Hap Ehelp 032
Hap Ehelp 032
Figure 1. Diagram of Heat Recovery Plant with Air-Cooled Chillers with Heat Recovery Condensers
(Note: This is a simplified diagram only intended to show the basic arrangement of components)
System Overview
Basics of Equipment Configuration and Operation
Figure 1 contains a simple diagram of a heat recovery plant using air-cooled chillers with heat recovery condensers:
• The upper half of the diagram shows a hot water plant with two hot water boilers in parallel and a primary/secondary
water loop providing hot water to heating coils in air handlers or fan coil units. Note that there can be different types of
of heat recovery systems. Some will supply heat to a service hot water (SHW) system instead of or in addition to
serving space heating loads.
Figure 4. Figure 5.
• Specify the condenser water flow rate, the required flow delta-T or flow per unit capacity for heat recovery
mode (see 5). This will depend on the system design.
• Specify the minimum entering condenser water temperature for heat recovery mode (see 6).
• On the Performance tab specify the chiller performance map for air-cooled condenser (heat rejection)
operation (Figure 6) and water-cooled condenser (heat recovery) operation (Figure 7). If off-design and part-
load performance data is available from the manufacturer, it should be entered here. Because this data is
sometimes not available, a common practice is to use the default maps supplied by HAP, which are
automatically adjusted based on your full load capacity and full load input power specifications on the Design
Tab.
• Make sure the data in the performance maps spans the range of entering condenser temperature conditions
expected for this building.
Air-Cooled Heat Rejection Mode: Suppose the chiller is expected to operate during times of year when the
outdoor air dry-bulb temperature is between 95 F (35 C) and 40 F (4.4 C). Therefore the air-cooled
performance map (Figure 6) must have rows which span at least this range of outdoor air temperatures. If
operating conditions fall outside the range of conditions specified in the map, HAP uses the closest data in the
map, but this introduces error. The most accurate results will be obtained when the performance map spans
the expected range of operating conditions.
Water-Cooled Heat Recovery Mode: Suppose the entering water temperature for the heat recovery
condenser is expected to range between 100 F (37.8 C) and 120 F (43.3 C). Therefore the water-cooled
performance map (Figure 6) must have rows that span at least this range of conditions. As explained for the
air-cooled map above, if operating conditions fall outside the range defined, HAP uses the closest data in the
map. For example, if the entering condenser temperature rises to 120 F and the map only contains data to
110 F, HAP will use data from the 110 F row since that is the closest available. This will underestimate chiller
energy use operating at 120 F entering water temperature and therefore introduce error in the results.
• After data on all the tabs has been entered, save the chiller.
Figure 6. Figure 7.
3. If necessary, create and save the boilers for the heat recovery plant. In many applications the same boiler
equipment is used for both conventional and heat recovery plants. This is because common practice is to size
the boilers to meet the full heating plant demand in the heat recovery plant as if no heat recovery is available. If
this is the case, then the boilers entered previously for the conventional plant can be reused in the heat recovery
plant. No additional boiler inputs are required.
Figure 7. Figure 8.
Figure 14.
Step 4g – Source Water Tab
For a heat recovery plant using air-cooled chillers with heat recovery condensers, the Source Water tab is
disabled as it is not relevant. In other types of heat recovery systems this tab defines performance of condenser
water and in some cases heat recovery pumps.
1. Lack of Heat Recovery Savings – The most common questions arising from heat recovery energy simulations
are “Why didn’t heat recovery provide any savings?” or “Why are the heat recovery savings so small?”. In many
cases the answer is the building lacks heat recovery potential because of the small number of hours with
simultaneous cooling and heating loads.
Figure 3, shown earlier, contains an example of a building which is not a good candidate for heat recovery.
Cooling (blue) is predominant in summer. Heating (red) is predominant in winter. There are very few hours
where simultaneous cooling and heating demands occur. This example is for an office building in a cool climate.
The building uses floor-by-floor VAV AHUs with an outdoor air economizer. The economizer provides partial free
cooling when the outdoor air dry-bulb (OADB) is between 55 F (12.8 C) and 75 F (23.9 C), and provides full free
cooling when the OADB is less than 55 F. While an outdoor air economizer is a useful device for reducing cooling
energy use, and may be required by prescriptive codes, it reduces heat recovery potential because it reduces the
number of hours when simultaneous cooling and heating loads exist.
Figure 2, shown earlier, shows an example of a building which is a good candidate for heat recovery. Again
cooling coil loads are shown in blue and heating coil loads are shown in red. This is a hotel building in a warm
climate. It uses 4-pipe fan coils to cool and heat guest rooms, with a dedicated outdoor air system (DOAS) for
ventilation, and it has significant service hot water (SHW) loads throughout the year. These characteristics result
in cooling loads for much of the year and persistent heating plant demands all year long. As a result there are
many hours throughout the year with simultaneous cooling and heating demands where heat recovery can
operate.
You can assess the heat recovery potential of your building using HAP as follows:
a. Create the conventional chiller plant and hot water plant using standard HAP procedures.
b. Run the plant simulations for these two plants.
c. For the chiller plant request a graph of hourly simulation results for January 1 thru December 31. Choose the
“Plant Cooling Load” item as the data to be graphed (Figure 15). This will plot the total hourly cooling load
imposed on the plant for the full year.
d. For the hot water plant request a graph of hourly simulation results for January 1 thru December 31. choose
the “Boiler Output” item as the data to graphed (Figure 16). This will plot the total hourly heating load
imposed on the plant, including space heating and SHW loads.
e. Place the graphs side by side to visually evaluate whether simultaneous cooling and heating demands exist
during the year.
2. Plant Cooling Control – Sequenced or Equal Unloading – As noted in Step 4d of the Tutorial, it is usually
beneficial to use “sequenced” control for the air-cooled chillers and to place the chiller with heat recovery
condenser in the lead (CH-1) position in the equipment schedule. Because CH-1 is the first on and last off, the
plant will be able to delivered recovered heat to the heating system any hour when cooling and heating demands
exist simultaneously. Using sequenced control will tend to maximize loading of CH-1, particularly at off-design
and lower part-load conditions. This increases the chiller heat rejection and provides greater heat rejection
potential.