The matrix Zabc represents the impedance series and mutual
coupling of a three phase conductor. ZM12 represents the
impedance between the phase L1 and the phase L2. ZL1
Fig. 1: a) Single conductors in trefoil
represents the impedance of the phase L1. This impedance can
b) Single conductors in parallel
be described in the symmetrical component with the
transformation of the matrix with the matrix A. If the mutual coupling is not neglected as in equation (6),
1 1 1 then equation (7) proves that a positive sequence current will
A 1 a2 a 2 create a zero sequence voltage. This coupling is represented in
Fig. 2 by M01.
1 a a2
U0 I0
with the symbol a; a phase angle of 120°. 012
U1 Z I1 7
j2
a e 3 3 U2 I2
The impedance matrix of the symmetrical components is Fig. 2 illustrates that even in sound operation a zero
calculated with equation (4): sequence voltage can be measured only because a perfectly
balanced load current is supplied.
012 1 abc
Z A Z A 4
Fig. 5: Network builds with a loop of two and four feeders where the field
measurements have been recorded.
Fig. 7: On some recordings, circulating currents are higher than the fault
current for the four feeders loop. Fault occurs on J03 and J07.
active current on each feeder and if this current is too high, the
feeder is considered as faulty. Such relays could not work
when circulating currents are measured on the loop.
Because these currents depend on the load power, the
amplitude and phase of this current is supposed to be stable
during the faulty process. Estimating this current during the
pre fault state and filtering it for the faulty state with active or
non linear filter could allow a correct detection of the fault.
Another method could be to consider the loop as a single
feeder by summing the current of each feeder. This sum will
eliminate the circulating current part of the signal and keep
Fig. 9: Influence of the load power on the zero sequence circulating current in only the faulty information.
case of loop of two and four feeders.
VI. ACKNOWLEDGMENT
Simulations have proved the link between the positive The authors gratefully acknowledge the help and support of
sequence system and the zero sequence system due to M. Kereit from Siemens AG during the research project.
unbalanced serial impedance in loop. This current can have a Gratitude is also expressed to Pfalzwerke Netzgesellschaft
big impact on protection because this current does not have the GmbH for their field tests in compensated network.
expected behavior for a proper detection of the faulty feeder.
In case of high impedance fault it can be observed that the zero VII. REFERENCES
sequence current caused by the fault is smaller than the zero [1] H. Y. Li, P. A. Crossley, and N. Jenkins, "Transient Directional
sequence circulating current. Protection for Distribution Feeders with Embedded Generations," in
However, this circulating current is probably stable during 14th PSCC, 2002, pp. 24-28
[2] S. Repo, A. Nikander, H. Laaksonen, and P. Järventausta, "A Method to
the whole fault because the load is not disturbed by a single
Increase the Integration Capacity of Distributed Generation on Weak
phase earth fault in such network. The phase to phase voltage Distribution Networks," in 17th International Conference on Electricity
does not vary in case of single phase to earth fault. This Distribution, 2003, no.60, pp. 12-15
current is then stable if the consideration that the load is [3] B. Li, X. Yu, Z. Bo, and S. Member, “Protection schemes for closed
loop distribution network with distributed generator,” in 1st
constant during the time window for the earth fault detection. International Conference on Sustainable Power Generation and
Estimating the phase angle and the amplitude of this current Supply, 2009, no. 8, pp. 1-6, Apr. 2009.
during the pre fault state could allow filtering this component [4] G. Celli, F. Pilo, G. Pisano, R. Cicoria, and a Iaria, “Meshed vs. radial
MV distribution network in presence of large amount of DG,” in IEEE
without filtering the 50Hz component produced by the fault at PES Power Systems Conference and Exposition, 2004., pp. 1357-1362.
least for the first 100 millisecond after the fault inception. [5] G. Druml, R.-W. Klein, and O.Seifert, "New adaptive algorithm for
Active filter and non linear filter could be solution. detecting low- and high ohmic faults in meshed networks," in 20th
International Conference on Electricity Distribution, 2009, no. 631, pp.
Another solution is to consider the loop as a single feeder. 1-5
The sum of the current of each feeder from one loop makes the [6] L. B. Perera, "Directional Earth Fault Relay operation in Mutually
circulating current equals to zero. The effect of this current is Coupled Multiple Circuit Distribution Lines," in 20th Australasian
not measured anymore and the detection of an earth fault can Universities Power Engineering Conference (AUPEC), Christchurch,
New Zealand, 2010.
be done as usual. This solution could have the disadvantage to [7] M. F. Abdel-fattah and M. Lehtonen, “A New Transient Impedance-
not detecting the faulty part of the loop anymore. As a Based Algorithm for Earth Fault Detection in Medium Voltage
consequence a fault would be cleared unselective. Networks,” in International Conference on Power Systems Transients
(IPST), Kyoto, Japan, 2009.
[8] G. Druml, A. Kugi, and B. Parr, "Control of Petersen Coils", presented
V. CONCLUSIONS at XI International Symposium on Theoretical Electrical Engineering,
Linz, Austria, 2001.
This paper presents a problematic of the more and more [9] G. Druml, A. Kugi, and O. Seifert, “New Method to Control Petersen
common closed loop structure in distribution network. The Coils by Injection of Two Frequencies,” in 18th International
position of the cables and overhead lines can create unbalance Conference on Electricity Distribution, 2005.
in the matrix impedance. This unbalanced system has a mutual
coupling between the positive sequence and the zero sequence VIII. BIOGRAPHIES
system which could be neglected in radial structure. A zero
sequence voltage is induced on both feeder and if they are Matthieu Loos was born in Arlon in Belgium, on
July 15, 1987. He studied Electrical Engineering at
connected at both ends, a circulating current will flow in the
the Free University of Brussels (ULB), Belgium and
loop. Multi loops structures are also studied and show that the graduated with his Diploma in 2010.
circulating current can be even bigger in this case due to He is currently working as a PhD student in the
mutual coupling between the zero sequence systems. Electrical Engineering Department (BEAMS) since
2010. His main topic is earth fault detection and
This circulating current can negatively influence state of the location in compensated and isolated distribution
art protection devices because it creates randomly active or network.
reactive current measurement. Some devices are measuring the His working experience is as an intern in the
7