I-Et-3010.00-5140-741-P4x-002 - H - Medium-Voltage Motor Control Center and Switchgear For Offshore Units
I-Et-3010.00-5140-741-P4x-002 - H - Medium-Voltage Motor Control Center and Switchgear For Offshore Units
AREA:
TITLE:
MEDIUM-VOLTAGE MOTOR CONTROL CENTER AND NP-1
DP&T/SRGE SWITCHGEAR FOR OFFSHORE UNITS ESUP
MICROSOFT WORD / V. 2003 /I-ET-3010.00-5140-741-P4X-002_H.DOCX
INDEX OF REVISIONS
TABLE OF CONTENTS
1. OBJECTIVE ............................................................................................................................................... 3
2. REFERENCE DOCUMENTS, STANDARDS AND CODES ..................................................................... 3
2.1 PETROBRAS DOCUMENTS ............................................................................................................................... 3
2.2 IEC - INTERNATIONAL ELECTROTECHNICAL COMMISSION ................................................................................. 4
2.3 IEEE - THE INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (ONLY WHERE SPECIFIED) .................... 4
2.4 BRAZILIAN LABOUR AND EMPLOYMENT MINISTRY ........................................................................................... 4
2.5 ASTM – AMERICAN SOCIETY FOR TESTING AND MATERIAL.............................................................................. 5
2.6 IMO - INTERNATIONAL MARITIME ORGANIZATION............................................................................................ 5
2.7 IOGP - INTERNATIONAL ASSOCIATION OF OIL & GAS PRODUCERS.................................................................... 5
3. GENERAL CONDITIONS .......................................................................................................................... 5
4. CONSTRUCTIVE CHARACTERISTICS ................................................................................................... 6
4.1 GENERAL REQUIREMENTS .................................................................................................................................. 6
4.2 SPARE FUNCTIONAL UNITS (FEEDERS AND STARTERS) ...................................................................................... 6
4.3 ENVIRONMENTAL CONDITIONS, INCLINATION REQUIREMENTS AND VIBRATION REQUIREMENTS ...................... 6
4.4 INSULATION LEVEL ............................................................................................................................................ 7
4.5 CLASSIFICATION OF ASSEMBLIES ....................................................................................................................... 7
4.6 STRUCTURE ........................................................................................................................................................ 8
4.7 BUSBARS .......................................................................................................................................................... 10
4.8 INTERNAL WIRING AND CONDUCTORS ............................................................................................................. 11
4.9 EXTERNAL WIRING AND CONDUCTORS ENTRANCE .......................................................................................... 12
4.10 CABLE LUGS AND TERMINALS .......................................................................................................................... 13
4.11 TERMINAL BLOCKS........................................................................................................................................... 13
4.12 CHANNELS ........................................................................................................................................................ 13
4.13 HEATING RESISTORS......................................................................................................................................... 14
4.14 FUNCTIONAL UNITS .......................................................................................................................................... 15
4.15 BUSBAR TRUNKING (BUSWAYS) ....................................................................................................................... 27
4.16 EXTRACTION TRUCK ........................................................................................................................................ 27
4.17 SHORT-CIRCUIT PEAK CURRENT LIMITING DEVICES (LIMITER) ....................................................................... 28
4.18 NAMEPLATES AND MARKINGS .......................................................................................................................... 29
4.19 PAINTING .......................................................................................................................................................... 32
4.20 PROTECTION ..................................................................................................................................................... 32
4.21 ELECTROMAGNETIC COMPATIBILITY (EMC) .................................................................................................... 33
4.22 CONTROL VOLTAGES ........................................................................................................................................ 34
4.23 AUXILIARY VOLTAGES ..................................................................................................................................... 35
4.24 INTERFACE WITH AUTOMATION........................................................................................................................ 35
5. MANUFACTURER DOCUMENTATION.................................................................................................. 36
6. PACKAGE AND TRANSPORT................................................................................................................ 37
7. INSPECTION AND TESTS...................................................................................................................... 38
7.1 GENERAL .......................................................................................................................................................... 38
7.2 TYPE TESTS ...................................................................................................................................................... 38
7.3 ROUTINE TESTS ................................................................................................................................................ 38
7.4 SPECIAL TESTS ................................................................................................................................................. 38
8. TRAINING ................................................................................................................................................ 40
9. SPARE PARTS AND TOOLS .................................................................................................................. 40
10. DATA SHEETS FORMS .......................................................................................................................... 41
11. ABBREVIATIONS AND ACRONYMS ..................................................................................................... 41
12. ANNEX..................................................................................................................................................... 42
Nº. REV.
TECHNICAL SPECIFICATION I-ET-3010.00-5140-741-P4X-002 H
AREA: SHEET:
3 of 42
TITLE:
MEDIUM-VOLTAGE MOTOR CONTROL CENTER AND NP-1
SWITCHGEAR FOR OFFSHORE UNITS ESUP
1. OBJECTIVE
This specification establishes the technical requirements for the design, construction and tests of
Medium-Voltage Motor Control Centers (MCC) and Medium-Voltage Switchgears (CDC) for
Offshore Units.
Panel design shall comply with requirements of Classification Society, Brazilian Legislation,
applicable regulatory rules, Supplementary Specification to IEC 62271-200 High-voltage
switchgear and controlgear (version 1.0, October 2018) attached to this Specification and
standards listed below.
At the design development and for equipment specification, IEC standards shall be used, all on
their latest revisions. Exceptionally, where it is clearly justifiable, the ANSI, NEMA, IEEE and
other internationally recognized standards may be used. Their use shall be restricted to specific
cases and approved by PETROBRAS.
2.3 IEEE - The Institute of Electrical and Electronics Engineers (only where specified)
C37.2 Standard for Electrical Power System Device Function Numbers, Acronyms,
and Contact Designations
3. GENERAL CONDITIONS
3.1 For the purpose of this document, requirements concerning both MCCs and CDCs are cited
using the word “Panel” or no word. Requirements concerning only MCCs are cited using
the word “MCC” and requirements concerning only CDCs are cited using the word “CDC”.
Refer to abbreviations on item 11.
3.2 Panels shall be designed and manufactured complying with the requirements of
Classification Society rules, I-ET-3010.00-5140-700-P4X-005 - REQUIREMENTS FOR
HUMAN ENGINEERING DESIGN FOR ELECTRICAL SYSTEM OF OFFSHORE
UNITS and NR-10.
3.3 The specific characteristics of the Panel shall be indicated in the Data-Sheet.
3.4 The Manufacturer shall supply all the electric materials, accessories (connection cables,
connectors, software, software licenses, calibration boxes, etc.), equipment and specific
tools, which are necessary for the assembly, start-up, commissioning, operation,
disassembly and maintenance of the Panel.
3.5 The final assembly of the Panels in the Unit shall be done by Manufacturer.
3.6 It shall not be acceptable out of date or obsolete equipment or components. Technical
support and supply of replacement parts shall be guaranteed for ten (10) years.
3.7 The use of switchgear and controlgear assemblies and sub-components with less than 3
years proven operational service shall be approved by PETROBRAS.
3.8 For terms and definitions, refer to I-ET-3010.00-1200-940-P4X-002 - GENERAL
TECHNICAL TERMS.
3.9 The following items of the Supplementary Specification to IEC 62271-200 High-voltage
switchgear and controlgear (version 1.0, October 2018) shall not be applicable to this
specification:
Items 2.1.2, 4.1, 4.2, 4.4.1, 4.4.2, 4.8, 4.101.2, 5.0.101, 5.0.102, 5.3.101, 5.3.101.2, 5.4.1.2,
5.4.3.4.1, 5.9, 5.15.1, 5.15.2, 5.15.3, 5.17, 5.20, 5.102.1, 5.103.1, 5.104, 5.106, 5.106.2,
5.107, 5.108.3, 5.109, 5.111, 5.112.1, 5.112.2, 5.112.4, 5.114.3, 5.115.2, 5.115.3 and 7.
Nº. REV.
TECHNICAL SPECIFICATION I-ET-3010.00-5140-741-P4X-002 H
AREA: SHEET:
6 of 42
TITLE:
MEDIUM-VOLTAGE MOTOR CONTROL CENTER AND NP-1
SWITCHGEAR FOR OFFSHORE UNITS ESUP
4. CONSTRUCTIVE CHARACTERISTICS
4.1.1 Panels shall be manufactured, tested and installed according to all standards listed
on item 2.
4.1.2 For installation in FPSOs and FSOs platforms, the standard IEC 60092-201 shall
have priority over others.
4.1.3 Panels shall be designed to withstand the thermal stresses due to thermal equivalent
short-circuit current (Ith, according to IEC 60909) informed in Data-Sheet for 1s. The
rated short-time withstand current (Ik according to IEC 62271-1) of the Panel
considering rated duration of short-circuit (tk according IEC 62271-1) of 1s shall be
bigger than the informed Ith.
4.1.4 Panels shall be designed to withstand the dynamic stresses due to peak short-circuit
current (ip according to IEC 60909) informed in Data-Sheet. The rated peak
withstand current (Ip according to IEC 62271-1) of the Panel shall be bigger than the
informed ip.
4.1.5 Panels using flammable liquids in its components shall not be accepted.
4.2.1 Besides the definition from Supplementary Specification to IEC 62271-200 High-
voltage switchgear and controlgear, the spare Functional Units shall, include all
hardwired and network interface signals regarding interlock, protection, control and
supervision according to I-LI-3010.00-5140-797-P4X-001 - ELECTRICAL
SYSTEM AUTOMATION INTERFACE SIGNALS LIST considering the Spare
Functional Unit Classification according control mode.
4.2.2 Spare functional units quantities shall be defined in Data-Sheets, but at least 1 (one)
spare functional unit per busbar, suitable for motor load, shall be supplied, with rated
current equal to the rated current of the biggest load of the Panel.
4.2.3 Spare Functional Units classification according to control mode shall comply with
I-ET-3010.00-5140-700-P4X-003 – ELECTRICAL REQUIREMENTS FOR
PACKAGES FOR OFFHORE UNITS.
4.3.1 The ambient temperature design for the Panels shall be 45°C, as stated in IEC
61892-1.
4.3.2 The design humidity, as a function of temperature, shall be 95% up to 45°C and 70%
above 45°C, as stated in IEC 61892-1.
4.3.3 Panels and internal equipment and materials shall be suitable for storage, service
and installation on marine and petrochemical environment, complying with
requirements related to these conditions defined in I-ET-3010.00-5140-700-P4X-
002 - SPECIFICATION FOR ELECTRICAL MATERIAL AND EQUIPMENT
FOR OFFSHORE UNITS.
Nº. REV.
TECHNICAL SPECIFICATION I-ET-3010.00-5140-741-P4X-002 H
AREA: SHEET:
7 of 42
TITLE:
MEDIUM-VOLTAGE MOTOR CONTROL CENTER AND NP-1
SWITCHGEAR FOR OFFSHORE UNITS ESUP
4.3.4 When installed in mobile units and ships (FPSO and FSO), the Panels shall be
suitable to operate under inclination variations (static and dynamic) and acceleration
conditions specified by IMO MODU CODE, IEC 61892 and Classification Society.
4.3.5 Panels shall comply with vibrations requirements defined in I-ET-3010.00-5140-
700-P4X-002 - SPECIFICATION FOR ELECTRICAL MATERIAL AND
EQUIPMENT FOR OFFSHORE UNITS and Classification Society rules.
4.5.1 The Panels shall be classified according to IEC 62271-1, IEC 62271-200, and IEC
61892-3.
4.5.2 Unless otherwise stated in Project Documentation, Panels shall be proper for indoor
installation.
4.5.3 Panels shall be stationary assemblies.
4.5.4 The external protection degree shall be defined according to IEC 62271-200 and
IEC 60529 with a minimum:
IP42W, for Panels installed in panel rooms;
IP44W, for Panels installed in machinery rooms;
IP56SW, for Panels installed outdoors.
Notes: 1 - W means Panel suitable for saline, hot and damp atmosphere;
2 - S means that the test for ingress of water is carried-out with the movable
parts at stationary conditions.
3 - Outdoors installations shall be submitted to PETROBRAS for approval
and installation in hazardous areas shall not be permitted.
4.5.5 Panel shall be designed to keep the external protection degree with the functional
units in test and isolated positions and during transfer from one position to another.
4.5.6 Panels shall be composed by withdrawable parts with the following positions:
a) Connected or inserted;
b) Test;
c) Disconnected or Extracted;
d) Removed.
Nº. REV.
TECHNICAL SPECIFICATION I-ET-3010.00-5140-741-P4X-002 H
AREA: SHEET:
8 of 42
TITLE:
MEDIUM-VOLTAGE MOTOR CONTROL CENTER AND NP-1
SWITCHGEAR FOR OFFSHORE UNITS ESUP
4.6 Structure
4.6.1 The maximum height, including the skid, shall not exceed 2400mm (excluding the
exhaust ducts for expansion of gases from short-circuits).
4.6.2 The base of the Panel shall be drilled and the Panel shall be fixed to one additional
metallic base (skid) by screws passing through the holes.
4.6.3 The skid shall be dimensioned just like a bi-supported beam along the longitudinal
direction, to support the whole Panel weight. The skid shall have sides covered with
plates to avoid access of humidity to the Panel’s lower portion. The skid shall be
drilled and fixed to the floor. The skid and all accessories necessary to fix the skid
to the floor shall be supplied by Panel manufacturer.
4.6.4 To avoid a dangerous the inclination of equipment when manoeuvring equipment
during construction and installation, the two points supported beam on the
longitudinal direction fixing base shall also have transversal directional beams.
These transversal beams shall not interfere with cable access and any other
installation requirements. Other solution may be accepted if it is previously
submitted and approved by PETROBRAS
4.6.5 Maximum height for installation of push-buttons and instruments shall be in
accordance with I-ET-3010.00-5140-700-P4X-005 - REQUIREMENTS FOR
HUMAN ENGINEERING DESIGN FOR ELECTRICAL SYSTEM OF
OFFSHORE UNITS.
Nº. REV.
TECHNICAL SPECIFICATION I-ET-3010.00-5140-741-P4X-002 H
AREA: SHEET:
9 of 42
TITLE:
MEDIUM-VOLTAGE MOTOR CONTROL CENTER AND NP-1
SWITCHGEAR FOR OFFSHORE UNITS ESUP
4.6.6 Panels shall be self-supported with extension possibility at both ends. The rear side
shall be provided with removable sheets. Lifting devices at the upper side shall be
provided.
4.6.7 The panels shall be designed in such a way that a maximum of 2 columns are
connected for mechanical handling.
4.6.8 Panels shall have access for installation and maintenance through the front and rear
side. Back doors shall be provided with hinges and locks to keep them in open
position.
4.6.9 Panels shall be comprised of independent vertical sections, formed by metallic
compartments, aiming the flame retardation of a possible fire from one functional
unit to another.
4.6.10 CANCELLED.
4.6.11 Each vertical section shall contain doors with hinges in its front part. The extraction
of the circuit-breaker or contactor to the test position or its insertion shall be possible
only with the door closed, through crank.
4.6.12 All vertical sections of incoming, tie and outgoing circuit-breakers of CDCs and
MCCs shall be subdivided in no less than the following compartments:
a) compartment of busbar (busbar section for tie vertical sections);
b) compartment of switching devices;
c) cable compartment (busbar section for tie vertical sections);
d) compartment of low-voltage components for control, protection, signalling,
measurement and other auxiliaries.
4.6.13 All vertical sections of measurement/protection voltage transformers (VTs) and
busbar transitioning shall be subdivided in no less than the following compartments:
a) compartment of busbar;
b) compartment of the device (VT or transitioning connection bars);
c) compartment of low-voltage components for control, protection, signalling,
measurement and other auxiliaries.
4.6.14 All removable parts and components of the same type, rating and construction shall
be mechanically and electrically interchangeable.
4.6.15 The arrangement shall enable easy access for external wiring installation and
maintenance, including space to manipulate necessary tools.
4.6.16 The structure of the withdrawable parts shall be dimensioned to support its weight
in all positions.
4.6.17 All the switching devices, being circuit-breakers or contactors, shall allow
placement of padlocks to lock them in the OFF (open) position.
4.6.18 Equipment that allows either set or calibration shall be installed in such a way that
it shall not be necessary to withdraw or to open the switching device compartment
door to operate them. Exceptions shall be agreed with PETROBRAS.
4.6.19 The grips and switching devices connection systems to busbars shall be protected
against rusting and they shall be able to support, without deformations, the electrical,
mechanical and thermal stresses due to short-circuit currents.
Nº. REV.
TECHNICAL SPECIFICATION I-ET-3010.00-5140-741-P4X-002 H
AREA: SHEET:
10 of 42
TITLE:
MEDIUM-VOLTAGE MOTOR CONTROL CENTER AND NP-1
SWITCHGEAR FOR OFFSHORE UNITS ESUP
4.6.20 When installed in FPSO, FSO or SS, the Panels shall have isolated handrails along
the front and rear sides.
4.6.21 Panels shall be provided with a durable mimic one-line (synoptic) diagram on the
front of the assembly, displaying the single line arrangement of busbars and the main
circuit switching devices of incomers, bus couplers, limiter (when applicable),
feeders and starters.
4.6.22 The arrangement of the panels shall be conceived aiming the lowest heat dissipation
in the main busbars at the worst operation condition.
4.6.23 The panels shall be constructed so that thermal inspection by optical infrared
thermographic devices could be safely performed with the circuits energized. This
facility shall not compromise arc withstand capability to comply with IEC 62271-
200.
4.7 Busbars
Q ≤ 16 Q
50 % of the current-carrying
Q ≥ 16 conductor, but not less than
16 mm2
4.8.1 All cables shall comply with the requirements of the I-ET-3010.00-5140-700-P4X-
002 - SPECIFICATION FOR ELECTRICAL MATERIAL AND EQUIPMENT
FOR OFFSHORE UNITS.
Nº. REV.
TECHNICAL SPECIFICATION I-ET-3010.00-5140-741-P4X-002 H
AREA: SHEET:
12 of 42
TITLE:
MEDIUM-VOLTAGE MOTOR CONTROL CENTER AND NP-1
SWITCHGEAR FOR OFFSHORE UNITS ESUP
4.8.2 All cables shall be flame retardant according to IEC 60332-3-22, Category A.
4.8.3 Power conductors shall be provided with EPR or XLPE insulation.
4.8.4 Control and signal conductors shall be provided with EPR, XLPE or PVC insulation.
Control and signal circuits with rated voltage up to 220V with neutral bolted
grounded shall use cables with minimum rated voltage (U0/U) 150/250(300)V.
Control and signal circuits with rated voltage up to 220V with isolated neutral shall
use cables with minimum rated voltage (U0/U) 450/750V.
4.8.5 Discrete signals cables shall be collectively shielded. Analog signals cables shall
have twisted pairs with a shield for each pair and a collective shield under the
external cover.
4.8.6 All internal wiring shall be duly identified through plastic rings at the ends, with the
codification shown on the wiring drawings.
4.8.7 The insulation of cables used for D.C. circuits shall be red for wiring with positive
voltage and black for wiring with negative voltage.
4.8.8 The outer sheath (protective cover) colour of cables used in ground circuits shall be
striped with green and yellow, according to IEC 60445.
4.8.9 Panels shall be delivered with all connections between installed components done.
4.8.10 The wiring between sections separated for transport shall finish on terminal blocks,
so that the final interconnection could be easily completed with jumpers, by the time
the sections are assembled.
4.8.11 Power cables shall be suitable for the functional unit rated power and shall withstand
the thermal effect resulting from short-circuit currents.
4.8.12 Components assembled on doors shall be connected through extra-flexible
conductors.
4.8.13 The electric cables of the low-voltage compartment shall have segregated internal
path and terminal blocks, according to requirements of IEC 61000-5-2.
Additionally, these cables shall have path and terminal blocks segregated in the
following groups:
a) control in 220 VDC;
b) heating, lighting and socket-outlet circuits in 220VAC,
c) 4-20mA analogical signals, RTD signals, data transmission signals;
d) instrument transformers incoming signals.
4.8.14 The minimum cross-section area for internal cables shall be of 0.5mm² for control
circuits (item a) of 4.8.13), 1.0mm2 for instrumentation circuits (item c) of 4.8.13),
2.5mm² for power, lighting and VTs circuits and 4mm² for CTs circuits.
4.9.1 Unless otherwise stated in Project Documentation, all incoming and outgoing cables
of medium-voltage CDCs shall enter through the bottom of the Panel.
4.9.2 All incoming and outgoing cables entrance in medium-voltage MCCs shall be
according to project documentation.
Nº. REV.
TECHNICAL SPECIFICATION I-ET-3010.00-5140-741-P4X-002 H
AREA: SHEET:
13 of 42
TITLE:
MEDIUM-VOLTAGE MOTOR CONTROL CENTER AND NP-1
SWITCHGEAR FOR OFFSHORE UNITS ESUP
4.9.3 Unless otherwise stated in Project Documentation, if bus trunking connections are
used, the Panels shall have appropriate edges and flexible connectors for entrance
through the top.
4.9.4 For single core cables, Manufacturer shall provide removable plates, with a
minimum thickness of 2.8mm, made of AISI-316 stainless steel or non-magnetic
material. For all other cases, the removable plates shall be of painted galvanized
steel, with galvanization thickness for 30 years lifetime. The removable plates shall
be provided with neoprene rubber gaskets. MCTs can be used as an alternative.
4.9.5 Metallic cable-glands made of material galvanically compatible with the removable
plates material shall be supplied with the Panel.
4.10.1 Control circuits shall use ring (preferred) or pin cable lugs. CTs and power circuits
shall use ring cable lugs.
4.10.2 Terminals for control circuits shall be indirect pressure screw type and shall be
covered with melamine or other similar equivalent material, which shall not have
organic and toxic substances.
4.10.3 Lugs for power circuits shall be compression type.
4.10.4 Sizes of terminals for power circuits shall be defined according to feeders’ cross-
sectional area that shall be determined during the Detailed Design execution.
4.10.5 All cable lugs for power circuits shall be supplied within the Panel.
4.11.1 Only one cable shall be connected to each cable lug and only one cable lug shall be
connected to each terminal. Jumpers between terminals by external conductors shall
not be accepted. For this purpose, metallic bridges shall be used.
4.11.2 Each control terminal block shall have at least 10% of reserve, for future application.
4.11.3 Terminal blocks installation shall permit enough space to perform the cable
termination, their fitting, easy access to terminals and easy reading of identification.
4.12 Channels
4.12.1 The internal conductors shall be installed in channel type cable trays with covers.
4.12.2 The power cables shall be segregated from control and data cables, by installation
in separated cable trays, placed as far as possible.
4.12.3 Cable channels filling shall not exceed 75% of their capacity in order to prevent
damage in internal cables during construction, commissioning and maintenance.
Nº. REV.
TECHNICAL SPECIFICATION I-ET-3010.00-5140-741-P4X-002 H
AREA: SHEET:
14 of 42
TITLE:
MEDIUM-VOLTAGE MOTOR CONTROL CENTER AND NP-1
SWITCHGEAR FOR OFFSHORE UNITS ESUP
4.14.1 General
4.14.1.1 Unless otherwise stated in Project Documentation, the starters up to
1.2MW in 4.16kV and 6.6kV systems for MCCs shall be formed by
current-limiting fuses, SF6 or Vacuum contactors and microprocessor-
based multifunction relays (MMRs). For other cases, the starters in MCCs
shall be formed by SF6 or Vacuum circuit-breakers and MMRs. The
starters shall be configured in full compliance with the NR-10 Standard.
4.14.1.2 Unless otherwise stated in Project Documentation, the starters in CDCs
shall be formed by SF6 or Vacuum circuit-breakers and MMRs.
4.14.1.3 Manufacturer shall dimension all functional units according to the loads
rated power defined by Detailed Design.
4.14.2 Protective Devices
4.14.2.1 Circuit-breakers and MMRs shall be used as protective devices for the
power conductors and power equipment in CDCs and also in incoming, tie
and back-feed circuits of MCCs.
4.14.2.2 Fuses, MMRs and contactors shall be used as protective devices for the
power conductors and power equipment in outgoing circuits of MCCs.
4.14.2.3 Each panel functional unit shall have dedicated miniature circuit-breaker to
protect circuits of spring charging motor (when applicable), and other
miniature circuit-breakers to MMRs control and signalling.
4.14.3 Power Fuses
4.14.3.1 Functional units of MCCs shall be supplied with current-limiting fuses with
appropriated capacity to give the maximum protection and to allow the
motors starting, complying with IEC 60282-1.
4.14.3.2 The manufacturer shall supply test certificate, issued by official laboratory,
testifying that the fuses are of “current-limiting" type.
4.14.3.3 Fuses shall be installed in such a way that they can be removed and inserted
with no voltage in their terminals.
4.14.3.4 Blown fuses shall trip main contactors and shall block their closing. Blown
fuses signalling in the front side of the panel shall be provided according
to 4.14.15.1 and 4.14.15.2 and shall be available to the MMR in order to
send an alarm through network.
4.14.3.5 Contactor-fuse combinations shall be furnished by the same manufacturer
and comply with IEC 62271-106.
4.14.4 Main Contactors
4.14.4.1 Power circuits of functional units of MCCs shall use withdrawable vacuum
or SF6 contactors complying with IEC 62271-106 and MMRs.
4.14.4.2 Main contactors shall be with three-poles, dry and suitable for direct-on-
line start of three-phase induction motors.
Nº. REV.
TECHNICAL SPECIFICATION I-ET-3010.00-5140-741-P4X-002 H
AREA: SHEET:
16 of 42
TITLE:
MEDIUM-VOLTAGE MOTOR CONTROL CENTER AND NP-1
SWITCHGEAR FOR OFFSHORE UNITS ESUP
4.14.4.3 Nominal operating voltage for contactors coils shall be 220VDC. These
devices shall close satisfactorily their contacts at voltage variation between
85% and 110% of rated voltage. The maximum voltage limit for drop out,
as defined in IEC 62271-1, shall be 70% of rated voltage.
4.14.4.4 It is recommended to use fuses and contactors from the same manufacturer.
4.14.4.5 In the cases where is not possible to comply with the previous item, the
Manufacturer of the Panel shall present a declaration of the contactor
manufacturer guaranteeing that the contactor is appropriately protected by
the specified fuse.
4.14.4.6 Electric control shall be executed by closing and opening contacts of
buttons or switches installed in the front door of the cubicle or by remote
signals, energizing or de-energizing coils. STOP action (turn off) shall be
available through frontal push-buttons for all main contactors. START
action (turn on) shall be delayed to close and available through frontal
push-button for outgoing feeders for transformers, non-motor loads
classified as EA03 and non-motor loads classified as EA02. For the other
kind of loads the closing action from front door buttons or switches shall
be active only with functional unit in test position. For loads classification
according control mode, refer also to I-ET-3010.00-5140-700-P4X-003 –
ELECTRICAL REQUIREMENTS FOR PACKAGES FOR OFFHORE
UNITS.
4.14.5 MCCs Functional Units Interlocks
4.14.5.1 There shall be a mechanical lock to prevent the opening of the enclosure
door when the contactor is racked in.
4.14.5.2 There shall be a mechanical lock to prevent the racking-in of the contactor
when the enclosure door is open.
4.14.5.3 There shall be a mechanical lock to prevent the racking in and out of the
contactor when closed.
4.14.5.4 There shall be provided means to assure that the contactor shall never be
left in an intermediary position when racked in or out.
4.14.5.5 There shall be an electrical lock to prevent the contactor from closing or
remain closed between the test and operation positions.
4.14.5.6 There shall be provided means to avoid the contactor to be inadvertently
extracted beyond the "Test" position.
4.14.5.7 The “Test” position shall allow local and remote test of the starter without
energize the load.
4.14.5.8 There shall be provided means to prevent misoperation of the power and
interlocking devices due to the application of too much force by the
operator.
4.14.5.9 Refer also to interlocks with the grounding switch on item 4.14.21.
Nº. REV.
TECHNICAL SPECIFICATION I-ET-3010.00-5140-741-P4X-002 H
AREA: SHEET:
17 of 42
TITLE:
MEDIUM-VOLTAGE MOTOR CONTROL CENTER AND NP-1
SWITCHGEAR FOR OFFSHORE UNITS ESUP
4.14.10.2 All output contacts shall be sized for the making and breaking capacity
required by the respective load.
4.14.10.3 Auxiliary contactors and auxiliary relays shall be able to work
continuously energised, without economy resistance.
4.14.10.4 Multiplication of trip signals for safety functions and interlocks shall be
done only through approved lockout (86) relays.
4.14.11 Arc Protection
4.14.11.1 All busbar compartments (horizontal and vertical), all outgoing cables
compartments and all compartments with coupling parts of switching
devices shall be provided with arc flash optical sensors connected to “Arc
Monitoring Relay” for protection against short-circuit with electrical
arcs.
4.14.11.2 Arc Monitoring Relay shall consider optical and current signals to
prevent nuisance tripping.
4.14.11.3 The “Arc Monitoring Relay” shall be fitted with solid state output relays
and shall be capable to send trip signal to circuit-breakers in no more than
4ms to isolate the faulty busbar. They shall also have outputs for trip the
related upstream panels circuit-breakers or generators.
4.14.11.4 One lockout relay shall be provided to block all circuit-breakers in busbar
A and tie circuit-breaker in case of arc detection in any functional unit of
busbar A. One lockout relay shall be provided to block all circuit-
breakers in busbar B and tie circuit-breaker in case of arc detection in
any functional unit of busbar B. Lockout relays related to Arc Monitoring
Relays shall send a status signal to the relay associated to the circuit-
breaker where current sensor is connected. For lockout relays, refer to
4.14.9.
4.14.11.5 Arc detection in tie compartments shall trip and block all circuit-breakers
from busbars A and B.
4.14.11.6 Arc detection in MV MCCs incoming functional units shall trip and
block outgoing circuit-breakers of upstream panel. For more details, refer
to project documentation.
4.14.12 Temperature Monitoring System of Power connections
4.14.12.1 For MV CDCs and MCCs, manufacturer shall provide an on-line
Temperature Monitoring System for predictive temperature monitoring
of all busbars connections, all circuit-breaker incoming terminals and all
outgoing bars for cables connection. This monitoring shall be performed
in incoming, tie, busbar connection and outgoing functional units.
4.14.12.2 Detailed design shall supply to Panel Manufacturer a list of all points to
be monitored.
4.14.12.3 The Temperature Monitoring System shall consist of one or more
intelligent relays with integrated HMI and a set of temperature sensors
(associated to each intelligent relay) properly installed and appointed to
internal targets mentioned in 4.14.12.1.
Nº. REV.
TECHNICAL SPECIFICATION I-ET-3010.00-5140-741-P4X-002 H
AREA: SHEET:
22 of 42
TITLE:
MEDIUM-VOLTAGE MOTOR CONTROL CENTER AND NP-1
SWITCHGEAR FOR OFFSHORE UNITS ESUP
4.14.14.3 Analogue instruments scales shall be such that, at full load, the indicator
needle remains between 50% and 75% of the upper limit of the scale.
4.14.14.4 Instruments sizes, deflections, types (analogue or digital), position,
orientation and quantity shall be according to I-ET-3010.00-5140-700-
P4X-005 - REQUIREMENTS FOR HUMAN ENGINEERING
DESIGN FOR ELECTRICAL SYSTEM OF OFFSHORE UNITS.
4.14.14.5 Active energy meters shall have maximum demand indicator for 15
(fifteen) minutes integration time.
4.14.14.6 All analogue measurement instruments shall have the gauge marked in
red on the rated or maximum operational position.
4.14.14.7 Digital measuring devices having capacity for data gathering and data
availability through digital communication port shall be able to indicate
a reverse power up to 15% of the rated power.
4.14.14.8 One Power Quality Monitoring System (PQMS) shall be furnished for
CDCs.
4.14.14.9 The PQMS shall be capable to indicate the busbar THDv, and individual
harmonics components up to 50th harmonic. The PQMS relay shall have
at least one (1) Ethernet network rear output capable to communicate
through network with the Electrical System Automation according to I-
ET-3010.00-5140-797-P4X-001 - ELECTRICAL SYSTEM
AUTOMATION ARCHITECTURE and I-DE-3010.00-5140-797-P4X-
001 - ELECTRICAL SYSTEM AUTOMATION ARCHITECTURE
DIAGRAM for supervision and historical data recording.
4.14.15 CDC/MCC Signalling
4.14.15.1 Incoming and outgoing functional units of CDCs and outgoing
functional units of MCCs shall be provided with signalling leds for
indication of:
Red (R) - circuit-breaker or main contactor closed;
Yellow (Y) - circuit-breaker or contactor opened by protection;
Yellow (Y) - Blown fuse;
Green (G) - circuit-breaker or contactor opened;
White (W) - functional unit extracted;
Blue (B) - functional unit tripped by emergency shut-down.
White (W) – circuit-breaker trip coil circuit fault (when applicable).
4.14.15.2 Tie functional unit of CDCs and incoming and tie functional units of
MCCs shall be provided with signalling leds for indication of:
Red (R) - circuit-breaker or main contactor closed;
Yellow (Y) - circuit-breaker or contactor opened by protection;
Green (G) - circuit-breaker or contactor opened;
White (W) - functional unit extracted;
White (W) – circuit-breaker trip coil circuit fault (when applicable).
Nº. REV.
TECHNICAL SPECIFICATION I-ET-3010.00-5140-741-P4X-002 H
AREA: SHEET:
24 of 42
TITLE:
MEDIUM-VOLTAGE MOTOR CONTROL CENTER AND NP-1
SWITCHGEAR FOR OFFSHORE UNITS ESUP
4.14.15.3 On each heating resistor circuit, for motors and for vertical sections, a
red signalling led shall be provided, which shall be activated when the
heating resistor is turned-on.
4.14.15.4 Two signalling LEDs shall be installed upstream the control voltage
decoupling module to signalize control voltage available downstream
the protection of each control voltage source.
4.14.15.5 Signalling LEDs shall be provided with bayonet type base. The
replacement of LEDs shall be performed without necessity to open the
compartment door and without necessity to extract the switching device.
4.14.16 Remote Commands, Signalling and Measuring
4.14.16.1 The list of remote interface signals that shall be implemented for each
kind of functional unit is described in the I-LI-3010.00-5140-797-P4X-
001 - ELECTRICAL SYSTEM AUTOMATION INTERFACE
SIGNALS LIST.
4.14.16.2 Remote ESD signals shall be through wet contacts (24VDC) and through
auxiliary interposing relays installed in the functional unit. The auxiliary
contacts of the interposing relays shall actuate directly opening contactors
or circuit-breakers. Additional auxiliary contacts shall be used to replicate
the trip signal to the MMR.
4.14.16.3 Auxiliary interposing relays for Remote ESD signals shall have enough
auxiliary contacts in order to, at least, actuate directly opening the circuit-
breaker or main contactor, send the ESD signal to the MMR, provide
signalling and to avoid closing the circuit-breaker or main contactor.
4.14.16.4 Remote ESD signals shall follow the Emergency Shutdown (ESD)
Criteria for Electrical Loads from I-ET-3010.00-5140-700-P4X-001 -
SPECIFICATION FOR ELECTRICAL DESIGN FOR OFFSHORE
UNITS.
4.14.16.5 Hardwired interface signals with A&C and Package Control Panels shall
follow the interface requirements from I-ET-3010.00-5520-888-P4X-001
- AUTOMATION PANELS and I-ET-3010.00-1200-800-P4X-002 -
AUTOMATION, CONTROL AND INSTRUMENTATION ON
PACKAGE UNITS.
4.14.17 CDC/MCC Push Buttons
4.14.17.1 START (turn on) push-buttons shall be with automatic return (return
after push). STOP (turn off) push buttons shall be mushroom type with
release (retain after push) and with possibility to lock by padlock when
activated.
4.14.17.2 They shall be externally operated, with no necessity to open the cubicle
door.
4.14.18 Switches
4.14.18.1 The ammeter and voltmeter selector switches shall be externally
installed.
4.14.18.2 All control switches used at the Panel shall be rotary switches.
Nº. REV.
TECHNICAL SPECIFICATION I-ET-3010.00-5140-741-P4X-002 H
AREA: SHEET:
25 of 42
TITLE:
MEDIUM-VOLTAGE MOTOR CONTROL CENTER AND NP-1
SWITCHGEAR FOR OFFSHORE UNITS ESUP
4.14.22 Capacitors
Capacitors installed inside the Panels may be accepted only if considered as
integrated to the Panel in the type tests certificates presented in the proposal.
4.14.23 Surge Protection Devices
Unless otherwise stated, protection devices against switching surges shall not be
integral part of the Panel’s functional units, but installed at the loads.
4.14.24 Power Transducers
4.14.24.1 Power transducers complying with I-ET-3010.00-5140-700-P4X-002 -
SPECIFICATION FOR ELECTRICAL MATERIAL AND
EQUIPMENT FOR OFFSHORE UNITS.
4.14.24.2 It shall be provided transducers for all outgoing feeders of CDCs for
motor compressors. These transducers shall be hardwired to Package
Control Panels, sending current measurements to be used for overload
control.
4.14.24.3 Galvanic isolators shall be provided for all analog signals from
transducers output.
4.14.25 Voltage detecting and indicating systems
A capacitive three-phase voltage detecting system to confirm both the presence and
absence of main circuit voltage in accordance with IEC 61243-5 shall be provided.
The voltage detectors on each functional unit shall be installed adjacent to the
connection (cable) compartment on all incoming circuits and outgoing feeders, and
on the front of the bus coupler panels for each bus section.
Voltage indicating/detection systems shall be installed in panel front doors and shall
be fitted with measuring test points which permit connection of an external phase
comparator (phasing-out) instrument.
4.15.1 Busbar trunkings, when applied, shall comply with the requirements of I-ET-
3010.00-5140-700-P4X-002 - SPECIFICATION FOR ELECTRICAL MATERIAL
AND EQUIPMENT FOR OFFSHORE UNITS.
4.16.1 Suitable devices mounted on truck shall be supplied to remove circuit-breakers and
contactors for maintenance facility. A minimum of 2 extraction trucks for each
circuit-breaker and contactor frame size shall be supplied.
4.16.2 Circuit-breakers and contactors extraction shall be executed on a safe way, being
the functional unit structure dimensioned to support the circuit-breaker or contactor
weight even when totally extracted.
4.16.3 Circuit-breakers for CDCs shall have capability for local and remote motorized
extraction and insertion, complying with interlocks of item 4.14.7.
4.16.4 Circuit-breakers and contactors for MCCs shall have capability for local and remote
motorized extraction and insertion, complying with interlocks of item 4.14.5.
Nº. REV.
TECHNICAL SPECIFICATION I-ET-3010.00-5140-741-P4X-002 H
AREA: SHEET:
28 of 42
TITLE:
MEDIUM-VOLTAGE MOTOR CONTROL CENTER AND NP-1
SWITCHGEAR FOR OFFSHORE UNITS ESUP
4.17.1 Limiter shall be used as short-circuit current limiting device when required in
PETROBRAS documentation.
4.17.2 Limiter shall be capable to provide fast protection against short-circuit peak
currents higher than the short-circuit withstand of the Panel, limiting the fault
current in the first rise (first quarter-cycle).
4.17.3 Limiter shall consist of a replaceable bursting element in parallel with a high
rupture capacity fuse plus sensors, control and ignition devices.
4.17.4 The bursting element, the fuse and the current sensors shall be part of Limiter
power part, which shall be installed in the Panel to be protected.
4.17.5 Limiter shall be installed in series with tie circuit-breaker of the Panel and with a
no-load switch, in order to isolate the Limiter for maintenance. Withdrawable
Limiter is acceptable as an alternative to the no load switch, since it is not possible
to insert or remove the Limiter with the tie circuit-breaker closed. No-load Switch
in open position shall ground the Limiter power part (grounded position).
4.17.6 It shall be provided signalling for Limiter Position (Extracted or Inserted, in case
of withdrawable Limiter), Limiter Blocking (Limiter Enabled or Limiter Disabled)
and Limiter Actuation (Actuated or Not Actuated).
4.17.7 When the Limiter is withdrawn, shutters shall cover all live parts of the Limiter
cubicle.
4.17.8 The no-load switch rated capacity shall be equal to the rated capacity of the tie
circuit-breaker.
4.17.9 There shall be interlocks in order to permit opening Limiter power part cubicle
door only when the tie circuit-breaker is open and the no-load switch is at grounded
position.
4.17.10 There shall be interlocks between the no-load switch and the tie circuit-breaker, so
that:
It shall be possible to move no-load switch from busbar position to the grounded
position only if tie circuit-breaker is open;
It shall not be possible to close the tie circuit-breaker with the switch at the
grounded position.
4.17.11 The control, measuring and tripping devices shall be
preferably mounted in the low-voltage compartment of the cubicle of the Limiter.
If not feasible, the devices can be mounted in a low-voltage separate steel-sheet
floor-mounted cabinet, to be installed as close as possible to the Limiter cubicle.
4.17.12 The control, measuring and tripping systems shall be electronic and shall have
protection against interference signals. The control boards shall be replaceable.
Arrangement of wiring without open loop and with twisted pair wires immunized
against disturbance like high frequencies. Special designed electronic (filter)
against EMI (embedded inside the impulse transformer).
4.17.13 The control cabinet shall have local indication of tripped phases, UAM (unit alarm
malfunction) and failure of control voltage.
Nº. REV.
TECHNICAL SPECIFICATION I-ET-3010.00-5140-741-P4X-002 H
AREA: SHEET:
29 of 42
TITLE:
MEDIUM-VOLTAGE MOTOR CONTROL CENTER AND NP-1
SWITCHGEAR FOR OFFSHORE UNITS ESUP
4.17.14 The control cabinet shall have dry type contacts for remote indication of UAM and
summary of trip.
4.17.15 The electronic circuitry of the Limiter shall be capable to analyze the instantaneous
current magnitude (i) and the rate of current rise (di/dt) at the first rise, in order to
decide when to send a triggering signal.
4.17.16 After the confirmation of actuation of the Limiter, its control shall send a trip signal
to the tie circuit-breaker, in order to avoid unbalanced connection between the
busbars.
4.17.17 After the confirmation of actuation of the Limiter, its control shall send a triggering
signal to the MMR of tie functional unit in order to initiate an oscillography of
currents and voltages in this event.
4.17.18 Along with the Limiter it shall also be supplied three (3) spare inserts, one (1) test
equipment and three (3) test inserts.
4.17.19 It shall be possible to test the control, measuring and tripping systems.
4.17.20 Limiter control system shall be capable to receive two auxiliary supplies. The main
auxiliary supply for Limiter operation shall be provided by voltage transformers
(included in Limiter devices) connected to the main circuit to be protected. An
external stand-by auxiliary supply shall be provided in 220VDC, provided from
Unit’s battery-chargers.
4.17.21 Tests in Limiter shall be performed by Limiter Manufacturer. The manufacturer
shall perform an Is limiter block test during commissioning. If there is improper
performance of the inserts during commissioning, the manufacturer shall replace
the damaged inserts at no cost to PETROBRAS.
4.17.22 All certificates and tests reports required for the panel shall include the column
where the Limiter is installed.
4.17.23 Limiter control system shall include one discrete input for external inhibition of its
actuation.
4.17.24 Limiter control system shall be capable of communicating in Ethernet Network
according to I-DE-3010.00-5140-797-P4X-001 - ELECTRICAL SYSTEM
AUTOMATION ARCHITECTURE DIAGRAM.
4.17.25 Interface signals to be exchanged shall follow at least the signals listed in I-LI-
3010.00-5140-797-P4X-001 - ELECTRICAL SYSTEM AUTOMATION
INTERFACE SIGNALS LIST.
4.17.26 The manufacturer shall provide procedures and devices for the mechanical
blocking of the Is limiter during the commissioning phase.
4.18.1 The Panels’ nameplates shall be in accordance with IEC 62271-1 and made with
AISI-316L stainless steel.
4.18.2 The Panel shall be outfitted with plate of supplemental identification containing, at
least, the following data:
a) PETRÓLEO BRASILEIRO S.A. - PETROBRAS;
b) name of the department of PETROBRAS;
Nº. REV.
TECHNICAL SPECIFICATION I-ET-3010.00-5140-741-P4X-002 H
AREA: SHEET:
30 of 42
TITLE:
MEDIUM-VOLTAGE MOTOR CONTROL CENTER AND NP-1
SWITCHGEAR FOR OFFSHORE UNITS ESUP
4.18.8 The Panels shall have warning labels following the model below, with the values of
the protective clothing risk category (in field “Nível de Proteção do EPI”) rated
voltage (in field “Tensão Nominal do Painel”), arc-flash hazard distance (in field
“Distância Segura de Aproximação para Atividades Sujeitas a Arco Elétrico”) and
arc fault incident energy (in field “Energia Incidente”). The values to be filled in
will be informed to Panel Manufacturer during Detailed Design.
4.18.9 It shall be provided a specific plate with warnings and instructions for access the
Limiters’ compartment.
4.18.10 Panels shall have warning labels indicating the protective clothing risk category
that shall be used for technical intervention.
4.18.11 Panels shall have warning labels indicating that any technical intervention in the
panels shall be executed only for authorized people.
4.18.12 Panels shall have labels with brief description of the interlocks and
allowed/forbidden momentary parallelisms in Portuguese language. For the
allowed momentary parallelism, there shall be an additional label with details of
the synchronization and load transfer operation. The label shall also include the
document number which details the interlocks and momentary parallelisms.
4.18.13 Panels shall have labels with information about the control voltage supply
characteristics in Portuguese language, including information about control
voltage earthing and expected autonomy of the Unit’s Battery Chargers.
4.18.14 Each functional unit shall have a label indicating the maximum continuous current
capacity of the functional unit, protection functions parameterized and the related
relay parameterization report.
4.18.15 Limiter cubicle shall have a label indicating clearly the blocking criteria
implemented for the Limiter operation.
Nº. REV.
TECHNICAL SPECIFICATION I-ET-3010.00-5140-741-P4X-002 H
AREA: SHEET:
32 of 42
TITLE:
MEDIUM-VOLTAGE MOTOR CONTROL CENTER AND NP-1
SWITCHGEAR FOR OFFSHORE UNITS ESUP
4.18.16 Functional Units with Grounding Switch shall have a label indicating clearly the
interlock and inhibition of circuit-breaker closing.
4.18.17 Incomers Functional Units shall have a label indicating the TAG of the feeder
panel.
4.19 Painting
4.19.1 All electrical materials, equipment and supports shall be painted. Painting process
shall be proper for offshore installations, and shall comply with the requirements of
I-ET-3010.00-1200-956-P4X-002 - GENERAL PAINTING.
4.19.2 The last coat colour shall be Light Green Munsell notation 5G8/4. Inner components
mounting plates, internal faces of doors and safety barriers shall be Safety Orange
Munsell 2.5YR6/14.
4.20 Protection
4.20.1 For general protection, minimum protection functions for each functional unit and
adjustments criteria, refer to I-ET-3010.00-5143-700-P4X-001 – ELECTRICAL
SYSTEM PROTECTION CRITERIA.
4.20.2 Panels shall have one key activated selector switch in their front side with the
positions “Operação / Manutenção” (Operation / Maintenance). When this selector
switch is in “Manutenção” position, the instantaneous overcurrent function (50) of
incoming and tie MMRs shall be activated, overriding protection coordination and
minimizing damage in case of internal fault.
4.20.3 There shall be a local signalling lamp, turned on with the switch in “Manutenção”
position, indicating “Coordenação Desativada”.
4.20.4 There shall be a remote signalling of the position of the switch in Electrical System
Automation Operational Workstation.
4.20.5 It shall be possible to close the functional units circuit-breakers or contactors listed
in this item bypassing all necessary interlocks and protections (such as ESD and
protection function 27) in a dead-ship scenario. The interlocks shall be overridden
by a "OVERRIDE PROTECTIONS" switch installed in the front external part of
each CDC or MCC Functional Unit. There shall be a label in this control switch with
the following text “Atenção! Na posição "OVERRIDE" o sinal externo de ESD e
várias proteções são desativadas. Usar apenas em cenário de dead-ship”. The
following Functional Units shall have this switch:
- MCC outgoings to transformers that feeds Auxiliary and Essential low voltage
CDCs;
- Any other functional unit in order to allow Emergency Loads Battery Chargers
energization.
4.20.6 For the cases described in 4.20.2, there shall be a label beside the switch with
following warning text:
Nº. REV.
TECHNICAL SPECIFICATION I-ET-3010.00-5140-741-P4X-002 H
AREA: SHEET:
33 of 42
TITLE:
MEDIUM-VOLTAGE MOTOR CONTROL CENTER AND NP-1
SWITCHGEAR FOR OFFSHORE UNITS ESUP
4.20.7 For the cases described in 4.20.5, there shall be a label beside the switch with
following warning text:
4.21.1 The Panels and all their components shall comply with the emission and immunity
requirements for electromagnetic compatibility stated in IEC 60533, presenting
performance criterion A.
4.21.2 Regarding induced disturbances, all electronic equipment shall comply with IEC
61000-4-6 class 3.
4.21.3 Regarding surges, all electronic equipment shall comply with IEC 61000-4-5 class
4 with wave forms 1.2/50µs and 10/700µs and peaks up to 4kV.
4.21.4 Regarding oscillatory waves, all electronic equipment shall comply with IEC 61000-
4-12 class 3 and common mode disturbances up to 150 kHz as per IEC 61000-4-16
level 4. Data communications and signal circuits shall be tested only in common
mode, but at the same surge magnitude as specified for transverse mode tests,
according to IEC 61850-3.
4.21.5 Regarding fast transients, all electronic equipment shall comply with IEC 61000-4-
4 class 4, or above. In addition, power supply circuits shall be tested with transverse
mode applied voltages, according to IEC 61850-3.
4.21.6 Regarding electromagnetic disturbances, all electronic equipment shall comply with
IEC 61000-4-3 class 3.
Nº. REV.
TECHNICAL SPECIFICATION I-ET-3010.00-5140-741-P4X-002 H
AREA: SHEET:
34 of 42
TITLE:
MEDIUM-VOLTAGE MOTOR CONTROL CENTER AND NP-1
SWITCHGEAR FOR OFFSHORE UNITS ESUP
4.21.7 Regarding damped oscillatory magnetic, all electronic equipment shall comply with
IEC 61000-4-10 level 5.
4.21.8 Regarding power frequency magnetic field, all electronic equipment shall comply
with IEC 61000-4-8 level 5 for continuous and short duration fields.
4.21.9 All electronic equipment shall operate correctly in the presence of a power
frequency voltage in accordance with table 1 of IEC 61850-3
4.22.1 The control voltage for each Panel shall be in 220VDC achieved from Unit’s
redundant battery-chargers.
4.22.2 The Panels shall have two control busbars, one for loads connected to main busbar
A and other for loads connected to main busbar B.
4.22.3 Each control busbar shall be fed by both control voltage sources (redundant battery
chargers) continuously in parallel.
4.22.4 Decoupling modules, including blocking diodes, shall be foreseen to each control
voltage source in order to avoid back feeding control voltage sources. These
decoupling modules shall monitor continuously the decoupling path. Failure in any
component of the decoupling module shall generate a network signal to A&C,
through Electrical System Automation by Incomers MMRs.
4.22.5 Control incoming circuits from the external power supply shall have surge
protective devices (SPD) with a maximum discharge current of 10 kA in 8/20
microseconds, as required by NFPA 780.
4.22.6 Each control busbar incoming shall be protected by miniature circuit-breakers. The
control busbars shall be connected by miniature circuit-breakers.
4.22.7 Undervoltage at any 220VDC control voltage sources at the panel shall generate a
remote network alarm signal (control voltage failure) to A&C, through Electrical
System Automation by Incomers MMRs. Each Incomer MMR shall detect control
voltage failure from both control voltage sources redundantly.
4.22.8 Functional Units shall not be tripped for lack of control voltage in MMRs
4.22.9 Outgoing Functional Units for motors with protective devices supplied together with
the motor as, for example, bearing over temperature protection shall supply
220VDC to the protective device by using a dedicated circuit breaker installed in
the functional unit.
4.22.10 MCCs connected to Hull Generators shall have a third option for control voltage
supply, by means of transformer, an auxiliary rectifier with incoming rated voltage
in 220VAC and outgoing rated voltage in 220VDC, connected to the terminals of
incoming feeders of the Hull Generators. The auxiliary rectifiers shall be installed
in the MCC (one per generator, included in MCC Manufacturer scope of supply)
and shall have the proper capacity to supply control loads of the MCC. In these
cases, there shall be a switch in order to select the control voltage source from each
Hull Generator (3 positions switch) or from the main control voltage sources (Unit’s
redundant battery chargers).
Nº. REV.
TECHNICAL SPECIFICATION I-ET-3010.00-5140-741-P4X-002 H
AREA: SHEET:
35 of 42
TITLE:
MEDIUM-VOLTAGE MOTOR CONTROL CENTER AND NP-1
SWITCHGEAR FOR OFFSHORE UNITS ESUP
4.23.1 The power supply for heating resistors shall be achieved from 220VAC three phase
external source. The circuits for heating resistors shall be two phases and shall be
balanced among three phases internally.
4.23.2 Each Panel division for transport shall be provided with externally accessible
terminals to energize the heating circuits during storage periods. These terminals
shall have a label with:
4.23.3 The power supply for internal lighting and socket outlets shall be achieved from
220VAC three phase external source. The circuits for internal lighting and socket
outlets shall be two phases and shall be balanced among three phases internally.
4.23.4 The auxiliary circuit branches for internal lighting and internal sockets shall have
miniature thermomagnetic circuit-breakers with integrated or additional differential
residual current protection.
4.23.5 Internal lighting shall turned on by the door opening detection devices. Internal
lighting shall be installed at least in the following compartments:
- Control cubicle;
- Cable compartments;
- Other compartments where PETROBRAS understands that lighting is poor.
4.24.1 Panel shall have internal communication networks among IEDs connecting these
devices to the Electrical System Automation and to A&C (through Electrical System
Automation) for remote control, supervision and monitoring.
4.24.2 Devices connected to the networks shall have the time synchronized. Refer to I-ET-
3010.00-5140-797-P4X-001 - ELECTRICAL SYSTEM AUTOMATION
ARCHITECTURE.
4.24.3 Panel Manufacturer shall propose the internal network architecture in order to
comply with requirements of I-ET-3010.00-5140-797-P4X-001 - ELECTRICAL
SYSTEM AUTOMATION ARCHITECTURE and I-DE-3010.00-5140-797-P4X-
001 - ELECTRICAL SYSTEM AUTOMATION ARCHITECTURE DIAGRAM.
This internal network architecture and configuration shall be submitted to
PETROBRAS approval.
4.24.4 Minimum Interface Signals to be exchanged are listed in I-LI-3010.00-5140-797-
P4X-001 - ELECTRICAL SYSTEM AUTOMATION INTERFACE SIGNALS
LIST.
4.24.5 Switches internal to the panel shall be manageable.
Nº. REV.
TECHNICAL SPECIFICATION I-ET-3010.00-5140-741-P4X-002 H
AREA: SHEET:
36 of 42
TITLE:
MEDIUM-VOLTAGE MOTOR CONTROL CENTER AND NP-1
SWITCHGEAR FOR OFFSHORE UNITS ESUP
5. MANUFACTURER DOCUMENTATION
6.1 Panels shall be packed properly for the foreseen transportation, so that no damage occurs
during transport, storage and lifting operations.
6.2 It shall be considered
6.3 Each volume shall be properly identified with:
a) Storage position;
b) PETROBRAS unit, achievement, and business unit;
c) Delivery address;
Nº. REV.
TECHNICAL SPECIFICATION I-ET-3010.00-5140-741-P4X-002 H
AREA: SHEET:
38 of 42
TITLE:
MEDIUM-VOLTAGE MOTOR CONTROL CENTER AND NP-1
SWITCHGEAR FOR OFFSHORE UNITS ESUP
7.1 General
7.1.1 The Manufacturer or an independent inspection authority accepted by
PETROBRAS shall perform all inspections and tests, in conformity with the
specification documents and applicable rules.
7.1.2 Manufacturer shall be responsible for obtaining all necessary certification related to
the equipment.
7.1.3 Manufacturer shall be responsible for contact the Classification Society, in order to
define the procedures to be followed, related to the submission of documents, and
to carry out the necessary inspections and tests to certificate the Panels.
8. TRAINING
8.1 Manufacturer shall provide training for at least 10 (ten) PETROBRAS personnel, about
Panel system and components.
8.2 Training shall be provided in Brazil, during commissioning period, in Portuguese language.
8.3 Training plan shall include at least control diagram analysis, storage, transportation,
installation, operation, corrective maintenance, preventive maintenance, disassembly,
assembly, extraction and insertion of switching devices, use of tools and accessories,
interface with automation, use of softwares, configuration, parameterization and adjustment
of MMR and IEDs, equipment and devices.
9.1 Manufacturer shall provide the necessary spare parts for the commissioning and pre-
operation periods.
Nº. REV.
TECHNICAL SPECIFICATION I-ET-3010.00-5140-741-P4X-002 H
AREA: SHEET:
41 of 42
TITLE:
MEDIUM-VOLTAGE MOTOR CONTROL CENTER AND NP-1
SWITCHGEAR FOR OFFSHORE UNITS ESUP
9.2 Manufacturer shall provide a list of spare parts for all electrical equipment, for at least 2
(two) years of continuous operation, including prices and part number codes.
9.3 Manufacturer shall provide all unusual tools necessary for maintenance, assembly or
disassembly of the Panel.
9.4 Manufacturer shall guarantee the supply of the same or compatible network components
(MMRs, concentrators, switches, etc.), from the point of view of functionality, mounting
and wiring, during platform lifetime.
For data-Sheet models for medium-voltage MCCs and switchgears, refer to I-LI-3010.00-5140-
700-P4X-001 - ELECTRICAL EQUIPMENT DATA-SHEET MODELS.
12. ANNEX