Model 8600 GenPurp Rev 2
Model 8600 GenPurp Rev 2
General
Purpose
TECTRON METAL DETECTION
INSTALLATION & OPERATION MANUAL
GENERAL
· All standard safety procedures should be observed when working on electrically powered
equipment.
· Proper care should be taken when connecting or disconnecting the power source.
· When connected to a power source, un-insulated, dangerous voltage is present within the Detector's
electronics enclosure which may constitute a risk of electric shock.
· Do not allow moisture to collect in the electronics enclosure or near the power connections. Always
close the enclosure and secure the locking mechanism after working with the electronics.
· The user should not attempt to service the Detector. All servicing should be referred to certified
service personnel qualified to work on electrical equipment.
INSTALLATION
· Do not install this Detector near heat sources such as radiators or air ducts.
· Place the Detector in a location with adequate air circulation to prevent internal heat buildup.
CONNECTIONS
· As standard, this Detector is set for connection to 115 VAC. If specifically requested, the Detector
can be set for 220 VAC. The Detector must be connected only as supplied.
· The power cable should be routed so that it is not likely to be walked on or pinched by items placed
upon or against it, paying particular attention to the point where it exists from the Detector.
i
GENERAL INFORMATION
Tectron detectors are custom fabricated to suit each user's particular application. Each detector system is
subjected to extensive testing both at the sub-assembly level and after final assembly to ensure compliance
with performance and electrical safety standards.
Within the warranty period, the product will be repaired or replaced at Tectron's option, free of charge;
shipping costs will be paid by Tectron. Except as mentioned above, no other warranty, expressed or implied,
applies. If Modules are not covered by warranty as mentioned above, Dealer/User will be billed for the repair
and shipping. Non warranty repairs, Dealer/User must issue a PO # or Credit Card # prior to any repair.
Installation Assistance
Tectron detectors have been designed for installation by qualified personnel with detailed instructions
provided with each shipment. When required, a Tectron Field Engineer will supervise or check the
installation, activate the system and provide training on periodic adjustments and care of the Detector for user
maintenance personnel. Please contact Tectron for Field Service rates.
Technical/Application Assistance
Tectron welcomes your inquiries concerning metal detectors and their application, installation and servicing.
If technical or application assistance is needed, contact:
TECTRON ENGINEERING
Contact Information:
ii
1
Chapter
Description
1.1 General
T
he Model 8600 provides protection to downstream processing equipment by detecting the
presence of potentially damaging metal objects. It is specifically designed for use on
conveyor systems carrying materials which contain consolidated or fractured magnetic or
nonmagnetic ore, as well as ores ranging in electrical conductivity. The Detector will
discriminate between these conveyed materials and tramp metal of any type: ferrous, nonferrous,
magnetic or nonmagnetic.
The Detector makes use of the latest in solid state technology. The design includes a number of
innovative features: self-test circuits that monitor the performance of the detection circuitry using
light emitting diodes (L.E.D.'s) which indicate the status of the test circuits; wide programming
capability to custom tailor the Detector to suit specific application requirements; and solid state
relays to provide reliable arc-free switching.
Having detected metal by a waveform change, the signal generated is amplified and filtered. The
signal is then compared to a threshold determined by the size of metal that must be detected. When
the signal exceeds this threshold, the Detector, at the appropriate time, triggers solid state relays.
These solid state relays in turn switch the line voltage to the Detector's output alarm terminals.
1
1.2 (continued)
Various combinations of alarm horns, belt stop relays, alarm beacons, etc., can then be activated by
the switched alarm outputs.
The Detector is influenced only by change. Therefore, stationary structural members, metal belt
cords, symmetrical idlers and other objects which do not represent a moving mass to the field are not
detected. Metal belt repair clips are passed by the unit with an optional clip detector sensor and
inhibitor circuit which is properly adjusted to the clip signal.
Visible and accessible on the front panel are: Power On/Off Switch, Green Power "On" Indicator
Lamp, Red Trip Indicator Lamp that lights when the unit has detected metal and a Reset Button. See
Figure 1.
2
108-018
PAR TS LIST
ITM QTY DESCRIPTION
OFF ON RE SET
4
3
16 .75 16 .25
(45 1) (41 3)
JO M ODEL
SCALE DAT E PRO JECT T IT LE
DRAW N
FRONT PANEL LAYOUT
APPR
N.E.M .A. 4, 4X
REV
Figure 1
M ATERI AL DWG NO
REV DATE 108 -018
1.3.2 Electronic/ Interface Modules
All the electronics and controls for the Detector are contained in two modules, the Interface Module
and the Electronic Module shown in Figure 2. The Electronic Module houses the electronic circuitry
and components associated with metal signal processing and analysis. Visible on the front panel of
the Electronic Module are the “Metal Sensitivity” control knob, “Clip Override” control knob and
L.E.D. status indicators used to monitor the status of the Detector's self-test circuits. By removing the
front cover of the module, all of the electronics are exposed for calibration and troubleshooting. All
connections for the Electronic Module are made through a 36-pin connector located along the bottom
edge of the modules.
The Interface Module interconnects all external signals and power to the Electronic Module. This
module houses the power transformer; solid state relays and interface circuit board. Visible on the
face of the Interface Module are system fuses and two terminal blocks for external wiring; all are
clearly identified.
The right terminal block, a 13-pin, 3/8" center screw type, connects the Detector's external
transducers and signals. The left terminal block, a 7-pin, 7/16" center screw type, is used for all
connections handling the A.C. line voltage.
4
ELECTRONIC MODULE Figure 2
Size: 10.5” x 8” x 1.5”
Weight: 2.5 Lbs.
S Power Supply 6
5 4
3
7
T
2
2
Metal Signal
A
1
9
T
0
10
3
N Self-Test
D
6
I Self-Test
C 6
5 4
7
A Clip Timer
3
7
8
2
T
8
1
9
O Timed Output 10
0
R Clip Override
9
S Direct Output
Serial Number:
INTERFACE MODULE
Size: 11” x 2.5” x 4”
Weight: 4.75Lbs.
SERIAL No.
HOT
INPUT POWER ALARM OUTPUTS
LINE: 115 (220) VAC 5 AMP MAX REMOTE SYNC SWING CLIP RECEIVER
FUSE
10 AMP 50/60 Hz TIMED DIRECT RESET LINE AWAY DETECT OR TRANSMIT TER (COM.)
PWR NEUT GND OUT NEUT OUT NEUT IN 0v SIG SW 0v 9-12v SIG (+) (- ) SHLD (+) SHLD (-)
1 AMP YEL SHLD YEL SHLD
GRN BLK WHT BLK WHT WHT BLK WHT WHT BLK RE D WHT BLK BLK
FUSE
1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 11 12 13
10 AMP
TB 2 TB 1
5
1.3.3 Search Coil Assembly
The Search Coil Assembly includes receiver and transmitter antennas, mounting frame and
interconnecting cables. Each assembly is custom designed to suit its particular application.
Please refer to the Frame Assembly Diagram, Figure 4.
Receiver Coil
The receiver coil is typically located under the conveyed material within 2” of the loaded
conveyor belt.
Transmitter Coil
The transmitter coil is located opposite and parallel to the receiver coil. The distance
between the transmitter and receiver (aperture) is typically 4” greater than the maximum
burden depth of the processed material.
Mounting Frame
The mounting frame supports the antennas on trough and slider bed conveyors. Special
designs are available to accommodate other types of material handling systems. The swing-
away assembly, shown in Figure 3, protects the transmitter from oversized conveyed
materials.
Interconnecting Cables
Shielded cables connect the receiver and transmitter to the Main Control Enclosure. 25’ of
cable between the frame assembly and control unit is supplied as standard. Optimum
performance is assured with cable lengths of 25’ or under. However, lengths of up to 100’
are acceptable where detector sensitivity requirements are minimal.
6
Figure 4
Swing-Away Frame Assembly
7
2
Chapter
Installation
PLEASE READ THROUGH COMPLETELY BEFORE BEGINNING WORK!
2.1 Unpacking
U pon receipt of the crate(s) containing the Metal Detector System, inspect the contents for
physical damage and missing parts. If anything is broken or missing, please contact the
carrier and notify the supplier immediately.
2.2.1 Choose a location for the detector so the material handling system has ample time to
react to tramp metal. Locate the detector far enough in advance of the head pulley so the belt
can come to a stop before the metal falls off the end of the belt. If a diverter is used, consider
the reaction time of the system and speed of the conveyor belt.
2.2.2 Select a site with minimum vibration. High vibration areas may degrade detector
sensitivity and shorten component life.
2.2.3 Locate the Search Coil Assembly away from sources of airborne electrical interference
emitted from variable-speed drives, large motors, ballasts, FM radios, induction furnaces and
other radio frequency (RF) sources. Because RF energy travels along a straight line (line-of-
sight), position the receiver coil or relocate RF sources so they are out of the direct line-of-
sight with the top and bottom of the receiver coil. Cables carrying high voltage or varying
loads must be enclosed in steel conduit, grounded at both ends and located at least 4' from the
detector antennas.
8
2.2.4 Position the entire search coil assembly so that the bottom of the coil (usually the
receiver) is equally spaced between the two adjacent idler rollers. Center the receiver coil. Do
not center the 2” x 2” uprights.
Figure 5
48
24 24
2.2.5 The magnetic field generated by the transmitter coil induces eddy currents in nearby
metal cross bracing, stairways, handrails and pipes. These eddy currents may cause false
tripping if the current path intermittently makes contact. Eddy current loops can be broken by
cutting the conductive paths in these structures. Use non-metallic hardware as required to
restore structural support. If conveyor idlers are used in your application, the idlers adjacent to
the Search Coil Assembly may require modification or isolation to break eddy current loops.
Refer to the Conveyor Idler Modification Diagram for details.
2.2.6 If the Search Coil Assembly is located where a metal skirt passes through the coils, it
must be replaced with a five-foot section of non-metallic material (i.e., wood or plastic).
2.2.7 Remove metallic decking, skirt boards, cross bracing and return idlers below and
within 3' of the center line of the receiver coil (upstream and downstream). Relocate or tightly
secure moving or vibrating pieces of metal such as cables, conduit and piping within 36" of
the Search Coil Assembly.
9
Figure 6
Isolation Kit
8 --- 4 x 4 x .25
(101.6mm x 101.6mm x 6.36mm)
FRP Flat Plate 16 ---OD 1(25.4mm) x ID 5/8 (15.89mm) Flat Washers
Isolation Kit contains 8 4”x4” FRP plates, 16 1” dia flat washers, 16 5/8” nuts and 1 48” long 5/8”
threaded rod. Note: When isolation kit ordered by its self the threaded rod may be precut into 4
pieces to aid in packaging. Iso Kits supplied with unit orders do not have the threaded rod pre cut.
10
110-002
PARTS LIST
DETECTOR AN TENNAS
ITM QTY DESCR IPTI ON
11
1
3
INSTALLATION INSTRUCTIONS
4
1. Remove the adjacent idler on either side of the detector installation location.
2. Position 4 isolation pads under idler feet (two on each side) so they are
centered on the idler foot hole, drill a holes into the four isolation plates. It
may be necessary to enlarge the holes in the idler feet and conveyor frame
to accept the 5/8" threaded rod.
3. Cut the threaded rod into 8, 6" long sections.
4. Re-mount the idlers onto the frame so that the isolation plates are in between
the idlers mounting foot and the conveyor frame. Secure the idlers with the EXISTING CONVEYOR
FRAME
threaded studs, washers, and nuts. When completed, the idler will be
electrically isolated from the conveyor frame.
NOTE:
Use caution not to excessively torque the nuts onto the thr eaded fiberglass studs. JO M ODEL
1. NO METAL DECKING, CROSSBRACING, OR RETURN IDLERS BELOW OR DRAWN Jules 06 /1 3/20 07 IDLER MODIFICATION DETAILS
BETWEEN IDLERS ADJACENT TO RECEIVER ANTENNA. APPR
2.3.1 Assemble the top crossbar to the vertical upright supports using four 3/8" x 1" bolts
with washers (provided). Be sure the crossbar is located on the upstream side of the upright
supports and the base of the metal mounting feet angles point in toward the belt.
2.3.2 Assemble the top transmitter coil (with swing-away brackets attached) to the upright
supports. The height of the transmitter coil should be as low as possible without being hit by
overburden. The nominal height for the transmitter coil is indicated by dimension "S" on the
Frame Assembly Diagram. Use two 31/2" bolts with washers (provided). Each of the two
bolts contains four flat washers and two nuts. Make sure two washers are located between the
swing-away bracket and upright support to insure proper spacing and freedom of movement.
The remaining washers are located at the end of each bolt. Hand tighten each bolt with a nut
until light drag is exerted on the swing-away bracket. Tighten the second nut against the first
nut to serve as a jam nut. Verify that the swing-away brackets are free to move.
CAUTION: If the swing-away assembly is not free to move, damage to the transmitter coil
may result if hit by overburden.
2.3.3 Position the upright assembly onto the conveyor frame with the arrow on the
transmitter coil pointing in the direction of belt flow.
2.3.4 Assemble the receiver coil (mounting brackets attached) to the upright supports using
four 3/8" x 31/2" bolts with washers (provided). Position the height of the receiver to allow
for 1” distance between the bottom of the belt and the top of the receiver antenna at maximum
belt load. Bolt the brackets into place with the nuts and washers facing in toward the belt.
2.3.5 Verify that the search coil assembly is square and all bolts installed are properly
tightened.
2.3.6 Position the entire search coil assembly so the bottom receiver coil is equally spaced
from the idler rollers on either side.
2.3.7 Weld or bolt the metal support feet to the conveyor frame. Be sure unwanted twists and
torques in the frame assembly are corrected before you weld. A twist in the frame may cause
the swing-away bracket to pull away from the upright support. This may cause the transmitter
coil to bounce from vibration while in operation.
12
2.4 Mounting – Main Control Enclosure
After installing the Search Coil Assembly, select a place to mount the Main Control Enclosure
for ease of operation. Avoid high vibration areas. Note the length of interconnecting cables
and the location of the connectors on the coil. Locate the Control Enclosure on the same side
of the conveyor frame as the connectors for ease in routing the cables.
2.4.1 The Enclosure should be positioned so the front panel hinge is on the left side and the
indicators are on top.
2.4.2 Fabricate and install a sun/rain shade for added protection over the Enclosure if it is
mounted outdoors. Do not obstruct the natural airflow around the Enclosure.
2.4.3 Familiarize yourself with the type of electrical connections required for this installation
and any safety precautions before proceeding. Please refer to the Control Connection Diagram
for information about connections and color code hook-up.
2.4.4 Use an electrician's conduit punch or drill to make either 1/2" or 3/4" conduit entries on
the bottom of the Enclosure. The Control Connection Diagram shows where to position each
entry. Remember to remove all metal shavings when you are finished. Use caution to not
damage the electronics and to ensure that no metal particles enter the electronics. Do not run
metal conduit along the sides or near the Search Coil Assembly.
2.4.5 Transmitter and receiver cables should be routed in conduit. Do not run any power
wiring in the same conduit or near the transmitter and receiver cables.
2.4.6 All line voltage connections terminate at TB2. Install line voltage cables between
devices controlled by the Detector including diverters, auxiliary relays, marking devices,
alarm horns or motor control equipment and TB2 in the Main Control Enclosure. The direct or
timed outputs should not be connected to a Programmable Logic Controller (PLC) or other
low voltage computer interface equipment that may require dry contact closures. The direct
and timed output contacts are typically programmed as normally "OFF" at the Factory. They
may be set to normally "ON" if required. Refer to the System Programming Section for
details.
2.4.7 Connect a 115/220 VAC (50/60 Hz), single phase power line with at least 10 amp
capacity to TB2. Make sure to connect an electrical ground to terminal #3. The power should
be the "cleanest" available and free of significant voltage variations or spikes. Do not connect
the Detector to a line which is used for operation of motors or motor controls. Proceed with
the Start-Up & Calibration Section before applying power.
CAUTION: The Interface Module is preset at the Factory for 115 or 220 volt (±10%),
50/60 Hz, single phase operation. If the voltage source is different, contact the Factory for
instructions to select the proper voltage source.
13
2.5 Swing-Away Switch (if applicable)
The Swing-Away Cutout Switch (Optional) is a pre-wired switch mounted on the swing-away
bracket. Its purpose is to prevent the Metal Detector from tripping when the transmitter coil is hit
by an overburden of material. Route the free end of this cable in the same conduit as the transmitter
cable to the Main Control Enclosure. Refer to Appendix A Control Connection Diagram for
hookup.
2.6.1 Refer to Control Connection Diagram (Appendix A) and Figure 9 for positioning. If
there are idlers adjacent to the search coils, position the Clip Detector Sensor approximately
1" to 3" upstream of the nearest upstream idler before the Search Coil Assembly. For slider
bed type conveyors, position the Clip Detector Sensor approximately (but no closer than) 2’
from the center line of the receiver coil on the upstream side of the Search Coil Assembly.
The flat face of the Clip Detector should be facing toward the belt with approximately ½” to
1” of clearance. This clearance must be maintained in order to assure proper operation.
The Clip Detector should be a few inches from the edge of the belt. Do not mount the Sensor
too far from the edge, as tramp metal lying close to the belt may trigger the sensor and pass
through the search coils as a repair splice.
14
Figure 9
2.6.2 With the Clip Detector Sensor in the proper position below the belt, weld the 3/4"
support pipe (provided) to the conveyor frame. The pipe may be cut to the proper size for an
easier fit. The multi-axis swivel joint will provide adequate movement for proper adjustment.
2.6.3 It is recommended that the Clip Detector cable running to the Main Control Enclosure
be installed in conduit. The same conduit that houses the transmitter coil cable may be used.
2.6.4 Feed the Clip Detector cable into the conduit from the Clip Detector end to the Main
Control Enclosure.
2.6.5 Cut off excess cable. Connect wires to terminal block (TB1) using the supplied spade
lugs. Refer to the Control Connection Diagram for color code hook-up. Be certain all wires
are attached securely and connected to their proper terminals.
2.6.6 When metal repair clips are used, two or more clips close together must pass directly
over the Clip Detector Sensor in order to activate it, refer to Figure 11. If a small patch of
repair clips are used on the belt, which would not pass directly over the Clip Detector,
reference clips are required. Reference clips are made by installing two or more clips which
will pass directly over the Clip Detector to trip it when a small patch passes by. Numerous
repair and reference clips on the belt will degrade the Detector's performance because it will
frequently be in a desensitized mode.
15
Figure 11
Conveyor Belt
Leading edge
of repair clips
16
2.7 Marking Device (if applicable)
The Marking Device is a pressurized, solenoid activated liquid spray system which pinpoints the
location of tramp metal to eliminate costly search and down time.
2.7.1 Specifications
Tank Pressure Rating: 50 psig (maximum working pressure)
Tank Capacity: 2.5 Gallons (liquid)
Operational Voltage: 115/220 VAC (50/60 Hz), 15 Watts
Air: Plant air or any source of 100 to 200 psig inert gas
Figure 12
112-002
VE RTICA L POSITION IN G
BR AC KET
TAN K LID HAN D LE
HORIZONTAL SUPPORT
1 inch SOLID FRP 3 /8 IN C H N PS
PLAN T A IR SUP PLY 8 0 PS I
H OSE CON N ECTOR
NOTE 3 STR AIGHT FITTIN G
1 /4 IN C H NP T (TH RE AD)
N OTE 1
H ORIZONTA L POSITIONIN G
BR AC KET
FILL CAP
3 /8 IN C H TO 1/4 IN CH NPS
R EDU C ER WITH ELB OW
FITTIN G
JO MODEL
SCALE DATE PROJECT TITLE
L OCATE D OWN STRE AM OF
D ETEC TOR RE F: FR AME AS SY D WG DRAWN JULES MARKI NG DEVICE AND
1/5/2009
APPR DYE RESERVOI R
MATERIAL DWG NO
UNLESS OTHERWISE NOTED REV
H
NOTES UNLESS OTHERWISE SPECIFIED ALL DIMENSIONS ARE IN INCHES REV D ATE
6/4/2009 112-002
17
2.7.2 Installation Instructions
2.7.2.1 Refer to the Frame Assembly Drawing for layout of the Marking Device on the belt
Figure 13.
2.7.2.2 Position the solenoid support upright and cross arm as shown. Distance from the coils
should be 3' to 6'. Clamp in place temporarily.
2.7.2.3 Position the support bracket of the solenoid spray valve so that the nozzle is pointed
directly on the center of the conveyor belt. The nozzle may be positioned as shown or on the
opposite side of the arm. Bolt the bottom of the support frame to the conveyor frame.
2.7.2.4 The solenoid control cable is connected to the Interface Module Timed Output
(Terminal TB2, Pins 4 & 5). Route the cable accordingly.
2.7.2.5 Connect the hose between the tank outlet and the solenoid valve.
2.7.2.6 Connect the facility air source to the tank regulator inlet. Be sure the facility air
source is shut off and no pressure is in the tank.
2.7.2.8 The spray solution is supplied by the User. The recommended mixture is five (5)
fluid ounces of colorant, Chrome Yellow (or other contrasting color) manufactured by
Tenneco Chemical (or equivalent) mixed with a two (2) gallon solution of water and
antifreeze appropriate for local climate conditions (minimum of 25% antifreeze). DO NOT
USE PAINT. Paint will clog the spray valve.
2.7.2.9 Mix the solution and pour it into the holding tank. Replace the cap.
2.7.2.10 Verify that the pressure regulator valve is closed prior to turning on the facility air.
2.7.2.11 Apply the facility air and adjust the pressure regulator between 60 and 100 psig, as
noted on the pressure gauge on top of the holding tank.
18
119-001
R H
AD JU STABL E H EIGHT RE CEIV ER
1 -1/2 i n. INC RE MEN TS S
R ECE IV ER AN TEN NA
S
1 x 1 3 x (W- 5) W
(4 ) BOLT, 1/4 - 2 0 X 2 C.S.
(4 ) NU T, 1 /4 - 20
(4 ) WASH ER , FL AT, 1/4 i n.
(4 ) WASH ER , FEN D ER, 1 /4 in .
R
19
(2 )MOU NTING FOOT
A 9
2 i n. RT AN GL E CAR BON STL
(6 ) BOLT, 3/8 - 1 6 X 3 C.S.
(2 ) BOLT, 3/8 - 1 6 X 3 .5 C .S .
(8 ) NU T, 3 /8 - 16 C.S.
(8 ) WASH ER , FL AT, 3/8 i n. C.S.
A/2
12
MARKING DEVICE
DYE RESERVOIR
REF DWG 112-002 BEL T LE FT HA ND S HO WN
(IF APPLICABLE) DIR ECTION RIGHT HAND OPP OSI TE
ELECTRONICS
ENCLOSURE
16 H X 14 X 6.D
A ND C ON TR OLLER S.
1 .A LL OW AT LEA ST 6FT(2 M) DISTA NC E BETWE EN D ETEC TOR POWE R AN D SIGN AL L INES ,P LA NT CON DU IT, SCALE DATE PROJECT TITLE
C ABL E AN D PIPIN G R U NS. DRAWN FRAME ASSY, MODEL 50 & 8600
Ju le s 6/12/07
APPR STD SWI NG AWAY
MATERIA L UNLESS OTHERWISE NOTED REV DWG NO
ALL DIMENSIONS ARE IN INCHES
REV DATE 119-001
NOTES UNLESS OTHERWISE SPECIFIED
2.7.3 Calibration of Marking Device
2.7.3.1 Refer to Section 4.5 and 4.6 to set the desired timing for marking a predetermined
location.
2.7.3.2 Using a sample piece of tramp metal, with the belt operating at normal load, adjust
the Marking Device timing by trial and error.
2.8.1 Specifications
Plastic NEMA 4X box which holds the electronics and flag
One set of 3 flags
Operational Voltage: 115/220 VAC (50/60 Hz), 15 Watts
2.8.2.1 Refer to the Figures 14 for mounting and Figure 15 for positioning of the Flag Marking
Device.
2.8.2.2 Attach the upright support to the upright. Position the frame upright in front of the first
down stream idler roller. Lay the upright support on the top of the C channel and adjust the upright
so that it is straight up and down. Clamp in place now drill the a hole in the side of the C channel
to secure the bottom of the upright and drill a couple of holes through the upright support and top
of C channel and secure the support to the conveyor C channel.
2.8.2.3 Attach the frame cross bar with gusset to the upright.
2.8.2.4 Mount the NEMA box to the cross bar. Position the box on the cross bar so that the flag
will drop on the product where the edge of the product touches the belt, (if the product comes to the
edge of the belt then position the box so the flag is far enough in so that the flag does not fall off of
the belt).
2.8.2.5 Route the power cord across the cross bar and down the upright, secure cord with ty-raps.
Make connections to the Metal Detector electronics Ref Appendix A Figure A12.
20
9
EN CL OSU RE
N EMA 4 X
4
Mounting of the flag drop marker
21
8
U PRIGH T S UP PORT
INSTALLATION:
1. Attach the Upright Support 8 to Upright 4 .
2. Place Upright and Support on conveyor frame.
3. Adjust Upright so it is vertical. Allow the Support
to pivot so it is laying flat on top of the conveyor frame.
4. Temporarily clap the Support to the conveyor frame.
5. Us the holes in the Upright and Support as drill hole templates.
Drill holes in the conveyor frame and using supplied bolts, washer and nuts
Figure 14
20"
Flag Drop Marker
2.8.3.1 Refer to Section 4.5 and 4.6 to set the desired timing for marking a predetermined
location.
2.8.3.2 Using a sample piece of tramp metal, with the belt operating at normal load, adjust
the Marking Device timing by trial and error.
22
3
Chapter
B efore turning on the system, locate the switches and lights on the door panel and the
controls inside the cabinet.
3.1.1 The power switch is located on the lower left-hand corner of the door panel. Place it
on the “ON” position. The green “ON” indicator should light at this time.
3.1.2 If the green “ON” does not come on, return the power switch to the “OFF” position and
inspect the light bulb and fuses; also check the power and wiring for proper connections.
3.1.3 Approximately 5 seconds after power "ON", the No. 1 status indicator (power supply)
located on the front panel of the Electronic Module will light (reference Figure 2). This
indicates that the power supply is fully operational and all the electronics are enabled.
3.1.4 If the power supply L.E.D. status indicator or the "ON" indicator does not light, refer to
Chapter 5, Troubleshooting Flow Diagram #1 for instructions. Until the power supply L.E.D.
is lit, calibration of the unit cannot begin.
23
3.2.1 Set the “Metal Sensitivity” control knob, located on the front panel of the Electronic
Module, to the middle of the dial (reading of 5).
3.2.2 The Detector discriminates between interference and a signal given off by tramp metal.
The tramp metal must enter the sensing coil at the direction and speed of normal belt flow,
before the Detector will alarm. However, the "Metal Signal", L.E.D. No. 2, will light anytime
moving metal is in the sensing field. When calibrating the system, be careful not to introduce
extraneous metal into the field in the form of rings, belt buckles, keys, steel-toed shoes, etc.
When calibrating the system, it is best to set the metal to be detected on a cardboard box (with
no staples) at the appropriate height and pass at the speed and direction of belt flow.
3.2.3 Pass the larger sample piece of metal between the coils at the height of the average
burden and at a speed comparable to belt travel. If the Detector does not trip on the sample,
turn the "Metal Sensitivity" control knob to a higher sensitivity (in direction of ascending
numbers), so the Detector will trip just as the metal is passed above the coils.
In the event that the unit doesn't trip with the "Metal Sensitivity" control knob on 10, check to
see if the metal signal L.E.D. No. 2 lights as the metal is passed through the field. If the
L.E.D. does not light as the tramp metal is passed through the field, additional sensitivity may
be required. In this case, please refer to Section 4.2. If the L.E.D. does light and the unit won’t
trip, refer to Troubleshooting Flow Diagram #1
3.2.4 Pass the smaller sample piece of metal between the coils in the same manner as the
larger piece. The unit should not trip when the small piece of metal passes between the coils.
If the unit does trip, adjust the “Metal Sensitivity” control knob until it does not trip on the
metal.
3.2.5 Repeat step 3.2.3 and 3.2.4 until the system accepts the larger piece of metal and
rejects the smaller. When the final setting is determined, note the number on the control knob
for future reference. If this number is greater than 8, increase the gain of the Detector as
described in section 4.2 and repeat steps 3.2.3 and 3.2.4.
3.3.2 Observe the reference clips to see if they are passing within 1" of the Clip Sensor Head
when the belt is empty. Adjust the Clip Detector if it is not within this distance making sure
that the clips or the belt do not hit the Clip Detector Sensor Head when the belt is fully loaded.
If the clip is located properly, the Clip Timer, status indicator No. 7, located on the Electronic
Module will light for approximately 1 second each time the clips pass over the Clip Detector
Head. NOTE: If the Clip Detector is spaced more than 1” from the passing clips, erratic
performance may occur.
24
3.3.3 If the Detector is tripping on the clips with a "Clip Override" setting of 10, refer to
Section 4.3, Clip Gain.
3.3.4 Gradually turn the clip control knob counterclockwise to a lower setting until the unit
trips on the largest set of repair clips on the belt.
3.3.5 Turn the clip control knob clockwise one number higher as a safety factor.
NOTE: This setting should be periodically checked to compensate for shifting of the conveyor
belt. Turn the control knob to a “0” setting if the clip detector is not used.
3.4 Operation
The Detector may be programmed to operate in a manual or an automatic reset mode; the standard
mode of operation is manual reset.
The Detector may be converted to an "Automatic Reset Mode". In this mode the Detector will
momentarily signal when tripped then self-reset according to the placement of the
programming switches. For complete programming instructions, refer to Section 4.8.
Provisions have been made to externally reset the Detector from a remote location. Wire a
normally open set of contacts across the remote reset terminals TB1 pins 1 & 2 located on the
Interface Module. Upon closure of the contacts, the unit will reset.
25
3.5 Excessive Electrical Interference
The Metal Detector has a unique circuit that distinguishes electrical noise from a legitimate
metal signal. When this circuitry "sees" interference that lasts longer than .1 second or that
interferes more than 25% of the time, the Detector will turn off L.E.D. status indicator No. 4
each time the interference occurs. In addition, the incoming "noisy" signals are blocked from
downstream circuitry to reduce the chance of any false tripping.
If an excessive amount of electrical interference occurs, the source of the interference must be
found and corrected. Excessive interference will reduce the Detector's sensitivity and may
false trigger the system. Such interference problems are usually associated with motor phase
to ground shorts, severely arcing brushes on motors, poor ground conditions, etc.
26
4
Chapter
System Programming
4.1 General
To program the Electronic Module, the cover must be removed. Remove the control knobs
with the 1/16" Allen wrench (provided). Unscrew the six screws securing the cover with the
5/64" Allen wrench (provided).
When replacing the cover, it is essential to re-index the control knobs. Before tightening the
set screw, line it up with the flat of the shaft. The knob, when properly indexed, will indicate
10 in a full clockwise position and 0 in a full counterclockwise position.
The amount of gain required in the receiver circuitry depends on the following factors:
• Coil Length
• Coil Aperture
• Belt Speed
• Type of Metal to be Detected
• Size, Shape and Orientation of the Metal to the Search Coil
27
4.2 (continued)
The internal gain of the Detector is adjusted by a rotary switch, S4, located inside the
Electronic Module (refer to Figure 13 Programming and Test Point Locations). Each step in
gain represents an increase over the last step. Ideally, the gain is adjusted to pick up the
desired piece of tramp metal with the "Metal
Sensitivity" control knob located on the outside of the Electronic Module set to 5.
If the gain must be changed, use a sample of tramp metal the same size as the piece to be
detected and follow the procedures listed below:
4.2.1 Remove the control knobs and cover of the Electronic Module as indicated in Section
4.1.1.
4.2.2 Set the “Metal Sensitivity: control knob (R56) to its rotational midpoint (if the cover
was not removed, the “Metal Sensitivity” would be 5)
4.2.3 Check that the clip timer, status indicator No. 7, is not lit during any portion of this test.
If the clip timer is lit, the data will be incorrect.
4.2.4 Pass the sample piece of tramp metal completely through the coils at a height midway
between the transmitter and receiver coils and at a speed near that of the conveyed material
under normal operating conditions. Increase or decrease the gain of the system with the rotary
switch as needed until the Detector will trip just as the sample metal is passed between the
coils. The larger numbers on the gain setting switch correlate to a higher gain, the lowest gain
being 1 and the highest 0 (representing 10). If the unit never trips, refer to Troubleshooting
Flow Diagram #1, page 37.
4.2.5 If all other functions are properly programmed, replace the cover and knobs. Re-index
the control knobs as indicated in Section 4.1.1.
4.2.6 Recalibrate the "Metal Sensitivity" control knob as instructed in Section 3.2.
28
For calibration of the clip gain, follow these steps:
4.3.1 Run the belt at normal running speed and maximum belt load.
4.3.2 Verify that the clip timer, status indicator No. 7, lights each time a clip passes the
sensor head. If it does not, adjust the clip sensor head as described in Section 2.6.
4.3.3 Record the settings for the “Metal Sensitivity” control knob and the Clip Override
control knob. Adjust the “Clip Override” control knob, shown in Figure 2, to a setting of 5.
4.3.4 Remove the cover as described in Section 4.1.1 without changing the setting on the
“Clip Override” control knob.
4.3.5 Adjust the Clip Gain, Switch S5 shown in Figure 15, to the highest gain that does not
trip the Detector when the clips pass. If the unit continues tripping even at the minimum clip
gain of 1, the desensitized length of the belt may be too short. In other words, the system is
switched back to full sensitivity before the clips are completely out of the Detector's field. To
correct, increase the clip detector time delay as described in Section 4.4.
4.3.6 If all other functions are properly programmed, replace the cover as described in
Section 4.1.1. Return the controls to recorded settings.
1 2 3 4 5
-
-
-
O
p
e
n
-
-
O
29
4.5 Delay Before Alarm
The timed output alarm can be accurately programmed with a time delay before turn on.
This allows the conveyed material to travel for a programmed period before the timed output
alarm signal is energized. Typically this feature is used in conjunction with a marking device
or diverter gate to delay the system until the detected tramp metal has reached the auxiliary
equipment. Switches S2-1 through S2-5 control this time delay
TABLE 2
from .01 to 22.0 seconds. Refer to Table 2 for tabulation of the
S-2 Delay Before Alarm
delay time versus switch settings and Figure 15 for the switch
S-3 Time Alarm On
locations.
Position Time
4.6 Time Alarm On 1 2 3 4 5 sec + - 20%
C C C C O .01
O C C C O .14
The timed output can be accurately programmed to remain C O C C O .30
energized for a timed period once it is switched on. This feature can O O C C O .44
C C O C O .52
activate a diverter gate, sound an alarm for a given period, O C O C O .65
command a marking device to spray a given length of the belt, etc. C O O C O .81
Switches S3-1 through S3-5 control this time delay from .01 to 22.0 O O O C O .94
seconds. Refer to Table 2 for a tabulation of the delay time versus C C C O O 1.10
O C C O O 1.20
switch settings and Figure 15 for the switch locations. C O C O O 1.40
O O C O O 1.50
C C O O O 1.60
4.7 Standard or Fail – Safe Output O C O O O 1.70
C O O O O 1.90
Operation O O O O O 2.00
C C C C C .14
O C C C C 1.60
As standard, the alarm outputs of the Detector will energize when C O C C C 3.30
tramp metal is detected. In this mode, the solid state relay is O O C C C 4.90
programmed to operate in a Normally "OFF" condition. The C C O C C 5.70
O C O C C 7.10
outputs will not energize until metal is detected. C O O C C 8.90
O O O C C 10.00
Provisions have been made to program C C C O C 12.00
TABLE 3 O C C O C 13.00
Timed Output Reset the Detector to operate in a fail-safe C O C O C 15.00
(Switch S2 & S3) mode. In this mode, the outputs of the O O C O C 16.00
Position Detector are always energized and de- C C O O C 17.00
Contact O C O O C 19.00
6 Mode energize when tramp metal is detected C O O O C 21.00
C Normally ON or when power to the Detector is turned O O O O C 22.00
O Normally OFF off. In the fail-safe mode, the solid state
relay is programmed to operate in a
Normally “ON” condition.
-
-
C
l
o
s
e
d
-
C
1 2 3 4 5 6 7
-
-
C
l
o
s
e
d
-
C
1 2 3 4 5 6 7
-
-
-
O
p
e
n
-
-
O
-
-
-
O
p
e
n
-
-
O
-- ---------- --OPEN--------------
30
4.7 (continued)
Both outputs can be independently programmed. The direct output (status indicator No. 9) and
timed output (status indicator No. 8) will monitor the alarm's output condition. If the status
indicator is lit, its associated output is energized. Switch S2-6 controls the direct output and
S3-6, the timed output as shown in Table 3. To operate the solid state relay condition in a
Normally "OFF" condition, open the appropriate switch. Conversely, to operate the relay in a
Normally "ON" condition, close the switch.
-
-
C
l
o
s
e
d
-
C
1 2 3 4 5 6 7
-
-
-
O
p
e
n
-
-
O
the Detector will momentarily signal when tripped then self-reset.
----- ---------OPEN----- ---------
The direct output can be programmed to automatically reset by shorting the remote reset
terminals TB1 pins 1 & 2, located on the front of the Interface Module. To "short", install a
jumper from pin 1 to pin 2, Appendix A Figure A17. Open Switch S2-7, Figure 15.
The operating mode of the timed output is governed by the position of Switch S3-7 as shown
in Table 4. With the switch in the open position, the timed output operates in the Automatic
Reset Mode. When the switch is closed, the timed output will follow the mode programmed
on the direct output.
TABLE 5
4.9 Reset Override Timed Output Reset
(Switch S2)
If required, the Detector can be programmed so the system is disabled during Position
Mode
7
the reset period. This means the Detector is prevented from tripping as long
C Manual Reset
as a reset signal is provided, either manually on the front panel or remotely
O Automatic Reset
through a set of external contacts.
-
-
C
l
o
s
e
d
-
C
With S2-7 in the open position, the reset signal does not disable the Detector. 1 2 3 4 5 6 7
Closing S2-7 will program the Detector so it is disabled while a reset signal
-
-
-
O
p
e
n
-
-
O
31
4.10 Sampling
The Detector Sampling Mode is set at the factory to make the Detector sensitivity selective
between various materials as required for each particular application. Switches S1-1 through
S1-4 inclusive are preset and are not to be adjusted by the user.
The operating frequency of the Detector can best be measured at the zero gate test point "Z",
shown in Figure 15. The signal switches between 0V and +15V as referenced to 0V of the
system (Test Point 0V). If viewed on an oscilloscope, this signal would be high one pulse
width and low for seven.
32
s
r
i pt
i
l a l
c s
︶
r d Of. s d t p u g m a 0
" e p t n
go
i f e "o h t n g r " fh
o n n n " g; d r ye
dn ez e a i
t i o t
i t
︶
i .
s yet
l c s a n o
f y et
l c t a 0
" n
i s f v t
no mg e l ri e s o
l l rwi m e g a n 1 i
t a
ad i r aa w 2 a s ; ng i i
t r g m as t
︵
t n s
lt; ee m
i mws s n w e w e r i ot
i a e
l ns
a
t e hn t ras a i
t o l ra s s o n a t s m b eo
te o b o f a
︵
e s d i t h i e g a e a sm
mre sis n net h n e
s s a n eth r 4 o
i
t t
s
c
i e r T l0"
t
n tp
t
c t a sBg
.
o
i
t r
t
c
T s Bg l
i e a a f
i
l l
" r
o o a
t
u as o a .n w l c p 1 t 1
Programing Controls Summary
e c y ep
l s n
i c o
f e
l t i b i
f e
l m" t
c e"
m er
t e t g sgt
t e
t e r sg
t t t a i
l " . e r
e m.
m e o Sou n c nr
i a e 5 S e c nr
i a u T p 1 ae t f r
dct i
t att e d e f
e att e p
t m " ln e e o
o a . t
e t ep l l . t ep u o
t a d R t
C oF td s n
oso a b t R n
o so o a . no sc
t u u r l e gz e ee
︶
r. pme cre t a p .. c re e a n i h . ct
oc ti n o e T t d o d f n o s g t s . ue
e o eu o ul b b e
f e r t ul b f
i .
y l
a n
i mse l i t u
dpr md p ob t a e m e d ob t s l t s w a d o .
ie r tae c s
i R i nn d aec e a e n sn o p n shr n
ed e
︵
t o c t
he
t sct f eTe
r o
f
f d
o . s
ea
ss
e Tf
m oe
f n
i
c
i
t m e
s ei
t
a e h r
c
a
s
et
t
a
o
i
t
sey l
o e 2 i t t d l
o ng i ti m a s
t n uar s
t i g uss a
r t e d r t
i d e r i n t r t r m c i ns c l n na u
wv t
n e l sfe u i
l t
n a i sfe u e o e s ep e a i ep n
b e t t t
33
on
l od a t
e eic s p o met t
e eic t
e t l
e p tl l
e e t to e
t
l o s r p es r u i
l t i m e t t
A c Ci T SRc U a C r S Rc D a S c A c S s A t a
t
c t
c t
m e e e s
l d l u
j
e r
a e i
r n e t y y
t d
d l tS r O tS
u u e a i
v e A
o A u f e pff p d n
i n l
e i
t d
n M e pf v m t t o a i D i
s i
r y
c
o
i r t
u O O r u O u G a r
t g o / a On/ O M G e n e n
c n f On t
e l t l e v e
n i
l e tO s A dO d e a p m S O u
u p B c e ey e s t
e i
l i
T l q
F m y ely e ml m e C a p e
a r
i a R m i R M p t i
l r
a l D t
l i ia
T T i
l e C F
S e m e T m C M e
D r
o B r
o n
N N i
F
n
o
i
t
i 1 2 34 1 2 3 45 6 7 12 3 4 5 6 7 1234
s
o 6 4 6
P 4 5 5 4 9
l S S R R R
o
r
t
n 1 2 3
o S S S
C
34
7 -
-
-
-
-
R
E
M
R
O
F
X
-
-
6 -
-
-
-
-
-
5
C
N
Y
S
-
N
4 E
P
O
-
-
3 -
-
-
-
2 -
-
-
-
-
-
1 -
-
1
6
C
1
1
C
3
S
7 -
-
-
-
-
-
6 -
-
-
-
-
-
5 -
-
N
4 E
P
O
3 -
-
-
-
V
4
2
+
-
-
2 -
-
-
-
-
-
1 -
-
U
O
V
5
1
+
F
P
L T
V
4
2
-
2
S
4
4
R
5
4
2 S
6
0
G
C
8
N
E
S
+
J7 J8
4
2
-
-
5 -
-
S
-
V
0
-
-
-
-
4 -
-
6 N
Z
E
8
G
M
3 P
O
J6 J5
-
V
5
1
-
2 -
-
-
-
-
-
1 -
-
-
Clip Jumpers
74C00N
S ingle & Dual
4
S
B
B
6
S
T
M
X
-
R96
6
5
R
V
0
R
U
C
T
M
X
+
4 -
-
-
-
-
-
3 N
E
2 P
O
-
-
-
-
1 -
-
V
5
+
RF
UE
80E6-1 CR
1
S
Programing Controls & Test Point Locations
Figure 16
5
Chapter
Troubleshooting
5.1 Status Indicators
To aid in troubleshooting the Detector, two easy to follow, step-by-step, flow diagrams were
designed. Troubleshooting Flow Diagram #1 deals with insufficient metal sensitivity. This
diagram is used if the unit detects metal, but is not sensitive enough for the required
application or if the Detector does not respond to metal at all.
Refer to Troubleshooting Flow Diagram #2, if the unit continually false trips (triggers with no
metal in the field).
35
* When programed to operate in a fail-safe mode (output normally "ON"), the LED's will be lit.
. . d e
de d e h
l t a m t
This kit contains all parts necessary for basic maintenance. The items included are as follows:
e r o n s c e
b e r . hzo t
i e h m f
I
t
s w o d s
i s u t a h
, er eg c
r e r
o r .
t t
i s
i .
u o t
n te
a r n i d t g u w l s
m p e v w h
t i
s c o c o p a e
; n s i
t n e t e r
p t
u d n m
l e e c o ee l
u t
i t
e e g i
a h r ap hs n d s o z
i i
s t
n p r t d u a m g d
o
i w se
i en o r p w r r t n
t t s
i t
f vi M o i
l a e e
s a
a
r h ha
c os f c r l n e s
e g e t bli c
i t f o
t a e r
Prior to shipment, a maintenance kit is packed in the Main Control Enclosure.
p i
l g i s aa n i
l o ce. d s g
t a w d t o e en e i s n
i
o o t
l sn se
i r b y
t t t a t
t
y n o yco tm t
c i e o m u n e
v t m
Electronic Module Status Indicator Summary
l
p l
l ae u e s dz i
t p o s
p i e ws ple l u i
x dg e t
u i
t r
t u W n a5 t
u b E M o oin h o c o
n s i
l ota l r i
r s t e f
e r .
l w gy a p en f m t 5
m e a nel rc
e n .
y n pe o r e
t o i e r
e l i a d e
m w e l w t
a ze
y t t a s es n l l l
b
o o m , sm l d n m i har o
i a a a
C p s ri a i p t t
i d t
e T
r t
c n e x nn d r
o i rle d e
o e o t
t ae e n l
c o c n m o
t t i
t i o
r lh i
f f o m t
c e c mp a i
c g r
i to
i c i
t e
l r
e d n sp nw e n a l t e b e
t
e u na gy p i p ss e h . a f
e
d o f
l as i
s l s n e np
i h t e s
t . o r i t i R
TABLE 7
s t a r
t t n sua s i a l , g d
e i
n m lg
a
h o es e t
c s
e mc s
e t
i
l a
t
l o .
t u y nli d tu t nl. t eow t s o t d
a r l e a a ua a r a i v d e
i
36
c
i o p oD
i n c
i ,
t c
i f t c Dal
l c
i D e l
d f p t r d i d ee i
d d e s p
n t u p E u nlm n r m n Eo n E n p
I i
l s oL t I i I a I Lt I L i
l U a
lon
a i F
mit N F N F F F
rnd F F F
o O O O O O O
No
C
(1) 1/16" Allen Key Wrench
(1) 5/64" Allen Key Wrench
y
5.4 Maintenance Kit
n l l
a
o
i p n t t t t r t t
u
t p g s s s s e u
a u i e e e e m O O
c
i S S T T T T i t
f
i r l f
l f
l f
l f
l t d c
t
n e a e e e e p e e
e w t
e S S S S i
l m r
i
d o M C i
T D
37
FUSE, DOOR PLUG yes INDICATOR NO.9 no CONTACT
ENCLOSURE CONNECTION, FLASH WHEN
LIGHT WHEN FACTORY
LIT? POWER SWIT CH & MET AL IS PASSED
STAT US INDICAT OR FOR SERVICE
GREEN LIGHT THROUGH NO.2 LIGHTS?
yes SEARCH COILS?
no yes
IS 1 AMP FUSE
ON INTERFACE
yes REPLACE yes
MODULE 1 AMP FUSE
TRACE ANTENNA CONNECT
BLOWN? CABLE. ARE no
SET METAL CABLES TO
no REPLACE CABLES CONNECTED PROPER
SENSITIVIT Y RE-CALIBRATE TO PROPER
INTERFACE TERMINALS
CONTROL KNOB MET AL DET ECTOR TERMINALS?
MODULE
TO "0" SENSITIVITY
REPLACE CONTROL KNOB
ELECTRONIC
DOES METAL MODULE
DETECT OR HAVE
A SWING-AWAY no
CUTOUT yes yes
SWITCH? DOES STATUS
no IS THE MET AL
yes REDUCE INDICATOR NO.2 GAIN SWITCH S4 AT
IS STATUS DOES STATUS SEARCH COIL FLASH WHEN no ITS MAXIMUM
INDICATOR INDICATOR NO.2 APERTURE T O MET AL IS PASSED SETT ING "0"
NO. 1 LIT? FLASH WHEN no MINIMUM SAFE THROUGH REPRESENTING "10"?
DISCONNECT yes METAL IS PASSED DISTANCE SEARCH COILS?
SWING-AWAY THROUGH no
CUTOUT SEARCH COILS?
CABLE F ROM
INTERFACE
yes
MODULE CHECK
ADJUST METAL
SWING-AWAY
GAIN SWITCH S4
CUTOUT
SWIT CH AND TO NEXT HIGHER
SETT ING
CABLE
METAL DOES DISCONNECT DOES UNIT IS STATUS VERIFY
yes INDICATOR
DETECT OR DETECTOR TRANSMITTER STILL yes "CLEAN"
FALSE TRIP no FALSE TRIP no CABLE FALSE TRIP? NO. 4 LIT GROUND TO
ON REPAIR ON REPAIR FROM THE ALL OF THE CONVEYOR
CLIPS ON CLIPS ON INTERFACE no TIME?
RETURN SIDE MAIN SIDE MODULE
OF BELT? OF BELT ---------- ----------
no
REMOVE ALL
NO.6 LIGHT "POSSIBLE"
yes yes WILL T URN METAL LOCATED
OFF NEAR THE
SEARCH COIL DISCONNECT REPLACE
ASSEMBLY VERIF Y
RECEIVER COIL no ELECTRONIC
"CLEAN"
ADD A WIRE DOES STATUS MODULE
INCREASE GR OUND TO
JUMPER INDICATOR N0. 4
DISTANCE DETECTOR
BETWEEN TB1-5 LIGHT UP?
BETWEEN INST ALL
RETURN BELT & TB1-7 ON ARE ADJACENT yes
INTERFACE ISOLAT ION KIT IDLER ROLLERS
& RECEIVER TO ADJACENT no
COIL MODULE ISOLAT ED
IDLER ROLLERS FROM
REFER TO SECTION CONVEYOR
2.2.5 IN MANUAL FRAME REFER TO
yes SECTION N0. 3.5
IN MANUAL
ON EXCESSIVE
RECONNECT INTERFERENCE
TRANSMITTER CABLE DISCONNECT
IF UNIT STILL TO INT ERFACE RECEIVER
FALSE TRIPS MODULE CABLE
CONTACT THE FROM THE
FACTORY FOR CONTACT INTERFACE
SERVICE FACTORY FOR MODULE
SERVICE
REPLACE
ELECTRONIC STRIKE THE
IS STATUS no MODULE CONVEYOR
INDICATOR -- ---------------- -- FRAME, CROSS
38
NO. 7 LIT? REMOVE BRACING, IDLER
JUMPER ROLLERS, RETURN yes
IDLERS, CONDUIT
yes RUNS, CAT WALK, IS INPUT
GUARD SCREENS, POWER TO yes DOES UNIT
IN AREAS AROUND METAL STILL
THE ANTENNAS DETECTOR FALSE TRIP?
"STABLE" ?
RE-CALIBRATE no
DOES UNIT CLIP GAIN. no
STILL F ALSE yes REFER TO
TRIP ON SECTION 4.3
REPAIR CLIPS? MARK CONVEYOR
IN MANUAL
JOINTS WHICH LINE
no TRIP THE DETECTOR VOLTAGE
WHEN CONVEYOR IS CHECK FOR
REGULATOR ELECTRICAL
STRUCK REQUIRED INTERFERENCE
I.E. ARCING
REMOVE CONTACTS, RADIO
JUMPER TRANSMISSION
------ ---- ----------- -- OR PHASE TO
WELD MARKED GROUND SHORT
PLACE
JOINTS T O ENSURE
SCREWDRIVER
OVER PERMANENT
CLIP HEAD ELECTRICAL
CONNECTIONS MODEL 8600
TROUBLE SHOOTING
FLOW DIAGRAM #2
********* RECONNECT
CHECK CLIP IF UNIT STILL TRANSMITTER
RE-CALIBRATE DETECTOR FALSE TRIPS,
CLIP TIME, IS STATUS FALSE TRIPPING & RECEIVER
yes INDICATOR
no SENSOR & CABLE CONTACT THE CABLES TO
REFER TO FOR OPEN FACTORY FOR
SECTION 4.4 NO. 7 LIT? INTERFACE
CIRCUIT SERVICE MODULE
IN MANUAL
APENDIX A
39
Power Input Figure A1
INTERFAC E
MODU LE
SE RIAL No.
HOT
INPUT POWER ALARM OUTPUTS
LINE: 115 (220) VAC 5 AMP MAX REMOTE SYNC SWI NG CLIP RECEIVER
FUSE RESE T LINE AWAY DETECTOR
10 AMP 50/60 Hz TI ME D DIRECT TRANSMI TTER (COM.)
PWR NEUT GND OUT NEUT OUT NEUT IN 0v SIG SW 0v 9-12v SIG (+) (-) SHLD (+) SHLD (-)
1 AMP
GRN BLK WHT BLK WHT WHT BLK WHT WHT BLK RED WHT YEL BLK SHLD YEL SHLD BLK
FUSE
1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 11 12 13
10 AMP
TB 2 TB 1
EL ECTRONIC EN CL OS URE
40
Transmitter and Receiver Antenna Figure A2
INTERFAC E
MODU LE
SE RIAL No.
HOT
INPUT POWER ALARM OUTPUTS
LINE: 115 (220) VAC 5 AMP MAX REMOTE SYNC SWI NG CLIP RECEIVER
FUSE RESE T LINE AWAY DETECTOR
10 AMP 50/60 Hz TI ME D DIRECT TRANSMI TTER (COM.)
PWR NEUT GND OUT NEUT OUT NEUT IN 0v SIG SW 0v 9-12v SIG (+) (-) SHLD (+) SHLD (-)
1 AMP
GRN BLK WHT BLK WHT WHT BLK WHT WHT BLK RED WHT YEL BLK SHLD YEL SHLD BLK
FUSE
1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 11 12 13
10 AMP
TB 2 TB 1
EL ECTRONIC EN CL OS URE
RC VR AN TE NNA
41
Clip Detector Figure A3
INTERFAC E
MODU LE
SE RIAL No.
HOT
INPUT POWER ALARM OUTPUTS
LINE: 115 (220) VAC 5 AMP MAX REMOTE SYNC SWI NG CLIP RECEIVER
FUSE RESE T LINE AWAY DETECTOR
10 AMP 50/60 Hz TI ME D DIRECT TRANSMI TTER (COM.)
PWR NEUT GND OUT NEUT OUT NEUT IN 0v SIG SW 0v 9-12v SIG (+) (-) SHLD (+) SHLD (-)
1 AMP
GRN BLK WHT BLK WHT WHT BLK WHT WHT BLK RED WHT YEL BLK SHLD YEL SHLD BLK
FUSE
1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 11 12 13
10 AMP
TB 2 TB 1
EL ECTRONIC EN CL OS URE
CL IP D ETECTOR
42
Dual Clip Detector Figure A4
INTERFAC E
MODU LE
SE RIAL No.
HOT
INPUT POWER ALARM OUTPUTS
LINE: 115 (220) VAC 5 AMP MAX REMOTE SYNC SWI NG CLIP RECEIVER
FUSE RESE T LINE AWAY DETECTOR
10 AMP 50/60 Hz TI ME D DIRECT TRANSMI TTER (COM.)
PWR NEUT GND OUT NEUT OUT NEUT IN 0v SIG SW 0v 9-12v SIG (+) (-) SHLD (+) SHLD (-)
1 AMP
GRN BLK WHT BLK WHT WHT BLK WHT WHT BLK RED WHT YEL BLK SHLD YEL SHLD BLK
FUSE
1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 11 12 13
10 AMP
TB 2 TB 1
EL ECTRONIC EN CL OS URE
NC TB 1-7 WHITE
1 Pwr 2 1 Pwr out 2 UP STR EAM CLIP DE TEC TOR
NC 1k ohm
out
1 N4 00 2
Blk Blk
Red Wht Red Wht
Clip heads need to be modified as shown above. Also J6 & J8 on the Electronics Module must be
made. Normally Jumpers J5 and J7 are made for single clip operation. Refer to Figure 16
Programming Controls and Test Point Locations.
43
Synchronization Figure A5
INTERFAC E
MODU LE
SE RIAL No.
HOT
INPUT POWER ALARM OUTPUTS
LINE: 115 (220) VAC 5 AMP MAX REMOTE SYNC SWI NG CLIP RECEIVER
FUSE RESE T LINE AWAY DETECTOR
10 AMP 50/60 Hz TI ME D DIRECT TRANSMI TTER (COM.)
PWR NEUT GND OUT NEUT OUT NEUT IN 0v SIG SW 0v 9-12v SIG (+) (-) SHLD (+) SHLD (-)
1 AMP
GRN BLK WHT BLK WHT WHT BLK WHT WHT BLK RED WHT YEL BLK SHLD YEL SHLD BLK
FUSE
1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 11 12 13
10 AMP
TB 2 TB 1
EL ECTRONIC EN CL OS URE
44
Spray Marker Figure A6
INTERFAC E
MODU LE
SE RIAL No.
HOT
INPUT POWER ALARM OUTPUTS
LINE: 115 (220) VAC 5 AMP MAX REMOTE SYNC SWI NG CLIP RECEIVER
FUSE RESE T LINE AWAY DETECTOR
10 AMP 50/60 Hz TI ME D DIRECT TRANSMI TTER (COM.)
PWR NEUT GND OUT NEUT OUT NEUT IN 0v SIG SW 0v 9-12v SIG (+) (-) SHLD (+) SHLD (-)
1 AMP
GRN BLK WHT BLK WHT WHT BLK WHT WHT BLK RED WHT YEL BLK SHLD YEL SHLD BLK
FUSE
1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 11 12 13
10 AMP
TB 2 TB 1
EL ECTRONIC EN CL OS URE
TB 2- 4 BLACK
TB 2- 5 WHITE
45
Swing Away Switch Figure A7
INTERFAC E
MODU LE
SE RIAL No.
HOT
INPUT POWER ALARM OUTPUTS
LINE: 115 (220) VAC 5 AMP MAX REMOTE SYNC SWI NG CLIP RECEIVER
FUSE RESE T LINE AWAY DETECTOR
10 AMP 50/60 Hz TI ME D DIRECT TRANSMI TTER (COM.)
PWR NEUT GND OUT NEUT OUT NEUT IN 0v SIG SW 0v 9-12v SIG (+) (-) SHLD (+) SHLD (-)
1 AMP
GRN BLK WHT BLK WHT WHT BLK WHT WHT BLK RED WHT YEL BLK SHLD YEL SHLD BLK
FUSE
1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 11 12 13
10 AMP
TB 2 TB 1
EL ECTRONIC EN CL OS URE
TB 1-5 BLACK
SWING AWAY
SWITCH
46
Control Unit Extension Figure A8
INTERFAC E
MODU LE
SE RIAL No.
HOT
INPUT POWER ALARM OUTPUTS
LINE: 115 (220) VAC 5 AMP MAX REMOTE SYNC SWI NG CLIP RECEIVER
FUSE RESE T LINE AWAY DETECTOR
10 AMP 50/60 Hz TI ME D DIRECT TRANSMI TTER (COM.)
PWR NEUT GND OUT NEUT OUT NEUT IN 0v SIG SW 0v 9-12v SIG (+) (-) SHLD (+) SHLD (-)
1 AMP
GRN BLK WHT BLK WHT WHT BLK WHT WHT BLK RED WHT YEL BLK SHLD YEL SHLD BLK
FUSE
1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 11 12 13
10 AMP
TB 2 TB 1
1
2
3
4
5
6
TB3A
EL ECTRONIC EN CL OS URE
47
Auxiliary 2 or 4 Relay Sq D 115 vac or 220 vac Figure A9
INTERFAC E
MODU LE
SE RIAL No.
HOT
INPUT POWER ALARM OUTPUTS
LINE: 115 (220) VAC 5 AMP MAX REMOTE SYNC SWI NG CLIP RECEIVER
FUSE RESE T LINE AWAY DETECTOR
10 AMP 50/60 Hz TI ME D DIRECT TRANSMI TTER (COM.)
PWR NEUT GND OUT NEUT OUT NEUT IN 0v SIG SW 0v 9-12v SIG (+) (-) SHLD (+) SHLD (-)
1 AMP
GRN BLK WHT BLK WHT WHT BLK WHT WHT BLK RED WHT YEL BLK SHLD YEL SHLD BLK
FUSE
1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 11 12 13
10 AMP
TB 2 TB 1
EL ECTRONIC EN CL OS URE
48
Auxiliary Relay KRPA 115 vac or 220 vac Figure A10
INTERFAC E
MODU LE
SE RIAL No.
HOT
INPUT POWER ALARM OUTPUTS
LINE: 115 (220) VAC 5 AMP MAX REMOTE SYNC SWI NG CLIP RECEIVER
FUSE RESE T LINE AWAY DETECTOR
10 AMP 50/60 Hz TI ME D DIRECT TRANSMI TTER (COM.)
PWR NEUT GND OUT NEUT OUT NEUT IN 0v SIG SW 0v 9-12v SIG (+) (-) SHLD (+) SHLD (-)
1 AMP
GRN BLK WHT BLK WHT WHT BLK WHT WHT BLK RED WHT YEL BLK SHLD YEL SHLD BLK
FUSE
1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 11 12 13
10 AMP
TB 2 TB 1
EL ECTRONIC EN CL OS URE
49
Voltage Regulator Figure A11
INTERFAC E
MODU LE
SE RIAL No.
HOT
INPUT POWER ALARM OUTPUTS
LINE: 115 (220) VAC 5 AMP MAX REMOTE SYNC SWI NG CLIP RECEIVER
FUSE RESE T LINE AWAY DETECTOR
10 AMP 50/60 Hz TI ME D DIRECT TRANSMI TTER (COM.)
PWR NEUT GND OUT NEUT OUT NEUT IN 0v SIG SW 0v 9-12v SIG (+) (-) SHLD (+) SHLD (-)
1 AMP
GRN BLK WHT BLK WHT WHT BLK WHT WHT BLK RED WHT YEL BLK SHLD YEL SHLD BLK
FUSE
1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 11 12 13
10 AMP
TB 2 TB 1
EL ECTRONIC EN CL OS URE
BRN
WHT
WHT
YEL
INPUT GN D OU TP UT
50
Flag Drop Marker Figure A12
INTERFAC E
MODU LE
SE RIAL No.
HOT
INPUT POWER ALARM OUTPUTS
LINE: 115 (220) VAC 5 AMP MAX REMOTE SYNC SWI NG CLIP RECEIVER
FUSE RESE T LINE AWAY DETECTOR
10 AMP 50/60 Hz TI ME D DIRECT TRANSMI TTER (COM.)
PWR NEUT GND OUT NEUT OUT NEUT IN 0v SIG SW 0v 9-12v SIG (+) (-) SHLD (+) SHLD (-)
1 AMP
GRN BLK WHT BLK WHT WHT BLK WHT WHT BLK RED WHT YEL BLK SHLD YEL SHLD BLK
FUSE
1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 11 12 13
10 AMP
TB 2 TB 1
EL ECTRONIC EN CL OS URE
51
Alarm Horn & Flashing Beacon Figure A13
INTERFAC E
MODU LE
SE RIAL No.
HOT
INPUT POWER ALARM OUTPUTS
LINE: 115 (220) VAC 5 AMP MAX REMOTE SYNC SWI NG CLIP RECEIVER
FUSE RESE T LINE AWAY DETECTOR
10 AMP 50/60 Hz TI ME D DIRECT TRANSMI TTER (COM.)
PWR NEUT GND OUT NEUT OUT NEUT IN 0v SIG SW 0v 9-12v SIG (+) (-) SHLD (+) SHLD (-)
1 AMP
GRN BLK WHT BLK WHT WHT BLK WHT WHT BLK RED WHT YEL BLK SHLD YEL SHLD BLK
FUSE
1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 11 12 13
10 AMP
TB 2 TB 1
EL ECTRONIC EN CL OS URE
TB 2-6 BLACK
TB 2-7 WHITE
FLASH IN G BE ACON/
AL ARM HORN
52
Alarm Horn Figure A14
INTERFAC E
MODU LE
SE RIAL No.
HOT
INPUT POWER ALARM OUTPUTS
LINE: 115 (220) VAC 5 AMP MAX REMOTE SYNC SWI NG CLIP RECEIVER
FUSE RESE T LINE AWAY DETECTOR
10 AMP 50/60 Hz TI ME D DIRECT TRANSMI TTER (COM.)
PWR NEUT GND OUT NEUT OUT NEUT IN 0v SIG SW 0v 9-12v SIG (+) (-) SHLD (+) SHLD (-)
1 AMP
GRN BLK WHT BLK WHT WHT BLK WHT WHT BLK RED WHT YEL BLK SHLD YEL SHLD BLK
FUSE
1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 11 12 13
10 AMP
TB 2 TB 1
EL ECTRONIC EN CL OS URE
TB 2-5 WHITE
AL AR M H OR N
CONTINUOUS OPERAT ION UN TIL RESET
TB 2-6 BLACK
TB 2-7 WHITE
53
Flashing Beacon Figure A15
INTERFAC E
MODU LE
SE RIAL No.
HOT
INPUT POWER ALARM OUTPUTS
LINE: 115 (220) VAC 5 AMP MAX REMOTE SYNC SWI NG CLIP RECEIVER
FUSE RESE T LINE AWAY DETECTOR
10 AMP 50/60 Hz TI ME D DIRECT TRANSMI TTER (COM.)
PWR NEUT GND OUT NEUT OUT NEUT IN 0v SIG SW 0v 9-12v SIG (+) (-) SHLD (+) SHLD (-)
1 AMP
GRN BLK WHT BLK WHT WHT BLK WHT WHT BLK RED WHT YEL BLK SHLD YEL SHLD BLK
FUSE
1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 11 12 13
10 AMP
TB 2 TB 1
EL ECTRONIC EN CL OS URE
TB 2-6 BLACK
TB 2-7 WHITE
FLASH IN G BE ACON
54
Remote Reset Switch Figure A16
INTERFAC E
MODU LE
SE RIAL No.
HOT
INPUT POWER ALARM OUTPUTS
LINE: 115 (220) VAC 5 AMP MAX REMOTE SYNC SWI NG CLIP RECEIVER
FUSE RESE T LINE AWAY DETECTOR
10 AMP 50/60 Hz TI ME D DIRECT TRANSMI TTER (COM.)
PWR NEUT GND OUT NEUT OUT NEUT IN 0v SIG SW 0v 9-12v SIG (+) (-) SHLD (+) SHLD (-)
1 AMP
GRN BLK WHT BLK WHT WHT BLK WHT WHT BLK RED WHT YEL BLK SHLD YEL SHLD BLK
FUSE
1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 11 12 13
10 AMP
TB 2 TB 1
EL ECTRONIC EN CL OS URE
TB 1-1 WHITE
TB 1- BLACK
55
Automatic Reset Figure A17
INTERFAC E
MODU LE
SE RIAL No.
HOT
INPUT POWER ALARM OUTPUTS
LINE: 115 (220) VAC 5 AMP MAX REMOTE SYNC SWI NG CLIP RECEIVER
FUSE RESE T LINE AWAY DETECTOR
10 AMP 50/60 Hz TI ME D DIRECT TRANSMI TTER (COM.)
PWR NEUT GND OUT NEUT OUT NEUT IN 0v SIG SW 0v 9-12v SIG (+) (-) SHLD (+) SHLD (-)
1 AMP
GRN BLK WHT BLK WHT WHT BLK WHT WHT BLK RED WHT YEL BLK SHLD YEL SHLD BLK
FUSE
1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 11 12 13
10 AMP
TB 2 TB 1
EL ECTRONIC EN CL OS URE
56
Strip Heater 115 vac or 220 vac Figure A18
INTERFAC E
MODU LE
SE RIAL No.
HOT
INPUT POWER ALARM OUTPUTS
LINE: 115 (220) VAC 5 AMP MAX REMOTE SYNC SWI NG CLIP RECEIVER
FUSE RESE T LINE AWAY DETECTOR
10 AMP 50/60 Hz TI ME D DIRECT TRANSMI TTER (COM.)
PWR NEUT GND OUT NEUT OUT NEUT IN 0v SIG SW 0v 9-12v SIG (+) (-) SHLD (+) SHLD (-)
1 AMP
GRN BLK WHT BLK WHT WHT BLK WHT WHT BLK RED WHT YEL BLK SHLD YEL SHLD BLK
FUSE
1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 11 12 13
10 AMP
TB 2 TB 1
STRIP HEATER
TEMP ADJ
EL ECTRONIC EN CL OS URE
57
APENDIX B
Service, Parts, Repairs
58
Search Coil Assembly Swing Away Figure B1
1 Crossbar
2 Upright Pair
3 Mounting Feet Carbon Steel
4 Receiver Bracket Pair
5 Transmitter Bracket Pair
6 Receiver Antenna
7 Transmitter Antenna
8 Roughing Guard
9 Swing-Away Switch
5
8
9
3
6
59
This section of the manual provides information about service and repair of your metal detector.
When you call for service you MUST have the serial number from the electronics, or the
Tectron Job Order number available. Please direct all service inquiries directly to Tectron at
+1 904-394-0683
Tectron can provide on-site service for your metal detector to assist with calibration & start-up,
customer training, or troubleshooting. Contact Tectron (+1 904-394-0683) to schedule on-site
service. When you call for parts you MUST have the serial number from the electronics,
or the Tectron Job Order number available to ensure you receive the correct parts.
A general drawing with parts listed is shown on the next page. This is to assist you in
determining which parts need replacement.
Tectron also offers repair services for the electronics at our facility in Jacksonville, Florida. When
sending ANY materials to Tectron, you must have a Return Materials Authorization (RMA)
number issued by Tectron. For your convenience we have provided a form for providing the
necessary information to obtain an RMA number. Simply fill out the form and fax it to Tectron,
or call Tectron with all the information required and you will be issued an RMA number.
60
RETURN MATERIALS AUTHORIZATION FORM
Company: _______________________________________________
Address: _____________________________________
_____________________________________
_____________________________________
________________________________________________________________________________________
________________________________________________________________________________________
61
There is a minimum charge of $__________ for inspecting components with no problem found.
When a problem is found, there is a minimum charge of $__________
Please fax a copy of this form to 904-394-0691, or call Tectron (904-394-0683) with the above
information and you will be given an Return Materials Authorization Number. Upon receipt of the
RMA Number from Tectron, please comply with the following:
1. Item being returned must be clean - Removing all foreign material. Any residue could be
considered hazardous. If all residue cannot be removed, you MUST provide a Material Safety
Data Sheet (MSDS) to identify the material, or a signed statement verifying no hazardous
materials are present.
2. Please include a copy of this form completed with the RMA number with the item you are returning
to Tectron.
3. Before any repairs take place, we MUST have received a purchase order to invoice the repair
charges to (warranty repairs excluded). Please include a copy of the purchase order with the
shipment or fill out the information below.
Please send materials (freight pre-paid – COLLECT shipments will NOT be accepted) to:
62