Training Module CONTROL SYSTEMS &operational Procedures
Training Module CONTROL SYSTEMS &operational Procedures
1. THE SEQUENCER
Programmable Logic Controller (PLC) has been installed to control the machine run up and shut down This
is mounted in the Old Automatic control panel (machine control suite-MCS). Once start up or shut down
commands are given the sequencer step through the sequence as described in the machine start up and
shut down sequences. The sequencer is interfaced to other plant items as shown in below
The sequencer will monitor the status of various plant items through the inputs and drive various plant items
through the outputs - see notes on PLC basics
Unit
Exciter
ACB Board
C/O(Q7)
Auxiliaries
Sequencer • MCW valve(Q15)
Master Trip • Stator heaters(Q8)
(86)(Q9) • Governor oil
pump(Q10)
• HP jacking oil
pump(
BH BA • Brakes( Q35/Q36)
(Q2) (Q1) • S/by GOP alarm
Control
(Q34)
Room
The major steps in the run up and shut down of a unit are as outline in the flow charts below and
summarised as follows
Run Up
1- Pre-start checks conditions which have to be satisfied before machine can be run. Once satisfied the
sequencer will go to the status – ready to start
2- Auxiliaries start up. When the start sequence commences the fist stage is to start up the auxiliaries
listed. Once all auxiliaries are started succsesfully the sequencer will proceed to turbine run up
3- Turbine run up- start with the release of the guide vane lock. Energisation of the valve BA the turbine
governor start. the turbine governor will step through its own turbine start up sequence until the unit is up
to speed
4- Excitation- once the machine is @90 % speed Excitation can start. The first stage of excitation is closure
of field breaker followed by switch on of the Excitation, filed flashing i.e. the rotor is energised from
common services via a rectifier cct so as to build up voltage enough for the exciter to sustain self
excitation whilst excitation is building up the unit bard supplies will change over @ ~87% and @ 90@
Shut down
1. Unloading of unit – shedding of MW & MVArs Necessary to allow smooth shut down load pick up by
other units & extend ACB life When load <5MW& MVArs < 5Kvar the ACB will be opened
2. De-excitation- switch off of the Excitation as Volts decrease the unit board supplies will change over
3. Turbine shut down.- Governor shut down and the guide vanes will close, the BA valve de energises &
the BH de energises allowing the lock to engage
4. @ 40% speed the HP jacking oil pump starts to improve lubrication of the thrust bearing & @ 25%
brakes will apply brake dust extractor fans starts heaters come on CW valve closes GOP pump stops
5. unit the sequencer goes to the turbine at rest status and eventually back to ready to start
The unit runs up and start up is summarised diagrammatically by the flow charts and graph below
Pre-Start Conditions
Ready to Start
Start Order
Auxiliaries On
Guide vane lock released
Unit Excite 4
U/B change er @ 87%V
Unit @ 95 % Volts
Unit @ SNL 5
Ready to Synch
Order to synchronise
Stop Order 1
Float MW , MVR 2
Open ACB
Unit @SNL 3
Reset Auto
Synch
Stop Order 4
Governor Stop
Unit De Excite Ready To
synch
Unit @ 40 % Speed
Brakes Apply
Speed @ <8%
Turbine @ reset 7
Ready To Start 9
A display unit (DU) mounted on the MCS door indicate the stage at which the sequence is and also shows
the Status of the inputs contacts from field devises and the state of the out put relays
The sequencer output relays have red flags, which drop when the relay is energised and reset, if relay is de-
energised. The relays are labelled RL01, RL02… with RL01 driven by out put Q01 and RL2 by output Q02
and so on.
Turbine At rest : Machine speed less than 8% but condition prior to start not
Satisfied
Unit at rests Available for Start: Machine speed less than 8% and conditions prior to start
Satisfied
Unit Start up In Progress Machine start up sequence initiated until all auxiliaries start up
Unit Start up TO Speed no load Machine start up sequence initiate d& all auxiliaries started
Stays on until machine speed and volts > 90%
Unit at Speed NO load Machine speed Volts > 90%
Guide vanes fail to close : Comes up if guide vanes do not close within 12secs from the turbine stop
signal
Brakes fail to operate: comes up if machine speed does not drop below 8% within 2 minutes from
The time a brake application pulse is sent
Fail to start : Generated by the auxiliaries start timer( 2mins after start pulse) or speed no
load timer(5mins from start of Seed no Load Sequence)
Exciter trip to manual- Trip of Excitation from Auto to manual
Brake interlock failure Not Programmed
Urgent excitation trouble : Loss of excitation trip supplies
If the sequencer does not complete the shut down sequence due to the above alarms being sustained (i.e.
Hangs up with DU reading Unit stop in progress) clear alarms before start up by resetting the excitation
alarms as necessary and then pressing the reset push button below the PLC. The display unit will display
UNIT AT REST AVAILABLE FOR START
Exercises
Operational Procedures
Question 1 Describe in your own words what checks you would make as
a Leading Turbine Driver when first coming on shift.
What importance would you attach to the previous shifts’ log book and log
sheets?
Question 2 Describe the action you would take on receipt of the following Alarms with
the machine on load.
Question 3 Describe your actions as a Leading Turbine Driver the Operations and
checks that you would do to:
Question 5 Where and what is the Emergency Drain Pump – how is it supplied and are
there any monitoring circuits to check availability of Emergency Drain Pump.
What tests are done on this pump, at what frequency? Describe the test in
your own words, itemising readings and precautions to be taken during the
test.
Question 6 What provides power in the event of all Machines being off the bars at
Kariba South?
How many sources of Electricity Supply can be obtained in the above
circumstances and where?
Are there any Routine Tests carried out to check Validity of Emergency
Supplies both A.C. and D.C.
Control systems
1. Describe the machine start up sequence in detail
2. What are the most common causes of sequencer hang ups and how are they cleared
3. DeScribe the logic in the main sequencer control blocks
4. Auxiliaries start-up
5. Automatic start-up
6. Manual shut down
7. What happens if there is a speed signal fail alarm
8. If the sequencer looses power supplies what will happen(describe in detail)
9. What are the main causes of failure to start and how are they cleared
10. If on shut down the governor fails to De-load what is the most likely cause and what action can
be taken
M/c JB
MCS-1 MC MC MC MC MC
S-2 S-3 S-4 S-5 S-6
Why Automation:
• Interfacing different control systems (from different suppliers) to one common supervisory
control system
• Enhance reliability
Software
Governor
• primary control of the turbine
• start-up and shut down sequencing
• load control
• speed control
• Supervision and alarm signalling
Exciter
• primary control of machine voltage /MVArs/Power factor
• start-up and shut down sequencing
• Voltage control
• MVAR control
• Power factor control
• Power system stabilisation
• Supervision and alarm signalling
Sequencer
• Co ordinates start up and shut down of unit
• Accept commands from Operator
• Gives commands for
• Auxiliary start-up
• Turbine start-up
• Excitation start up
• Unit shutdown
• Auto synchroniser activation
• Supervise start-up/shutdown sequence and generate alarm signals
Station computer
• AGC functions
IMS station
• reports ,
• trends,
• time tagged event/alarms lists list
Analogue inputs collect analogue data from the field and convert to computer format
ADC converts the analogue signal to digital bits 0 or 5v(0-or1) format suitable for computerised processing
Processor read the digital bits from the ADC and uses the information
+5V
Processor
Opto-coupler
+5v
Typical digital input can use relays, transistors, opto-cuoplers, thyristor ,triac etc
Analogue inputs collect analogue data from the field and convert to computer format
DAC converts the Digital signal to digital bits 0 or 5v(0 or1) to an analogue signal
Processor 5v
Solenoid v/v for e.g.
Digital outputs are normally volt free contacts used in the control circuits of unit control systems or
auxiliaries
18 kV 18 kV
Old Control Desk. Excitation
Switchgear protection
Control Suite
Panel
1 2 3 4 5 6 7
16