Wiring Systems and Joints.
Wiring Systems and Joints.
WIRING SYSTEM
System of Supply
There are two systems for tapping off Electric supply from the main, namely,
1. Tree system
2. Distribution system
Tree System
System in which sub-circuits are tapped off from the main circuit at some convenient
place. Nowadays, this system is out of practice as there are many joints for sub-circuits.
Moreover, it is very difficult to find faults. Figure 1 shows the connection of such a
system.
Advantages
1 The length of cables required for the installation of the wiring is less and therefore
the initial cost is also very less.
2 Disadvantages
System is most commonly used nowadays. In this system the main distribution circuits
is brought to one or more distribution boxes from where it is further distributed to
different branch circuits as shown in figure 2.
This system is tapped off from the distribution box without interfering with the other
circuit. Moreover, each circuit is independently tested for finding the faults.
Advantages
Disadvantages
1 In this system more length of cable is required for installation. Therefore, the more
initial cost of erection.
Wiring systems are of many types. The selection of an individual system depends upon
number of factors. When selecting a wiring system following factor must be considered.
1. Initial Cost: The initial cost of the wiring system adopted must be economical to suit
the consumer.
2. Durability: The cable used in the installation of the wiring must be sufficiently sound
so as to bear the changing atmosphere of the surrounding. It should also be in a position
to pass the full-load current of the circuit.
3. Mechanical Protection: The system chosen must provide good mechanical protection
to the cables used in the installation of the wiring.
4. Safety from Fire: This is an important factor and must be considered while selecting
an individual system. The system adopted should be free from risk as far as possible.
5. Appearance after Completion of the Job: The wiring should appear attractive, from
this point of view concealed conduit wiring is best, but its initial cost is very high.
However, C.T.S (Closed Tree System) wiring also looks attractive and has low cost of
installation.
6. Accessibility: It should be easy to extend or repair the wiring.
7. Life: The system adopted should have long life.
1. According to Pakistan Electricity rule 1937, the total lighting load in a sub-circuit
should not be less than 400W. For estimating the load, the following values should be
considered for individual points.
2. According to Pakistan Electricity rule 1937, the maximum power load in a sub-circuit
should, not be more than 2000 W or two Electric points, whichever is less.
3. The current rating of the main switch and distribution box should be calculated
according to the load on the circuit.
4. The cable used in the installation should be kept free from dampness, fire, chemical
fumes and leakage. Therefore, all metal coverings provided for the protection of cables
must be earthed, so that there is no damage due to the leakage of the installation.
5. In domestic wiring, wall socket used must have an earth continuity conductor.
6. All the metal (as the cover of the main switches, pipes, brackets, fans, etc. including the
earth point of the wall socket) in an installation should be earthed
7. No switch or fuse should be installed in the earth continuity conductor. (Because
earthing need easiest path).
It is a temporary wiring used for function and construction work. Wooden and plastic
cleats used for this purpose and distance between the two cleats lies between 4 to 6 feet.
Wooden pieces and steel clips are used for this purpose Distance between two clips will
be 4 to 6 inches. Steel clips is fixed with the help of nail and then lay out the wire on
the wooden piece and then fixed them with steel clips.
Advantages
1. Cheap wiring.
2. Installation is easy.
3. Extension is possible.
4. Easy to locate the fault as the wires are open.
Disadvantages
1. In case of short circuit wood can easily catch the fire.
2. Unsafe from mechanical damages
3. Unsafe from water.
4. Life span is short i.e. about 10 to 15 years.
It consists of two parts lower one is called casing and the upper part for covering is
known as capping. Casing is fixed with the help of rawal plug. Then lay out the wires
and cables in the casing and finally covered with capping.
1. 16x16mm
2. 16x25mm
3. 16x38mm
4. 38x40mm
AIR UNIVERSITY, PAF COMPLEX E-9, ISLAMABAD
9
5. 40x40mm
6. 40x60mm
7. 60x80mm
8. 80x80mm
Advantages
a. Installation is easy.
b. Extension is possible.
c. Material can be reused.
Disadvantages
1. Costly wiring.
2. Difficult to locate the fault as the wires or cables are covered.
3. In case of short circuit casing and capping can catch fire as they are made of
Plastic.
4. Conduit Wiring:
1. Open or External
2. Internal or Concealed
P.V.C (Poly Vinyl Chloride) pipes are used for this type of wiring in which cable passes
from one point to other point for electric supply within P.V.C. pipes. In internal wiring
the pipe is fixed concealed in the roof and wall, while in open wiring the pipes are fixed
on the wall with clips or saddle.
1. L-Bend
2. T-Bend
3. Junction Box
4. Socket
5. Saddle
Advantages
Disadvantages
6. Trunking Wiring
It is used for heavy voltage lines in substation and generation. Iron trunks are used for this
wiring. Trunks available in circular or square shape. Couplers are used for jointing different
lengths which fixed with screw. Trunking wiring is used mostly in developed cities.
Procedure
1. First remove the insulation from ends of both wires and cables up to minimum
length of 8cm.
2. Clean the ends of wires with sand paper.
3. Bend the two wires form 2cm at 90 degree and couple them with each other.
4. Take 4-6 turns for bending.
BRITANNIA JOINT
Procedure
MARRIED JOINT
This type of joint is used to joint the stranded wires or cables as shown in the figure 8.
Procedure
TEE JOINT
This type of joint is used to get the connection from horizontal wire
Procedure
This type of joint is used to get connection from centre of two core cable.
Procedure
Procedure
1. Remove the insulation from ends of both wire up to 5cm and twist them with each
other.
AIR UNIVERSITY, PAF COMPLEX E-9, ISLAMABAD
14
SCARF JOINT
This type of joint use to joint the solid (single) earthing wire from electric supply pole to
ground
Procedure
1. Make the shape of ends of wire as shown in the figure and than overlap them and
use another wire for jointing.
TYPES OF INSULATORS
1. Organic
2. Inorganic
In general, organic insulators such as rubber, paper, oil, cotton, thermoplastic materials,
and so forth composed of long molecular chains of carbon and hydrogen sometimes linked
with other elements (oxygen, chlorine, etc.). Organic insulator deteriorates rapidly when
the temperatures exceed about 150 degree centigrade.
Inorganic insulators, such as mica, porcelain, air, etc, can function indefinitely in
temperature exceeding 10000C.
1 Solid Insulators
2 Liquid Insulators
3 Gaseous Insulators
SOLID INSULATORS
Solid insulators such as wood, rubber, cotton, paper, polymers and some other are used in
electric supply for insulation and protection. Natural rubber, resins, varnishes and bakelite
are all polymers. one type of chemical reaction called polymerization some simple
molecules are linked to form much larger molecules containing thousands of the original
molecules. A new substance formed in the way is said t be polymers Depending on their
composition and molecular structure, polymers can be subdivided into many classes:
polyvinyl, polyurethanes, polyesters, polyamides, polyamide, Dacron and Mylar are
polyesters and Kapton is a polyimide.
Such synthetic materials are uses to insulate the wires in the coils of motors, transformers,
electromagnets, relays, etc, as well as the heavily-insulated wires and cables which
distribute electric power in building. Although we tend to use more and more synthetic
materials, natural insulators are still indispensable in many applications. Cotton is still
widely used in the manufacture of insulating sheets, plates and cables. Paper is still one of
the best materials to cover high voltage conductors. Asbestos, a natural inorganic material,
is employed in the sistant control panels. Mica, a superb insulators, acts as support for the
heating elements in toasters and as a high-temperature, uncrushable insulator in the
commutators of direct current machines.
LIQUID INSULATORS
AIR UNIVERSITY, PAF COMPLEX E-9, ISLAMABAD
16
Mineral oil is used in big power transformer as both an insulator and heat-transferring
agent. It also prevents oxidation of the insulating materials because it completely surrounds
the windings and inhibits the access of air. Oxidation is a particularly important problem in
high-voltage transformers because they tend to produce corona discharges. In The presence
of air, such HV discharges generate ozone, which is a very strong oxidizing agent. By
immersing the winding in oil, we prevent the formation of ozone and, at the same time,
heat dissipated by windings is carried away to the surrounding tank. Because oil is a much
better insulator than air, we can also reduce the size of transformer.
Oil, however has the disadvantage of being flammable and its ignition temperature is only
about 1500C .Some higher-temperature synthetic liquid insulators get around this problem,
but they are more expensive and often cannot be used with other insulators because they
tend to attack them chemically
GASEOUS INSULATORS
Air
One of the best insulators known is the air which surrounds us. Its thermal properties are
better than those of porcelain; it acts as a cooling agent, and costs absolutely nothing.
However at very high temperature, air becomes a good conductor, owing to the
phenimen9n of ionization. For example at 20000C the resistively of air is still as high as
that of porcelain, when its temperature increases to between 50000C and 500000C its
conductivity approaches that of salt water.
Sulfur Hexafluoride
Sulfur Hexafluoride (SF6) is another important insulating gas. Its molecules have the
special ability to absorb free electrons, which accounts for its very high dielectric strength
(10 times greater than air at a pressure of 400kg ) Sulfur hexafluoride is used in high-
voltage circuit breakers and enclosed transmission lines where space reduction is
particularly important.
Hydrogen
Hydrogen is another important insulating gas sometimes used to cool large rotating
machines. Hydrogen has a much lower density and viscosity than air and, consequently,
produces less traction at high rotational speeds. Furthermore, for a given temperature rise,
it absorbs almost 14 times as much heat as air does, Finally m pure hydrogen prevents any
oxidation of the insulating materials and thereby prolongs their life. Hydrogen cooling
systems, however, are very complex and require constant maintenance; their use is only
justified in very large machines.
Form a safety point of view, hydrogen does not explode or burn, even in the presence of an
electric arc, provided that the oxygen content is kept is low 10 percent.
105 0C
130 0C
155 0C
180 0C
H Materials or combination of materials such as silicone elastomer, mica, glass
fiber asbestos, etc, with suitable bonding substances such as appropriate
silicone resins. Other materials or combination of materials may be included
in this class if by experience or accepted tests they can be shown to have
comparable life at 1800C
Above Material consisting entirely of mica, porcelain, glass, quartz, and similar
240 0C inorganic materials. Other material or combinations of material may be
Included in this class if by experience or accepted tests they can be shown
AIR UNIVERSITY, PAF COMPLEX E-9, ISLAMABAD
18
0
To have the required thermal life at temperature above 240 C.
Following type of insulators are commonly used in transmission and distribution line
This is made up of porcelain or glass.
1. D-shackle
2. Pin type
3. Disk type
D-shackle
For low voltage (220,440-600 V)
EXPERIMENT # 1
APPARATUS
Lamp, lamp holder, one way switch, cable(1.5mm2),wire cutter, screw driver,
electric tester and pliers.
PROCEDURE
Connect one terminal of the lamp with one end of the switch. The other terminal of the
lamp holder and switch is connected with the power source, in such a way that cable
connected with the lamp holder connect with the Neutral Terminal of the power source and
the cable connected with the switch connected with the Phase Terminal of the Power
Source. When the Switch is closed the connection made circuit completed and the Lamp
lights up, and when the Switch is opened, connection in switch breaks and the lamp turned
off.
SAFETY PRECATIONS
CIRCUIT DIAGRAM
APPARATUS
Lamp, lamp holder, one way switch, cable(1.5mm2),wire cutter, screw driver,
electric tester and pliers.
PROCEDURE
Connect one terminal of the lamp L1 with one end of the switch. The other terminal of the
lamp holder connects with terminal of the second lamp holder (in series connection).
Connect the second terminal of the lamp L2 with switch S. The other terminal of the lamp
L1 and switch is connected with the power source in such a way that cable connected with
the lamp holder connects with the Neutral terminal N of the power source and the cable
connected with the switch connected with the Phase terminal P of the power source. When
the switch S is closed, the connection makes circuit complete and the lamp lights up, and
when the Switch is open, connection breaks and the lamp turns off.
SAFETY PRECATIONS
CIRCUIT DIAGRAM
APPARATUS
PROCEDURE
Connect One Cable with one terminal of 4 Switches in series and one cable with one end of
two lamps holder and Sockets in series .Connect second end of lamps holder and socket
with switches. Connect the common cable of Switches and lamps and socket with Power
Source in such a way that Cable Connected with switches should connect with Phase and
the Cable connected with lamps and socket connect with Neutral side of Power source.
When the Switch is closed the connection made circuit completed and the Lamp lights up,
and when the Switch is opened, connection in switch breaks and the lamp turned off.
SAFETY PRECATIONS
CIRCUIT DIAGRAM