QUALITY CONTROL Document No.

17a/1347
FINISHED GOODS Issue No. 678
3 PHASE Issued Date 8 /4 /2021

Revision

PROCEDURES: Check in conformity with approved drawings , IEC 61439-2


JOB NO. : P-RM-3594-05-2020 PANEL REF. : MCC-P03-P2
CLIENT NAME : SAUDI TECHNICAL LIMITED / STL ITEM No. : 8
PROJECT NAME : SABB NEW HEADQUARTER - RIYADH INSPECTION REF. :
DRAWING No. : TYPE :
Enclosure Type Checklist STATUS
A. ASPECT AND PRESENTATION OK
B. LAYOUT OK
C. SERVICE SPECIFICATIONS
Volt : 400/230 Phase: 3ph, Wires: _ Hz: 60 Temp: 50C
,
D. CONFORMITY OF COMPONENTS
1. Enclosures
Dimensions: - H: 2200 mm W: 1850 mm D: 1050 mm No of Sections : _1
Degree of Protection IP : 55 , Enclosure Type: blockset : : , ,
2. Control & Protection Units
Main Breaker ( 1 ) Rating 100 A. 3P. Sub/ Main Breaker ( 2 ) Rating :32A. 3P.
Mfg. & Type :Schneider nsx Mfg./Type : Schneider .nsx
Sub/Main Breaker ( 3 ) Rating 32 A . 3 P. Sub/Main Breaker ( 4 ) Rating : 18 A. 3 P.
Mfg. & Type: Schneider ,nsx Mfg. & Type Schneider .nsx
Branch Breakers ( See Drawing ) OK
Control Relays ( Types ) schneider OK
Protection Relays ( Types ) schneider OK
Fixation of Components OK
Panel main label/Component’s Labeling / Inside – Outside OK
3. Metering Digital
3.1 Ammeter Calibration and CT Test OK
Mfg. & Type: , , CT Rating: , Ammeter Range: , Ammeter Selector Switch Pos.:
Current Injected
Phase CT Ratio Calculated Current Scaled (Amps) Meter Reading (Amps) Remarks
Primary Secondary
R 100/5 100 5 5 100 Ok
Y 100/5 100 5 2.5 50 ok
B 100/5 100 5 1.25 25 ok
3.2 Volt. Meter Calibration
Mfg. & Type: ISKRA , MC 330 , Range: , Voltmeter Select. Switch Pos.:
Phase Applied Voltage Meter Reading Volt Remarks
L1-N 230 230
L2-N 230 230
L3-N 230 230
L1-L2 400 400
L2-L3 400 400
L3-L1 400 400
4. Main Busbars
Size :50 X 5 mm (L1. L2. L3) No. Of Busbars: 2
Neutral : 50 X 5 mm No. Of Busbars.2 , Earth: 50 X 5 mm No. Of Busbars: 1
Material: Tin Plated Copper / Insulated Copper / Bare Copper
: ISC: 85 ( 1S )
: Space Between Supports ( Max.) : mm
: Conformity of Components to panel ISC. ok
: Tightness of Connections Bolts ok
( RFPB-QC-01 ) Page 1 of 2
QUALITY CONTROL Document No. RFPB-QC-01
FINISHED GOODS Issue No. 02
3 PHASE Issued Date 05/06/2015
Revision 01

5 Mechanical Check of Breakers (Opening & Closing) ok


6 Main C.B. Incoming Cables : Size 25 mm2 Terminal Pads : lugs ok
6.1 Branch C.B. Outgoing Cables ( Provided with Terminal Pads for Oversize cables ) Ok
6.2 Power Cable Busbar Marking ( Black, Red, Yellow, Blue ) ( Blue, Black, Red, Brown ) Ok
Control Wiring
Size : Current Circuit : 2.5 mm2, Volt Circuit : 1.5 mm2 Ok
Control Cable Marking : ( Circuit Numbers ) Ok
Neutral Circuit : Distributed / Not distributed / TNS / TNC Ok
7 Earth Circuit Continuity Ok
8 Cable Entry / Bus Duct / Cable Duct
- Incoming : Top / Bottom Top
- Outgoing : Top / Bottom Top
9 Cable Connection Access
- Incoming : Front / Rear / Side Front /rear
- Outgoing : Front / Rear / Side Front/rear
10 Interlocking – In comers / Feeders / Bus Couplers feeders
Type : Mech. / Elect. / Key ( See Panel Drawing for Details )
11 Auto Changeover Facility : ( Yes / No ) yes
12 Insulation Resistance Test ( Megger Test ) and Dielectric Test
500V / 1 min Connection 1 KVDC/1min, Ω 2.0 KV/1min, mA
1000V / 1 min L1, L2, L3 - E 219 GΩ Passed
5000V / 1 min. L1, L2, L3 - N 324 GΩ Passed
N-E 258 GΩ Passed
L1 - L2 117 GΩ Passed
L2 - L3 92 GΩ Passed
L3 - L1 123 GΩ Passed
13 Functional Test ( In Accordance with the Drawings )
A. Mechanical Operation Test Ok
B. Phase Continuity Test Ok
C. Phase Sequence Test Ok
D. Electrical Operation Test ok
14 Supplied Loose Items
15 Comments
16 Equipment Type Used for Testing
RFPB-TE-12 Megger: HIOKI 3453, RFPB-TE-1 Dielectric Test: SEFELEC Premier 2725, RFPB-TE-16 Multi Voltage Test Unit

RFPB-TE-19 Current Injector : PTE-100-C, RFPB-TE-9 Digital Multimeter M5097, RFPB TE-13 Digital Clamp Meter FLUKE 337

A.M ADNAN HANI GHONEAMI E.EHAB

Tested by QC Inspector QC/QA Manager Client Date


(RFPB-QC-01) Page 2 of 2