14.01.2024 Test Report MFO 180 HS MT Cendrawasih - 094612
14.01.2024 Test Report MFO 180 HS MT Cendrawasih - 094612
Test Report
No. TR-003 /PND941000/STS-AR/II /2024
Limitation
Parameter Test Method Units Results
Min Max
0
Visc. Kin. at 50 C ASTM D445 mm2/dt - 180 126
0 3
Density at 15 C ASTM D1298 kg/m - 991 947
Sulphur Content ASTM D2622 % m/m - 4,5 2,07
0
Pour Point ASTM D97 C - 30 3
0
Flash Point ASTM D93 C 60 - 125
Sedimen Conten ASTMD 473 % m/m - 0,1 0,05
Water Content ASTM D95 % v/v - 1,000,10
Note : -
Ref :
- SK Dirjen Migas No. 14496K/14/DJM/2008 tanggal 21 Agustus 2008 tentang Standar dan Mutu (Spesifikasi) Bahan
Bakar Minyak Jenis Minyak Bakar yang Dipasarkan di Dalam Negeri.
- This Sample was received form the customer and only as reported for the sample.
Distribution :
1. Integrated Terminal Balikpapan
2. Arsip
3. Customer
Balikpapan, 14 Januari 2024
Pjs. Spv. Quality & Quantity
Febri Rudiyanto