Part 1 Three Phase Circuits
Part 1 Three Phase Circuits
Three-Phase Circuits
• Zia A. Yamayee, Juan L. Bala. Jr., Electromechanical Energy Devices and Power Systems,1994.
345,000 V
69,000 V 13,200 V
13,200 V 110/
220 V
Production of Three-Phase Power
• If three coils (A, B, & C) are physically displaced by 120 degrees, and a
magnet is rotated in the middle, a three-phase voltage profile is induced.
Balanced Three-Phase Voltages
• If the rotation of the magnet is constant, balanced three-phase voltages are
induced.
Vm
𝑣𝑎 𝑡 = 𝑉𝑚 𝑠𝑖𝑛(𝑤𝑡)
𝑣𝑏 𝑡 = 𝑉𝑚 𝑠𝑖𝑛(𝑤𝑡 − 120)
𝑣𝑐 𝑡 = 𝑉𝑚 𝑠𝑖𝑛(𝑤𝑡 − 240)
Vm
𝑣𝑎 𝑡 = 𝑉𝑚 𝑠𝑖𝑛(𝑤𝑡)
𝑣𝑏 𝑡 = 𝑉𝑚 𝑠𝑖𝑛(𝑤𝑡 − 120)
𝑣𝑐 𝑡 = 𝑉𝑚 𝑠𝑖𝑛(𝑤𝑡 − 240)
𝑉𝐶 𝑉𝐵
𝑉𝐴 𝑉𝐴
𝑉𝐵 𝑉𝐶
abc sequence acb sequence
(positive sequence) (negative sequence)
Phase Sequence – An Example
• Assume that the phase voltage 𝑉𝑎 = 120 + 𝑗0 𝑉. What would be the voltages of
𝑉𝑎𝑏 , 𝑉𝑏𝑐 , and 𝑉𝑐𝑎 if the sequence is:
a) positive (abc)
b) negative (acb)
Wye and Delta Connections
• Looking back at the stator windings figure, we see two ends for each coil:
Note: In Y connection, the phase current and line current are equal.
Wye (Y) Connection – An Example
Assume that the phase voltage = 120𝑉. What would be the line voltages
assuming positive sequence?
𝑉𝑎𝑛 = 120∠0 𝑉𝑏𝑛 = 120∠ − 120 𝑉𝑐𝑛 = 120∠ − 240
Delta (Δ) Connection
Let us determine the relationships between the line and phase currents:
𝐼𝑎 = 𝐼𝑎𝑏 − 𝐼𝑐𝑎
𝐼𝑎 = 𝐼∠0 − 𝐼∠ − 240
𝐼𝑎 = 𝐼(1 − 1 ∠ − 240)
𝐼𝑎 = 𝐼( 3∠ − 30)
Therefore:
𝐼𝑎 = 𝐼𝑎𝑏 × 3∠ − 30
Note: In Δ connection, the phase voltage and line voltage are equal.
Load Configuration
• Loads may also be connected using Y or Δ configurations:
𝑍𝑌 𝑍𝑌
𝑍Δ 𝑍Δ
𝑍𝑌 𝑍Δ
• We can make the two loads behave identically for an outside observer by setting the following:
𝑍Δ
𝑍𝑌 =
3
Balanced Three-Phase Systems
• For a 3-phase system to be balanced, the following conditions must be met:
1) All 3 sources are balanced.
2) All loads are 3-phase with equal impedance
3) Line impedance are equal in all 3 phases.
Ia 𝑍𝑌 = 4 + 𝑗3 Ω 𝑍Δ = 12 − 𝑗9 Ω
a
Van = 120 v
b b c b
c c
Balanced Three-Phase Systems – An Example
A Y-connected 3-phase source with phase voltage magnitude of 120 V is connected to a Y-
connected and Δ connected balanced loads as shown in the figure. Compute the labeled current.
Ia 𝑍𝑌 = 4 + 𝑗3 Ω 𝑍Δ = 4 − 𝑗3 Ω
a
Van = 120 v
b b c b
c c
Power Calculations
Let's calculate the total power absorbed by a balanced 3-phase Y connected load.
where 𝜃 is the angle between the phase voltage (𝜃𝑣 ) and the
phase current (𝜃𝑖 ).
𝜽 = 𝜽𝒗 − 𝜽𝒊
Solution
(i)
Power Calculations – An Example
(ii)
(iii)
Solution
(iv)
(i)
(v)
Power Calculations – Y Connected Loads
Recall that for balanced Y-connected loads, the following 𝐼𝐿
relations for the voltage and current magnitudes apply:
+ +
𝑉𝐿 = 3𝑉𝜃 𝐼𝜃 𝑍𝑎 𝑉𝜃
𝑉𝐿 −
𝐼𝐿 = 𝐼𝜃
−
Therefore, the total power can be computed as follows:
Similarly:
𝑉𝐿
𝐼𝐿 = 3𝐼𝜃 𝐼𝜃
−
Therefore, the total power can be computed as follows:
𝑍𝑏
𝑃3𝜙 = 3𝑉𝜃 𝐼𝜙 cos(𝜃) 𝑃3𝜙 = 3𝑉𝐿 𝐼𝐿 cos(𝜃)
Similarly:
𝐼𝑙
+ +
𝐼𝑝 𝑍𝑎 𝑉𝑎𝑛
𝑉𝑎𝑏 −
n
−
Power Calculations – An Example
𝐼𝑙
+ +
𝐼𝑝 𝑍𝑎 𝑉𝑎𝑛
Solution 𝑉𝑎𝑏 −
n
−
Power Calculations – An Example
𝐼𝑙
+ +
𝐼𝑝 𝑍𝑎 𝑉𝑎𝑛
Solution 𝑉𝑎𝑏 −
n
−
𝑉𝑙 = 173.2𝑉
𝐼𝑙 = 14.14A
𝜃 = 45°
Apparent and Complex Power
Apparent Power (VA) Complex Power (VA)
ST = S1 + S 2 + S3 ST = S1 + S 2 + S3
ST = 3 S ph ST = 3 S ph
ST = 3V ph I *ph
ST = 3V ph I ph
or
or
ST = PT + jQT
ST = 3VLL I L
The Power Factor
The power factor is the ratio of the real power to the apparent power.
𝑃
𝑝𝑓 =
𝑆
However, power system components are typically rated by the apparent power.
Recall: 𝜃 = 𝜃𝑣 − 𝜃𝑖 .
Angles of phase values not line values.
The Power Factor
Load types have different effects on the AC voltage and current signals, and hence, the classification of
the power factor.
Loads, in general, may not be pure and contain a mix of resistive, inductive, and capacitive loads.
Power Calculations – An Example
Power Calculations – An Example
Solution
900
𝑃3𝜙 = 3𝑉𝐿 𝐼𝐿 𝑐𝑜𝑠(𝜃𝑣 − 𝜃𝑖 ) ⇒ 𝐼𝐿 = = 3.12 𝐴
3(208)(0.8)
𝑉𝜃 𝑉𝐿 / 3
𝑍𝑌 = = = 38.49 Ω
𝐼𝜃 𝐼𝐿
Sine the power factor is leading, 𝜃 < 0.
IL / 3
Power Calculations – An Example
Compute the following for the shown systems:
(a) the magnitude of the line current, (b) the magnitude of the load’s line and phase voltages, (c)
the real, reactive, and apparent power consumed by the load, (d) the load power factor, (e) the real,
reactive, and apparent powers consumed by the TL, (f) the powers supplied by the generator, and
(g) the generator power factor.
Power Calculations – An Example
Compute the following for the shown systems:
(a) the magnitude of the line current, (b) the magnitude of the load’s line and phase voltages, (c)
the real, reactive, and apparent power consumed by the load, (d) the load power factor, (e) the real,
reactive, and apparent powers consumed by the TL, (f) the powers supplied by the generator, and
(g) the generator power factor.
Power Calculations – An Example
A 208-V 3-phase power system is shown below. Calculate:
(a) the magnitude of the line current, (b) the magnitude of the load’s line and phase voltages, (c)
the real, reactive, and apparent power consumed by the load, (d) the load power factor, (e) the real,
reactive, and apparent powers consumed by the TL, (f) the powers supplied by the generator, and
(g) the generator power factor.
Power Calculations – An Example
A 208-V 3-phase power system is shown below. Calculate:
(a) the magnitude of the line current, (b) the magnitude of the load’s line and phase voltages, (c)
the real, reactive, and apparent power consumed by the load, (d) the load power factor, (e) the real,
reactive, and apparent powers consumed by the TL, (f) the powers supplied by the generator, and
(g) the generator power factor.
One-Line Diagrams
One-Line Diagrams – An Example
The figure below shows a one-line diagram of a small 480-V industrial distribution system. The power
system supplies a constant line voltage of 480V, and the impedance of the distribution lines is
negligible. Find:
(a) The power factor of the combined load.
(b) The total line current supplied to the distribution system.
Three-Phase Power Measurement
Suppose we want to measure the total power delivered to a three-phase load.
One way is to connect three Wattmeters (one for each phase). The total power would be the
summation of the three Wattmeter readings.
In turns out that we can compute the total power using only two Wattmeters.
Credit: P.C. SEN. Figure B.10(a) from the course book. Credit: P.C. SEN. Figure B.10(a) from the course book.
𝑍෨ = 8 + 𝑗6 Ω