drops below this
(RO Type) value, then turn this stage off.
54 CND MIN SPD Minimum speed percentage for variable speed condenser control.
(RO Type)
55 CND MAX SPD Maximum speed percentage for variable speed condenser control.
(RO Type)
90 COND FAULT For Condensers with Fault Indicators: If Setpoint is active, a condenser fault oc-
curs, and the Setpoint type is Alarm, then an alarm message will be generated.
If the type is Lockout, and a condenser fault occurs, then all of the compressors
associated with this fault will be locked off.
For Common VFD Fan Condensers with Bypass: Time in seconds before the by-
pass can be used when a fault has occurred.
When the discharge control pressure is greater than 250 psi the relay VFD ENABLE will be on and the VFD on the
fan will be set to 100%. If the discharge control pressure drops to 210, then the fan speed will be set to 60%. The
discharge control pressure is half of its Cut In and Cut Out range (250 – 170 = 80 / 2 = 40= 170 = 210) therefore, the
VFD will be positioned to half of its range (100 –20 = 80 / 2 = 40 + 20 = 60). The VFD will continue to be modulated
in this matter until the discharge control pressure drops below 170. Then the VFD will be at 0% and relay VFD
ENABLE will remain on. If the pressure goes above 170 the VFD will be modulated. For example if the discharge
control pressure goes to 190.0 the VFD will be set to 50%.
92
MCS-MAGNUM-V. 14 REVISION 3.2
If the fault resets itself, and is no longer on, the state of VFD LOAD will be set to AUTO, the VFD BYPASS relay will
be turned off and VFD will be enabled to control the fan speed if it is needed.
11.77.1.2. General
Select the Run/Stop Switch and the Alarm Relay from dropdown lists (if applicable).
Select either Water In or Water Out for the control of the boilers.
Select the Water In and Water Out sensors from dropdown lists (if applicable).
11.77.1.3. Pumps
Select the Pump Control method:
# of Pumps: Indicates the number of pumps that will be controlled (Maximum of 12).
Max Pumps Allowed: Indicates the maximum number of pumps that can be turned on concurrently.
93
MCS-MAGNUM-V. 14 REVISION 3.2
Starting Pump RO: Select the starting pump Relay Output from a dropdown list. There must be one Relay Output
for each pump.
Pump VFD: Select the pumps variable speed Analog Output from a dropdown list (if applicable).
Pump In PSI: Select the sensor from a dropdown list that will display the pressure coming into the pumps.
Pump Out PSI: Select the sensor from a dropdown list that will display the pressure leaving the pumps. If this is
provided the system will calculate a pressure differential by subtracting Pump In PSI from the value of this sensor.
The target Setpoint #160 must reflect the target as a differential.
Starting Pump Proof: Select the sensor from a dropdown list that will indicate the status of a pump that has been
turned on. If used, there must be one input per pump. If the pump is on and the associated digital input is OFF a
boiler fault has occurred.
Pump VFD Fault: Select the sensor from a dropdown list that will indicate when a pump VFD has occurred. If no
sensor is selected this safety will not be checked.
Starting Pump Fault: Select the sensor from a drop down list that will indicate the status of a pump that has been
turned on. If used, there must be one input per pump. If the associated pump is on and this digital input is ON a fault
has occurred.
Pump Amps: Select the sensor from a drop down list that will indicate the amp draw of the associated pump. If
selected, there must be one sensor per pump. If no sensor is selected, the amp safety will not be checked.
11.77.1.4. Boiler
# of Boilers: Indicates the number of boilers that will be controlled (Maximum of 12).
Starting Boiler RO: Select the starting boiler relay output from a drop down list. There must be one Relay Output
for each boiler.
Max Boilers Allowed: Indicate the maximum number of boilers that can be turned on concurrently.
Starting Boiler Proof: Select the sensor from a dropdown list that will indicate the status of a boiler that has been
turned on. If used, there must be one input per boiler. If the associated boiler is on and this digital input is OFF a
boiler fault has occurred.
Starting Boiler Fault: Select the sensor from a dropdown list that will indicate the status of a boiler that has been
turned on. If used, there must be one input per boiler. If the associated boiler is on and this digital input is ON a fault
has occurred.
11.77.2 The following set points are required by the Boiler Logic
94
MCS-MAGNUM-V. 14 REVISION 3.2
95
MCS-MAGNUM-V. 14 REVISION 3.2
96
MCS-MAGNUM-V. 14 REVISION 3.2
Screen 1
Screen 2
If there are more than 4 pumps addition screens will be displayed showing up to the maximum of 12 pumps. The
status of 4 pumps will be displayed per screen.
Screen 3
97
MCS-MAGNUM-V. 14 REVISION 3.2
Screen 4
If there are more than 4 boiler stages addition screens will be displayed showing up to the maximum of 12 boiler
stages. The status of 4 boiler stages will be displayed per screen.
In the General Information panel under the MAG V8 screen, the Unit Type must be set to heat pump.
In the Evaporator Information panel the Type of Defrost must not be ‘NONE’.\
Either or both Condenser Coil Temperature #1 or #2 must be set up in the Circuit Base screen.
If the reversing valve is common, it is specified in the General Information panel under the MAG V8 screen. If
individual reversing valves, they must be in the compressor relay sequence, following the 3rd liquid line solenoid of
each circuit.
Heat pump-defrost Setpoints #158 - #162 must be set up. Note: The value in these Setpoints will be used
regardless if they are active or not. (See section 13 for Setpoint description)
In the “DEFROST” state the LLS will be turned on and the reversing valve will be turned off. This will reverse the flow
99
MCS-MAGNUM-V. 14 REVISION 3.2
of hot gas and perform the defrost function. The condenser fans will also be affected during this time and the amp’s
slide adjustment will be set to 70.0% if a variable step compressor.
The DEFROST state will be terminated when both condenser coil temperatures, are greater than Setpoint #161
“DEF TERM TMP” or the state time is greater than Setpoint #162 “DEF TERM DEL”. The circuit state will be
changed to “DEF PUMP DOWN”.
The action and termination in the “DEF PUMP DOWN” state is the same as “DEF PREPMP OUT”. When this state
is terminated a variable step compressor will have its state changed to “HOLD”. A fixed step compressor’s state will
return to its state prior to the defrost cycle and the LLS will be turned on.
When the system is in a run condition, both lead pumps of each bank will be turned on to provide flow. If either of the
lead pumps fails, the running pump will be locked off and the backup pump for that respective bank will be started.
The circuits associated with the failed pump will be moved to a no flow state (disabled) as soon as flow is lost. If flow
is restored the circuit will be enabled again. If both pumps on a bank fail, then the circuit will be in a safety off state.
The 2 pump banks function independently, however, they both use common Setpoints to determine pump rotation,
pump lead, and safety times.
The Pump/Fan section now consists of entries for bank A and bank B.
100
MCS-MAGNUM-V. 14 REVISION 3.2
Select Output and Sensor Inputs per circuit panel under the Circuit Base button:
In the Flow column, select the flow indicators for the individual pump bank control.
Pump bank B has 2 pumps, Pump 1-B and Pump 2-B, and the flow indicator is Flow B. If Flow B indicates that there
is no flow, then circuits 2 and 4 will be disabled.
However if Flow A indicates that there is flow then circuits 1 and 3 will be in a ready to run state and Flow B indicates
that there is flow then circuits 2 and 4 will be in a ready to run state. The circuit states are based upon the flow
indicators associated with that circuit.
If Flow A indicates no flow, then circuits 1 and 3 will immediately be placed in a disabled state due to no flow, the
lead pump will be Locked Out after the time delay as stated in the ‘Value’ field in Setpoint #105 “PUMP FAILURE”.
When the lead pump is Locked Out the backup pump will be started. If flow is returned, then circuits 1 and 3 will be
allowed to run. If flow is not returned and the backup pump is Locked Out, then circuits 1 and 3 will be placed in a
Safety Off state. The same is true with Flow B and circuits 2 and 4.
The unit and all individual circuits will be placed in a Lockout state if all pumps have failed.
101
MCS-MAGNUM-V. 14 REVISION 3.2
2) RO Type selected.
Condenser Level: select from a drop down list of sensor inputs. This sensor will provide the level of the
condenser liquid level.
Valve Position: select from a drop down list of sensor inputs. This sensor will provide the position of the CLLC
valve.
In the Relay Output Information screen 2 relays must be added at the end of the compressor relay output
sequence:
The relays must be set up as Pulse Relay type and the Pulse on Time (in tenth of second) and the Delay
Between Pulse (in seconds) columns must be setup. Suggest the initial values are Pulse on Time of 5 (.5
seconds) and Delay Between Pulse of 2 (2 seconds).
3) AO Type selected.
Condenser Level: select from a drop down list of sensor inputs. This will provide the level of the condenser liquid
level.
Valve Actuator: select from a drop down list of analog outputs. This will be the analog output that controls the
CLLC valve.
102
MCS-MAGNUM-V. 14 REVISION 3.2
CLLC OFF: in this state there are no compressors on. The CLLC valve will be move to 100% open.
CLLC UNSTABLE: in this state a compressor is running but it either in startup mode or the chilled water
temperature is not within an acceptable range. The CLLC valve is not being controlled to provide the target level
of the condenser liquid but to provide a liquid seal to enable the compressor to generate lift. This state will be
entered whenever the chilled water temperature is not within an acceptable range. Refer to section on CLLC
Determining Stable or Unstable Condition.
CLLC STABLE: in this state a compressor is running but and the chilled water temperature is within an
acceptable range. The CLLC valve will be modulated to maintain the condenser liquid level within the target
control zone as defined by set point #216. Refer to section on CLLC Determining Stable or Unstable Condition.
103
MCS-MAGNUM-V. 14 REVISION 3.2
either (AO) or (RO) indicating the type of valve control that has been selected.
VALVE OPENING (XX): The unit is in an unstable state and valve is being opened.
VALVE CLOSING (XX): The unit is in an unstable state and valve is being closed.
VALVE HOLDING (XX): The unit is in an unstable state and valve not being changed.
ZONE 1 VLV HOLDG (XX): The unit is stable and the condenser liquid level is in ZONE 1 which requires no valve
positioning.
ZONE 2 VLV HOLDG (XX): The unit is stable and the condenser liquid level is in ZONE 2 and the valve position is
not being changed as the condenser liquid level rate of change is decreasing at an acceptable rate.
ZONE 2 VLV OPENG (XX): The unit is stable and the condenser liquid level is in ZONE 2 above the target opening
and the liquid level rate of change is not decreasing at an acceptable rate; therefore, the valve must be opened.
ZONE 2 VLV CLOSG (XX): The unit is stable and the condenser liquid level is in ZONE 2 below the target opening
and the liquid level rate of change is not increasing at an acceptable rate; therefore, the valve must be closed.
ZONE 3 VLV HOLDG (XX): The unit is stable and the condenser liquid level is in ZONE 3 and the valve position is
not being changed as the condenser liquid level rate of change is decreasing at an acceptable rate.
ZONE 3 VLV OPENG (XX): The unit is stable and the condenser liquid level is in ZONE 3 above the target opening
and the liquid level rate of change is not decreasing at an acceptable rate; therefore, the valve must be opened.
ZONE 3 VLV CLOSG (XX): The unit is stable and the condenser liquid level is in ZONE 3 below the target opening
and the liquid level rate of change is not increasing at an acceptable rate; therefore, the valve must be closed.
ZONE 4 VLV HOLDG (XX): The unit is stable and the condenser liquid level is in ZONE 4 and the valve position is
not being changed as the condenser liquid level rate of change is decreasing at an acceptable rate.
ZONE 4 VLV OPENG (XX): The unit is stable and the condenser liquid level is in ZONE 4 above the target
opening and the liquid level rate of change is not decreasing at an acceptable rate; therefore, the valve must be
opened.
ZONE 4 VLV CLOSG (XX): The unit is stable and the condenser liquid level is in ZONE 4 below the target opening
and the liquid level rate of change is not increasing at an acceptable rate; therefore, the valve must be closed.
VLV FULLY OPENED (XX): The valve position is fully opened, 100%.
bThe valve position is fully closed, 0%.
The CLLC status is display as the first line of the Status screen.
1) The CLLC State.
2) The CLLC Time, this is the time in the display CLLC State.
3) Level, this is the level of the condenser liquid level.
4) Rate of Change, this is the change of the liquid level.
5) Valve State.
6) Valve %, if AO this is the actual value of the analog output; if RO then this is the value reported by the sensor
input of the valve position feedback pot.
7) Delay is the delay between valve adjustments.
104
MCS-MAGNUM-V. 14 REVISION 3.2
In this state the purpose of the CLLC is to position the valve to create a sub-cooler level to get the efficiency out of
the chiller and not to control the valve within a couple percent of the actual set point. As long as the condenser liquid
level is stable and in the control range then the valve is being controlled properly. To accomplish this control of the
CLLC valve is based upon the level of the condenser liquid level.
The value of set point #216 contains the target and the ‘Time(sec)’ field provides a plus and minus dead band. For
example if the value is 60.0 and the ‘Time(sec)’ field is 3 then the control zone will be between 57.0 and 63.0. An
additional control range is developed by adding/subtracting the ‘Time(sec)’ field to the original zone.
Setpoints 1 (chilled water target), 2 (plus dead band) & 3 (negative dead band) are used in this determination.
The zone boundaries can be increased by using the ‘Time(sec)’ field as a multiplier (Setpoint #2 for positive and
Setpoint #3 for negative boundaries). If this value is a 0 or 1 then the multiplier will be an assumed 1. In the example
above, if the ‘Time(sec)’ field was set to 2, then the differential between zones would be 1.0°F instead of 0.5°F; if set
to 3, then the zone differential would be 1.5°F, etc.
105
MCS-MAGNUM-V. 14 REVISION 3.2
Once the chilled water temperature is within the stable zone the CLLC will control the CLLC valve to maintain the
condenser liquid level. Once the system is considered stable it will remain in this condition unless the chilled water
temperature raises or drops into the unstable zones.
2) CLLC UNSTABLE in this state the compressor is on but the chilled water is not with in an acceptable
temperature range. Refer to section on CLLC Determining Stable or Unstable Condition.
In this state the purpose of the CLLC is to position the valve to create a liquid seal so that the chiller can generate lift
and pull the water temperature within the acceptable range.
If the liquid level is above the value in set point #216, the CLLC valve setting will remain at its present position. The
valve state will be VALVE HOLD.
If the liquid level is less than the value in set point #216, the CLLC valve setting will be closed until its opening is equal
to the value of set point #217, once this is reached the valve state will be VALVE HOLD. The CLLC will not leave this
state until the chilled water temperature returns to acceptable level or the compressor is turned off.
3) CLLC STABLE in this state the compressor is on and the chilled water is with in an acceptable temperature
range. Refer to section on CLLC Determining Stable or Unstable Condition.
In this state the purpose of the CLLC is to position the valve to create a sub-cooler level to get the efficiency out of the
chiller and not to control the valve within a couple percent of the actual set point. As long as the condenser liquid level
is stable and in the control range then the valve is being controlled properly. To accomplish this control of the CLLC
valve is based upon the level of the condenser liquid level.
The value of set point #216 contains the target and the ‘Time(sec)’ field provides a plus and minus dead band. For
example if the value is 60.0 and the ‘Time(sec)’ field is 3 then the control zone will be between 57.0 and 63.0. An
additional control range is developed by adding/subtracting the ‘Time(sec)’ field to the original zone.
Zone
Reduce Delay/4 4
69°
Reduce Delay/3 3 Valve State = Valve Opening
66°
Reduce Delay/2 Check slope of liquid level if
2
63° less than Setpoint open valve
1
Target 60°
1 Valve State = Valve Hold
57°
Check slope of liquid level if
Reduce Delay/2 2
greater than Setpoint close valve
54°
Reduce Delay/3 3 Valve State = Valve Closing
51°
Reduce Delay/4 4
If the condenser liquid level is above the target and in ZONES 2, 3, or 4, the rate of change of the condenser
liquid level will be checked. If the rate of change is greater than the negative value of set point #216, this
indicates that the condenser liquid level is NOT decreasing a rate fast enough; therefore, the valve position must
be increased, opened. The valve state will indicate that the valve is opening.
If the condenser liquid level is below the target and in ZONES 2, 3, or 4, the rate of change of the condenser
liquid level will be checked. If the rate of change is greater than the value of set point #216, this indicates that
the condenser liquid level is increasing a rate fast enough make no change to the valve positioning. The valve
state will indicate that the valve is holding.
If the condenser liquid level is below the target and in ZONES 2, 3, or 4, the rate of change of the condenser
liquid level will be checked. If the rate of change is not greater than the value of set point #216, this indicates
that the condenser liquid level is NOT increasing a rate fast enough; therefore, the valve position must be
decreased, closed. The valve state will indicate that the valve is closing.
11.80.11 Condenser Liquid Level Adjustment
If the valve type is a Relay Output, the pulse time and pulse delay will be the same for all zones.
If the valve type is an Analog Output, the amount of valve adjustment will be the difference from the Condenser
Liquid Level Target (Setpoint #216). The adjustment will be limited to the setting of the ‘Window to Extend Safety
Time’ of Setpoint #216. This is true for all zones.
Each I/O board in the system will have its own column (Relay Output boards on the left, Sensor Input boards on the
right). Each circuit (compressor) will have its own row, as well as the entire chiller and no lockout options.
To setup this feature, first select Yes to the prompt ‘Enable locks based on Boards?’ Then simply select which circuit(s)
you want locked out when I/O communications are lost for each particular board. If ‘No Lockouts’ is selected, then
the unit will continue to run normally when communication with that board is lost. If ‘Lockout Chiller’ is selected, then
the entire unit will lockout when communication with that board is lost. If ‘Lockout Comp #X’ is selected then all the
107
MCS-MAGNUM-V. 14 REVISION 3.2
circuit(s) that match will lockout when communication with that board is lost.
When communication is reestablished the circuit state is automatically reset from “LOST IO LOCKED” to “CMP
ANTICYCLE” or “COMP OFF/READY”.
108
MCS-MAGNUM-V. 14 REVISION 3.2
When the password for Factory Startup activation is entered and the function is active, the user is allowed to
deactivate it. When deactivated the chiller state will be changed to UNIT IN POWER UP and normal operations will
be allowed.
To activate the Factory Startup function from the Magnum keypad, open the Password menu option and enter the
Factory Startup password. The following pop-up will appear asking if you would like to activate this feature.
When active, the following heading will appear on all Status screens, showing that the unit is locked out until Factory
Startup authorization is entered.
109
MCS-MAGNUM-V. 14 REVISION 3.2
To deactivate the Factory Startup function, navigate back to the password screen and the following screen will appear.
Select Yes to deactivate.
110
MCS-MAGNUM-V. 14 REVISION 3.2
When the password for Maximum Run Time is entered the user can reset the maximum number of compressor
run hours. If reset is selected and chiller state is MAXIMUM RUN TIME the state will be changed to UNIT IS OFF.
The maximum run hours counters for all compressors will be reset and normal processing will be allowed. If reset is
selected and the chiller state is not MAXIMUM RUN TIME the state will not be changed but the maximum run hours
counter will be reset.
To activate the Maximum Run Time function from the Magnum keypad, open the Password menu option and enter the
Maximum Run Time password. The following pop-up will appear asking if you would like to activate this feature.
When active, the following heading will appear on all Status screens, showing that the unit is locked out until Maximum
Run Time authorization is entered.
111
MCS-MAGNUM-V. 14 REVISION 3.2
To deactivate the Maximum Run Time function, navigate back to the password screen and the following screen will
appear. Select Yes to deactivate.
Enter the correct password to deactivate the Maximum Run Time function.
112
MCS-MAGNUM-V. 14 REVISION 3.2
11.83.1 Operands
Operands are the building blocks of the Magnum User Logic. An operand consists of
two parts: the top cell provides a drop down list to select the types and then a drop
down list to select the item within that type:
TYPE ITEM
Fixed Value Enter a fixed value with decimal place if required.
SI Select Sensor Input
AO Select Analog Output
RO Select Relay Output
Setpoints Select Setpoint, number is also display for ease of selection. All Setpoints are shown,
both active and inactive.
CLOCK Select system clock. The following can be selected: Hours, Minutes, Seconds, Day of
Month, Day of Week (1 = Sunday - 7 = Saturday), Year (2 digits), and Month (1-12).
These are current values from the Magnum.
Unit Chiller The following can be selected: FLA %, Steps wanted, Steps ON, Steps available,
steps allowed on, % Load, STATE, Lead Compressor, Mode (cooling or heating), and
Ice Mode Done (if ice mode option selected).
Compressor #1 - The following can be selected for any compressor: Compressor State, Suction
Compressor #20 Pressure, Discharge Pressure, Oil Pressure Differential, Motor Amps, Suction Tem-
perature, Discharge Temperature, Oil Temperature, Motor Temperature, EXV Value
Position, Oil Pressure, Refrigerant Temperature, Flow Indicator, Compressor Proof,
Compressor Speed, Oil Float, Refrigerant Level, Condenser Temperature #1, Con-
denser Temperature #2, Fla %, Saturated Suction Temperature, Suction Superheat,
Saturated Discharge Temperature, and Discharge Superheat.
Note all of the above may not exist for an individual configuration.
The value that is passed to the User Logic depends on the item selected. For example:
113
MCS-MAGNUM-V. 14 REVISION 3.2
11.83.2 Operators
The action cell is located between the operand cells.
The following actions can be selected from a drop down list this will determine the value of the sensor:
114
MCS-MAGNUM-V. 14 REVISION 3.2
First select the display type and then complete the selections. Note operand #1 and #2 are defined in the Operands
section above and the Action Cell is defined in the drop down menu between.
The window below is from MCS-Config is configuring a User Logic type of sensor. It is a digit type of sensor (ON or
OFF) and it is only looking an Operand 1. If the RO Sump and Doors is ON then the value of this sensor will be ON.
The window below is from MCS-Config building a User Logic type of sensor. It is a pressure type of sensor (display a
value with 1 decimal place). The value of this sensor will be result of Operand 1 minus Operand 2.
115
MCS-MAGNUM-V. 14 REVISION 3.2
116
MCS-MAGNUM-V. 14 REVISION 3.2
In the above example the “Store Alarm Msg“ option has been enabled. When this relay goes from an OFF to an ON
state an alarm message will be generated with the name of this relay.
In the above example the “Store Alarm Msg“ option has been enabled. When this relay goes from an OFF to an ON
state an alarm message will be generated with the name of this relay.
117
MCS-MAGNUM-V. 14 REVISION 3.2
In this example, if either of the operands become true, then this relay will turn ON, an alarm message will be
generated, and the General alarm relay will also turn ON.
In the above example if relay ‘RUN’ is OFF, the value of this Analog Output will be zero. If ON, the value will be
calculated based on the Sensor Input ‘ChilWtrOut’. If ‘ChilWtrOut’s value is 40 (or less) then the Analog Output will
be set to 0%; If 60 (or above) then the Analog Output will be 100%. The output value will vary based on a linear
calculation between these two points.
118
MCS-MAGNUM-V. 14 REVISION 3.2
All alarms have the same format. The alarm is identified and is date/time stamped. Alarms can be viewed from the
Magnum keypad by selecting the ‘Alarms’ from the main menu, or through MCS-Connect.
119
MCS-MAGNUM-V. 14 REVISION 3.2
RS485 CHANGED – Generated when a user makes changes to the RS485 address through the Keypad/
Display.
CF CARD INSERTED – Generated when a user inserts a Compact Flash memory card into the Magnum.
CF CARD REMOVED – Generated when a user removes a Compact Flash memory card from the Magnum.
The following is a list of safeties that are incorporated in the standard chiller algorithm control. These safeties are
checked every second. For a system with multiple circuits, each one is tested individually. If a safety trip occurs, only
that respective compressor will be affected, the others will continue to function normally.
No Flow Protection
If a flow switch is used, then the entire system will be Locked Out if Setpoint #105 is active. If the Setpoint is inactive,
the Magnum will determine if there is a second pump, if so it will be started. Else, the system will shut down and
automatically restart when the flow switch is on, indicating flow has returned. There is also an option to have a flow
switch for each individual circuit. Refer to section 11 Setpoint #105.
the suction pressure. When this safety trip occurs, all compressors in the same suction group will react in the same
manner. Refer to section 11 Setpoint #77.
No Compressor Proof
If a compressor is called to be on and the compressor proof digital input is OFF, a NO COMP PROOF alarm will be
generated. Refer to section 11 Setpoint #96.
123
MCS-MAGNUM-V. 14 REVISION 3.2
124
MCS-MAGNUM-V. 14 REVISION 3.2
125
MCS-MAGNUM-V. 14 REVISION 3.2
126
MCS-MAGNUM-V. 14 REVISION 3.2
13.3. MCS-SI16-AO4
127
MCS-MAGNUM-V. 14 REVISION 3.2
13.4. MCS-RO10
128
MCS-MAGNUM-V. 14 REVISION 3.2
130
MCS-MAGNUM-V. 14 REVISION 3.2
*- Indicates value multiplied by 10 to include one decimal place. (I.e. BMS value of 500 indicates actual value 50.0)
131
MCS-MAGNUM-V. 14 REVISION 3.2
BACnet BACnet
Magnum ID BACnet Name Modbus N2 Magnum ID BACnet Name Modbus N2
Relay M - 1 BO: 1 Refer to Config 00001 BO: 1 Relay 4 - 1 BO:41 Refer to Config 00041 BO: 41
Relay M - 2 BO: 2 Refer to Config 00002 BO: 2 Relay 4 - 2 BO:42 Refer to Config 00042 BO: 42
Relay M - 3 BO: 3 Refer to Config 00003 BO: 3 Relay 4 - 3 BO:43 Refer to Config 00043 BO: 43
Relay M - 4 BO: 4 Refer to Config 00004 BO: 4 Relay 4 - 4 BO:44 Refer to Config 00044 BO: 44
Relay M - 5 BO: 5 Refer to Config 00005 BO: 5 Relay 4 - 5 BO:45 Refer to Config 00045 BO: 45
Relay M - 6 BO: 6 Refer to Config 00006 BO: 6 Relay 4 - 6 BO:46 Refer to Config 00046 BO: 46
Relay M - 7 BO: 7 Refer to Config 00007 BO: 7 Relay 4 - 7 BO:47 Refer to Config 00047 BO: 47
Relay M - 8 BO: 8 Refer to Config 00008 BO: 8 Relay 4 - 8 BO:48 Refer to Config 00048 BO: 48
Relay M - 9 BO: 9 Refer to Config 00009 BO: 9 Relay 4 - 9 BO:49 Refer to Config 00049 BO: 49
Relay M-10 BO:10 Refer to Config 00010 BO: 10 Relay 4 -10 BO:50 Refer to Config 00050 BO: 50
Relay 1 - 1 BO:11 Refer to Config 00011 BO: 11 Relay 5 - 1 BO:51 Refer to Config 00051 BO: 51
Relay 1 - 2 BO:12 Refer to Config 00012 BO: 12 Relay 5 - 2 BO:52 Refer to Config 00052 BO: 52
Relay 1 - 3 BO:13 Refer to Config 00013 BO: 13 Relay 5 - 3 BO:53 Refer to Config 00053 BO: 53
Relay 1 - 4 BO:14 Refer to Config 00014 BO: 14 Relay 5 - 4 BO:54 Refer to Config 00054 BO: 54
Relay 1 - 5 BO:15 Refer to Config 00015 BO: 15 Relay 5 - 5 BO:55 Refer to Config 00055 BO: 55
Relay 1 - 6 BO:16 Refer to Config 00016 BO: 16 Relay 5 - 6 BO:56 Refer to Config 00056 BO: 56
Relay 1 - 7 BO:17 Refer to Config 00017 BO: 17 Relay 5 - 7 BO:57 Refer to Config 00057 BO: 57
Relay 1 - 8 BO:18 Refer to Config 00018 BO: 18 Relay 5 - 8 BO:58 Refer to Config 00058 BO: 58
Relay 1 - 9 BO:19 Refer to Config 00019 BO: 19 Relay 5 - 9 BO:59 Refer to Config 00059 BO: 59
Relay 1- 10 BO:20 Refer to Config 00020 BO: 20 Relay 5 -10 BO:60 Refer to Config 00060 BO: 60
Relay 2 - 1 BO:21 Refer to Config 00021 BO: 21 Relay 6 - 1 BO:61 Refer to Config 00061 BO: 61
Relay 2 - 2 BO:22 Refer to Config 00022 BO: 22 Relay 6 - 2 BO:62 Refer to Config 00062 BO: 62
Relay 2 - 3 BO:23 Refer to Config 00023 BO: 23 Relay 6 - 3 BO:63 Refer to Config 00063 BO: 63
Relay 2 - 4 BO:24 Refer to Config 00024 BO: 24 Relay 6 - 4 BO:64 Refer to Config 00064 BO: 64
Relay 2 - 5 BO:25 Refer to Config 00025 BO: 25 Relay 6 - 5 BO:65 Refer to Config 00065 BO: 65
Relay 2 - 6 BO:26 Refer to Config 00026 BO: 26 Relay 6- 6 BO:66 Refer to Config 00066 BO: 66
Relay 2 - 7 BO:27 Refer to Config 00027 BO: 27 Relay 6 - 7 BO:67 Refer to Config 00067 BO: 67
Relay 2 - 8 BO:28 Refer to Config 00028 BO: 28 Relay 6 - 8 BO:68 Refer to Config 00068 BO: 68
Relay 2 - 9 BO:29 Refer to Config 00029 BO: 29 Relay 6 - 9 BO:69 Refer to Config 00069 BO: 69
Relay 2 -10 BO:30 Refer to Config 00030 BO: 30 Relay 6 - 10 BO:70 Refer to Config 00760 BO: 70
Relay 3 - 1 BO:31 Refer to Config 00031 BO: 31 Relay 7 - 1 BO:71 Refer to Config 00071 BO: 71
Relay 3 - 2 BO:32 Refer to Config 00032 BO: 32 Relay 7 - 2 BO:72 Refer to Config 00072 BO: 72
Relay 3 - 3 BO:33 Refer to Config 00033 BO: 33 Relay 7 - 3 BO:73 Refer to Config 00073 BO: 73
Relay 3 - 4 BO:34 Refer to Config 00034 BO: 34 Relay 7 - 4 BO:74 Refer to Config 00074 BO: 74
Relay 3 - 5 BO:35 Refer to Config 00035 BO: 35 Relay 7 - 5 BO:75 Refer to Config 00075 BO: 75
Relay 3- 6 BO:36 Refer to Config 00036 BO: 36 Relay 7 - 6 BO:76 Refer to Config 00076 BO: 76
Relay 3 - 7 BO:37 Refer to Config 00037 BO: 37 Relay 7 - 7 BO:77 Refer to Config 00077 BO: 77
Relay 3 - 8 BO:38 Refer to Config 00038 BO: 38 Relay 7 - 8 BO:78 Refer to Config 00078 BO: 78
Relay 3 - 9 BO:39 Refer to Config 00039 BO: 39 Relay 7 - 9 BO:79 Refer to Config 00079 BO: 79
Relay 3 - 10 BO:40 Refer to Config 00040 BO: 40 Relay 7 - 10 BO:80 Refer to Config 00070 BO: 80
132
MCS-MAGNUM-V. 14 REVISION 3.2
Analog Output PointsAnalog Output points are read-only. Sensor numbering is based upon SI16-
AO4 hardware type board.
Notable BACnet properties available: Units
*- Indicates value multiplied by 10 to include one decimal place. (I.e. BMS value of 500 indicates
actual value 50.0)
133
MCS-MAGNUM-V. 14 REVISION 3.2
15.3. Setpoints
Setpoints are read-only. Notable BACnet properties available: Units
BAC-
Magnum net ID BACnet Name Modbus N2
Setpoint #1 AV:0 STP# 1-<Setpoint name> 40301 ADF:1
Setpoint #21 AV:88 STP# 21-<Setpoint name> 40321 ADF:89
Setpoint AV:230 STP# 163-<Setpoint
#163 name> 40463 ADF:231
*- Indicates value multiplied by 10 to include one decimal place. (I.e. BMS value of 500 indicates
actual value 50.0)
134
MCS-MAGNUM-V. 14 REVISION 3.2
136
MCS-MAGNUM-V. 14 REVISION 3.2
137
MCS-MAGNUM-V. 14 REVISION 3.2
*- Indicates value multiplied by 10 to include one decimal place. (I.e. BMS value of 500 indicates
actual value 50.0)
The MCS-Magnum must be setup to accept these inputs. The configuration file must contain a
Network Run/Stop, Network Target, Network Demand FLA, and Network Demand Steps sensors.
Magnum BACnet ID BACnet Name Modbus N2
Network Run/Stop AV:246 Net_R/S 40201 BO:247
Network Target/Reset AV:247 Net_Tar/Res 40202 AO:248
Network Demand/FLA AV:248 Net_Demad_FLA 40204 AO:249
Network Demand/Steps AV:249 Net_Demad_Steps 40205 AO:250
The MCS-Magnum must be setup to accept these inputs. The configuration file in the MCS-Magnum
must contain a Network Run/Stop, and /or Network Target Reset, and/or Network Demand FLA,
and/or Network Demand Steps sensors. Note the following Information panel has a Network Run/
Stop, and /or Network Target Reset sensors inputs indicated. This is an example of how MCS-Config
must be setup in the General Information and Evaporator Information panels.
138
MCS-MAGNUM-V. 14 REVISION 3.2
139
MCS-MAGNUM-V. 14 REVISION 3.2
140
MCS-MAGNUM-V. 14 REVISION 3.2
141
MCS-MAGNUM-V. 14 REVISION 3.2
181 XX
Bacnet Bacnet MS/TP
Vendor ID Address
The Bacnet address can be verified and changed (with the proper authorization code) from the Keypad/LCD. The
following steps will display the Bacnet MSTP Network address, and the Baud Rate:
Press the Menu key, select Serv Tools, and then press the Enter key.
Select RS485 Network then press Enter.
Select Protocol then press Enter. Change the protocol to BACnet MSTP
Select address then press Enter. Change the address so it matches the last two digits of the device ID then
press Enter.
Select Protocol then press Enter. Set the protocol back to MCS.
Press the Menu key, select Serv Tools, and then press the Enter key.
Select Ethernet Network then press Enter.
Set “DHCP Enabled” to NO.
Set the “IP Address”.
Set the “Subnet Mask”.
Set “Default Gateway”.
If you are going to let your network assign the IP Address, Subnet Mask, and Default Gateway:
Press the Menu key, select Serv Tools, and then press the Enter key.
Select Ethernet Network then press Enter.
Set “DHCP Enabled” to YES.
Connect the MCS-Magnum to the network and power up the board.
Press the Menu key, select Serv Tools, and then press the Enter key.
Select RS485 Network then press Enter.
Select Protocol then press Enter. Change the protocol to Modbus.
Select address then press Enter. Change the address then press Enter.
Select Baud then press Enter. Set the baud rate then press Enter.
Connect the communication wires to the TX RS485 three-position terminal located above the Ethernet
connector.
142
MCS-MAGNUM-V. 14 REVISION 3.2
Press the Menu key, select Serv Tools, and then press the Enter key.
Select Ethernet Network then press Enter.
Set “DHCP Enabled” to NO.
Set the “IP Address”.
Set the “Subnet Mask”.
Set “Default Gateway”.
If you are going to let your network assign the IP Address, Subnet Mask, and Default Gateway:
Press the Menu key, select Serv Tools, and then press the Enter key.
Select Ethernet Network then press Enter.
Set “DHCP Enabled” to YES.
Connect the MCS-Magnum to the network and power up the board.
15.10.4 Johnson N2
The N2 address can be verified and changed (with the proper authorization code) from the keypad/LCD.
Press the Menu key, select Serv Tools, and then press the Enter key.
Select RS485 Network then press Enter.
Select Protocol then press Enter. Change the protocol to N2.
Select address then press Enter. Change the address then press Enter.
Select Baud then press Enter. Set the baud rate then press Enter.
Connect the communication wires to the TX RS485 three-position terminal located above the Ethernet
connector.
143
MCS-MAGNUM-V. 14 REVISION 3.2
15.11. Reciprocating Compressors (Recip Comp w/Oil) and (Recip Comp w/o Oil)
Compressor relay
Part winding compressor relay (OPTIONAL)
Liquid line solenoid
Unloader 1 (OPTIONAL)
Unloader 2 (OPTIONAL)
Unloader 3 (OPTIONAL)
Oil pump (OPTIONAL, ONLY USED WITH Recip Comp w/Oil)
Oil heater (OPTIONAL, ONLY USED WITH Recip Comp w/Oil)
Hot gas bypass (OPTIONAL)
Common Hot gas bypass (OPTIONAL)
Liquid injection (OPTIONAL)
Fast unloader (OPTIONAL)
Second liquid line solenoid (OPTIONAL)
Oil equalization (OPTIONAL)
Oil seal cooler (OPTIONAL)
VI increase valve % (OPTIONAL)
VI decrease valve % (OPTIONAL)
Start unloader bypass (OPTIONAL)
Low disc superheat (OPTIONAL)
Hot gas reheat off (OPTIONAL) If hot gas reheat all 3 hot gas relays are required.
Hot gas reheat on (OPTIONAL)
Hot gas reheat bleed (OPTIONAL)
Third liquid line solenoid (OPTIONAL)
Reversing valve (heat pump) (OPTIONAL)
Liquid injection #2 (OPTIONAL)
Mod motor (OPTIONAL)
144
MCS-MAGNUM-V. 14 REVISION 3.2
Hot gas reheat off (OPTIONAL) If hot gas reheat all 3 hot gas relays are required.
Hot gas reheat on (OPTIONAL)
Hot gas reheat bleed (OPTIONAL)
Third liquid line solenoid (OPTIONAL)
Reversing valve (heat pump) (OPTIONAL)
Liquid injection #2 (OPTIONAL)
Mod motor (OPTIONAL)
Hot gas reheat off (OPTIONAL) If hot gas reheat all 3 hot gas relays are required.
Hot gas reheat on (OPTIONAL)
Hot gas reheat bleed (OPTIONAL)
Third liquid line solenoid (OPTIONAL)
Reversing valve (heat pump) (OPTIONAL)
Liquid injection #2 (OPTIONAL)
Mod motor (OPTIONAL)
148
MCS-MAGNUM-V. 14 REVISION 3.2
# (Number) - From 1 to 230 (maximum number of Setpoints supported). Only active Setpoints will be displayed in
MCS-Connect and on the keypad display.
Name - The Setpoint’s name consists of up to 12 characters. The name is displayed following the number on the
LCD display. The Setpoint name can be changed to make it more meaningful to the current application, however the
function of the Setpoint will remain the same.
Value - The value or target of the Setpoint. With proper authorization this value can be changed, within limits that
have been established in MCS-Config.
Min - The minimum value that can be set. This field is not displayed and cannot be changed in MCS-Connect or in
the keypad display.
Max - The maximum value that can be set. This field is not displayed and cannot be changed in MCS-Connect or in
the keypad display.
Adjust Value - The interval that the value field can be changed by. This field is not displayed and cannot be
changed in MCS-Connect or in the keypad display.
‘Time (sec)’ – this field has two purposes: 1) In either a LOCKOUT or ALARM type; this is the length of time the
Setpoint must be true before it will trip. This time is always in seconds and it is displayed on the keypad display and
MCS-Connect if the Setpoint is either a LOCKOUT or ALARM type. This field can be changed in MCS-Connect and
through the keypad. 2) In a non-safety type Setpoint this field can be used as an extra timer. This will be specified in
the Setpoint definition if it is used.
Lockout Delay Hrs. – If a second safety occurs within this time, the unit or compressor will be locked out. This
field is not displayed and cannot be changed through MCS-Connect or in the keypad display.
Safety Down Time (min.) – After the first safety occurs the Magnum will wait this number of minutes before the
unit or associated compressor is allowed to run again.
Active or Non-Active – Only active Setpoints will be displayed in MCS-Connect or on the keypad display, but
only if the needed authorization level has been achieved.
Select Value: # decimals and print char – This indicates the number of decimal places and the unit character
that accompanies the value displayed. The number of decimal places is crucial when the Value, Minimum, and
Maximum data is entered in MCS-Config.
Level of Auth. To Display – This column indicates what authorization level a user must have in order to view
the Setpoint from MCS-Connect or the keypad display.
Comments – This column allows the user to add comments about the function of the Setpoint.
Sec. to ignore safety - If this value is not zero, at compressor startup this safety will be ignored for the time in this
field.
Window to extend Safety ‘Time (sec)’ – If this value is not zero, at compressor startup the normal Safety
Time will be increased by the value in Safety Time Extension field for the time specified in this field.
Safety Time Extension (Sec) – This is the value that will be added to the Safety Time during the Window to extend
Safety Time period.
150
MCS-MAGNUM-V. 14 REVISION 3.2
17.1.1 SETPOINT
This type of Setpoint contains a target or provides information for some action. The time element in this type can be
used for an additional counter if specified. This time is displayed and can be changed through MCS-Connect, MCS-
Config or from the keypad display.
17.1.2 LOCKOUT
This type of Setpoint contains a safety value and the time that the safety must be violated before the safety will trip.
Once a safety has tripped the Magnum will take the appropriate action, shutting down the entire package or an
individual compressor depending on the purpose of the safety. The Magnum will then wait the Safety Down Time
contained in that Setpoint before trying to return the normal. If successful, the system will continue to operate. If
a second trip occurs on the same Setpoint with in the Lock Out Delay Time that is contained in that Setpoint the
system will move to a LOCKOUT state. If the lockout delay time is set to zero the lockout will occur on the first trip.
This requires manual intervention to reset the system. With each safety trip, the Magnum will generate an alarm;
refer to section 6 Magnum Alarms and Safeties.
The Safety Down Time and the Lock Out Delay Time are unique for each Setpoint. They cannot be viewed or
adjusted in a live unit; only through MCS-Config.
17.1.3 ALARM
This type of Setpoint has two uses:
1) When it is used as a safety, it will be similar to the LOCKOUT Setpoint except it will never cause a lock out. The
system will continue to try returning to normal operation after waiting the safety down time. An ALARM Setpoint type
will never require manual intervention to reset the system.
2) When the Setpoint is being used as a second timer it will be available to change in a live unit. If the type is not
changed to ALARM then the time field cannot be viewed or changed from a live unit.
151
MCS-MAGNUM-V. 14 REVISION 3.2
# Name Description
1 CTL TARGET Control target. This value is used as the base to develop the Control Zone. Refer
to Setpoints #2 and #3.
The control target is used with the control zone and rate of change of the control-
ling sensor to determine required action for the Magnum. The controlling sensor is
usually one of the following:
Leaving Temperature – Most common used as a target, fitting for most applica-
tions.
Return Temperature – Used in sites with large air masses, ice rinks, common
areas, etc.
Suction Pressure – Used in continuously running process systems.
2 CTL ZONE + Added to the CTL TARGET to create the upper limit of the control zone.
2 STAGE CUT OUT Offset used in calculating the cut out value. Subtracted from the stage cut in Set-
(Cut In/Out Con- points #3 through #18
trol)
3 CTL ZONE - Subtracted from the CTL TARGET to create the lower limit of the control zone.
(Only CENT) If this Setpoint is a target type and the Low Zone cell is >0 and <=5, use this value
as the offset to the target to allow an unload adjustment of 3 else use 1.
STAGE 1 CUT IN Stage 1 cut in, Setpoint value contains the voltage when this stage is turned on.
(Cut In/Out Con-
trol)
4 HGS TEMP ON This Setpoint is used with screw compressors with a hot gas bypass solenoid.
When this Setpoint is active and the control temperature is less than the CTL TAR-
GET plus the value in this Setpoint and the FLA % is within 25% of Setpoint #31
“MIN SLIDE%”, the hot gas bypass solenoid for the compressor will be turned on.
‘Time (sec)’ field: Contains the minimum slide percentage offset to enable the
HGB. If non-zero, this value is added to Setpoint #31 “MIN FLA%” to determine
the range in which to enable the HGB. If zero, then the default value of 25 is
added. For example, if this value is 10, then the HGB will enable when the com-
pressors FLA% is within 10% of Setpoint #31 “MIN FLA%”.
STAGE 2 CUT IN Stage 2 cut in, Setpoint value contains the voltage when this stage is turned on.
(Cut In/Out Con-
trol)
152
MCS-MAGNUM-V. 14 REVISION 3.2
# Name Description
5 HGS TEMP OFF This Setpoint is used with screw compressors with a hot gas bypass solenoid.
When this Setpoint is active and the control temperature is greater than the CTL
TARGET plus the value in this Setpoint or the FLA % is not within 25% of Setpoint
#31 “MIN SLIDE%”, the hot gas bypass solenoid for the compressor will be turned
off.
‘Time (sec)’ field: Contains the minimum slide percentage offset to disable the
HGB. If non-zero, this value is added to Setpoint #31 “MIN FLA%” to determine
the value at which to disable the HGB. If zero, then the default value of 30 is
added. For example, if this value is 15, then the HGB will disable when the com-
pressors FLA% is 15% or more above Setpoint #31 “MIN FLA%”.
STAGE 3 CUT IN Stage 3 cut in, Setpoint value contains the voltage when this stage is turned on.
(Cut In/Out Con-
trol)
6 HGS PSI ON This Setpoint is used with screw compressors with a hot gas bypass solenoid.
When this Setpoint is active and the suction pressure is less than the value of this
Setpoint and the FLA % is within 25% of the Setpoint #31 “MIN SLIDE%”, the hot
gas bypass solenoid for the compressor will be turned on.
STAGE 4 CUT IN Stage 4 cut in, Setpoint value contains the voltage when this stage is turned on.
(Cut In/Out Con-
trol)
7 HGS PSI OFF This Setpoint is used with screw compressors with a hot gas bypass solenoid.
When this Setpoint is active and the suction pressure is greater than the value of
this Setpoint or the FLA % is not within 25% of the Setpoint #31 “MIN SLIDE%”,
the hot gas bypass solenoid for the compressor will be turned off.
STAGE 5 CUT IN Stage 5 cut in, Setpoint value contains the voltage when this stage is turned on.
(Cut In/Out Con-
trol)
8 L.INJECT.ON This Setpoint can be used for both liquid injection solenoids.
Value: Liquid injection is turned on when the discharge temperature is greater
than or equal to this Setpoint, and is turned off when the discharge temperature is
less than this Setpoint minus 10.0°F (5.5°C). If the controlling SUPER HEAT is 3x
its target, LIQ INJ is turned ON and remains ON until the controlling SUPER HEAT
falls below 2x its target. u(If you change the Setpoint to a target type, the High
Zone cell if not zero will be the ON multiplier and the Low Zone sell if no zero will
be the OFF multiplier.)
‘Time (sec)’ field: If the first liquid injection solenoid has been on for a time greater
than this value, then turn on the second liquid injection solenoid.
STAGE 6 CUT IN Stage 6 cut in, Setpoint value contains the voltage when this stage is turned on.
(Cut In/Out Con-
trol)
153
MCS-MAGNUM-V. 14 REVISION 3.2
# Name Description
9 SPRHT TARGET If EXV control is based upon superheat, this is the Superheat target that the Mag-
or num will control from.
LEVEL TARGET If EXV control is based upon refrigerant level, this is the refrigerant level target
that the Magnum will control from.
‘Time (sec)’ field: Seconds between samples used for calculating the Superheat
Rate of Change.
STAGE 7 CUT IN Stage 7 cut in, Setpoint value contains the voltage when this stage is turned on.
(Cut In/Out Con-
trol)
10 SPRHT ZONE +- The value in this Setpoint is added and subtracted to Setpoint #9 to determine the
upper and lower limits of the control zone respectively.
‘Time (sec)’ field: If non-zero, skip ROC adjustment logic in the control zone.
STAGE 8 CUT IN Stage 8 cut in, Setpoint value contains the voltage when this stage is turned on.
(Cut In/Out Con-
trol)
11 EXV LOAD ADJ The opening adjustment that will be made to the EXV percentage when the circuit
changes to the Loading state, or the closing adjustment that will be made when
the circuit changes to the Unloading state.
Note: In MOP hold state, only closing adjustments are allowed.
STAGE 9 CUT IN STAGE 9 cut in, Setpoint value contains the voltage when this stage is turned on.
(Cut In/Out Con-
trol)
12 EXV FINE ADJ The adjustment is made when in the 1st zone above or below the control zone.
STAGE 10 CUT IN Stage 10 cut in, Setpoint value contains the voltage when this stage is turned on.
(Cut In/Out Con-
trol)
13 EXV COURSE This adjustment is made when in the 2nd zone above or below the control zone
and the adjustments are made in 1/2 the time. When above or below the 2nd con-
trol zone the adjustments are made in 1/4 the time.
STAGE 11 CUT IN Stage 11 cut in, set point value contains the voltage when this stage is turned on.
(Cut In/Out Con-
trol)
14 EXV LOAD DIV As the Amp draw % changes this divides the EXV % change. It is calculated as
follows:
[(Max slide% – min slide%) / (Max vlv% - min vlv%)] +1
STAGE 12 CUT IN Stage 12 cut in, Setpoint value contains the voltage when this stage is turned on.
(Cut In/Out Con-
trol)
15 EXV MIN % This is the minimum valve position allowed when modulating the expansion valve.
This value should be set so when hot gas is applied the valve opening is ad-
equate.
STAGE 13 CUT IN Stage 13 cut in, Setpoint value contains the voltage when this stage is turned on.
(Cut In/Out Con-
trol)
154
MCS-MAGNUM-V. 14 REVISION 3.2
# Name Description
16 EXV MAX % This is the maximum position allowed when modulating the expansion valve to
maintain the superheat target. This value should be the valve % opening at full
capacity plus a 10 to 15 % margin.
STAGE 14 CUT IN Stage 14 cut in, Setpoint value contains the voltage when this stage is turned on.
(Cut In/Out Con-
trol)
17 LO SUPERHEAT If the calculated superheat remains below this value for the time specified, the
Magnum will generate a LOW SUPERHEAT alarm.
STAGE 15 CUT IN Stage 15 cut in, Setpoint value contains the voltage when this stage is turned on.
(Cut In/Out Con-
trol)
18 LOWSUCPSI DLY Delay in seconds when in ‘Low Suction PSI Opening’ between adjustments to the
EXV valve.
STAGE 16 CUT IN Stage 16 cut in, Setpoint value contains the voltage when this stage is turned on.
(Cut In/Out Con-
trol)
19 EXV DELAY Delay in seconds between valve adjustments. Should not be less than 48. (When
adjusting at 4x this will allow 12 seconds for the controller to process the results of
the last action before making the next adjustment)
20 EXV STRT TIME This is the time in seconds to hold the valve at the start % Setpoint when the com-
pressor starts. Since the superheat calculation is not valid when the compressor
is not running the EXV logic sets the valve to a given position for a set time to
allow the system to develop a valid superheat.
‘Time (sec)’ field: If zero, then there is no delay when a compressor is ready to
start. If non-zero, this is the time delay in which the EXV valve is allowed to open
before the compressor starts.
21 MAX TRG RESET This value is used to adjust Setpoint #1 “CTL TARGET”. The Sensor Input value
will vary between 0 and 5 volts and the adjustment to the control target will be
modulated from negative “MAX TRG RESET” to the positive “MAX TRG RESET”
value.
22 LOW AMBIENT If the ambient temperature is below this value the system will be disabled and the
unit state will be AMBIENT OFF. The unit will remain off until the ambient tempera-
ture rises above this Setpoint value by 5.0F (2.5C).
23 POWERUP DELAY The time in seconds that the system will remain in the START UP state before
moving to the next state.
24 HI AMBIENT If the ambient temperature is above this value the system will be disabled and the
unit state will be AMBIENT OFF. The unit will remain off until the ambient tempera-
ture drops below this Setpoint value by 5.0F (2.5C).
25 STEP SENSTIY This value is used to adjust the rate of response to changes in the control algo-
rithm. 1 is the fastest response, whereas higher numbers will mean a more gradu-
al response. Used only with the Magnum Control Zone control method.
26 STEP DELAY Value: This is the time delay before making adjustments to the system capacity.
Used only with the Magnum Control Zone control method.
‘Time (sec)’ field: If used, this will force a minimum time delay between any two
compressor starts. This time delay is specified in the ‘Minimum Delay Between
Compressor Starts’ box in the ‘Compressor Information’ panel under the MAG V8
screen.
155
MCS-MAGNUM-V. 14 REVISION 3.2
# Name Description
27 MAX ROC - Maximum negative Rate of Change allowed before preventing the unit from load-
ing. If the ROC is less than this value the capacity control state is set to HOLD-
ING. Used only with the Magnum Control Zone control method.
28 MAX ROC + Maximum positive Rate of Change allowed before preventing the unit from un-
loading. If the ROC is greater than this value the capacity control state is set to
HOLDING. Used only with the Magnum Control Zone control method.
29 ROC INTERV Seconds between samples used for calculating the Rate of Change. Used only
with the Magnum Control Zone control method. (Maximum 60 seconds)
30 MAX FLA% Indicates the maximum amp draw, slide %, digital scroll load%, or speed allowed.
or Usually set to 100%, else compressors will load to the value of this Setpoint until
MAX SLIDE % all steps are on, then the system will load to 100%.
or ‘Time (sec)’ field: If non-zero, then force individual compressors to stay at maxi-
MAX CAPACITY% mum capacity when another compressor starts. This option is selected in in the
or ‘Keep Running Comp at 100% when starting next?’ box in the ‘Compressor Infor-
MAX VFD % mation’ panel under the MAG V8 screen.
‘SEC to Ignore Safety’ field (Fully Loaded Screw Compressor logic): If non-zero,
turn on the load solenoid every 5 min for 5 seconds when fully loaded. If zero,
then do not turn on solenoid for 5 seconds every 5 minutes.
‘SEC to Ignore Safety’ field (Holding Screw Compressor logic): If non-zero, turn on
the load solenoid every 5 min for 5 seconds when holding. If zero, then do not turn
on solenoid for 5 seconds every 5 minutes.
31 MIN FLA% Value: Indicates the minimum amp draw, slide %, digital scroll load%, or speed
or allowed (usually 40%). This is where the slide valve or VFD will be set when the
MIN SLIDE % compressor is turned on. This % is a function of actual amp draw relative to the
or FLA.
MIN CAPACITY% ‘Time (sec)’ field: If used, this forces a time delay before unloading all running
or compressors before the next compressor is started. This time delay is specified in
MIN VFD % the ‘Unload Compressor Before Starting Next’ box in the ‘Compressor Informa-
tion’ panel under the MAG V8 screen. Will Delay next compressor for this time
after EVAP pump/valve is opened.
32 MAX ADJUST % Indicates the maximum percentage change that can be made to the slide valve or
VFD.
‘Time (sec)’ field: A zero indicates that the calculated FLA will be used, else the
value in Setpoint #31 will be used when starting the next compressor. This value
is specified in the ‘Wanted FLA starting next Compressor’ box in the ‘Compressor
Information’ panel under the MAG V8 screen.
33 MIN ADJUST % Indicates the minimum percentage change that can be made to the slide valve or
the VFD.
For Fixed Step Compressors with adjustable speed AO’s when returning to 100%
after shutting down another compressor, this Setpoint will be the percent of adjust-
ment along with Setpoint #56 “PULSE DELAY” which is the time frame between
capacity adjustments.
34 SLIDE SENSITY This controls the sensitivity of the adjustment made to the Wanted Percentage
(adjustments are relative to the difference between the current control sensor and
target). The larger the value the larger the adjustment (usually 1).
156
MCS-MAGNUM-V. 14 REVISION 3.2
# Name Description
35 AMP DB HI Used only with screw and centrifugal compressors. This value is the upper dead
band limit of the FLA. If the amps are within the dead band, the slide valve will not
be moved.
If controlled by Slide Position, instead of FLA, this Setpoint will not be used.
36 AMP DB LO Used only with screw and centrifugal compressors. This value is the lower dead
band limit of the FLA. If the amps are within the dead band, the slide valve will not
be moved.
If controlled by Slide Position, instead of FLA, this Setpoint will not be used.
37 LOAD PULSE Length of time to engage the slide valve load solenoid in tenths of a second (usu-
ally between 1 and 9).
‘Time (sec)’ field: If non-zero, use this value as a multiplier to increase the load
pulse when the compressor’s amp draw is more than three times the value of
Setpoint #36 “AMP DB LO”.
‘SEC to Ignore Safety’ field: If zero, then use delay between pulses. If non-zero,
then no delay between pulses when the compressor’s amp draw is more than
twice the value of Setpoint #36 “AMP DB LO” away from the wanted FLA.
38 UNLOAD PULSE Length of time to engage the slide valve unload solenoid in tenths of a second
(usually between 1 and 9).
Optional: If compressor type is Hanbell 3 solenoid and Time (SEC) cell of Setpoint
#38, is not zero DO NOT turn the unload solenoid ON (which is normal) when the
compressor is in a fast unload state, pumpdown unloading state or for the first 15
minutes after the compressor is turned off.
39 LUBE OIL TMP The oil must reach this temperature before the system will move out of the LUBE
state. If the oil temperature is below this value before the compressor begins its
startup sequence, the circuit will be placed in the OFF-LO OIL TMP state.
‘Time (sec)’ field: If in LUBE state, the compressor type is centrifugal, and this
field is equal to 0 then the calculated oil temperature shut down is the saturated
suction temperature plus the value of this Setpoint, else it is simply the value of
this Setpoint. This option is selected in in the ‘Lube State Oil Setpoint’ box in the
‘Compressor Information’ panel under the MAG V8 screen.
40 LUBE OIL PSI The oil must reach this pressure differential between low and high oil pressure
before the circuit will move out of the LUBE state.
41 LUBE DELAY This is the maximum time that a compressor can be in the LUBE state. When this
time is exceeded, an alarm is generated and the compressor is locked out. Both
the oil temperature and pressure must be satisfied before the LUBE state will be
exited. Refer to the OIL PMP LUBING state.
42 HI WATER TMP If active, the control sensor’s value will be compared to the value of this Setpoint.
If it exceeds this temperature for the time specified in the ‘‘Time (sec)’ field’ a
HI WATER TMP alarm will be generated. No lockouts will occur. This alarm will
repeat if the control value drops .5° below this Setpoint and then rises above it
again.
43 CENT P-DWN FLA Only used for centrifugal compressors. If active, this will be the threshold for
ending the pump down state (can either be number of amps or vane percentage,
depending on the compressor control method). If the Setpoint is inactive then the
FLA Setpoint for that compressor will be used.
44 CENT P-DWN Only used for centrifugal compressors. This is the maximum time allowed in the
TMR pump down state. NOTE: This value is used whether the Setpoint is active or inac-
tive.
157
MCS-MAGNUM-V. 14 REVISION 3.2
# Name Description
45 CND STG1 ON When the discharge pressure is above this value, turn on the first stage of the
(RO Type) condenser fans.
‘Time (sec)’ field: (Applies to compressors with shared condensers) If non-zero,
then the compressor in startup state will not be in sole control of the condenser
fans, it will control off of highest discharge pressure. If zero, then compressor in
startup will have sole condenser control for 5 minutes. This option is selected in
in the ‘Newly started Comp Controls Common Fan Bank’ box in the ‘Condenser
Information’ panel under the MAG V8 screen.
46 CND STG1 OFF If stage 1 of condenser capacity is on and the discharge pressure drops below this
(RO Type) value, then turn this stage off.
47 CND DIFF ON Differential pressure added to Setpoint #45 to set the threshold at which each ad-
(RO Type) ditional stage of condenser capacity will turn on.
48 CND DIFF OFF Differential pressure added to Setpoint #46 to set the threshold at which each ad-
(RO Type) ditional stage of condenser capacity will turn off.
CND ADJ DELAY If active this is the time in seconds between condenser adjustments to the AO. If
(Modulating Type) inactive, then 30 seconds will be used as the delay.
If type is DELAY: (required for condenser relay delays).
-MIN VFD Opening cell contains the time delay between turning on a relay
and moving the AO to its minimum position (Setpoint #52).
-MAX VFD Opening cell contains the time delay between turning off a relay
and moving the AO to 100%.
DUAL PSI DELTA Minimum difference in pressure before the second stage of condenser capacity
(Dual V8) can be started.
49 CND MIN RUN Once a condenser stage has been turned on, it will remain on for at least the
(RO Type) amount of minutes specified in this Setpoint.
DUAL TIME DE- Time delay once the pressure difference in Setpoint #48 has been reached before
LAY the second condenser stage can be started.
(Dual V8)
CND START % If active, then the value is the starting % for the AO when the RO that is tied to it
(Modulating Type) turns on. The value in the “Time (SEC)” cell is the AO starting stage. If no Relays
are used when CMP starts set value.
50 CND TRGT Target the logic will try to maintain by modulating the AO.
(Modulating Type)
LO AMB SUMP If active and ambient temperature is less than the value of this Setpoint, then the
OFF sump pump relay will be locked off if it is the starting condenser Relay Output.
(RO Type) When the ambient temperature rises above the value of this Setpoint plus two
times the value in Setpoint #192 “FRZ TEMP DIFF” if active (hardcoded 15°F if
inactive), then the sump pump relay will be allowed on again.
51 CND ADJ DIV Controls scaling of the amount the AO is adjusted (usually 1). The larger the num-
(Modulating Type) ber the smaller the AO adjustment as the adjustment will be divided by this value.
CND VFD MIN If there is a VFD associated with the condenser, this is the starting minimum
speed.
‘Time (sec)’ field: This field contains the condenser stage that must be on before
the VFD is modulated.
158
MCS-MAGNUM-V. 14 REVISION 3.2
# Name Description
52 CND MIN % Minimum AO % allowed.
(Modulating Type) If compressor is off, then check the “Time (SEC)” field:
If 0, then the AO % will be set to the value of this Setpoint. If 2 and the run/stop is
set to run, then set the AO % to 100%, else set the AO % to 0%. This option is se-
lected in the “Default Valve Opening % when Comp. is OFF” box in the condenser
information section in the MAG HVAC screen.
53 CND ROC Maximum negative rate of change allowed. If the rate of change is less than this
(Modulating Type) Setpoint, then stop modulating the AO. The absolute value of this Setpoint also
serves as the maximum positive rate of change allowed. If the rate of change is
greater than the absolute value of this Setpoint, then stop modulating the AO.
54 CND MIN SPD Minimum speed percentage for variable speed condenser control.
(RO Type)
CND ADJ MULT Controls scaling of the amount the AO is adjusted. The larger the number the
(Modulating Type) larger the AO adjustment as the adjustment will be multiplied by this value.
55 CND MAX SPD Maximum speed percentage for variable speed condenser control.
(RO Type)
CND MIN ADJ The value in this Setpoint is the minimum % the AO will be modulated when a
(Modulating Type) change is made.
56 PULSE DELAY Used with variable capacity screws. The number of seconds between load or un-
load pulses (Usually between 3 and 5. Allows load change to be checked before
next pulse and eliminates oil foaming when unloading too fast).
‘Time (sec)’ field: If used, this is the fast unloading state time delay. This option is
selected in in the ‘Fast Unload Delay’ box in the ‘Compressor Information’ panel
under the MAG V8 screen.
For Fixed Step Compressors with adjustable speed AO’s when returning to 100%
after shutting down another compressor, this Setpoint will be the time frame be-
tween capacity adjustments along with Setpoint #33 “MIN ADJUST %” which is
the percent of adjustment.
57 LO AMB PROC When this Setpoint is active and there is a process pump, the process pump will
be turned on when the ambient temperature is less than the value of this Setpoint.
The process pump will be turned off again when the ambient temperature is 5.0°
Fahrenheit greater than the value of this Setpoint.
58 CFG TESTING This must be setup as ‘Not Used’. If active the system will not lockout when an
I/O communications signal is lost. This Setpoint should NOT be active in a live
unit.
59 ACYC OFF->ON This is the anti-cycle time delay (in seconds) from when the compressor was
turned off. This value is used in a calculation to determine how long a compressor
should be in the anti-cycle state. Refer to the Standard Control Options section
5.11, Compressor Anti-Cycle Logic (OFF to ON).
60 MITSI P-DWN If the compressor is a Mitsubishi, is being unloaded, and the suction pressure
CUTIN is greater than this Setpoint, then the compressor will be forced to pump down.
NOTE: this value is used whether the Setpoint is active or inactive.
61 PMP DWN OFF This is the suction pressure value for turning off the compressor when in the
PUMP DOWN or for opening the liquid line solenoid during the PRE-PUMP down
state.
159
MCS-MAGNUM-V. 14 REVISION 3.2
# Name Description
62 PMP DWN DELY Maximum time delay (in seconds) that a compressor can remain in the PUMP
DOWN or PRE-PUMP down states. The Time in sec field specifies the time the
unit will remain in unloading before shutting off the LLS & EXV and pumping
down.
63 ACYC ON->ON This is the anti-cycle time delay (in seconds) from when the compressor was
turned on. This value is used in a calculation to determine how long a compressor
should be in the anti-cycle state. Refer to the Standard Control Options section
5.11, Compressor Anti-Cycle Logic (ON to ON).
64 COMP MIN RUN This is the minimum run time (in minutes) for a compressor once it is turned on.
This minimum run time can be overridden by a safety condition, however.
65 EXV ZONE1 Temperature differential used to build the EXV Zone 1 both plus and minus.
66 EXV ZONE2 Temperature differential that is used to build the EXV Zone 2 both plus and minus.
Temperatures above this zone are considered in zone 3.
67 EXV ROC ZONE 1 The EXV control logic will compare the value of this Setpoint to the temperature
rate of change to determine the valve adjustment when the temperature is within
the EXV control zone.
‘Safety Down Time (MIN)’ field: The minimum time delay between EXV adjust-
ments when in the EXV control zone.
68 EXV ROC ZONE1 The EXV control logic will compare the value of this Setpoint to the temperature
rate of change to determine the valve adjustment when the temperature is within
zone 1.
‘Safety Down Time (MIN)’ field: This is the minimum time delay between EXV
adjustments when in the EXV control zone 1. If this Setpoint is inactive then the
ROC for this zone is 0 and the delay is 15 seconds.
69 EXV ROC ZONE2 The EXV control logic will compare the value of this Setpoint to the temperature
rate of change to determine the valve adjustment when the temperature is within
zone 2.
‘Safety Down Time (MIN)’ field: This is the minimum time delay between EXV
adjustments when in the EXV control zone 2. If this Setpoint is inactive then the
ROC for this zone is 0 and the delay is 15 seconds.
70 EXV ROC ZONE3 The EXV control logic will compare the value of this Setpoint to the temperature
rate of change to determine the valve adjustment when the temperature is within
zone 3.
‘Safety Down Time (MIN)’ field: This is the minimum time delay between EXV
adjustments when in the EXV control zone 3. If this Setpoint is inactive then the
ROC for this zone is 0 and the delay is 15 seconds.
71 EXV TOO FAST When the superheat is with the control zone, the EXV control logic will compare
the value of this Setpoint to the temperature rate of change to determine the valve
adjustment when the temperature is within the zone and rising too fast.
‘Safety Down Time (MIN)’ field: This is the minimum time delay between EXV ad-
justments if the rate of change is too fast when in EXV control zones 1 or 2. If this
Setpoint is inactive then the ROC for this zone is 0 and the delay is 15 seconds.
72 EXV CHANGING When the superheat is with the control zone, the EXV control logic will compare
the value of this Setpoint to the temperature rate of change to determine the valve
adjustment when the temperature is within the zone and rising.
160
MCS-MAGNUM-V. 14 REVISION 3.2
# Name Description
73 STARTER DLAY This Setpoint controls the start of a compressor’s second relay.
If the ‘Select Value: # decimals & print char’ cell is set to ‘HUMD or %’ then logic
is:
If the slide amp percentage is less than the value of this Setpoint and the first re-
lay has been on for 2 seconds or it has been on longer than the value in the safety
time of this Setpoint, then turn on the second relay. Else it is off.
If the ‘Select Value: # decimals & print char’ cell is set to ‘Seconds’ then the Set-
point’s value is a time delay between the first and second relay’s starts. Used for
part wind (typical value of 1) and star delta (typical value of 5) starter.
74 OIL PUMP OFF If oil pump is always on (specified in MCS-Config), this Setpoint is not used.
Otherwise this Setpoint contains the oil pressure value when the oil pump is to be
turned off.
75 HI AMPS This Setpoint is a percentage of the FLA; it is used to create the high amp draw
limit. The value of this Setpoint is multiplied by the respective compressor’s full
load amps Setpoint (#171 through #190) to obtain its upper limit. If the compres-
sor’s amps exceed this value for the time specified in this Setpoint, then a safety
trip occurs.
76 LO AMPS This Setpoint is a percentage of the FLA; it is used to create the low amp draw
limit. The value of this Setpoint is multiplied by the respective compressor’s full
load amps Setpoint (#171 through #190) to obtain its lower limit. If the compres-
sor’s amps fall below this value for the time specified in this Setpoint, then a safety
trip occurs.
77 LOW SUCTION If active, the Magnum checks for low suction pressure for each running compres-
sor. If suction pressure is less than this value for the specified period of time, a
safety trip occurs.
Refers to ‘Suction Pressure’ column in the Circuit SI screen.
78 LO SUCT UNLD The purpose of this Setpoint is to take corrective action to prevent a low suc-
tion pressure safety trip. For fixed step compressors: If a compressor has more
than one step, is fully loaded, and if the suction pressure is less than the value of
Setpoint #77 “LOW SUCTION” plus the value of this Setpoint, then one step of
capacity will be turned off. For variable step compressors: If a compressor has a
suction pressure less than the value of Setpoint #77 “LOW SUCTION” plus the
value of this Setpoint, then the compressor will be forced to unload. The circuit
state will be changed to LO SUCT HOLD, and will remain in this state for a mini-
mum of the time in Setpoint #101 “SAFETY HOLD DELAY”. At that time, if the
suction pressure has increased greater than the value of Setpoint #77 “LOW
SUCTION” plus the value of Setpoint #79 “LOW SUCT RELD” the compressor will
return to normal control.
79 LOW SUCT RELD Refer to Setpoint #78 description.
80 UNSAFE SUCT If active, the Magnum checks for unsafely low suction pressure for each running
compressor. If suction pressure is less than this value for the specified period of
time a lockout occurs (can configured as a regular safety with automatic reset if
‘Setpoint Type’ is Setpoint instead of Lockout). NOTE: The time period specified
should be very short (2-5 seconds). If this Setpoint trips, the compressor will be
sent straight to the Lockout state.
Refers to ‘Suction Pressure’ column in the Circuit SI screen.
161
MCS-MAGNUM-V. 14 REVISION 3.2
# Name Description
81 HI DISC PSI If active, the Magnum checks for high discharge pressure for each running com-
pressor. If the discharge pressure sensor reads greater than this Setpoint for the
specified period of time, a safety trip will occur.
Refers to ‘Discharge Pressure’ column in the Circuit SI screen.
82 HI DISC UNLD The purpose of this Setpoint is to take corrective action to prevent a high dis-
charge pressure safety trip. For fixed step compressors: If a compressor has more
than one step, is fully loaded, and if the discharge pressure is more than the value
of Setpoint #81 “HI DISC PSI” minus the value of this Setpoint, then one step of
capacity will be turned off. For variable step compressors: If a compressor has a
discharge pressure more than the value of Setpoint #81 “HI DISC PSI” minus the
value of this Setpoint, then the compressor will be forced to unload. The circuit
state will be changed to HI DISC HOLD, and will remain in this state for a mini-
mum of the time in Setpoint #101 “SAFETY HOLD DELAY”. At that time, if the
discharge pressure has decreased below than the value of Setpoint #81 “HI DISC
PSI” minus the value of Setpoint #83 “HI DISC RELD” the compressor will return
to normal control.
83 HI DISC RELD Refer to Setpoint #82 description.
84 LO DISC SHEAT If the calculated discharge superheat is less than this value for the specified
period of time, a safety trip will occur. Also, there is an option in the Circuit Base
screen to tie a Relay Output to this Setpoint that will activate whenever a low
discharge superheat condition occurs. A Low Discharge Superheat condition can
also put the circuit into a ‘HI DISC UNLOAD’ state where the compressor will un-
load to try to raise the superheat.
If economizer is being used, when the discharge superheat goes below the value
for the safety time / 9 the economizer is turned off.
85 LO DISC PSI If active, the Magnum checks for low discharge pressure. If the discharge sensor
reading is less than this value for the specified period of time, a safety trip occurs.
86 HI RETURN TEMP Only active in Mitsubishi compressors. If active the Magnum will check for high
entering liquid temperature. If this temperature is greater than the value in this
Setpoint, the circuit state will be HI WATER HOLD.
87 HI DISC TMP If active, the Magnum checks for high discharge temperature for each compres-
sor. If the discharge temperature sensor reading is greater than this Setpoint for
the specified period of time, a safety trip will occur.
Refers to ‘Discharge Temperature’ column in the Circuit SI screen.
88 DIS TMP UNLD The purpose of this Setpoint is to take corrective action to prevent a high dis-
(Not CENT?) charge temperature safety trip. For fixed step compressors: If a compressor has
more than one step, is fully loaded, and if the discharge temperature is more
than the value of Setpoint #87 “HI DISC TMP” minus the value of this Setpoint,
then one step of capacity will be turned off. For variable step compressors: If a
compressor has a discharge temperature more than the value of Setpoint #87 “HI
DISC TMP” minus the value of this Setpoint, then the compressor will be forced to
unload. The circuit state will be changed to HI DISC HOLD, and will remain in this
state for a minimum of the time in Setpoint #101 “SAFETY HOLD DELAY”. At that
time, if the discharge temperature has decreased below than the value of Setpoint
#87 “HI DISC TMP” minus the value of Setpoint #89 “HDISC T RELD” the com-
pressor will return to normal control.
89 DIS TMP RELD Refer to Setpoint #88 description.
162
MCS-MAGNUM-V. 14 REVISION 3.2
# Name Description
90 COND FAULT For Condensers with Fault Indicators: If Setpoint is active, a condenser fault oc-
curs, and the Setpoint type is Alarm, then an alarm message will be generated.
If the type is Lockout, and a condenser fault occurs, then all of the compressors
associated with this fault will be locked off.
For Common VFD Fan Condensers with Bypass: Time in seconds before the by-
pass can be used when a fault has occurred.
91 LOW OIL DIF If active, the Magnum checks for low differential oil pressure. If the calculated
differential oil pressure is less than this value for the specified period of time, a
safety trip occurs.
Refers to ‘Oil Pressure’ column in the Circuit SI screen.
92 UNSAFE OIL If active, the Magnum checks for unsafe differential oil pressure. If the calculated
differential oil pressure is less than this value for the specified period of time, a
lockout occurs. NOTE: The time period specified should be very short (2-5 sec-
onds). If this Setpoint trips, the compressor will be sent straight to the Lockout
state.
Refers to ‘Oil Pressure’ column in the Circuit SI screen.
93 HI OIL SEAL Only used with screw or centrifugal compressors. If the oil seal or oil cooler tem-
perature exceeds the value of this Setpoint for the time specified, a safety trip
occurs.
Refers to ‘Oil Seal Temp’ column in Circuit SI screen.
94 HI OIL TEMP If active, the Magnum checks for high oil temperature. The sensor can be either
an analog or digital input. If the oil temperature sensor reading is ON (Digital) or
exceeding the temperature value of this Setpoint (Analog) for the specified period
of time, a safety trip occurs.
Refers to ‘Oil Temp’ column in the Circuit SI screen.
95 MOTOR FAULT If active, the Magnum checks for high motor temperature. The sensor can be
either an analog or digital input. If the motor temperature sensor reading is ON
(Digital) or exceeding the temperature value of this Setpoint (Analog) for the
specified period of time, a safety trip occurs.
Refers to ‘Motor Temp’ column in the Circuit SI screen.
96 NO CMP PROOF If active, when the compressor is called to be on by the controller, the Magnum
will check for a digital input to indicate that the compressor is indeed running. If
the controller calls for a compressor to turn on and no proof is given in the speci-
fied period of time, a safety trip occurs.
Refers to ‘Comp Proof’ column in the Circuit Base screen
97 DIRTY FILTER Only used for screw compressors. If discharge pressure minus oil filter pressure is
greater than this value for the time specified, a safety trip occurs.
98 LLS#2 ON This Setpoint is used to control a second liquid line solenoid. When the actual
circuit capacity is greater than this value (can either be number of steps for Fixed
Step compressors, or percentage of full load amps for Variable Step compressors)
for the number of seconds in the ‘Time (sec)’ field, the second liquid line solenoid
will open. When the actual circuit capacity falls below this value minus the ‘Lock-
out Delay Hrs.’ Field, then the second liquid line will be turned off.
‘Time (sec)’ field: The delay in seconds before the solenoid will be turned on. If
zero, then there will be no delay.
‘Lockout Delay Hrs.’ Field: Offset that will be subtracted from the value of this Set-
point. When the actual circuit capacity falls below this offset, the solenoid will be
turned off. If zero, then an offset of 20% will be used.
163
MCS-MAGNUM-V. 14 REVISION 3.2
# Name Description
99 LLS#3 ON This Setpoint is used to control a third liquid line solenoid. When the actual circuit
(ECONOMIZER) capacity is greater than this value (can either be number of steps for Fixed Step
compressors, or percentage of full load amps for Variable Step compressors) for
the number of seconds in the ‘Time (sec)’ field, the third liquid line solenoid will
open. When the actual circuit capacity falls below this value minus the ‘Lockout
Delay Hrs.’ Field, then the third liquid line will be turned off.
‘Time (sec)’ field: The delay in seconds before the solenoid will be turned on. If
zero, then there will be no delay.
‘Lockout Delay Hrs.’ Field: Offset that will be subtracted from the value of this Set-
point. When the actual circuit capacity falls below this offset, the solenoid will be
turned off. If zero, then an offset of 20% will be used.
If the LO DISC SHEAT Setpoint #84 is active and the discharge superheat goes
below the value in this Setpoint for the safety time / 9, the economizer will be
turned off.
100 HIGH SUMP If active, and sump temperature is above the value of this Setpoint for the time
TEMP specified, a HIGH SUMP TEMP alarm is generated and the unit is locked out.
101 SAFETY HOLD Time in seconds that the circuit will remain in a hold state after the condition that
DELAY caused it has returned to normal. The circuit can be holding for the following rea-
sons:
Low suction pressure
Low refrigerant temperature
High discharge pressure
High discharge temperature
High amperage
102 PUMP FREEZE If active, and the leaving temperature sensor is below the value of this Setpoint, a
PROTECTION pump will be forced on to protect against freezing. The leaving temperature must
rise above this Setpoint plus Setpoint #192 “FRZ TMP DIFF” to turn the pump off
again.
103 LEAD COMP Enables the user to specify the lead compressor. The value of this Setpoint will
indicate the lead compressor. If zero, then auto rotation is enabled.
‘Time (sec)’ field: If non-zero, the compressor with the least amount of run time will
be made the lead upon rotation.
104 COMP ROTATION Specifies the number of days between rotations (Setpoint #103 must be set to
zero to enable auto rotation). If zero, then rotation will occur with every cycle.
105 PUMP FAILURE If active, flow is lost, and only one pump is present, then the system will be locked
(NO FLOW) out. If the system has two pumps and flow is lost, then the backup pump will start
and the lead pump will be locked out. If the second pump is running and flow is
lost again then the entire system will be locked out. A lock out reset will be re-
quired to restart the system or to reactivate a locked out pump.
If inactive, and the flow is lost, the system will move to the OFF- NO EVAP FLOW
state. When flow is returned the system will automatically restart.
If looking at individual pumps for each circuit in the Circuit base. Make this Set-
point a “Lockout”. If flow is not made within the value of this Setpoint the first time
than, an alarm will be generated. The system counts through the value of this
Setpoint a second time, if flow is made then the unit will run as normal. If flow
is not made the second time, the pump and all associated compressors for that
circuit will be locked out.
164
MCS-MAGNUM-V. 14 REVISION 3.2
# Name Description
106 LEAD PUMP Indicates which pump is the lead. If zero, then rotation of the pumps will occur
whenever the lead pump is turned off. If no rotation has occurred during the cur-
rent day, a forced rotation will occur at midnight, ensuring at least one rotation per
day. If value is non-zero, then rotation of the pumps is inactive and the value will
specify the lead pump. This Setpoint can be changed in a live unit and the appro-
priate action will be taken immediately.
107 EcoDelayMech Seconds to delay after the economizer is fully loaded, valve opened to its maxi-
mum, and all associated fans are on before the mechanical cooling is enabled. If
inactive, then the value of Setpoint #125 “Eco StageDly” will be used for this delay.
‘Time (sec)’ field: This value is used as a multiplier in the calculation that deter-
mines when it is too cold to use economizer cooling. If the control temperature
drops below Setpoint #1”CTL TARGET” minus (‘Time (sec)’ field of this Setpoint
multiplied by the value of Setpoint #3 “CTL ZONE -“) then shut off all economizer
cooling. If the value in this ‘Time (sec)’ field is zero, a hardcoded 3 will be used
instead.
108 PUMP DELAY Time in seconds to keep the chilled water pump running after the last compressor
has been turned off to ensure the chiller barrel does not freeze.
109 HiRefLevel This Setpoint has two functions.
If active, the Magnum checks for high refrigeration level. If the refrigeration level
sensor is greater than this value for the specified period of time, a safety trip oc-
curs.
If active, system has EXV valve control based on refrigerant level, and the refrig-
erant level is greater than this value, then the EXV valve adjustment will be set to
the value in Setpoint #13 “EXV COURSE” * ( –3).
Refers to ‘Refrig Level’ column in the Circuit SI screen
110 RefLvlExvAdj If Setpoint #84 “LO DiscSPRHT” is active and it has reached one third of its safety
(EXV Control: Re- time, then Setpoint #9 “REF LVL TRG” will be set to the value of this Setpoint. The
frigerant Level) purpose is to decrease the EXV valve opening to avoid a low discharge superheat
safety trip. This change will be updated in the Setpoint status value.
DSprhtExvAdj If Setpoint #84 “LO DiscSPRHT” is active and it has reached one third of its safety
(EXV Control: Dis- time, then Setpoint #9 “SUPERHT TRGT” will be increased by the value of this
charge or Suction Setpoint. The purpose is to decrease the EXV valve opening to avoid a low dis-
Superheat) charge superheat safety trip.
111 FREEZE If active, the Magnum will compare the leaving temperature to this Setpoint. If it is
less than this value for the specified period of time, a safety trip occurs.
112 NO STOP This Setpoint is used to ensure that a compressor is actually off when the control-
ler calls for it to be off. This Setpoint contains a percentage of the FLA for Set-
points #65-#72. If the compressor amperage is greater than this percentage of the
FLA Setpoint for the specified period of time, signaling that the compressor is still
running, then the entire system is locked out and a NO STOP alarm is generated.
If a Control Power relay is specified, then it will be turned off when this safety trips.
113 OIL INJ TEMP This is a temperature differential subtracted from Setpoint #8 to control the oil
DIFF injection relay. When discharge temperature is above this differential, then oil
injection is turned on. If inactive then value will be 5.6° F (2.8° C).
114 OIL TEMP DIFF This is a temperature differential used in controlling the oil heater and second
liquid line solenoid. If inactive then value will be set to 5° F.
165
MCS-MAGNUM-V. 14 REVISION 3.2
# Name Description
115 EcoVFDfanDely If active, and the fluid cooler has a VFD condenser fan, this Setpoint will be the
time in seconds between adjustments to the VFD. If inactive, then the value of
Setpoint #124 “EcoVlvAdjDly “will be used for this delay timer.
116 Defrost On Temp Only used in Turbo Ice Machines. When control temperature falls below this value,
then a defrost cycle begins. When the temperature rises .5° F above this value
then the defrost cycle will be terminated.
117 Defrost On Delay Only used in Turbo Ice Machines. Time in seconds of pre-defrost delay.
118 Defrost On Cycle Only used in Turbo Ice Machines. Time in defrost cycle for each circuit.
119 EcoOffsetON Temperature offset to determine when the economizer can be used. The ambient
temperature must be less than Setpoint #1 “CTL TARGET “minus the value of this
Setpoint for the economizer to begin.
120 Eco Stg Dely Once the economizer valve has been opened to its maximum and all fans associ-
ated only with it have been turned on, the economizer function will wait this time in
seconds before the first condenser fan is turned on or VFD is set to its minimum
position. The minimum setting of the VFD is the value of Setpoint #54 “CND MIN
SPD”.
120 H-PMP SW TIME Time delay for switching between heating and cooling modes for heat pumps.
121 Eco MIN VLV% Minimum Economizer Analog Output valve percentage. This will be the value used
when first starting the economizer function as well as the lowest level before turn-
ing off. This Setpoint must be active to indicate that the Economizer AO option is
active.
122 Eco MAX VLV% Maximum Economizer Analog Output valve percentage.
123 Eco MAX ADJ Maximum adjustment to the Economizer Analog Output valve percentage with
each calculation. Formula:[absolute value of(Target – current) * Multiplier Setpoint
#126] / Divisor Setpoint #127
124 EcoVlvAdjDly Delay between Economizer Analog Output valve adjustments.
125 Eco StageDly Time delay between economizer reaching its maximum opening and turning on
the associated condenser fans.
If no condenser fans associated, then this Setpoint needs to be 0 and non-active.
126 Eco MULTI Multiplier to scale adjustments to the Economizer Analog Output valve percent-
age. The difference between the control sensor and its target will be multiplied by
this value.
127 Eco DIVIDE Divisor to scale adjustments to the Economizer Analog Output valve percentage.
The difference between the control sensor and its target will be divided by this
value.
128 Lost Leg Alarm If active, a check for a lost leg (lost current flow) on a part winding starter is add-
(Only HVAC) ed. A current sensor will be placed on only one of the legs; it must be set up to be
multiplied by 2 in MCS-Config (select CT-### x2 as the sensor in the SI screen). If
current flow to the leg with the sensor is lost, a low amp alarm will be generated.
If the sensor is reading more than the wanted FLA times the value of this Setpoint
for the specified period of time, then a high amp alarm is generated.
CmpMinSpeed% This is the minimum allowed compressor speed. This value will dynamically
(Only CENT) change based on an internal calculation, but will never be less than the original
number.
166
MCS-MAGNUM-V. 14 REVISION 3.2
# Name Description
129 RH CUTIN Used with the ‘Hot Gas Reheat’ option. If the reheat sensor temperature is less
(Only HVAC) than this value, then the hot gas reheat function will be activated.
CmpMaxSpeed% This is the maximum allowed compressor speed.
(Only CENT)
130 RH CUTOUT ADJ The reheat cutout temperature is calculated by adding this value to Setpoint #129
(Only HVAC) “RH CUTIN”
CmpSpdUnld% The value in this Setpoint is the actual % decrease in this adjustment to the com-
(Only CENT) pressor AO, when adjusting to meet the calculated Wanted %. Cannot be greater
than 1.
131 RH START DLY Delay in seconds that the hot gas reheat function will remain in startup mode.
(Only HVAC)
CmpSpdLoad% The value in this Setpoint is the actual % increase in this adjustment to the com-
(Only CENT) pressor AO, when adjusting to meet the calculated Wanted %. Cannot be greater
than 1.
132 RH BLEED DLY Delay in seconds that the hot gas reheat function will keep the bleed solenoid on
(Only HVAC) before exiting reheat mode.
MinLiftTemp This is the minimum allowed lift temperature. Refer to Setpoint #128 “CmpMin-
(Only CENT) Speed%“.
133 RH STAGE DLY Delay in seconds until the hot gas reheat function starts when all criteria has been
(Only HVAC) meet.
MaxLiftTemp This is the maximum allowed lift temperature. Refer to Setpoint #128 “CmpMin-
(Only CENT) Speed%“.
134 BARREL HEATER If ambient falls below this temperature, then the barrel heater will turn on.
135 REFRIG LEAK Used to detect a digital signal from a refrigerant leak detector.
136 VI PULSE Used with an adjustable VI, volume ratio. This is the pulse time expressed in
tenths of a second to adjust the VI.
137 VI DEADBAND Used with an adjustable VI, volume ratio. If the VI reading is greater than the VI
wanted ratio plus the value of this Setpoint, then the increase RO is off and the
decrease RO is pulsed. If the VI reading is less than the VI wanted ratio minus the
value of this Setpoint, then the increase RO is pulsed and the decrease RO is off.
138 VI DELAY This is the time delay between VI wanted ratio calculations.
139 OIL FLOAT If active, the Magnum checks for an oil float digital input. It must be ON for the
period of time specified in the Setpoint before this Setpoint will trip.
140 NOT IN USED: Compressors with a low SI Off sensor will be disabled when the sensor is below
208 this Setpoint.
141 NOT IN USED: Compressors with a high SI Off sensor will be disabled when the sensor is above
209 this Setpoint.
142 SERVICE MODE If non-zero, then a compressor being disabled by the pump down switch will be
continue to run until its suction pressure is zero. The compressor will be turned on
to perform the pump down the number of times indicated in this Setpoint. This is in
preparation for service to be performed on the compressor.
167
MCS-MAGNUM-V. 14 REVISION 3.2
# Name Description
143 UNLOADED % Used if a slide percentage sensor is present. When this sensor is reading less
than the value of this Setpoint, then the slide is considered unloaded. Also used
for a centrifugal vane closed. If the vane% sensor is reading less than the value of
this Setpoint, then the vane is considered closed.
Optional: If Setpoint is set up as a target, the value of this Setpoint equals the %
at which the slide is considered closed. If the Time(SEC) field is set > 0 then slide
control will be used instead of AMPS. High & low zone are used to develop the
control zone based upon the capacity wanted %. Make Setpoint #35 “AMP DB HI”
and Setpoint #36 “AMP DB LO” non-active.
144 OIL HEATER ON The oil heater will be turned on if the oil temperature is less than the value of this
Setpoint. It will be turned off if the oil temperature is greater than the value of this
Setpoint plus 5.0° Fahrenheit.
‘Time (sec)’ field: If zero, then the calculated oil temp will be the saturated suction
temperature plus the value of the Setpoint. Else it will be the value of this Setpoint.
145 OIL COOLER ON The oil cooler will be turned on if the oil seal temperature is greater than the value
of this Setpoint. It will be turned off if the oil seal temperature is less than the value
of this Setpoint minus 5.0° Fahrenheit.
146 PROC TARG Process pump target. The control value can be either temperature or pressure.
147 PROC ZONE Process pump control zone. This value is added to Setpoint #146 “PROC TARG”
to calculate the high value and subtracted to calculate the low value of the control
zone. The process pump’s VFD will be modulated to maintain inside this zone.
The adjustment to the pump speed is calculated by subtracting the controlling
SI from the value of Setpoint #146. This range has a minimum of 1% ADJ and a
maximum of 15%.
148 PROC DELY Process pump delay in seconds before next change. If calculated adjustment (Tar-
get minus controlling SI) is greater than the zone x2, or if the slope is greater than
the ROC x2, decrement twice as fast.
149 PROC MAX ROC Process pump rate of change limit. If the ROC exceeds this value, no change is
required. The ROC window equals the value of Setpoint 148 to a maximum of 60
seconds.
150 PROC MIN SPD% Minimum process pump speed if using the Modulating (AO) option.
Number of Relay Outputs that will be staged if using the Staging (RO) option.
151 UNLOADED OFF If active, the system is fully unloaded, and the control temperature is greater than
this value, then the capacity state will be set to holding.
‘Time (sec)’ field: If non-zero, then the value of this Setpoint is used as a differen-
tial and not a set temperature. The value of this Setpoint is subtracted from Set-
point #1.
152 HP OVERHEAT This Setpoint is only used when the heat pump option has been selected in the
‘Unit Type’ box in the ‘General Information’ panel under the MAG V8 screen. It
is used to protect against a heat pump with unloaders (or variable speed) from
overheating. When this Setpoint is active and the leaving temperature sensor is
greater than this Setpoint minus 3.0° Fahrenheit, then the compressor will enter
HIGH TEMP UNLOAD state. The temperature must drop to less than this Setpoint
minus 4.5° Fahrenheit before the system will move to the holding state.
153 SftyUnld Del The time delay in seconds between compressor capacity adjustments when safety
unloading.
168
MCS-MAGNUM-V. 14 REVISION 3.2
# Name Description
154 VFD Sfty Adj The VFD percentage adjustment to be made after every amount of time in Set-
point #153 “SftyUnld Del” when safety unloading.
155 LO REF TMP If active, the Magnum checks for low refrigerant temperature. If the refrigerant
temperature is less than the value of this Setpoint for the specified period of time,
a safety trip occurs.
156 LO REF UNLD The purpose of this Setpoint is to take preventative action before a low refrigerant
temperature safety trip. The compressor will unload when the refrigerant tempera-
ture is less than the value of the Setpoint #155 “LO REF TMP” plus this Setpoint.
The compressor state will be changed to LO TMP UNLOAD. The compressor will
remain in this state until the refrigerant temperature is above the value of Setpoint
#155 “LO REF TMP” plus twice the value of this Setpoint. The compressor state
change to LO TMP HOLD.
157 HP LoSuctAdj This Setpoint is only used when the heat pump option has been selected in the
(Only HVAC) ‘Unit Type’ box in the ‘General Information’ panel under the MAG V8 screen.
When in heating mode, the low suction value Setpoint #77 “LOW SUCTION” is
reduced by the value of this Setpoint.
COV LIFT TEMP Minimum change to the saturated lift before calculating a new minimum speed.
(Only CENT)
B-PUMP DELAY The time delay expressed as seconds between making decisions as to pump set-
(Boiler/Pump Con- tings.
trol)
158 DEF TRIG TMP If a defrost option has been specified and either coil #1 or coil #2 temperature is
(Only HVAC) less than or equal to this Setpoint a defrost cycle will be started if sufficient time
has elapsed since the last defrost.
B-STAGE DELY The time delay expressed as seconds between making decisions as to boiler
(Boiler/Pump Con- stage settings.
trol)
159 DEF TRIG DEL Time in minutes between defrost cycles.
(Only HVAC)
B-VFD DELAY The time delay expressed as seconds between making decisions as to pump VFD
(Boiler/Pump Con- setting.
trol) ‘Sec. to Ignore Safety’ field: contains the minimum valve setting. For example if
this cell contains 500, the valve will initially be set to 50.0% and it will never be
less than this value.
‘Window to extend Safety Time(sec)’ field: contains the maximum valve setting.
This will normally be 1000 for 100.0%.
169
MCS-MAGNUM-V. 14 REVISION 3.2
# Name Description
160 DEF REV DEL If a reversing valve is used, this is the delay in minutes the system must wait once
(Only HVAC) the valve has been opened before the defrost cycle can continue.
B-VFD TARGET The target flow that is to be maintained. This can be a differential if both input and
(Boiler/Pump Con- output pressures sensors are specified or the actual flow of the input if only sensor
trol) specified.
‘Time(sec)’ field: contains the delay in seconds before another pump can be
turned on once the valve gets to 100.0%
‘Sec. to Ignore Safety’ field: contains high dead band for the control zone. This
is added to the value of this set point. In this example the high dead band will be
63.0.
‘Window to extend Safety Time(sec)’ field: contains low dead band for the control
zone. This is subtracted from the value of this set point. In this example the low
dead band will be 57.5.
‘Safety Time Extension’ field: contains the maximum valve adjustment that can be
made at one time. In this example the maximum adjustment to the valve will be
3.0%..
161 DEF TERM TMP If both coil #1 and coil #2 temperature are greater than the value of this Setpoint,
(Only HVAC) then the defrost cycle can be terminated.
B-PUMP FLT The ‘Value’ is not used as this set point is set up to check the status of a digital
(Boiler/Pump Con- input indicated in the Starting Pump Fault cell.
trol) ‘Time(sec)’ field: contains the delay before the system will place a pump in a failed
state.
162 DEF TERM DEL The length of time in minutes of the defrost cycle.
(Only HVAC)
163 HP HEAT TARG If active, then this value will become the target temperature during heating mode.
(Only HVAC)
Purge Target If active, it indicates that a Trane external purge system is incorporated. When
(Only CENT) the suction temperature is less than this value for the number of seconds in the
‘Safety Down Time’, then the purging sequence will begin.
B-HEAT TRGT The heating target that is to be maintained.
(Boiler/Pump Con-
trol)
164 HP CTL ZONE + Added to Setpoint #163 “HP HEAT TARG” to create the upper limit of the control
(Only HVAC) zone during heating mode.
Purge Fault If active and a purge safety switch is used, this Setpoint will contain the number of
(Only CENT) seconds the switch must be ON before a purge error alarm occurs.
B-HEAT ZONE+ The high dead band for the heating control zone. This value is added to the value
(Boiler/Pump Con- of set point #163.
trol)
165 HP CTL ZONE – Subtracted from Setpoint #163 “HP HEAT TARG” to create the lower limit of the
(Only HVAC) control zone during heating mode.
Purge ExTime If the time in purging mode for the last 24 hours is greater than the value of this
(Only CENT) Setpoint, an excessive purging alarm will be generated.
B-HEAT ZONE- The low dead band for the heating control zone. This value is subtracted form the
(Boiler/Pump Con- value of set point #163.
trol)
170
MCS-MAGNUM-V. 14 REVISION 3.2
# Name Description
166 PHASE LOSS If active and the phase loss digital input is ON for the specified period of time, a
safety trip occurs. The system will attempt to restart after waiting the number of
minutes contained in the ‘Safety Down Time’ field of this Setpoint.
167 PURGE FLT ER- If active and purge float error occurs, a purge float alarm is generated. This Fault
ROR requires a lockout reset to resume purge operation.
168 PURGE COUNT If the total number of purges that occurred during the last three purge cycles
exceed this value, then reset all counters and generate a Maximum Purges Ex-
ceeded alarm. For the first thirty minutes of compressor run time – this alarm is
by passed.
169 PURGE PSI ST When the purge pressure sensor reading is equal or greater than this value, then
a purge cycle will be initiated. The cycle will end when the purge pressure sensor
reading is less than the value of this Setpoint minus Setpoint #193 “PSI DIFF”, or
5 psi if inactive.
170 EXCESS PURGE If the time in a purge cycle exceeds this Setpoint’s value in seconds, then the
cycle will be terminated and an Excessive Purge Time alarm will be generated.
This fault requires a lockout reset to resume purge operation.
171 FLA COMP#1 Full Load Amps for compressor #1. This is the amps at design suction and dis-
charge pressures referenced in the MCS-Config RO screen. This value is used to
calculate the high and the low amperage safety limits. Refer to Setpoints #75 and
#76.
For screw compressors: The amp draw when the compressor is fully loaded. This
value is used to calculate the Full Load Amps Percentage (FLA %), which is used
to control loading and unloading the slide valve.
172 FLA COMP#2 Full Load Amps for compressor #2. Refer to Setpoint #171.
173 FLA COMP#3 Full Load Amps for compressor #3. Refer to Setpoint #171.
174 FLA COMP#4 Full Load Amps for compressor #4. Refer to Setpoint #171.
175 FLA COMP#5 Full Load Amps for compressor #5. Refer to Setpoint #171.
176 FLA COMP#6 Full Load Amps for compressor #6. Refer to Setpoint #171.
177 FLA COMP#7 Full Load Amps for compressor #7. Refer to Setpoint #171.
178 FLA COMP#8 Full Load Amps for compressor #8. Refer to Setpoint #171.
179 FLA COMP#9 Full Load Amps for compressor #9. Refer to Setpoint #171.
180 FLA COMP#10 Full Load Amps for compressor #10. Refer to Setpoint #171.
181 FLA COMP#11 Full Load Amps for compressor #11. Refer to Setpoint #171.
182 FLA COMP#12 Full Load Amps for compressor #12. Refer to Setpoint #171.
183 FLA COMP#13 Full Load Amps for compressor #13. Refer to Setpoint #171.
184 FLA COMP#14 Full Load Amps for compressor #14. Refer to Setpoint #171.
185 FLA COMP#15 Full Load Amps for compressor #15. Refer to Setpoint #171.
186 FLA COMP#16 Full Load Amps for compressor #16. Refer to Setpoint #171.
187 FLA COMP#17 Full Load Amps for compressor #17. Refer to Setpoint #171.
188 FLA COMP#18 Full Load Amps for compressor #18. Refer to Setpoint #171.
171
MCS-MAGNUM-V. 14 REVISION 3.2
# Name Description
189 FLA COMP#19 Full Load Amps for compressor #19. Refer to Setpoint #171.
B-FLA PUMP The expended amp draw of the pump. If active this value is used to calculate the
(Boiler/Pump high and the low ampere safeties limits. Refer to set points 75 and 76.
Control)
190 FLA COMP#20 Full Load Amps for compressor #20. Refer to Setpoint #171.
B-FLA BOILER The ‘Value’ is not used as this set point is set up to check the status of a digital
(Boiler/Pump Con- input indicated in the Starting Boiler Fault cell.
trol) ‘Time(sec)’ field: contains the delay before the system will place a boiler stage in
a failed state.
191 TEMP DIFF This temperature differential is used to replace the hardcoded temperature differ-
ential values of several other Setpoints. It is used with the following:
Discharge temperature
Low oil seal temperature
Low/high ambient cutoffs
Compressor discharge superheat
If inactive, then hardcoded value of 5° F is used.
192 FRZ TEMP DIFF This value is added to Setpoint #102 “PUMP FREEZE PROTECTION” to deter-
mine if the leaving temperature is above the freeze protection zone.
193 CND HI/LO ZONE The value in this Setpoint is the high and low zone for your target of Setpoint #50
“CND TRGT“. If inactive then a default zone of 5 psi will be used, if metric .3 Bar.
194 CND 2ND ZONE The value in this Setpoint is the 2nd high and low zone for your target of Setpoint
#50 “CND TRGT“. If inactive then a default zone of 20 psi will be used, if metric
1.4 Bar.
195 LOW VOLTAGE If the voltage of any one of the voltage sensors is less than the value of this Set-
point, then a Low Voltage alarm will be generated and the unit will be locked out.
Voltage sensors are specified in the General Information panel under the MAG V8
screen.
196 HI VOLTAGE If the voltage of any one of the voltage sensors is greater than the value of this
Setpoint, then a Hi Voltage alarm will be generated and the unit will be locked out.
Voltage sensors are specified in the General Information panel under the MAG V8
screen.
197 LEAD Procom If zero, then rotation of the process pumps will occur whenever the lead process
(Only HVAC) pump is turned off. If no rotation has occurred during the current day, a forced
rotation at midnight will occur.
If non-zero, then process pumps rotation is inactive and this value will specify the
lead process pump.
COND LOW AMB Standard condenser logic dictates that a newly started compressor will use its
(Only CENT) own discharge pressure as the control for the first five minutes. If this Setpoint is
active and the ambient temperature sensor is reading less than the value of this
Setpoint, then this compressor’s discharge pressure will remain in control for the
additional time in seconds as specified in the ‘Time (sec)’ field.
198 PROC PUMP FLT. If active, the Magnum checks for process pump failure. The process pump sensor
(Only HVAC) reading is ON (Digital).
199 MOP TARG PSI If active, maximum operating pressure (MOP) control will be added to the EXV
(Only HVAC) control logic. This value will be the MOP suction pressure target.
200 MOP PSI ZONE Added to and subtracted from Setpoint #199 to develop the upper and lower limits
(Only HVAC) of the MOP control zone.
172
# Name Description
201 MOP ADJ % TME The adjustment value by which the EXV valve will close each time the MOP logic
(Only HVAC) calls for it to maintain the suction pressure target. This adjustment will be made
each time after the delay in the ‘Time (sec)’ field has expired.
‘Time (sec)’ field: The delay between MOP adjustments.
LOW SI OFF FEATURE NOT YET AVAILABLE
(Only CENT) If active, the Magnum checks for a Low SI Off sensor for each compressor. The
sensor can be either an analog or digital input, and is specified in the Circuit SI
screen. If the Low SI Off sensor reading is OFF (Digital) or falls below the value of
this Setpoint (Analog) for the specified period of time, the circuit will be disabled. If
a digital input, the circuit will be enabled once the sensor is ON. If an analog input,
the circuit will be enabled once the sensor is greater than this value plus the value
in the ‘Time (sec)’ field.
‘Time (sec)’ field: Differential value of this Setpoint which the analog input must be
greater than to enable the compressor.
202 DELTA TEMP EVP If active, the Magnum will check the temperature differential before additional
(Only HVAC) capacity is enabled. If the difference between entering and leaving temperature
is greater than the value of this Setpoint for the amount of time in the ‘Time (sec)’
field, then no additional capacity will be allowed.
HI SI OFF FEATURE NOT YET AVAILABLE
(Only CENT) If active, the Magnum checks for a High SI Off sensor for each compressor. The
sensor can be either an analog or digital input, and is specified in the Circuit SI
screen. If the High SI Off sensor reading is ON (Digital) or rises above the value of
this Setpoint (Analog) for the specified period of time, the circuit will be disabled.
If a digital input, the circuit will be enabled once the sensor is OFF. If an analog
input, the circuit will be enabled once the sensor is less than this value minus the
value in the ‘Time (sec)’ field.
‘Time (sec)’ field: Differential value of this Setpoint which the analog input must be
less than to enable the compressor.
203 HiSuctSheat If active, the Magnum will check for high suction superheat. If the suction super-
(Only HVAC) heat is greater than the value of this Setpoint for the specified period of time, an
alarm will be generated and a safety trip occurs.
204 COND LOW AMB Standard condenser logic dictates that a newly started compressor will use its
(Only HVAC) own discharge pressure as the control for the first five minutes. If this Setpoint is
active and the ambient temperature sensor is reading less than the value of this
Setpoint, then this compressor’s discharge pressure will remain in control for the
additional time in seconds as specified in the ‘Time (sec)’ field.
SurgeHldDlay The time in minutes to remain in a surge increase hold state after the occurrence
(Only CENT) of a surge. The surge counter will be reset with each new surge. When the surge
counter exceeds this value the compressor state will move to CMP IS HOLDING
state.
# Name Description
205 MDP MIN OIL If active, MDP logic will be added to EXV control. If the oil differential pressure is
DIFF less than the value of this Setpoint following compressor start up during the time
(Only HVAC) specified in the Sec to Ignore Safety field, then the MDP function is active and will
close the EXV valve to restore the oil differential pressure. However, the EXV will
not be allowed to go into the MDP logic if the suction pressure is less than Set-
point #77 “LOW SUCTION” plus the value of Setpoint #79 “LOW SUCT RELD”.
The MDP logic will be exited and go to EXV HOLDING when the suction pressure
is less than the Setpoint #77 “LOW SUCTION” plus the value of Setpoint #78
“LOW SUCT UNLD”.
The ‘‘Time (sec)” field contains the offset value added to Setpoint #205 value
field to calculate the oil differential pressure for exiting the MDP control. Magnum
software version 8.05S1 and later multiple this value by 10 to add a decimal, so if
you enter a value of 5 in this field the offset is 5.0psi. Prior to 8.05S1 software ver-
sion you need to enter the value with 1 assumed decimal place, for example if you
wanted an offset of 5.0psi you need to enter 50 in this field.
The ‘Lockout Delay” field contains the percentage to close the EXV valve when in
the “MDP CLOSE” state. Magnum software version 8.05S1 and later multiple this
value by 10 to add a decimal, so if you enter a value of 2 in this field the adjust-
ment is 2.0%. Prior to 8.05S1 software version you need to enter the value with
1 assumed decimal place, for example if you wanted an adjustment of 2.0% you
need to enter 20 in this field.
The ‘Sec to Ignore Safety’ cell contains the time (in minutes – not seconds) that
the MDP will be active after a compressor is started.
SurgeLoadAdj The adjustment to increase compressor speed when surging is detected.
(Only CENT)
206 COND HI AMB If active, standard condenser control on compressor startup logic will be bypassed
when there is a high ambient temperature. If the condenser type is common and
the ambient temperature is above the value of this Setpoint, then the compressor
with the highest discharge pressure will have control of the condenser.
207 UNBAL VOLTS If active, the average of the voltage sensors is calculated. Each individual voltage
sensor is compared to this average and if the difference is greater than the value
of this Setpoint, an alarm is generated and the unit is locked out.
208 LOW SI OFF FEATURE NOT YET AVAILABLE
(Only HVAC) If active, the Magnum checks for a Low SI Off sensor for each compressor. The
sensor can be either an analog or digital input, and is specified in the Circuit SI
screen. If the Low SI Off sensor reading is OFF (Digital) or falls below the value of
this Setpoint (Analog) for the specified period of time, the circuit will be disabled. If
a digital input, the circuit will be enabled once the sensor is ON. If an analog input,
the circuit will be enabled once the sensor is greater than this value plus the value
in the ‘Time (sec)’ field.
‘Time (sec)’ field: Differential value of this Setpoint which the analog input must be
greater than to enable the compressor.
# Name Description
209 HI SI OFF FEATURE NOT YET AVAILABLE
(Only HVAC) If active, the Magnum checks for a High SI Off sensor for each compressor. The
(HVAC 08.02E1 or sensor can be either an analog or digital input, and is specified in the Circuit SI
Greater screen. If the High SI Off sensor reading is ON (Digital) or rises above the value of
Formerly #140) this Setpoint (Analog) for the specified period of time, the circuit will be disabled.
If a digital input, the circuit will be enabled once the sensor is OFF. If an analog
input, the circuit will be enabled once the sensor is less than this value minus the
value in the ‘Time (sec)’ field.
‘Time (sec)’ field: Differential value of this Setpoint which the analog input must be
less than to enable the compressor.
COMP SURGING The number of surges allowed before a safety trip occurs. Surges can either come
(Only CENT) in the form of sudden amperage or lift changes.
(HVAC 08.02E1 or The amp draw rate of change difference for the compressor is recorded over a
Greater period of time, not to exceed 60 seconds. When change exceeds the value in
Formerly #141) Setpoint #210 “AMP SurgeROC”, it is counted as a surge. This rate of change dif-
ference can be either a positive or negative value.
The lift pressure rate of change is the difference between discharge and suction
pressure for the compressor recorded over a period of time, not to exceed 60
seconds. When change exceeds the value in Setpoint #211 “LiftSurgeROC”, it
is counted as a surge. This rate of change difference can be either a positive or
negative value.
210 ECO LL3 D-SHT If active and the economizer liquid line solenoid is controlled on percentage (not
(Only HVAC) last step), then a low discharge superheat test is added before checking whether
the solenoid should be turned on or not.
If discharge superheat is less than this value plus Setpoint #84 “LO DISC SHEAT”,
then the solenoid will simply be turned off.
AMP SurgeROC Refer to Setpoint #209 “COMP SURGING”.
(Only CENT)
211 NO OIL FLOW If active and there is an Oil Flow sensor specified in the ‘Oil Flow Switch’ cell of
(Only HVAC) the Circuit SI screen, then the Magnum will test for oil flow. If the No Oil Flow sen-
sor reading is OFF (Digital) or falls below the value of this Setpoint (Analog) for
the specified period of time, then a safety trip occurs.
LiftSurgeROC Refer to Setpoint #209 “COMP SURGING”.
(Only CENT)
212 COMP SPD FLT If active and there is an Compressor Speed Fault sensor specified in the ‘Com-
(Only HVAC) pressor speed fault’ cell of the Circuit Base screen, then the Magnum will test
for Compressor Speed Fault whether the compressor is running or not. The fault
sensor can be either an analog or digital input. If the fault sensor reading is ON
(Digital) or falls below the value of this Setpoint (Analog) for the specified period of
time, then a safety trip occurs.
SurgingCount This Setpoint is used to take preventive action to avoid a safety trip from excess
(Only CENT) surges. If the number surges exceed this value within the time in seconds of Set-
point #213 “SurgingTime”, then the compressor speed will increase and the vain
will close and the compressor state will change to UNIT LOADING-VFD.
213 PROC LOW FLOW If active and process pump differ. is less than this Setpoint, then a safety trip oc-
(Only HVAC) curs.
SurgingTime Refer to Setpoint #212 “SurgingCount”.
(Only CENT)
MCS-MAGNUM-V. 14 REVISION 3.2
# Name Description
214 NO OIL FLOW If active and there is an Oil Flow sensor specified in the ‘Oil Flow Switch’ cell of
(Only CENT) the Circuit SI screen, then the Magnum will test for oil flow. If the No Oil Flow sen-
sor reading is OFF (Digital) or falls below the value of this Setpoint (Analog) for
the specified period of time, then a safety trip occurs.
215 COMP SPD FLT If active and there is an Compressor Speed Fault sensor specified in the ‘Com-
(Only CENT) pressor speed fault’ cell of the Circuit Base screen, then the Magnum will test
for Compressor Speed Fault whether the compressor is running or not. The fault
sensor can be either an analog or digital input. If the fault sensor reading is ON
(Digital) or falls below the value of this Setpoint (Analog) for the specified period of
time, then a safety trip occurs.
‘SEC to Ignore Safety’ field: delay before adjusting the EXV on TurboCor com-
pressors on a common suction group, allowing the system to stabilize before mak-
ing an adjustment.
216 LIS MOTOR TEMP If active, and motor temperature is greater than this value then Liquid injection
solenoid (LIS) is ON. If it is less than this value minus the ‘Time (sec)’ field of this
set point then the LIS is OFF.
‘Time (sec)’ field: Offset of motor temperature to turn LIS OFF.
CLLC LEVEL TRG The ‘Value’ is the target that is to be maintained of the condenser liquid level.
(Only CENT) The ‘Time(sec)’ contains the dead band of the target. For example if the value
is 60.0 (target) and the ‘Time(sec)’ field is 5 (dead band) the control zone for the
condenser liquid level is between 55.0 and 65.0.
176
MCS-MAGNUM-V. 14 REVISION 3.2
# Name Description
217 CLLC VALVE TRG The ‘Value’ is the target or minimum opening of the CLLC control valve.
(Only CENT) The ‘Time(sec)’ contains the normal delay between making valve adjustments.
This time is expressed in seconds.
The ‘Sec. to Ignore Safety’ contains the delay between making valve adjustments
when the CLLC is in a startup mode or the chilled water is not with in its control
zone, this is an unstable condition.
The ‘Window to extend Safety Time(sec)’ contains the maximum valve adjustment
value. This value has an assumed decimal place; that is a value of 50 will allow a
maximum adjustment of 5.0. The actual adjustment will be calculated based upon
the valve setting and its desired position.
This set point is only used if the AO TYPE of CLLC valve has been selected.
LOW EXV TAR- The minimum Refrigerant Level target. If active and the EXV is controlled by Re-
GET frigerant Level, then a new variable level target logic will be activated. As the unit
(Only HVAC) capacity increases, the refrigerant level target will change according to a linear
calculation between Setpoint #9 “LEVEL TARGET” (the maximum target level) and
Setpoint #217 “LOW EXV TARGET” (the minimum target level). This relationship
is explained in the following graph:
EXV Level Target
(Example of a 3 step system)
50% Setpoint #9
Calculated EXV Level Target
“LEVEL TARGET”
45%
40%
35%
30% EXV Level
Target
25% Setpoint #217
“LOW EXV TARGET”
20%
25% 80% 135% 190% 245% 300%
Setpoint #31 (Number of steps
"MIN FLA%" (3) × Setpoint #30
Total Cooling Capacity of Unit "MAX FLA %")
218 CLLC MAX ROC The ‘Value’ contains the rate of change that will determine if the condenser liquid
(Only CENT) level rate of change is moving fast enough.
OIL REC VENT Time on for device #1vent cycle.
CYCLE #1
219 OIL REC VENT Time on for device #2 vent cycle.
CYCLE #2
220 OIL REC VENT Time on for device #3 vent cycle.
CYCLE #3
221 OIL REC VENT Time on for device #4 vent cycle.
CYCLE #4
222 OIL REC OIL POT Time on for oil pot cycle, common.
CYCLE
223 OIL REC OIL Time on for oil charge cycle.
CHARGE CYCLE
224 OIL REC REPEAT Time delay before repeating cycles.
CYCLE
177
MCS-MAGNUM-V. 14 REVISION 3.2
# Name Description
225 CLLC LEVEL TAR- Condenser Liquid Level Control level target.
GET The safety time is dead band + and -.
226 CLLC VALVE TAR- ‘Safety Time’ is normal delay between valve adjustments.
GET Time to bypass safety test is delay when in startup or unstable.
Time to extend safety time is ADJ % if AO valve.
227 CLLC MAX ROC Condenser Liquid Level Control max ROC both + & -.
228 Force On Oil Re- If active, this Setpoint force compressor ON for oil, if more than 1 compressor in a
covery group is needed then the safety time is delay.
The ‘Value’ is compressor current run time in minutes.
The safety time is time between turning on multiple compressors.
Time to bypass or extend safety time is not used.
The max adj is time that a compressor is in ON OIL RECOVERY state.
Extend safety test time is on time to force off ready compressor to on.
229 CHK VALVE FLT If active, when the compressor is off, test the difference between discharge & suc-
tion psi. This safety is to determine if a check valve has failed; when triggered an
error message with “CHK VALVE FLT” and the circuit that has the problem will be
generated and the entire unit will be locked out.
Value: The pressure difference.
Time (SEC): The safety delay; SEC to Ignore Safety cell contains the time in sec-
onds that the compressor must be off before the safety test is made.
230 MAX DIFF PSI If active, this Setpoint helps with Low Suction/Unsafe Suction trips in EXV Logic.
ROC Value field: Maximum Differential Pressure Rate of Change before forcing a
change to the EXV position (Suggested value of 10 PSI).
‘Time (sec)’ field: Seconds between samples used for calculating the Rate of
Change (Suggested value of 15 seconds).
‘Safety Down Time(min)’ field: Minimum delay between EXV adjustments (Sug-
gested value of 10 seconds).
‘Sec. to Ignore Safety’ field: Delay after compressor start before adjusting the EXV
based on the Maximum Differential Pressure Rate of Change (Suggested value of
300 seconds).
‘Window to Extend Safety Time(sec)’ field: Adjustment multiplier to the EXV (Sug-
gested value of 1).‘Safety Time Extension (sec)’ field: Adjustment divisor to the
EXV (Suggested value of 20).
178
Providing HVAC/R Control Solutions Worldwide